Documente Academic
Documente Profesional
Documente Cultură
of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
Amsterdam University of Applied Science, dept. Electrical Engineering, Amsterdam, the Netherlands
c.h.a.keyer@hva.nl
2
University of Twente, Enschede, the Netherlands.
3
Thales Nederland, Hengelo, the Netherlands.
compared the declarations of conformity from the three
suppliers.
II.
I.
INTRODUCTION
74
Proc. of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
power into grid power. Local Dutch rules, NEN 1010, for grid
connected installations in the Netherlands allow a low power
600 VA, to be connected straight in to a socket without
special measures. PV inverters which can supply more power >
600 VA should be connected on a separate feeder line with
fuse. No other equipment is allowed to connect on that feeder
line. Dutch standard (NEN 1010) on low voltage (230 V) grid
systems requires this due to the fact that if you deliver power
back into the grid the current flows through the fuse. When
equipment is connected on the same fused line, for example,
16 A fuse, and the PV installation is delivering 10 A from your
PV inverter, the equipment should use a fault current of 26 A,
to blow the fuse out, which is undesirable.
A current probe clamp, Fischer Custom Communications
F-35 and a Rigol DSA 815 spectrum analyzer, as shown in
Figure 1, were used for the measurements. Although different
measurement methods are described for CM mode current
measurements [2, 5] on the DC bus, in this case there was no
possibility to open up the DC bus for connecting a Line
Impedance Stabilization network.
The measurement setup for all three inverters was the same.
The DC bus is clamped with both wires to prohibit DC
saturation of the clamp, and to measure the high-frequency
common mode (CM) current. The measurements on the DC
bus are done with the inverter switch on and switched off. This
is done to check if the inverter causes the CM current, or not.
The CM current loop is created by the actual installation so
measurements have to be performed in-situ.
The first measurement was performed on Friday January
31st at 08:00 UTC, in Schagen, the Netherlands.
Figure 3: PV cells with Ham Radio antennas
75
Proc. of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
IV.
INTERFERENCE
76
Proc. of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
V.
Soladin 600
IEC 55022
IEC 61000-3-2
Omnik 3K
IEC 61000-6-3
IEC 61000-6-4
IEC 61000-3-12
IEC 61000-3-11
Both the SMA Sunny Boy and Omnik inverters are tested
against the generic emission standards, IEC 61000-6-3 and
IEC61000-6-4. Hence the DC bus is tested as well. The
Soladin 600, however, is tested against the IEC 61000-3-2 and
IEC 55022 standards.
The IEC 61000-3-2 is for harmonic distortion on the grid, for
apparatus with a rated current up to 16A. IEC 61000-3-12 is
for harmonic distortion on the grid for apparatus with a rated
current between 16 and 75 A. IEC 61000-3-11 is for voltage
fluctuations flicker and voltage changes. Comparison of the
Declarations of conformity [10,11,12] shows that the Soladin
600, and SMA Sunny Boy are tested against EN55022
(CISPR 22). This is the product standard for information
technology (IT) equipment the SMA inverter contains a wifi
adapter hence CISPR 22. In IEC 61000-6-3 limits are
described for a DC power bus. In the definitions of this
standard it is stated: 3.5 power port port at which a
conductor or cable carrying the primary electrical power
needed for the operation (functioning) of an apparatus or
associated apparatus is connected to the apparatus.
Hereinafter in the standard is stated: 3.8 d.c. power network
local electricity supply network in the infrastructure of a
certain site or building intended for flexible use by one or
more different types of equipment and guaranteeing
continuous power supply independently from the conditions of
the public mains network[13]. Hence a DC bus of a PV
installation is not a DC bus within the scope of this standard.
VI.
MIS-USE OF ARTICLE 6
All apparatus being put on the European market shall fulfil the
requirements of the EMC Directive. A common approach is
to follow Article 6 stating that presumption of conformity is
raised when harmonized standards have been used. These
77
Proc. of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
REFERENCES
[1]
[2]
[3]
VII. CONCLUSION
DC bus emissions of PV installations are not described in
international harmonized standards. So the manufacturer is
free to do what is best for his wallet. Even the general
standards do not apply if the PV inverter is equipped with an
Ethernet port, as then the manufacturer can state it is a
computer with special functions. Manufacturers search for
creative ways to get their product on the market with
disregarding the rights of the radio spectrum users. The
currents can cause high radiated interference levels. Actually,
the suppliers are violating the essential requirements of the
European EMC Directive. Due to budget constraints of the
national authorities the PV inverter suppliers can continue
their illegal activities.
[4]
[5]
[6]
[7]
[8]
ACKNOWLEDGMENT
We would like to thank the ham radio operator PA5KK for
leading us in to these measurements.
[9]
[10]
[11]
[12]
[13]
78