Documente Academic
Documente Profesional
Documente Cultură
INLET SIZE
WORKING
PRESSURE
FLANGE
CONNECTION
WEIGHT
(Approx)
65 NB 80 NB 100 NB -
VAPOUR SEAL
RUPTURE
PRESSURE
UL Listed
MAXIMUM
PERMISIBLE BACK
PRESSURE ON
VAPOUR SEAL
VAPOUR SEAL
Glass
Deflector
FINISH
APPROVAL
UL Listed
APPLICATION
ORDERING
INFORMATION
LISTED
4UT3
34.5 Kg
49.5 Kg
72.0 Kg
FEATURES
JUNE, 2014
PAGE 1 OF 6
HD 254
SPECIFICATION
JUNE, 2014
PAGE 2 OF 6
HD 254
NOTE:
1.
2.
K - FACTOR
65 NB
89.6 TO 207.8
80 NB
179.2 TO 385.9
100 NB
358.5 TO 907.2
Q=KP
Q = Total solution flow in litres per minute.
K = Constant for Foam Chamber
P = Inlet pressure in kg/sq.cm.
CAUTION
Do not install Foam chambers on pressured storage
tanks (Inert gas blanketed tanks) and storage tanks
containing product which attack the foam chamber
standard construction material.
Maximum permissible back pressure on vapour seal
is 0.07 Kg/sq.cm.2 (1.0 PSI)
JUNE, 2014
PAGE 3 OF 6
HD 254
FOAM CHAMBER
C
6
F2
5
2
1
OUTLET
A
SIZE
F2
100NB 756
150NB 1093
200NB 1221
600
908
996
175
225
275
ITEM
NO.
F1
PART LIST
MATERIAL SPECIFICATON
DESCRIPTION
FCA
FCA-S
STAINLESS STEEL
STAINLESS STEEL
ORIFICE ASSEMBLY
INLET FLANGE
STEEL
STAINLESS STEEL
STRAINER ASSEMBLY
STAINLESS STEEL
STAINLESS STEEL
STEEL PIPE
SS PIPE
FOAM CHAMBER
STEEL
STAINLESS STEEL
INSPECTION COVER
STEEL
STAINLESS STEEL
DISCHARGE PIPE
STEEL PIPE
SS PIPE
OUTLET FLANGE
STEEL
STAINLESS STEEL
GLASS
GLASS
NOTE:
1. Pipes used are ERW (Seamless Pipe are optional)
2. Foam chambers are open to atmosphere & do not have internal shutoff device,hence no hydrotest is
offered during inspection.
JUNE, 2014
PAGE 4 OF 6
HD 254
OUTLET FLANGE
FOAM CHAMBER
MODEL FCA
GASKETS
SPLIT DEFLECTOR
MODEL SD
TANK SHELL
MOUNTING PAD
ASSEMBLY
SPLIT DEFLECTOR
INLET FLANGE
STORAGE TANK
NOTE:
Stud Mounting Pad with gasket & split deflector
are optional items. To be ordered separately.
TANK CUTOUT FOR MOUNTING OF SPLIT DEFLECTOR
FLANGE OUTLINE
PCD
'd'
CUTOUT SIZE
TYPE
INLET
FLANGE
SIZE
OUTLET
FLANGE
SIZE
PCD
HOLE
d
NO OF
HOLES
FCA 65
65
100
114
191
19
FCA 80
80
150
168
241
22
FCA 100
100
200
219
298
22
BY INSTALLER
TYPICAL INSTALLATION OF FOAM CHAMBER WITH STUD FLANGED TANK NOZZLE AND SOLID DEFLECTOR
TANK NOZZLE
(BY OTHERS)
200
FOAM CHAMBER
MODEL FCA
150
SOLID DEFLECTOR
MODEL FD
150
STORAGE TANK
*
GLASS VAPOUR SEAL
WITH HOLDER (STANDARD SUPPLY)
BY INSTALLER
NOTE:
1. Above dimensions are general guidelines only. The system designer can adopt the dimensions as per
NFPA/TAC/OISD or as per the governing rules & ordinance having local jurdiction.
2. Tank Nozzle nutbolts & gasket are optional to be ordered separately.
3. Split deflector Model SD and solid deflector Model FD is standard supply in carbon steel material and
optional in stainless steel.
JUNE, 2014
PAGE 5 OF 6
HD 254
1000
FOAM SOLUTION FLOW
FLOW IN LPM
500
400
300
200
100
2
3
4
5
6
INLET PRESSURE (KG/SQ.CM)
800
600
400
200
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
600
2
JUNE, 2014
C-3/6, THE NANDANVAN IND. ESTATE, L.B.S. MARG, THANE 400 604., INDIA.
PHONES : + (91) 22 2583 5434 2582 6958 2582 6793
FAX : +(91) 22 2581 2524 6796 9049
EMAIL : info@hdfire.com WEBSITE : www.hdfire.com
PAGE 6 OF 6
HD 254