POWER TRANSFORMER
INDUCE TEST
APPROVED BY:
DOCUMENT
ISSUED DATE
PAGE
1 of 8
REVISION
TABLE OF CONTENTS
No.
Descriptions
Page
TABLE OF CONTENS
TITLE
SCOPE
OBJECTIVE
REFERENCE
TEST ITEMS
TEST PROCEDURE
TEST FORM
7-8
POWER TRANSFORMER
[Type text]
DOCUMENT
[Type text]
INDUCE TEST
APPROVED BY:
1.
2.
3.
ISSUED DATE
PAGE
2 of 8
REVISION
TITLE
TRANSFORMER WITHSTAND TEST
SCOPE
OBJECTIVE
This is to assure that the requirements of electrical individual test works are
meets the codes requirements and contract specifications. To make sure, the
works are carried out in acceptable workmanship and follow the requirements in
the quality manual.
4.
REFERENCE
4.1 Reference Manual
4.2 Applicable Manufacturers Manuals/Standards
4.3 Contract Specifications and Construction Drawing
4.4
High voltage testing area should be circled by rail with warning board and
make special person to watch.
DOCUMENT
POWER TRANSFORMER
INDUCE TEST
APPROVED BY:
CHIEF ENGINEER
5.3
PAGE
3 of 8
REVISION
[Type text]
ISSUED DATE
[Type text]
5.4
6.
7.
Visual Inspection
POWER TRANSFORMER
INDUCE TEST
APPROVED BY:
DOCUMENT
ISSUED DATE
PAGE
4 of 8
REVISION
7.3
[Type text]
Insulation resistance must be measured before and after applied voltage test.
Power Frequency Induce Test
[Type text]
7.3.1` Precaution
7.3.2
Test Frequency
50 Hz
Test Duration
15 minute
kV
Test Voltage
15 minute
Time duration
TRANSFORMER UNDER TEST
Test set
LV
HV
A
Trafo Step up
400 V / 20 kV
Power
input
c
Trafo Regulator
0 - 240 V/ 2 X 30 kVA
V Test
kV
meter
Vin
Amp
POWER TRANSFORMER
DOCUMENT
INDUCE TEST
APPROVED BY:
PAGE
7 of 8
Test Form.
TRANSFORMER AC VOLTAGE WITHSTAND TEST
Power Plan/Substation
Equipment
: Power Transformer
Number of Unit
: ....
[Type text]
REVISION
[Type text]
Manufacture
: Unindo
Model / Type
Power Rating
: 60 MVA
Operating Voltage
: 150 kV / 20kV
Nominal current
Cooling system
: ONAF
Serial Number
Year
: 20
Amp
kV
kV
Induce test
Test Point
TEST VOLTAGE ( kV )
Time
TEST RESULT
Durantion
R phase
107
15 minute
S phase
T phase
DOCUMENT
POWER TRANSFORMER
INDUCE TEST
ISSUED DATE
APPROVED BY:
PAGE
8 of 8
REVISION
INSULATION RESISTANCE ( M )
15 Second
60
second
HV LV
HV - TV
[Type text]
10 minute
Absorbtion
PI
R1/R15
R10/R1
REMARK
[Type text]
HV - Ground
LV - Ground
TV - Ground
LV - TV
Remark :
INSULATION RESISTANCE (AFTER APPLIED VOLTAGE TEST)
Meausere Point
INSULATION RESISTANCE ( M )
15 Second
60
10 minute
Absorbtion
PI
R1/R15
R10/R1
REMARK
second
HV LV
HV - TV
HV - Ground
LV - Ground
TV - Ground
LV - TV
Remark :
Tested by
Signature
Name
Date
[Type text]
Witneesed by
Supervised by