Sunteți pe pagina 1din 100

FORM 100.

09-EG1 (100)

AIRPAK
AIR HANDLING UNITS

28669a

27446A

AI

R
AN

PLY

ST

IED TO ARI
AS

ON

MA

ING WITH

DLING

CENTRAL

I
AT

OM

NUFACTUR
ER

TIF
ER

U NITS

RI

S TA

NDARD

43

INDOOR CENTRAL STATION AIR HANDLING UNITS

TABLE OF CONTENTS
PAGE

GENERAL DESCRIPTION .............................................. 3


Unit Description .......................................................... 3
Quality ......................................................................... 3
Flexibility ...................................................................... 3
Serviceability ............................................................... 3
Construction ............................................................... 3
Unit Design Summary ................................................ 4
Variable Air Volume Application .................................. 7
Factory-Packaged Controls ........................................ 8
Integrated Systems Network ...................................... 9
Segment Availability .................................................... 10
Nomenclature ............................................................. 11
QUICK SELECTION TABLES ..........................................
CDW Coils ..................................................................
BDW Coils ..................................................................
Forward Curved Fans .................................................
Dimensions and Weights ..........................................

12
12
12
13
14

ENGINEERING DATA .......................................................


Forward Curved & Airfoil Fan and
Motor Data ...............................................................
Plenum Fan ................................................................
Variable Inlet Vanes Operating Torques (DWDI) ........
SWSI Plenum Fan Operating Torques .......................
Coil Data .....................................................................
Multi-Zone Coil Data ...................................................
Flat Filter and Open Return Filter Segments .............
Angle, Filter/Mix. Box, Economizer Filter Segments ...
Bag Filter and Rigid Filter Segments .........................
HEPA Filter Segments ................................................
Carbon Filter Segments .............................................
Damper Data ..............................................................
Mixing Box/Filter Mixing Box Economizer ...............
Internal Face & Bypass ..........................................
External Face & Bypass .........................................
Face Damper Data ................................................
Damper Leakage Data ..........................................
Blender Data ..........................................................
Sound Attenuator ........................................................
Carbon Filter Design & Performance .........................
Electric Heater Design & Performance ......................
Min. Air Velocity for Open Coil-type Heaters ...............

16
16
17
18
19
20
21
22
23
24
25
26
27
27
27
28
28
29
29
31
32
33
33

UNIT SELECTION ...........................................................


Selecting an AirPak Unit .............................................
Reference Literature ...................................................
Altitude/Temperature Conversion Factors .................

34
34
35
35

AIR PRESSURE DROP ...................................................


Instructions .................................................................
Static Pressure Schematics .......................................
Turbofin CDW or CDX for Cooling & Dehumidifying ..
Turbofin CDW for Heating & CDW or CDX for
Sensible Cooling ....................................................
Free-Flow BDW or BDX for Cooling & Dehumidifying
Free-Flow BDW for Heating & BDW or BDX for
Sensible Cooling ....................................................
Air Blender ..................................................................
Steam Distributing ......................................................

36
36
36
38

38
39
39
40
40

PAGE

Electric Heater Air Pressure Drop ..............................


Diffuser .......................................................................
Vertical Casing Pressure Loss ..................................
Attenuator ....................................................................
Filter ............................................................................
Carbon Filter Air Pressure Drop .................................
Mixing Box Damper/Filter Mixing Box/ Economizer
And External Face and Bypass Damper ................
Internal Face and Bypass Damper Bypass ............
Internal Face and Bypass Damper Face ................
Face Damper Segment And External Face
and Bypass Damper ...............................................
Multi-Zone ...................................................................

40
40
40
40
40
41

SEGMENT DIMENSIONS ................................................


FS Supply Fan Segment ..........................................
FP Plenum Fan Segment ........................................
Coils (SC, MC, LC, XC, HC) ........................................
VC Vertical Coil Segment ........................................
IC Internal Face & Bypass Coil Segment ...............
Filter Dimensions (OF, FF, AF, RF, BF, HF, CF) ..........
FM Filter/ Mixing Box Segment .................................
MB Mixing Box Segment ..........................................
FR Return Fan Segment .........................................
FE Exhaust Fan Segment ........................................
AB Air Blender Segment ..........................................
EE Economizer Segment ........................................
EF Filter / Economizer ..............................................
SA, MA, LA Access Segment ...................................
IB Internal Face & Bypass Damper Segment ........
EB External Face & Bypass Segment .....................
FD Face Damper Segment .....................................
AT Sound Attenuator Segment ................................
DI Diffuser Segment ...............................................
DP Discharge Plenum Segment ............................
VP Vertical Plenum ..................................................
MZ Multi-Zone ..........................................................
EH Electric Heat .......................................................
IO Inlet / Outlet ..........................................................

46
46
48
50
51
52
53
56
57
58
60
62
63
64
65
66
67
68
69
70
71
72
73
74
75

PHYSICAL DATA ..............................................................


AirPak Segment Overall Dimensions &
Weight Calculations ..............................................
AirPak Segment Weights ...........................................
Coil Weights ...............................................................
IC Coil Connection Locations ....................................
Water Coil Connection Locations ..............................
Steam Coil Connection Locations .............................
Water Coil Dimensions ..............................................
Inlet Cone Dimensions ..............................................
Unit & Coil Hand Selection .........................................

76

41
42
43
44
45

76
77
78
83
84
86
87
88
89

MISCELLANEOUS DATA ................................................. 90


Power Wiring Options ................................................. 90
Typical Electric Heater Wiring Diagram ...................... 91
GUIDE SPECIFICATIONS ................................................
Part 1 General ..........................................................
Part 2 Products ........................................................
Part 3 Execution .......................................................

92
92
93
98

YORK INTERNATIONAL

FORM 100.09-EG1

General Description
UNIT DESCRIPTION
The YORK AirPak introduces a new level of quality, flexibility, and serviceability to the HVAC industry.
QUALITY
AirPak units are available with single wall and/or double
wall panels. Panels are available with a variety of insulation. Double wall panels have a full 2 inches of insulation
with solid or perforated lining. The additional option of 4
inch panels are available in discharge segments for acoustical application. Insulation and liners can be mixed and
matched to meet a variety of applications.
The AirPak coil drain pan is designed to meet the intent
of Indoor Air Quality (IAQ) requirements. The pan is 4
inches deep with a V-shaped design that reduces standing condensate. The pan has a full 2 inches of insulation
to give the pan the thermal protection it requires. Indoor
Air Quality drain pans (optional) are sloped in all directions with a single drain connection to minimize standing
condensate. Auxiliary drain pans are available in every
section. Intermediate drain pans are provided on all cooling coils that exceed 48 inches in finned height.
FLEXIBILITY

For maximum flexibility the AirPak is based on a segmented design concept. The unit construction is unitized, built as a single unit, for greater unit integrity. The
unit may be split per customer defined needs if required,
to meet various shipping and job site requirements.
The unitized construction means that each unit is built
as a unit, not as a assembly of segments. This adds
integrity to the unit and decreases the opportunity for
unit air leakage by greatly reducing the number of sheet
metal joints.
A complete line of Factory-Packaged Controls are available with the YORK AirPak. Factory Packaged Controls
assures the customer of single source responsibility, lower
first cost and high quality. YORK International now features an RS-232 PROTOCOL that can communicate with
any Building Automation System on the job site.
SERVICEABILITY
The AirPak features unparalleled accessibility. All AirPak
panels (single or double wall) are completely removable
as a single piece assemble. This eliminates the time
consuming practice of removing the interior and exterior
panels as separate pieces.
Access doors are available throughout the unit for access. The fan and filter segments come equipped with
access doors as a standard feature.
The YORK AirPak can also be offered with Quick-Connect Fasteners on the side access panels on most unit
sizes. The unique YORK panel latching system allows
panels to be removed and replaced in a matter of sec-

LD02600

00088VIP

AIRPAK IAQ COIL DRAIN PAN

YORK INTERNATIONAL

REMOVABLE ACCESS PANELS

General Description
SPRING RETURN
DAMPER ACTUATOR
(OPTIONAL)

4" DEEP
"V" SHAPED
DRAIN PAN

LOW LEAK
DAMPERS

CAST ALUMINUM
CORNER CONNECTOR

STRUCTURAL
BASE CHANNEL
INTERNAL
SPRING
ISOLATION

27509A

HEATING
COIL

MEDIUM
COIL

FILTER /
MIXING
BOX

FAN
SEGMENT

AIRPAK (PANELS REMOVED)

onds with a simple hand tool. The Quick Connect Fasteners allow for easier and more complete unit access.
The panels can also be removed in tight clearance areas
that do not permit normal door operation. This is an exclusive feature of the YORK AirPak.

CONSTRUCTION
The YORK AirPak design and construction is unequaled
in quality and serviceability. Its unique design gives the
strength and durability for industrial applications and the
complete serviceability that can only be found in the YORK
AirPak.

UNIT DESIGN SUMMARY


Unitized Construction
The design and application concept of the AirPak allows
the designer the flexibility to arrange individual segments
for a variety of applications. Each unit is then engineered
and built as a single piece of equipment. This results in
superior integrity when compared to units utilizing modules (sections) that are connected with sheet metal
screws to form a unit.
Each individual unit is custom designed to minimize the
number of panels in the unit. This decreases the opportunity for air leakage and assures better unit integrity.

YORK INTERNATIONAL

FORM 100.09-EG1

28669AR

AIRPAK UNITIZED CONSTRUCTION

Full Perimeter Base Rail Channel


The AirPak is completely supported by a full-perimeter
base rail channel. The base rail is constructed of heavy
gage galvanized steel and has intermediate cross- members for unit support. The base rail gives support to the
internal components and protects the unit during shipment and installation. The base rail also provides additional height for job site trapping of condensate drain pans.
Unit Frame
The rugged unit frame gives the unit industrial quality and
durability. The integral frame permits the unit panels to
be removed without affecting the integrity of the unit. After all of the panels have been removed, the frame remains to support the internal components.

26744A

AIRPAK UNIT FRAME

YORK INTERNATIONAL

General Description
Cast Aluminum Corner Post

Removable Panels

The rugged cast aluminum corner posts add strength and


rigidity to the unit. The beveled corner finish also symbolizes the comprehensive engineering, style and quality of
the YORK AirPak.

All of the AirPak panels are completely removable without affecting the structural rigidity of the unit. As an option, the panels can be provided with Quick-Connect Fasteners on the side access panels for most unit sizes.
The removable panels reduce the time required to service
and clean components - which is an important part of
maintaining good Indoor Environmental Quality.

28759A

26757A

AIRPAK CORNER CONNECTOR

REMOVABLE ACCESS PANELS (CUTAWAY)

Quick Connect Fastener


Full Length and Height Raceway Channels
The fully insulated, double-wall raceway channels tie the
entire unit together by connecting the corner posts, unit
frame and base rail. The raceway also creates the panel
sealing.

The Quick-Connect Fastener is the key to the optional


panel removal system. The latch is operable with a simple
wrench. The motion of the latch is 180 degrees. The first
90 degrees moves the lever arm to a sealing position on
the frame and the second 90 degrees pulls the latch snug,
creating the panel seal.

RACEWAY
CHANNELS

26753A

RACEWAY CHANNELS
6

26833A, 26832A

QUICK CONNECT FASTENER


YORK INTERNATIONAL

FORM 100.09-EG1

VARIABLE AIR VOLUME APPLICATIONS

For additional information on the Air-Modulator, refer to


Form 100.04-EG1.

Factory mounted variable frequency drives (YORK AirModulator) and variable inlet vanes are available with the
YORK AirPak for Variable Air Volume Applications.
YORK Air-Modulator (Variable Frequency Drive):
The YORK Air-Modulator (variable frequency drive) offers
the most efficient means of fan control for variable air
volume systems. The Air-Modulator varies the speed of
the fan to match the VAV load requirements.
The Air-Modulator takes maximum advantage of the relationship between fan speed and fan horsepower. With
the Air-Modulator, any given reduction in fan speed results in a cubic reduction in fan horsepower. For example,
a 10% speed reduction results in a 27% fan horsepower
reduction!
The Air-Modulator offers the following benefits over variable inlet vanes and discharge dampers:
Extended Equipment Life - soft start of motor and fan.
Quieter Fan Operation - fan operating at reduced speed
and constant line of efficiency.
Eliminates need for starter panels.
Improved system control and response - DDC Controls
with LED Digital Display.
Available on all unit sizes as a factory mounted option.
Proven Reliability.

YORK will balance the fan for the entire range of operation (10 - 100% RPM) for added reliability. Actual fan turndown will vary with fan type and selection.
Variable Inlet Vanes
Variable inlet vanes are another method of energy efficient fan control. While the fan runs at a constant speed,
the inlet vanes modulate the air entering the fan. This
produces a reduced air volume which results in lower
operating horsepowers.
Variable inlet vanes are available on all Airfoil fans, Plenum fans and Forward Curved fans sizes 12 x 12 and
larger.
The vanes are located within each inlet cone of Airfoil
fans, Plenum fans, and adjacent to the inlet ring of Forward Curved fans. The vanes consist of a series of radial
damper blades which operate in parallel and are controlled by a common control shaft which extends to the
outside of the fan.
YORK INTERNATIONAL

27447A

YORK AIR-MODULATOR WITH OPTIONS PANEL


7

General Description

27446A

AIRPAK AIR HANDLING UNIT WITH FACTORY PACKAGED


CONTROLS (FPC) AND INTEGRATED SYSTEMS NETWORK (ISN) PANEL

FACTORY-PACKAGED CONTROLS

Quality Control

Factory Engineered

YORK Factory-Packaged Controls assure you of getting


a higher quality control system, right from the factory.
The control system is designed and mounted following
the same stringent quality control standards by which
the units are built.

YORK Factory-Packaged Controls assures you of getting a complete factory-engineered system no surprises,
no hassles, and no compromises. The control system is
designed with each specific piece of equipment in mind.
This assures you that the system will control, monitor
and diagnose only those points that are necessary to
maintain optimum performance.
Reduce Costs
YORK Factory-Packaged Controls reduce costs by taking the guesswork out of control installation. Each control is mounted in the factory as the equipment is being
manufactured. There are no worries over job site locations or conditions. Factory labor means faster assembly and lower first cost.

Single Source Responsibility


When an air unit with field-applied controls develops a
problem, getting some answers and action can be difficult. The controls supplier believes the equipment manufacturer is responsible, and vice versa. With YORK
Factory-Packaged Controls there is only one company
to call YORK.
Full Service Support
Because YORK Factory-Packaged Controls are an integral part of the equipment, who better to troubleshoot
and service the system than a professional YORK Service technician. The YORK Service technician knows not
only the equipment and the controls hardware, but he
also has a working knowledge of equipment application
and operation. Every unit is backed by this kind of professional support.
Stand-Alone Or Network Control

26750A

YORK Factory-Packaged Controls offer you the flexibility of stand-alone or network control. Each unit has an
integral time clock and a full-featured array of optimization and diagnostic function. Included with the controls is
the capability to tie into a YORK Integrated Systems
Network (ISN). For further information see Form
450.11-EG1.

AIRPAK MIXING BOX WITH DAMPER ACTUATOR


8

YORK INTERNATIONAL

FORM 100.09-EG1

INTEGRATED SYSTEMS NETWORK (ISN)


The YORK Integrated Systems Network (ISN) is the
complete integration of airside, chiller, and building automation controls. YORK Factory-Packaged Controls
make it easy to upgrade from a group of air handling
units operating individually to an ISN airside system, with
all the units operating in concert. Thats because each
unit is able to share information with all the other units on
the network.

each unit control center with the central control center,


which can coordinate the operation of the entire air handling system. Other YORK airside and waterside equipment can also be integrated into the system.
No longer will HVAC equipment be responding as a collection of individual devices, but rather as a network the
YORK Integrated Systems Network.

Theres no need to duplicate or replace existing sensors


and actuators. Instead, a twisted pair of wires connects

LD04321
26363A

INTEGRATED SYSTEMS NETWORK (ISN)


CONTROL CENTER
YORK INTERNATIONAL

YORK INTEGRATED SYSTEMS NETWORK (ISN)


9

General Description
SEGMENT AVAILABILITY

LD04293

10

YORK INTERNATIONAL

FORM 100.09-EG1

SEGMENT IDENTIFICATION
Access
-

Unit Type:
' AP - AirPak Central Station
Air Handling Unit

' SA
' MA
' LA

Fan Segment:

Segments:
Short Access (12")
Medium Access (18")
Long Access (24")

Coils (Contd.)

Accessory Segments:

' FS - Supply Fan


' FR - Return Fan
' FE - Exhaust Fan

' AT
' Dl
' AB
' DP
' FD
' IO
' VP
' EH

Fan Types:
 ' Forward Curved Fan
' Standard
' Class II
' Airfoil
' Standard
' Class II

- Attenuator (3', 5' & 7')


- Diffuser
- Air Blender
- Discharge Plenum
- Face Damper
- Inlet / Outlet
- Vertical Plenum
- Electric Heat (24" & 36")

Bypass Segments:

' IB
' EB

' FP - SWSI Plenum Fan


Fan Types:
' Airfoil
' Standard
' Class II

- Internal Face & Bypass


- External Face & Bypass

' LC
' XC
' HC
' VC
' IC

- Long Coil (28" Coil Space)


- Extra-Long Coil (36" Coil Space)
- Heating Coil (8" Coil Space)
- Vertical Coil (20" Coil Space)
- Integral Face & Bypass Coil

Filter
' OF
' FF
' AF
' BE
' RF
' HF
' CF

Segments:
- Open Return Filter (2" & 4")
- Flat Filter (2" & 4")
- Angle Filter (2" & 4")
- Bag Filter (21" & 32") w / 2" or 4" Pre-filters
- Rigid Filter (12") w / 2" or 4" Pre-filters
- HEPA Filter
- Carbon Filter

Mixing Box Segments:


' FM - Filter / Mixing Box
' MB - Mixing Box
' EE - Economizer
' EF - Filter / Economizer

Coil Segments:

' SC - Short Coil (10" Coil Space)


' MC - Medium Coil (20" Coil Space)
' MZ - Multi-Zone

NOMENCLATURE
AIR FLOW

AP

120

FS

15 x 11

(AF) (MB)
Accessories

Unit Type
AP - AirPak

AB
AF
AT
BF
CF
Dl
DP
EB
EE
EF
EH
FD
FF
FM
HC
HF

Unit Size
35
60
80
105
120
150
170
215
250

305
360
400
500
580
660
800
1000

- Air Blender
- Angle Filter (2" & 4")
- Attenuator (3', 5', 7')
- Bag Filter (21" & 32")
- Carbon Filter
- Diffuser
- Discharge Plenum
- External Face & Bypass
- Economizer
- Filter / Economizer
- Electric Heat (24" & 36")
- Face Damper
- Flat Filter (2" & 4")
- Filter / Mixing Box (2" & 4")
- Heating Coil (8")
- HEPA Filter

IB
IC
IO
LA
LC
MA
MB
MC
MZ
OF
RF
SA
SC
VC
VP
XC

- Internal Face & Bypass


- Integral Face & Bypass
- Inlet / Outlet
- Long Access (24")
- Long Coil
- Medium Access (18")
- Mixing Box
- Medium Coil
- Multi-Zone
- Open Return Filter (2" & 4")
- Rigid Filter (12")
- Short Access (12")
- Short Coil
- Vertical Coil (20")
- Vertical Plenum
- Extra-Long Coil (36")

Fan Segment
Fan Size

FS - Supply Fan (Standard)


FS II - Supply Fan (Class II)
FE
- Exhaust Fan (Standard)
FE II - Exhaust Fan (Class II)
FR - Return Fan (Standard)
FR II - Return Fan (Class II)
FP
- Plenum Fan (Standard)
FP II - Plenum Fan (Class II)

YORK INTERNATIONAL

FC Fans
9x6
9x9
10x10
12x12
15x11
15x15
18x18

20x18
20x20
22x20
22x22
25x22
25x25
27x25

AF Fans
28x28
30x30
32x32

12
15
18
20
22
25

28
32
36
40
44

SWSI
Plenum Fans
20
40
24
44
27
49
30
54
33
60
36
66

11

Quick Selection Tables


CDW COILS (5/8" O.D.)

UNIT
SIZE
AP

FACE VELOCITY - FPM


450

475

500

525

550

575

CFM

COIL
DIMENSIONS
(INCHES)

COIL
FACE
AREA
(SQ. FT.)

FH

FL

35

1,527

1,612

1,697

1,782

1,867

1,952

21.25

23.00

3.4

60

2,470

2,607

2,744

2,881

3,018

3,156

27.25

29.00

5.5

80

3,406

3,595

3,785

3,974

4,163

4,352

27.25

40.00

7.6

105

4,538

4,798

5,042

5,294

5,546

5,798

30.25

48.00

10.1

120

5,388

5,688

5,987

6,286

6,586

6,885

30.25

57.00

12.0

150

6,617

6,985

7,352

7,720

8,088

8,455

30.25

70.00

14.7

170

7,585

8,007

8,428

8,849

9,271

9,692

33.25

73.00

16.9

215

9,567

10,099

10,630

11,162

11,693

12,225

39.25

78.00

21.3

250

11,030

11,642

12,255

12,868

13,481

14,093

45.25

78.00

24.5

305

13,570

14,324

15,078

15,832

16,586

17,340

48.25

90.00

30.2

360

16,172

17,070

17,969

18,867

19,766

20,664

57.50

90.00

35.9

400

17,969

18,967

19,965

20,964

21,962

22,960

57.50

100.00

39.9

500

22,225

23,460

24,694

25,929

27,164

28,399

63.50

112.00

49.4

580

26,425

27,893

29,361

30,829

32,297

33,765

75.50

112.00

58.7

660

29,728

31,380

33,031

34,683

36,334

37,986

75.50

126.00

66.1

800

35,634

37,614

39,594

41,573

43,553

45,533

90.50

126.00

79.2

1000

45,199

47,710

50,221

52,732

55,243

57,755

108.75

133.00

100.4

BWD COILS (1/2" O.D.)

UNIT
SIZE
AP

FACE VELOCITY - FPM


450

475

500

525

550

575

CFM

12

COIL
DIMENSIONS
(INCHES)
FH

FL

COIL
FACE
AREA
(SQ. FT.)

35

1,438

1,517

1,597

1,677

1,757

1,837

20.00

23.00

3.2

60

2,492

2,631

2,769

2,908

3,046

3,184

27.50

29.00

5.5

80

3,438

3,628

3,819

4,010

4,201

4,392

27.50

40.00

7.6
10.0

105

4,500

4,750

5,000

5,250

5,500

5,750

30.00

48.00

120

5,344

5,641

5,938

6,234

6,531

6,828

30.00

57.00

11.9

150

6,563

6,927

7,292

7,656

8,021

8,385

30.00

70.00

14.6

170

7,414

7,826

8,238

8,650

9,062

9,474

32.50

73.00

16.5

215

9,141

9,648

10,156

10,664

11,172

11,680

37.50

78.00

20.3

250

10,969

11,578

12,188

12,797

13,406

14,016

45.00

78.00

24.4

305

13,359

14,102

14,844

15,586

16,328

17,070

47.50

90.00

29.7

360

16,172

17,070

17,969

18,867

19,766

20,664

57.50

90.00

35.9

400

17,969

18,967

19,965

20,964

21,962

22,960

57.50

100.00

39.9

500

22,750

24,014

25,278

26,542

27,806

29,069

65.00

112.00

50.6

580

26,250

27,708

29,167

30,625

32,083

33,542

75.00

112.00

58.3

660

29,531

31,172

32,813

34,453

36,094

37,734

75.00

126.00

65.6

800

36,422

38,445

40,469

42,492

44,516

46,539

92.50

126.00

80.9

1000

44,680

47,162

49,644

52,126

54,609

57,091

107.50

133.00

99.3

YORK INTERNATIONAL

FORM 100.09-EG1

FORWARD CURVED FANS

CFM

STATIC PRESSURE
2.0

2.5

1500

3.0

3.5

4.0

4.5

5.0

5.5

2500

10 x 10

3000
3500

AP60

9x9

AP80

10 x 10

4000

UNIT
SIZE

AP35

9x9

2000

6.0

4500
5000

15 x 15

12 x 12

AP105

15 x 15

15 x 11

AP120

18 x 18

15 x 15

AP150

20 x 20

18 x 18

AP170

20 x 20

18 x 18

AP215

22 x 22

20 x 20

AP250

5500
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
11000
11000
12000
13000
14000
15000

25 x 25

22 x 22

AP305

28 x 28

25 x 25

AP360

28 x 28

25 x 25

AP400

32 x 32

28 x 28

AP500

16000
16000
17500
19000
19000
20500
22000
24000
26000
28000
28000
30000

32 x 32

AP580

32 x 32

AP660

32000
32000
34000
36000
NOTES:

1. All fan sizes specified in the quick selection chart above are based on the most efficient forward curved fan for the specified
static pressure and CFM.

YORK INTERNATIONAL

13

Quick Selection Tables


DIMENSIONS & WEIGHTS
UNIT SIZE
UNIT HEIGHT
UNIT WIDTH

35
37
36

SEGMENT

60
43
42

80
43
53

105
46
62

120
46
70

150
46
83

170
52
86

215
55
91

250
61
91

L = LENGTH OF SEGMENT IN THE DIRECTION OF AIRFLOW (INCHES)

FS

FAN 1

L / lbs.

42 / 486

44 / 604

46 / 833

46 / 965

46 / 1065 48 / 1277 54 / 1729 54 / 1863 58 / 2040

FR

FAN 2

L / lbs.

40 / 479

44 / 669

44 / 742

46 / 936

46 / 1186

46 / 1252 48 / 1247 48 / 1604 54 / 1880

FE

FAN 3

L / lbs. N/A / N/A N/A / N/A N/A / N/A 46 / 1038

46 / 1180

46 / 1242 48 / 1418 54 / 1797 58 / 1993

FAN 4

L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A 54 / 1847

FAN 1
FAN 2

L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A 40 / 1141 44 / 1365 46 / 1534 50 / 1725
L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A 46 / 1454 50 / 1744 52 / 1995

SA

SHORT ACCESS (12")

12 / 80

12 / 92

12 / 108

12 / 124

12 / 133

12 / 149

12 / 163

12 / 169

12 / 174

MA

MEDIUM ACCESS (18")

18 / 114

18 / 125 18 / 141

18 / 165

18 / 187

18 / 197

18 / 209

18 / 225

18 / 249

LA

LONG ACCESS (24")

24 / 144

24 / 158 24 / 177

24 / 207

24 / 222

24 / 245

24 / 260

24 / 280

24 / 317

SC

SHORT COIL (10')


(using 6 Row / 8 FPI BDW coil)
MEDIUM COIL (20")
(using 8 Row / 8 FPI BDW coil)
LONG COIL (28")
(using (2) 8 Row/ 8 FPI BDW coil)
EXTRA LONG COIL (36") (using (2)

16 / 227

18 / 301 18 / 345

18 / 423

18 / 480

18 / 547

18 / 608

20 / 679

20 / 743

28 / 779

30 / 864

30 / 987

FP

MC
LC
XC

/ lbs.
/ lbs.
L / lbs.
L / lbs.
L

/ lbs.

26 / 311

28 / 493 28 / 459

28 / 539

28 / 601

28 / 692

/ lbs.

34 / 418

36 / 546 36 / 660

36 / 800

36 / 917

36 / 1051 36 / 1188 38 / 1308 38 / 1467

/ lbs.

42 / 492

44 / 650 44 / 773

44 / 915

44 / 1044 44 / 1189 44 / 1341 46 / 1487 46 / 1662

/ lbs. * / 400
/ lbs. 10 / 113

* / 610

* / 722

* / 806

* / 944

* / 1106

10 / 134 10 / 158

10 / 191

10 / 212

10 / 242

10 / 270

* / 1206 * / 1398
10 / 302 10 / 338

24 / 601

24 / 682

24 / 789

24 / 899

24 / 931

24 / 1055

/ 13
10 / 111
18 / 170
20 / 181
26 / 199
36 / 300
18 / 164
20 / 178
18 / 186
42 / 36
44 / 36
22 / 258
24 / 292
20 / 222
22 / 173
38 / 242
62 / 403
86 / 564
18 / 141
20 / 185
26 / 209
40 / 374
12 / 128
12 / 111
N/A / N/A
24 / 391
36 / 482
32 / 480
38 / 546
N/A / N/A

/ N/A
/ 14 0 / 17
2 / 18
2 / 22
10 / 128 10 / 146
20 / 190 20 / 219
22 / 215 22 / 249
26 / 224 26 / 255
36 / 327 36 / 365
18 / 192 18 / 220
20 / 211 20 / 238
18 / 223 18 / 273
46 / 42
46 / 53
48 / 42
48 / 53
26 / 318 26 / 379
28 / 343 28 / 407
20 / 263 20 / 296
28 / 235 34 / 289
38 / 294 38 / 336
62 / 490 62 / 559
86 / 686 86 / 783
18 / 166 22 / 223
20 / 206 20 / 228
26 / 255 26 / 302
40 / 431 40 / 481
12 / 161 12 / 193
12 / 145 12 / 168
N/A / N/A N/A / N/A
24 / 460 24 / 523
36 / 567 36 / 644
32 / 569 32 / 667
38 / 648 38 / 756
46 / 1202 50 /1348

/ 28
2 / 38
10 / 181
20 / 253
22 / 281
26 / 308
36 / 430
18 / 277
20 / 301
18 / 326
46 / 62
40 / 62
26 / 448
28 / 477
20 / 365
36 / 362
38 / 385
62 / 642
86 / 898
22 / 261
20 / 276
26 / 378
40 / 546
12 / 240
12 / 195
N/A / N/A
24 / 615
36 / 754
32 / 832
38 / 942
50 / 1558

/ 31
2 / 42
10 / 202
20 / 283
22 / 318
26 / 351
36 / 465
18 / 318
20 / 345
18 / 413
46 / 70
48 / 70
26 / 503
28 / 536
20 / 402
28 / 330
38 / 441
62 / 736
86 / 1030
22 / 284
20 / 310
26 / 403
40 / 624
12 / 268
12 / 215
N/A / N/A
24 / 658
36 / 807
32 / 942
38 / 1066
50 / 1726

/ 36
2 / 49
10 / 228
20 / 314
22 / 340
26 / 390
36 / 525
18 / 353
20 / 387
18 / 430
46 / 83
48 / 83
26 / 571
28 / 609
20 / 455
30 / 380
38 / 485
62 / 809
86 / 1133
22 / 302
20 / 335
26 / 458
40 / 691
12 / 305
12 / 236
* / 580
24 / 746
36 / 914
32 / 1068
38 / 1207
50 / 1964

/ 46
2 / 61
10 / 239
16 / 357
18 / 398
26 / 425
36 / 549
18 / 378
20 / 413
18 / 520
44 / 66
46 / 66
24 / 628
26 / 663
22 / 506
34 / 450
38 / 526
62 / 877
86 / 1228
26 / 357
22 / 395
26 / 512
42 / 777
12 / 348
12 / 271
* / 688
24 / 837
36 / 1020
32 / 1219
38 / 1370
54 / 2195

/ 47
2 / 63
10 / 253
22 / 387
24 / 437
26 / 451
36 / 615
18 / 418
20 / 466
18 / 594
56 / 91
58 / 91
30 / 739
32 / 789
26 / 596
36 / 497
38 / 560
62 / 933
86 / 1307
26 / 419
26 / 452
32 / 608
52 / 916
12 / 395
12 / 293
* / 778
24 / 917
36 / 1114
32 / 1311
38 / 1474
56 / 2472

/ 53
/ 69
10 / 267
18 / 416
20 / 503
26 / 480
36 / 656
18 / 435
20 / 483
18 / 617
56 / 91
58 / 91
30 / 846
32 / 928
26 / 651
34 / 504
38 / 610
62 / 1017
86 / 1423
30 / 478
26 / 474
32 / 674
52 / 1074
12 / 424
12 / 325
* / 860
24 / 969
36 / 1176
32/ 1488
38 / 1607
60 / 2756

20 / 192

20 / 220 20 / 242

8 Row/ 8 FPI & (1) 1 Row/ 8 FPI BDW coils)

VC

VERTICAL COIL (20")

HC

HEATING COIL (10")


(using 1 Row / 8 FPI SDC Coil)

INTEGRAL FACE & BYPASS COIL

/ lbs.
/ lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.

IC

OPEN RETURN FILTER (2")

OF

OPEN RETURN FILTER (4")

FF

FLAT FILTER (2" or 4")

AF

ANGLE FILTER (2")


ANGLE FILTER (4")
BAG FILTER (21" w/ 2" or 4" Pre-filter)

BF

BAG FILTER (32" w/ 2" or 4" Pre-filter)


RIGID FILTER (12" w/ 2" Pre-filter)

RF

RIGID FILTER (12" w/ 4" Pre-filter)

HF

HEPA FILTER
FILTER / ECONOMIZER (2")

EF

FILTER / ECONOMIZER (4")


FILTER / MIXING BOX (2")

FM

FILTER / MIXING BOX (4")

MB

MIXING BOX

AB

AIR BLENDER
ATTENUATOR (3')

AT

ATTENUATOR (5')
ATTENUATOR (7')

DI

DIFFUSER

DP

DISCHARGE PLENUM

EB

EXTERNAL FACE & BYPASS

EE

ECONOMIZER

FD

FACE DAMPER

IB

INTERNAL FACE & BYPASS

VP

VERTICAL PLENUM
ELECTRIC HEATER (EH-2)

EH

ELECTRIC HEATER (EH-3)


CARBON FILTER (CF-1) (Rechargeable)

CF

CARBON FILTER (CF-2) (Rechargeable)

MZ

MULTI-ZONE (Includes Hot Deck


and Cold Deck with coils & Diffuser)

IO

SEGMENT

*
14

N/A

/ N/A

0 / 11

N/A / N/A N/A


0

0
2

20 / 297

20 / 325

20 / 365

22 / 398

26 / 478

26 / 517

End Channels - 5" Base

Weight (lbs.)

74

81

88

100

106

116

121

126

128

End Channels - 8" Base

Weight (lbs.)

85

92

101

114

121

133

138

143

146

= Same as FS.

/ lbs.

* / 610

NOTES: 1.
2.
3.
4.
5.

Add 6" in length (for the two end channels) to determine the overall unit length.
The unit widths do not include coil connections.
For coil segments, the dimensions in (") represents the coil space available.
The unit height includes the base rail (5" for the AP-35 AP-500 and 8" for the AP-580 AP-1000.
Fan weights includes the largest available motor.

YORK INTERNATIONAL

FORM 100.09-EG1

DIMENSIONS & WEIGHTS


UNIT SIZE
UNIT HEIGHT
UNIT WIDTH

305
64
103

SEGMENT
FS
FR
FE

FAN 2
FAN 3

FAN 1
FAN 2
SHORT ACCESS (12")

MA

MEDIUM ACCESS (18")

LA

LONG ACCESS (24")

SC

SHORT COIL (10')


(using 6 Row / 8 FPI BDW coil)
MEDIUM COIL (20")
(using 8 Row / 8 FPI BDW coil)
LONG COIL (28")
(using (2) 8 Row/ 8 FPI BDW coil)
EXTRA LONG COIL (36") (using (2)

LC
XC

/ lbs
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.

SA

MC

400
73
113

500
81
125

580
95
125

660
95
139

800
113
139

1000
131
146

L = LENGTH OF SEGMENT IN THE DIRECTION OF AIRFLOW (INCHES)

FAN 1

FAN 4
FP

360
73
103

62 / 2497

68 / 2834

68 / 3071

76 / 3958

76 / 4276

76 / 5205

82 / 6131

82 / 6419

58 / 2738

62 / 2808

62 / 3068

68 / 3874

72 / 4264

76 / 4694

88 / 5971

88 / 7057

62 / 2679

62 / 2751

68 / 3112

76 / 4080

76 / 4392

82 / 5181

94 / 7028

94 / 8502

58 / 2625 58 / 2670

62 / 2925

68 / 3704 N/A

52 / 2292

52 / 2462

56 / 2819

60 / 3617

66 / 4376

70 / 5255

74 / 5823

80 / 6945

56 / 2403

56 / 2557

60 / 3212

66 / 3966

70 / 4704

74 / 5709

80 / 6405

84 / 7867

12 / 219

12 / 243

12 / 275

12 / 302

12 / 328

12 / 353

12 / 374

12 / 399

18 / 289

18 / 310

18 / 330

18 / 384

18 / 429

18 / 461

18 / 489

18 / 523

24 / 359

24 / 375

24 / 396

24 / 477

24 / 530

24 / 586

24 / 605

24 / 647

22 / 933

24 / 1044

24 / 1137

26 / 1404

26 / 1603

28 / 1826

32 / 2109

36 / 2555

N/A N/A

N/A N/A

/ N/A

N/A

/ N/A

/ lbs.

32 / 1197

34 / 1364

34 / 1467

36 / 1740

36 / 2003

38 / 2224

42 / 2621

46 / 3153

/ lbs.

40 / 1788

42 / 2061

42 / 2257

44 / 2714

44 / 3119

46 / 3462

50 / 4049

54 / 4993

/ lbs.

48 / 2042

50 / 2326

50 / 2510

52 / 3129

52 / 3458

54 / 3819

N/A

/ N/A

N/A

/ N/A

/ lbs. * / 1691
/ lbs. 10 / 399

* / 1954
10 / 435

* / 2105
10 / 474

* / 2554
10 / 545

N/A

/ N/A

N/A

/ N/A

N/A

/ N/A

10 / 657

10 / 705

10 / 835

10 / 969

8 Row /8 FPI & (1) 1 Row/8 FPI BDW coils)

VC

VERTICAL COIL (20")

HC

HEATING COIL (10")


(using 1 Row / 8 FPI SDC Coil)

IC

INTEGRAL FACE & BYPASS COIL

OF

OPEN RETURN FILTER (2")


OPEN RETURN FILTER (4")

FF

FLAT FILTER (2" or 4")

AF

ANGLE FILTER (2")


ANGLE FILTER (4")

BF
RF
HF
EF
FM

BAG FILTER (21" w/ 2" or 4" Pre-filter)


BAG FILTER (32" w/ 2" or 4" Pre-filter)
RIGID FILTER (12" w/ 2" Pre-filter)
RIGID FILTER (12" w/ 4" Pre-filter)
HEPA FILTER
FILTER / ECONOMIZER (2")
FILTER / ECONOMIZER (4")
FILTER / MIXING BOX (2")
FILTER / MIXING BOX (4")

MB

MIXING BOX

AB

AIR BLENDER
ATTENUATOR (3')

AT

ATTENUATOR (5')
ATTENUATOR (7')

DI

DIFFUSER

DP

DISCHARGE PLENUM

EB

EXTERNAL FACE & BYPASS

EE

ECONOMIZER

FD

FACE DAMPER

IB

INTERNAL FACE & BYPASS

VP

VERTICAL PLENUM

EH
CF
MZ

ELECTRIC HEATER (EH-2)


ELECTRIC HEATER (EH-3)
CARBON FILTER (CF-1) (Rechargeable)
CARBON FILTER (CF-2) (Rechargeable)
MULTI-ZONE

(Includes Hot Deck

/ N/A

N/A

/ lbs.
/ lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.
L / lbs.

24 / 1117

24 / 1355

23 / 1437

34 / 1843

34 / 2028

34 / 2387

34 / 2615

34 / 2950

/ 52
2 / 72
10 / 333
18 / 539
20 / 618
26 / 597
36 / 768
18 / 517
20 / 563
18 / 737
58 / 103
60 / 103
32 / 1102
34 / 1179
28 / 822
36 / 648
38 / 775
62 / 1291
86 / 1808
30 / 595
28 / 615
32 / 825
54 / 1208
12 / 531
12 / 418
* / 1000
24 / 1080
36 / 1309
32 / 1755
38 / 1953
62 / 3277

/ 61
2 / 87
10 / 360
20 / 588
22 / 680
26 / 648
36 / 831
18 / 611
20 / 654
18 / 799
68 / 103
70 / 103
36 / 1265
38 / 1354
32 / 946
40 / 739
38 / 932
62 / 1554
86 / 2175
34 / 680
32 / 720
38 / 981
64 / 1532
12 / 590
12 / 463
* / 1039
24 / 1197
36 / 1445
32 / 1919
38 / 2139
68 / 3686

/ 76
2 / 105
10 / 400
20 / 627
22 / 726
26 / 697
36 / 895
18 / 661
20 / 718
18 / 893
68 / 113
70 / 113
36 / 1363
38 / 1462
32 / 1050
42 / 801
38 / 999
62 / 1666
86 / 2332
34 / 724
32 / 774
38 / 1057
64 / 1675
12 / 639
12 / 501
* / 1159
24 / 1326
36 / 1594
32 / 2127
38 / 2378
68 / 3971

/ 91
2 / 126
10 / 478
20 / 738
22 / 836
26 / 838
36 / 1085
18 / 772
20 / 841
18 / 1121
72 / 125
72 / 125
40 / 1740
40 / 1827
40 / 1408
42 / 1006
38 / 1125
62 / 1875
86 / 2624
34 / 864
40 / 1096
38 / 1298
72 / 2123
12 / 785
12 / 607
* / 1412
24 / 1477
36 / 1775
32 / 2491
38 / 2777
70 / 4671

/ 95
2 / 131
10 / 554
22 / 785
26 / 934
26 / 967
36 / 1238
18 / 856
20 / 931
18 / 1267
82 / 125
84 / 125
44 / 2028
48 / 2104
44 / 1703
48 / 1169
38 / 1279
62 / 2131
86 / 2984
36 / 1065
44 / 1343
44 / 1567
82 / 2620
12 / 910
12 / 695
N/A / N/A
24 / 1605
36 / 1927
34 / 2991
40 / 3309
N/A / N/A

0 / 111

0 / 138

0 / 167

2 / 139

2 / 190

2 / 234

10 / 611

10 / 683

10 / 764

/ lbs

28 / 662

32 / 755

32 / 840

40 / 1123

44 / 1367

44 / 1528

50 / 1811

50 / 2107

22 / 904

22 / 1092

22 / 1187

26 / 1054

24 / 1323

26 / 1497

26 / 1065

26 / 1206

26 / 1632

36 / 1303

36 / 1473

36 / 2002

18 / 953

18 / 1100

18 / 1292

20 / 1035

20 / 1194

20 / 1407

18 / 1420

18 / 1660

18 / 1942

82 / 139

92 / 139

96 / 146

84 / 139

94 / 139

98/ 146

44 / 2286

52 / 2846

52 / 3246

48 / 2447

54 / 3077

54 / 3513

44 / 1703

50 / 1900

50 / 2709

50 / 1250

48 / 1305

54 / 1587

38 / 1373

38 / 1541

38 / 1642

62 / 2288

62 / 2568

62 / 2737

86 / 3203

86 / 3595

86 / 3832

36 / 1150

36 / 1245

36 / 1366

44 / 1496

50 / 1769

50 / 2032

44 / 1701

44 / 1938

50 / 2121

82 / 2674

90 / 3123

94 / 3602

12 / 1022

12 / 1155

12 / 1361

12 / 765

12 / 875

N/A

/ N/A

N/A

/ N/A

12 / 1023
N/A

/ N/A

24 / 1795

24 / 1980

24 / 2384

36 / 2147

36 / 2364

36 / 2829

34 / 3256

34 / 3856

34 / 4662

40 / 3611

40 / 4267

N/A

/ N/A

N/A

/ N/A

40 / 5131
N/A

/ N/A

and Cold Deck with coils & Diffuser)

IO

SEGMENT

End Channels - 5" Base

Weight (lbs.)

146

150

158

171

N/A

N/A

N/A

N/A

End Channels - 8" Base

Weight (lbs.)

168

171

181

196

200

213

220

237

6. See VC segment dimensions on page 51 for specific segment height.


7. MZ, VC and VP segments are taller than the nominal unit height.
8. Certain items (i.e. coil connections, door handles, mounting feet, etc.) may extend beyond the cabinet
dimensions.
9. Weights are shipping weights not operating weights.

YORK INTERNATIONAL

= Same as FS.

15

Engineering Data Fans


FORWARD CURVED & AIRFOIL FAN AND MOTOR DATA
UNIT
SIZE
35
60
80
105

120

150

170

215

250

305

360

400

500

580

660

800

1000

FAN
SEGMENT
NUMBER1

TYPE

SIZE

1
2
1
2
1
2
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
3
1
2
3
1
2
3
1
2
3
1
2
3

FC
FC
FC
FC
FC
FC
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
FC
AF
FC
FC *
FC
AF
FC
FC *
FC
AF
FC
FC *
FC *
AF
FC
FC *
FC
AF
FC
AF
AF
AF
AF
AF
AF
AF
AF

9-9
9-6
10-10
9-9
12-12
10-10
15-15
12-12
12
15-15
15-11
15
18-18
15-15
15
20-20
18-18
18
20-20
18-18
20
22-22
20-20
22
20-18
25-25
22-22
25
22-20
28-28
25-25
25
22-20
28-28
25-25
28
25-22
32-32
28-28
32
27-25
32-32
30-30
32
32-32
32
36
36
40
44
36
40
44

MAX.
MOTOR
HP

MAX.
MOTOR
FRAME

FAN OUTLET
AREA
(sq. ft.)

3
3
5
7.5
7.5
7.5
7.5
10
15
7.5
10
20
15
10
20
20
15
25
25
15
30
20
25
30
25
20
40
40
40
30
40
40
40
25
40
50
40
40
50
60
50
50
50
75
60
75
75
100
75
60
100
100
100

182T
182T
184T
213T
213T
213T
213T
215T
254T
213T
215T
256T
254T
215T
256T
256T
254T
284T
284T
254T
286T
256T
284T
286T
284T
256T
324T
324T
324T
286T
324T
324T
324T
284T
324T
326T
324T
324T
326T
364T
326T
326T
326T
365T
364T
365T
365T
404T
365T
364T
404T
404T
404T

0.84
0.59
1.03
0.84
1.45
1.03
2.04
1.45
1.45
2.04
1.62
2.04
2.86
2.04
2.04
4.38
2.86
2.86
4.38
2.86
4.38
5.50
4.38
5.50
3.91
6.91
5.50
6.91
4.78
8.68
6.91
6.91
4.78
8.68
6.91
8.68
6.13
10.92
8.68
10.92
7.55
10.92
9.38
10.92
10.92
10.92
13.75
13.75
17.28
20.49
13.75
17.28
20.49

1. Fan Segment Numbers (1), (2) and (3) refer to segment lengths which vary in size
depending on the fan selected within a given AP unit size.

16

FC = Forward Curved Fan


AF = Airfoil Fan

YORK INTERNATIONAL

FORM 100.09-EG1

PLENUM FAN
PLENUM FAN AND MOTOR DATA
UNIT
SIZE
150
170
215
250
305
360
400
500
580
660
800
1000

FAN
SEGMENT
NUMBER1

TYPE

SIZE

1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2

SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI

20
24
27
27
30
30
33
33
36
33
36
36
40
40
44
44
49
49
54
54
60
60
66

MAX.
MOTOR
HP

MAX.
MOTOR
FRAME

FAN INLET
AREA
(sq. ft.)

15
15
15
20
20
20
20
25
25
30
30
40
40
40
40
50
50
60
60
75
75
75
75

215T
254T
254T
256T
256T
256T
256T
256T
256T
286T
286T
324T
324T
324T
324T
326T
326T
364T
364T
365T
365T
365T
365T

2.16
3.21
3.60
3.60
4.72
4.72
5.82
5.82
7.05
5.82
7.05
7.05
8.62
8.62
10.47
10.47
12.80
12.80
15.54
15.54
19.02
19.02
22.87

1. Fan Segment Numbers (1) and (2) refer to segment lengths which vary in size depending on the fan
selected within a given AP unit size.
2. Plenum fan performance is not within the scope of ARI Certification.

YORK INTERNATIONAL

17

Engineering Data Fans


VARIABLE INLET VANES OPERATING TORQUES (in. lbs.)
FORWARD CURVED

FAN SIZES (IN.)


RPM

Shaded area indicates


an area where the RPM
is below minimum or
exceed the Class II limits.

12 x 12

300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100

15 x 15
15 x 11

35
35
38
43
49
55
63
70
78
85
90

35
35
35
35
42
45
50
55
61
68
73
78
83

35
35
35
35
35
38
43
45
50
52
58
60
65
69

18 x 18

20 x 20

35
44
53
64
75
85
95
108
120
133

22 x 22
35
40
48
60
72
83
95
108
120

25 x 25
40
48
61
75
90
108
125
137

27 x 27

30 x 30

37
45
71
88
110
135
160
189

48
73
100
133
165
200
225

AIRFOIL FAN (DWDI)


RPM
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700

18

12
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
22
24
26
28
31
33
36
38
41
44
47
49
53
56
59
62
66
69
73
76
88

15
20
20
20
20
20
20
20
20
20
20
20
20
20
20
22
25
28
31
34
37
40
43
47
50
54
58
62
67
71
75

18
20
20
20
20
20
20
20
20
22
25
29
34
38
43
49
54
60
66
73
79
86
94
101
109
118
126

20
20
20
20
20
20
20
22
26
32
37
43
49
56
63
71
79
88
97
106
116
126
137
148

22
20
20
20
20
21
27
33
40
48
56
65
75
85
96
108
120
133
147
161
176
191

FAN SIZES (IN.)


25
28
20
20
20
20
20
26
24
36
32
47
40
59
49
73
60
88
71
105
83
123
97
142
111
164
126
186
142
210
160
236
178
197

32
26
41
58
79
104
131
162
196
234
274
318
365
415
469

36
39
61
87
119
155
197
243
294
350
410
476
546

40
57
89
129
175
229
289
357
432
514

44
86
134
193
263
343
435
536
649
772
907
1051

YORK INTERNATIONAL

FORM 100.09-EG1

VARIABLE INLET VANES OPERATING TORQUES (in. lbs.)

SWSI PLENUM FAN


RPM

FAN SIZE (in.)


20

22

24

27

30

33

36

40

44

49

54

60

66

400

20

20

20

20

20

20

20

26

39

57

84

128

188

500

20

20

20

20

20

20

27

40

61

89

132

201

294

600

20

20

20

20

20

26

40

58

87

129

190

289

423

700

20

20

20

20

25

36

54

79

119

175

258

393

576

800

20

20

20

21

32

47

70

103

155

228

337

514

752

900

20

20

20

27

41

59

89

131

197

289

426

650

952

1000

20

20

22

33

50

73

110

162

243

357

527

802

637

1100

20

20

27

40

61

89

133

196

294

432

1200

20

22

32

47

72

106

158

233

350

514

1300

20

25

38

56

85

124

186

273

410

1400

20

29

44

64

98

144

215

317

476

1500

22

34

50

74

113

165

247

364

1600

25

39

57

84

128

188

281

1700

29

43

64

95

145

212

318

1800

32

49

72

107

163

238

1900

36

54

81

119

181

265

2000

40

60

89

132

201

2100

44

66

98

145

221

2200

48

73

108

159

243

2300

52

80

118

174

2400

57

87

129

190

2500

62

94

139

2600

67

102

151

2700

72

110

2800

78

118

2900

83

126

3000

89

135

3100

95

3200

101

3300
3400
3500
3600
3700
3800
3900
4000
4100
4200

Shaded area indicates an area where the fan


exceeds the Class II limits.

YORK INTERNATIONAL

19

Engineering Data Coils


COIL DATA

UNIT
SIZE

FREE FLOW COILS


1/2" DIA. TUBES

BDW

Full Face
Reduced Face
(Quantity) Area 1(Quantity) Area
(sq.ft.) FH x FL (sq.ft.)
FH x FL

35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

(1)
20.0 x 23.0
(1)
27.5 x 29.0
(1)
27.5 x 40.0
(1)
30.0 x 48.0
(1)
30.0 x 57.0
(1)
30.0 x 70.0
(1)
32.5 x 73.0
(1)
37.5 x 78.0
(1)
45.0 x 78.0
(1)
47.5 x 90.0
(2)
57.5 x 90.0
(2)
57.5 x 100.0
(2)
65.0 x 112.0
(2)
75.0 x 112.0
(2)
75.0 x 126.0
(2)
92.5 x 126.0
(3)
107.5 x 133.0

3.2
5.5
7.6
10.0
11.9
14.6
16.5
20.3
24.4
29.7
35.9
39.9
50.6
58.3
65.6
80.9
99.3

(1)

2.4

15.0 x 23.0
(1)

4.0

20.0 x 29.0
(1)

5.6

20.0 x 40.0
(1)

7.5

22.5 x 48.0
(1)

8.9

22.5 x 57.0
(1)
22.5 x 70.0
(1)
25.0 x 73.0
(1)
27.5 x 78.0
(1)
32.5 x 78.0
(1)
35.0 x 90.0
(1)
42.5 x 90.0
(1)
42.5 x 100.0
(1)
47.5 x 112.0
(2)
57.5 x 112.0
(2)
57.5 x 126.0
(2)
67.5 x 126.0
(2)
80.0 x 133.0

10.9
12.7
14.9
17.6
21.9
26.6
29.5
36.9
44.7
50.3
59.1
73.9

TURBOFIN COILS
5/8" DIA. TUBES

CDW

Full Face
Reduced Face
(Quantity) Area 1(Quantity) Area
FH x FL
(sq.ft.) FH x FL (sq.ft.)

(1)
21.25 x 23.0
(1)
27.25 x 29.0
(1)
21.25 x 40.0
(1)
30.25 x 48.0
(1)
30.25 x 57.0
(1)
30.25 x 70.0
(1)
33.25 x 73.0
(1)
39.25 x 78.0
(1)
45.25 x 78.0
(1)
48.25 x 90.0
(2)
57.5 x 90.0
(2)
57.5 x 100.0
(2)
63.5 x 112.0
(2)
75.5 x 112.0
(2)
75.5 x 126.0
(2)
90.5 x 126.0
(3)
108.75 x 133.0

3.4
5.5
7.6
10.1
12.0
14.7
16.9
21.3
24.5
30.2
35.9
39.9
49.4
58.7
66.1
79.2
100.4

(1)
15.25 x 23.0
(1)
21.25 x 29.0
(1)
21.25 x 40.0
(1)
21.25 x 48.0
(1)
21.25 x 57.0
(1)
21.25 x 70.0
(1)
24.25 x 73.0
(1)
27.25 x 78.0
(1)
33.25 x 78.0
(1)
36.25 x 90.0
(1)
42.25 x 90.0
(1)
42.25 x 100.0
(1)
48.25 x 112.0
(2)
57.5 x 112.0
(2)
57.5 x 126.0
(2)
66.5 x 126.0
(2)
81.5 x 133.0

2.4
4.3
5.9
7.1
8.4
10.3
12.3
14.8
18.0
22.7
26.4
29.3
37.5
44.7
50.3
58.2
75.3

SDC

NON-FREEZE COILS
1" DIA. TUBES (SDC TYPES)

Full Face
(Quantity) Area1
FH x FL
(sq.ft.)

(1)
21.0 x 23.0
(1)
27.0 x 29.0
(1)
27.0 x 40.0
(1)
30.0 x 48.0
(1)
30.0 x 57.0
(1)
30.0 x 70.0
(1)
33.0 x 73.0
(1)
39.0 x 78.0
(1)
45.0 x 78.0
(1)
48.0 x 90.0
(2)
57.0 x 90.0
(2)
57.0 x 100.0
(2)
63.0 x 112.0
(2)
75.0 x 112.0
(2)
75.0 x 126.0
(2)
90.0 x 126.0
(3)
108.0 x 133.0

3.4
5.4
7.5
10.0
11.9
14.6
16.7
21.1
24.4
30.0
35.6
39.6
49.0
58.3
65.6
78.8
99.8

Reduced Face
(Quantity) Area
FH x FL (sq.ft.)
(1)
15.0 x 23.0
(1)
21.0 x 29.0
(1)
21.0 x 40.0
(1)
21.0 x 48.0
(1)
21.0 x 57.0
(1)
21.0 x 70.0
(1)
24.0 x 73.0
(1)
27.0 x 78.0
(1)
33.0 x 78.0
(1)
36.0 x 90.0
(1)
42.0 x 90.0
(1)
42.0 x 100.0
(1)
48.0 x 112.0
(2)
57.0 x 112.0
(2)
57.0 x 126.0
(2)
66.0 x 126.0
(2)
81.0 x 133.0

2.4
4.2
5.8
7.0
8.3
10.2
12.2
14.6
17.8
22.5
26.3
29.2
37.3
44.3
49.9
57.8
74.8

NOTE: 1. (Quantity) = Connections per Unit


(1) = 1 set of connections (1 supply, 1 return)
(2) = 2 set of connections (2 supply, 2 return)
(3) = 3 set of connections (3 supply, 3 return)

FH x FL = Finned Height (Inches) x Finned Length (Inches)

20

YORK INTERNATIONAL

FORM 100.09-EG1

MULTI-ZONE HOT DECK COIL DATA

NOTES:

FREE FLOW COILS


1/2" DIA. TUBES

BDW

UNIT
SIZE

CDW

TURBOFIN COILS
5/8" DIA. TUBES

SDC

NON-FREEZE COILS
1" DIA. TUBES

Quantity
FH x FL

Area
(sq. ft.)

Quantity
FH x FL

Area
(sq. ft.)

Quantity
FH x FL

Area
(sq. ft.)

60

12.5 x 29

2.5

12.25 x 29

2.5

12 x 29

2.4

80

12.5 x 40

3.5

12.25 x 40

3.4

12 x 40

3.3

105

15 x 48

5.0

15.25 x 48

5.1

15 x 48

5.0

120

15 x 57

5.9

15.25 x 57

6.0

15 x 57

5.9

150

15 x 70

7.3

15.25 x 70

7.4

15 x 70

7.3

170

15 x 73

7.6

15.25 x 73

7.7

15 x 73

7.6

215

17.5 x 78

9.5

18.25 x 78

9.9

18 x 78

9.8

250

20 x 78

10.8

21.25 x 78

11.5

21 x 78

11.8

305

22.5 x 90

14.1

21.25 x 90

13.6

21 x 90

13.1

360

27.5 x 90

17.2

27.25 x 90

17.0

27 x 90

16.9

400

27.5 x 100

19.1

27.25 x 100

18.9

27 x 100

18.8

500

27.5 X 112

21.4

27.25 X 112

21.2

27 X 112

21.0

1. All coils have one set of connections (1 supply, 1 return).


2. FH x FL = Finned Height (inches) x Finned Length (inches)

INTEGRAL FACE & BYPASS COILS


UNIT
SIZE

NOTES:

YORK INTERNATIONAL

INTEGRAL FACE & BYPASS COILS


MAXIMUM
CFM

OUTLET
AREA

L.J. WING
MODEL

35

N/A

N/A

N/A

60

N/A

N/A

N/A

80

N/A

N/A

N/A

105

5,632

7.04

IFB - B - 36

120

6,176

7.72

IFB - B - 42

150

9,264

11.58

IFB - B - 60

170

12,384

15.48

IFB - C - 60

215

12,384

15.48

IFB - C - 60

250

15,392

19.24

IFB - D - 60

305

15,392

19.24

IFB - D - 60

360

21,600

27.00

IFB - F - 60

400

21,600

27.00

IFB - F - 60

500

28,980

32.20

VIFB - VC - 9

580

36,180

40.20

VIFB - VD - 9

660

44,190

49.10

VIFB - VD - 11

800

57,420

63.80

VIFB - VE - 11

1000

70,830

78.70

VIFB - VF - 11

1. All coil information used with permission of the L.J. Wing Company.
2. IFB coils are available in 2 or 4 row. VIFB coils are available in 1 and 2 rows.
3. All IFB coils have side connections.
4. All VIFB coils have center connections.

21

Engineering Data Filters


FLAT FILTER (FF) AND OPEN RETURN FILTER (OF) SEGMENTS 2" or 4"
FILTER SIZES AND QUANTITIES PER UNIT SIZE

Area (sq. ft.)


12" x 24"
16" x 20"
Filter
16" x 25"
Size
20" x 20"
24" x 20"
24" x 24"

35

60

80

105

120

150

UNIT SIZE
170 215 250

305

360

400

500

580

660

800

4.0

6.0
1

8.0

11.1

13.3

16.7

17.8

32.0

40.0

41.7

50.0

60.0

66.0
3

82.7 108.8
3

6
4

22.2

24.0

8
6
8

15
12

1000

15
15

15

5
15

14
21

NOTES: 1. See the filter configurations below for specific filter arrangements.
2. Flat filters are side-loaded.
3. Open return filters are front-loaded.

LD04351

22

YORK INTERNATIONAL

FORM 100.09-EG1

ANGLE FILTER (AF), FILTER/MIXING BOX (FM) SEGMENTS, ECONOMIZER/FILTER SEGMENT (EF), 2" or 4"
FILTER SIZES AND QUANTITIES PER UNIT SIZE

Area (sq. ft.)

Filter
Size

12" x 24"
16" x 20"
16" x 25"
20" x 20"
20" x 24"
20" x 25"
24" x 24"

35

60

80

105

120

150

UNIT SIZE
170 215 250

305

360

400

500

580

660

4.4

8.9

11.1

15.6

16.7

21.1

22.2

35.6

42.2

50.0

55.6

66.7

80.0

88.0 133.3 140.0

16

4
12

29.2

800

1000

4
2

2
8

24

48
42

16
20

20

NOTES: 1. See the filter configurations below for specific filter arrangements.
2. Angle and filter / mixing box filters are side-loading.

LD04352

YORK INTERNATIONAL

23

Engineering Data Filters


BAG FILTER (BF) AND RIGID FILTER (RF) (WITH 2" or 4" PREFILTERS) SEGMENTS
FILTER SIZES AND QUANTITIES PER UNIT SIZE

Area (sq. ft.)


Filter
Size

12" x 24"
20" x 20"
24" x 20"
24" x 24"

35

60

80

105

120

150

UNIT SIZE
170 215 250

305

360

400

500

580

660

800

4.0

6.0

8.0

12.0

12.3

16.0

17.1

22.2

32.0

40.0

41.7

50.0

60.0

66.0

82.7 108.8

2
3

3
4

2
1

24.0

15

5
15

15

12
6

15
15

1000

14
21

NOTES: 1. Filter sizes are dimensioned width by height (W x H). Example: Filter size 12 x 24 = 12" wide by 24" high filter.
2. See the filter configurations below for specific filter arrangements.
3. Bag, rigid & pre-filter filters are all side-loading.

LD04353

24

YORK INTERNATIONAL

FORM 100.09-EG1

HEPA FILTER (HF) SEGMENTS


FILTER SIZES AND QUANTITIES PER UNIT SIZE

Area (sq. ft.)


Max CFM
24" x 24"
24" x 12"
12" x 24"
15" x 24"
15" x 30"
Filter
24" x 30"
Size
12" x 30"
30" x 24"
30" x 30"
30" x 12"

UNIT SIZE
35
60
80
105 120 150 170 215 250 305 360 400 500 580 660 800 1000
4.0 6.2
7.5
10.0 12.5 15.0 18.0 21.1 26.0 30.0 37.5 40.0 49.8 61.7 68.2 81.3 98.9
2,000 3,125 3,750 5,000 6,250 7,500 9,000 10,563 13,000 15,000 18,750 20,000 24,938 30,875 34,125 40,888 49,500
1
3
2
4
2
2
8
8
12
3

3
2
1
1

1
1

1
3
6

3
2

8
6

4
1
2

1
3

4
1

4
1

8
2

NOTES: 1. See the filter configurations below for specific filter arrangements.
2. HEPA filters are front-loading.
3. All gasketing is located on the HEPA Media. The filter holding frames are
not gasketed.
4. 500 fpm is the maximum face velocity.

LD04353

YORK INTERNATIONAL

25

Engineering Data Filters


CARBON FILTER (CF) SEGMENTS CF1 or CF2
FILTER SIZES AND QUANTITIES PER UNIT SIZE

AREA (sq.ft.)
24" x 24"
24" x 12"

35
16
4

60
24
4
4

80
32
8

105
40
10

120
50
10
5

150
60
15

170
72
18

UNIT SIZE
215 250
305
84
98
128
18
21
32
6
7

360
144
36

400
162
36
9

500
200
50

580
240
60

660
264
60
12

800
330
75
15

1000
432
108

NOTES: 1. See the filter configurations below for specific filter arrangements.
2. Carbon filters are side loading.

LD02513

26

YORK INTERNATIONAL

FORM 100.09-EG1

Engineering Data Dampers


DAMPERS
MIXING BOX (MB) / FILTER MIXING BOX (FM) ECONOMIZER (EE),
ECONOMIZER / FILTER (EF), DAMPER DATA OA/RA/EA

AREA

INDIVIDUAL
DAMPERS
TORQUE (in.lbs.)

COMBINATION
DAMPERS
TORQUE (in. lbs.)

MINIMUM
# OF ACTUATORS
REQUIRED

1.54
2.25
3.07
3.99
4.71
5.74
6.56
7.93
9.08
11.24
13.00
14.49
18.20
20.92
23.43
28.43
35.25

20
20
20
20
20
20
20
24
27
34
39
43
55
63
76
85
105

28
30
31
34
35
37
40
43
49
65
70
78
98
112
126
153
190

1
1
1
1
1
2
2
2
2
2
2
2
3
3
3
3
3

DAMPER ACTUAL DIMENSIONS*

UNIT
SIZE

WIDTH

HEIGHT

35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

15.00
22.00
30.00
39.00
46.00
56.00
64.00
55.00
63.00
78.00
70.00
78.00
98.00
92.00
103.00
125.00
131.00

14.75
14.75
14.75
14.75
14.75
14.75
14.75
20.75
20.75
20.75
26.75
26.75
26.75
32.75
32.75
32.75
38.75

NOTES:

1. Damper openings are 1/8" larger than the actual damper body.
2. Combination torque is for the combination of two dampers.

TORQUE:

1. Torque required to achieve maximum leakage performance.


2. Torques are based on 1 inch wg pressure differential.
3. Damper performance is based on AMCA 500 test setup 5.4/5.5.
4. Maximum damper face velocity is 2000 FPM.

INTERNAL FACE & BYPASS (IB) DAMPER DATA


FACE DAMPER

AREA

FACE & BYPASS


DAMPERS TORQUE
(in.lbs.)

MINIMUM
# OF ACTUATORS
REQUIRED

1.75
2.13
2.81
3.42
3.93
4.75
6.88
8.65
8.65
8.66
10.06
11.12
15.13
17.10
19.15
24.39
31.01

20
20
23
31
36
43
51
57
67
85
101
111
138
160
179
218
272

1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
4
4

BYPASS DAMPER

UNIT
SIZE

WIDTH

HEIGHT

AREA

WIDTH

HEIGHT

35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

28.00
34.00
45.00
54.00
62.00
75.00
78.00
83.00
83.00
95.00
95.00
105.00
117.00
117.29
131.29
131.29
138.29

15.00
21.00
21.00
23.88
23.88
23.88
26.29
27.00
33.00
37.88
44.75
44.75
49.38
57.04
57.04
69.29
81.75

2.92
4.96
6.56
8.95
10.28
12.44
14.24
15.56
19.02
24.99
29.52
32.63
40.12
46.46
52.01
63.17
78.51

28.00
34.00
45.00
54.00
62.00
75.00
78.00
83.00
83.00
95.00
95.00
105.00
117.00
117.29
131.29
131.29
138.29

9.00
9.00
9.00
9.12
9.12
9.12
12.71
15.00
15.00
13.12
15.25
15.25
18.62
21.00
21.00
26.75
32.29

NOTES:

1. Damper openings are 1/8" larger than the actual damper body.
2. The torque data is for the combined face & bypass damper assembly.
3. The face damper is opposed blade, the bypass damper is parallel blade.

TORQUE:

1. Torque required to achieve maximum leakage performance.


2. Torques are based on 1 inch wg pressure differential.
3. Damper performance is based on AMCA 500 test setup 5.4/5.5.
4. Maximum damper face velocity is 2000 FPM.

YORK INTERNATIONAL

27

Engineering Data Dampers


DAMPER DATA
EXTERNAL FACE & BYPASS (EB) DAMPER DATA
UNIT
SIZE
35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000
TORQUE:

WIDTH

HEIGHT

AREA

TORQUE

WIDTH

HEIGHT

AREA

TORQUE

FACE &
BYPASS
DAMPERS
TORQUE

28.0
34.0
45.0
54.0
62.0
75.0
78.0
83.0
83.0
95.0
95.0
105.0
117.0
117.0
131.0
131.0
138.0

24.0
24.0
30.0
33.0
33.0
33.0
39.0
42.0
48.0
51.0
60.0
60.0
68.0
78.0
78.0
96.0
114.0

4.67
5.67
9.38
12.38
14.21
17.19
21.13
24.21
27.67
33.65
39.58
43.75
55.25
63.38
70.96
87.33
109.25

20
21
28
37
43
52
63
73
83
102
118
131
165
190
213
263
327

15.0
22.0
30.0
39.0
46.0
56.0
64.0
55.0
63.0
78.0
70.0
78.0
98.0
92.0
103.0
125.0
131.0

14.8
14.8
14.8
14.8
14.8
14.8
14.8
20.8
20.8
20.8
26.8
26.8
26.8
32.8
32.8
32.8
38.8

1.54
2.25
3.07
3.99
4.71
5.74
6.56
7.93
9.08
11.24
13.00
14.49
18.20
20.92
23.43
28.43
35.25

20
20
20
20
20
20
20
24
27
34
39
43
55
63
76
85
105

28
30
35
42
48
58
73
83
94
115
134
147
187
215
241
296
396

FACE DAMPER

BYPASS DAMPER

MINIMUM
# OF
ACTUATORS
REQUIRED
1
1
1
2
2
2
2
2
2
3
3
3
4
4
5
5
5

1. Torque required to achieve optimum leakage performance.


2. Torques are based on 1 inch wg pressure differential.
3. Damper performance is based on AMCA 500 test setup 5.4/5.5.
4. Maximum damper face velocity is 2000 FPM.

FACE (FD) DAMPER DATA


UNIT
SIZE

WIDTH

HEIGHT

AREA

TORQUE

MINIMUM
# OF ACTUATORS
REQUIRED

35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

28.0
34.0
45.0
54.0
62.0
75.0
78.0
83.0
83.0
95.0
95.0
105.0
117.0
117.0
131.0
131.0
138.0

24.0
24.0
30.0
33.0
33.0
33.0
39.0
42.0
48.0
51.0
60.0
60.0
68.0
78.0
78.0
96.0
114.0

4.67
5.67
9.38
12.38
14.21
17.19
21.13
24.21
27.67
33.65
39.58
43.75
55.25
63.38
70.96
87.33
109.25

20
21
28
37
43
52
63
73
83
102
118
131
165
190
213
263
327

1
1
1
2
2
2
2
2
2
3
3
3
4
4
5
5
5

TORQUE:

28

FACE DAMPER

1. Torque required to achieve optimum leakage performance.


2. Torques are based on 1 inch wg pressure differential.
3. Damper performance is based on AMCA 500 test setup 5.4/5.5.
4. Maximum damper face velocity is 2000 FPM.

YORK INTERNATIONAL

FORM 100.09-EG1

DAMPER DATA
DAMPER LEAKAGE DATA
LOW LEAK
UNIT
SIZE

ULTRA LOW LEAK

LEAKAGE (cfm. / sq. ft.)


@ 1" WG

@ 4" WG

@ 1" WG

@ 4" WG

35

7.2

14.5

3.7

8.0

60

7.2

14.5

3.7

8.0

80

7.2

14.5

3.7

8.0

105

7.2

14.5

3.7

8.0

120

7.2

14.5

3.7

8.0

150

7.2

14.5

3.7

8.0

170

7.2

14.5

3.7

8.0

215

7.2

14.5

3.7

8.0

250

7.2

14.5

3.7

8.0

305

7.2

14.5

3.7

8.0

360

7.2

14.5

3.7

8.0

400

7.2

14.5

3.7

8.0

500

7.2

14.5

3.7

8.0

580

7.2

14.5

3.7

8.0

660

7.2

14.5

3.7

8.0

800

7.2

14.5

3.7

8.0

1000

7.2

14.5

3.7

8.0

NOTE: Damper performance is based on AMCA 500 test setup 5.4/5.5.

BLENDER DATA

UNIT SIZE

VENDOR
MODEL*

QUANTITY

TOTAL BLENDER
AREA
(sq. ft.)

35

H - 16

1.45

60

H - 20

2.28

80

H - 24

3.29

105

H - 26

3.85

120

H - 20

4.56

150

H - 22

5.52

170

H - 24

6.58

215

H - 26

7.72

250

H - 24

9.87

305

H - 26

11.58

360

H - 28

13.44

400

H - 30

15.42

500

H - 34

19.80

580

H - 36

20.20

660

H - 38

24.75

800

H - 42

30.24

1000

H - 44

33.18

*Model numbers are used with the permission of Blender Products Inc.
*Air Blender is a registered trademark of Blender Products Inc.

YORK INTERNATIONAL

29

Engineering Data Dampers


DAMPER DATA
MULTI-ZONE (MZ)

NOTES:

30

TOTAL DAMPER ACTUAL DIMENSIONS

UNIT
SIZE

QUANTITY
OF ZONES

WIDTH

HEIGHT

AREA

COMBINATION
DAMPER TORQUE (in.lbs)

60

35.5

9.0

2.2

120

80

46.5

9.0

2.9

168

105

55.5

9.0

3.5

192

120

10

63.5

9.0

4.0

240

150

12

76.5

9.0

4.8

288

170

12

79.5

9.0

5.0

288

215

13

84.5

11.0

6.5

312

250

13

84.5

12.0

7.0

312

305

15

96.5

12.0

8.0

360

360

15

96.5

15.0

10.1

360

400

17

106.5

15.0

11.1

408

500

19

118.5

16.0

13.2

456

1. Torque required to achieve maximum leakage performance.


2. Torques are based on 1 inch wg pressure differential.
3. Damper performance is based on AMCA 500 test setup 5.4/5.5.
4. See page 73 for actual damper locations.
5. Maximum damper face velocity is 2000 FPM.

YORK INTERNATIONAL

FORM 100.09-EG1

SOUND ATTENUATOR

LD02500

ATTENUATOR AREAS
35

60

80

105

120

150

170

215

Area (sq. ft.) 4.0

4.0

5.0

7.5

7.5

10.0

12.0

15.0

UNIT SIZE
250
305
15.0

21.0

360

400

500

580

660

800

1000

24.0

24.0

30.0

35.0

40.0

48.0

63.0

DYNAMIC INSERTION LOSS RATING


ATTENUATOR
LENGTH

ATTENUATOR
TYPE

DYNAMIC INSERTION LOSS (dB)

FACE
VEL. (FPM)

FLOW

1000
1000
1000
1000
1000
1000

FORWARD
REVERSE
FORWARD
REVERSE
FORWARD
REVERSE

7
7
8
11
10
12

12
13
18
21
20
23

16
17
24
25
35
37

28
30
40
43
45
46

35
36
45
47
50
51

35
33
46
44
48
48

28
26
41
39
45
44

17
13
26
22
34
30

STANDARD

STANDARD

STANDARD

LOW
FREQUENCY

1000
1000

FORWARD
REVERSE

10
9

13
14

23
24

27
27

26
25

22
19

17
16

14
14

LOW
FREQUENCY

1000
1000

FORWARD
REVERSE

13
16

19
21

31
35

36
41

39
41

27
28

22
21

16
15

LOW
FREQUENCY

1000
1000

FORWARD
REVERSE

13
16

24
26

40
44

48
49

49
50

37
35

29
25

19
17

HOSPITAL /
CLEAN ROOM

1000
1000

FORWARD
REVERSE

7
7

9
11

14
17

19
22

22
25

28
30

30
30

13
13

HOSPITAL /
CLEAN ROOM

1000
1000

FORWARD
REVERSE

9
10

13
15

19
22

26
30

35
40

44
46

35
35

15
16

HOSPITAL /
CLEAN ROOM

1000
1000

FORWARD
REVERSE

12
15

14
18

23
27

36
40

50
50

51
51

38
38

17
17

SELF-NOISE POWER LEVELS


ATTENUATOR
TYPE

FACE
VEL. (FPM)

FLOW

STANDARD

1000
1000

LOW
FREQUENCY
HOSPITAL /
CLEAN ROOM
YORK INTERNATIONAL

DYNAMIC INSERTION LOSS (dB)


1

FORWARD
REVERSE

55
54

49
51

49
50

47
51

46
54

49
56

42
52

32
40

1000
1000

FORWARD
REVERSE

46
45

42
42

45
45

43
43

45
45

49
49

44
44

37
37

1000
1000

FORWARD
REVERSE

55
54

49
51

49
50

47
51

46
54

49
56

42
52

32
40

31

Engineering Data
CARBON FILTER SEGMENT DESIGN & PERFORMANCE DATA

VOC (TOLUENE)
EFFICIENCY %

CARBON
WEIGHT

CARBON
MEDIA

OZONE
EFFICIENCY

(Lbs)

(ft 3)

INITIAL

AVERAGE

35

48

2.67

80

71

50

60

72

4.00

80

71

50

80

96

5.33

80

71

50

105

120

6.67

80

71

50

120

150

8.33

80

71

50

150

180

10.00

80

71

50

170

216

12.00

80

71

50

215

252

14.00

80

71

50

250

294

16.33

80

71

50

305

384

21.33

80

71

50

360

432

24.00

80

71

50

400

486

27.00

80

71

50

500

600

33.33

80

71

50

580

720

40.00

80

71

50

660

792

44.00

80

71

50

800

990

55.00

80

71

50

1000

1296

72.00

80

71

50

UNIT
SIZE

NOTES:
1. Standard media will be 60% CTC Virgin activated carbon.
2. Standard media will absorb VOC (organic solvents and hydrocarbons), ozone, chlorine, ambient levels of sulfur
dioxide, and nitrogen dioxide.
3. Carbon panels filled with IVP (Improved Vapor Phase) are available as a SQ.
4. Carbon Media Volume (Cu.Ft.) is based on nominal carbon panel dimensions.
5. Carbon Weight is the nominal weight of the carbon in the tray.
6. Filter weight is the weight of the filter tray with carbon.
7. Ozone and VOC (Toluene) Efficiency is based on single pass and not indicative of total removal during recirculation.
8. The efficiency is based on design media velocities listed in above table. While higher velocities reduce the efficiency
and service life, lower than design velocities will increase the efficiency.
9. The average VOC efficiency is the time-averaged (arithmetic) efficiency based on 50% saturation service life.
10. Ozone efficiency is constant with service time.
11. All performance data listed above is based upon 500 FPM design face velocity across the coil.
12. The design is based on a minimum residence time of 0.08 seconds with a resulting contact efficiency of 99.6%
13. Contact efficiency is the percent of total contaminant molecules which have come in contact with the media.
14. Removal efficiency is that fraction of the contaminant molecules which, once in contact with the media, are removed
by either physical or chemical means.

32

YORK INTERNATIONAL

FORM 100.09-EG1

ELECTRIC HEATER DESIGN & PERFORMANCE DATA (OPEN COIL TYPE ELEMENTS)

AirPak
SIZE

HEATER OPEN
AREA

MAX
KW

35

2.2

46

60

3.3

78

80

4.6

106

105

5.7

149

120

6.7

180

150

8.3

219

170

9.5

252

215

12.1

315

250

14.0

361

305

17.9

435

360

22.8

485

400

25.4

538

500

32.7

673

580

40.3

742

660

45.4

831

800

59.3

957

1000

77.4

1160

NOTES:
1. The maximum kW ratings are at design CFM conditions
only and applications at lower than design CFM will
result in lower ratings.
2. The minimum velocity for each heater of a certain kW
is to be calculated from the minimum velocity vs. kW/
sq.ft curves.
3. Delta T =

kW x 3160
CFM

MINIMUM AIR VELOCITY FOR OPEN COIL TYPE HEATERS

28 KW/FT2 MAXIMUM

LD02453

YORK INTERNATIONAL

33

Unit Selection
SELECTING AN AIRPAK AIR HANDLING UNIT
AirPak air handlers permit selection of components to
meet individual job requirements. The wide selection of
basic sections, optional components, coils, and accessories, enables the design engineer to obtain optimum
performance and temperature control.
Selection of the optimum system for each individual application requires only the following simple steps:
Step 1 Step 2 Step 3 Step 4 -

Determination of Total Air Supply Quantity.


Selection of Basic Unit Size and Arrangement.
Selection of Cooling and/or Heating Coils.
Selection of Accessories (filters, mixing boxes,
dampers, etc.).
Step 5 - Selection of Fan, Motor and Drive.
STEP 1
TOTAL AIR SUPPLY QUANTITY
The total air supply quantity will be determined by the
largest of:
a. Ventilation, make-up or pressurization requirement
b. Cooling load (most frequent for air conditioning)
c. Heating load (for heating only)
d. Contaminant or odor removal
Ventilation requirements may be dictated by the local
code or ordinance, or established through the use of recommendations in the ASHRAE Guide. Make-up air should
at least equal total exhaust from the space, plus allowance for pressurization to minimize infiltration.
For comfort air conditioning, the total air supply quantity
will usually be determined by the simultaneous peak cooling load - calculated by established methods published
in the ASHRAE Guide. The required air supply may be
determined by the formula:
CFM =

Sensible Space Cooling (or Heating) Load (BTU/HR)


1.08 x (Entering dry Bulb F Leaving dry Bulb F)

Depending on available cooling medium, air distribution


considerations, and humidity control requirements, the
Cooling Temperature Differential is usually in the 15F to
25F range.
Since Heating Temperature Differentials are frequently
much higher, the air quantity required for heating is usually less than for cooling. For projects requiring heating
only, the heating load may be the controlling factor. Heat
losses in long duct runs must be considered.

STEP 2
BASIC UNIT SIZE AND ARRANGEMENT
With a selection of five different fans for most units, the
basic unit size may be selected on the basis of coil face
area.
AirPak units for cooling and dehumidification service must
hold the coil face velocity below the point of moisture
carry-over. The usual limit is 600 FPM. For lower life cycle
costs, 350-400 FPM velocity is recommended. For a VAV
system at minimum part load conditions, it is recommended that coil face velocity not be allowed to fall below
200 FPM for a water coil and 400 FPM for a refrigerant
coil. Use the next larger unit size if the approximate face
area falls between that of two units.
Refer to the Table on page 20 (Coil Data) for actual face
areas.
Approximate
=
Face Area

Total CFM
Desired Face Velocity

For heating and ventilation service, or for units involving


only sensible cooling, face velocity is limited only by the
high internal air pressure drop and resultant higher sound
level of higher air flows. Selections are typically made in
the 800 to 1000 FPM face velocity range. The following
formula may be used:
Unit arrangement will be determined by system requirements and space considerations.
STEP 3
COOLING AND HEATING COILS
Approximate
=
Face Area

Total CFM
Desired Face Velocity

Cooling and Heating loads may be determined by established methods as published in the ASHRAE Guide. Available media will determine whether coils will be selected
for hot water, chilled water, steam, refrigerant or glycol.
With loads determined and the medium selected, the
coil rows, fins, and circuiting can be selected from the
appropriate Engineering Guides on YORK TURBOFIN and
FREEFLOW coils or by a YORK Sales Engineer with
YorkWorks. Coil sizes and face areas for each unit size
are shown in the Engineering Data Section.
Internal face and bypass coil selection may be determined using reduced face coils.

Humidity control, contaminant removal, or odor control


will occasionally effect total air quantity.

34

YORK INTERNATIONAL

FORM 100.09-EG1

STEP 4
ACCESSORIES

to the internal resistance to obtain total static pressure


for fan selection.

A wide range of accessories are available to tailor the


YORK AirPak to specific system requirements. Included
in the Accessories are: face and bypass dampers, mixing dampers, flat or angle filters, rigid or bag filters, air
blenders, economizers, diffusers, discharges, access
segments, etc.
STEP 5
FANS, MOTORS AND DRIVES
Total air system resistance must be determined for fan
selection. Internal air flow resistance of the unit accessories can be determined from Tables on pages 38-45.
Add the external system resistance (ref. ASHRAE Guide)

The nominal ranges of Total Static Pressure (TSP) for the


available fan types are: up to 6" for FC, 9" for AF and up
to 6.25" for SWSI fans. Casing limitations are 6" w.g.
Fan RPM and BHP is determined from fan performance
curves and tables using unit size, fan type, CFM and
TSP. Correct fan RPM and BHP, if necessary, for air temperature and altitude, using factors given on page 35.
Fan tables and curves do not include drive losses.
Refer to Form 100.09-EG1.1 (Forward Curved and Airfoil
Fan Curves and Tables) for individual AirPak units.

REFERENCE LITERATURE
FAN PERFORMANCE ............................................................................................................ FORM 100.09-EG1.1
COOLING AND HEATING COILS
DRAINABLE WATER (DW) AND DIRECT EXPANSION (DX) 5/8" O.D. TUBES ................... FORM 105.17-EG1
DRAINABLE WATER (DW) DIRECT EXPANSION (DX) 1/2" O.D. TUBES ........................... FORM 105.18-EG1
NON-FREEZE STEAM COILS (SDC) 1" O.D. TUBES ......................................................... FORM 105.26-EG2
FACTORY-PACKAGED CONTROLS ................................................................................... FORM 450.11-EG1
AIR-MODULATOR ............................................................................................................... FORM 100.40-EG1

ALTITUDE / TEMPERATURE CONVERSION FACTORS


ALTITUDE (FEET)

AIR
TEMP F

1000

2000

3000

4000

5000

-20

1.20

1.16

1.12

1.08

1.04

1.00

.97

.93

.89

1.15

1.10

1.06

1.02

.99

.95

.92

.88

.85

20

1.11

1.06

1.02

.98

.95

.92

.88

.85

.82

40

1.06

1.02

.98

.94

.91

.88

.84

.81

.78

60

1.02

.98

.94

.91

.88

.85

.81

.79

.76

70

1.00

.96

.93

.89

.86

.83

.80

.77

.74

80

.98

.94

.91

.88

.84

.81

.78

.72

.72

100

.94

.91

.88

.84

.81

.78

.75

.70

.70

120

.92

.88

.85

.81

.78

.76

.72

.68

.67

140

.89

.85

.82

.79

.76

.73

.70

.68

.65

160

.85

.82

.79

.76

.74

.70

.68

.65

.63

200

.80

.77

.75

.72

.69

.67

.64

.62

.60

250

.75

.72

.69

.67

.65

.62

.60

.58

.56

YORK INTERNATIONAL

6000

7000

8000

35

Air Pressure Drop


INSTRUCTIONS FOR USING AIR PRESSURE DROP TABLES
The air pressure drop Tables on pages 38-45 are to be
used to determine the unit internal resistance. The internal resistance, along with the supply duct pressure drops,
return duct pressure drops and external static pressures
should be used to select supply, return and/or exhaust

fans from the fan performance curves and tables, Form


100.09-EG1.1 and 100.09-EG1.2. The Engineering Data
tables, (pages 16-33) provide the necessary data (face
areas) to develop the face velocity required to use the
appropriate air pressure drop tables.

STATIC PRESSURE SCHEMATICS


ECONOMIZER WITH RETURN AIR FAN

LD00011(09)

Supply Air Fan Total Static Pressure (TSP)


External Static Pressure (ESP - given)
Final Filters (BF, RF, HF)
Prefilters (BF, RF)
Diffuser (DI)
Reheat Coil (HC, MC, LC, XC)
Cooling Coil (SC, MC, LC, XC)
Preheat Coil (HC, MC, LC, XC, IC)
Face & Bypass (IB, EB)
High Efficiency Filters (BF, RF)
Prefilters (OF, FF, AF, FM)
Blender (AB)
Outside Air Damper (FM, MB, EE)
Supply Air Fan (TSP)

________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________

Return Air Fan Total Static Pressure (TSP):


External Static Pressure (RETURN ESP - given)
Exhaust Air Damper (EE)

________________
________________

Return Air Fan (TSP)

________________

________________

ECONOMIZER WITH EXHAUST AIR FAN

Supply Fan Total Static Pressure (TSP)


External Static Pressure (ESP - given)
Final Filters (BF, RF, HF)
Prefilters (BF, RF)
Diffuser (DI)
Reheat Coil (HC, MC, LC, XC)
Cooling Coil (SC, MC, LC, XC)
Preheat Coil (HC, MC, LC, XC, IC)
Face & Bypass (IB, EB)
High Efficiency Filters (BF, RF)
Prefilters (OF, FF, AF, FM)
Blender (AB)
Outside Air Damper (FM, MB, EE)
Supply Fan (TSP)

36

________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________

LD00012(09)

Exhaust Fan Total Static Pressure (TSP):


External Static Pressure (RETURN ESP - given)
Exhaust Air Damper (EE)
Exhaust Fan (TSP)

________________
________________
________________
YORK INTERNATIONAL

FORM 100.09-EG1

STATIC PRESSURE SCHEMATICS (Contd.)


EE - ECONOMIZER WITHOUT RETURN AIR FAN

LD00013(09)

Supply Fan Total Static Pressure (TSP)


External Static Pressure (ESP - given)
Final Filters (BF, RF, HF)
Prefilters (BF, RF)
Diffuser (DI)
Reheat Coil (HC, MC, LC, XC)
Cooling Coil (SC, MC, LC, XC)
Preheat Coil (HC, MC, LC, XC, IC)
Face & Bypass (IB, EB)
High Efficiency Filters (BF, RF)
Prefilters (OF, FF, AF, FM)
Blender (AB)
Outside Air (OA)
Supply Fan (TSP)

________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________

EE - ECONOMIZER WITH HORIZONTAL SWSI RETURN AIR FAN

LD00014(09)

Supply Fan Total Static Pressure (TSP)


External Static Pressure (ESP - given)
High Efficiency Filters (BF, RF, HF)
Prefilters (OF, FF, AF, FM)
Reheat Coil (HC, MC, LC, XC)
Cooling Coil (SC, MC, LC, XC)
Preheat Coil (HC, MC, LC, XC, IC)
High Efficiency Filters (BF, RF)
Prefilters (OF, FF, AF, FM)
Blender (AB)
Return Air (Damper) (RA)
Other Components
Supply Fan (TSP)
YORK INTERNATIONAL

________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________
________________

Return Fan Total Static Pressure (TSP):


External Static Pressure - Return Air
Exhaust Air Damper
Return Fan (TSP)

________________
________________
________________

37

Air Pressure Drop Coils


TURBOFIN CDW OR CDX FOR COOLING AND DEHUMIDIFYING (5/8") APD (in. wg.)
WET COIL
ROWS

10

12

For Standard Air


FIN NO.
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14

400
0.35
0.40
0.45
0.50
0.44
0.50
0.57
0.64
0.53
0.60
0.68
0.76
0.70
0.80
0.91
1.02
0.87
0.99
1.12
1.25
1.05
1.19
1.35
1.51

425
0.38
0.44
0.50
0.56
0.48
0.55
0.62
0.69
0.58
0.66
0.75
0.84
0.77
0.88
1.00
1.12
0.95
1.09
1.24
1.39
1.14
1.30
1.48
1.66

450
0.42
0.48
0.55
0.62
0.62
0.60
0.68
0.76
0.63
0.72
0.82
0.92
0.83
0.95
1.09
1.23
1.04
1.18
1.35
1.52
1.24
1.42
1.62
1.82

AIR VELOCITY (FPM)


475
0.42
0.52
0.59
0.66
0.56
0.65
0.74
0.83
0.68
0.78
0.89
1.00
0.90
1.03
1.19
1.35
1.12
1.28
1.47
1.66
1.34
1.54
1.77
2.00

500
0.48
0.56
0.64
0.72
0.61
0.70
0.80
0.90
0.73
0.84
0.97
1.10
0.97
1.12
1.29
1.46
1.20
1.39
1.60
1.81
1.44
1.66
1.91
2.16

525
0.52
0.60
0.70
0.80
0.65
0.75
0.87
0.99
0.78
0.90
1.04
1.18
1.04
1.20
1.39
1.58
1.29
1.49
1.72
1.95
1.55
1.79
2.07
2.35

550
0.56
0.64
0.75
0.86
0.69
0.81
0.94
1.07
0.83
0.97
1.12
1.27
1.11
1.29
1.50
1.71
1.38
1.60
1.86
2.12
1.65
1.92
2.23
2.54

TURBOFIN CDW FOR HEATING & CDW OR CDX FOR SENSIBLE COOLING (5/8") APD (in. wg.)
DRY COIL
ROWS

10

12

38

For Standard Air


FIN NO.
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14

400
0.07
0.08
0.09
0.10
0.14
0.16
0.18
0.21
0.24
0.27
0.30
0.28
0.32
0.36
0.40
0.35
0.40
0.45
0.50
0.43
0.48
0.54
0.60
0.57
0.64
0.72
0.80
0.71
0.80
0.90
1.00
0.85
0.96
1.08
1.20

450
0.09
0.10
0.11
0.12
0.17
0.20
0.22
0.24
0.26
0.29
0.33
0.37
0.35
0.39
0.44
0.49
0.43
0.49
0.55
0.61
0.52
0.59
0.66
0.73
0.69
0.78
0.88
0.98
0.87
0.98
1.10
1.22
1.04
1.17
1.32
1.47

500
0.10
0.12
0.13
0.14
0.21
0.23
0.26
0.29
0.31
0.35
0.39
0.43
0.42
0.47
0.52
0.57
0.52
0.58
0.66
0.76
0.62
0.70
0.79
0.88
0.83
0.93
1.05
1.17
1.04
1.17
1.31
1.45
1.25
1.40
1.57
1.71

550
0.12
0.14
0.15
0.17
0.25
0.27
0.31
0.35
0.37
0.41
0.46
0.51
0.49
0.55
0.61
0.67
0.61
0.69
0.77
0.85
0.73
0.82
0.92
1.02
0.98
1.10
1.23
1.36
1.22
1.37
1.54
1.71
1.47
1.64
1.84
2.04

AIR VELOCITY (FPM)


600
0.14
0.16
0.18
0.20
0.28
0.32
0.36
0.40
0.43
0.48
0.53
0.58
0.57
0.64
0.71
0.78
0.71
0.80
0.89
0.98
0.85
0.95
1.07
1.19
1.14
1.27
1.42
1.52
1.42
1.59
1.78
1.97
1.70
1.91
2.13
2.35

700
0.19
0.21
0.23
0.25
0.37
0.41
0.46
0.51
0.56
0.62
0.69
0.76
0.74
0.83
0.92
1.10
0.93
1.03
1.15
1.27
1.11
1.24
1.38
1.52
1.48
1.65
1.84
2.30
1.85
2.06
2.30

2.22
2.48
2.76

800
0.23
0.26
0.29
0.32
0.47
0.52
0.58
0.64
0.70
0.78
0.86
0.94
0.93
1.04
1.15
1.26

900*
0.29
0.32
0.35
0.38
0.57
0.63
0.70
0.77
0.86
0.95
1.05
1.15
1.14
1.26
1.40
1.54

1000*
0.34
0.38
0.42
0.46
0.68
0.76
0.84
0.92
1.03
1.13
1.25
1.37
1.37
1.51
1.67
1.83

* Beyond scope of ARI Certification for cooling applications.

YORK INTERNATIONAL

FORM 100.09-EG1

FREE-FLOW BDW OR BDX FOR COOLING AND DEHUMIDIFYING (1/2") APD (IN. WG.)
WET COIL
Rows

10

12

For Standard Air


Fin No.
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14

300
0.06
0.08
0.10
0.12
0.10
0.12
0.15
0.18
0.13
0.17
0.20
0.23
0.17
0.21
0.25
0.29
0.20
0.25
0.30
0.35
0.27
0.33
0.40
0.47
0.34
0.43
0.51
0.59
0.42
0.52
0.63
0.74

325
0.08
0.09
0.11
0.13
0.11
0.14
0.17
0.20
0.15
0.19
0.22
0.25
0.19
0.23
0.28
0.33
0.23
0.28
0.34
0.40
0.31
0.37
0.45
0.53
0.39
0.47
0.56
0.65
0.48
0.60
0.73
0.86

AIR VELOCITY (in. wg.)


375
400
425
0.10
0.10
0.12
0.12
0.13
0.14
0.14
0.16
0.17
0.16
0.18
0.19
0.14
0.16
0.18
0.18
0.19
0.21
0.21
0.23
0.25
0.24
0.26
0.29
0.19
0.21
0.23
0.23
0.26
0.28
0.28
0.31
0.34
0.33
0.36
0.40
0.24
0.27
0.29
0.29
0.32
0.35
0.35
0.38
0.42
0.42
0.44
0.49
0.29
0.32
0.35
0.35
0.39
0.42
0.42
0.46
0.50
0.49
0.53
0.58
0.38
0.42
0.47
0.47
0.52
0.57
0.56
0.61
0.67
0.65
0.70
0.77
0.47
0.52
0.58
0.61
0.68
0.75
0.70
0.78
0.86
0.79
0.88
0.97
0.60
0.66
0.73
0.78
0.88
0.98
0.93
1.03
1.13
1.08
1.18
1.28

350
0.09
0.10
0.12
0.14
0.13
0.16
0.19
0.22
0.17
0.21
0.25
0.29
0.21
0.26
0.31
0.36
0.26
0.31
0.38
0.45
0.34
0.42
0.50
0.58
0.42
0.54
0.62
0.70
0.54
0.68
0.83
0.98

450
0.13
0.15
0.18
0.20
0.19
0.23
0.27
0.30
0.26
0.31
0.37
0.43
0.32
0.39
0.46
0.53
0.38
0.46
0.55
0.64
0.51
0.62
0.73
0.84
0.65
0.83
0.94
1.05
0.81
1.08
1.23
1.38

475
0.14
0.17
0.20
0.22
0.21
0.25
0.30
0.35
0.28
0.34
0.40
0.46
0.35
0.42
0.50
0.58
0.42
0.50
0.60
0.70
0.56
0.67
0.79
0.91
0.72
0.90
1.03
1.16
0.89
1.13
1.34
1.55

500
0.15
0.18
0.21
0.23
0.23
0.27
0.32
0.37
0.30
0.36
0.43
0.49
0.38
0.45
0.54
0.63
0.45
0.55
0.64
0.73
0.61
0.73
0.86
0.99
0.79
0.97
1.11
1.25
0.99
1.28
1.46
1.64

525
0.16
0.20
0.23
0.25
0.25
0.29
0.35
0.40
0.33
0.39
0.46
0.51
0.41
0.49
0.58
0.67
0.49
0.59
0.69
0.79
0.65
0.78
0.92
1.06
0.88
1.05
1.20
1.35
1.10
1.38
1.58
1.78

550
0.18
0.21
0.25
0.27
0.26
0.32
0.37
0.42
0.35
0.42
0.49
0.56
0.44
0.53
0.62
0.71
0.53
0.63
0.74
0.85
0.71
0.84
0.99
1.14
0.93
1.12
1.29
1.46
1.20
1.48
1.70
1.92

FREE-FLOW BDW FOR HEATING & BDW OR BDX FOR SENSIBLE COOLING (1/2") APD (IN. WG.)
WET COIL
Rows

10

12

For Standard Air


Fin No.
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14

400
0.04
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.11
0.13
0.14
0.16
0.14
0.17
0.19
0.21
0.18
0.21
0.24
0.27
0.21
0.25
0.29
0.33
0.28
0.33
0.38
0.43
0.37
0.43
0.49
0.55
0.48
0.55
0.62
0.69

450
0.04
0.05
0.06
0.06
0.09
0.10
0.12
0.14
0.13
0.15
0.18
0.21
0.17
0.20
0.23
0.26
0.22
0.25
0.29
0.33
0.26
0.31
0.35
0.39
0.35
0.41
0.47
0.53
0.44
0.51
0.58
0.65
0.55
0.63
0.71
0.79

500
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.16
0.18
0.21
0.24
0.21
0.24
0.28
0.32
0.26
0.30
0.35
0.40
0.31
0.36
0.42
0.48
0.41
0.49
0.56
0.63
0.50
0.59
0.67
0.75
0.61
0.71
0.80
0.89

AIR VELOCITY (in. wg.)


550
600
650
0.06
0.07
0.08
0.07
0.08
0.09
0.08
0.10
0.11
0.09
0.12
0.13
0.12
0.14
0.16
0.14
0.17
0.19
0.16
0.19
0.22
0.18
0.21
0.25
0.18
0.21
0.24
0.21
0.25
0.28
0.25
0.29
0.33
0.29
0.33
0.38
0.24
0.28
0.32
0.29
0.33
0.38
0.33
0.38
0.43
0.37
0.43
0.48
0.30
0.35
0.40
0.36
0.41
0.47
0.41
0.48
0.54
0.46
0.55
0.61
0.36
0.42
0.48
0.43
0.50
0.57
0.49
0.57
0.65
0.55
0.64
0.73
0.49
0.56
0.64
0.57
0.66
0.76
0.66
0.76
0.87
0.75
0.86
0.98
0.58
0.65
0.73
0.67
0.76
0.86
0.76
0.87
0.98
0.85
0.98
1.10
0.69
0.76
0.84
0.79
0.88
0.98
0.89
1.00
1.11
0.99
1.12
1.24

700
0.09
0.11
0.12
0.14
0.18
0.21
0.25
0.29
0.27
0.32
0.37
0.42
0.37
0.43
0.49
0.55
0.46
0.54
0.62
0.70
0.55
0.60
0.74
0.88
0.73
0.86
0.98
1.10
0.82
0.96
1.09
1.22
0.93
1.08
1.22
1.36

* Beyond scope of ARI Certification for cooling applications.

YORK INTERNATIONAL

800
0.11
0.13
0.15
0.17
0.23
0.27
0.31
0.35
0.34
0.40
0.46
0.52
0.46
0.54
0.62
0.70

900*
0.14
0.16
0.19
0.21
0.28
0.33
0.38
0.43
0.42
0.49
0.56
0.63
0.56
0.65
0.75
0.85

1000*
0.17
0.20
0.22
0.24
0.33
0.39
0.45
0.51
0.50
0.59
0.67
0.75
0.67
0.78
0.90
1.02

39

Air Pressure Drop


AIR BLENDER APD (IN. WG.)
BLENDER FACE VELOCITY
PRESSURE DROP

1000
.07

1100
.08

1200
.10

1300
.12

1400
.14

1500
.16

1600
.18

1700
.20

1800
.23

1900
.26

2000
.29

NOTE: Variable air volume locations with blender velocities below 1000 FPM should be reviewed to ensure proper blender performance.

STEAM DISTRIBUTING (SDC) APD (IN. WG.)


COIL

SDC

ROW
DEPTH

FI N
SERIES

6
8
10
11
12
13
14

200
.02
.03
.03
.03
.04
.04
.04

300
.04
.05
.06
.07
.07
.08
.08

400
.07
.09
.10
.11
.12
.13
.14

500
.10
.13
.15
.16
.18
.19
.20

AIR VELOCITY (FPM)


600
700
800
.14
.18
.22
.17
.22
.28
.21
.27
.33
.22
.29
.36
.24
.31
.38
.25
.33
.41
.27
.35
.44

900
.28
.34
.40
.44
.47
.50
.53

1000
.34
.41
.48
.52
.56
.59
.63

1100
.40
.48
.56
.61
.65
.70
.74

1200
.46
.55
.66
.70
.75
.81
.86

Ratings for more than one row deep are obtained with multiple sections of one-row coils. All unit coils are rated and certified In accordance with ARI
Standard 410.

ELECTRIC HEATER AIR PRESSURE DROP (IN. WG.)


Air Velocity (FPM)

400

450

500

550

600

650

700

750

800

APD

0.03

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

DIFFUSER APD (IN. WG.)

DIFFUSER (DIF)

1600

1800

2000

0.09

0.11

0.14

FAN OUTLET VELOCITY


2200
2400
0.17

0.20

2600

2800

3000

0.24

0.27

0.32

VERTICAL CASING PRESSURE LOSS APD (IN. WG.)

CASING LOSS

350
0.14

COIL FACE VELOCITY


450
500
0.23
0.29

400
0.18

550
.0.36

600
0.41

ATTENUATOR APD (IN. WG.)


300

400

500

FACE VELOCITY
600
700

800

900

1000

Standard
Standard
Standard
Hospital
Hospital
Hospital
Low Frequency
Low Frequency

0.03
0.04
0.04
0.03
0.04
0.04
0.05
0.05

0.06
0.07
0.07
0.06
0.07
0.07
0.09
0.10

0.09
0.11
0.11
0.09
0.11
0.11
0.14
0.16

0.13
0.15
0.16
0.13
0.15
0.16
0.21
0.23

0.18
0.20
0.22
0.18
0.20
0.22
0.28
0.31

0.23
0.26
0.28
0.23
0.26
0.28
0.37
0.41

0.30
0.33
0.35
0.30
0.33
0.35
0.46
0.51

0.37
0.40
0.43
0.37
0.40
0.43
0.57
0.63

7' Low Frequency

0.06

0.08

0.14

0.22

0.32

0.43

0.53

0.63

MODEL
3'
5'
7'
3'
5'
7'
3'
5'

FILTER APD (IN. WG.)


TYPE FILTER MEDIA
2" - Throwaway
2" - Pleated
2" - Cleanable
4" - Pleated
12" - 65% Rigid
12" - 85% Rigid
12" - 95% Rigid
21" - 65% Efficient Bag
21" - 85% Efficient Bag
21" - 95% Efficient Bag
30" - 65% Efficient Bag
30" - 85% Efficient Bag
30" - 95% Efficient Bag
HEPA XT - 99.97% Efficient

200
0.08
0.08
0.02
0.06
0.15
0.17
0.20
0.07
0.14
0.19
0.08
0.09
0.15
0.44

250
0.10
0.10
0.03
0.08
0.17
0.21
0.24
0.09
0.18
0.23
0.11
0.12
0.21
0.60

300
0.12
0.12
0.04
0.10
0.20
0.26
0.29
0.11
0.22
0.27
0.13
0.15
0.27
0.76

FILTER VELOCITY (FPM)


350
400
450
0.14
0.18
0.21
0.15
0.20
0.24
0.05
0.07
0.09
0.13
0.16
0.19
0.23
0.28
0.31
0.30
0.37
0.45
0.33
0.41
0.50
0.13
0.16
0.19
0.26
0.30
0.35
0.31
0.36
0.42
0.15
0.19
0.23
0.19
0.23
0.27
0.33
0.39
0.45
0.92
1.08
1.24

500
0.25
0.27
0.10
0.22
0.39
0.53
0.58
0.22
0.39
0.48
0.27
0.32
0.51
1.40

550
0.30
0.32
0.11
0.28
0.44
0.63
0.67
NR
NR
NR
0.32
0.38
0.59
NR

625
0.37
0.38
0.13
0.33
0.54
0.77
0.81
NR
NR
NR
0.37
0.45
0.68
NR

NOTE: 1. Filter pressure drop is through clean filters.

40

YORK INTERNATIONAL

FORM 100.09-EG1

CARBON FILTER AIR PRESSURE DROP (IN W.G.)


CARBON MEDIA VELOCITY
Air Velocity (FPM)
APD

63

75

88

100

113

125

138

150

0.19

0.26

0.34

0.41

0.48

0.55

0.63

0.71

MIXING BOX DAMPER (MB) / FILTER MIXING BOX (FM) / ECONOMIZER (EE) / ECONOMIZER
FILTER (EF) AND EXTERNAL FACE AND BYPASS DAMPER (EB) (BYPASS DAMPER)
LOW LEAK APD (IN. WG.)
UNIT
SIZE

DAMPER
AREA

500

600

700

800

DAMPER VELOCITY (FPM)


900
1000
1100
1200

1300

1400

1500

1600

35

1.54

0.06

0.09

0.12

0.15

0.18

0.23

0.29

0.33

0.38

0.43

0.48

0.56

60

2.25

0.06

0.09

0.10

0.14

0.17

0.21

0.26

0.30

0.33

0.38

0.44

0.48

80

3.07

0.06

0.08

0.10

0.12

0.15

0.18

0.23

0.27

0.30

0.36

0.44

0.46

105

3.99

0.05

0.08

0.09

0.12

0.15

0.18

0.21

0.24

0.29

0.33

0.38

0.41

120

4.71

0.05

0.06

0.08

0.10

0.14

0.17

0.19

0.24

0.27

0.32

0.35

0.39

150

5.74

0.05

0.06

0.08

0.10

0.14

0.15

0.18

0.23

0.26

0.30

0.33

0.38

170

6.56

0.05

0.06

0.08

0.10

0.12

0.15

0.18

0.21

0.24

0.29

0.32

0.36

215

7.93

0.03

0.06

0.06

0.09

0.10

0.14

0.17

0.19

0.23

0.26

0.30

0.33

250

9.08

0.03

0.05

0.06

0.09

0.10

0.14

0.15

0.18

0.21

0.23

0.26

0.29

305

11.24

0.03

0.05

0.06

0.08

0.09

0.12

0.14

0.17

0.19

0.21

0.24

0.27

360

13.00

0.03

0.05

0.05

0.08

0.09

0.11

0.14

0.17

0.19

0.21

0.23

0.26

400

14.49

0.03

0.03

0.05

0.06

0.08

0.11

0.12

0.15

0.18

0.19

0.21

0.24

500

18.20

0.03

0.03

0.05

0.06

0.08

0.09

0.11

0.14

0.15

0.18

0.19

0.21

580

20.92

0.02

0.03

0.05

0.06

0.08

0.09

0.11

0.12

0.15

0.17

0.18

0.19

660

23.43

0.02

0.03

0.05

0.05

0.06

0.08

0.09

0.12

0.14

0.15

0.17

0.18

800

28.43

0.02

0.03

0.03

0.05

0.06

0.08

0.09

0.11

0.12

0.14

0.15

0.17

1000

35.25

0.02

0.03

0.03

0.05

0.05

0.06

0.08

0.09

0.11

0.12

0.14

0.15

ULTRA LOW LEAK APD (IN. WG.)


DAMPER VELOCITY (FPM)

UNIT
SIZE

DAMPER
AREA

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

35

1.54

0.04

0.06

0.08

0.10

0.12

0.15

0.18

0.22

0.25

0.28

0.32

0.39

60

2.25

0.04

0.06

0.07

0.09

0.11

0.14

0.17

0.20

0.22

0.25

0.29

0.32

80

3.07

0.04

0.05

0.07

0.08

0.10

0.12

0.15

0.18

0.20

0.23

0.27

0.30

105

3.99

0.03

0.05

0.06

0.08

0.10

0.12

0.14

0.16

0.18

0.22

0.25

0.27

120

4.71

0.03

0.04

0.05

0.07

0.09

0.11

0.13

0.16

0.18

0.21

0.23

0.26

150

5.74

0.03

0.04

0.05

0.07

0.09

0.10

0.12

0.15

0.17

0.20

0.22

0.25

170

6.56

0.03

0.04

0.05

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.21

0.24

215

7.93

0.02

0.04

0.05

0.06

0.07

0.09

0.11

0.13

0.15

0.17

0.20

0.22

250

9.08

0.02

0.03

0.04

0.06

0.07

0.09

0.10

0.12

0.14

0.16

0.17

0.19

305

11.24

0.02

0.03

0.04

0.05

0.06

0.08

0.09

0.11

0.13

0.14

0.16

0.18

360

13.00

0.02

0.03

0.04

0.05

0.06

0.07

0.09

0.11

0.13

0.14

0.15

0.17

400

14.49

0.02

0.02

0.03

0.04

0.05

0.07

0.08

0.10

0.12

0.13

0.14

0.16

500

18.20

0.02

0.02

0.03

0.04

0.05

0.06

0.07

0.09

0.10

0.12

0.13

0.14

580

21.92

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.10

0.11

0.12

0.13

660

23.43

0.01

0.02

0.03

0.03

0.04

0.05

0.06

0.08

0.09

0.10

0.11

0.12

800

28.43

0.01

0.02

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

1000

35.25

0.01

0.02

0.02

0.03

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

NOTES:

1. Damper performance is based on AMCA 500 test setup 5.4/5.5.


2. Based on 100% open dampers.

YORK INTERNATIONAL

41

Air Pressure Drop


INTERNAL FACE AND BYPASS DAMPER (IB) - BYPASS DAMPER
LOW LEAK APD (IN. WG.)
UNIT
SIZE

BYPASS
DAMPER
AREA

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

35

1.75

0.09

0.12

0.15

0.18

0.23

0.27

0.33

0.38

0.42

0.49

0.59

0.65

0.73

60

2.13

0.09

0.11

0.14

0.17

0.21

0.26

0.30

0.33

0.38

0.45

0.49

0.55

0.61

80

2.81

0.09

0.11

0.14

0.17

0.19

0.24

0.29

0.32

0.36

0.44

0.47

0.53

0.61

105

3.42

0.08

0.11

0.12

0.15

0.18

0.23

0.27

0.30

0.36

0.44

0.46

0.51

0.58

120

3.93

0.08

0.09

0.12

0.15

0.18

0.21

0.24

0.29

0.33

0.38

0.41

0.47

0.52

150

4.75

0.06

0.09

0.11

0.14

0.18

0.19

0.24

0.27

0.32

0.35

0.39

0.46

0.50

170

6.88

0.06

0.06

0.11

0.12

0.17

0.18

0.21

0.24

0.29

0.32

0.36

0.40

0.44

215

8.65

0.05

0.06

0.09

0.11

0.15

0.15

0.18

0.21

0.24

0.26

0.29

0.32

0.35

250

8.65

0.05

0.06

0.09

0.11

0.14

0.15

0.18

0.21

0.24

0.26

0.29

0.32

0.35

305

8.66

0.05

0.06

0.09

0.11

0.14

0.15

0.18

0.21

0.24

0.26

0.29

0.32

0.35

360

10.06

0.05

0.06

0.09

0.11

0.14

0.15

0.18

0.21

0.23

0.26

0.29

0.32

0.35

400

11.12

0.05

0.06

0.08

0.09

0.14

0.14

0.17

0.19

0.21

0.24

0.27

0.30

0.33

500

15.13

0.03

0.05

0.06

0.08

0.12

0.12

0.15

0.18

0.19

0.21

0.24

0.27

0.30

580

17.10

0.03

0.05

0.06

0.08

0.11

0.12

0.15

0.17

0.18

0.19

0.23

0.26

0.29

660

19.15

0.03

0.05

0.06

0.08

0.09

0.11

0.12

0.15

0.17

0.18

0.19

0.23

0.24

800

24.39

0.03

0.03

0.06

0.08

0.09

0.11

0.12

0.15

0.17

0.18

0.19

0.23

0.24

1000

31.01

0.03

0.03

0.06

0.08

0.09

0.11

0.12

0.15

0.17

0.18

0.19

0.23

0.24

DAMPER VELOCITY (FPM)

ULTRA LOW LEAK APD (IN. WG.)


UNIT
SIZE

BYPASS
DAMPER
AREA

600

35

1.75

0.06

60

2.13

0.06

80

2.81

0.06

105

3.42

120

DAMPER VELOCITY (FPM)


700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

0.08

0.10

0.12

0.15

0.18

0.22

0.25

0.28

0.32

0.39

0.43

0.48

0.07

0.09

0.11

0.14

0.17

0.20

0.22

0.25

0.29

0.32

0.36

0.40

0.07

0.09

0.11

0.13

0.16

0.19

0.21

0.24

0.28

0.31

0.35

0.40

0.05

0.07

0.08

0.10

0.12

0.15

0.18

0.20

0.23

0.27

0.30

0.34

0.38

3.93

0.05

0.06

0.08

0.10

0.12

0.14

0.16

0.18

0.22

0.25

0.27

0.31

0.34

150

4.75

0.04

0.05

0.07

0.09

0.11

0.13

0.16

0.18

0.21

0.23

0.26

0.30

0.33

170

6.88

0.04

0.05

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.21

0.24

0.26

0.29

215

8.65

0.03

0.04

0.06

0.07

0.09

0.10

0.12

0.14

0.16

0.17

0.19

0.21

0.23

250

8.65

0.03

0.04

0.06

0.07

0.09

0.10

0.12

0.14

0.16

0.17

0.19

0.21

0.23
0.23

305

8.66

0.03

0.04

0.06

0.07

0.09

0.10

0.12

0.14

0.16

0.17

0.19

0.21

360

10.06

0.03

0.04

0.06

0.07

0.09

0.10

0.12

0.14

0.15

0.17

0.19

0.21

0.23

400

11.12

0.03

0.04

0.05

0.06

0.08

0.09

0.11

0.13

0.14

0.16

0.18

0.20

0.22

500

15.13

0.02

0.03

0.04

0.05

0.07

0.08

0.10

0.12

0.13

0.14

0.16

0.18

0.20

580

17.10

0.02

0.03

0.04

0.05

0.07

0.08

0.10

0.11

0.12

0.13

0.15

0.17

0.19

660

19.15

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.10

0.11

0.12

0.13

0.15

0.16

800

24.39

0.02

0.02

0.04

0.05

0.06

0.07

0.08

0.10

0.11

0.12

0.13

0.15

0.16

1000

31.01

0.02

0.02

0.04

0.05

0.06

0.07

0.08

0.10

0.11

0.12

0.13

0.15

0.16

NOTES: 1. Damper performance is based on AMCA 500 test setup 5.4/5.5.

42

YORK INTERNATIONAL

FORM 100.09-EG1

INTERNAL FACE AND BYPASS DAMPER (IB) - BYPASS DAMPER


LOW LEAK APD (IN. WG.)
UNIT
SIZE

FACE
DAMPER
AREA

300

400

500

600

700

800

900

35

2.92

0.04

0.05

0.06

0.08

0.10

0.12

0.15

60

4.96

0.03

0.05

0.05

0.06

0.08

0.10

0.14
0.12

DAMPER VELOCITY (FPM)

80

6.56

0.02

0.03

0.05

0.06

0.08

0.10

105

8.95

0.02

0.03

0.03

0.05

0.06

0.09

0.10

120

10.28

0.02

0.03

0.03

0.05

0.06

0.09

0.09

150

12.44

0.02

0.03

0.03

0.05

0.06

0.08

0.09

170

14.24

0.02

0.03

0.03

0.03

0.05

0.06

0.08

215

15.56

0.02

0.02

0.03

0.03

0.05

0.06

0.08

250

19.02

0.02

0.02

0.02

0.03

0.05

0.06

0.08

305

24.99

0.02

0.02

0.02

0.03

0.05

0.05

0.06

360

29.52

0.02

0.02

0.02

0.03

0.05

0.05

0.06

400

32.63

0.02

0.02

0.02

0.03

0.04

0.05

0.06

500

40.12

0.02

0.02

0.02

0.03

0.03

0.05

0.05

580

46.46

0.02

0.02

0.02

0.03

0.03

0.05

0.05

660

52.01

0.02

0.02

0.02

0.03

0.03

0.05

0.05

800

63.17

0.02

0.02

0.02

0.03

0.03

0.05

0.05

1000

78.51

0.02

0.02

0.02

0.03

0.03

0.05

0.05

900

ULTRA LOW LEAK APD (IN. WG.)


UNIT
SIZE

FACE
DAMPER
AREA

300

400

500

600

700

800

DAMPER VELOCITY (FPM)

35

2.92

0.02

0.03

0.04

0.06

0.07

0.09

0.11

60

4.96

0.02

0.03

0.03

0.04

0.05

0.07

0.09
0.08

80

6.56

0.01

0.02

0.03

0.04

0.05

0.07

105

8.95

0.01

0.02

0.02

0.03

0.04

0.06

0.07

120

10.28

0.01

0.02

0.02

0.03

0.04

0.06

0.07

150

12.44

0.01

0.02

0.02

0.03

0.04

0.05

0.06

170

14.24

0.01

0.02

0.02

0.03

0.04

0.05

0.06

215

15.56

0.01

0.01

0.02

0.03

0.04

0.05

0.06

250

19.02

0.01

0.01

0.01

0.03

0.03

0.04

0.05

305

24.99

0.01

0.01

0.01

0.03

0.03

0.03

0.04

360

29.52

0.01

0.01

0.01

0.03

0.03

0.03

0.04

400

32.63

0.01

0.01

0.01

0.02

0.02

0.03

0.04

500

40.12

0.01

0.01

0.01

0.02

0.02

0.03

0.03

580

46.46

0.01

0.01

0.01

0.02

0.02

0.03

0.03

660

52.01

0.01

0.01

0.01

0.02

0.02

0.03

0.03

800

63.17

0.01

0.01

0.01

0.02

0.02

0.03

0.03

1000

78.51

0.01

0.01

0.01

0.02

0.02

0.03

0.03

NOTES: 1. Damper performance is based on AMCA 500 test setup 5.4/5.5.

YORK INTERNATIONAL

43

Air Pressure Drop


FACE DAMPER SEGMENT (FD) AND
EXTERNAL FACE AND BYPASS DAMPER (EB) - (FACE DAMPER)
LOW LEAK APD (IN. WG.)
FACE
DAMPER
AREA

300

400

500

600

700

800

900

35

4.67

0.03

0.05

0.05

0.06

0.08

0.10

0.14

60

7.08

0.02

0.03

0.05

0.06

0.08

0.10

0.12

80

9.38

0.02

0.03

0.03

0.05

0.06

0.09

0.10

105

12.38

0.02

0.03

0.03

0.05

0.06

0.08

0.09

120

14.21

0.02

0.03

0.03

0.03

0.05

0.06

0.08

150

17.19

0.02

0.02

0.03

0.03

0.05

0.06

0.08

170

21.13

0.02

0.02

0.02

0.03

0.05

0.06

0.08

215

24.21

0.02

0.02

0.02

0.03

0.05

0.05

0.06

250

27.67

0.02

0.02

0.02

0.03

0.05

0.05

0.06

305

33 65

0.02

0.02

0.02

0.03

0.04

0.05

0.06

360

39.58

0.02

0.02

0.02

0.03

0.03

0.05

0.05

400

43.75

0.02

0.02

0.02

0.03

0.03

0.05

0.05

500

55.25

0.02

0.02

0.02

0.03

0.03

0.05

0.05

580

63.58

0.02

0.02

0.02

0.03

0.03

0.05

0.05

660

71.17

0.02

0.02

0.02

0.03

0.03

0.05

0.05

800

87.56

0.02

0.02

0.02

0.03

0.03

0.05

0.05

1000

109.52

0.02

0.02

0.02

0.03

0.03

0.05

0.05

UNIT
SIZE

DAMPER VELOCITY (FPM)

ULTRA LOW LEAK APD (IN. WG.)


UNIT
SIZE

FACE
DAMPER
AREA

300

400

500

600

700

800

900

35

4.67

0.02

0.03

0.03

0.04

0.05

0.07

0.09

60

7.08

0.01

0.02

0.03

0.04

0.05

0.07

0.08

80

9.38

0.01

0.02

0.02

0.03

0.04

0.06

0.07

105

12.38

0.01

0.02

0.02

0.03

0.04

0.05

0.06

120

14.21

0.01

0.02

0.02

0.03

0.04

0.05

0.06

150

17.19

0.01

0.01

0.02

0.02

0.03

0.04

0.05

170

21.13

0.01

0.01

0.01

0.02

0.03

0.04

0.05

215

24.21

0.01

0.01

0.01

0.02

0.03

0.03

0.04

250

27.67

0.01

0.01

0.01

0.02

0.02

0.03

0.04

305

33.65

0.01

0.01

0.01

0.02

0.02

0.03

0.04

360

39.58

0.01

0.01

0.01

0.02

0.02

0.03

0.03

400

43.75

0.01

0.01

0.01

0.02

0.02

0.03

0.03

500

55.25

0.01

0.01

0.01

0.02

0.02

0.03

0.03

580

63.58

0.01

0.01

0.01

0.02

0.02

0.03

0.03

660

71.17

0.01

0.01

0.01

0.02

0.02

0.03

0.03

800

87.56

0.01

0.01

0.01

0.02

0.02

0.03

0.03

1000

109.52

0.01

0.01

0.01

0.02

0.02

0.03

0.03

NOTES:

44

DAMPER VELOCITY (FPM)

1. Damper performance is based on AMCA standard 500 test setup 5.4/5.5.

YORK INTERNATIONAL

FORM 100.09-EG1

MULTI-ZONE (MZ)
ULTRA LOW LEAK APD (IN. WG.)
DAMPER VELOCITY (FPM)

UNIT
SIZE

DAMPER
AREA

1000

1200

1400

1600

1800

2000

2200

60

2.22

0.06

0.09

0.13

0.16

0.21

0.26

0.31

80

2.91

0.06

0.09

0.13

0.16

0.21

0.26

0.31

105

3.47

0.06

0.09

0.13

0.16

0.21

0.26

0.31

120

3.97

0.06

0.09

0.13

0.16

0.21

0.26

0.31

150

4.78

0.06

0.09

0.13

0.16

0.21

0.26

0.31

170

4.97

0.06

0.09

0.13

0.16

0.21

0.26

0.31

215

6.45

0.06

0.08

0.11

0.14

0.18

0.24

0.27

250

7.04

0.05

0.08

0.11

0.14

0.17

0.22

0.26

305

8.04

0.05

0.08

0.11

0.14

0.17

0.22

0.26

360

10.05

0.05

0.07

0.10

0.13

0.16

0.20

0.24

400

11.09

0.05

0.07

0.10

0.13

0.16

0.20

0.24

500

13.17

0.05

0.07

0.09

0.12

0.15

0.19

0.23

NOTES:

1. Pressure Drop Data is for wide open damper.


2. Maximum face velocity for dampers is 2000 fpm.

YORK INTERNATIONAL

45

Segment Dimensions
FS - SUPPLY FAN SEGMENT

LD04320

LD04304

LD04319

All dimensions are approximate and not certified for construction.

1
NOTES:

46

"S" DIMENSION IS ON MOTOR / DRIVE SIDE OF FAN SEGMENT.

1. Motor / Drive may be located on either the right hand (R.H.) or left (L.H.) side of unit. (See page 88 for orientation)
2. An access door is supplied as standard on the motor / drive side of unit.
3. Access doors (opposite motor / drive side), access doors (both sides), window in door, auxiliary drain pan and perforated liners
are all optional.
4. Certain items (i.e. coil connections, door handles, mounting feet and etc.) may extend beyond the cabinet dimensions.
5. H dimension is based on standard base rail height.
YORK INTERNATIONAL

FORM 100.09-EG1

FS - SUPPLY FAN SEGMENT


UNIT DIMENSIONS
UNIT
SIZE
35
60
80
105

120

150

170

215

250

305

360

400

500

580

660

800

1000

FAN
NUMBER
FAN 1
FAN 2
FAN 1
FAN 2
FAN 1
FAN 2
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3

FAN
TYPE
FC
FC
FC
FC
FC
FC
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
AF
AF
AF
AF
AF
AF
AF
AF

FAN
SIZE
9-9
9-6
10-10
9-9
12-12
10-10
15-15
12-12
12
15-15
15-11
15
18-18
15-15
15
20-20
18-18
18
20-20
18-18
20
22-22
20-20
22
20-18
25-25
22-22
25
22-20
28-28
25-25
25
22-20
28-28
25-25
28
25-22
32-32
28-28
32
27-25
32-32
30-30
32
32-32
32
36
36
40
44
36
40
44

FAN DISCHARGE DIMENSIONS

36
36
42
42
53
53
62
62
62
70
70
70
83
83
83
86
86
86
91
91
91
91
91
91
91
103
103
103
103
103
103
103
103
113
113
113
113
125
125
125
125
125
125
125
139
139
139
139
139
139
146
146
146

42
40
44
42
46
44
46
46
46
46
46
46
48
46
46
54
48
48
54
48
54
58
54
58
54
62
58
62
58
68
62
62
58
68
62
68
62
76
68
76
68
76
72
76
76
76
82
82
88
94
82
88
94

37
37
43
43
43
43
46
46
46
46
46
46
46
46
46
52
52
52
55
55
55
61
61
61
61
64
64
64
64
73
73
73
73
73
73
73
73
81
81
81
81
95
95
95
95
95
95
113
113
113
131
131
131

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
8
8
8
8
8
8
8
8
8
8
8
8

13.70
13.75
14.57
13.70
15.59
14.57
17.95
16.59
16.59
17.95
17.95
17.95
16.45
17.95
17.95
16.64
19.98
19.98
19.67
19.98
19.67
21.49
20.17
21.49
20.06
22.60
21.49
22.60
21.56
25.06
23.10
23.10
21.56
25.06
23.10
25.06
22.81
27.20
25.06
27.20
24.56
27.20
26.06
27.20
27.20
27.20
29.46
29.46
30.43
39.78
29.46
30.43
39.78

9.31
9.31
9.31
9.31
9.19
9.31
10.31
10.19
10.19
10.31
10.31
10.31
6.76
10.31
10.31
5.94
10.29
10.29
8.97
10.29
8.97
9.53
9.47
9.53
10.81
9.07
9.53
9.07
11.31
9.55
9.57
9.57
11.31
9.55
9.57
9.55
11.31
9.57
9.55
9.57
11.31
9.57
11.31
9.57
9.57
9.57
9.55
9.55
9.57
12.59
9.55
9.57
12.59

18.88
16.31
19.27
18.88
19.61
19.27
16.97
19.30
19.30
16.97
16.97
16.97
14.61
16.97
16.97
13.77
14.61
14.61
13.77
14.61
13.77
13.42
13.77
13.42
14.06
12.67
13.42
12.67
14.56
12.84
12.67
12.67
14.56
12.84
12.67
12.84
13.31
14.15
12.84
14.15
14.55
14.15
14.56
14.15
14.15
14.15
13.11
13.11
13.00
14.75
13.11
13.00
14.75

11.73
8.25
13.03
11.73
15.55
13.03
18.54
15.55
15.55
18.54
14.69
18.54
21.93
18.54
18.54
25.12
21.93
21.93
25.12
21.93
25.12
28.15
25.12
28.15
22.75
31.54
28.15
31.54
25.25
35.35
31.54
31.54
25.25
35.35
31.54
35.35
28.25
39.65
35.35
39.65
31.75
39.65
36.75
39.65
39.65
39.65
44.49
44.49
49.88
63.44
44.49
49.88
63.44

10.30
10.25
11.36
10.30
13.45
11.36
15.88
13.45
13.45
15.88
15.88
15.88
18.78
15.88
15.88
25.12
18.78
18.78
25.12
18.78
25.12
28.15
25.12
28.15
24.75
31.54
28.15
31.54
27.25
35.35
31.54
31.54
27.25
35.35
31.54
35.35
31.25
39.65
35.35
39.65
34.25
39.65
36.75
39.65
39.65
39.65
44.49
44.49
49.88
46.50
44.49
49.88
46.50

12.14
13.88
14.49
15.14
18.73
19.99
26.29
27.26
27.26
29.04
29.04
29.04
30.54
35.54
35.54
32.44
32.04
32.04
34.94
34.54
34.94
35.30
34.94
35.30
39.00
41.67
41.30
41.67
39.00
37.33
41.67
41.67
39.00
42.33
46.67
42.33
45.25
42.68
48.33
42.68
48.75
42.68
52.25
42.68
49.68
49.68
47.26
47.26
44.56
43.56
50.76
48.06
50.56

All dimensions are in inches.


YORK INTERNATIONAL

47

Segment Dimensions
FP - PLENUM FAN SEGMENT

LD04305

All dimensions are approximate and not certified for construction.

PLENUM FAN DIMENSIONS (in.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

46

52

55

61

64

73

73

81

95

95

113

131

83

86

91

91

103

103

113

125

125

139

139

146

1. Certain items (i.e. coil connections, door handles, mounting feet and etc.) may extend beyond the cabinet dimensions.
2. H dimension is based on standard base rail height.

48

YORK INTERNATIONAL

FORM 100.09-EG1

FP - SEGMENT DIMENSIONS (IN.)

LD02606

All dimensions are approximate and not certified for construction.


UNIT DIMENSIONS
UNIT
SIZE
150
170
215
250
305
360
400
500
580
660
800
1000
NOTES:

FAN
NUMBER
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN
FAN

1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2

FAN DISCHARGE DIMENSIONS

FAN
TYPE

FAN
SIZE

SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI
SWSI

20
24
27
27
30
30
33
33
36
33
36
36
40
40
44
44
49
49
54
54
60
60
66

83
86
86
91
91
91
91
103
103
103
103
113
113
125
125
125
125
139
139
139
139
146
146

40
44
46
46
50
50
52
52
56
52
56
56
60
60
66
66
70
70
74
74
80
80
84

14.88
14.88
14.88
20.88
20.88
20.88
20.88
20.88
20.88
26.88
26.88
26.88
26.88
26.88
26.88
32.88
32.88
32.88
32.88
32.88
32.88
38.88
38.88

13.44
10.94
10.94
17.94
17.94
13.94
13.94
12.44
12.44
16.44
16.44
17.44
17.44
13.44
13.44
16.44
16.44
17.94
17.94
6.94
6.94
7.44
7.44

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
11
11
11
11
11
11
11
11

14
16
18
18
18
18
20
22
22
22
22
24
24
26
28
28
28
32
32
32
34
30
30

56.13
64.13
64.13
55.13
55.13
63.13
63.13
78.13
78.13
70.13
70.13
78.13
78.13
98.13
98.13
92.13
92.13
103.13
103.13
125.13
125.13
131.13
131.13

35
41
41
44
44
50
50
53
53
62
62
62
62
70
70
81
81
81
81
99
99
11 7
11 7

4
4
4
4
6
6
6
4
6
4
6
4
6
4
6
6
8
4
6
6
8
10
12

1. Motor / Drive may be located on either the right hand (R.H.) or left (L.H.) side of unit. (See page 88 for orientation)
2. An access door is supplied as standard on the motor / drive side of unit.
3. Access doors (opposite motor / drive side), access doors (both sides), window in door, auxiliary drain pan and perforated liners
are all optional.
4. Certain items (i.e. coil connections, door handles, mounting feet and etc.) may extend beyond the cabinet dimensions.
5. H dimension is based on standard base rail height.

YORK INTERNATIONAL

49

Segment Dimensions
COILS
HC
SC
MC
LC
XC

HEATING COIL (8")


SHORT COIL (10")
MEDIUM COIL (20")
LONG COIL (28")
EXTRA-LONG COIL (36")

LD04306

All dimensions are approximate and not certified for construction.

COIL SEGMENT DIMENSIONS (IN.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

SC (10")

16

18

18

18

18

18

18

20

20

22

24

24

26

26

28

32

36

MC (20") 26

28

28

28

28

28

28

30

30

32

34

34

36

36

38

42

46

LC (28")

34

36

36

36

36

36

36

38

38

40

42

42

44

44

46

50

54

XC (36")

42

44

44

44

44

44

44

46

46

48

50

50

52

52

54

N/A

N/A

HC (8")

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

L/2

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

6.6

6.6

6.6

6.6

NOTES:

50

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

All cooling coil segments have a 4" deep, sloped drain pan with connections on both sides of the unit.
All coils located in the same coil segment must have the same coil hand.
Full and reduced face coils can not be used in the same coil segment.
Viewing ports must be placed in adjacent segments.
Access doors must be placed in adjacent segments.
Auxiliary drain pan and perforated liners are available as options in the heating coil segment (HC).
Number in parenthesis indicates available coil space.
A sloped drain pan with a single (1) connection is available as an option in the SC, MC, LC & XC coil segments.
Certain items (i.e. coil connections, door handles, mounting feet and etc.) may extend beyond the cabinet dimensions.
H dimension is based on standard base rail height.
YORK INTERNATIONAL

FORM 100.09-EG1

VC - VERTICAL COIL SEGMENT


VC - VERTICAL COIL

FOR COIL CONNECTION


LOCATION & SIZE
SEE PAGES 84, 85

LD04307

All dimensions are approximate and not certified for construction.

VERTICAL COIL DIMENSIONS (IN.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

H2

37

43

43

46

46

46

52

55

61

64

73

73

81

H1

32

38

38

41

41

41

47

50

56

59

68

68

76

69

81

81

87

87

87

99

105

117

123

141

141

157

36

42

53

62

70

83

86

91

91

103

103

113

125

SAME AS FS SEGMENT

13

14

14

14

14

14

14

15

15

16

17

17

18

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

NOTES: 1. Rear, rear inverted, top, top inverted, front and front inverted discharges
available for the supply fan segment (FS).
2. All VC segments have 20" of available coil space.
3. The FS segment will be located on top of the VC segment.
4. The FS segment will be the last segment in the direction of airflow.
5. All cooling coil segments have 4" deep, sloped drain pan.
6. All coils located in the same coil segment must have the same coil hand.
7. Full and reduced face coils can not be used in the same segments.

YORK INTERNATIONAL

8. Perforated liners are available in cooling coil segment.


9. Viewing ports are available.
10. Access doors are available.
11. A sloped drain pan with a single (1) connection is available as an
option.
12. FS can easily be removed from the VC.
13. H and H2 dimensions are based on standard base rail height.

51

Segment Dimensions
IC - INTEGRAL FACE & BYPASS COIL SEGMENT

IC - INTEGRAL FACE & BYPASS COIL

LD04308

All dimensions are approximate and not certified for construction.

INTEGRAL FACE & BYPASS COIL DIMENSIONS (IN.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800 1000

N/A

N/A

N/A

46

46

46

52

55

61

64

73

73

81

95

95

113

131

N/A

N/A

N/A

62

70

83

86

91

91

103

103

113

125

125

139

139

146

N/A

N/A

N/A

24

24

24

24

24

24

24

24

24

34

34

34

34

34

N/A

N/A

N/A

NOTES: 1. Unit sizes AP105 - 400 have side connections.


2. Unit sizes AP500 - 1000 have center connections.
3. Access doors and viewing ports must be located in adjacent segments.
4. Connection and condensate trapping information is detailed on page 83.
5. H dimension is based on standard base rail height.

52

YORK INTERNATIONAL

FORM 100.09-EG1

FILTER DIMENSIONS (IN.)


OF - OPEN RETURN FILTER (2" & 4")
FF - FLAT FILTER
AF - ANGLE FILTER (2" & 4")

FLAT FILTER (2")


FLAT FILTER (4")

ANGLE FILTER (2")

LD04309

LD02337

All dimensions are approximate


and not certified for construction.

FILTER SEGMENT DIMENSIONS (IN.)


DIMENSION

OF
L

FF
AF

35
H
37
W
36
(2")
0
(4")
2
(2" or 4") 10
(2")
18
(4")
20
B
5

60
43
42
0
2
10
20
22
5

80
43
53
0
2
10
20
22
5

105
46
62
0
2
10
20
22
5

120
46
70
0
2
10
20
22
5

150
46
83
0
2
10
20
22
5

170
52
86
0
2
10
16
18
5

UNIT SIZE
215 250 305
55
61
64
91
91 103
0
0
0
2
2
2
10
10
10
22
18
18
24
20
20
5
5
5

NOTES:1. All filters are side-loading (except for open return segments - front
loading).
2. Open return (2") filters fit within the frame of the unit and do not add
any length in the direction of air flow.
3. All filter segments (except OF segment) come equipped with a full
height access door on the motor / drive side of the unit as part of
standard construction.
4. Viewing ports are not available in the FF and AF filter segments.

YORK INTERNATIONAL

360
73
103
0
2
10
20
22
5

400
73
113
0
2
10
20
22
5

500
81
125
0
2
10
20
22
5

580
95
125
0
2
10
22
26
8

660
95
139
0
2
10
22
26
8

800
113
139
0
2
10
22
24
8

1000
131
146
0
2
10
22
26
8

5. Access doors (opposite motor / drive side), access doors (both


sides) and auxiliary drain pans are all options for the FF & AF
filter segments.
6. Perforated liner is available for the FF, and AF filter segments.
7. Certain items (eg. coil connections, door handles, mounting
feet and etc.) may extend beyond the cabinet dimensions.
8. H dimension is based on standard base rail height.

53

Segment Dimensions
FILTER DIMENSIONS (IN.)
RF - RIGID FILTER (12" w/2" or 4" Pre-Filter)
BF - BAG FILTER (21" OR 32" w/2" or 4" Pre-Filter)
HF - HEPA FILTER (12")

BAG FILTER (21")


RIGID FILTER (12")

BAG FILTER (32")

LD04322

HEPA FILTER (12")

LD04323

LD04324

All dimensions are approximate and not certified for construction.

FILTER SEGMENT DIMENSIONS (IN.)


DIMENSION

35
H
37
W
36
w/2" Pre-filter 18
RF
w/4" Pre-filter 20
L
(21")
26
BF
(32")
36
HF (12")
18
B
5

60
43
42
18
20
26
36
18
5

80
43
53
18
20
26
36
18
5

105
46
62
18
20
26
36
18
5

120
46
70
18
20
26
36
18
5

150
46
83
18
20
26
36
18
5

170
52
86
18
20
26
36
18
5

NOTES: 1. Bag Rigid filters are side-loading, HEPA filters are front
loading.
2. BF & RF filter segments come equipped with a full height
access door on the motor / drive side of the unit as part of
standard construction.
3. The BF segment can be equipped with either a 2" or 4"
Pre-filter the segments overall length does not change.

54

UNIT SIZE
215 250 305
55 61
64
91 91
103
18 18
18
20 20
20
26 26
26
36 36
36
18 18
18
5
5
5

360
73
103
18
20
26
36
18
5

400
73
113
18
20
26
36
18
5

500
81
125
18
20
26
36
18
5

580
95
125
18
20
26
36
18
8

660
95
139
18
20
26
36
18
8

800 1000
113
131
139 146
18
18
20
20
26
26
36
36
18
18
8
8

4. Access doors (opposite motor / drive side), access doors (both sides) and
auxiliary drain pans are all options for the BF & RF filter segments.
5. Viewing port in door is available for the BF & RF filter segment.
6. Perforated liner is available for the BF and RF filter segments.
7. All gasketing is located on the HEPA media. The frames are not gasketed.
8. H dimension is based on standard base rail height.

YORK INTERNATIONAL

FORM 100.09-EG1

FILTER DIMENSIONS (IN.)


CF - CARBON FILTER (CF-1 & CF-2)
CF-1

CF-2

TOP
VIEW

TOP
VIEW

CF-2

CF-1

(w / Pre-Filter Option)

SIDE
VIEW

SIDE
VIEW

CF-1

CF-2

(w / Post-Filter Option)

(w / Pre- & Post-Filter Option)

SIDE
VIEW

SIDE
VIEW

LD02502

All dimensions are approximate and not certified for construction.

CARBON FILTER SEGMENT DIMENSIONS


DIMENSIONS
H
W
L (CF-1)
L (CF-2)
B

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

8 0 0 1000

37
36
32
38
5

43
42
32
38
5

43
53
32
38
5

46
62
32
38
5

46
70
32
38
5

46
83
32
38
5

52
86
32
38
5

55
91
32
38
5

61
91
32
38
5

64
103
32
38
5

73
103
32
38
5

73
113
32
38
5

81
125
32
38
5

95
125
34
40
8

95
139
34
40
8

113
139
34
40
8

131
146
34
40
8

NOTES:
1. Carbon Filters are side loading.
2. Carbon filter segments come equipped with a full height access door on the motor/drive side of the unit as part of standard construction.
3. Access doors (opposite motor/drive side, access doors (both sides) and auxiliary drain pans are all options for the carbon filter segment.
4. Viewing port in door is not available for this segment.
5. Perforated liner is available for the carbon filter segment.
6. The CF-1 segment offers a post filter option only. The CF-2 segment offers both pre and post filter options.
7. H dimension is based on standard base rail height.
YORK INTERNATIONAL

55

Segment Dimensions
FM - FILTER / MIXING BOX SEGMENT
FM - FILTER / MIXING BOX

MIXING BOX
(MB)

LD04310

DAMPER OPENING DIMENSIONS


UNIT
SIZE

35

14.88

10.44

10.13

15.13

60

14.88

9.94

16.13

22.13

80

14.88

11.44

16.13

30.13

105

14.88

11.44

19.13

39.13

120

14.88

11.94

19.13

46.13

150

14.88

13.44

19.13

56.13

170

14.88

10.94

25.13

64.13

215

20.88

17.94

22.13

55.13

250

20.88

13.94

28.13

63.13

305

20.88

12.44

31.13

78.13

360

26.88

16.44

34.13

70.13

400

26.88

17.44

34.13

78.13

500

26.88

13.44

42.13

98.13

580

32.88

16.44

47.13

92.13

660

32.88

17.94

47.13

103.13

800

32.88

6.94

65.13

125.13

1000

38.88

7.44

77.13

131.13

LD04312

All linkages
are on
drive side.

LD04311

All dimensions are approximate and not certified for construction.

FILTER / MIXING BOX DIMENSIONS (IN.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

(2")

22

26

26

26

26

26

24

30

30

32

36

36

40

44

44

52

52

(4")

24

28

28

28

28

28

26

32

32

34

38

38

40

48

48

54

54

L
B

DAMPER
HEIGHT
DAMPER
WIDTH

14.75 14.75 14.75 14.75 14.75 14.75 14.75 20.75 20.75 20.75 26.75 26.75 26.75 32.75 32.75 32.75 38.75
15

22

30

39

46

56

64

55

63

78

70

78

98

92

103

125

131

NOTES: 1. Segment has a full-height access door on the drive side of the unit for side servicing of filters.
2. View port is not available for FM segment.
3. Access doors (opposite side & both sides), auxiliary drain pans are available (except with bottom opening) and perforated liners
are all available.
4. H dimension is based on standard base rail height.

56

YORK INTERNATIONAL

FORM 100.09-EG1

MB - MIXING BOX SEGMENT


MB - MIXING BOX

MIXING BOX
(MB)

LD04313

DAMPER OPENING DIMENSIONS


UNIT
SIZE

35

14.88

10.44

10.13

15.13

60

14.88

9.94

16.13

22.13

80

14.88

11.44

16.13

30.13

105

14.88

11.44

19.13

39.13

120

14.88

11.94

19.13

46.13

150

14.88

13.44

19.13

56.13

170

14.88

10.94

25.13

64.13

215

20.88

17.94

22.13

55.13

250

20.88

13.94

28.13

63.13

305

20.88

12.44

31.13

78.13

360

26.88

16.44

34.13

70.13

400

26.88

17.44

34.13

78.13

500

26.88

13.44

42.13

98.13

580

32.88

16.44

47.13

92.13

660

32.88

17.94

47.13

103.13

800

32.88

6.94

65.13

125.13

1000

38.88

7.44

77.13

131.13

LD04315

All linkages
are on
drive side.

LD04314

All dimensions are approximate and not certified for construction.

MIXING BOX DIMENSIONS (IN.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

60

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

20

20

20

20

20

20

22

26

26

28

32

32

40

44

44

50

50

DAMPER
HEIGHT
DAMPER
WIDTH
NOTES:

14.75 14.75 14.75 14.75 14.75 14.75 14.75 20.75 20.75 20.75 26.75 26.75 26.75 32.75 32.75 32.75 38.75
15

22

30

39

46

56

64

55

63

78

70

78

98

92

103

125

131

1. MB segment must be the first segment in the direction of air flow.


2. Access doors (drive side, opposite side & both sides), viewing ports, auxiliary drain pans (except with bottom opening) and
perforated liners are all available.
3. H dimension is based on standard base rail height.

YORK INTERNATIONAL

57

Segment Dimensions
FR - RETURN FAN SEGMENT

SIDE VIEW

All dimensions are approximate and not certified for construction.

NOTES: 1. Return fan segment (FR) must be first segment in the direction of air flow, unless preceded by an (AT) segment.
2. Motor / drive may be located on either the right side (R.H.) or the left hand (L.H.) side of the unit.
3. An access door is supplied as standard on the motor / drive side of the unit.
4. Access doors (opposite motor / drive side), access doors (both sides), window in door, auxiliary drain pan, and perforated liners
are all available.
5. H dimension is based on standard base rail height.

58

YORK INTERNATIONAL

FORM 100.09-EG1

FR - SEGMENT DIMENSIONS (IN.)


UNIT DIMENSIONS

INLET DIMENSIONS

UNIT
SIZE

FAN
NUMBER

FAN
TYPE

FAN
SIZE

35

FAN 1
FAN 2
FAN 1
FAN 2
FAN 1
FAN 2
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3

FC
FC
FC
FC
FC
FC
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
AF
AF
AF
AF
AF
AF
AF
AF

9-9
9-6
10-10
9-9
12-12
10-10
15-15
12-12
12
15-15
15-11
15
18-18
15-15
15
20-20
18-18
18
20-20
18-18
20
22-22
20-20
22
20-18
25-25
22-22
25
22-20
28-28
25-25
25
22-20
28-28
25-25
28
25-22
32-32
28-28
32
27-25
32-32
30-30
32
32-32
32
36
36
40
44
36
40
44

36
36
42
42
53
53
62
62
62
70
70
70
83
83
83
86
86
86
91
91
91
91
91
91
91
103
103
103
103
103
103
103
103
113
113
113
113
125
125
125
125
125
125
125
139
139
139
139
139
139
146
146
146

42
40
44
42
46
44
46
46
46
46
46
46
48
46
46
54
48
48
54
48
54
58
54
58
54
62
58
62
58
68
62
62
58
68
62
68
62
76
68
76
68
76
72
76
76
76
82
82
88
94
82
88
94

37
37
43
43
43
43
46
46
46
46
46
46
46
46
46
52
52
52
55
55
55
61
61
61
61
64
64
64
64
73
73
73
73
73
73
73
73
81
81
81
81
95
95
95
95
95
95
113
113
113
131
131
131

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
8
8
8
8
8
8
8
8
8
8
8
8

26
26
32
32
32
32
35
35
35
35
35
35
35
35
35
41
41
41
44
44
44
50
50
50
50
53
53
53
53
62
62
62
62
62
62
62
62
70
70
70
70
81
81
81
81
81
81
81
99
99
99
117
117

41
39
43
41
45
43
45
45
45
45
45
45
47
45
45
53
47
47
53
47
53
57
53
57
53
61
57
61
57
67
61
61
57
67
61
67
61
75
67
75
67
75
71
75
75
75
81
81
87
93
81
87
93

30
30
36
36
47
47
56
56
56
64
64
64
77
77
77
80
80
80
85
85
85
85
85
85
85
97
97
97
97
97
97
97
97
107
107
107
107
119
119
119
119
119
119
119
119
133
133
133
133
133
140
140
140

60
80
105

120

150

170

215

250

305

360

400

500

580

660

800

1000

YORK INTERNATIONAL

59

Segment Dimensions
FE - EXHAUST FAN SEGMENT

LD04025
LD04026

"S" DIMENSION IS ON MOTOR / DRIVE SIDE OF FAN SEGMENT.

LD04027

LD04028

INLET DIMENSIONS (IN.)

60

UNIT
SIZE

35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

26
32
32
35
35
35
41
44
50
53
62
62
70
81
81
99
117

30
36
47
56
64
64
80
85
85
97
97
107
119
119
133
133
140

All dimensions are approximate and not certified for construction.

1 "S" DIMENSION IS ON MOTOR / DRIVE SIDE OF FAN SEGMENT.

NOTES: 1. Exhaust fan segment (FE) must be first segment in the direction of air flow.
2. Motor / drive may be located on either the right side (R.H.) or the left hand
(L.H.) side of the unit.
3. An access door is supplied as standard on the motor / drive side of the unit.
4. Access doors (opposite motor / drive side), access doors (both sides),
window in door, auxiliary drain pan, and perforated liners are all available.
5. H dimension is based on standard base rail height.

YORK INTERNATIONAL

FORM 100.09-EG1

FE - SEGMENT DIMENSIONS (IN.)


UNIT DIMENSIONS

INLET

FAN DISCHARGE DIMENSIONS

UNIT
SIZE

FAN
NUMBER

FAN
TYPE

FAN
SIZE

35

FAN 1
FAN 2
FAN 1
FAN 2
FAN 1
FAN 2
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 4
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3
FAN 1
FAN 2
FAN 3

FC
FC
FC
FC
FC
FC
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
FC
FC
AF
FC
AF
AF
AF
AF
AF
AF
AF
AF

9-9
9-6
10-10
9-9
12-12
10-10
15-15
12-12
12
15-15
15-11
15
18-18
15-15
15
20-20
18-18
18
20-20
18-18
20
22-22
20-20
22
20-18
25-25
22-22
25
22-20
28-28
25-25
25
22-20
28-28
25-25
28
25-22
32-32
28-28
32
27-25
32-32
30-30
32
32-32
32
36
36
40
44
36
40
44

36
36
42
42
53
53
62
62
62
70
70
70
83
83
83
86
86
86
91
91
91
91
91
91
91
103
103
103
103
103
103
103
103
113
113
113
113
125
125
125
125
125
125
125
139
139
139
139
139
139
146
146
146

42
40
44
42
46
44
46
46
46
46
46
46
48
46
46
54
48
48
54
48
54
58
54
58
54
62
58
62
58
68
62
62
58
68
62
68
62
76
68
76
68
76
72
76
76
76
82
82
88
94
82
88
94

37
37
43
43
43
43
46
46
46
46
46
46
46
46
46
52
52
52
55
55
55
61
61
61
61
64
64
64
64
73
73
73
73
73
73
73
73
81
81
81
81
95
95
95
95
95
95
113
113
113
131
131
131

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
8
8
8
8
8
8
8
8
8
8
8
8

13.70
13.75
14.57
13.70
15.59
14.57
17.95
16.59
16.59
17.95
17.95
17.95
16.45
17.95
17.95
16.64
19.98
19.98
19.67
19.98
19.67
21.49
20.17
21.49
20.06
22.60
21.49
22.60
21.56
25.06
23.10
23.10
21.56
25.06
23.10
25.06
22.81
27.20
25.06
27.20
24.56
27.20
26.06
27.20
27.20
27.20
29.46
29.46
30.43
39.78
29.46
30.43
39.78

9.31
9.31
9.31
9.31
9.19
9.31
10.31
10.19
10.19
10.31
10.31
10.31
6.76
10.31
10.31
5.94
10.29
10.29
8.97
10.29
8.97
9.53
9.47
9.53
10.81
9.07
9.53
9.07
11.31
9.55
9.57
9.57
11.31
9.55
9.57
9.55
11.31
9.57
9.55
9.57
11.31
9.57
11.31
9.57
9.57
9.57
9.55
9.55
9.57
12.59
9.55
9.57
12.59

18.88
16.31
19.27
18.88
19.61
19.27
16.97
19.30
19.30
16.97
16.97
16.97
14.61
16.97
16.97
13.77
14.61
14.61
13.77
14.61
13.77
13.42
13.77
13.42
14.06
12.67
13.42
12.67
14.56
12.84
12.67
12.67
14.56
12.84
12.67
12.84
13.31
14.15
12.84
14.15
14.55
14.15
14.56
14.15
14.15
14.15
13.11
13.11
13.00
14.75
13.11
13.00
14.75

11.73
8.25
13.03
11.73
15.55
13.03
18.54
15.55
15.55
18.54
14.69
18.54
21.93
18.54
18.54
25.12
21.93
21.93
25.12
21.93
25.12
28.15
25.12
28.15
22.75
31.54
28.15
31.54
25.25
35.35
31.54
31.54
25.25
35.35
31.54
35.35
28.25
39.65
35.35
39.65
31.75
39.65
36.75
39.65
39.65
39.65
44.49
44.49
49.88
63.44
44.49
49.88
63.44

10.30
10.25
11.36
10.30
13.45
11.36
15.88
13.45
13.45
15.88
15.88
15.88
18.78
15.88
15.88
25.12
18.78
18.78
25.12
18.78
25.12
28.15
25.12
28.15
24.75
31.54
28.15
31.54
27.25
35.35
31.54
31.54
27.25
35.35
31.54
35.35
31.25
39.65
35.35
39.65
34.25
39.65
36.75
39.65
39.65
39.65
44.49
44.49
49.88
46.50
44.49
49.88
46.50

12.14
13.88
14.49
15.14
18.73
19.99
26.29
27.26
27.26
29.04
29.04
29.04
30.54
35.54
35.54
32.44
32.04
32.04
34.94
34.54
34.94
35.30
34.94
35.30
39.00
41.67
41.30
41.67
39.00
37.33
41.67
41.67
39.00
42.33
46.67
42.33
45.25
42.68
48.33
42.68
48.75
42.68
52.25
42.68
49.68
49.68
47.26
47.26
44.56
43.56
50.76
48.06
50.56

60
80
105

120

150

170

215

250

305

360

400

500

580

660

800

1000

YORK INTERNATIONAL

61

Segment Dimensions
FE - EXHAUST FAN SEGMENT
AB - AIR BLENDER

LD04318

All dimensions are approximate and not certified for construction.

AIR BLENDER DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

22

28

34

36

28

30

34

36

34

36

40

42

42

48

50

48

54

NOTES: 1. Air blender should be applied immediately after the mixing box/economizer segment.
2. Access doors (drive side, opposite sides) (and both sides), viewing ports, auxiliary drain pans (located downstream of blender)
and perforated liners are all available.
3. H dimension is based on standard base rail height.

62

YORK INTERNATIONAL

FORM 100.09-EG1

EE - ECONOMIZER SEGMENT

LD04326

GO TO PAGE 65, ACCESS SEGMENT DIMENSIONS, FOR RA OPENING DIMENSIONS.

LD04327

All dimensions are approximate and not certified for construction.

ECONOMIZER SEGMENT DIMENSIONS (IN.)


UNIT SIZE

SEGMENT
DIM.

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

40

40

40

40

40

40

42

52

52

54

64

64

72

82

82

90

94

OPENING
DIM.

35

60

80

105

120

150

170

215

305

360

400

500

580

660

800

1000

1000

UNIT SIZE
250

2.75

2.75

2.75

2.75

2.75

2.75

4.75

2.75

2.75

4.75

2.75

2.75

10.8

8.75

8.8

16.8

14.8

14.9

14.9

14.9

14.9

14.9

14.9

14.9

20.9

20.9

20.9

26.9

26.9

26.9

32.9

32.9

32.9

38.9

15.1

22.1

30.1

39.1

46.1

56.1

64.1

55.1

63.1

78.1

70.1

78.1

98.1

92.1

103.1 125.1 131.1

10.4

9.94

11.4

11.4

11.9

13.4

10.9

17.9

13.9

12.4

16.4

17.4

13.4

16.4

17.9

6.9

7.4

NOTES:
1. Access doors available on upstream part of segment (drive side, opposite side & both sides), viewing ports, auxiliary drain pans
and perforated liners are all available.
2. Outside air and return air dampers are linked together.
3. H dimension is based on standard base rail height.
YORK INTERNATIONAL

63

Segment Dimensions
EF - FILTER / ECONOMIZER

LD04328

LD02334

GO TO PAGE 65, ACCESS SEGMENT DIMENSIONS, FOR RA OPENING DIMENSIONS.

LD02335

All dimensions are approximate and not certified for construction.


UNIT SIZE

SEGMENT
DIM.

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

L (2")

42

46

46

46

46

46

44

56

56

58

68

68

72

82

82

92

96

L (4")

44

48

48

48

48

48

46

58

58

60

70

70

72

86

86

94

98

OPENING
DIM.

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

D (2")

4.75

8.75

8.75

8.75

8.75

8.75

6.75

6.75

6.75

8.75

6.75

6.75

10.8

8.75

8.75

D (4")

6.75

10.8

10.8

10.8

10.8

10.8

8.75

8.75

8.75

10.8

6.75

6.75

10.8

12.8

12.75 20.75 18.75

14.9

14.9

14.9

14.9

14.9

14.9

14.9

20.9

20.9

20.9

26.9

26.9

26.9

32.9

32.88 32.88 38.88

15.1

22.1

30.1

39.1

46.1

56.1

64.1

55.1

63.1

78.1

70.1

78.1

98.1

92.1

103.1 125.1 131.1

10.4

9.94

11.4

11.4

11.9

13.4

10.9

17.9

13.9

12.4

16.4

17.4

13.4

16.4

17.94

NOTE:

64

UNIT SIZE
18.75 16.75

6.94

7.44

1. Access doors available on upstream part of segment (drive side, opposite side & both sides), viewing ports, auxiliary drain pans
and perforated liners are all available.
2. H dimension is based on standard base rail height.
3. Outside air and return air dampers are linked together.
YORK INTERNATIONAL

FORM 100.09-EG1

SA, MA, LA - ACCESS SEGMENT


SA - SHORT ACCESS SEGMENT (12")
MA - MEDIUM ACCESS SEGMENT (18")
LA - LONG ACCESS SEGMENT (24")

LD04329

All dimensions are approximate and not certified for construction.

ACCESS SEGMENT DIMENSIONS (IN.)


UNIT SIZE
DIMENSION
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

SA (12")

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

L MA (18")

18

18

18

18

18

18

18

18

18

18

18

18

18

18

18

18

18

LA (24")

24

24

24

24

24

24

24

24

24

24

24

24

24

24

24

24

24

28.5

34.5

45.5

54.5

62.5

75.5

78.5

83.5

83.5 95.75 95.75 105.75 117.75 116.3 130.3 130.3 137.3

24.1

30.1

30.1

33.1

33.1

33.1

39.1

42.1

48.1

51.1

60.1

60.1

68.1

78.3

78.3

96.3

114.3

NOTE: 1. Access segments can be used at any point in the unit configuration.
2. Dimensions X & Y define the smallest interior dimension. (segment bulkheads).
3. Access doors (drive side, opposite side & both sides), viewing ports, auxiliary drain & perforated liners are all available.
4. H dimension is based on standard base rail height.

YORK INTERNATIONAL

65

Segment Dimensions
IB - INTERNAL FACE & BYPASS DAMPER SEGMENT
IB - INTERNAL FACE & BYPASS

LD02333

All dimensions are approximate and not certified for construction.

FACE AND BYPASS DAMPER DIMENSIONS (IN.)


UNIT SIZE
DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

9.0

9.0

9.0

9.1

9.1

9.1

H1 (By-pass)

800 1000

12.7 15.0 15.0 13.1 15.3

15.3 18.6

21.0

21.0

26.8 32.3

H2 (Face Damper) 15.0 21.0 21.0 23.9 23.9 23.9 26.3 27.0 33.0 37.9 44.8

44.8 49.4

57.0

57.0

69.3 81.8

W1
DAMPER
FACE
AREA
(sq- ft)

28.0 34.0 45.0 54.0 62.0 75.0 78.0 83.0 83.0 95.0 95.0 105.0 117.0 117.3 131.3 131.3 138.3
By-pass
1.8
Damper

2.1

2.8

3.4

3.9

10.1

11.1 15.1

17.1

19.2

24.2 31.0

Face
Damper 2.9

5.0

6.6

9.0

10.3 12.4 14.2 15.6 19.0 25.0 29.5

32.6 40.1

46.5

52.0

63.2 78.5

4.8

6.9

8.7

8.7

8.7

NOTE: 1. The IB segment must be located immediately upstream of a reduced face coil.
2. When a full face coil is required downstream of the reduced face coil, add size 35 SA, size 60-170 MA, 215 LA, 250305 SA & MA, 360-400 (2) MA, 500 MA & LA, 580-800 SA, MA, & LA, 1000 (2) MA & LA.
3. H dimension is based on standard base rail height.

66

YORK INTERNATIONAL

FORM 100.09-EG1

EB - EXTERNAL FACE & BYPASS SEGMENT


EB - EXTERNAL FACE & BYPASS

LD02332

All dimensions are approximate and not certified for construction.

EXTERNAL FACE & BYPASS SEGMENT DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

26

26

26

26

26

26

26

32

32

32

38

38

38

44

44

44

50

10.44

9.94

6.94

7.44

15.13

22.13 30.13 39.13 46.13 56.13 64.13 55.13 63.13 78.13 70.13 78.13 98.13 92.13 103.13 125.13 131.13

14.88

14.88 14.88 14.88 14.88 14.88 14.88 20.88 20.88 20.88 26.88 26.88 26.88 32.88 32.88 32.88 38.88

11.44 11.44 11.94 13.44 10.94 17.94 13.94 12.44 16.44 17.44 13.44 16.44 17.94

1000

NOTE: 1. The EB Segment must be located immediately upstream of a full face coil.
2. Access doors (opposite motor / drive side), access doors (both sides) perforated liners, viewing ports and auxiliary drain pans
are all available.
3. Bypass duct is field supplied.
4. H dimension is based on standard base rail height.
YORK INTERNATIONAL

67

Segment Dimensions
FD - FACE DAMPER SEGMENT
FD - FACE DAMPER

SIDE VIEW

TOP VIEW

LD04331

All dimensions are approximate and not certified for construction.

FACE DAMPER SEGMENT DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

156

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

7.1

9.4

12.4

14.2

17.2

21.1

24.2

27.7

33.7

39.6

43.8

55.3

63.6

71.2

FACE DAMPER
AREA (sq. ft.) 4.7

87.6 109.5

NOTE: 1. The FD Segment must be located first in direction of air flow.


2. Auxiliary drain pans and perforated liners are available.
3. Access doors and viewing ports must be located in adjacent segments.
4. H dimension is based on standard base rail height.

68

YORK INTERNATIONAL

FORM 100.09-EG1

FD - FACE DAMPER SEGMENT


AT3 - SOUND ATTENUATOR (3')
AT5 - SOUND ATTENUATOR (5')
AT7 - SOUND ATTENUATOR (7')

LD04332

All dimensions are approximate and not certified for construction.

AT3, 5 & 7 SOUND ATTENUATOR SEGMENT DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

AT3

38

38

38

38

38

38

38

38

38

38

38

38

38

38

38

38

38

AT5

62

62

62

62

62

62

62

62

62

62

62

62

62

62

62

62

62

AT7

86

86

86

86

86

86

86

86

86

86

86

86

86

86

86

86

86

NOTE: 1. Access doors and viewing ports must be located in adjacent segments.
2. H dimension is based on standard base rail height.

YORK INTERNATIONAL

69

Segment Dimensions
DI - DIFFUSER SEGMENT

DI - DIFFUSER

LD04333

All dimensions are approximate and not certified for construction.

DIFFUSER DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

18

18

22

22

22

22

26

26

30

30

34

34

34

36

36

36

36

NOTES: 1. The DI segment must be immediately downstream of a rear-discharge FS segment.


2. Access doors (Drive side, opposite side & both sides), viewing ports, auxiliary drain pans, and perforated liners are all available.
3. Diffuser segment cannot be first in airstream.
4. Diffuser plate is removable through the side of the unit.
5. H dimension is based on standard base rail height.

70

YORK INTERNATIONAL

FORM 100.09-EG1

DP - DISCHARGE PLENUM SEGMENT


DP - DISCHARGE PLENUM

LD04334

All dimensions are approximate and not certified for construction.

DISCHARGE PLENUM SEGMENT DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

20

20

20

20

20

20

22

26

26

28

32

32

40

44

44

50

50

NOTE: 1. The DP segment must be the last segment in the direction of airflow.
2. Access doors (drive side, opposite side & both sides), viewing ports, auxiliary drain pans (except with bottom opening) and perforated
liners are all available.
3. H dimension is based on standard base rail height.

DISCHARGE DIMENSIONS

DISCHARGE OPENING
DIMENSIONS

LD04335

YORK INTERNATIONAL

UNIT
SIZE
35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

A
14.88
14.88
14.88
14.88
14.88
14.88
14.88
20.88
20.88
20.88
26.88
26.88
26.88
32.88
32.88
32.88
32.88

C
10.44
9.94
11.44
11.44
11.94
13.44
10.94
17.94
13.94
12.44
16.44
17.44
13.44
16.44
17.94
6.94
7.74

D
10.13
16.13
16.13
19.13
19.13
19.13
25.13
22.13
28.13
31.13
34.13
34.13
42.13
47.13
47.13
65.13
77.13

K
15.13
22.13
30.13
39.13
46.13
56.13
64.13
55.13
63.13
78.13
70.13
78.13
98.13
92.13
103.13
125.13
131.13

71

Segment Dimensions
VP - VERTICAL PLENUM SEGMENT

LD04336

All dimensions are approximate and not certified for construction.

VERTICAL PLENUM DIMENSIONS (IN.)


DIMENSION

UNIT SIZE
35

60

80

105

120

150

170

215

250

305

360

400

500

H2

37

43

43

46

46

46

52

55

61

64

73

73

81

H1

32

38

38

41

41

41

47

50

56

59

68

68

76

69

81

81

87

87

87

99

105

117

123

141

141

157

36

42

53

62

70

83

86

91

91

103

103

113

125

L
NOTES:

SAME AS FS SEGMENT
1. The VP segment must be the last segment in the direction of airflow.
2. The VP can easily be removed from the FP.
3. H2 assumes a 5" baserail. If the 8" baserail option is selected, ADD 3".

4. No access doors, viewports or auxiliary drainpan are available in the vertical discharge plenum.

DISCHARGE DIMENSIONS

72

UNIT
SIZE

35

14.88

10.44

10.13

15.13

60

14.88

9.94

16.13

22.13

80

14.88

11.44

16.13

30.13

105

14.88

11.44

19.13

39.13

120

14.88

11.94

19.13

46.13

150

14.88

13.44

19.13

56.13

14.00

35.00

4.00

170

14.88

10.94

25.13

64.13

16.00

41.00

4.00

215

20.88

17.94

22.13

55.13

18.00

44.00

4.00

250

20.88

13.94

28.13

63.13

18.00

50.00

6.00

305

20.88

12.44

31.13

78.13

22.00

53.00

4.00

360

26.88

16.44

34.13

70.13

22.00

62.00

4.00

400

26.88

17.44

34.13

78.13

24.00

62.00

4.00

500

26.88

13.44

42.13

98.13

26.00

70.00

4.00

YORK INTERNATIONAL

FORM 100.09-EG1

MZ - MULTI-ZONE SEGMENT
MZ - MULTI-ZONE DIMENSIONS

LD02457

END VIEW

SIDE VIEW

All dimensions are approximate and not certified for construction.

SEGMENT
DIMENSIONS

60

80

105

120

150

A
B
C
D
H1
H2
H
L
W
Total # of Zones
# of Zones at 6"

9
5
8.75
25.75
22
43
65
46
42
5
3

9
5
8.25
25.75
22
43
65
50
53
7
5

9
5
9.75
28.75
23
46
69
50
62
8
6

9
5
7.75
28.75
23
46
69
50
70
10
8

9
5
8.25
28.75
23
46
69
50
83
12
10

NOTES:

UNIT SIZE
170
215
9
5
9.75
34.75
24
52
76
54
86
12
10

11
5
9.25
35.75
26
55
81
56
91
13
11

250

305

360

400

500

12
5
9.25
40.75
28
61
89
60
91
13
11

12
5
9.25
43.75
29
64
93
62
103
15
13

15
5
9.25
49.75
31
73
104
68
103
15
13

15
5
8.25
49.75
31
73
104
68
113
17
15

16
5
8.25
56.75
34
81
115
70
125
19
17

1. H2 and H dimensions include the 5" baserail. If the option for 8" baserail is selected, add 3 inches to both dimensions.
2. The MZ segment must be the last segment in the direction of airflow.
3. All MZ segments can accommodate a maximum 8-Row Cold Deck and a 4-Row Hot Deck.
4. The Cold Deck will have a 4" deep, sloped drain pan.
5. A sloped drain pan with a single (1) connection is available as an option.
6. The hot deck can be easily separated from the cold deck.
7. The upstream FS segment must have a rear inverted discharge.
8. Top or Rear discharge can be selected.

YORK INTERNATIONAL

73

Segment Dimensions
EH - ELECTRIC HEAT SEGMENT
EH - ELECTRIC HEAT (24" & 36") DIMENSIONS

LD02455

TOP VIEW

SIDE VIEW

All dimensions are approximate and not certified for construction.

UNIT SIZE

DIMENSION

35

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

L (24")

24

24

24

24

24

24

24

24

24

24

24

24

24

24

24

24

24

L (36")

36

36

36

36

36

36

36

36

36

36

36

36

36

36

36

36

36

NOTES:

74

60

1. An access door is available opposite drive side of unit.


2. Electric heat control panel is located on the drive side of the unit.
3. H dimension is based on standard base rail height.

YORK INTERNATIONAL

FORM 100.09-EG1

IO - INLET / OUTLET SEGMENT


IO - INLET / OUTLET DIMENSIONS
SIDE VIEW

TOP VIEW

LD02456

DAMPER OPENING DIMENSIONS

DAMPER OPENING

UNIT SIZE

35
60
80
105
120
150
170
215
250
305
360
400
500
580
660
800
1000

14.88
14.88
14.88
14.88
14.88
14.88
14.88
20.88
20.88
20.88
26.88
26.88
26.88
32.88
32.88
32.88
38.88

10.44
9.94
11.44
11.44
11.94
13.44
10.94
17.94
13.94
12.44
16.44
13.44
13.44
16.44
17.94
6.94
7.44

15.13
22.13
30.13
39.13
46.13
56.13
64.13
55.13
63.13
78.13
70.13
98.13
98.13
92.13
103.13
125.13
131.13

All dimensions are approximate and not certified for construction.


UNIT SIZE

DIMENSION

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

37

43

43

46

46

46

52

55

61

64

73

73

81

95

95

113

131

36

42

53

62

70

83

86

91

91

103

103

113

125

125

139

139

146

20

20

20

20

20

20

22

26

26

28

32

32

40

44

44

50

50

DAMPER
HEIGHT
DAMPER
WIDTH
NOTE:

14.75 14.75 14.75 14.75 14.75 14.75 14.75 20.75 20.75 20.75 26.75 26.75 26.75 32.75 32.75 32.75 38.75
15

22

30

39

46

56

64

55

63

78

70

78

98

92

103

125

131

1. Access doors (drive side, opposite side & both sides), viewing ports, auxiliary drain pans (except with bottom opening) and
perforated liners are all available.
2. H dimension is based on standard base rail height.

YORK INTERNATIONAL

75

Physical Data
AIRPAK SEGMENT OVERALL DIMENSIONS AND WEIGHT CALCULATIONS

LD04338

All dimensions are approximate and not certified for construction.


AIRPAK AHU LENGTH & WEIGHT CALCULATIONS
SEGMENT

SEGMENT LENGTH

SEGMENT WEIGHT*

FS - Supply Fan
FP- Plenum Fan
SC - Short Coil
MC - Medium Coil
LC - Long Coil
XC - Extra-Long Coil
HO - Heating Coil
VC - Vertical Coil
IB - Internal Face & By-pass
IC - Internal Face & By-pass
EB - External Face & By-pass
FF - Flat Filters
AF - Angle Filters
BF - Bag Filters
RF - Rigid Filters
OF - Open Return Filter
HE - HEPA Filter
AB - Air Blender
FD - Face Damper
AT - Attenuator (3' & 5')
FM - Filter / Mixing Box
MB - Mixing Box
EE - Economizer
FR - Return Fan
FE - Exhaust Fan
SA - Short Access
MA - Medium Access
LA - Long Access
Dl - Diffuser
DP - Discharge Plenum
VP - Vertical Plenum
MZ - Multizone
EH - Electric Heat (24" & 36")
CF - Carbon Filter
IO - Inlet/Outlet
EF - Filter/Economizer
SEGMENT TOTALS
End Channel Dimension Add
UNIT TOTALS

TOTAL LENGTH =
TOTAL HEIGHT =

+ 6"

TOTAL WEIGHT =
TOTAL WIDTH =

NOTES: 1. Motor weight must be added to the Fan Segment weight for TOTAL Segment weight. See page 82 for motor weights.
2. Coil weight(s) must be added to the Coil segment weight for TOTAL Segment weight. See pages 78 - 82 for specific coil weights.
3. When calculating Vertical Coil Segment (VC) dimensions, the height of the VC Segment must be added to the Fan Segment - thus increasing the overall
unit height. See page 51 for Vertical Coil Dimensions. Also, you must add the coil weight to the VC Segment weight for TOTAL Segment weight.
* See page 77 for AirPak segment weights.

76

YORK INTERNATIONAL

FORM 100.09-EG1

AIRPAK SEGMENT WEIGHTS (Ibs.)


SEGMENT
FS
FR
FE

FP
SA
MA
LA
SC
MC
LC
XC
VC
HC
IC
OF
FF
AF
BF
RF
HF
FM
MB
AB
AT
Dl
DP
EB
EE
FD
IB
VP
EH
CF
MZ

FAN 1
L/lbs
FAN 2
L/lbs
FAN 3
L/lbs
FAN 4
L/lbs
PLENUM FAN 1
PLENUM FAN 2
SHORT ACCESS (12")
MEDIUM ACCESS (18")
LONG ACCESS (24")
SHORT COIL (10")
MEDIUM COIL (20")
LONG COIL (28")
EXTRA LONG COIL (36")
VERTICAL COIL (20")
HEATING COIL (8")
INTEGRAL FACE & BYPASS COIL

OPEN RETURN FILTER (2")


OPEN RETURN FILTER (4")
FLAT FILTER (2" or 4")
ANGLE FILTER (2")
ANGLE FILTER (4")
BAG FILTER (21")
BAG FILTER (32")
RIGID FILTER (12")
RIGID FILTER (32")
HEPA FILTER
FILTER/MIXING BOX (2")
FILTER/MIXING BOX (4")
MIXING BOX
AIR BLENDER
ATTENUATOR (3")
ATTENUATOR (5")
ATTENUATOR (7")
DIFFUSER
DISCHARGE PLENUM
EXTERNAL FACE & BYPASS
ECONOMIZER
FACE DAMPER
INTERNAL FACE & BYPASS
VERTICAL PLENUM
ELECTRIC HEATER (EH-2)
ELECTRIC HEATER (EH-3)
CARBON FILTER (CF-1)
CARBON FILTER (CF-2)
MULTI-ZONE (w/Hot Deck only)
(w/ Hot & Cold Deck & Diffuser (w/o coils)

EF
IO

FILTER/ECONOMIZER (2")
FILTER/ECONOMIZER (4")
IO SEGMENT
End Channels - 5" Base
End Channels - 8" Base

NOTES:

1.
2.
3.
4.

35
486
479
N/A
N/A
N/A
N/A
80
114
144
167
237
270
316
400
98

60
604
669
N/A
N/A
N/A
N/A
92
125
158
207
376
312
377
610
110

80
833
742
N/A
N/A
N/A
N/A
108
141
177
225
307
356
424
610
124

105
965
936
1038
N/A
N/A
N/A
124
165
207
272
347
416
478
722
146

120
1065
1186
1180
N/A
N/A
N/A
133
187
222
306
378
471
539
806
158

150
1277
1252
1242
N/A
882
N/A
149
197
245
339
425
517
588
944
176

170
1729
1247
1418
N/A
1106
1195
163
209
260
360
459
548
624
1106
195

UNIT SIZE
215 250 305
1863 2040 2497
1604 1880 2738
1797 1993 2679
N/A 1489 1964
1244 1435 1934
1454 1705 2045
169 174 219
225 249 289
280 317 359
398 411 536
502 558 683
584 609 760
678 705 901
1206 1398 1691
207 228 264

360
2834
2808
2751
2009
2046
2141
243
310
375
569
747
827
960
1954
275

400
3071
3068
3112
2264
2310
2703
275
330
396
614
788
899
1010
2105
296

500
3958
3874
4080
3018
3108
3457
302
384
477
753
891
1016
1261
2554
324

580
4276
4264
4392
N/A
3827
4155
328
429
530
856
1030
1173
1319
N/A
395

660
5205
4694
5181
N/A
4456
4910
353
461
586
994
1137
1288
1436
N/A
410

800
6131
5971
7028
N/A
4973
5555
374
489
605
1091
1290
1387
N/A
N/A
439

1000
6419
7057
8502
N/A
6095
7017
399
523
647
1317
1532
1751
N/A
N/A
474

N/A
11
13
111
170
181
199
300
164
178
186
258
292
222
173
242
403
564
141
185
209
374
128
111
N/A
391
482
480
546
N/A
N/A
410
444
192
74
85

N/A
14
18
128
190
215
224
327
192
211
223
318
343
263
235
294
490
686
166
206
255
431
161
145
N/A
460
567
569
648
472
1014
486
511
220
81
92

N/A
17
22
146
219
249
255
365
220
238
273
379
407
296
289
336
559
783
223
228
302
481
193
168
N/A
523
644
667
756
573
1103
564
592
242
88
101

601
28
38
181
253
281
308
430
277
301
326
448
477
365
362
385
642
898
261
276
378
546
240
195
N/A
615
754
832
942
652
1260
629
658
297
100
114

682
31
42
202
283
318
351
465
318
345
413
503
536
402
330
441
736
1030
284
310
403
624
268
215
N/A
658
807
942
1066
712
1374
725
758
325
106
121

789
36
49
228
314
340
390
525
353
387
430
571
609
455
380
485
809
1133
302
335
458
691
305
236
580
746
914
1068
1207
814
1541
807
845
365
116
133

899
46
61
239
357
398
425
549
378
413
520
628
663
506
450
526
877
1228
357
395
512
777
348
271
688
837
1020
1213
1370
879
1695
899
936
396
121
138

931
47
63
253
387
437
451
615
418
466
594
739
789
596
497
560
933
1307
419
452
608
916
395
293
778
917
1114
1311
1474
980
1901
1059
1109
478
126
143

1355
61
87
360
588
680
648
831
611
654
799
1265
1354
946
739
932
1554
2175
680
720
981
1532
590
463
1039
1197
1445
1919
2139
1298
2725
1851
1940
755
150
171

1437
76
105
400
627
726
697
895
661
718
893
1363
1462
1050
801
999
1666
2332
724
774
1057
1675
639
501
1159
1326
1594
2127
2378
1400
2912
1988
2087
840
158
181

1843
91
126
478
738
836
838
1085
772
841
1121
1740
1827
1408
1006
1125
1875
2624
864
1096
1298
2123
785
607
1412
1477
1775
2491
2777
1591
3346
2455
2542
1123
171
196

2028
95
131
554
785
934
967
1238
856
931
1267
2028
2104
1703
1169
1279
2131
2984
1065
1343
1567
2620
910
695
N/A
1605
1927
2991
3309
N/A
N/A
2945
3021
1367
N/A
200

2387
111
139
611
904
1054
1065
1303
953
1035
1420
2286
2447
1900
1250
1373
2288
3203
1150
1496
1701
2674
1022
765
N/A
1795
2147
3256
3611
N/A
N/A
3060
3221
1528
N/A
213

2615
138
190
683
1092
1323
1206
1473
1100
1194
1660
2846
3077
2260
1305
1541
2568
3595
1245
1769
1938
3123
1155
875
N/A
1980
2364
3856
4267
N/A
N/A
3709
3940
1811
N/A
220

2950
167
234
764
1187
1497
1632
2002
1292
1407
1942
3246
3513
2709
1587
1642
2737
3832
1366
2032
2121
3602
1361
1023
N/A
2384
2829
4662
5131
N/A
N/A
4157
4406
2107
N/A
237

1055
53
69
267
416
503
480
656
435
483
617
846
928
651
504
610
1017
1423
478
474
674
1074
424
325
860
969
1176
1438
1607
1046
2082
1269
1351
517
128
146

1117
52
72
333
539
618
597
768
517
563
737
1102
1179
822
648
775
1291
1808
595
615
825
1208
531
418
1000
1080
1309
1755
1953
1184
2462
1488
1565
662
146
168

Motor weights must be added to the Fan Segment weight for TOTAL Segment Weight.
Coil weight(s) must be added to the Coil Segment weight for TOTAL Segment Weight.
All filter segments include filters.
All weights are approximate.

YORK INTERNATIONAL

77

Physical Data
COIL WEIGHTS

FULL FACE
Coil Weights BDW/BDX 1/2" Full Face Coils (Dry Weight)
WEIGHT (LBS.)

ROWS FPI

10

12

78

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

28

39

45

53

59

67

77

85

99

113

132

142

170

193

209

251

299

10

28

40

47

55

61

70

81

89

103

119

139

150

180

204

222

267

318

12

29

41

48

57

63

72

84

93

108

124

146

157

189

214

234

282

336

14

29

42

50

59

66

75

87

96

112

130

152

164

199

225

246

297

354

34

49

60

72

81

94

110

123

144

169

200

217

265

302

332

403

485

10

35

52

63

76

86

100

117

131

153

180

213

232

284

324

357

433

522

12

36

54

65

80

90

105

124

138

162

191

226

246

303

345

381

463

559

14

37

56

68

83

94

110

130

146

171

202

240

261

321

367

405

493

595

40

60

74

91

104

122

144

161

190

225

267

292

360

411

455

554

670

10

42

63

79

97

110

130

154

173

204

241

287

314

388

444

492

600

726

12

43

66

83

103

117

138

164

184

217

258

307

336

416

476

528

645

781

14

45

70

87

108

123

146

173

195

231

274

327

358

444

509

565

690

837

46

70

88

110

126

149

177

199

235

280

334

366

454

520

578

706

856

10

48

74

94

117

134

160

190

214

254

302

361

396

492

564

627

766

930

12

50

78

100 125

143

170

203

229

272

324

388

426

529

607

675

826

1004

14

53

83

105 132

152

181

216

244

290

346

414

455

567

650

724

886

1078

53

82

104 131

150

179

213

240

284

339

405

445

553

634

705

862

1047

10

56

87

112 140

161

192

229

259

307

366

439

482

600

688

767

938

1140

12

59

92

119 149

172

206

246

278

330

394

472

519

647

742

827

1013

1232

14

62

98

126 158

183

219

262

296

352

421

505

556

694

796

888

1088

1324

60

94

120 151

174

208

248

281

332

397

475

523

651

747

832

1018

1238

10

63

100

129 162

187

224

268

303

360

430

516

568

708

812

906

1109

1350

12

67

106

137 173

201

241

288

326

387

463

556

612

764

877

979

1199

1460

14

70

112

146 184

214

257

308

348

414

496

596

656

820

942

1052

1289

1571

74

117

152 192

223

267

320

362

429

514

617

679

849

973

1087

1331

1621

10

78

125

163 207

240

289

346

392

466

559

670

739

924

1061

1185

1451

1769

12

83

133

175 222

258

311

373

422

502

603

724

798

999

1147

1282

1572

1916

14

88

142

186 236

276

332

399

453

538

647

777

858

1074

1234

1380

1692

2064

88

140

184 233

271

327

391

443

526

632

758

836

1046

1200

1342

1644

2003

10

94

151

198 252

293

354

424

481

572

687

825

911

1140

1309

1464

1795

2188

12 100

161

212 270

315

381

457

519

617

742

891

985

1234

1417

1586

1945

2372

14 106

171

226 289

337

408

490

557

662

797

958

1059

1328

1525

1708

2095

2556

102

164

215 274

320

386

463

525

623

749

899

993

1243

1427

1596

1956

2385

10 109

176

233 296

346

419

502

570

678

816

979

1082

1356

1558

1743

2138

2607

12 116

189

250 319

373

451

542

615

732

882

1059

1171

1469

1687

1889

2318

2828

14 123

201

267 341

399

484

581

661

786

948

1139

1260

1581

1817

2035

2498

3049

YORK INTERNATIONAL

FORM 100.09-EG1

COIL WEIGHTS

REDUCED FACE
Coil Weights BDW/BDX 1/2" Reduced Face Coils (Dry Weight)
WEIGHT (LBS.)

ROWS FPI

10

12

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

22

30

36

43

48

54

60

67

76

89

103

111

131

154

167

191

230

10

23

31

37

44

49

56

62

70

79

92

108

116

138

162

177

202

244

12

23

32

38

46

51

58

65

72

83

97

113

122

145

170

186

213

258

14

24

33

39

47

53

60

67

76

86

101

118

127

152

179

195

224

271

27

38

46

57

64

75

84

95

109

130

153

166

200

237 1

261

302

368

10

28

40

48

60

68

79

89

101

116

138

163

177

214

254

280

324

396

12

29

41

50

63

71

83

93

106

122

146

173

188

228

271

299

346

423

14

29

42

52

65

74

87

98

112

129

154

183

199

242

287

317

368

451

32

46

57

71

81

96

108

123

142

171

203

222

270

321

355

412

507

10

33

48

60

76

86

102

115

132

152

183

218

238

290

346

384

445

548

12

34

50

63

80

91

108

122

140

162

195

233

255

311

371

412

478

589

14

35

52

66

84

96

114

129

U8

172

207

248

271

332

396

440

511

630

36

53

67

85

98

116

131

151

175

211

252

277

339

405

449

523

645

10

37

56

71

91

104

124

141

162

188

228

272

299

366

438

487

567

700

12

39

59

75

96

111

132

150

173

201

244

292

321

394

471

524

611

755

14

41

62

79

102

117

140

159

184

214

260

312

342

421

504

562

654

810

42

62

79

101

117

139

157

182

211

255

305

336

412

493

548

633

788

10

43

66

84

108

125

149

169

195

227

276

330

363

446

534

595

693

857

12

46

70

89

115

133

159

181

209

243

296

355

391

481

576

642

748

925

14

48

73

94

122

141

169

193

223

260

316

380

417

515

617

689

803

994

8 47 1

71

91

117

135

161

183

212

246

299

358

394

484

580

646

753

931

10

49

75

97

125

145

173

197

228

266

324

388

427

526

630

703

819

1014

12

52

80

103

133

155

185

212

245

285

348

417

460

567

680

759

884

1096

14

55

84

109

142

165

198

226

261

305

372

447

492

608

729

815

950

1178

57

88

114

148

172

206

235

272

317

387

463

511

630

755

843

982

1217

10

61

94

123

159

185

223

254

295

343

420

503

555

685

822

918

1071

1327

12

65

100

131

170

198

239

273

317

370

452

543

599

740

888

993

1158

1437

14

68

106

139

182

212

255

292

339

396

485

582

642

795

954

1067

1246

1547

68

105

138

180

209

252

288

333

388

475

569

628

776

930

1040

1212

1503

10

73

113

148

194

226

272

311

361

421

516

619

683

845

1013

1134

1323

1641

12

77

120

159

207

242

293

335

389

454

556

668

738

913

1096

1227

1432

1778

14

82

128

169

221

259

313

358

416

486

597

717

792

982

1179

1320

1542

1915

79

123

162

211

246

297

340

394

459

562

675

745

921

1105

1236

1442

1789

10

85

132

174

228

266

322

368

427

499

611

734

811

1004

1205

1349

1574

1955

12

90

141

187

244

286

346

396

460

538

660

793

877

1086

1305

1461

1706

2119

14

95

150

199

261

306

370

424

494

577

709

852

942

1168

1404

1573

1837

2284

YORK INTERNATIONAL

79

Physical Data
COIL WEIGHTS

FULL FACE
Coil Weights CDW/CDX 5/8" Full Face Coils (Dry Weight)
ROWS FPI

10

80

WEIGHT (LBS.)
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800 1000

32

42

52

61

70

83

89

103

112

136

151

164

193

273

294

341

397

10

33

43

54

63

73

86

92

108

118

143

159

173

203

286

308

359

419

12

34

45

56

65

76

90

96

112

123

149

167

182

214

299

323

376

441

14

35

46

57

68

78

93

100

117

129

156

174

190

225

311

337

393

489

39

53

68

82

95

113

123

146

162

198

223

245

292

392

428

502

600

10

41

56

71

86

100

119

130

156

173

211

239

263

314

418

457

537

645

12

42

58

74

90

105

126

138

165

184

224

255

280

336

444

486

572

689

14

44

61

78

95

110

132

145

174

195

237

271

298

357

468

514

606

733

46

65

84

103

119

143

158

190

212

259

296

326

392

511

562

663

804

10

49

69

88

109

127

153

169

204

228

279

320

353

425

550

606

715

870

12

51

72

93

115

135

163

180

218

245

299

344

379

456

589

650

768

937

14

54

76

99

122

143

172

191

232

261

319

367

405

490

626

691

818 1003

53

76

99

123

143

173

192

233

262

320

369

407

492

630

696

823 1007

10

56

81

105

131

154

186

207

251

283

347

400

442

536

682

755

894 1096

12

59

85

112

140

164

199

221

270

305

373

432

477

579

734

813

963

14

63

90

119

149

175

211

236

289

326

400

463

512

622

783

868

1031 1293

63

92

119

149

173

210

233

283

319

390

450

498

603

761

843

998

10

67

98

127

159

187

226

252

306

346

423

489

541

657

825

915

1085 1336

12

71

103

136

170

200

242

270

330

373

456

529

585

711

890

988

1172 1447

14

75

109

144

182

213

258

288

353

399

490

578

629

765

952

1057 1256 1557

73

107

138

174

203

246

273

333

375

459

531

588

713

892

989

10

77

114

149

187

219

265

296

361

408

499

578

640

778

869

1076 1278 1578

12

82

121

159

200

235

285

318

389

440

539

626

693

843

1047

1163 1382 1710

14

86

128

169

214

251

304

340

417

472

579

673

745

907

1121

1248 1484 1842

92

134

176

222

261

316

354

433

488

599

694

768

933

1151

1279 1519 1881

10

97

144

189

240

282

342

384

470

532

652

757

838

1019

1254

1395 1658 2058

12

104

153

203

258

304

368

413

508

575

705

820

908

1106

1358

1512 1798 2235

14

110

163

216

276

325

394

443

545

618

758

883

978

1193

1456

1621 1833 2411

105

156

207

263

310

376

422

519

588

721

839

930

1133

1484

1628 1938 2394

10

113

168

224

286

336

408

460

566

642

788

918

1017

1241

1594

1773 2113 2615

12

120

180

240

308

363

441

497

613

696

854

997

1105

1349

1723

1918 2287 2836

14

128

192

257

330

389

473

534

660

750

921

1075

1192

1457

1846

2056 2456 3056

1185

1126

1173 1445

YORK INTERNATIONAL

FORM 100.09-EG1

COIL WEIGHTS

REDUCED FACE
Coil Weights CDW/CDX 5/8" Reduced Face
ROWS FPI

10

12

WEIGHT (LBS.)
35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

30

40

49

55

63

74

79

90

99

121

132

143

169

244

264

299

346

10

31

41

50

56

65

76

82

93

103

126

138

149

177

254

273

312

362

12

32

42

52

58

67

79

85

96

107

131

144

156

186

264

284

324

379

14

32

43

53

60

68

81

87

99

111

136

149

162

194

274

295

337

395

35

49

61

69

80

95

104

120

136

167

185

202

245

335

364

417

498

10

36

50

63

72

84

100

110

126

144

177

197

215

261

355

386

443

532

12

37

52

66

76

83

105

116

133

152

187

209

228

278

375

408

468

565

14

38

54

69

79

91

109

121

139

160

197

220

241

294

394

436

494

598

40

58

73

78

97

116

129

150

173

213

239

262

321

426

466

535

651

10

42

60

77

88

103

123

138

160

185

228

257

281

346

455

499

574

701

12

43

63

81

93

106

130

146

169

196

243

274

301

371

485

532

612

751

14

45

66

85

98

109

137

154

179

208

258

291

320

396

514

566

650

800

45

66

85

98

114

137

154

180

209

259

292

321

397

476

568

653

804

10

47

70

90

104

122

146

165

193

225

279

316

347

430

556

612

705

870

12

49

74

95

111

129

155

176

206

241

299

339

373

464

595

652

756

937

14

51

77

100

117

136

164

187

219

256

319

362

399

498

635

701

807

1003

53

79

102

112

137

165

186

217

253

314

355

391

434

618

682

784

971

10

56

84

108

125

147

176

200

233

273

339

384

423

515

668

738

848

1054

12

58

89

114

133

156

187

213

249

292

364

413

455

556

717

793

912

1137

14

61

93

121

141

165

199

227

266

312

389

442

488

598

766

848

976

1219

61

92

118

137

159

192

217

254

296

368

417

460

570

721

682

918

1139

10

64

98

126

146

171

206

234

273

320

398

452

499

599

780

863

994

1238

12

67

104

134

156

182

220

250

293

344

428

487

538

649

839

929 1071 1338

14

70

109

141

165

193

233

266

312

367

458

521

576

698

898

996

75

114

148

174

203

245

279

327

383

477

541

598

743

924

1023 1178 1474

10

80

122

159

186

218

263

301

353

415

517

588

649

768

1002

1111 1280 1606

12

84

130

170

199

233

281

323

377

447

557

644

711

834

1081

1200 1383 1739

14

88

137

180

211

247

299

344

405

478

597

680

772

900

1160

1288 1485 1871

85

132

172

202

237

287

329

387

456

569

648

717

895

1180

1307 1512 1884

10

90

141

185

218

255

309

356

420

496

619

706

781

936

1278

1413 1640 2050

12

96

151

198

234

274

332

383

452

535

669

765

846

1019 1397

1528 1766 2216

14

101

160

211

249

292

355

410

485

575

719

822

910

1101

1475

1639 1896 2381

95

149

196

231

271

329

379

447

529

661

755

836

1047

1400

1550 1777 2222

10

101

161

212

250

293

356

411

487

577

721

825

913

1105

1518

1683 1931 2421

12

108

172

227

269

315

383

444

526

624

781

895

99

1204

1686

1811 2085 2620

14

114

183

243

287

338

410

476

565

672

841

964

1068

1303

1754

1940 2238 2818

YORK INTERNATIONAL

1148 1437

81

Physical Data
COIL WEIGHTS
STEAM DISTRIBUTING COIL (1 ROW) FULL & REDUCED FACE COILS (DRY WEIGHT)
UNIT SIZE

COIL

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

FULL FACE

15

24

34

45

54

66

75

95

110

135

160

178

221

262

295

396

495

REDUCED FACE

11

19

26

32

37

46

55

66

81

101

118

131

168

199

225

301

372

7-1/2

FAN MOTOR HEAT (MBH)


HORSEPOWER

HEAT
10

15

20

25

30

40

50

60

75

100

FAN MOTOR

2.8

3.6

4.4

6.2

7.5

8.7

9.4

13.0

16.0

19.0

21.0

25.0

FAN

12.7

19.1

24.5

38.2

51.0

63.6

76.3

102.0

127.0

153.0

191.0

254.0

FAN & FAN MOTOR

15.5

22.7

29.9

44.4

58.5

72.3

85.7

115.0

143.0

172.0

212.0

279.0

AIR UNIT TEMPERATURE LIMITATIONS


Standard motors (Class B Insulation) -104F.
Motors with Class F Insulation -140F.
Power Wiring - 140F.
Controls & Control Wiring - 140F.
Prefilters - 150F.
High Efficiency Filters - 200F.
Fan Bearings - 120F (FC), 180F (AF)
Gasketing - 200F
AirPak unit casing limits are designed for +/ 6" W.G.

INTEGRAL FACE & BYPASS COILS


COIL
IFB - 2 ROW
IFB - 4 ROW
VIFB - 1 ROW
VIFB - 2 ROW

UNIT SIZE
305
360

105

120

150

170

205

250

310
620
N/A
N/A

330
660
N/A
N/A

400
800
N/A
N/A

488
976
N/A
N/A

488
976
N/A
N/A

562
1124
N/A
N/A

1-1/2

7-1/2

36
36
26
29
38
N/A
28
31

42
42
29
32
46
66
39
37

42
42
33
61
44
66
42
68

67
87
60
71
81
92
65
73

78
94
71
115
89
99
83
107

106
130
94
131
142
158
83
128

562
1124
N/A
N/A

755
1510
N/A
N/A

400

500

580

660

800

1000

755
1510
N/A
N/A

N/A
N/A
920
1042

N/A
N/A
1025
1220

N/A
N/A
1287
1525

N/A
N/A
1460
1719

N/A
N/A
1720
1900

MOTOR WEIGHTS (lbs.)


MOTOR
HI-EFF ODP
PREMIUM-EFF ODP
2 SPD ODP (1800/900)
2 SPD ODP (1800/1200)
HI-EFF TEFC
PREMIUM-EFF TEFC
2 SPD TEFC (1800/900)
2 SPD TEFC (1800/1200)

82

HORSEPOWER
10
15
20

25

30

40

50

60

75

100

118
126
116
192
154
200
107
222

240
309
266
295
394
358
393
334

283
300
280
296
436
436
440
470

372
415
358
400
661
661
504
516

440
414
398
N/A
686
686
538
796

591
652
N/A
N/A
790
800
N/A
N/A

670
706
N/A
N/A
840
850
N/A
N/A

750
782
N/A
N/A
1450
1475
N/A
N/A

170
217
203
298
250
259
218
223

212
250
208
270
287
290
331
361

YORK INTERNATIONAL

FORM 100.09-EG1

IC COIL CONNECTION LOCATIONS

LD04339

IC COIL CONNECTION LOCATIONS


UNIT

L J Wing

SIZE

Model #A

Steam Coil - 1 Row

Steam Coil - 2 Row

Hot Water Coil - 1 Row Hot Water Coil - 2 Row

Conn.

Conn.

Conn.

35

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Conn.
N/A

N/A

60

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

80

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

105

IFB

B-36

N/A

N/A

N/A

17.68

39.43

3" NPT

N/A

N/A

N/A

17.68

39.43

3" NPT

120

IFB

B-42

N/A

N/A

N/A

17.75

39.50

3" NPT

N/A

N/A

N/A

17.75

39.50

3" NPT

150

IFIB

B-60

N/A

N/A

N/A

17.75

39.50

3" NPT

N/A

N/A

N/A

17.75

39.50

3" NPT

170

IFB

C-60

N/A

N/A

N/A

15.75

45.00

3" NPT

N/A

N/A

N/A

15.75

45.00

3" NPT

215

IFB

C-60

N/A

N/A

N/A

17.75

47.00

3" NPT

N/A

N/A

N/A

17.75

47.00

3" NPT

250

IFB

D-60

N/A

N/A

N/A

15.75

54.25

3" NPT

N/A

N/A

N/A

15.75

54.25

3" NPT

305

IFB

D-60

N/A

N/A

N/A

17.75

56.25

3" NPT

N/A

N/A

N/A

17.75

56.25

3" NPT

360

IFB

F-60

N/A

N/A

N/A

12.54

66.42

3" NPT

N/A

N/A

N/A

12.54

66.42

3" NPT

400

IFB

F-60

N/A

N/A

N/A

12.54

66.42

3" NPT

N/A

N/A

N/A

12.54

66.42

3" NPT

500

VIFB

VC-9

16.37

73.31

3" NPT

13.56

75.06

3" NPT

16.37

73.31

3" NPT

14.06

17.06

2" NPT

580

VIFB

VD-9

18.38

87.32

3" NPT

15.56

89.06

3" NPT

18.38

87.32

3" NPT

16.06

19.06

2" NPT

660

VIFB

VD-11

18.38

87.32

3" NPT

16.06

89.00

4" NPT

18.38

87.32

3" NPT

16.06

19.06

2" NPT

800

VIFB

VE-11

19.75

106.69

3" NPT

16.06

107.06 4" NPT

19.75

106.69

3" NPT

16.06

19.06

2" NPT

1000

VIFB

VF-11

18.38

123.32

3" NPT

16.06

126.06 4" NPT

18.38

123.32

3" NPT

16.06

19.06

2" NPT

NOTES:
1. AP 35-500 size units have 5" baserails as standard and AP 580-1000 have 8" baserails as standard. Above connection locations include
standard baserail height. If, for any reason, extra height is needed for connection locations, the optional 8" baserail for AP 35-500 can
be used and / or utilize appropriate height housekeeping pad / structural steel rails at the jobsite.
2. The inlet & return connections are the same size.
3. N/A = Coil Not Available
4. Coil connections terminate inside the unit (not extended through casing) to allow flexibility to the piping contractor.
5. The dimensions listed are from the bottom of the baserail and from the upstream edge of the segment for height and length respectively.
6. The dimensions listed are the the center of the coil connections located inside the unit.

YORK INTERNATIONAL

83

Physical Data
WATER COIL CONNECTION LOCATIONS
STANDARD COILS

LD02338

CONN.
DIA.

ROWS
DEEP

1.25
1.50
2.00
2.50
3.00

2.25
2.38
2.63
2.88
3.13

1-4
5-6
8
10
12

7.38
10.00
12.63
15.25
17.63

TUBE
DIA.

1/2"
5/8"

1.31
1.50

AIRFLOW
LEFT HAND SHOWN
RIGHT HAND OPPOSITE

NOTES: 1. Dimensions Inches 1/4".


2. See page 20 for FH.

84

YORK INTERNATIONAL

FORM 100.09-EG1

WATER COIL CONNECTION LOCATIONS


TALL COILS

LD02339

CONN.
DIA.

ROWS
DEEP

1.25
1.50
2.00
2.50
3.00

2.25
2.38
2.63
2.88
3.13

1-4
5-6
8
10
12

7.38
10.00
12.63
15.25
17.63

NOTE:

1/2"
Tube
Dia.

5/8"
Tube
Dia.

TUBE
DIA.

1/2"
5/8"

1.31
1.50

AIRFLOW
LEFT HAND SHOWN
RIGHT HAND OPPOSITE

1. Dimensions Inches 1/4".

B
C
D
E
F

42.5
N/A
N/A
N/A
N/A
N/A

45
N/A
N/A
N/A
N/A
N/A

47.5
N/A
N/A
N/A
N/A
N/A

50
25.50
25.50
50.50
14.13
14.13

52.5
28.00
25.50
53.00
15.38
14.13

55
29.00
28.00
55.50
15.38
15.38

57.5
30.50
28.00
58.00
16.63
15.38

60
30.50
30.50
60.50
16.63
16.63

Coil Face Height


62.5 65 67.5 70
33.00 33.00 35.50 35.50
30.50 33.00 33.00 35.50
63.00 65.50 68.00 70.50
17.88 17.88 19.13 19.13
16.63 17.88 17.88 19.13

72.5
38.00
35.50
73.00
20.38
19.13

75
38.00
38.00
75.50
20.38
20.38

77.5
40.50
38.00
78.00
21.63
20.38

80
40.50
40.50
80.50
21.63
21.63

82.5
43.00
40.50
83.00
22.88
21.63

85
43.00
43.00
85.50
22.88
22.88

87.5
45.50
43.00
88.00
24.13
22.88

90
45.50
45.50
90.50
24.13
24.13

92.5
48.00
45.50
93.00
25.38
24.13

95
48.00
48.00
95.50
25.38
25.38

B
C
D
E
F

51
27.25
24.25
51.50
15.13
13.63

54
27.25
27.25
54.50
15.13
15.13

57
30.25
27.25
57.50
16.63
15.13

60
30.25
30.25
60.50
16.63
16.63

63
33.25
30.25
63.50
18.13
16.63

66
33.25
33.25
66.50
18.13
18.13

69
36.25
33.25
69.50
19.63
18.13

72
36.25
36.25
72.50
19.63
19.63

Coil Face Height


75
78 81
84
39.25 39.25 42.25 42.25
36.25 39.25 42.25 42.25
75.50 78.50 81.50 84.50
21.13 21.13 22.63 22.63
19.63 21.13 21.13 22.63

87
45.25
45.25
87.50
24.13
22.63

90
45.25
45.25
90.50
24.13
24.13

93
48.25
48.25
93.50
25.63
24.13

96
48.25
48.25
96.50
25.63
25.63

99
N/A
N/A
N/A
N/A
N/A

102
N/A
N/A
N/A
N/A
N/A

105
N/A
N/A
N/A
N/A
N/A

108
N/A
N/A
N/A
N/A
N/A

111
N/A
N/A
N/A
N/A
N/A

114
N/A
N/A
N/A
N/A
N/A

YORK INTERNATIONAL

85

Physical Data
STEAM COIL CONNECTION LOCATIONS

STANDARD COILS

AIRFLOW
LEFT HAND SHOWN
RIGHT HAND OPPOSITE

LD02601

NOTES: 1. Dimensions Inches 1/4".


2. Coil shown is for Horizontal Airflow.

Dim.
A

9
6.00

12
7.50

15
9.00

18
10.50

21
12.00

24
13.50

Coil Face Height


27
30
33
15.00
16.50
18.00

36
19.50

39
21.00

TALL COILS

42
22.50

45
24.00

AIRFLOW
LEFT HAND SHOWN
RIGHT HAND OPPOSITE

NOTES: 1. Dimensions Inches 1/4".


2. Coil shown is for Horizontal Airflow.

Dim.
A
B
C

86

51
15.00
28.75
40.50

54
15.00
28.75
42.00

57
16.50
31.75
45.00

60
16.50
31.75
46.50

63
18.00
34.75
49.50

66
18.00
34.75
51.00

Coil Face Height


69
72
75
19.50 19.50 21.00
37.75 37.75 40.75
54.00 55.50 58.50

48
25.50

LD02602

78
21.00
40.75
60.00

81
22.50
43.75
63.00

84
22.50
43.75
64.50

87
24.00
46.75
67.50

90
24.00
46.75
69.00

93
25.50
49.75
72.00

96
25.50
49.75
73.50

YORK INTERNATIONAL

FORM 100.09-EG1

WATER COIL DIMENSIONS


FULL FACED COOLING / HEATING

LD02340(R)

1" for AP-35 to AP-500


1-1/4" for AP-580 to AP-1000

REDUCED FACED COOLING ONLY

LD02341(R)

1" for AP-35 to AP-500


1-1/4" for AP-580 to AP-1000

REDUCED FACED HEATING ONLY

LD02342(R)

1" for AP-35 to AP-500


1-1/4" for AP-580 to AP-1000

All dimensions are in inches.


UNIT
SIZE

35

60

80

105

120

150

170

215

250

305

360

400

500

580

660

800

1000

A
B

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
9.79

3.79
15.79

4.43
16.43

4.43
16.43

4.43
16.43

4.43
16.43

YORK INTERNATIONAL

87

Physical Data
INLET CONE DIMENSIONS

FORWARD CURVED FANS

FAN DIAMETER

INLET DIMENSION A
COMEFRI

LAU

7.80

7.81

LD02603

10

8.78

8.81

12

10.24

10.38

15

12.52

12.62

18

15.47

15.50

20

16.22

16.25

22

18.19

18.06

25

20.39

21.31

27

N/A

23.94

28

22.95

N/A

30

N/A

26.38

32

25.79

N/A

36

29.02

N/A

40

32.72

N/A

All dimensions are in inches.

AIRFOIL FANS

FAN SIZE

12
15
18
20
22
25
28
32
36
40

13.75
17.44
19.34
21.67
24.41
27.51
31.06
34.86
38.67
43.29

8.54
10.83
12.01
13.46
15.16
17.09
19.29
21.65
24.02
26.89

All dimensions are in inches.

LD02507

88

YORK INTERNATIONAL

FORM 100.09-EG1

UNIT & COIL HAND SELECTION

LD04340

FAN SEGMENT ACCESS DOOR LOCATIONS

LD02617

LD02508

NOTE: Front and Front Inverted configurations are only available with the VC option.

YORK INTERNATIONAL

89

Miscellaneous Data
POWER WIRING OPTIONS
U.L. Listed Starter Panels
And Disconnects Are Available On All Sizes
As A Factory-Mounted Option.

LD02629

90

TRANSFORMER WIRING CONFIGURATION WILL BE DIFFERENT FOR DIFFERENT VOLTAGES

STARTER PANEL ONLY

STARTER PANEL WITH LIGHTING TRANSFORMER (SQ OPTION)


YORK INTERNATIONAL

FORM 100.09-EG1

Miscellaneous Data
TYPICAL ELECTRIC HEATER WIRING DIAGRAM

CAUTION: EXTERNAL MULTISTEP THERMOSTAT OR STEP CONTROLLERS MUST BE WIRED


SO THAT THE HEATER STAGES ARE TURNED ON SEQUENTIALLY STARTING WITH STAGES
1, 2, 3 . . . AND TURNED OFF SEQUENTIALLY IN THE REVERSE ORDER; i.e. . . . 3, 2, 1.

LD02466

NOTES:

1. FOR SUPPLY CONNECTIONS, USE MIN AWG COPPER CONDUCTORS


SUITABLE FOR AT LEAST 78C (167F).
2. SUPPLY VOLTAGE
, PHASE
, CONTROL VOLTAGE
.
3. FIELD TERMINALS SUITABLE FOR USE WITH
AWG COPPER CONDUCTORS ONLY.
4.THIS HEATER REQUIRES 1 SUPPLY CIRCUIT OF
KW.
5. CONTROL CIRCUIT WIRING TO BE N.E.C. CLASS 1.
POWER: (FACTORY WIRED)
POWER: (FIELD WIRED)
CONTROL (FACTORY WIRED)
CONTROL (FIELD WIRED)

YORK INTERNATIONAL

91

Guide Specifications
PART 1: GENERAL
1.01

SECTION INCLUDES

A. Central station air handling units and components as


shown, scheduled and indicated on the Drawings, including but not necessarily limited to:
1. Completely factory assembled central station air
handling unit

and complies with these specifications. If equipment


utilized is by a manufacturer other than that scheduled, the Mechanical Contractor shall be responsible
for coordinating with the General Contractor and all affected Sub-Contractors, to insure proper provisions for
installation of the furnished unit. This coordination shall
include, but not necessarily be limited to the following:
1. Structural supports for units
2. Piping size and connection/header locations

2. Chilled water [Refrigerant] connections


3. Steam [Hot water] connections
4. Electric power connections
1.02

RELATED DOCUMENTS

A. The requirements of the General Conditions, Supplementary Conditions, Division 1, and Drawings apply
to all Work herein.
B. The requirements of the following Division 15 sections
also apply to this section.

3. Electrical power requirements and wire/conduit and


over current protection sizes
4. The Mechanical contractor shall be responsible
for all costs incurred by the General Contractor,
Subcontractors, and Consultants to modify the
building provisions to accept the furnished units
B. Fan Performance Ratings: conform to AMCA 210
where applicable.
C. Sound Ratings: AMCA 300 where applicable.
D. Fabrication: conform to ARI 430.

1. Other sections as defined by the design engineer.


1.03

SYSTEM DESCRIPTION

E. Filter Media: ANSI/U.L. 900 listed, Class I or Class II,


approved by local authorities.

A. The air-handling unit manufacturers standard materials and components as indicated by published product information, designed and constructed as recommended by the manufacturer and as required for a
complete air handling unit installation as specified
herein.

F. Air coils: certify capacities, pressure drops, and selection procedures in accordance with ARI 410.

B. Air handling unit shall meet or exceed the scheduled


cooling and heating capacity, selected and rated in
accordance with ARI 410. All necessary components
for meeting scheduled performance shall be factory
assembled in accordance with ARI 430. If unit is not
ARI 430 rated, units shall be tested in accordance
with the standards to establish acceptability.

H. ISO 9002 certified.

C. Air handling units shall be provided with all necessary


tags and decals to aid in the service and/or indicate
caution areas. Electrical wiring diagrams shall be attached to the control panel access door. Lifting lugs
will be supplied to facilitate rigging of the air-handling
unit.
1.04

QUALITY ASSURANCE

A. Manufacturers: The design shown on the drawing is


based upon products of the manufacturer scheduled.
Alternate equipment manufacturers will be acceptable if equipment meets the scheduled performance
92

G. Air Handling Units: product of manufacturer regularly


engaged in production of components that issues complete catalog data on total product.

1.05

REFERENCES

A. AMCA 99 - Standard Handbook


B. AMCA 210 - Laboratory Methods of Testing Fans for
Rating Purposes
C. AMCA 300 - Test Code for Sound Rating Air Moving
Devices
D. AMCA 301 - Method of Publishing Sound Ratings for
Air Moving Devices
E. AMCA 500 - Test Methods for Louver, Dampers, and
Shutters
F. ANSI/AFBMA 9 - Load Ratings and Fatigue Life for
Ball Bearings

YORK INTERNATIONAL

FORM 100.09-EG1

G. ANSI/U.L. 900 - Test Performance of Air Filter Units


H. ARI 410 - Forced-Circulation Air Cooling and Air
Heating Coils
I. ARI 430 - Central-Station Air-Handling Units
J. NFPA 90A - Installation of Air Conditioning and
Ventilation Systems
K. SMACNA - Low Pressure Duct Construction
Standards.
1.06

SUBMITTALS

A. Submit shop drawings and product data under provisions of Division 1 Sections.

C. All openings shall be protected against damage from


shipping. Damage occurring, as a result of inadequately prepared units shall be the manufacturers
responsibility to correct. If necessary, units should
be covered with tarps or shipped in closed in trucks.
Units shall be sprayed with light oil prior to shipment
to protect the exterior surface of the unit.
1.09

ENVIRONMENTAL REQUIREMENTS

A. Do not operate units for any purpose, temporary or


permanent, until ductwork is clean, filters are in place,
bearings lubricated, and fan has been test run under
observation.
1.10

EXTRA MATERIALS

A. Furnish under provisions of Division 1 Sections.


B. Shop drawings shall indicate assembly, unit dimensions, weight loading, required clearances, construction details, and field connection details.
C. Product data shall indicate dimensions, weights,
capacities, ratings, fan performance, motor electrical
characteristics, and gauges and finishes of
materials.

B. Provide [one set for each unit] [________________]


of [fan belts] [filters] [__________].
PART 2: PRODUCTS
2.01

ACCEPTABLE MANUFACTURERS

A. York AirPak
D. Provide fan curves with specified operating point clearly
plotted.
E. Submit product data of filter media, filter performance
data, filter assembly, and filter frames.

B. McQuay Vision
C. Trane MCC
2.02

F. Submit electrical requirements for power supply wiring including wiring diagrams for interlock and control
wiring, clearly indicating factory-installed and field-installed wiring.
G. Submit manufacturers installation instructions.
1.07

OPERATION AND MAINTENANCE DATA

A. Submit operation and maintenance data under provisions of Division 1 Sections.


B. Include instructions for lubrication, filter replacement,
motor and drive replacement, spare parts lists, and
wiring diagrams.
1.08

DELIVERY, STORAGE, AND HANDLING

A. Store and protect products under provisions of Division 1 Sections.


B. Inspect for damage. Store in a clean dry place and
protect from weather and construction traffic. Handle
carefully to avoid damage to components, enclosures
and finish.
YORK INTERNATIONAL

GENERAL DESCRIPTION

A. Fabricate [draw-through] [blow-through] type double[single-] wall air-handling units suitable for the capacities as scheduled. All internal components specified
in the air handling unit schedule shall be factory furnished, installed and shipped at the same time. Units
shall be completely factory assembled (unit sizes AP215 and larger shall be split for shipment). The Engineer shall approve all third-party unit fabrications. Unit
capacity shall meet or exceed that indicated in the
schedules.
B. All necessary tags and decals to aid in the service or
indicate caution areas shall be provided. Electrical
wiring diagrams shall be attached to the control panel
access door. Installation and maintenance manuals
shall be supplied with each unit. Units shall ship in
one (1) piece wherever possible. Shipping splits can
be provided as required for installation. Lifting lugs
shall be supplied on each side of the split to facilitate
rigging and joining of segments.
C. Fabricate units with fan and coil segments, plus accessories, including but not necessarily limited to the
following (as detailed on the drawings):
93

Guide Specifications
1. Cooling coil segment
2. Heating coil segment
3. Filter segment
4. Mixing box segment

The unit shall have a frame construction consisting of


cast aluminum corner pieces and insulated galvanized
steel vertical and horizontal structural members. The
frame shall be constructed to permit complete removal
of the wall and roof panels without affecting the structural integrity of the unit. Panels shall be of one-piece
design to facilitate removal.

5. Economizer segment
6. Air blender segment
7. Face and bypass damper segment
8. Discharge plenum segment
9. Access segment
10. Diffuser segment
11. Return or exhaust air fan segment
12. Integral face and bypass coil segment
13. Sound attenuator segment
14. Electric heat segment
D. Factory fabricate and test air handling units of sizes,
capacities, and configuration as indicated and
specified.
E. Base performance on sea level conditions.
F. Units shall ship in one (1) piece where possible. Shipping splits can be provided as required for installation. Lifting lugs will be supplied on each side of the
split to facilitate rigging and joining of segments.
G. UNITS WITH SHIPPING SPLITS SHALL BE PROVIDED WITH MALE AND FEMALE CONNECTION PIECES FOR EASY FIELD ASSEMBLY. UNITS
REQUIRING FIELD INSTALLED GASKETING MUST
BE ASSEMBLED UNDER SUPERVISION BY FACTORY TRAINED AND EMPLOYED PERSONNEL
FROM THE AIR UNIT MANUFACTURER.
2.03

CASING

A. The entire unit shall be provided with a full-length,


continuous, base rail channel. Base rail channels
shall be formed of a minimum of 12 gauge galvanized steel. The base channel shall have a minimum
height of 5 inches for sizes AP-35 through AP-500,
and 8 inches for sizes AP-580 through AP-1000. All
major components shall be supported from the base.
Integral lifting lugs shall be provided. Units without a
complete and continuous base rail are not acceptable.

94

All segments shall be double- [single-] wall and shall


be constructed of G90 mill galvanized sheet steel,
formed and reinforced to provide a rigid assembly. The
exterior casing shall be constructed of a minimum 18
gauge galvanized steel. The interior lining shall be a
solid [perforated] lining of a minimum of 20 gauge
galvanized steel [minimum 18 gauge perforated aluminum liner. Perforated liner shall be used in segments as specified].
All panels shall be completely gasketed prior to shipment with a minimum of 1/4" thick and 3/4" wide
closed cell neoprene.
B. All panels shall be insulated 2"-1.5# [2"-3#] fiberglass
insulation. [Units with double wall construction shall
have a full 2" of NON-COMPRESSED insulation
throughout the entire unit. Double wall units with less
than 2" of insulation in any part of the walls, floor, roof
or drain pan are not acceptable.] The insulation shall
meet the flame and smoke generation requirements
of NFPA-90A.
C. The cooling coil segments shall have a full width, multisloped (IAQ) [single-slope] drain pan THAT EXTENDS
DOWNSTREAM of the coil to provide sufficient amount
of space to contain moisture carry-over. The unit design shall not require a drain pan in any downstream
section to contain the coil condensate. Drain pan
MUST be accessible for inspection and cleaning.
The main coil drain pan shall be sloped to assure
positive condensate drainage with a connection at one
end [connections on both sides]. The pan shall be of
double wall construction with a galvanized [stainless
steel] liner and have a minimum of 2" of
UNCOMPRESSED insulation. The pan shall have a
minimum depth (freeboard) of 4 inches. [Anti-microbial coating available as an option].
D. Coils with finned height greater than 48" shall have an
intermediate drain pan extending the entire finned
length of the coil. Cooling coils in excess of 48" in
height shall not be acceptable unless provided with
an intermediate drain pan. The intermediate pans shall
have drop tubes to guide condensate to the main drain
pan.
E. Double wall access doors shall be provided in
the fan and filter segments on the coil
header-side of the unit.

YORK INTERNATIONAL

FORM 100.09-EG1

Doors shall be of the same thickness and construction as the wall panels. A 3/8" bulb-type gasket shall
be provided around the entire door perimeter. Industrial style hinges shall permit a complete 180-degree
door swing.
Door latches shall be 2-position die-cast zinc, with
retainer, spring and o-ring. Latches that incorporate a
setscrew to attach the pawl onto the handle shaft are
not permitted. [Inside/outside latch is available as an
option].
F. Viewing windows shall be available as specified by
the engineer in all access doors. Windows will be
single [double] pane glass, and a minimum size of
four inches by eight inches.
G. [The exterior of the unit shall be completely cleaned
prior to application of paint. A prime coat shall be
applied to a minimum thickness 1.5 mils. A finish
coat of Meter-White low gloss, low VOC acrylic alkyd
enamel shall then be applied to a minimum thickness
of 2.5 mils.
When tested in accordance with ASTM B-117 the finished unit shall withstand 125-hour salt spray solution (5%) without any sign of red rust.]
H. [All remaining segments of the unit shall be provided
with auxiliary drain pans. THE AUXILIARY PANS
ALSO SHALL BE OF DOUBLE WALL CONSTRUCTION WITH DRAIN CONNECTIONS ON BOTH
SIDES OF THE UNIT.]
2.04

FANS

A. The fan segment shall be equipped with double width


double inlet (DWDI) centrifugal type wheels. All fans
shall be forward curved (FC) or airfoil (AF) as required
for stable operation.
Fan and unit performance shall be rated and certified
in accordance with ARI Standard 430. All units that
are not ARI Certified shall be witness tested at an
independent laboratory to assure performance.
All airfoil fans shall bear the AMCA Seal. Airfoil fan
performance shall be based on tests made in accordance with AMCA standards 210 and comply with the
requirements of the AMCA certified ratings program
for air and sound. In addition, all airfoil wheels shall
comply with AMCA standard 99-2408-69 and
99-2401-82.
A. The fan segment shall be equipped with single width
single inlet (SWSI) centrifugal type wheels. All fans
shall have airfoil (AF) blades. Flat plate blades shall
not be acceptable.
YORK INTERNATIONAL

All airfoil fans shall bear the AMCA Seal. Airfoil fan
performance shall be based on tests made in accordance with AMCA standards 210 and comply with
the requirements of the AMCA certified ratings program for air and sound. In addition, all airfoil wheels
shall comply with AMCA standard 99-2408-69 and
99-2401-82.
B. After the pre-balanced fan is installed in the air handler the entire fan section shall be run-balanced at
the specified speed to insure smooth and trouble-free
operation. The run balance shall include filter-in and
filter-out balancing in all three (3) planes, on both sides
of the fan assembly at the bearings.
Filter-in measurements shall be taken in the horizontal and vertical planes on the drive and opposite-drive
sides of the fan shaft. Measurements shall not exceed 2 mils.
Filter-out measurements shall be taken in the horizontal, vertical and axial planes on the drive and opposite-drive sides of the fan shaft. Measurements shall
not exceed 4 mils in the horizontal and vertical planes
and 5 mils in the axial plane.
Fans with variable frequency drives shall be balanced
for inverter duty operation. The fan will be balanced
over the entire range of fan operation (30% to 100% of
RPM). Filter-in measurements shall not exceed 5 mils
in the horizontal and vertical planes. Filter-out measurements shall not exceed 7.5 mils in the horizontal, vertical and axial planes.
Fan assemblies shall be rated for Seismic Zone 4
use.
C. Fan and fan motor shall be internally mounted and
isolated on a full width isolator support channel using
1" springs [2" springs] [1" springs with seismic restraints] [2" springs with seismic restraints] [3" springs
for use with SWSI fans only]. The fan discharge shall
be connected to the fan cabinet using a flexible connection to insure vibration-free operation. The isolator
support rail shall be structurally supported from the
unit base. Cantilever supports of the isolator support
base are unacceptable.
D. Rear, rear-inverted, top, top-inverted, bottom and
bottom-inverted discharges shall be available on all
unit and fan sizes.
E. Variable inlet vanes for airfoil wheels shall be an integral part of the inlet cone and constructed of heavy
gauge, corrosive resistant blades with zinc-plated steel
interlocking and operating mechanism. Both inlet
vanes must operate from a single shaft and be synchronized for precise control.
95

Guide Specifications
The forward curved wheel shall have variable inlet vanes
attached to the scroll of the fan. The support ring shall
be rolled angle iron. The blades shall be heavy gauge
galvanized steel. Both inlet vanes must operate from
a single shaft and be synchronized for precise control.
2.05

BEARINGS AND DRIVES

A. Fan bearings shall be self-aligning, pillow block or


flanged type regreaseable ball bearings (except Class
I forward curve fans are permanently lubricated) and
shall be designed for an average life (L50) of at least
200,000 hours. All bearings shall be factory lubricated
and equipped with standard hydraulic grease fittings
and lube lines extended to the motor side of the fan
[extended lubrication lines available as an option].
B. Fan drives shall be selected for a 1.2 [1.5] service
factor on brake horsepower (bhp) and antistatic belts
shall be furnished. All drives shall be fixed [adjustable] pitch.
C. Fan shafts shall be selected to operate well below
the first critical speed and each shaft shall be factory
coated after assembly with an anticorrosion coating.
2.06

ELECTRICAL CHARACTERISTICS AND


COMPONENTS

A. Fan motors shall be NEMA design ball bearing type


with electrical characteristics and horsepower as
specified on the schedule. Motors shall be 1750 FPM,
open drip-proof [totally enclosed, fan cooled] type.
All motors shall be high [premium] efficiency.
The motor shall be mounted on the same isolation
base as the fan. The motor shall be on a base that is
adjustable in TWO planes.
B. Fan unloading for variable-air-volume control shall be
accomplished through a factory mounted variable frequency drive (York Air-Modulator). The VFD shall bear
the same label as the unit manufacturer to assure
compatibility and proper fan balancing.
After final assembly, the fan and motor assembly shall
be factory balanced for 10 - 100% of design speed of
the air handling unit. Units that are balanced for a
specific point of operation shall be field balanced for
the entire RPM range.
After the air handling unit is installed, the VFD shall
be field commissioned by a factory trained and employed service technician.
The VFD shall be U.L. listed and comply with all applicable provisions of the National Electric Code.

96

C. Each unit shall be equipped with a power panel that


will serve as the fan motor starter(s). The panel and
all associated components shall be U.L. listed. All
wiring shall be done in accordance with the latest
N.E.C. Guidelines.
The power panel shall be enclosed in a NEMA 3R
equivalent enclosure. The panel shall contain a main
power block, single speed fan motor contactor with
overload device, three phase ambient compensated
overload heater elements, power wiring to the fan motor, two primary control fuses, one secondary control
line size fuse, terminal strip and on/off/auto switch.
Control voltage will be 115 volt.
A single panel enclosure containing supply and return
fan motor starters shall be provided with separate on/
off/auto switch when a return air fan is specified.
D. Each unit shall be equipped with a unit mounted, nonfused disconnect switch. The disconnect shall be
mounted on the exterior of the unit in a NEMA 3R
enclosure. The disconnect shall be U.L. listed.
The disconnect shall be factory wired through flexible
metal conduit to the power panel. All wiring shall be
done in accordance with the latest N.E.C. Guidelines.
E. A marine-type, vapor proof service light shall be provided in the fan segment [and additional segments].
Each light will be 100-watt service and shall be wired
to an individual switch. Lights will require a 115/1/60power source that is separate from the main power to
the unit. This will permit light operation during periods
of unit shutdown.
A single 115-volt convenience outlet shall be provided
at the light switch.
2.07

COILS

A. All cooling and/or heating coils shall be furnished to


meet the performance requirements set forth in the
schedule. All coils shall have performance certified in
accordance with ARI Standard 410.
B. All coils shall be installed on tracks for easy removal
from the air handling unit. Units that require disassembly of the unit for coil removal are not acceptable.
C. Drainable water coils shall be designed to operate at
250 PSIG design working pressure and up to 300F
and shall be tested with 325 PSIG compressed air
under water. Circuiting shall provide free and complete
draining and venting when installed in the unit. All
vent and drain connections shall be extended to the
outside of the unit casing.

YORK INTERNATIONAL

FORM 100.09-EG1

Coils shall be circuited for counter flow of air and water. Water velocities shall not to exceed 8 feet per
second and/or exceed the water pressure drops scheduled. All coils must have same end connections regardless of the number of rows deep.
D. Direct expansion coils shall be designed to conform
to the ANSI B9.1 (Safety Code for Mechanical Refrigeration) when operating with a refrigerant pressure not
exceeding 250 psig and shall be tested with 325 PSIG
compressed air under water. The completed coil, including headers, return bends and distributors shall
be charged with clean nitrogen and sealed for shipment. Each coil shall be furnished with a brass distributor with solder-type connections. Suction and discharge connections shall be on the same end regardless of rows deep.

The outer tube shall be 1" OD and the inner distribution tube will be 5/8" OD. The circuiting shall be of a
non-trapping condensate drainable design facilitating
gravity drain. The steam shall discharge in the direction of condensate flow to insure even distribution and
heat transfer through the full length of each tube.
2.08

FILTERS

A. Flat Filter Segments shall accommodate 2 [4] inch


media. Media shall be throwaway (2"), permanent
cleanable (2") or 40% [60-65%] pleated (2" or 4").
The filter frames shall be constructed of galvanized
steel and be built as an integral part of the unit. All
filter segments shall be side service with an access
door on the drive side of the unit.

E. Coil casing to be constructed of 16 gauge galvanized


steel [stainless steel]. Intermediate casing supports
shall be supplied for finned lengths that exceed 60".

B. Angle Filter Segments shall accommodate 2 [4] inch


media. Media shall be throwaway (2"), permanent
cleanable (2") or 30% pleated (2" or 4").

F. The primary surface shall be 5/8" OD copper tube,


staggered in direction of airflow. Tubes shall be mandrel expanded to form fin bond and provide burnished,
work-hardened interior surface. The tubes shall have
a minimum tube wall thickness of 0.020" [0.025"]
[0.035"].

The filter frames shall be constructed of galvanized


steel and be built as an integral part of the unit. All
filter segments shall be side service with an access
door on the drive side of the unit.

F. The primary surface shall be 1/2" OD copper tube,


staggered in direction of airflow. Tubes shall be mandrel expanded to form fin bond and provide burnished,
work-hardened interior surface. The tubes shall have
a minimum tube wall thickness of 0.016" [0.020"]
[0.032"].
G. Extended surface shall consist of die-formed, continuous, aluminum [copper] fins. The fins shall have
fully drawn collars to accurately space fins, and to
form a protective sheath for the primary surface. The
fin thickness shall be 0.006" or 0.010" [0.006"].
H. Headers shall be of heavy seamless copper tubing,
silver-brazed to tubes. Connections shall be of red
brass, with male pipe threads, silver-brazed to the
headers. A 1/4" FPT plugged, vent or drain tap will be
provided on each connection, accessible without penetrating the unit casing.
I. Coil grommets shall be provided on all coils to completely seal the area between the coil c o n n e c t i o n
and the unit casing.
J. Steam Distributing (1" OD) coils shall be designed for
operation at 100 psig pressure and a corresponding
saturated steam temperature of 338F. Coils shall be
tested with 315 PSIG compressed air under water.

YORK INTERNATIONAL

C. Open Return Filter Segments shall accommodate 2


[4] inch media. Media shall be throwaway (2"), permanent cleanable (2") or 30% pleated (2" or 4").
The filter frames shall be constructed of galvanized
steel and be built as an integral part of the unit. The
filter segment shall be front service.
D. Bag Filter Segments shall accommodate 2 [4] inch
pre-filters and high efficiency bag filters of the specified efficiency. Filter frames shall be provided with
neoprene gasketing on the leaving airside of the filter
for pressure sealing assembly.
Bag filter media shall be 21 [32] inches deep and the
efficiency shall be a minimum of 65% [85%] [95%] as
determined by ASHRAE Standard 52-76. Filter media shall be listed Class 1 under U.L. Standard 900.
The filter frames shall be constructed of galvanized
steel and be built as an integral part of the unit. All
filter segments shall be side service with an access
door on the drive side of the unit.
E. Rigid Filter Segments shall accommodate 2 [4] inch
pre-filters and high efficiency rigid filters of the specified efficiency. Filter frames shall be provided with
neoprene gasketing on the leaving airside of the filter
for pressure sealing assembly.

97

Guide Specifications
Rigid filter media shall be 12 inches deep and the
efficiency shall be a minimum of 65% [85%] [95%] as
determined by ASHRAE Standard 52-76. Filter media shall be listed Class 2 [Class 1] under U.L. Standard 900.
The filter frames shall be constructed of galvanized
steel and be built as an integral part of the unit. All
filter segments shall be side service with an access
door on the drive side of the unit.
F. A magnahelic differential pressure gauge shall be
factory installed and flush mounted on drive side to
measure the pressure drop across the [pre-filter only]
[high efficiency filter only] [pre-filter and high efficiency
filters].
2.09

APPURTENANCES

A. The Mixing Box Segment shall consist of multi-leaf,


parallel [opposed] acting blades, with inter-connecting
return air and outside air dampers. The dampers shall
be located in the top and rear [bottom and rear] [top
and bottom] of the unit.
B. The Combination Filter/Mixing Box shall combine the
filtering and mixing functions in one standard segment. Filter media shall be arranged in an angle configuration and shall provide 2" [4"] filters available as
throwaway (2"), permanent cleanable (2") or 30% efficient pleated (2" or 4").
The segment shall have a hinged access door on the
drive side of the unit. The dampers shall be located in
the top and rear [bottom and rear] [top and bottom] of
the unit.
C. The Economizer Segment shall contain three sets of
dampers to control the return, exhaust and outside
air. The economizer section shall be an integral part
of the unit.
D. The Internal Face and Bypass Segment shall be of
the internal type as called for in the schedule. The
dampers to be multi-leaf opposed acting blades interlocked with one control point. The blades to rotate in
nylon bearings providing smooth action and requiring
no lubrication. Dampers shall be segmented to limit
blade length and prevent warping, assuring a tight closure.
E. The Diffuser Segment shall be constructed with a perforated diffuser plate assuring even distribution of airflow across the entire unit air tunnel. Units with
blow-through coils and final filters (downstream of the
fan) must have a diffuser segment immediately downstream of the fan. Units with fans blowing directly into
coils and/or filters are unacceptable.
98

F. The Access Segment(s) shall be provided for placement anywhere in the unit to gain access to a particular area. The access segment shall be available
with a depth of 12", 18" or 24".
G. The Air Blender Segment shall have factory installed
air blenders as an integral part of the air-handling unit.
Blenders shall be integrated into the overall unit design to maximize the performance of the downstream
components. The blenders shall be fixed devices, with
no moving parts.
H. The Discharge Plenum shall be provided as the last
segment in direction of airflow. The plenum shall be
suitable for single or multiple discharges [horizontal]
[top] [bottom]. The Multizone Segment shall have factory installed hot and cold decks. The decks shall be
internally sealed to prevent the two air streams from
mixing. The hot deck shall be completely removable
from the cold deck without disassembly of the segment. A balance plate shall be provided as needed to
equate the pressure of the two paths. Hot and cold
deck dampers shall be provided. The hot and cold
deck dampers are to be opposite acting, secured at
90 to each other. The dampers shall be removable
from the unit and from each other. Dampers shall have
airfoil blades with Santoprene rubber seals and metalcompressible jamb seals. All bearings shall be stainless steel sleeve type.
2.10

DAMPERS

A. Dampers shall be of low leak design having stamped


16 gauge galvanized steel blades. The damper blades
shall be provided with a PVC coated polyester fabric
mechanically locked into the blade edge. The jamb is
a flexible metal, compression type. Leakage will not
exceed 7.20 CFM/square foot at 1" w.g. and 14.0
CFM/square foot at 4" w.g. The blades shall be parallel [opposed] acting.
A. Dampers will be of ultra-low leak design having airfoil
blades constructed of 14 gauge, double skin, galvanized steel. The damper blades shall be provided with
extruded vinyl edge seals and flexible metal compressible jamb seals. Leakage shall not exceed 3.70 CFM/
square foot at 1" w.g. and 8.0 CFM/square foot at 4"
w.g. The blades shall be parallel [opposed] acting.
PART 3: EXECUTION
3.01

INSTALLATION

A. Install in accordance with manufacturers instructions.


B. Install in conformance with ARI 435.
C. Assemble high-pressure units by bolting segments
together. Isolate fan segment with flexible duct connections.
YORK INTERNATIONAL

Notes

YORK INTERNATIONAL

FORM 100.09-EG1

99

P.O. Box 1592, York, Pennsylvania USA 17405-1592


Copyright by York International Corporation 2000
Form 100.09-EG1 (100)
Supersedes: 100.09-EG1 (699)
100.09-EG1 (1197)

(717) 771-7890
www.york.com

Subject to change without notice. Printed in USA


ALL RIGHTS RESERVED

S-ar putea să vă placă și