IB-51000B
Installation
Maintenance
Renewal Parts
POWELL
INDUSTRIES, INC.
REVISION 11/2003
IB-51000B
Contents
Section
I.
INTRODUCTION ............................................................................................................. 5
A.
B.
C.
D.
E.
II.
SCOPE ................................................................................................................................................. 5
PURPOSE ............................................................................................................................................ 5
CONFLICT WITH OTHER DOCUMENTS ........................................................................................... 5
OTHER ITEMS OF CAUTION .............................................................................................................. 5
INSTRUCTION BULLETINS ON THE WEB ......................................................................................... 5
SAFETY .......................................................................................................................... 5
A.
B.
C.
D.
III.
Page
GENERAL ............................................................................................................................................ 6
SPECIFIC SAFETY RULES ................................................................................................................. 6
X-RAYS ................................................................................................................................................ 6
SAFETY LABELS ................................................................................................................................. 7
DESCRIPTION ................................................................................................................ 8
A. GENERAL ............................................................................................................................................ 8
1) One-high Construction ................................................................................................................... 8
2) Two-high Construction ................................................................................................................... 8
B. SECONDARY COMPARTMENT .......................................................................................................... 9
C. PRIMARY COMPARTMENT ................................................................................................................ 9
D. VOLTAGE RATINGS ............................................................................................................................ 9
E. LIGHTING IMPULSE WITHSTAND (BIL) ............................................................................................. 9
F. FACTORY DIELECTRIC TEST ............................................................................................................ 9
G. CIRCUIT BREAKER: THE REMOVABLE ELEMENT ......................................................................... 10
H. SAFETY INTERLOCKS AND PROVISIONS ..................................................................................... 10
1) Positions Interlocks ..................................................................................................................... 10
2) Circuit Breaker Compartment Safety Provisions .......................................................................... 10
I. CIRCUIT BREAKER RACKING MECHANISM ................................................................................... 11
1) Disconnected position .................................................................................................................. 11
2) Test Position ................................................................................................................................ 12
3) Connected Position ...................................................................................................................... 12
J. CIRCUIT BREAKER OPERATION ..................................................................................................... 12
K. AUXILIARY ENCLOSURES AND COMPARTMENTS ........................................................................ 13
L. ANTI-CONDENSATION HEATERS .................................................................................................... 13
M. VOLTAGE (POTENTIAL) TRANSFORMER (ROLLOUT CARRIAGE) ............................................... 13
N. FUSE DISCONNECTING DEVICE (ROLLOUT CARRIAGE) ............................................................. 14
O. CURRENT TRANSFORMERS (THROUGH-TYPE) ........................................................................... 14
P. MAIN BUS, MAIN BUS TAPS, AND GROUNDS ................................................................................ 14
Q. PRIMARY DISCONNECT DEVICES AND SUPPORTS ..................................................................... 14
R. LIGHTING .......................................................................................................................................... 15
IV.
INSTALLATION ............................................................................................................. 15
A.
B.
C.
D.
E.
F.
GENERAL .......................................................................................................................................... 15
RECEIVING ........................................................................................................................................ 15
STORAGE .......................................................................................................................................... 15
HANDLING ......................................................................................................................................... 16
POSITIONING THE METAL-CLAD SWITCHGEAR ........................................................................... 16
1) Drawings and Diagrams ............................................................................................................... 1 6
PREPARATION OF FLOOR-ANCHORING ........................................................................................ 17
1) Indoor Metal-clad Switchgear ....................................................................................................... 17
2) Outdoor Metal-Clad Switchgear ................................................................................................... 17
IB-51000B
Contents
Section
Page
V.
OPERATION ................................................................................................................. 24
A. GENERAL .......................................................................................................................................... 24
1) Inserting the Circuit Breaker into the Compartment ...................................................................... 24
2) Removing a Circuit Breaker from the Upper Compartment .......................................................... 25
3) Electrical Operation ...................................................................................................................... 25
4) Shutters ....................................................................................................................................... 25
5) Racking Mechanism ..................................................................................................................... 27
6) Floor Pan ..................................................................................................................................... 27
7) Truck-Operated Cell Switch (TOC) (Optional) .............................................................................. 27
8) Removable Element Position Interlock (Optional) ........................................................................ 28
9) Mechanism-Operated Cell Switch (MOC) (Optional) .................................................................... 28
10) Secondary Disconnect Device ..................................................................................................... 29
11) Dummy Removable Element ....................................................................................................... 30
12) Ground and Test Device ............................................................................................................... 30
B. TEST AND INSPECTION ................................................................................................................... 31
IB-51000B
Figures
Figure
Page
Figure 1.
Figure 2.
Figure 3.
Figure 4.
Figure 5.
Figure 6.
Figure 7.
Figure 8.
Figure 9.
Figure 10.
Figure 11.
Figure 12.
Figure 13.
Figure 14.
Figure 15.
Figure 16.
Figure 17.
Figure 18.
Figure 19.
Figure 20.
Figure 21.
Figure 22.
Figure 23.
Figure 24.
Figure 25.
Figure 26.
Tables
Table
Table A.
Table B.
Table C.
Table D.
Page
PowlVac Metal-clad Switchgear ....................................................................................................... 9
Bolt Torque Values for PowlVac Metal-clad Switchgear .................................................................... 20
Accessories ........................................................................................................................................ 35
Troubleshooting Topics ........................................................................................................................ 36
IB-51000B
WARNING
THIS EQUIPMENT MAY CONTAIN HIGH VOLTAGES AND CURRENTS WHICH CAN CAUSE SERIOUS INJURY OR DEATH.
THE EQUIPMENT IS DESIGNED FOR USE, INSTALLATION, AND MAINTENANCE BY KNOWLEDGEABLE USERS OF SUCH EQUIPMENT HAVING EXPERIENCE AND TRAINING IN THE FIELD OF
HIGH VOLTAGE ELECTRICITY. THIS DOCUMENT, AND ALL OTHER DOCUMENTATION SHALL BE
FULLY READ, UNDERSTOOD, AND ALL WARNINGS AND CAUTIONS SHALL BE ABIDED BY. IF
THERE ARE ANY DISCREPANCIES OR QUESTIONS, THE USER SHALL CONTACT POWELL ELECTRICAL MANUFACTURING COMPANY IMMEDIATELY AT 1-800-480-7273.
CAUTION
Before any adjustment, servicing, parts replacement, or any other act is performed requiring
physical contact with the electrical working components or wiring of this equipment, the POWER
SUPPLY MUST BE DISCONNECTED. Failure to follow this caution may result in injury or death.
IB-51000B
IMPORTANT
The information in this Instruction Bulletin is not intended to explain all details or variations of the
metal-clad switchgear with circuit breakers, nor to provide for every possible contingency or hazard
to be met in connection with installation, testing, operation, and maintenance of the equipment. For
additional information and instructions for particular problems, which are not presented sufficiently
for the users purposes, contact Powell Electrical Manufacturing Company at 1-800-480-7273.
I.
INTRODUCTION
A. SCOPE
This instruction bulletin describes the following
PowlVac Metal-clad Switchgear: IB-50000, IB-60000,
IB-60200 PowlVac Vacuum Circuit Breakers.
B. PURPOSE
This instruction bulletin provides:
II.
SAFETY
5.
6.
7.
8.
IB-51000B
C. X-RAYS
High test voltage that is applied across the contacts of
a vacuum interrupter may generate x-rays. The
intensity of this radiation is dependent on the peak
voltage and the contact gap. At the normal operating
voltage of this equipment, the radiation levels are
negligible. At the voltages specified for testing, the test
operator shall be no closer than one meter in front of
the circuit breaker, and shall be separated from the
vacuum interrupters under test by the two thicknesses
of steel used in the construction of the circuit breaker
frame and the front cover. The circuit breaker shall be
either fully opened or fully closed when making high
potential test. Do not test the circuit breaker with
contacts partially opened.
IB-51000B
D. SAFETY LABELS
The metal-clad switchgear has danger, warning, and
caution labels attached to various locations. Read and
HAZARDOUS VOLTAGE
WILL CAUSE SERIOUS
INJURY OR DEATH.
IB-51000B
III. DESCRIPTION
A. GENERAL
The P-51000 PowlVac Metal-clad Switchgear with
vacuum circuit breaker is designed to comply with
ANSI Standard C37.20.2 and the portions of NEMA
Standard SG-5 applying to metal-clad switchgear.
Metal-clad switchgear is characterized by removable
interrupting devices, isolation of major circuit elements,
grounded metal compartments, and insulated primary
bus conductors. The metal-clad switchgear is a line-up
of one or more switchgear vertical sections known as
units, which are enclosed on all sides, top, and bottom
except for the ventilation openings, lower unit cable
penetrations, and view windows.
IB-51000B
C. PRIMARY COMPARTMENT
The primary compartment contains the high
voltage equipment and connections arranged in
compartments to offer increased safety by
minimizing personnel exposure and limiting the
effects of faults. The primary enclosure contains
control devices, current transformers, shutters,
interlocks, and a ground bus. See Figure 3 for
the location of the primary enclosure and see
Figure 4 for the equipments devices.
D. VOLTAGE RATINGS
PowlVac Metal-Clad Switchgear is available in
the standard voltage ratings listed in Table 1.
These ratings correspond to the ratings of the
circuit breaker used:
NOTE: Certain non-standard ratings are available for special applications. Consult the manufacturer for details. Refer to the specific job
drawings for detailed voltage ratings applicable to
particular switchgear line-up.
B. SECONDARY COMPARTMENT
IB-51000B
b
h
i
c
d
j
e
k
l
CAUTION
Before placing metal-clad switchgear with key
interlocks in operation, the key scheme must
be carefully checked and only the proper keys
left in the locks.
All extra keys must be removed and destroyed, or secured where they are accessible
only in an Emergency.
10
IB-51000B
e f
h
i
j
k
l
m
n
o
Figure 6. Front Description of Circuit Breaker
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
n.
o.
I.
11
IB-51000B
2) Test Position
CAUTION
3) Connected Position
In the connected position, the movable primary
disconnects and stationary primary disconnects are
engaged, the shutters are open, and the secondary
devices and control contacts are completed.
CAUTION
If the circuit breaker main closing spring is
charged, withdrawing the secondary disconnect
plug will cause this main closing spring to discharge.
e
Figure 7. Circuit Breaker Cover Removed
a.
b.
c.
d.
e.
12
IB-51000B
1.
2.
3.
4.
5.
6.
7.
L. ANTI-CONDENSATION HEATERS
Anti-condensation heaters are provided in all outdoor
metal-clad switchgear in order to facilitate drying and
to prevent condensation. It is recommended that
heaters are energized at all times; accordingly, no
switch or thermostat is provided in the heater circuit
unless specified. Each one-high basic construction is
furnished with a heater providing 125 watts of heat.
Each two-high basic construction has two such
heaters, for a total of 250 watts of heat. See Figure 8.
Heaters in circuit breaker compartments are located at
the side of the secondary compartment, below the
lower primary disconnect devices. Heaters in auxiliary
compartments are located in a similar location. In
auxiliary compartments equipped with rollouts, it may
be necessary to remove the lower rollout to gain
access to the heater.
a
Figure 8. Unit Space Heater
a.
Anti-Condensation Space
Heaters
13
IB-51000B
CAUTION
O. CURRENT TRANSFORMERS
(THROUGH-TYPE)
WARNING
Before servicing or removing current transformers, de-energize the associated primary
circuits.
P.
The main bus, main bus taps, and ground bus conductors are made of copper. The main bus, main bus
joints, and taps are insulated. This insulation provides
protection against the propagation of arcing ground
faults, but does not offer personnel protection against
shock hazards. The bolted connections are silverplated or tin-plated.
14
IB-51000B
B. RECEIVING
R. LIGHTING
For through-door and closed-door racking, all metalclad switchgear are equipped with a 120 VAC interior
light and a door-mounted light switch. When the light is
switched on, the user can read the circuit breaker
position indicator messages in the view window of the
compartment door. One of the following messages
appears: breaker test/disconnected or breaker
connected. See Figure 23 for an illustration of the
interior view light switch.
IV. INSTALLATION
For assistance with installation, maintenance, and for
ordering renewal parts, contact the Powell Apparatus
Service Division (PASD). Visit the Web site at: http://
www.powellservice.com or call 1-800-480-PASD or
713-944-6900.
C. STORAGE
If it is necessary to store the metal-clad switchgear
and equipment for any length of time, the following
precautions should be taken to prevent corrosion:
A. GENERAL
This section contains information on receiving, handling, positioning, power cable termination, grounding,
and checks to make the equipment ready for operation.
Once the assembly of the metal-clad switchgear is
completed on site, all joints and hardware, including
bus connections, structural assemblies, and control
connections, should be checked for tightness and
proper torque values. See Table B, in Section J for
torque values.
15
IB-51000B
CAUTION
APPLICABLE NATIONAL OR LOCAL CODES
OR REGULATIONS MAY REQUIRE GREATER
AISLE SPACE THAN IS NEEDED FOR OPERATION OF THE METAL-CLAD SWITCHGEAR.
IT IS THE PURCHASERS RESPONSIBILITY
TO COMPLY WITH THESE CODES AND
REGULATIONS.
Mats, screens, railing, etc. that are external to metalclad switchgear may be required to meet local code.
These items must be provided by the purchaser.
16
PREPARATION OF FLOOR-ANCHORING
IB-51000B
IB-51000B
J Bolt
CAUTION
Removable elements located in the one-high construction, or in the lower compartment of a two-high construction may be rolled into place into the switchgear
vertical section from the floor. Removable elements
located in the upper compartments of two-high construction must be lifted into place using the optional lift
truck or some other method of crane or hoist.
IB-51000B
GROUNDING
J. CONNECTIONS
19
IB-51000B
CAUTION
The operating temperature of conductors in metal-clad switchgear may
reach 105C. Any insulating material
used in the metal-clad switchgear
must be suitable for this temperature.
CAUTION
ALL EXPOSED PRIMARY BUS AND
CABLE JOINTS AND CONNECTIONS
MUST BE INSULATED FOR THE
CORRECT SYSTEM INSULATION
RATING.
20
IB-51000B
1. Fill all cavities around the contact nuts and connection bars with the Solar Compounds Corporation Solarite KM1592 compound. Form a smooth
surface for taping, thus preventing air voids.
NOTE: The compound is not an insulating medium and should not be used for that purpose.
CAUTION
Use alcohol in a well-ventilated area to avoid
inhaling vapors.
CAUTION
Do not use any commercial soap-based or
detergent-based cleaner because they may
damage the insulation material.
Do not use carbon tetrachloride.
Avoid prolonged exposure to solvent vapors.
Use solvents in a well-ventilated area.
L. PRIMARY CABLES
IB-51000B
.
through the transformer. Armor clamps are furnished
for this purpose when specified.
Potheads may be used when it is desirable to hermetically seal the end of the cable to make a moistureproof connection between the cable and switchgear
bus. A pothead also prevents seeping of oil from the
end of oil impregnated varnish cambric or paper
insulated cable.
M. INSULATING PRIMARY CABLES
TERMINATIONS
All field assembled joints for primary cable terminations should be prepared as outlined under Section J.
Connections. Upon completion of the cable termination, care must be exercised when taping the exposed
termination.
1. All taping of roof bushing should be insulated as
outlined in Figure 17.
b
Figure 18. Rear View of Two-High Unit and
Ground Fault Transformer
a. Buses
b. Ground Fault Transformer
IB-51000B
Connect the cables to the terminal blocks in accordance with the wiring diagrams furnished for the
specific job. Control cables that must pass through
any primary enclosure must be routed in the metalenclosed wireways provided within the switchgear, and
all wireway covers must be replaced.
NOTE: The compound is not an insulating medium and should not be used for that purpose.
2. Wrap joint with insulating tape provided, maintaining tension on the tape while wrapping as shown in
Figures 16 and 18. Where there are sharp angles,
apply additional layers of tape to obtain the equivalent of the insulation on the flat surfaces.
P. SURGE PROTECTOR
It is the responsibility of the purchaser to provide
suitable surge arrestors to protect the metal-clad
switchgear from damage due to lightening or other
electrical surges. When surge arrestors are furnished
as part of the switchgear, the primary cable termination
is insulated at the factory unless it must be disconnected for shipment. When this connection is completed in the field, it is necessary to insulate the
primary connection before the switchgear is energized.
Normally, PVC boots are supplied to insulate these
connections.
Q. ROOF ENTRANCE BUSHING
V.
IB-51000B
OPERATION
A. GENERAL
All removable elements, such as the circuit breakers of
the same type, rating, and duplicate wiring may be
interchanged.
During operation, all live parts are enclosed by barriers
which permits the user to perform maintenance with
maximum safety. Separate covers are provided over
each different compartment, so that any compartment
of housing may be exposed without exposing other
compartments.
All PowlVac vacuum circuit breakers are equipped for
electrical operation. A manual charging handle is
supplied as part of the accessories to permit manual
operation of the circuit breaker during maintenance.
24
IB-51000B
CAUTION
When removing the circuit breaker from the lift
truck, hold the lift truck firmly in place to
prevent the truck from rolling away from the
circuit breaker.
4) Shutters
Metal shutters (Figure 20, a) cover the primary disconnect contacts when the removable element is withdrawn from the compartment.
a
a
Figure 20. Shutters
a.
25
Shutters
b.
c.
IB-51000B
d.
e.
f.
Figure 21. Recommended Method for Lifting Circuit Breaker To Upper Cell
26
IB-51000B
CAUTION
Before inserting the circuit breaker into the
compartment, be sure that the racking crank
arms of the circuit breaker are in the fully
withdrawn position, pointing towards the
movable primary disconnects. Otherwise, the
primary disconnects, shutters, or the racking
mechanisms may be damaged.
CAUTION
Before attempting to rack a circuit breaker in or
out of compartment, make sure that the key
interlock is unlocked and in the opened position. Otherwise, the racking mechanism may be
damaged.
CAUTION
BEFORE ATTEMPTING TO RACK A REMOVABLE ELEMENT IN OR OUT OF A COMPARTMENT EQUIPPED WITH A REMOVABLE ELEMENT KEY INTERLOCK, MAKE SURE THAT
THE INTERLOCK HAS BEEN UNLOCKED AND
IS IN THE OPEN POSITION. OTHERWISE, THE
RACKING MECHANISM MAY BE DAMAGED.
b c
IB-51000B
e
a
The interlock is held by gravity in the open, or noninterlock position. When the removable element is out
of the compartment, rotating the interlock 90 clockwise, and securing it will block the insertion of a
removable element. The L-shaped bar of the key
interlock is attached to a steel plate which blocks
movement of the removable element. There are two
varieties of the steel plate. When the first variety is
used, it blocks the operation of the key interlock when
a removable element is in the connected position.
This prevents locking the removable element in the
connected position, giving the interlock a lock out
only function. The second variety of steel plate
enables the interlock to be operated with the removable element in either in the connected or disconnected position, which gives the interlock a lock in and
out function.
IB-51000B
c
d
e
f
Figure 25. Lower Mechanism-Operated Cell
Switch (MOC) and Operating Mechanism
a.
b.
c.
d.
e.
f.
c
d
b
a
IB-51000B
CAUTION
30
IB-51000B
CAUTION
DC high potential testing is not recommended;
however, if it is required, the voltage level
appropriate for the equipment, must be used.
These are 20 kV for equipment rated 4.16 kV or
38 kV for equipment rated 7.2 kV or 13.8 kV.
The DC high potential test machine must not
produce instantaneous peak voltages exceeding 50 kV. For further information on DC high
potential testing, refer to the separate instructions for PowlVac Circuit Breakers.
NOTE: Exercise extreme care to ensure that equipment, which is to be supplied by the switchgear, is not
connected while preliminary tests are conducted.
31
IB-51000B
CAUTION
IB-51000B
33
A. ORDERING INSTRUCTIONS
Order Renewal Parts from Powell Apparatus Service
Division (PASD) on the Powell Web site at http://
www.powellservice.com, or call 1-800-480-7273.
1. Always specify complete nameplate information,
including:
a. Type
b. Serial Number
c.
Rated Voltage
d. Rated Amps
e. Impulse Withstand
f.
IB-51000B
Powell Electrical Manufacturing Company recommends that only qualified technicians perform maintenance on circuit breakers. To deter a break in service,
a spare circuit breaker should be kept on site. Should
a circuit breaker need replacing, the spare circuit
breaker should be installed and the malfunctioning
circuit breaker should be returned to the factory for
reconditioning.
34
IB-51000B
Table C. Accessories
Catalog
No.
Description
Breaker Type
Standard
Racking
Closed-Door
Racking
Qty.
per
Brk.
Secondary
Disconnect
Override
Device
51555G01
51555G03
Manual
Charging
Handle
50235-P1
50235-P1
Racking Handle
50218G01
50218G01
Racking
Start
Extension
51066G01
NA
CPT
Secondary
Disconnect
90421G01P
90421G01P
PT
Secondary
Disconnect
90422G01P
90422G01P
Umbilical Cord
51702G01
51702G08
NA
51702G11
(57")
Powl-Lube-102
Powel-Lube
Lubrication
Kit
Powl-Lube-102
35
Illustration
IB-51000B
Problem
Possible Cause
Debris or foreign
objects are in/on the
circuit breaker's
primary disconnects
Debris and foreign objects are in/on the upper and lower
primary disconnects.
Check and clean the upper and lower primary
disconnect thoroughly and remove any debris
or foreign objects.
Key interlock is in
locked position
Protective or control
devices
IB-51000B
Index
Electrical Operation
26
F
A
Abnormal Conditions
34
25
14
22
B
Battery and Charging Equipment
Breaker test position
18
15
Fuse Rollout
25
34
16
13
Breaker test/disconnected
16
Heaters
14
Circuit breaker
Interlocks
Floor-anchoring preparation
Breaker connected
10
10
13
Racking mechanism
12
10
22
16, 28
20
20
One-high Construction 9
Operation 25
Outdoor equipment 19
Outdoor metal-clad switchgear 19
P
Position Interlock 29
Positioning the Metal-clad
switchgear 17
Powell Apparatus Service Division
35
Power connections 20
Power Frequency Withstand 10
PowlVac Metal-clad Switchgear
9
Preparation of floor-anchoring 18
Primary cables 22
Primary compartment 10
Primary disconnect 15
Primary enclosure 10
Proper Bolt Assembly 20
PVC boot installation 22
24
14, 15
24
D
DC high potential testing 32
Disconnecting Contacts 33
Door alignment 19
Drawings and Diagrams 17
Dummy removable elements 31
K
Key interlocks
29, 31
L
Levering-in arms
Lift truck 20
Lighting 16
Lubricants 33
37
34
Racking Mechanism 28
Receiving 16
Removable element
dummy removable element 31
ground and test device 31
Removable Element Position
Interlock 29
Rremovable elements 16
Renewal parts 16
Ring-type current transformers 15
Rollout Carriage 14, 15, 24
Roof entrance bushing 24
IB-51000B
Safety 6
Safety labels 8
Safety of personnel 6
Secondary compartment 10
Shutters 26
Special compartments 11
Standard open-door racking 28
W
Web site 16
Wrapping of joints
X
X-rays
38
22
POWELL
INDUSTRIES, INC.
REVISION 11/2003