Sunteți pe pagina 1din 28

Generators

Electrical Maintenance

Synchronous Generator:
Fundamentals & Operation
Training Module

ALSTOM (Switzerland) Ltd

ABCD

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Copyright by ALSTOM (Switzerland) Ltd 2004
This is a training module.
All mentioned / attached values and settings are for information only. The values might be
changed during commissioning.
For actual values please refer to the Instruction Manual.

CSXA220052enB.doc

Power Plant Training Center


Page 2

ABCD

Generators
Electrical Maintenance

Synchronous Generator:
Fundamentals & Operation

Table of Contents

Module Objectives ...................................................................................................................................................4


Introduction ..............................................................................................................................................................5
Generator Types...................................................................................................................................................5
Generator Fundamentals........................................................................................................................................6
Conductor in a Magnetic Field .............................................................................................................................6
Synchronous Generator .......................................................................................................................................6
Reminder ............................................................................................................................................................10
Operation ................................................................................................................................................................11
Operating Range - Power Chart ........................................................................................................................11
Other Generator Charts .....................................................................................................................................13
Generator Excitation .............................................................................................................................................14
Brushless Excitation ...........................................................................................................................................14
Static Excitation ..................................................................................................................................................15
Automatic Voltage Regulator (AVR)....................................................................................................................15
Summary.................................................................................................................................................................16
Figure 1: Salient and Non-salient Pole Generator.............................................................................................17
Figure 2: Synchronous Generators.....................................................................................................................18
Figure 3: Generation of a Single Phase Alternating Voltage ...........................................................................19
Figure 4: Principal Arrangement of Stator Windings .......................................................................................20
Figure 5: Magnetic Field in a Generator at No-load Condition........................................................................21
Figure 6: Magnetic Field in a Generator at Load Condition.............................................................................22
Figure 7: Synchronous Generator: Equivalent Circuit Diagram,
Over-excited and Under-excited Vector Diagram.............................................................................23
Figure 8: Vector Diagram and Power Chart .......................................................................................................24
Figure 9: Open Circuit and Short Circuit Curves ..............................................................................................25
Figure 10: Power Chart of a Turbogenerator: Operating Ranges and Limits ...............................................26
Figure 11: Brushless and Static Excitation Systems .......................................................................................27
Figure 12: Major Components of a Typical Brushless Excitation System ....................................................28

CSXA220052enB.doc

Power Plant Training Center


Page 3

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Module Objectives

Upon completion of this section, the trainee is able to:

Explain how voltage is induced:


in a conductor rotating in a magnetic field
in a synchronous generator.

Draw the flow of the resulting magnetic field:


at no-load operation
at load operation.

Identify 3 conditions that must be met for a generator to produce electrical voltage.

Using the power chart and generator data sheet:


Find normal operating point and mark it in the power chart.
Find for any operating points the associated approximate field & stator currents.

Explain the mechanical analogy of the load angle.

By help of power chart & the above mentioned nature of the load angle list and explain
the limiting characteristics.

Describe with a drawing and with few words the excitation system as regards:
its purpose
list and explain the working principle of the two different types of excitation
explain the two regulator types.

Explain the AVR's behaviour when the actual generator output voltage changes;
in case the excitation is:
in the auto channel or
in the manual channel.

List different types of synchronous generator and describe their main features.

CSXA220052enB.doc

Power Plant Training Center


Page 4

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Introduction

The synchronous generator is the most important machine used for producing electrical energy for the following reasons:
The output voltage or the reactive power output can be controlled by a variable DC current applied to the machine from a control unit, the Automatic Voltage Regulator (AVR).
In parallel operation with the network the reactive- and active power output can be set
independently from one another over a wide range.

Generator Types
Figures 1 & 2

Salient & Non-Salient Pole Generators


There are two basic forms of Generators which differ mainly in their rotor design:
The first, called a salient-pole machine, has protruding field poles, each pole provided
with a concentrated field winding.
This type is used mostly on hydro-electric plant.
The second type of machine (non-salient pole), generally called turbogenerator has a
smooth cylindrical rotor. The field winding is placed in slots distributed over a specific
zone on the circumference of the rotor.
This type of generator is used mostly on thermal power plants.
The turbo generator was invented in 1901 by Charles Brown of the Brown Boveri Co.
In the following we mainly refer to the 2-Pole Turbogenerator

CSXA220052enB.doc

Power Plant Training Center


Page 5

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Generator Fundamentals
Conductor in a Magnetic Field
Figure 3

If a coil is rotating in a magnetic field as shown in the Figure 3 an (alternating, induced) voltage can be measured at the sliprings.

A voltage is induced because the flux (linked with the coil) is varying with time.

d
dt

winding turns
magnetic Flux
time

Flux is proportional to the flux density B (flux per unit area) and the surface within the
coil loop.

U = W

= B dA

B
A

flux density
surface area within coil winding

If the coil is turning with uniform speed (in this homogenous field) a sinusoidal voltage is
induced.

Synchronous Generator
In praxis the construction is different than discussed above:
The armature winding (the winding in which voltage is induced) is placed in the stator.
The magnetic field is produced by the rotor which is rotating
The advantage of this approach is:
Voltage, current on the rotating part are of lower magnitude. This will effect the design of
the generator.
The magnetic field is produced by a DC current flowing through the winding in the rotor.
Through the arrangement of field winding the field over the poles has a sinusoidal shape
which is slightly stepped (valid for the turbogenerator)
The field is moving (because of its rotation) relative to the stationary stator winding
Therefore the flux through the winding is changing and a voltage is induced in the armature/ stator winding as a consequence.

Figure 4.1

Figures 4.1 & 4.2

By special arrangement of the stator windings around the circumference with


multiple winding turns per phase and
displacement of each of the three winding set by 120 degrees
a practically sinusoidal 3-phase voltage (phase displaced in time by 120 degrees) is produced.
The Figure 4.2 shows a simplified winding arrangement with three winding loops per phase.
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 6

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Synchronous Generator (continued)


Multiple Pole Generator - Operation Speed
Above we mainly referred to a two pole generator type: During one revolution every winding on the stator sees the north pole & the south pole once. With a speed of 3000 rpm we
get 50 revolutions in one second which corresponds to 50Hz of the induced voltage.
If we have more poles, e.g. four, the stator windings see two north and two south poles
during one revolution. The speed would be reduced to 1500 rpm in this case for the same grid
frequency.
Figure 5

Magnetic Field in a Generator at no load


Figure 5 shows the magnetic field at no load operation of the generator (no current flowing in
the stator windings). We see the closed magnetic circuit, through rotor, air gap and back
through stator core (shown by closed lines (circles); the total number of line would correspond to the flux).

Figure 6.1

Under load condition


As soon as the generator is on grid (the load connected to generator terminals):
the currents flowing in every phase of the stator windings generate their one magnetic
fields. The sum of the three is called the armature reaction field,
rotor and armature reaction field form the total field. It can be imagined as armature or
stator field.

Figure 6.2

Load Angle (simplified view)


The angle between the rotor pole axis and the total field axis ("stator field") is the Load Angle
. To illustrate this,
we can imagine two vectors (arrows) rotating around a centre point O: one stands for the
rotor field the other for the stator field (total resulting field).
They are strongly coupled with each other. The rotor is actually pulling the stator field
(the grid) behind.
The stator field is rotating therefore with the same speed as the rotor, called synchronous
speed.
What gave the name to this type of machine: Synchronous Generator.
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 7

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Synchronous Generator (continued)


Figure 7.1

Figure 7.2

Figure 7.3

Figure 8.1

Simplified Equivalent Circuit Diagram


In order to better understand the electrical operating behaviour of a generator, an "Equivalent
Circuit Diagram" is used. In the diagram (where only one phase is shown), the generator is
represented by
the (internal) Pole Wheel Voltage UP and

its synchronous reactance Xd.

U1 (= UN / 3) is the phase voltage of the generator and I1 the current flowing in one of
the stator windings.
(The ohmic resistance of the stator winding is very small in relation to Xd ( 0.5 .. 2 per
mil) and is therefore neglected.)

At no load
the stator current I1 is 0. The voltage Ud over Xd is therefore 0, the Terminal Voltage the
same as the Pole Wheel Voltage UP. (UP = U1).

If a load is connected to the terminals


U1 and Up is not the same any longer. There will be a phase displacement between U1
and I1.

For clarification we look at the phasor or vector diagram of two special cases (which do not
appear during normal operation):
Vector Diagram for a mere Inductive Load
First we have a pure inductive load (no ohmic resistance).
The current I1 is lagging the voltage U1 by 90 degrees (as seen from the grid).
For a mere Capacitive Load
In the second case we have a pure capacitive load connected to the generator terminals.
The current is I1 is leading the voltage U1 by 90 degrees (as seen from the grid).
Vector Diagram for a normal Operating Mode (Ohmic-Inductive Load)
Under normal operating condition the generator feeds a load composed of two parts: a bigger
ohmic part (which is e.g. converted into heat at the consumer side) and a smaller inductive
part (which is e.g. used for the magnetisation of motors). The corresponding vector diagram
is shown in the figure. The load angle with the above mentioned explanation - angle between
rotor and stator field, pulling the stator field behind - can still be seen.
Of importance is the next step:
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 8

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Synchronous Generator (continued)


Figure 8.2

Turning into Power Chart


We divide the length of the vectors (of the diagram) by the synchronous reactance Xd and
rotate the vector diagram by -90 degrees:
As a result without going into the details - we obtain, out of the voltage vector diagram, a
current vector diagram. The current vectors are adapted in such a way that they fit into the
power chart of the generator.
The Power Chart
The Power Chart represents the actual operating range of a generator.
A point within the power chart stands for a momentary operating point.
Point N in the figure represents one special point (out of many possible points): The normal operating point for which the generator is designed.
The power chart is scaled for 1 per unit (p.u.) and is valid for 1 p.u. voltage referring to
the nominal data of the generator.
(The plant specific nominal data of the generator may be seized down compared to the
original data of the generator to meet e.g. the power data of the main step up transformer).

Figure 8.2

The normal Operating Point within the Power Chart


The normal operating point N in the Power Chart has a distance from the centre 0 which
represents
the nominal Apparent Power (in 1 p.u.). Projected to the axis we can read out:
the nominal Reactive Power part on the x-axis and
the nominal Active Power part on the y-axis.
As describe above we can overlay the vector diagram of the currents:
Horizontally to the left of the centre 0 we find the No-load Field Current;
it is used to magnetise the generator (it corresponds to the field current which is needed
to maintain nominal voltage at no-load operation of the generator).
Starting point is 1/ Xd. (valid for the a Turbogenerator only).

The Nominal Field Current is found as vector from point 1/ Xd to N

and the Nominal Stator Current from point 0 to N.


Also the Load Angle and the Phase Angle (displacement between phase voltage U1
and stator current I1) is to be found in the diagram.

(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 9

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Synchronous Generator (continued)


Point N can be derived from the data sheet of the generator. Also the values for the nominal currents and the synchronous reactance can be found there.
Be aware that you have to scale the field currents and the stator current separately. This
because the current vector diagram is composed by the vectors: stator current I1 and the
other two If0' and If' which are proportional to the actual values (If0 and If).

Figure 9

To become familiar with the findings refer to the various exercises included in the training
program.

Open Circuit Characteristic


The Open Circuit Curve is measured during no-load operation.
The terminal voltage is recorded against different field current values.
The voltage at the generator output is nearly proportional to the field current, being bent
at higher voltage because the iron core becomes saturated.
Short Circuit Characteristic
The Short Circuit Curve is taken while the terminals are shorted (Terminal voltage U1 = 0).

The stator current is recorded against different field current values.


The curve is a straight line.

The two curves are highly depending on the design of the generator (and they characterise the
generator). Also the synchronous reactance can be derived from these curves.

Reminder
Conditions needed for Production of Electrical Voltage
A rotating generator rotor will produce electrical voltage if three things are present:
Magnetic field.
Conductor in the stator.
Relative motion between the two.

CSXA220052enB.doc

Power Plant Training Center


Page 10

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Operation
Operating Range - Power Chart
Figure 8.2

Data of any Operating Point


The power and current values for any operating point can be derived from the power chart the
same way as discussed above.
The operating points are normally given by their active and reactive power values or the
apparent power and power factor values (given one pair value the other can be directly
read out of the power chart).
Furthermore, from the operating point the corresponding field and stator currents can be
deduced. This simply by putting the vector lengths of the new point in relation with the
reference vectors of point N.
Refer to the exercise during training for clarification.
Accuracy of the Readings
The readings are approximate values only. The drawing resolution plays a role. Another
factor is the following: By changing the field current it is possible to regulate the reactive
power output, the terminal voltage may change as well (depending on the grid strength and
plant design). As we already know the power chart is only valid for Nominal Voltage (= 1
p.u.).
Remark: The reactive power reading would change with the square of the terminal voltage.

Figure 10.2

Overexcited Power Range


As an example we look at a generator on the grid. We follow an operating point T in the
Power Chart along an horizontal line. That means the power output at the turbine stays the
same. The manipulations for the experiment are done at the Excitation System only (from
local control panel or from remote)!
We start in the right quarter of the power chart at point T1.
The machine is overexcited, phase angle inductive, lagging, power factor positive
(> 0); the generator produces reactive power.
Only Active Power Output
If we decrease the field current we come to a point T2

where the reactive power output is zero, the phase angle = 0 (voltage and current are
in phase),
the load angle has become bigger from T1 to T2

Underexcited Power Range


If the field current is further decreased we come into the underexcited region to a point
T3 (left quarter),
the phase angle becomes leading, capacitive; the power factor negative (<0),
the load angle gets bigger.
Remark: The generator can produce or consume reactive power simply by changing the field
current.
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 11

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Operating Range - Power Chart (continued)


Figure 10.1

Underexcited Limiting Range


At the point where the load angle becomes 90 degrees (with low field current), we reach an
unstable operating point.
Remember the spring/ rubber band between rotor and stator field.
At 90 degrees the torque is undefined and the machine starts to slip ("goes out of step",
"loses" synchronism).
The regulation of the field current actually defines the coupling strength between the rotor and stator field.
To prevent this status the P/Q Limiter (or Load Angle Limiter) limits the load angle by
limiting
the reactive power Q depending on the momentary load
(according a preprogrammed curve; P/Q-Limiter, for newer Excitation Systems) or
the load angle
(one straight inclined line; Load Angle Limiter, for older Excitation Systems)
in both cases the field current is kept above a certain value by the Excitation System.
Maximum Field / Rotor Current Limitation
The field current is limited by the maximum allowed heat production in the windings (depending on the ohmic resistance, the amount of current flowing in the conductor and the
cooling efficiency of the cooling system).
The field current is normally limited at 105% of rated value (for continuous operation).
In the Power Chart this is actually marked with an arc from C to E (of 100% in length and
centre point 1/ Xd (Turbogenerator)).
Stator Current Limitation
Is the maximum allowed stator current
(depending on ohmic resistance, current flow and cooling efficiency)
normally set at 105% of its rated value;
limiting arc C-D with centre A.
Change of Current Limitations
Both Rotor and Stator Limitations may be temperature dependent (depending on the Cold
Gas Temperature (temperature of coolant at inlet)).
More over the two limiters normally have a dynamic respond characteristic. With short
time (overrated) higher currents the Generator / Excitation System can respond to demands/ faults outside of its system.
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 12

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Operating Range - Power Chart (continued)


Limitation and Protection
The above limiters are built in functions (in newer system implemented within the software) of the excitation system:
they are normally part of the automatic channel only (voltage controlled channel)
Because the manual channel
is "field current controlled" (regulation according a preset field current) and
has normally no (or only few rudimentary) limiters
special care have to be taken by the personnel to operate the generator within its operating
range by changing field current set point (during load changes a.s.o., see also chapter
Automatic Voltage Regulator)
Limiters are backed up by protection functions (beyond the limiters' range). They are implemented in
the excitation system (e.g. excitation overcurrent),
generator protection system (e.g. loss of excitation, underfrequency) or
higher control system
(with alarm or trip: stator winding temperature or hot gas temperature too high).
Triggered protection functions will initiate one or several of following measures:
deload the generator (until cause of disturbance is cleared),
take generator off grid,
deexcitate the generator,
shut down the turbine.

Other Generator Charts


V-Curve
The V-Curve shows the correlation between field and stator current
for a certain active load (normally for 25, 50, 75, 100% load; every load level represents
one curve).
At the same time it indicates the power factor levels along the curve.
Unbalanced Load Curve
The generator is designed for a symmetrical 3-phase load (three symmetrical currents).
Asymmetrical current components will produce an inverse rotating field. This induces
currents in damper winding, resulting in losses and possible overheating. It is therefore not
desired.
The unbalanced load is defined as the ratio of counter current component to the rated current, in percent. The Unbalanced Load Curve expresses this ratio over time during which
this operation is allowed at most. For continuous operation the maximum allowed ratio
lies between 6 to 8%.
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 13

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Other Generator Charts (continued)


Other Charts
There are various (with the generators data less frequently enclosed) charts. For example:
Generator efficiency (efficiency as a function of active power output & power factor)
Generator losses (as a function of active power output & power factor)
Heat dissipation (as a function of active power output & power factor)
Generator capability (active power output) versus cooling water or air inlet temperature
Chart with operating range of voltage and frequency

Generator Excitation

Purpose of Excitation
As we have seen above, we need a field current regulation to produce and regulate the magnetic field in the rotor. There are two ways to bring this current to the rotor windings:
by brushless excitation system or
by static excitation system.
The two are shortly described below.

Brushless Excitation
Figures 11 & 12

Design and Operating Principle of Brushless Excitation System


When a brushless excitation system is used, the actual field current is produced by an
exciter machine:
an armature machine coupled to the generator shaft
(Armature: is the part of the machine where voltage is induced).
The exciter machine has a 3-phase winding in the rotor and a DC field winding in the
stator.
The induced voltage, current in the rotor is rectified by rotating diodes (also on the rotor) and the resulting DC current is fed to the field winding of the main generator.
The excitation system (AVR) feeds the stationary field winding of the exciter machine.
The regulator is either supplied
from the generator terminals (via excitation transformer) or
from a pilot exciter (permanent generator) located at the end of the generator shaft.
The terminal voltage is therefore indirectly regulated.
The control circuit has a relative big time constant
(compared to the static excitation system; see on the following page)

CSXA220052enB.doc

Power Plant Training Center


Page 14

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Static Excitation
Figure 11

Working Principle
In this case the field current is supplied to the rotor winding by the static excitation system
via brushes an slip-ring devices.
The excitation is usually shunt supplied, that means it is fed via the excitation transformer from its own generator terminals.
The rectifier is composed of one or more thyristor bridges (in parallel). Therefore its
name: Static, no moving parts.
The static excitation system has a faster dynamic response characteristic than the brushless
excitation system.
The ceiling voltage required (max. needed voltage) for the generator rotor is determined
by the ratio of the excitation transformer which has an influence on the response time of
the excitation system.

Automatic Voltage Regulator (AVR)

Figure 11

The term is a bit misleading because most of the time it is used for the whole controller system (either voltage or field current controlled).
Automatic Voltage Regulator (AVR)
With the actual meaning: the automatic voltage controller; in most cases referred to as Auto
Channel.
It regulates the generator terminal voltage to a given set point value.
If external factors changes (as e.g. load or grid conditions), the AVR automatically adjusts the field current to reach the preset voltage value.
The AVR may be superimposed by a
power factor controller (maintaining a given power factor) or
reactive power controller (maintaining a given power factor).
The superimposed regulator acts on the AVR-set point and is slower than the AVR
(Continued next page)

CSXA220052enB.doc

Power Plant Training Center


Page 15

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Automatic Voltage Regulator (AVR) (continued)


Field Current Regulator (FCR)
The field current regulator or referred to as manual channel.
It regulates the field current to a constant value given by a set point regardless of the generator terminal voltage.
If the load increases for example the reactive power output drops simultaneously.
The controller consequently cannot
respond to disturbances in the grid (e.g. voltage breakdown)
neither can it follow up- & down-loading of the turbine automatically.
The Manual Channel is
for emergency or maintenance purpose.
It has no automatic limiting characteristics (to keep within the allowed operating range)
as the auto channel does.

Summary

This section gave an overview of the generator fundamentals in such a way that the operating
range and limiting characteristics of the generator can be understood and applied in the
field. Further it explained rudimentary the different types of Synchronous Generators and
Excitation Systems.
To ensure that you understand the material covered, review each question in the Objectives
(page 4).

CSXA220052enB.doc

Power Plant Training Center


Page 16

Generators
Electrical Maintenance

Rotor Winding

Air-Gap

Synchronous Generator:
Fundamentals & Operation

Power Plant Training Center


Page 17

90

S
Rotor Pole

CSXA400353.cdr

ABCD

Non-Salient Pole Generator


Salient Pole Generator

Figure 1: Salient and Non-salient Pole Generator

Stator Conductors

CSXA220052enB.doc

Quadrature
Axis
Quadrature
Axis

Direct Axis
Stator Core
Direct Axis

Generators
Electrical Maintenance

Three phase synchronous


Turbogenerator (air-cooled)
(non-salient poles)

Synchronous Generator:
Fundamentals & Operation

Power Plant Training Center


Page 18

CSXA400354

ABCD
Figure 2: Synchronous Generators

CSXA220052enB.doc

Three phase synchronous


Hydrogenerator
(salient poles)

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Figure 3: Generation of a Single Phase Alternating Voltage

U: Induced voltage
f : Magnetic flux

Coil
Magnet

Sliprings

30

60

90

120

150

180

210

240

270

300

330

360

Induced voltage in function of angle or time


Magnetic flux linked with the coil

u= U x sin a
CSXA400356.cdr

CSXA220052enB.doc

Power Plant Training Center


Page 19

Rotor
field

Figure 4.1

n1

n1

phase 1
phase 2
Stator
windings

phase 3

S
2 Tp
3
120

Generation of a 3 phase voltage


by the rotating rotor field

U1

U2
V1

W1

"Inner surface"
of each loop are added together
CSXA400357.cdr

Synchronous Generator:
Fundamentals & Operation

Power Plant Training Center


Page 20

Equally drawn conductors


of stator belong to one phase

Generators
Electrical Maintenance

Tp
3

Tp
180

ABCD

Sinusoidal field of rotor is moving


relative to the stationary stator winding
(the curve is actually slightly stepped)

n1

Figure 4: Principal Arrangement of Stator Windings

CSXA220052enB.doc

Figure 4.2

ABCD

Generators
Electrical Maintenance

Synchronous Generator:
Fundamentals & Operation

Figure 5: Magnetic Field in a Generator at No-load Condition

Pole axis

Field axis

Stator

Slots containing
stator windings

Cooling holes

Slots containing
rotor windings
Rotor
Magnetic flux

Rotation of rotor
CSXA400358.cdr

CSXA220052enB.doc

Power Plant Training Center


Page 21

CSXA220052enB.doc

Rotor Field
Turbine/ Generator
"pulling load behind"

Load
angle

Armature Field or
"Stator Field"
Grid / Load

dd

Synchronous Generator:
Fundamentals & Operation

CSXA400359.cdr

Figure 6.1

Generators
Electrical Maintenance

Up

Power Plant Training Center


Page 22

Figure 6.2

ABCD

Coupling like spring


or rubber band

U1

Pole axis

Figure 6: Magnetic Field in a Generator at Load Condition

Field axis

angle
Load

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Figure 7: Synchronous Generator: Equivalent Circuit Diagram, Over-excited


and Under-excited Vector Diagram
Figure 7.1 Synchronous Generator: Equivalent Circuit Diagram
j Xd I1

I1

Xs

^
=

I1

If

If

Im
Ud

U1

Up

Xh

U1

RF

If

UF

Xs : Stray Reactance
Xh : Main Reactance

Xd : Synchronous Reatance
Xd= j ( Xs + Xh)

Figure 7.2 Over-excited Vector Diagram


(with inductive load only)

Figure 7.3 Under-excited Vector Diagram


(with capacitive load only)

Ud = j Xd I1

Ud = j Xd I1
Up

U1

U1

Up

j
j

I1

Ud

inductive
load

U1*

I1

Up

U1

( Generator working as capacity )

U1*

I1

Up

U1

( Generator working as inductivity )

seen from the consumer side


I1
Grid/ Load:
inductive
j = +90

Ud

capacitive
load

I1

seen from the consumer side

U1*

U1*

j = -90

I1 leading U1 *

I1 lagging U1 *
Gen. produces reactive power (Q

I1

Grid/ Load:
capacitive

O)

Gen. consumes reactive power (Q O)


CSXA400360.cdr

CSXA220052enB.doc

Power Plant Training Center


Page 23

Figure 8.2
If = Im + I1
Ud

I1

Xs

If

If
Im

Up

U1

Sn = 1p.u.

Uf

N
U1

IfI =

Up
Xd

1
Xd

Rotation by -90
with U1 = 1 per unit (p.u.)

Up

If ~
I

U1

1
Xd
U1
= IfoI
Xd

I f=

ur
dc
fiel

ren

I1 stator current

Ifo = Im

1 Q=

reactive power

Ifo = no load field current

overexcited
underexcited
lagging
leading
at consumer side/grid at consumer side/grid
I lags U
I leads U
* Valid for a Turbogenerator)

CSXA400361.cdr

Synchronous Generator:
Fundamentals & Operation

1
Xd

IfoI ~

Generators
Electrical Maintenance

Xd I

Rf

P = active power

1
Xd

Ud = j

If

Xh

U1

ABCD

Power Plant Training Center


Page 24

Figure 8: Vector Diagram and Power Chart

CSXA220052enB.doc

Figure 8.1

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Figure 9: Open Circuit and Short Circuit Curves


G

Stator voltage
Stator current

lin
e

ur
a

ti o

Ga
p

lin

p.u.

Sa
t

1.50

n circ
Ope

K1

1.00

uit curv

or t
Sh

ci

e
ur v
it c
u
rc

0.50

A
0.00

B
0.50

1.00

D
1.50

2.00

Field current
p.u.

Rating of a typical turbogenerator


Effective power
Appearent power
Stator voltage
Stator current
No load field current

500 MW
588 MVA
22'000 V = 1 p.u.
15'440 A = 1 p.u.
1'550 A = 1 p.u.

Stator armature leakage reactance

xa = 0.195 p.u.

Saturated synchronous reactance

AD = 2.450 p.u.
AB
AD = 2.080 p.u.
AC

No- load field current

AC = 1550 AMPS

Short-circuit field current

AD = 3220 AMPS

Short-circuit ratio

AC = 0.481
AC

Unsaturated synchronous reactance

CSXA400362.cdr

CSXA220052enB.doc

Power Plant Training Center


Page 25

Pw : Active power
Iaw : Active curent

Limit of stator current

h ~ If
Ep
= Xd
If*

Ifn~
I

Limit of rotor current

Ign

Ig

0.5

Ifn

T2

T3

T1
I

j
d
-1

1
Xd
" underexcited"
Leading Power Factor (PF O)

A
0

0.5

Pa : Reactive power
1 p.u. I aq: Reactive current

1
Xd

If

Ig

A
0

0.5

Pa
1 p.u.Iaq

" overexcited"
Lagging Power Factor (PF O)

d
j

: Load angle

: Phase angle

Ifn : Nominal field current

PF : Power factor (=cos


Xd

: Field current

)j

: Synchronous reactance

Ig
Ig

: Stator current
n

: Nominal generator current

CSXA400363.cdr

Synchronous Generator:
Fundamentals & Operation

Power Plant Training Center


Page 26

Maximum turbine
power

0.5

1.0 p.u.

Generators
Electrical Maintenance

1.0 p.u.

ABCD

Theoretical static
stability limit

Pw
Iaw

Figure 10: Power Chart of a Turbogenerator: Operating Ranges and Limits

CSXA220052enB.doc

Practical static
stability limit

Generators
Electrical Maintenance

ABCD

Synchronous Generator:
Fundamentals & Operation

Figure 11: Brushless and Static Excitation Systems

Generator
circuit breaker

Brushless Excitation System

Excitation
transformer

Automatic
voltage regulator

AVR

Rectifier

Rotating
rectifier

Generator
circuit breaker

Static Excitation System

Excitation
transformer

Automatic
voltage regulator

AVR

Rectifier

Field
breaker
G
3~

CSXA400364.cdr

CSXA220052enB.doc

Power Plant Training Center


Page 27

ABCD

Generators
Electrical Maintenance

3ph- AC supply

DC

Synchronous Generator:
Fundamentals & Operation

Power Plant Training Center


Page 28

3~ AC

Figure 12: Major Components of a Typical Brushless Excitation System


CSXA400365.cdr

AVR
Voltage
Sensor

Field windings

CSXA220052enB.doc

Automatic
or manual
AC
Generator
output

Permanent
magnets
Rotating
rectifier

Pilot
exciter
AC

DC
Generator field or
rotor winding

Main exciter
Generator
Turbine

S-ar putea să vă placă și