04 B
Best-Solution
High-Performance
One-rank higher
breaking performance
High-Reliability
Customer Friendly
Contents
Concept
Line up
Best Solution
High-Performance
High-Reliability
Customer Friendly
Product Specification
Connections
Charging
Accessories
For breaker unit
For drawout type
Wiring diagram
Outline dimensions
Drawout type
Fixed type
Panel-cut,Drawout handle,Terminal adapter
Neutral CT,External ZCT
ETR external units
Technical information
Ordering information
Memo
Service network
SS series
SH series
630
1000
1250
1600
2000
2500
3200
4000
AE2000-SH
AE2500-SH AE3200-SH
5000
6300
WM1 Generator
WM2 protection use
WB1
Special use
WB2
E1
Ground fault
Protection (GFR)
AP
(1)
N5
Power supply
P1
100-240V ACDC
P2
24-60V DC
P3
P4
P5
Additional function
EX1
Extension module
DP1
Display
TAL
Temperature alarm
MCR
Module for display and
communication
Current,Voltage,Power,
Harmonics,Trip current,etc.
MCR switch
Network
By using various application softwares for PLC, users can also connect to the
network SCADA system.
Personal
Computer
MELSECNET/10
Interface card
MELSECNET/10
Interface
Unit
PLC
I/O Unit
Eco Monitor II
ME110S
MDU
AE-SW
Interface unit
CC-Link
I/O unit
PROFIBUS-DP
Modbus(RS-485)
Communication items
Current, Voltage, Power, Harmonics, etc
Measurement / alarm
Tripping cause/current
Alarm (PAL,TAL,Self diagnosis)
Breaker ON,OFF
Breaker control
Spring charge
ON/OFF/spring charge status
Breaker status
VT unit
Drawout position
ETR characteristics setting
Power supply
P1: AC DC100-240V
P2: DC24-60V
P5: DC100-240V
with output contact (SSR)
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
Temperature alarm(TAL)
MCR switch(MCR-SW)
Network
BIF-CC
BIF-PR
BIF-MD
(Former model)
(New model)
(AE630-SW~AE2000-SWA)
(Former model)
(New model)
(AE2000-SW~AE4000-SWA)
690V AC
(Former model)
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE1000-SW
600V AC
65
~ 500V AC
65
AE1600-SW
AE2000-SWA
AE3200-SW
60
2s
50
3s
690V AC
75
600V AC
75
AE2000-SW
AE2500-SW
65
1s
65
AE630-SW
AE1250-SW
(New model)
(AE2000-SW~AE4000-SWA)
1s
75
2s
75
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
AE4000-SWA
85
~ 500V AC
0
20
40
60
80
65
3s
100
(kA)
Icu
20
40
60
80
(kA)
Icw
(Former model)
Electrical
Former model
New model
10000
5000
25000
AE630-SW AE1000-SW
AE1250-SW AE1600-SW
12000
AE630-SW AE1000-SW
AE1250-SW AE1600-SW
1500
10000
25000
AE2000-SWA
8000
AE2000-SWA
10000
AE2000-SW AE2500-SW
AE3200-SW
20000
AE2000-SW AE2500-SW
AE3200-SW
5000
500
20000
AE4000-SWA
0
5000
Former model
New model (V2)
10000
15000
20000
5000
AE4000-SWA
25000
(times)
2000
4000
6000
8000
10000
12000
(times/500V AC)
For convenience
3 sizes
Size1
Size2
New model
Present model
Size3
AE2000-SS
(Former)
AE2000-SWA
(New)
Bus bar
Interchangeable
Former model
New model
Vertical
Horizontal
Fixed type
AE-SW Series
1 Arc extinguishing chamber
2
5
6 Padlock hook
6
7 Charging indicator
8
8 ON/OFF indicator
AE1600-SW 3P
Drawout type
AE-SW Series
1 Cradle
3
2 Control circuit terminal block
3 Lifting hole
4 Charging handle
5 Drawout position indicator
4
6 Extention rail
7 Position lock
6
7
9
AE1600-SW 3P
Skeleton
8
10
30
31
29
26
27
24
25
1
12
28
11
13
14
15
16
21
17
18
20
22 Counter (CNT)
2 Cradle
14 Auxiliary switch
22
23
19
standard (AX)
15 Auxiliary switch
26 Safety shutters (SST)
6 I/O unit
7 Extension module
8 ETR unit
19 UVT-controller (U-CON)
30 Horizontal terminal
31 Vertical terminal
Product introduction
1
2
Type
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
3
Standard
IEC 60947-2
EN 60947-2(CE)
VDE
JIS C 8201-2
GB 14048.2(CCC)
Shipping standards are
available soon.
LR
GL
BV
DNV
ABS
NK
Interphase barrier
Mechanical interlock
Door interlock
Horizontal-Vertical
changeable.
8
Electronic
trip relay
General use
WS type
Generator protection use
WM type
Door frame
Dust cover
Connection
Drawout type
Horizontal terminal
Vertical terminal
Front terminal
5
Drawout type
accessories
Cell switch
Short-circuit B-contact
Lifting hooks
Safety shutter
Safety shutter lock
Mis-insert preventor
Test jumper
Electrical
accessories
Auxiliary switch
Motor charging device
Closing coil
Shunt trip device
Under voltage trip device
Condenser trip device
Fixed type
7
Mechanical
accessories
Special use
WB type
Optional
G1:Ground fault protection
E1:Earth leakage protection
AP:2nd AdditionalPre-alarm
N5:Neutral pole 50% protection
9
Relay
accessories
Extension module
Display
Temperature alarm
MCR switch
Neutral CT
External ZCT
VT unit
10
Network
Special
environment
Moisture-fungus treatment
Corrosion resist
Specification
Type
(A)
Frame size
AE630-SW
AE1000-SW
AE1250-SW
630
1000
1250
(AC.V)
1000
(AC.V)
690
(kV)
12
Number of poles
3, 4
Rated current In
1000
1250
315-346.5-378-409.5-441472.5-504-567-598.5-630
(Note 5)
500-550-600-650-700-750800-850-900-950-1000
625-687.5-750-812.5-875937.5-1000-1062.5-11251187.5-1250
150 Ir 630
400 Ir 1000
800 Ir 1250
630
1000
1250
630
General use
Current rating adjustable
0.5 to 1.0 Ir 0.05 step
(A)
with MCR
without
Instantaneous
690V AC
65
600V AC
65
240-500V AC
65
690V AC
65
600V AC
65
240-500V AC
65
690V AC
25 (Note1)
25 (Note1)
500V AC
Rated service breaking capacity Ics (kA rms) %Icu
Rated making capacity
Icm (kA peak)
with MCR
without
Instantaneous
Rated short time
withstand current
Icw (kA rms)
100%
690V AC
143
600V AC
143
240-500V AC
143
690V AC
143
600V AC
143
240-500V AC
143
690V AC
52.5
500V AC
1s
52.5
2s
60
65
3s
50
(ms)
40 (Note 6)
(ms)
With rated
current
80
AC500V In
5000
AC690V In
5000
25000 (Note 4)
Horizontal terminal
Vertical terminal
Front terminal
Fixed type
Drawout type
3-pole
410340290
4-pole
410425290
3-pole
430300368
4-pole
Weight (kg)
(without Accessory)
430385368
3-pole
40
41
4-pole
50
51
Drawout type
3-pole
63
64
(including cradle)
4-pole
77
78
Cradle only
3-pole
26
4-pole
30
Fixed type
(Note 1) The columns for without instantaneous are the values when the bare main body and the external relay is combined.
(Note 2) The number of operating cycles without rated current also include the number of operating cycles with rated current.
(Note 3) AE2000-SWA and AE4000-SWA apply for only vertical terminal of connecting terminal.
(Note 4) This value means number of operating cycles of ACB's body not including accessories.
(Note 5) Products with low rating types is available.
AE 630-SW
AE 2000-SW
250-275-300-325-350-375-400-425-450-475-500(CT 500A)
800-880-960-1040-1120-1200-1280-1360-1440-1520-1600(CT 1600A)
157.5-173.3-189-204.8-220.5-236.3-252-267.8-283.5-299.3-315(CT 315A)
625-687.5-750-812.5-875-937.5-1000-1062.5-1125-1187.5-1250(CT 1250A)
125-137.5-150-162.5-175-187.5-200-212.5-225-237.5-250(CT 250A)
(Note 6) This value means the instantaneous breaking time at shortcircuit interruption. As for accessories (SHT, UVT), refer to page 14.
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
1600
2000
2000
2500
3200
4000
1000
690
12
3
3, 4
1600
2000
2000
2500
3200
4000
800-880-960-1040-11201200-1280-1360-14401520-1600
1000-1100-1200-13001400-1500-1600-17001800-1900-2000
1000-1100-1200-13001400-1500-1600-17001800-1900-2000 (Note 5)
1250-1375-1500-16251750-1875-2000-21252250-2375-2500
1600-1760-1920-20802240-2400-2560-27202880-3040-3200
2000-2200-2400-26002800-3000-3200-34003600-3800-4000
1000 Ir 1600
1250 Ir 2000
800 Ir 2000
1600 Ir 2500
2000 Ir 3200
2500 Ir 4000
1600
2000
2000
2500
3200
4000
75
75
85
75
75
75
45 (Note1)
45 (Note1)
100%
165
165
187
165
165
165
94.5
94.5
75
75
65
40 (Note 6)
80
1500
1500
1000
500
1500
1500
1000
500
20000 (Note 4)
-
(Note 3)
(Note 3)
-
410475290
410605290
430435368
430439368
430565368
430569368
42
47
60
61
63
52
57
72
73
75
81
99
65
70
92
93
95
108
79
84
113
114
116
136
31
35
36
49
35
43
44
61
(Remark) All models conform the isolating functiion according to IEC 60947-2.
Reverse connection is available.
Over view
Connections
Horizontal
(Standard)
Type
Front
(FT)
Vertical
(VT)
(AE2000/4000-SWA only)
FIX-VT
DR-VT
Connections
Type
DR-FT
Horizontal-Vertical changeable
(HVT)
VTA
FIX-FTA
VTA
DR-FTA
DR-HVT
Available connections
Breakers
Connections
AE630-SW
AE1000-SW
AE1250-SW
AE2500-SW
Horizontal
Fixed type
(FIX)
FIX-VT
VTA
FIX-FTA
Horizontal
DR-VT
Drawout type
(DR)
DR-FT
VTA
DR-FTA
DR-HVT
Note : The dimensions of the terminal portion of DR-HVT are different from those of the standard part. As for details, refer to the external dimensional drawing.
AE3200-SW AE4000-SWA
Manual charging
The closing spring is charged by the manual charging handle. The breaker is closed
when the ON button is pressed, and opened when the OFF button is pressed.
When the closing spring is completely charged, the charging indicator will show
"CHARGED".
The indicator shows ON or OFF state of the main contacts.
The breaker cannot be closed while the OFF button is being pressed. (Safety feature)
OFF lock is available by padlock (See P7,P17) as standard.
Charged
signal
Charging completion
switch
413
414
Charging limit
switch
U1
Control
supply
U2
Motor
Control
relay
Motor charging circuit
Breaker
U1
U2
Axb
Control
supply
A OFF charging method is also
available. The closing spring is charged
automatically when the breaker is
opened. this is available only by
externally connecting in series b contact
(AXb) of the auxiliary switch to the
motor charging circuit.
In case of DC power supply, please use
high capacity auxiliary switch (HAX).
U1
U2
DC24
DC48
AC/DC
100-125
AC/DC
200-250
Inrush
Applicable
Steady
Applied
voltage
voltage (V) current(Peak current (A)
value) (A)
range (V)
18 ~ 26.4
36 ~ 52.8
85 ~ 137.5
170 ~ 275
24
48
100
125
200
250
22
14
10(10)
12(12)
5(7)
6(8)
6
3
3(4)
3(4)
1(2)
1(2)
Charging
time (s)
2
4
6
5
3
3
8
7
DC24-48V
(18~52.8)
AC DC common
100-250V
(75-275)
AC
DC
AC100V
0.7A (100VA)
AC250V
1.7A (200VA)
CC circuit diagram
Breaker
Closing
time (Note1)
C.C.Unit
A1
CC
Control
supply
0.08 s
or less
N o t e 1 ) In case of double rating of rated voltage, it is the value to the lower rating.
One-pulse
circuit
A2
Closing time is from the initial energization of the closing coil to the completion of the closing of the main contacts.
Do not use AXb contact for a cut-off switch,because pumping prevention is not perfomed.
This is the device that automatically trips the breaker when the circuit voltage drops below the
nominal voltage, and comprises a UVT coil and UVT controller. There are 3 kinds of tripping
time, INST, 0.5s and 3.0s.
Rated voltage
Frequency
operatingtime
(time delay)
Pickup
voltage
100-120V AC
200-240V AC
50/60Hz
65~85V
45~70V
130~170V
90~140V
Trip function
24V DC
-
100-110V DC
65~85V
45~70V
120-125V DC
78~102V
54~84V
Power
consumption
D1
UVT
controller
~
D2
UVT
coil
Trip button
380-460V AC
48V DC
Drop-out
voltage
DT1
20VA
Wiring length
< 2m
DT2
Breaker
Note2) The operating time is a guarantee value when it drops from 85% or more of rated voltage.
IN2
Note3) Time delay should be allowed for 1.5s between applying the voltage to the UVT and
closing the breaker.
OUT3
D1
External
transformer
(attached to
UVT controller)
UVT
controller
OUT4
D2
UVT
coil
Trip button
DT1
Note4) If a remote trip function is required,remove the shorting bar (DT1 DT2) and connect a
normally closed switch,rated 0.5A at 150VDC across them.
Wiring length
< 2m
DT2
Breaker
The shunt trip device is a device to open the breaker by remote control. A cut-off switch is included.
SHT circuit diagram
Operating voltage Operating inrush current (VA) Operating
Rated voltage
time (Note1)
(Applicable voltage range)
AC
DC
DC24-48V
(16.8~52.8)
Breaker
Cut-off switch
SHT unit
C1
AC DC common
100-250V(70-275)
AC380~500V
(266~550)
Control
supply
0.04 s
or less
C2
SHT
N o t e 1 ) In case of double rating of rated voltage, it is the value to the lower rating.
Example) In case of DC24 to 48, it is operating time to DC24V.
OCR alarm (AL) is a short-time operating switch (more than 30ms(1a)) for the electrical indication of
when the breaker trips due to over current.
Contact rating
Voltage (V)
Resistive load
Inductive load
240
AC
DC
125
240
0.2
0.2
125
0.4
0.4
30
Note1)
Note2)
The control supply is not required for the operation of the OCR
alarm (AL).
The self-hold circuit is required since the relay out put only operates
for 0.03 seconds.
When a continuous output signal is required, please use the output
signal from the trip indicator (TI) which is operated by the same
causes as the OCR alarm (AL).
In case of tripping the breaker in TC manual method, the manual
reset button located right side of the electronic trip relay projects
and the tripping indicative switch moves with continuous output.
Auxiliary switch
Standard (AX) High capacity type (HAX)
This is the contact that is used to remotely indicate the ON or OFF status of the breaker.
Standard (AX)
Type
Contact
capacity (A)
Resistive load
Inductive load
Inductive load
460V
2.5
AC 250V
10
10
10
10
125V
10
10
10
10
250V
0.3
0.3
1.5
DC 125V
0.6
0.6
10
30V
10
10
10
Maximum contacts
5a5b
Change-over
sequence
Breaker state
ON
OFF
a-contact (NO)
ON
OFF
b-contact (NC)
OFF
ON
5a5b
The a and b conacts may turn simultaneously to ON instantaneously at the time of changing the contact;
Pay attention to the contact state when designing circuits.
The chattering time at the time of contact ON-OFF is below 0.025 s.
For special environment specification, the contact capacity gets deteriorated.
Apply for further detail.
The cover is to prevent careless manual operation (ON,OFF) of the push buttons.
BC-L can be locked by a padlock (The padlock should be supplied by the customer.)
For the suitable size of a padlock, refer to Page 17
Cylinder lock(CYL)
Counter(CNT)
Door frame(DF)
The door frame improves the appearance, after cutting out the panel door to install the breaker.
Door interlock(DI)
The panel door cannot be opened unless the breaker is open.
A wire type mechanical interlock is used to allow flexbility in positioning breakers in the switchboard.
The parts of the Door panel should be supplied by the customer.
DI can not be installed to combine with "Mechanical interlock(MI)for 3 ACBs."
Interphase Barrier(BA)
This enhances the interphase insulation between the terminal portions of the breaker, and prevents
short-circuit due to conductive inclusion or dust. It can be attached and detached easily. As for its
availability, refer to the below table.
AE630-SW~
AE2000-SW~
AE2000-SWA
AE4000-SWA
AE1600-SW
AE3200-SW
Horizontal (FIX)
(FIX)
Horizontal (DR)
(DR)
Connections
IP20-Terminal Cover(IP-TC)
This is a transparent cover to be attached to the terminal block of control circuit, and to prevent the
charging portion from being exposed. The protection degree is IP20.
Breaker layout(630AF-4000AF)
Interlock combinations
(mm)
Vertical installation
Case circuit
Type
Horizontal installation
: ACB open
: ACB closed
ACB1
ACB1
ACB2
ACB1
ACB2
ACB3
ACB1
ACB2
ACB3
ACB1
ACB2
ACB3
ACB2
0~12
2 devices
144
ACB2
1000(Max.)
ACB3
1000(Max.)
Type
ACB1
ACB2
ACB3
1000(Max.)
Type
ACB1
ACB2
ACB3
3 devices : 2 Normal sources and 1 Replacement source
KF-100C
KF-200C
AC100/110
AC200/220
Type
Rated input voltage (V)
Rated frequency (Hz)
50-60
140/155
Note 2: The charging time starts from when the capacitor begins to
supply power at 85% of the rated AC input voltage, and
continues until the capacitor charging voltage reaches 60% of
rating.
140/155
820
Voltage range
60~125%
Note 3: The trip limit time means the time period in which the shunt trip
device (SHT) can make a tripping operation once, even after
the charged condenser with 100% supply voltage would be
stopped to charge.
1 VA max
Note2
Note3
0.5s max
30 seconds min.
Paint color
30 seconds min.
Black (N1.5)
AC 2000V
AC/DC 100-250V
R6
100
4-M30.5
Cover screw
4-M6 Mounting screw
Condenser
tripping
device
75
110.6
Front view
4-7
4-M4 screw
(for wiring)
16
13.3
15.4
87
90
106
Side view
DC+
AC1
04
1
S1
45
90
90
4-
Breaker
Type
ACB1
134
45
47(Max.)
45
45
Drilling plan
Open button
R1
R3
C
R2
AC2
N6
DC
Circuit diagram
C1
SHT
C2
(mm)
Padlock
A padlock can be arranged at the lock plate. Thereby, it is possible to prevent the connection
position from being changed unnecessarily. A padlock of 5 should be prepared by customer. As
for outline dimensions of the padlock, please refer to the left figure.
35
(mm)
Outline dimensions
(reference)
TEST position
DISCONNECTED position
DRAWOUT position
Contact rating
DISCON
CL-T
(TEST)
CL-D
(DISCONNECTED)
Change-over sequence
(a-contact)
Switch function
Display position of
drawout operation
CL-C
(CONNECTED)
Voltage (V)
Disconnected
Connected
TEST
CONNECT
ON
OFF
OFF
ON
ON
OFF
Drawout position
of breaker
Resistive load
Inductive load
2.5
460
250
AC
10
10
250
1.5
125
10
30
10
10
125
DC
Maximum contacts
Total 4c max.
Standard pattern
CL-C
CL-T
CL-D
CL1
CL2
CL3
CL4
Lifting hook(HP)
This is the metal fitting to suspend the main body when the breaker is removed from the drawout
cradle. The fixed type breaker is equipped with Hp as standard.
Safety shutter(SST)
The safety shutters cover the conductors (cradle side) and prevent contact with them when the
breaker is drawn out.
Mis-insertion preventer(MIP)
This prevents other breakers than specified from inserting into the breaker, and Max 5 settings are
available.
Test jumper(TJ)
With the breaker taken out of its cradle, this device enable the breaker to be electrically opened and
closed, and the operating sequence to be checked. 3m length one is equipped as standard
shipment.
C
F
G
F
A
Display (option)
RESET button
When push this reset button, trip indicator, and Pre-Alarm
will be reseted. And when the instantaneous test by
MITSUBISHI special tester and push this reset button, as a
result of LTD and STD function become ineffective.
Pre-alarm(PAL)
TEST terminal
This terminal already installed standard.This terminal is
used several test by MITSUBISHI special tester.
TAL (option)
When the temperature of main contact exceed normal temperature level, temperature alarm is indicated at LED ( on main
setting module ) and output by contact ( only installed power supply with output contact ).
If TAL is installed in the breaker according your order, Temperature alarm ( LED ) on main setting module become effective.
When the temperature of main contact goes down within normal tempter level, the temperature alarm ( LED and output ) is reset.
NCT (option)
Neutral CT is required for Ground fault or Neutral pole protection, when 3 pole breaker is used for 3 phase 4 wires system.
ZCT (option)
This device is necessary when installed earth leakage additional module ( ER ), for the purpose of effective the earth leakage
protect function.
Characteristic table
NA
G1
E1
AP
N5
Nothing
Ground fault
Earth leakage
Neutral pole
50% protection
2
1
WS
General use
LTD+STD+
INST/MCR
WM
Generator protection use
LTD+STD+
INST/MCR
WB
Special use
INST/MCR
Resistive load
Inductive load
cos=1.0
cos=0.4
L/R=7ms
240
1A
0.5A
120
1A
1A
125
0.1A
0.05A
30
1A
1A
Voltage(V)
Type
Rating
alarm output
P1
100-240V ACDC
Nothing
P2
24-60V DC
Nothing
P3
100-240V AC
100-125V DC
6 output contacts
P4
24-60V DC
6 output contacts
P5
100-240V DC
AC
DC
Peak overload
current
On resistance
(max.)
240
0.1A
0.3A
120
0.1A
0.3A
245
0.1A
0.3A
30
0.1A
0.3A
Voltage(V)
Note1: Over current protection and ground fault protection operates without control power source.
Note2: Factory setting of 6 output contacts is as follows.
LTD,STD/INST,Optional setting module function(G1,E1,AP),
PAL,TAL,Error(Self diagnosis)
AC
DC
250A
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
630A
1000A
1250A
1600A
2000A
315A
500A
1250A
1600A
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
2000A
2500A
3200A
4000A
Note1: Low rating type of AE630-SW does not available for the ground fault protection.
Note2: As for details of ratings, refer to page 9 and page 10.
Power supply
P1: ACDC100-240V
P2: DC24-60V
P5: DC100-240V
with output contact (SSR)
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
Temperature alarm(TAL)
MCR switch(MCR-SW)
Network
BIF-CC
BIF-PR
BIF-MD
F ERR. LED
E
F
O
P
Mark
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW
Accuracy
setting for
shipment
1.0
20%
150
15%
10
20%
0.060.04-0.08s
15%
WS116 (INST)
WS212 (INST)
AE2000-SWA AE4000-SWA
Current setting
Ir
Uninterrupted
current
Iu
LTD time
TL
122550100150s
STD pick-up
current
Isd
1.522.5345678910 x Ir
STD time
Tsd
0.50.40.30.20.10.060.060.10.20.30.40.5s
INST./MCR
pick-up current
Ii
Pre-alarm current
Ip
10%
OVER
Pre-alarm time
Tp
20%
at Iu x 2
(I2t ON)
(I2t OFF)
16-12-10-8-6-4-2-2-4-6-8-10-12-16 x Ir
(INST)
(MCR)
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
WS1
Upper figure and table denote that are include optional MCR function.
(INST)
(MCR)
WS2
(h)
4000
1
3000
40
2000
30
20
1000
PAL current : Ip
Iu x 0.68~1.0(0.04step)-OVER10%
15
10
Uninterrupted current : Iu
0.8~1.0 x Ir(0.02step)
500
400
300
(min)
4
200
LTD time : TL
12-25-50-100-150(s)20%
(at Iu x 2)
100
60
50
40
40
30
30
20
50
20
PAL time : Tp
TL/220%
10
10
(s)
With MCR
1
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.05
Current
.04
I2t ON
(ramp)
I2t OFF
.05
.04
.03
.03
.02
.01
1
10
20
50
current (%)
500
1000
1600 2000
5000
.01
10000
B Pre-alarm LED
C Temperature alarm LED
E
E RUN LED
F
F ERR. LED
O TEST terminal
Mark
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW
Accuracy
setting for
shipment
Comply with
ordering sheet
5%
1.15
20%
20
15%
20%
0.060.04-0.08s
15%
WM116 (INST)
WM212 (INST)
AE2000-SWA AE4000-SWA
Current setting
Ir
LTD pick-up
current
IL
1.01.051.11.151.2
LTD time
TL
152025304060s
STD pick-up
current
Isd
1.522.533.544.55 x Ir
STD time
Tsd
INST./MCR
pick-up current
Ii
Pre-alarm current
Ip
5%
OVER
Pre-alarm time
Tp
20%
at IL x 1.2
0.50.40.30.20.10.060.060.10.20.30.40.5s
(I2t ON)
(I2t OFF)
16-12-10-8-6-4-2-2-4-6-8-10-12-16 x Ir
(INST)
(MCR)
Upper figure and table denote that are include optional MCR function.
Pre-alarm current OVER setting is equal to 1.0.
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
WM1
(INST)
(MCR)
WM2
(h)
4000
1
3000
40
2000
30
20
Pre-alarm current : Ip
IL x 0.68 ~ 1.0(0.04step) 10%
1000
15
10
500
400
300
(min)
4
200
2
100
60
LTD time : TL
15-20-25-30-40-60(s)20%
(at IL x 1.2)
50
40
1
50
40
30
30
20
20
Pre-alarm time : Tp
TL/220%
10
10
(s)
With MCR
1
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
I2t ON
(ramp)
.05
.04
Current
.02
.04
I t OFF
.03
.05
.03
.01
1
10
20
50
current (%)
500
1000
1600 2000
5000
.02
.01
10000
B Pre-alarm LED
E RUN LED
H
F ERR. LED
J
K
Mark
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW
Accuracy
setting for
shipment
1.0
15%
WB116 (INST)
WB212 (INST)
AE2000-SWA AE4000-SWA
Current setting
Ir
INST./MCR
pick-up current
Ii
16-12-10-8-6-4-2-2-4-6-8-10-12-16 x Ir
Pre-alarm current
Ip
10%
OVER
Pre-alarm time
Tp
75s at Ir x 2
20%
(INST)
(MCR)
WB1
I
Upper figure and table denote that are include optional MCR function.
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
(INST)
(MCR)
WB2
4000
1
3000
40
2000
30
20
1000
15
10
Pre-alarm current: Ip
Ir x 0.68 ~ 1.0(0.04step)-OVER 10%
500
400
Max. time of
let-through current
8
6
Pre-alarm time: Tp
75s 20% at Ir x 2
300
200
(min)
Max. Setting of
External OCR
100
60
50
50
40
40
30
30
20
20
10
10
5
4
Up to Icw
2
(s)
.5
.5
.4
.4
Up to Icw
.3
.3
.2
.2
.1
.1
.05
.05
.04
.04
.03
.03
.02
.02
10
20
50
100 125
current(%)
200
500
1000
1600 2000
5000
.01
10000
Accessories
Ground fault protection(GFR)
The ground fault protection (GFR) of several hundred amperes is possible. This function can be
selected for trip and alarm (no trip). Power supply is necessary for this function, even if there is no
power supply, it can function at 0.2xIn or higher.
Mark Adjustable setting range
Setting item
Accuracy
Setting for
shipment
20%
1.0
0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0 x In
GFR time
3-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3s
20%
TRIP
ALARM
(at 1.5 x Ig)
Tg
Neutral CT(NCT)
3 (TRIP)
The Neutral CT is used for ground fault protection when the 3 pole breaker is used on a 3 phase 4
wires system and for over current protection on N phase. Please use this CT in combination with
ground fault protection (GFR). As for outline dimensions, refer to page 48.
30
20
Alarm
contact
output
ETR
P2
513
P1
544
Control
supply
Pick-up current : Ig
In x 0.1~1.020%
(0.1step)
10
8
0.1
1.0
6
5
4
3.0
ACB
ETR
P1
513
P2
Control
supply
N2
544
N1
Alarm
contact
output
.5
.4
.3
.2
0.15
AE630-SW 630A
NCT06
AE1000-SW 1000A
NCT10
AE1250-SW 1250A
AE2000-SW 1250A
NCT12
AE1600-SW 1600A
AE2000-SW 1600A
NCT16
AE2000-SWA 2000A
AE2000-SW 2000A
NCT20
AE2500-SW 2500A
NCT25
AE3200-SW 3200A
NCT32
AE4000-SWA 4000A
NCT40
.1
<0.1
(0.04~0.1)
.05
.04
.03
.02
10
20
50
100
150 200
% of rated current In
300
500
1000
Setting item
Accuracy
Setting for
shipment
+0%
30%
10A
ER pick-up current In
1A-2A-3A-5A-10A
ER time
3-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3s
20%
TRIP
ALARM
(at 1.5 x In)
Te
3 (TRIP)
External ZCT
This option is used to detect several amperes of earth leakage when use in combination with a
electronic trip relay that has the earth leakage tripping (ER) option.
Two methods are available. The first is where the all load conductors pass through the ZCT.
The other method uses a smaller ZCT through which the supply transformer's ground wire passes
through to earth.
ZCT for load circuit
ZCT163
ZCT323
ZCT324
30
ACB
20
ZCT
Pick-up current : In
+0
1A-2A-3A-5A-10A -30%
10
8
ETR with ER
Z1
Z2
P2
513
P1
544
1A
10A
Control
supply
3.0
Alarm contact
output
.5
.4
.3
ZCT
Z1
ETR with ER
.2
0.15
Z2
513
544
Alarm contact
output
P2
P1
Control
supply
.1
<0.1
(0.04~0.1)
.05
.04
.03
.02
0.7
10
20
50
100
Accessories
2nd Additional Pre-alarm (AP)
The Pre-Alarm (1st) function already installed in standard breaker, the 2nd Additional Pre-Alarm
function can be installed by option, thereby it is possible to monitor (observer) electric circuit in more
detail by 2nd Additional Pre-Alarm function.
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x Iu
0.3-0.4-0.5-0.6-0.7-0.8-0.9 x TL
/ 5-10-15-20-30-40-60s (FLAT)
LTD,STD,INST,GFR,PAL
10% ~ 2500%
OUTLINE DIMENSION
TIMER
0.000 ~ 999.999s
POWER SUPPLY
Additional functions
By adding the extension unit in ETR, measuring, display and communication are possible.
Name
Description
Extension module
EX1
DP1
DP2
VT
VT unit
BIF-CC
BIF-PR
BIF-MD
BIF-CON
I/O unit
BIF-CL
Power supply
P1: ACDC100-240V
P2: DC24-60V
P5: DC100-240V
with output contact (SSR)
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
Temperature alarm(TAL)
MCR switch(MCR-SW)
Network
BIF-CC
BIF-PR
BIF-MD
2 Communication function
2 display modules and 1 interface unit can be connected simultaneously by internal
communication.
3 Graphical display
By adopting dot matrix type LCD, graphical display such as bar graph display of load
current, current harmonics and characteristic curve are realized.
There are 2 types of this module. One is the ETR attachment type (DPI). Another is the panel
attachment type (DP2) and is connected to extension terminals of control circuit by 2m cable.
(As for outline dimensions, refer to page 49.)
Note;
Extension module (EX1) is required.
VT unit (VT)
It is possible to measure voltage, power, energy, current harmonics, etc. Combining the extension
module (EX1). (for outline dimensions, refer to page 50.)
Network
Interface unit (BIF-CC/BIF-PR/BIF-MD)
These Interface units can expand the future possibility in various communication and Intelligent control.
CC-Link
By using various application softwares for PLC, users can also connect to the
network SCADA system.
Personal
Computer
MELSECNET/10
Interface card
MELSECNET/10
PROFIBUS-DP
PLC
Interface
Unit
I/O Unit
Eco Monitor II
ME110S
MDU
AE-SW
Note:
Extension module (EX1) is required.
Modbus(RS-485)
I/O unit(BIF-CON/BIF-CL)
The Input & Output Controlling Unit (BIF-CON) is available for the remote controlling and remote
monitoring of the breaker condition through the various network systems.
With this BIF-CON unit in addition to the Interface Unit, it become possible to control the breaker
remotely, like a ON or OFF operations or Spring-charging.
Further, by combining the Drawout position switch (BIF-CL), the monitoring of drawout position
become available in case of the breaker drawout type.
Function Description
Control
Note
Breaker ON operation
Spring charge
Monitor
Combination sample
Type
WS
+ +
Note 1)
;Ex1;DP1(;DP2)
WM
WB
WS
Note 1)
;Ex1;DP1(;DP2),VT
WB
WM
NP AP G1 E1 NP AP G1 E1 NP AP G1 E1 NP AP G1 E1 NP AP G1 E1 NP AP G1 E1
P1~P5
P1~P5
Measurement
Load current (2.5%)
Leakage current (2.5%)
Note 4)
Voltage (2.5%)
power (active,reactive,apparent) (2.5%)
Power factor (5%)
Energy (active,reactive) (2.5%)
(3.5...19th)
Note 2)
Note 2)
Note 3)
Note 3)
Alarm history
PAL1
PAL2
OVER
GFR
EPAL
ER
TAL
Trip coil
Constant voltage
circuit
Setting input
Z1
Z2
A/D
CPU
Test
connector
N1
N2
W.D.T.
513
I/O
524
534
544
554
564
574
V2+
N
Power supply
with contact output
Alarm contact control circuit
0V
Trigger circuit
Micro
processor
ASIC
Rectifier circuit
V1+
Phase selection
sampling
Power supply CT
V2+
Integration circuit
RESET
CIRCUIT
RS1
RS2
Control power
circuit
P1
P2
P4
0V
FG
Power supply CT
Energy is supplied for the operation of the overcurrent tripping and ground fault tripping(GFR) function of the
electronic trip relay.
Current sensor coil
This detects current of each phase flowing through breaker. A coreless coil which has good linearity is a chieved.
Power supply circuit
This generates action energy of ETR, by energy from power supply CT.
ASIC
This amplifies signal detected by the current sensor coil, and detects ground fault current by vector composition.
Micro processor
This carries out tripping operation by signal amplified or detected by the exclusive ETR.
Characteristic setting module
This is the circuit for setting the characteristic of ETR.
Load current , PAL and Trip indicator
This displays load current and fault cause (including pre-alarm).
Power supply with contact output
This outputs contact signal at fault cause (including pre-alarm) and at other alarms.
A control supply is necessary for this function.
Setting procedure
1 Prepare a small flat tipped screwdriver.
0.8mm max. 6mm max.
ETR Cover
2 Insert the flat tipped screwdriver into the opening of the ETR cover.
Then, lightly turn the screwdriver to the upside as shown in the left
figure, and the relay cover will open.
Sealing hole
Operating hole for Resetting
Adjustable in steps
Rotary code switch is used. Do not set the switch at points
between steps. The setting value is same, when the switch is
positioned at the thick line. (Set the switch with a torque of
0.02Nm or below.)
(XIu)
Push-button
This is for temporary operation, and press it with force of 3N or
below.
Adjustable
in steps
Push-button
4 When the characteristics is set up, use a device like a field tester, etc
to make sure that the required characteristic has been set.
5 At sealing, seal the ETR cover by using the sealing hole at the top of
the ETR cover.
Sealing hole
97
Reset circuit
Power circuit
544
524
D1
413
U1
CC
98
C2
A2
DT2 DT1
short
bar
414
U2
open to trip
(less than 2m)
OCR
alarm
Accessory Symbols
Voltage Input terminal of UVT
D1
D2
DT1
DT2
13
14
53
54
11
12
51
52
U1
U2
Motor charging
413
414
Charged signal
A1
A2
Closing coil
SHT
CC
Closing coil
C1
C2
Shunt trip
97
98
OCR alarm
P2
P4
RS1
534
LTD
554
S/I
564
Terminal description
P1
SHT
ZCT
Main circuit
574
G/E/P2
P4
PAL
Z2
TAL
NCT
Z1
D2
UVT
ERR
N2
A1
Alarm contacts
Electronic trip
relay(ETR)
N1
C1
CLS
P2
Charged
P1
UVT
Controller
513
Supply voltage
ON
RS1 RS2
power supply
AL
Extension terminals
Less than 2m
OFF
cut-off switch
RESET
common
RS2
UVT coil
AX
Auxiliary switch
AL
OCR alarm
CLS
SBC
Short-circuit B-contact
CL
Cell switch
513 ~ 574
Alarm contacts
Z1
Z2
N1
N2
For Neutral CT
For external display DP2
Extension terminals
UVT
Internal wiring
External wiring (user's wiring)
Control circuit connecter (drawout type)
43
33
23
13
341
331
22
12
54
44
34
24
14
344
342
334
332
324
CL
CL
CL
AX
AX
AX
AX
CL
32
311
322
314
312
ON
42
OFF
52
321
SBC
53
AX
SBC
11
AX
SBC
21
AX
AX
AX
AX
31
SBC
41
SBC
51
Cell switch
Note;
On the drawout type, the cables are cut to enough length allow the control circuit terminal block to be moved to the left or right by 5mm.
When a coil load is connected in the same control circuit as the ETR, surge absorbers are required to absorb the surge voltage.
OCR alarm
The contact output of the OCR alarm is the one-pulse output for 30ms.
For this reason, this output needs self-holding circuit.
CC (Closing coil)
Do not use AXb contact for a cut-off switch, because pumping prevention is not performed.
UVT
Use the switch that can open and close DC150V, 0.5A to remote trip.
Remote trip terminal has short bar at shipment, so remove it before use.
Disconnect the wires in case of main circuit dielectric test.
Side view
Horizontal
terminal
Horizontal-Vertical
changeable(HVT)
48
368
Fully drawout
position
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
132
117
50
50
15
Earth terminal
M8 screw
23
*220
452
234(149)
15
15
53
172
40
Panel
4-14
100
15
15
25
40
42.5
149
Front
terminal
50
15
370
132
430
340
*200
Vertical
terminal
15
Neutral pole
66
57
15
61
61
366
Inside of the panel
(thickness 1.6~3.2)
Rear view
Horizontal terminal
Vertical terminal
85
Front terminal
Operating panel center
85
85
85
85
85
85
85
50
Neutral pole
Insulation
block
50
50
Neutral
pole
Outline
of breaker
4P
3P
15
Outline
of breaker
Neutral
pole
4P
Outline
of breaker
3P
4P
3P
Horizontal-Vertical
changeable(HVT)
34
Connecting area
2-13
2-11.5
50
25
50
15
25
38
124.5
4P
92
3P
283
92
Test 35
228
370
92
Front view
Front view
150
Side view
Disconnected 51
Test 35
228
283
3P
4P
370
57 100
340
430
157
Neutral pole
*200
149
40
Panel
4-14
48
452
234(149)
100
23
104
368
366
Fully drawout
position
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
172
*220
29.5
25
40
42.5
Rear view
75
115
75
50
10
10
105
50
10
Neutral
pole
Outline
of breaker
3P
Outline
of breaker
4P
Connecting area
100
15
25 25 25
38
4-13
79.5
15
15
Earth terminal
M8 screw
Front view
Side view
48
324(194)
368
61
366
Fully drawout
position
132
83
Earth terminal
M8 screw
Dimensions
23
*220
452
53
25
239
172
40
Panel
4-14
67
40
42.5
92
15
15
*200
125
182
125
132
430
340
Aperture for
the drawout
handle
Front
terminal
Vertical
terminal
Neutral pole
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
57
T
(mm)
Type
AE2000-SW AE2500-SW
AE3200-SW
20
25
Rear view
Horizontal terminal
23
130
130
Front terminal
Vertical terminal
Operating panel center
23
130
130
130
23
130
130
130
130
W
Insulation
block
Outline
of breaker
Outline
of breaker
4P
3P
Neutral pole
4P
Neutral pole
Outline
of breaker
3P
Neutral pole
4P
3P
15
38
Connecting area
5-13
34
Connecting area
4-13
15
25 25 25
125
15
Front terminal
4-13
Dimensions
(mm)
Connecting area
25 25 25 25
38
Horizontal terminal
25 25 25
Vertical terminal
370
Horizontal
terminal
4P
370
3P
283
92
Test 35
228
325(195)
240
Type
AE2000-SW AE2500-SW
AE3200-SW
95
103
Front view
Side view
Operating panel center
Control terminal
Disconnected 51
325(195)
Test 35
228
283
Neutral pole
25
40
67
15
15
42.5
*200
Panel
4-14
Earth terminal
M8 screw
23
368
109
366
Fully drawout
position
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
172
*220
452
324(194)
239
40
48
Rear view
23
190
170
190
Outline
of breaker
52
10
170
43
170
Outline
of breaker
52
10
11
11
197
242
Neutral pole
327
242
4P
3P
Connecting area
125
20
25 25 25 25
48
5-13.5
370
430
125
Aperture for
the drawout
handle
182
4P
340
3P
125
240
Front view
Side view
Operating panel center
142
227(142)
93.5
Control terminal
139
275
3P
4P
15
132
72
4-14
410
340
350
15
Neutral pole
Earth terminal
M8 screw
(Left side)
228
*156
170
Panel
40
*175
*241(156)
290
255(170)
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Rear view
85
85
50
Neutral pole
Outline of breaker
4P
3P
Connecting
area
2-13
50
17
25
38
31
40
Earth terminal
M8 screw
(Left side)
Front view
Side view
Operating panel center
142
227(142)
Control terminal
275
3P
93.5
139
4P
410
350
340
57 100
157
Neutral pole
228
*241(156)
*156
170
*175
Panel
290
255(170)
24.5
40
Earth terminal
M8 screw
(Left side)
31
108
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Rear view
75
115
105
50
105
50
10
10
10
105
75
Neutral pole
Outline of breaker
Outline of breaker
3P
4P
100
15
25 25 25
38
4-13
74.5
100
4-14
Earth terminal
M8 screw
(Left side)
Front view
Side view
Operating panel center
Control terminal
232
317(187)
93.5
139
275
132
20
4-14
40
5
Earth terminal
M8 screw
(Left side)
228
*246
*175
Panel
*331(201)
260
290
345(215)
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Rear view
23
130
130
95
Neutral pole
Outline of breaker
4P
3P
Connecting area
4-13
95
17
25 25 25
38
410
340
350
20
Neutral pole
4P
72
3P
31
40
Earth terminal
M8 screw
(Left side)
Front view
Side view
Control terminal
317(187)
93.5
275
139
Neutral pole
4P
228
Panel
*246
*175
*331(201)
290
345(215)
260
4.5
40
Earth terminal
M8 screw
(Left side)
67
129.5
4-14
31
117
Earth terminal
M8 screw
(Left side)
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Rear view
23
152
30.5
145
145
152
145
31
31
11
11
95
95
10
10
Outline
of breaker
Outline
of breaker
Neutral
pole
3P
4P
125
20
25 25 25 25
48
5-13.5
410
182
340
57
350
125
3P
Outline
200
7.7
8-7
200
405
345
324
381
357
max 173
345
169
Panel-cut dimensions
Breaker
247
235
Breaker
mounting frame
235
271
295
(mm)
A
175
195
Type
(mm)
53
13
Mtg.holes13
115
20
AE3200-SW
25
42
(mm)
Connecting area
AE630-SW~1600-SW
Fixed
type
Up side
Down side
Drawout type
AE2000-SW,2500-SW
13
Dimensions
Type
38
Dimensions
37.5
Connecting area
100
100
25 25 25 25
15
38
25 25 25
125
15
50
25
15
13
25
25 25 25
50
25
15
15
15
38
15
38
AE630~
AE2000~
1600-SW 3200-SW
AE2000~3200-SW
34
AE630~1600-SW
Connecting area
Type
Fixed Type
Drawout Type
Fixed
AE2000-SW,2500-SW type
Up side
Down side
Drawout type
AE3200-SW
Fixed
type
Up side
Down side
Drawout type
258.5
50
15
145
50
15
145
50
15
258.5
95
20
145
95
20
145
95
20
258.5
95
25
145
95
25
145
103 25
Terminals M5 screw
K
G
Dimensions
(mm)
Type
630~2000A
97
2500~4000A
162
219 160 31
48 192 212 68
38
66
11
55
87
30
28
12
7.7
40
52
100
70
90
Dimensions
(mm)
Dimensions
(mm)
ZT15B
48
15
29
62
46
15
70
25
ZT60B
140 60
73 150 46
ZT30B
68
30
37
82
66
30
90
50
ZT80B
160 80
82 169 48
ZT40B
85
40
43
92
81
40 100 50
Dimensions
(mm)
200
72
92
64
48
Panel (Note)
42
16
64
R1
50.4
60.4
50.5
46.5
29.5
64
49
64
Upper side
Operation display
surface side
Surface plate
hole dimension
77.5
30
Mounting bracket
terminal
90
23.5
37.5
67.5
35mm IEC
rail holder
65
Terminal
30
Frame Ground
M3 terminal screws
35
117
IEC35mm rail
107
100
30
35mm IEC
rail holder
FG
P1 P2 SLD DG DB DA
Power supply
(100-240V ACDC)
30
100
77.5
30
30
Mounting bracket
90
35
terminal
117
107
IEC35mm rail
23.5
37.5
67.5
35mm IEC
rail holder
65
Terminal
30
30
Input
M3 terminal screws
35mm IEC
rail holder
Shunt trip
(SHT)
Closing coil
(CC)
Motor charging
(MD)
100
77.5
30
30
Mounting bracket
terminal
90
35
107
117
IEC35mm rail
23.5
67.5
37.5
35mm IEC
rail holder
65
30
Terminal
30
P1 P2 FG
M3 terminal screws
Power supply
(100-240V ACDC)
35mm IEC
rail holder
Frame Ground
VT unit (VT)
30
30
Mounting bracket
terminal
IEC35mm rail
35mm IEC
rail holder
65
90
30
Terminal
V1 V2 V3 VN
Line voltage inputs(To AE-SW main circuit)
35mm IEC
rail holder
35
117
107
100
30
15~23mm
Tightening Torque(Nm)
M12
M10 (Note1)
Silver plated
conductor
40~50
26~33
Terminal
Note1:In case of Horizontal-Vertical changeable terminal (HVT), use M10 bolt, washer, and spring washer.
Since fault current flowing through the conductors cause large electromagnetic forces,the conductors should be
secured firmly, using the values in Table the below as a reference. Max distance between Fixing support and ACB
bus bar should be less than 200mm.
Type(A)
Conductor distance(mm)
AE630-SW~
AE1600-SW
85
AE2000-SWA
3-Pole
4-Pole
115
105
(N)
AE4000-SWA
AE2000-SW~
AE3200-SW
Fixed type
Drawout type
3-Pole
4-Pole
3-Pole
4-Pole
130
190
170
152
145
4500
AESW
Max.200mm
Fixing support
30(0.2)
7700
5700
6300
5100
3500
3900
4300
42(0.2)
15100
11200
12200
9900
6800
7600
8500
8900
50(0.2)
21400
15800
17300
14000
9600
10700
12000
12600
65(0.2)
36100
26700
29300
23600
16200
18100
20200
21200
75(0.2)
31500
21500
24100
26900
28200
85(0.2)
40400
27600
30900
34500
36200
When selecting conductors for connection to a Series AE breaker, ensure that they have a sufficient current
capacity, refer to the below table.
Conductor Size(IEC-60947-1; Ambient 40C Temp., Open air)
Rated current
Max.(A)
Conductor size(mm)
630
40 x 5
1000
60 x 5
1250
80 x 5
1600
100 x 5
100 x 5
Arrangement
2000
2500
With long
100 x 5
3150(3200)*1
surface vertical
100 x 10
4000
AE4000-SWA
Drawout type
150 x 10
4000
AE4000-SWA
Fixed type
150 x 10
*1 The temperature rise of rated current 3200A conforms to the requirement of IEC 60947-1 for
the connecting conductor size of a rated current 3150A.In case of more than 3200A,
conductor sizes are not defined in IEC 60947-1.
Insulation distance
When a short-circuit current is interrupted, hot gas
blows out discharged from the exhaust port of the arc
extinguishing chamber, so provide a clearance as
shown in the following table.
Note1:On the fixed type, maintenance is possible with
following clearance.
Dimensions
D
A
Side
plate
B
Type
Mounting
surface
Applicable voltage
A
B
Fixed type
C
D
A
B
Drawout type
C
D
AE-SW Series
AC600V or less
(Note 1) 0
(Note 3) 50
162
(Note 2) 50
0
(Note 3) 50
240
(Note 2) 50
AC660V, 690V
(Note 1) 100
(Note 3) 50
162
(Note 2) 50
100
(Note 3) 50
240
(Note 2) 50
Note1:300mm or more clearance is necessary to inspect the arc-extinguishing chamber and contacts.
Note2:The wiring space reguired for the control terminal block.
Note3:When using mechanical interlock, door interlock ,etc. are installed, dimension B becomes larger.
Service conditions
1. Normal service condition
Under ordinary conditions the following normal working conditions are all satisfied, the AE Series air
circuit breaker may be used unless otherwise specified.
1.Ambient temperature
2.Altitude
3.Environmental conditions
The air must be clean, and the relative humidity must be 85% or less at max.
temp. +40C.Do not use and store in atmospheres with sulfide gas and
ammonia gas etc.(H2S 0.01ppm, SO2 0.1ppm, NH3 < a few ppm.)
4.Installation conditions
When installing the AE Series air circuit breaker, refer to the installation
instructions in the catalogue and instruction manual.
5.Storage temperature
If it is used under high temperature and/or high humidity, the insulation durability
and other electrical/mechanical features may deteriorate. Therefore, the
breaker should be specially treated. Moisture fungus treatment with corrosion
proofing is recommended. Since some parts may have problems due to
corrosion caused by the use in the environments where corrosive gas occurs,
the corrosion proof specifications is recommended,in such environments.
3.High altitude
Since on the use at the 2,000m or higher, the heat radiation rate is reduced,
accordingly the operating voltage, continuous current capacity and breaking
capacity are derated.Moreover the insulation durability is also decreased
owing to the atmospheric pressure. Please inquire us for further detail.
Type
Connection
Internal
resistance
(m)
Reactance
(m)
Power
consumption
(W)
Fixed type
0.028
0.059
11
Drawout type
0.042
0.089
17
Fixed type
0.026
0.060
26
Drawout type
0.040
0.091
40
Fixed type
0.024
0.060
38
Drawout type
0.038
0.091
60
Fixed type
0.016
0.063
41
Drawout type
0.030
0.095
77
Fixed type
0.016
0.063
64
Drawout type
0.032
0.095
128
Fixed type
0.010
0.047
40
Drawout type
0.020
0.071
80
Fixed type
0.008
0.047
50
Drawout type
0.018
0.071
113
Fixed type
0.007
0.048
72
Drawout type
0.014
0.072
143
Fixed type
0.009
0.048
144
Drawout type
0.015
0.072
240
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
The above values are applicable for one pole. (New breaker)
Standard
Ambient Temperature
40C
45C
50C
55C
60C
AE630-SW
630
630
630
630
630
AE1000-SW
1000
1000
1000
1000
1000
AE1250-SW
1250
1250
1250
1250
1200
AE1600-SW
1600
1600
1600
1550
1500
AE2000-SWA
2000
2000
1900
1800
1700
AE2000-SW
2000
2000
2000
2000
2000
AE2500-SW
2500
2500
2500
2450
2350
AE3200-SW
3200
3200
3200
3000
2900
AE4000-SWA
4000
4000
4000
3800
3600
(A)
Ambient Temperature
40C
45C
50C
AE630-SW
630
630
630
AE1000-SW
1000
1000
1000
AE1250-SW
1250
1250
1250
AE1600-SW
1600
1600
1440
AE2000-SWA
2000
1900
1700
AE2000-SW
2000
2000
2000
AE2500-SW
2500
2500
2500
AE3200-SW
3200
3200
2880
AE4000-SWA
4000
3800
3600
The above table shows the maximum rated current (at new product) of drawout type breaker by vertical connection methods
and the ambient temperature of breaker and bus bar.
Connection bus bar is by IEC60947-1. AE3200-SW and AE4000-SWA are by manufacturer recommended size of P51.
Breaker and bus bar show the maximum current value in open air.
As for ambient temperature exceeding 60C, please inquire us.
In case of with extension module (EX1), display (DP1), and network attached, deratings are the values shown in this table.
Discrimination table
AE-SW Series air circuit breakers provide easy selective co-ordination with branch circuit breakers.
For selective co-crdinations,refer to the following table.
AC230V sym kA
Main circuit
breaker
ng
c
apa
Branch
c it y
circuit breaker
Un
it b
rea
ki
NF
|
S
MB
NV
|
S
NF
|
C
NV
|
C
NF
|
U
NF
|
C
NV
|
C
NF32-SW
MB30-SW
MB50-CW
NV32-SW
NF63-SW
MB50-SW
NV63-SW
NF63-HW
NV63-HW
NF125-SW
MB100-SW
NV125-SW
NV100-SEP
NF125-HW
NV125-HW
NF250-SW
MB225-SW
NV250-SW
NV250-SEW
NF250-HW
NV250-HW
NF400-SP
NV400-SP
NF400-SEP
NV400-SEP
NF400-HEP
NV400-HEP
NF400-REP
NV400-REP
NF630-SP
NV630-SP
NF630-SEP
NV630-SEP
NF630-HEP
NV630-HEP
NF630-REP
NF800-SEP
NV800-SEP
NF800-HEP
NV800-HEP
NF800-REP
NF63-CW
NV63-CW
NF125-CW
NV125-CW
NF250-CW
NV250-CW
NF400-CP
NV400-CP
NF630-CP
NV630-CP
NF800-CEP
NF125-RGW
NF125-UGW
NF250-RGW
NF250-UGW
NF400-UEP
NF630-UEP
NF800-UEP
NF30-KC
NF50-KC
NF100-KC
NV30-KC
NV50-KC
NV100-KC
AE-SW
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
65
65
65
65
65
85
85
85
85
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
10
9(10)
10
10
10
10
10
10
10
10
15
9(10)
10
10
10
10
10
10
10
10
25
9(25)
25
25
25
25
25
25
25
25
50
9(50)
45(50)
50
50
50
50
50
50
50
100
9(65)
50(65)
65
65
65
85
85
85
85
50
9(50)
20(50)
22(50)
42(50)
42(50)
50
50
50
50
100
9(65)
25(65)
40(65)
65
65
85
85
85
85
85
20(65)
27(65)
27(65)
42(65)
70
85
85
85
9(65)
15(65)
20(65)
27(65)
27(65)
42(65)
70
85
85
100
9(65)
15(65)
20(65)
27(65)
27(65)
42(65)
70
85
85
125
9(65)
15(65)
20(65)
27(65)
27(65)
42(65)
70
85
85
85
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
85
15(65)
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
100
15(65)
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
125
15(65)
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
85
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
100
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
125
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
30
9(30)
15(30)
18(30)
24(30)
24(30)
30
30
30
30
35
9(35)
15(35)
18(35)
24(35)
24(35)
35
35
35
35
50
15(50)
18(50)
24(50)
24(50)
30(50)
37(50)
48(50)
48(50)
50
24(50)
24(50)
30(50)
37(50)
48(50)
48(50)
50
125
200
125
200
200
200
200
65
65
9(65)
9(65)
9(65)
-
65
65
65
65
15(65)
15(65)
-
65
65
65
65
18(65)
18(65)
18(65)
24(50)
65
65
65
65
29(65)
24(65)
24(65)
24(50)
65
65
65
65
29(65)
24(65)
24(65)
30(50)
85
85
85
85
48(65)
30(65)
30(65)
37(50)
85
85
85
85
85
37(65)
37(65)
48(50)
85
85
85
85
85
68
68
48(50)
85
85
85
85
85
68
68
The values in the table represent the max.rated current for both Series AE-SW air circuit breakers and branch breakers,and the selective co-ordination applies when the AE-SW series air circuit
breakers instantaneous pick up is set to maximum.
The numerals shown in parentheses are for AE-SW with MCR.(When set MCR).
AC440V sym kA
Main circuit
breaker
ng
c
apa
Branch
city
circuit breaker
Un
it b
rea
ki
NF
|
S
MB
NV
|
S
NF
|
C
NV
|
C
NF
|
U
NF32-SW
MB30-SW
MB50-CW
NV32-SW
NF63-SW
MB50-SW
NV63-SW
NF63-HW
NV63-HW
NF125-SW
MB100-SW
NV125-SW
NV100-SEP
NF125-HW
NV125-HW
NF250-SW
MB225-SW
NV250-SW
NV250-SEW
NF250-HW
NV250-HW
NF400-SP
NV400-SP
NF400-SEP
NV400-SEP
NF400-HEP
NV400-HEP
NF400-REP
NV400-REP
NF630-SP
NV630-SP
NF630-SEP
NV630-SEP
NF630-HEP
NV630-HEP
NF630-REP
NF800-SEP
NV800-SEP
NF800-HEP
NV800-HEP
NF800-REP
NF63-CW
NV63-CW
NF125-CW
NV125-CW
NF250-CW
NV250-CW
NF400-CP
NV400-CP
NF630-CP
NV630-CP
NF800-CEP
NF125-RGW
NF125-UGW
NF250-RGW
NF250-UGW
NF400-UEP
NF630-UEP
NF800-UEP
2.5
AE-SW
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
65
65
65
65
65
85
85
85
85
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
10
9(10)
10
10
10
10
10
10
10
10
25
7(25)
20(25)
25
25
25
25
25
25
25
50
9(50)
30(50)
50
50
50
50
50
50
50
25
7(25)
14(25)
19(25)
25
25
25
25
25
25
50
7(50)
15(50)
25(50)
42(50)
42(50)
50
50
50
50
50
18(50)
24(50)
24(50)
33(50)
45(50)
50
50
50
9(50)
15(50)
18(50)
24(50)
24(50)
33(50)
45(50)
50
50
65
9(65)
15(65)
18(65)
24(65)
24(65)
33(65)
45(65)
65
65
125
9(65)
15(65)
18(65)
24(65)
24(65)
33(65)
45(65)
80
80
50
24(50)
24(50)
33(50)
45(50)
50
50
50
15(50)
18(50)
24(50)
24(50)
30(50)
40(50)
50
50
65
15(65)
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
125
15(65)
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
50
18(50)
24(50)
24(50)
30(50)
40(50)
60(50)
60(50)
65
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
125
18(65)
24(65)
24(65)
30(65)
40(65)
60(65)
60(65)
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
10
9(10)
10
10
10
10
10
10
10
10
15
9(15)
15
15
15
15
15
15
15
15
25
15(25)
18(25)
24(25)
24(25)
25
25
25
25
35
24(35)
24(35)
30(35)
35
35
35
35
125
200
125
200
200
200
200
35(65)
50(65)
9(65)
9(65)
9(65)
-
65
65
50(65)
65
15(65)
15(65)
-
65
65
65
65
18(65)
18(65)
18(65)
24(35)
65
65
65
65
29(65)
24(65)
24(65)
24(35)
65
65
65
65
29(65)
24(65)
24(65)
30(35)
85
85
85
85
48(65)
30(65)
30(65)
35
85
85
85
85
85
37(65)
37(65)
35
85
85
85
85
85
68
68
35
85
85
85
85
85
68
68
The values in the table represent the max.rated current for both Series AE-SW air circuit breakers and branch breakers,and the selective co-ordination applies when the AE-SW series air circuit
breakers instantaneous pick up is set to maximum.
The numerals shown in parentheses are for AE-SW with MCR.(When set MCR).
Order No.
AE
P9~10
-SW
Number of poles
AE
-SWA
CT rating
Applicable standard
IEC 60947-2
CCC
Ambient temperature
40C(Standard)
Others
Reset type
Connection
Fixed type
Main circuit
terminal
Horizontal terminal(FIX)
P11
units
4P
3P
Rated current
Number of units
(AE630~1600-SW / AE2000~3200-SW)
Vertical terminal(FIX-VT)
(AE2000-SWA / AE4000-SWA)
P17~18
Drawout type accessories
Cell switch(CL: 1 or 2 or 3 or 4)
Short-circuit B-contact(SBC)
Lifting hooks(HP)
Safety shutter(SST)
Shutter lock(SST-LOCK)
Mis-insertion preventer(MIP)
Test jumper(TJ)
Note2
Drawout type
Note3
Note1 P9,P20
Note3
Horizontal terminals(DR)(standard)
Vertical terminals(DR-VT)
Front terminals(DR-FT)
Horizontal-Vertical
Changeable(DR-HVT) Note4
Note5
Additional function
P32
EXAMPLE
Extension module(EX1)
Note6
Note7
Power supply
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
P1: ACDC100-240V
P2: DC24-60V
Network P33
BIF-CC
BIF-PR
BIF-MD
Temperature alarm(TAL)
MCR switch(MCR-SW)
P5: DC100-240V
with output contact (SSR)
Neutral CT(NCT)
BIF-CL
Note8
Note9
External ZCT
P28
BIF-CON
ZCT
ZT
ZTA
Electrical
accessories
P12~14
AC DC100250V
AC380500V
DC2448V
Special P52
environments
Corrosion resist
P16
AC100110V
AC200220V
N o t e 1 : In case of AE630-SW and AE2000-SW Low rating type, please specify CT rating.
Refer to Page 9 and Page 20.
N o t e 2 : There is a case to be derated by ambient temperature. Refer to Page 54.
N o t e 3 : As for the terminal for AE2000-SWA and AE4000-SWA, Vertical terminal type only is
available. (FIX-VT or DR-VT)
N o t e 4 : DR-HVT is available for AE630-SW~AE1600-SW. It is provided a special "Cradle"
and "Terminals", which have adifferent dimensions from the other connection. Refer to
Page 11 and Page 39.
N o t e 5 : This setting is available for change by customer later.A preliminary setting of CL at
factory shipment is as follows.
CL1: 1C
CL2: 1C1D
CL3: 1C1T1D
CL4: 2C1T1D
N o t e 6 : Not available for AE630-SW with CT rating : 250A or 315A or 500A.
N o t e 7 : Not available for WB1 or WB2 Main setting module.
N5 optional setting module is used for 3phase 4wires system.(4Pole breaker or 3pole
breaker with Neutral CT)
N o t e 8 : Neutral CT is required for Ground fault or Neutral pole protection,when 3 Pole breaker
is used for 3 phase 4 wires system.
Note9:
Note10:
Note11:
Note12:
Remark
Order Issuer
Order No.
AE
P9~10
-SW
Number of poles
AE
-SWA
CT rating
Applicable standard
IEC 60947-2
CCC
Ambient temperature
40C(Standard)
Others
Reset type
Connection
Fixed type
Main circuit
terminal
Horizontal terminal(FIX)
P11
units
4P
3P
Rated current
Number of units
(AE630~1600-SW / AE2000~3200-SW)
Vertical terminal(FIX-VT)
(AE2000-SWA / AE4000-SWA)
P17~18
Drawout type accessories
Cell switch(CL: 1 or 2 or 3 or 4)
Short-circuit B-contact(SBC)
Lifting hooks(HP)
Safety shutter(SST)
Shutter lock(SST-LOCK)
Mis-insertion preventer(MIP)
Test jumper(TJ)
Note2
Drawout type
Note3
Note1 P9,P20
Note3
Horizontal terminals(DR)(standard)
Vertical terminals(DR-VT)
Front terminals(DR-FT)
Horizontal-Vertical
Changeable(DR-HVT) Note4
Note5
Additional function
Type
P32
Extension module(EX1)
Note6
Note7
Power supply
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
P1: ACDC100-240V
P2: DC24-60V
Network P33
BIF-CC
BIF-PR
BIF-MD
Temperature alarm(TAL)
MCR switch(MCR-SW)
BIF-CON
BIF-CL
P5: DC100-240V
with output contact (SSR)
Neutral CT(NCT)
P28
Note8
Note9
External ZCT
ZCT
ZT
ZTA
Electrical
accessories
P12~14
AC DC100250V
AC380500V
DC2448V
Special P52
environments
Corrosion resist
P16
AC100110V
AC200220V
N o t e 1 : In case of AE630-SW and AE2000-SW Low rating type, please specify CT rating.
Refer to Page 9 and Page 20.
N o t e 2 : There is a case to be derated by ambient temperature. Refer to Page 54.
N o t e 3 : As for the terminal for AE2000-SWA and AE4000-SWA, Vertical terminal type only is
available. (FIX-VT or DR-VT)
N o t e 4 : DR-HVT is available for AE630-SW~AE1600-SW. It is provided a special "Cradle"
and "Terminals", which have adifferent dimensions from the other connection. Refer to
Page 11 and Page 39.
N o t e 5 : This setting is available for change by customer later.A preliminary setting of CL at
factory shipment is as follows.
CL1: 1C
CL2: 1C1D
CL3: 1C1T1D
CL4: 2C1T1D
N o t e 6 : Not available for AE630-SW with CT rating : 250A or 315A or 500A.
N o t e 7 : Not available for WB1 or WB2 Main setting module.
N5 optional setting module is used for 3phase 4wires system.(4Pole breaker or 3pole
breaker with Neutral CT)
N o t e 8 : Neutral CT is required for Ground fault or Neutral pole protection,when 3 Pole breaker
is used for 3 phase 4 wires system.
Note9:
Note10:
Note11:
Note12:
Remark
Order Issuer
Order No.
AE
P9~10
-SW
Number of poles
AE
-SWA
CT rating
Applicable standard
LR
Ambient temperature
40C(Standard)
GL
BV
Connection
Fixed type
DNV
ABS
Main circuit
terminal
Horizontal terminal(FIX)
(AE630~1600-SW / AE2000~3200-SW)
Vertical terminal(FIX-VT)
Note1 P9,P20
NK
IEC 60947-2
C
Note2
Drawout type
Note3
(AE2000-SWA / AE4000-SWA)
Others
Reset type
P11
units
4P
3P
Rated current
Number of units
Note3
Horizontal terminals(DR)(standard)
Vertical terminals(DR-VT)
Front terminals(DR-FT)
Horizontal-Vertical
Changeable(DR-HVT) Note4
P17~18
Drawout type accessories
Cell switch(CL: 1 or 2 or 3 or 4)
Short-circuit B-contact(SBC)
Lifting hooks(HP)
Safety shutter(SST)
Shutter lock(SST-LOCK)
Mis-insertion preventer(MIP)
Test jumper(TJ)
Note5
Additional function
Type
P32
Extension module(EX1)
Electrical
accessories
P12~14
P15~16
Special P52
environments
P2: DC24-60V
Temperature alarm(TAL)
MCR switch(MCR-SW)
BIF-CC
BIF-PR
BIF-MD
BIF-CON
BIF-CL
P5: DC100-240V
with output contact (SSR)
Neutral CT(NCT)
Note8
Note9
ZCT
ZT
ZTA
AC DC100250V
AC380500V
DC2448V
P1: ACDC100-240V
External ZCT
Network P33
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
P28
Power supply
Corrosion resist
P16
AC100110V
AC200220V
N o t e 1 : In case of AE630-SW and AE2000-SW Low rating type, please specify CT rating.
Refer to Page 9 and Page 20.
N o t e 2 : There is a case to be derated by ambient temperature. Refer to Page 54.
N o t e 3 : As for the terminal for AE2000-SWA and AE4000-SWA, Vertical terminal type only is
available. (FIX-VT or DR-VT)
N o t e 4 : DR-HVT is available for AE630-SW~AE1600-SW. It is provided a special "Cradle" and
"Terminals", which have adifferent dimensions from the other connection. Refer to
Page 11 and Page 39.
N o t e 5 : This setting is available for change by customer later.A preliminary setting of CL at
factory shipment is as follows.
CL1: 1C
CL2: 1C1D
CL3: 1C1T1D
CL4: 2C1T1D
N o t e 6 : Not available for AE630-SW with CT rating : 250A or 315A or 500A.
N o t e 7 : N5 optional setting module is used for 3 phase 4 wires system.(4 Pole breaker or 3 pole
breaker with Neutral CT)
N o t e 8 : Neutral CT is required for Ground fault or Neutral pole protection,when 3 Pole breaker
is used for 3 phase 4 wires system.
Note9:
Note10:
Note11:
Note12:
Remark
Order Issuer
Country / Region
Company
Address
Telephone
Australia
+ 61-2-9684-7586
Belgium
Emac S.A.
+ 32-(0)2-4810211
+ 56-32-320652
Chile
RHONA S.A.
Mitsubishi Electric Automation (Shanghai)
Limited
China
+ 86-(0)21-6475-3228
Colombia
Denmark
+ 57-4-235-00-28
+ 45-(0)43-95-95-95
+ 49-(0)2102-4860
52, Arkadias
STR.GR 121 32. Peristeri Athens Greece.
+ 30-1-57-81-599-699
+ 852-28878870
P.T.SAHABAT INDONESIA.
+ 62-(0)21-6621780
+ 353-(0)1-4505007
+ 390-39-60-531
Israel
+ 972-(0)4-867 06 56
Korea
+ 82-2-3668-6567
+ 856-21-215043, 21-215110
Lebanon
COMPTOIR D'ELECTRICITE
GENERALE INTERNATIONAL
+ 961-1-240430
Malaysia
+ 603-5569-3748
+ 977-1-411330
Egypt
Germany
Greece
Hong Kong
Indonesia
Ireland
Italy
Laos
Myanmer
Nepal
+ 20-2-7961337
+ 64-4-569-7350
Norway
SCANELEC
+ 47-55-506000
Pakistan
+ 92-(0)42-7654342
+ 63-(0)2-643-8691
+ 48-(0)12-632-28-85
+ 966-1-4770149
+ 65-473-2308
INEA d.o.o.
+ 386-(0)17-21 80 00
South Africa
+ 27-11-928-2000
Spain
+ 34-93-595-3131
Sweden
+ 46-(0)300-69 00 40
Trielec A G
+ 41-(0)52-6258425
+ 886-(0)2-2298-8889
+ 66-223-4220-3
+ 31-(0)10-487 19 11
GTS
+ 90-(0)212-2674011
+ 44-(0)1707-276-100
+ 598-2-92-08-08
ADESCO C.A.
+ 58-2-241-7634
New Zealand
Philippines
Poland
Saudi Arabia
Singapore
Slovenia
Switzerland
Taiwan
Thailand
The Netherlands
Turkey
U.K.
Uruguay
Venezuela
Vietnam
Safety Tips : Be sure to read the instruction manual fully before using this product.
FACTORY AUTOMATION SYSTEM: OFFICE TOWER Z 14F, 8-12 1chome, Harumi CHUO-KU, TOKYO 104-6214, JAPAN