Documente Academic
Documente Profesional
Documente Cultură
Abstract
Accurate measurement of the motor and/or motor drive system losses is very important in view of
upcoming stringent standard requirements. The EU eco-design directives 2005/32/EC through
Commission Regulation (EC) No 640/2009 is pushing for use of higher efficiency class motors for
industrial applications through the upcoming efficiency standards for motors and drive systems. For
motors of higher efficiency classes, the measurement of efficiency becomes more critical since small
errors introduced by measurement system have large effect of estimated efficiency. There are well
known established procedures to measure the efficiency of motors fed from sinusoidal supply as
outlined by IEC 60034-2-1 standard. The efforts are made in to draft a new technical specification IEC
60034-2-31 to address the methods to measure the additional losses incurred associated with
Variable Speed Drives (VSD) supplied motors [10] [21]. Similarly, the work is ongoing to describe
methods for measuring the system efficiency of complete motor-drive system for VSD fed motor
drives [7][6]. This draft specification describes either electrical input-output or calorimetric loss
measurement as preferred methods to measure efficiency of motor drive system.
This paper addresses our experience with measuring the VSD fed motor efficiency using calorimetric
loss measurement technique and comparing the measurements with other preferred efficiency
measurement methods. A calorimetric loss measurement system is built for measuring the losses of
motor supplied from a sinusoidal supply mains or VSD. The calorimeter is an open type two phase
system. The thermal equilibrium is established by running the test motor inside the calorimetric
chamber, and then the same thermal equilibrium is re-established using a heating resistor element
supplied from a DC power source. The power fed to the heating resistor at the thermal equilibrium is
subsequently interpreted as the motor losses. A series of tests were performed using calorimeter to
measure the motor losses at different load conditions. The measured losses are then compared with
losses measured with the direct input-output efficiency measurement method. The uncertainties of
calorimetric loss measurements are also established by considering all possible heat leakage points
and instrumentation error sources. Finally both electrical and calorimetric loss measurement results
are compared.
Keywords:- IEC60034-2-1, IEC 60034-2-3, Direct input-output efficiency measurement, calorimetric
loss measurement technique
The technical specification is still in draft stage, the publishing date is scheduled to be in late 2013. http://www.iec.ch
Introduction
The motor efficiency can be measured in a number of ways, IEC 60034-2-1 standard describes
methods for testing induction motors and also suggests the accuracy requirements of different
equipment used for measurements. The direct method (Method 2-1-1A) is the most common and
straightforward way of measuring motor efficiency; it involves testing the motor by coupling it to a
separate load machine together with a torque measurement device on the shaft. The test motor input
and output power is thus directly measured for several load points. The accuracy of the direct
efficiency measurements have been discussed extensively in literature and general observation is
that the method can lead to large measurement errors since it involves measurement of two large
quantities. A slight error in any of the quantity will result into large error in the efficiency. The other
popular and more accurate technique- called the summation of loss method, in fact measures
different loss components like no load losses and load losses separately using no load and load tests.
The additional stray load losses are either estimated by linear regression analysis on measured load
loss (Method 2-1-1B) or by using an assigned value as described by the standard (Method 2-1-1C).
The applicability of which method should be used is also described by the standard. Accordingly, the
stray load loss shall be determined from residual loss for motors up to 2 MW and it is to be calculated
from assigned value for higher than 2 MW machines.
Even with the use of a consistent and accurate efficiency measurement method, variations in the
results for the same motor do occur. This is primarily due to test equipment and instrument
characteristics, and in the case of non-automated testing, due to personnel factors. The situation is
very different when the motor is supplied from Variable Speed Drives (VSD), as the existing standard
is no longer applicable. The effect of PWM voltages applied by the VSD is increase in motor lossesthese are mainly the additional harmonic losses. A new draft specification IEC 60034-2-32 is under
preparation which describes the methods to measure motor efficiency under VSD supply [10][21].
Motor efficiency measurement methods involve use of standard equipment like power meters which
have higher measurement error margins under PWM supply voltages as compared to sinusoidal
voltage condition [23]. Both IEC 60034-2-1 and 60034-2-3 specify the necessary accuracy
requirements for different instrumentation used in the electrical loss measurements. Mainly the
instrumentation used for the electrical loss measurements shall have an accuracy class of 0.2 in
accordance with IEC 60051 and the instrumentation used for measuring mechanical quantities should
have accuracy range of 0.2% of full scale [3]. It has been reported that even when the same motor
has been tested in different laboratories, it was not possible to reproduce the same efficiency values
[6] [9]. This topic has been under review in the standards committee and efforts are being made in to
improve the accuracy of electrical test methods. As of now, more precise loss measurement under
these situations can be done using calorimetric loss measurements. The uncertainty associated with
calorimetric loss measurement is much lower than input-output method while measuring the higher
efficiency systems/components as reported in [22].
Calorimetric system measures actual loss in terms of generated heat of the machine, which is very
much different in principle from other methods described in the above standard specifications. The
heat dissipated in the test objects results in the temperature rise of the cooling medium. The
temperature rise is measured together with the coolant flow inside the calorimetric chamber. By
knowing the relative humidity, absolute pressure and temperature rise, the actual heat loss can be
calculated. This approach is termed as closed cycle calorimetric loss measurement.
In another approach, referred to as an open type calorimetric system, the measurements are carried
out in two stages. In the first stage- calibration phase, the induction motor is driven with specific load
and the respective temperature rise at known coolant flow rate is established. Then in the second
stage- balance phase, the DC power is fed to a known resistor network placed inside the box. This
power fed to the resistor is adjusted until the same thermal equilibrium as calibration phase is
achieved, which is then taken as the motor loss during the calibration phase. The open type
calorimetric loss measurement is simpler, mostly uses air as cooling medium and with proper care for
considering heat leakages, accurate results can be obtained.
The technical specification is still in draft stage, the publishing date is scheduled to be in late 2013. http://www.iec.ch
Still calorimetric loss measurements often involve more complex and time consuming tasks and thus
this method cannot be used for routine testing but rather should be used as an evaluation tool for
confirming the accuracy of efficiency measured by other methods. This is the main motivation for this
paper. The paper presents construction of a test setup which is capable of performing both
calorimetric loss measurements and electrical efficiency measurements simultaneously. The paper
addresses some common issues with calorimetric loss measurement systems involving electric
motors as test objects. The paper is organized as follows. First a literature overview of the calorimetric
loss measurement method is presented, with more focus on application to measurements involving
the electric motor as test object. Then the common issues, and difficulties associated with loss
measurements are discussed, and solutions are proposed. The main cause of heat leakage which
deteriorates the accuracy of measurements, and methods to account for these losses is described.
Then the actual measurement results by calorimetric loss measurement method performed on a test
motor at different load conditions are presented and compared with the losses measured by electrical
direct input-output power measurement method.
Minimize and estimate the heat loss from the walls and other sealing places
Mounting of motor inside calorimeter and arrangement for shaft opening and sealing
arrangement.
Accurately control and measure the air (or other mass) flow rate, minimize disturbance by
motor fan
The last two requirements is very specific to the measuring motor losses. Since the heavy motor mass
has to be securely mounted inside the calorimeter and the shaft has to be brought out. It is very
important to contain any heat leakage either from shaft opening or through the motor mounting bolts
in such situation. This heat leakage from different sources has to be calculated and used to readjust
the measured motor losses through dissipated heat loss. The next section of the paper presents
construction of the calorimetric measurement system and describes novel solutions to minimize the
heat leakages from both of the above mentioned points.
measurement of the mechanical speed and torque at the motor shaft. Both test and load motor
converters can be controlled from the central control system.
Supply
mains
L1
L2
L3
Load
Converter
Load machine
DC power
supply
Supply
mains
Current
Sensors
Test
Converter
L1 L2 L3
Current
Sensors
Heating
Resistor
Test Object
Calorimeter
Torque, Speed
Acquisition
I
Precision power
analyzer
U
Precision power
analyzer
Control system
The control system is designed on LabVIEW platform which runs on a control and data logging
computer. The LabVIEW comes with basic library function to establish interface with wide variety of
sensing, data acquisition and monitoring equipments and instruments. The interface to temperature
data logger, DC power supply, power analyzer is designed using these standard functions. The
interface with the test, load and blower fan drive is build using standard Modbus over Ethernet IP
protocol. The main tasks of the control system are described as below-
PID control for controlling heating resistor power during balance phase
Basic protection functions for chamber, motor over temperature and motor over speed
in two ways- first as function of input power (Pin) and losses (PL) and secondly as a function of losses
(PL) and output power (Pout). The efficiency calculation using both methods is shown in Table 1.This is
followed by calorimetric loss measurements at rated load point.
Table 1: Summary of motor efficiency measurement using electrical methods
Load Torque [%]
Efficiency (%)
Indirect method
(Pin - PL)/Pin
Pout/(Pout + PL)
Direct input-output power measurement
115
100
75
50
25
90.5
90.4
90.2
91.2
91.2
90.2
91.9
91.9
90.9
91.6
91.6
91.6
88.1
88.0
91.2
Calibration
phase
Balance phase 1
(motor standstill)
Balance phase 2
(motor running at nominal speed)
Temp Diff, T
Blower speed, Nblower
Blower freq
PL* (Pe_in-Pm)
Heating res. Current, Ires.
C
RPM
Hz
W
A
30.0
3199.6
53.30
1598.2
-
30.0
3198.1
53.30
30.0
3198.1
53.30
17.8
17.1
V
W
92.9
1651
89.7
1534.8
Figure 6: Temperature profile at various points during balance phase (a) outlet pipe, (b) input
pipe, (c) motor, (d) heating resistor power, (e) motor side temperature inside calorimeter, (f)
air blower speed
This is shown in Figure 6 (e), the motor side temperature sensors show around 12 degrees difference
between the top and middle temperature sensor. This even creates a temperature gradient inside
9
motor body which is evident from Figure 6(c). The temperature sensors mounted inside motor at
different locations show different temperatures. One option to create similar air circulation during
balance phase is to rotate test motor with the help of load motor in the same direction. The load motor
drive is now configured in speed control mode and controls the speed of the motor equal to the speed
during calibration phase. The temperature gradient diminishes as the test motor is started (at 18:00 hr
as shown in Figure 6). The balance phase after this point is referred as balance phase 2. The
heating resistor power during both balance test phases was found to be equal to 1651 W and 1552
W, the different between these two readings is ~100 W.
The main reason for this variation is that the thermal equilibrium (and air circulation) under both
balance phase conditions is very different to each other. When the test motor is driven from load
machine, the friction losses in the test motor are supplied by load machine through motor shaft. This
causes reduction in the power in the heating resistor. Thus the friction losses supplied by load
machine plus heating resistor power shall be considered as total losses during balance phase 2. The
shaft power recorded by torque transducer is equal to 107 watts in balance phase 2. As mentioned
above, the difference in the heating resistor power during balance phase 1 and balance phase 2 is
~100 W. Thus it can be concluded that when the test motor is rotated using the load drive to avoid
temperature gradients, part of the losses (which are mainly friction and windage losses inside test
motor) are supplied by load motor. This power should be considered together with heating resistor
power is determine total power loss inside calorimeter during balance phase.
Still the mechanical power measured by torque transducer (as described above) can be very
erroneous as the torque value in above case is a few percent of the rated torque for the transducer.
This can lead to significant errors in torque or power measurements under this condition.
During the calibration phase, the test motor is rotated using load machine but no power is fed
to the heating resistor. During this phase, the losses inside the calorimetric chamber are only
friction and windage losses inside test motor. The temperature rise and blower fan speed is
recorded when the thermal equilibrium is reached. It should be noted that in this phase, since
the power losses inside the chamber are very small, the temperature gradient is set to very
low value, to achieve reasonable blower speed. Otherwise the blower fan may run at very low
speed. For better accuracy, the calibration phase is first performed with temperature gradient
setting of 4 0C and then again with 2.7 0C to obtain two different blower fan speeds for thermal
equilibrium. The recoded blower speed at thermal equilibrium is both cases were 1440 rpm
and 2170 rpm respectively.
This is followed by a balance phase in which the temperature gradient and blower speed
obtained from calibration phase are set as reference and the DC power to heating resistor
elements is controlled to obtain desired temperature gradient. The resulting heating power,
blower speed and temperature gradient for two independent temperature gradients of 4 0C
and 2.7 0C (i.e. the friction losses) are equal to 94 watts and 113 watts. Again this closely
matches with the 100 W power difference recorded during balance phase 1 and 2 described
in previous section.
The test motor can be rotated using load machine during the balance test to maintain the
homogeneous temperature distribution inside calorimeter. This avoids large temperature
gradients which otherwise can be generated inside the box because of no air circulation
during balance phase.
In this condition, the total power loss in the balance test is the sum of power input to heating
resistor and motor friction and windage losses which are fed by the load motor through motor
shaft.
10
This part of loss i.e. motor friction and windage loss, fed by load motor can be measured from
torque transducer or a separate set of calibration and balance test can be performed. The
results from this balance test closely match with the power recorded by torque transducer.
---
1651
90.1
----
1647.8(1534.8 heating
resistor + 113 friction
loss from load motor)
90.1
Aluminium plate
Heating
resistor
Steel
plate
heater side
temp.
sensors
Middle temp.
sensors
Air circulation
fans
Motor
Motor side
temp.
sensors
Figure 7: Use of separate fans on calorimeter ceiling for air circulation inside the calorimeter
The difference in temperature between upper and lower temperature sensors during balance tests
with use of auxiliary fans is compared with balance test 1 described in pervious section. Figure 8
11
shows the temperature gradient between top and bottom temperature sensors at three different
locations shown in Figure 7; "motor side" refers to the temperature sensors towards motor side,
"heater side" towards heater side, and "middle" is in between heater and motor. The reduction in the
temperature gradient is clearly evident. The largest reduction in temperature gradient is obtained
directly under the circulating fan (for ex. Heater side temperature difference is reduced from 22.3 0C to
1.8 0C. On the other hand, the reduction in temperature is only 6.10 (from 17.5 0C to 11.4 0C) in the
central part. Thus placement of the circulation fans is very important. It is recommended that more
number of small fans shall be used rather than using one big fan.
Figure 8: Effect of air circulation fans on temperature gradient inside the calorimeter at three
locations
Calibration phase
First calibration test is performed for four different load conditions at rated speed with suitable
temperature gradient. The results are summarized in Table 4. A higher value of temperature gradient
T is required for nominal load conditions to handle higher loss inside calorimeter and it is gradually
decreased for partial load conditions. Thus the motor ambient temperature for all load conditions is
not similar. The blower speed Nblower at thermal equilibrium is summarized in Table 4 for different load
conditions. The electrical measurements like motor input power Pe_in, output (mechanical) power Pout,
and so the motor loss PLoss, motor is also recorded during the test so that the motor efficiency as per
direct input-output methods is known instantaneously.
Balance phase 1
The balance phase 1 is performed right after calibration phase and the test motor is rotated using load
motor in this phase to maintain the air circulation. The temperature gradient T and blower speeds
Nblower obtained in calibration phase are used as input variables and the calorimeter is allowed to
settle at thermal equilibrium by controlling the DC power fed to heating resistor elements. The heating
resistor power Pres. at thermal equilibrium condition is taken as the heat loss inside the calorimeter. As
the motor is rotated using load motor, the mechanical power from torque transducer is also recorded
which indicates the friction and windage losses for the test motor. Instead the second approach (as
described in previous section) is followed to estimate this power flow into the calorimeter through
motor shaft (i.e. the friction and windage loss supplied by load motor) by performing a separate set of
calibration and balance phase experiment. During the calibration phase, the tests motor is driven by
12
load motor and thermal equilibrium is established. As the friction and windage loss is a small
percentage of the total loss handling capacity of the calorimeter, the errors in the measurement are
anticipated. To increase the measurement accuracy, a constant power of 500 W is fed to heating
resistor as a bias power. The thermal equilibrium at temperature gradient of 5 0C is established at
1800 rpm. The blower speed value obtained at thermal equilibrium is used as reference value during
balance phase. The corresponding DC resistor power was found to be equal to 613 W under thermal
equilibrium. Thus the friction and windage loss power supplied from load motor is equal to the 113 W
(500 W being the bias power). This is used as mechanical power input Pmech during calculation of
total losses during balance phase 1.
Balance phase 2
A second set of balance tests is performed in which the air circulation inside calorimeter is maintained
using separate fans. The DC power fed to these auxiliary fans Pfan is also measured with power
meters, and kept constant around 22 W. The resulting heating resistor power Pres. at thermal
equilibrium for blower speed Nblower and temperature gradient T values obtained from calibration
phase for different load conditions is summarized in Table 4.
Table 4: Summary of calorimetric loss measurement tests with PWM supply conditions
Calibration phase
Balance Phase 1
Balance Phase 2
Motor loss
Direct input-output
Calorimetric- Balance phase 1
Calorimetric- Balance phase 2
Efficiency
Direct input-output
Calorimetric- Balance phase 1
Calorimetric- Balance phase 2
Load Torque
Pe in
Pout
PLoss, motor
T
Nblower
T
Nblower
Pres.
Pmech
Ptotal_1
T
Nblower
P res.
Pfan
Ptotal_2
[%]
kW
kW
W
0
C
RPM
0
C
RPM
W
W
W
0
C
RPM
W
W
W
100
16.8
15.0
1837.3
20.0
1447.7
20.0
1444.9
1729.9
113.0
1842.9
20.0
1445.8
1793.3
22.0
1815.3
75
12.6
11.4
1156.0
9.0
2008.4
9.0
2006.9
1069.6
113.0
1182.6
9.0
2010.3
1163.4
22.1
1185.5
50
8.6
7.8
812.4
5.0
2516.9
5.0
2507.9
691.0
113.0
804.0
5.0
2501.8
804.4
22.1
826.5
25
4.3
3.7
608.7
5.0
1628.0
5.0
1614.0
434.7
113.0
547.7
5.0
1614.0
515.7
22.3
538.0
PLoss, motor
Ptotal_1
Ptotal_2
W
W
W
1837.3
1842.9
1815.3
1156.0
1182.6
1185.5
812.4
804.0
826.5
608.7
547.7
538.0
%
%
%
89.1
89.0
89.2
90.8
90.6
90.6
90.6
90.7
90.4
85.9
87.3
87.5
The summary of motor loss and motor efficiency values determined based on above calibration and
balance phase tests are also given in Table 4. The results obtained with direct input-output and
calorimetric loss measurement system are in close agreement with each other. The only exception is
at 25% load torque where the electrical measurements deviate from calorimetric loss measurements
by approximately 50 W. The power loss inside calorimeter in this situation is small, thus small errors in
loss measurement leads to large variation in efficiency value.
13
Motor shaft
The heat flow through the motor shaft occurs due to different surface temperature inside and outside
the calorimeter. Two temperature sensors are mounted at these locations and used to monitor the
temperatures during the tests. Then the actual heat conduction through motor shaft is determined
based upon the temperature gradient, cross section area, and length of shaft between the
temperature sensors as
pshaft kA
Where
Tshaft
(1)
pshaft is heat conduction through shaft, k is the thermal conductivity (Wm1K1), A is the area of
cross section (m2), Tshaft is the temperature difference (K), and x is the distance of heat flow (m) [12].
For steel shaft, the diameter is 42 mm, the thermal conductivity of the steel is 50 (Wm1K1) [20], and
the distance between the inner and outer temperature sensor 150 mm (insulation width). The
corresponding values of heat flow through shaft are given in Table 5 for both calibration and balance
phase (the analysis is only performed for balance phase 1 described in previous section). It should be
noted that the temperature gradient across the shaft is a negative value for 20%, 50% and 75% load
condition. This is due to the local heat produced by the supporting bearing on the interconnecting
shaft. It is found that the outer bearing is producing more heat than the bearing inside calorimeter and
thus the actual heat flow is in reverse direction.
Mounting bolts
The motor baseplate is secured to the foundation using four glass fiber bolts. Two temperature
sensors are mounted on top and bottom of the one of the bolts to measure the heat conduction
through these bolts and the temperature measurements at these points are recorded during
calorimetric tests. Since the glass fiber bolts are good resistors of heat (thermal conductivity of glass
fiber is 0.04 (Wm1K1)), the heat flow through the bolts is very small. Thus the temperature recorded
by temperature sensors mounted on outer side of bolt does not show any influence from the
temperature inside calorimeter (although it is changing with respect to change in ambient room
temperature, this is indicated by Bolt_ambient in Table 5). It can be concluded that the heat leakage
through the mounting bolts can be neglected.
Calorimeter surface
The heat flow through calorimeter surface can be expressed as,
(2)
where U surface is heat transfer coefficient of calorimeter wall material, S surface is the surface area and
Tsurface is the temperature gradient between inner and outer surface of the calorimeter [12]. The
temperature of the inner surface is very difficult to measure. Even though the proper heat circulation
inside the calorimeter chamber is maintained, the inner surface temperature at different points is not
constant due to local vertical temperature gradients. Therefore average of the temperature measured
14
by sensors inside calorimeter is considered as inner surface temperature. The total heat leakage
pleakage from calorimeter is determined as below
(3)
The estimated value of heat dissipation according to the above described procedure is summarized in
Table 5 for calibration and balance phases.
Table 5: Estimation of heat leakage through different points
Calibration phase
Load Torque
Temp, Shaft inside
Temp, Shaft outside
Tshaft
pshaft
75
46.1
47.0
50
41.3
44.8
25
39.2
46.8
6.6
-1.0
-3.5
-7.6
W
C
0
C
0
C
0
C
3.1
42.4
20.6
21.5
21.8
-0.4
31.7
21.3
22.6
10.4
-1.6
26.8
21.0
21.7
5.9
-3.5
24.5
19.9
21.1
4.6
Bolt ambient
Surface
1.0
1.3
0.8
1.2
20.3
9.2
5.4
5.1
W
C
0
C
0
C
50.2
51.6
51.2
0.4
22.9
40.6
46.8
-6.2
13.4
36.5
45.9
-9.4
12.6
37.4
46.9
-9.5
0.2
43.4
-2.9
29.0
-4.4
22.8
-4.4
23.6
21.4
20.6
20.4
20.2
22.2
8.4
1.6
21.1
2.3
0.7
21.1
3.4
1.0
psurface
Temp, Shaft inside
Temp, Shaft outside
T
pshaft
Tsurface
psurface
pleakage
100
55.8
49.2
Tsurface
Balance phase 1
[%]
C
0
C
0
Calibration phase
Balance phase 1
Difference
C
0
C
0
22.7
22.0
1.3
20.8
7.4
3.6
4.9
W
W
W
51.6
53.3
51.8
1.5
18.4
22.4
15.5
6.9
9.0
11.8
4.7
7.1
12.1
9.0
7.7
1.3
It can be seen from Table 5 that the biggest portion of the heat leakage is from the calorimeter
surface whereas the heat leakage from motor shaft and mounting bolts is comparatively small. As
mentioned earlier, the accuracy of the calorimetric loss measurement is dependent upon the
difference between the heat leakage during calibration and balance phase. This difference is very
small compared to the actual loss measured during the tests as shown in Table 5. Thus its addition to
the actual measured loss will not result into big variation in the efficiency values which are presented
in Table 4. This also confirms the superior construction of the calorimeter.
15
Conclusions
The main purpose of the work is to validate the electrical (direct input-output) efficiency
measurements procedures being used extensively in ABB using alternate efficiency measurement
methods like calorimetric loss measurement. A calorimetric loss measurement system is built for this
purpose and series of the tests were performed to measure the efficiency of the induction motor at
different load conditions. The special construction methods are followed to avoid any heat leakage
through motor shaft and motor mountings. These are the main concerns (points of heat leakage)
when measurements on electric motor are performed inside calorimeter. The electrical efficiency is
determined as per direct input-output method and this was followed by calorimetric loss measurement
on rated load condition under converter supply. Because of the cooling fan of the motor, the air
circulation inside calorimeter is gets affected during calibration phase. To maintain the similar
conditions as calibration phase, the test motor is rotated with the help of load machine during balance
phase. The additional power flows inside calorimeter through motor shaft during this condition which
is the friction and windage losses inside test motor and this power should be accounted in the total
losses during calibration phase. A separate set of calibration and balance phase is performed to
measure this power flow from motor shaft. The measured friction and windage loss is then considered
together with heat resistor power to determine the total loss under different load conditions. The
resulting loss and efficiency values are in close agreement with the direct input-output method.
The heat leakage by conduction through shaft is calculated based on measured shaft temperature
inside and outside of calorimeter. Similarly, the non-variation of temperature recorded by temperature
sensor at outer side of mounting bolt indicates that there is no heat leakage through the mounting
bolt. It is seen that the estimated value of leakage loss is smaller as compared to the power loss
measured by calorimeter and thus considering the leakage value in total loss will not change the
estimated efficiencies considerably.
It is also observed that the calorimeter accuracy can be further enhanced by controlling the
temperature of the inlet air to the calorimeter. Since the calorimeter stability is based on temperature
gradient between inlet to outlet temperature, any slight variation in inlet temperature will cause the
whole motor mass inside the calorimeter either to absorb or dissipate the heat. This introduces errors
in the loss measurement. Clearly, the situation can be avoided by use of external inlet temperature
controller. Another source of error is the friction loss produced by the supporting bearing used for
interconnecting shaft. One of the support bearing is inside the calorimeter. The heat produced by this
bearing also contributes to the heat inside calorimeter. Thus the losses measured by calorimeter are
higher than the actual motor losses. Suitable methods to measure and compensate for these bearing
losses are the next steps towards accurate loss measurements using calorimetric method.
References
[1] IEC 60034-30, Rotating electrical machines Part 30: Efficiency classes of single-speed,
three phase, cage-induction motors, Edition 1, 2008
[2] IEC 60034-30 Ed. 2: Rotating electrical machines Part 30: Efficiency classes (IE-code),
Committee draft, 2011-xx-xx
[3] IEC 60034-2-1, Rotating electrical machines Part 2-1: Standard methods for determining
losses and efficiency from tests (excluding machines for traction vehicles), Edition 1.0, 200709
[4] IEC 60034-2-3, Rotating electrical machines Part 2-3: Specific test methods for determining
losses and efficiency of converter-fed AC induction motors, draft edition
[5] IEC 60034-31, Rotating electrical machines Part 31: Selection of energy-efficient motors
including variable speed applications Application guide, Edition 1.0, 2010-04
[6] prEN 50589-1 Procedure for determining the energy efficiency indicators or motor driven
applications by using the extended product approach and semi analytical model, CENELEC,
20xx.
16
[7] Zwanziger P., Energy-Efficiency Standards for Industrial Power Drive Systems and the
Driven Equipment in Consequence of EU Mandates M/470 and M/476, CENELEC,
http://www.eco-motors-drives.eu/
[8] A. Mhle, Determination of motor efficiency on the basis of IEC600034-2-1 Round-Robin
testing for the improvement of the standard, in Proc. 2010 Motor Summit, Zrich,
Switzerland, Oct. 2010, pp. 3839.
[9] Baghurst A.H., et al, Towards a standard algorithm for the calculation of induction motor
efficiency based on International Standard IEC 60034-2-1 EEMODS11 conference
th
2012, Zurich,
[11] Rasilo, P.; Ekstrm, J.; Haavisto, A.; Belahcen, A.; Arkkio, A., "Calorimetric system for
measurement of synchronous machine losses," Electric Power Applications, IET , vol.6, no.5,
pp.286,294, May 2012
[12] Aarniovuori, L.; Kosonen, A.; Niemela, M.; Pyrhonen, J., "Calorimetric measurement of
variable-speed induction motor," Electrical Machines (ICEM), 2012 20th International
Conference on , vol., no., pp.872,878, 2-5 Sept. 2012
[13] Lindstrm, J.: Calorimetric methods for loss measurements of small cage induction motors.
Masters thesis, Helsinki University of Technology, 1994
[14] W. Cao, G.M. Asher, X. Huang, H. Zhang, I. French, J. Zhang, and M. Short, Calorimeters
and techniques used for power loss measurements in electrical machines, IEEE Instrum.
Meas. Mag., vol. 13, no. 6, pp. 2633, Dec. 2010.
[15] Szabados, B., Mihalcea, A.: Design and implementation of a calorimetric measurement
facility for determining losses in electrical machines, IEEE Trans. Instrum. Meas., 2002, 51,
(5), pp. 902907
[16] Cao, W., Bradley, K.J., Ferrah, A.: Development of a high-precision calorimeter for
measuring power loss in electrical machines, IEEE Trans. Instrum. Meas., 2009, 58, (3), pp.
570577
[17] Cao, W., Huang, X., Fench, I.: Design of a 300-kW calorimeter for electrical motor loss
measurement, IEEE Trans. Instrum. Meas.,2009, 58, (7), pp. 23652367
[18] Turner, D.R., Binns, K.J., Shamsadeen, B.N., Warne, D.F.: Accurate measurement of
induction motor losses using balance calorimeter, IEE Proc. B, 1991, 138, (5), pp. 233242
[19] Bowman, J.K., Cascio, R.F., Sayani, M.P.,Wilson, T.G.: A calorimetric method for
measurement of total loss in a power transformer. PESC 91 Record. 22nd Annual IEEE
Power Electronics Specialists Conf., June 1991, pp. 633640
[20] J.P. Holman, Heat Transfer, McGraw-Hill publications, 7th ed., ISBN-0-07-112644-9
[21] Aldo Boglietti, Andrea Cavagnino, Marco Cossale, Alberto Tenconi, and Silvio Vaschetto,
Efficiency determination of converter-fed Induction Motors: Waiting for the IEC 60034-2-3
Standard, IEEE Energy Conversion Congress & Exposition (ECCE), Denver, CO, USA, 1519 September 2013
[22] Kosonen, A.; Aarniovuori, L.; Pyrhonen, J.; Niemela, M.; Backman, J., "Calorimetric concept
for measurement of power losses up to 2 kW in electric drives," Electric Power Applications,
IET , vol.7, no.6, pp.,, July 2013
[23] IM 760301-01E WT3000 Precision Power Analyzer User's Manual
17