TECHNICAL SPECIFICATION
OF
ELECTRICAL MATERIALS
(AB SWITCH, HG FUSE AND DO FUSE)

GROUP I & J

Details of require materials:


Sl No

Item Description

Unit

Quantity

3 Pole 11kv 200A A B Switch (H)

Set

1954

3 Pole 11kv 200A H.G. Fuse

Set

1829

2 Pole 11kv 200A A B Switch (H)

Set

250

2 Pole 11kv 200A H.G. Fuse

Set

250

3 Pole 11kv 400A A B Switch (H)

Set

250

3 Pole 11kv 200A DO Fuse

Set

625

2 Pole 11kv 200A DO Fuse

Set

625

3 Pole 33kv 200A A B Switch (H)

Set

150

3 Pole 33kv 200A H.G. Fuse

Set

150

10

3 Pole 33kv 400A A B Switch (H)

Set

150

11

3 Pole 33kv 400A H.G. Fuse

Set

150

NB: 1. Bidders should put their authorized signature with office seal on each page of
the documents.
2. Bidders should put their offer in the Guaranteed particulars column furnished
in the tender documents.
3. Purchaser may ask to the bidder who will qualify in Techno- Commercial
evaluation of the tenders for submission of Samples for verification , if
required.
4. Purchaser reserves the right to increase or decrease the above quantities
during placement of purchase order or may cancel any item/items without
assigning any reason thereof .
Dy. General Manager (C&P)
NESCO, Balasore, Odisha

11 KV 200 Amp 3 Pole AB Switch


Technical Specification
01.0

Scope: This specification covers manufacturing testing and supply of 11KV 200 Amps 50HZ
Air Break switches for outdoor installation in horizontal configuration. The switches are
suitable for operation under off load conditions only and are intended for use on
Distribution Sub stations and tapping sectionalizing points of 11 KV lines.

02.0

Description of the materials: The 11KV A.B. Switch sets shall confirm to the following parameters: a.
b.
c.
d.
e.
f.
g.
h.

Number of poles
Number of Post insulator per pole
Nominal system voltage
Highest system voltage
Rated frequency
System earthling
Rated nominal current
Altitude of installation

3
2nos12KVpostinsulator.
11KV
12KV
50Hz
effectively earthed.
200 amps
Not exceeding1000M

The post insulators used in the A.B. Switches shall have the following ratings :a.
b.
c.
d.
03.0

Power frequency withstand voltage (dry)


Power frequency withstand voltage(wet)
Implies withstand voltage(dry)
Power frequency puncture withstand

35KV (RMS)
35KV (RMS)
75KV
1.3

Standards: The AB Switch Set shall conform to the following standards: a. IS-9920 (Part-I to V)
b. IS-2544/1973 (for porcelain post insulators)
c. IS-2633, (for galvanization of ferrous parts.) or its latest amendments if any.

04.0

Insulator make: 12KV post insulators complete with post and cap duly cemented to be used in the AB
Switch Set conforming to IS-2544/1973.
The bidder shall furnish the type test certificate of the post insulators from their
manufacturer for reference and scrutiny.
The bidder shall mention make, type of insulation materials, metal fittings,
Creepage distance, protected Creepage distance, tensile Strength, compressing
strength, torsion strength and cantilever strength.

05.0

Climatic condition: The A.B. Switch set shall be suitable for operation under the following climatic
conditions.
a. Maximum ambient air temperature
b. Maximum daily average air temperature
c. Maximum yearly average ambient air temperature
d. Maximum temperature attainably by a body
e. Exposed to the Sum.
f. Minimum ambient air temperature
g. Maximum relative humidity
h. Minimum number of rainy days per annum
i. Average number of rainy days per annum
j. Average annual rain fall
k. Number of months of tropical monsoon conditions
l. Maximum wind pressure
m. Degree of exposure to atmospheric pollution
n. Atmosphere.

06.0

45 o C
35 o C
30 o C
50 o C
0o C
100%
70
120
150cm.
4
260Kg./mm2
normally
Polluted.

Other technical details: -

06.01 General: - The 11KV A.B. Switch Set shall be the gang operated rotating single air
break type having 2 post insulators per phase. The operating mechanism shall be
suitable for manual operation from the ground level and shall be so designed that
all the three phases shall open or close simultaneously. The Switches shall be
robust in construction, easy in operation and shall be protected against over travel or
staining that might adversely affect any of its parts. The required base M.S. Channel
(hot dip galvanized) phase coupling rod, operation rod with intermediate guide braided
with flexible electrolytic copper, tail piece of required current carrying capacity and
operation mechanism with ON & OFF positions shall be provided. The operation
rod shall be medium gage of 32mm diameter nominal bore G.I. pipe single length 6
meters. The phase coupling rod for gang operation shall be of medium gauge 25mm
dia &2100 mm length nominal bore G.I. pipe. The Rating post insulators shall be
provide with suitable bearing mounted on a base channel with 8mm dia thrust collar
and 6mm split pin made out of stainless steel. The operating down rod shall be
coupled to the spindle (minimum dia 32mm) for gang operation through another
suitable bearing by two numbers 10mm dia stainless steel bolts with double nuts.
All the bearings shall be provided with grease nipple. All metal (ferrous) parts
shall be galvanized an polished. The pipe shall be galvanized in accordance with IS4736/1968.The post insulators should be fixed with the base channel using
Galvanized Nuts and Bolts.
06.02. Mounting:- The A.B. Switches shall be suitable for horizontal mounting in double pole
sub-station structures. MS Galvanized base Channel & base support channel
should be of min. size 75x40x6 mm.
06.03. Switching Blades: - It shall be made out of electricity copper with silver plated.
The approximate size shall be 220mm X 35X 6mm. The Switch shall have such a spring
mechanism so as to ensure that the speed of the opening of contact is independent
of speed of manual operation.

06.04 Fixed Contacts: - The Fixed Jaw type female contacts o f s ize (70x35x6) mm
shall be made of electrolytic copper (minimum 95% copper composition) duly
silver coated controlled by phosphorous bronze high pressure spring housed in robust
G.I. Cover. It is essential that provision shall be made in fixed female contracts to
take the shock arising from the closing of move contract blade without the same
being transmitted to the post insulator. The arrangement made in this regard shall be
specifically shown in the drawing.
06.05 Arcing Horn: - As the switches are generally meant for isolating transmission line
and distribution transformers, suitable arcing horns shall be provided for breaking
the charging current horn shall be made of 8 mm dia G.I. Rod with spring assisted
operation.
06.06

Terminal Connectors: - Terminal connectors shall be robust in design. The size of


fixed connector shall be (65 X 35 X 6 mm) and size of movable connector shall be of
(65 X 35) X (65 X 35) X 6mm of copper casting with uniform machine finishing duly
silver plated made out of minimum 95% copper composition with 2 nos. 12mm dia
holes provided with suitable brass bolts and double nuts, flat washers & 2nos.
bimetallic solder less sockets suitable up to 55 mm2 conductor.

06.07Spacing: - The minimum clearance between phases to the switch shall be


760mm. The operation down rod shall be at a transverse distance of 300mm from the
outer limb of the switch. The centre spacing between two post insulators of the same
phase shall be 380 mm. In the open position of the A.B. switches the moving blade shall
rotate through 90 o. This shall be exhibited in the drawing.
06.08 Sample, Drawing & Literatures: - Three copies of drawings of 11KV 200 Amps.
A.B. Switch shall be furnished along with the tender. Technically successful bidder is to
be asked for submission of Sample for verification.
06.09 The details of construction and materials of different parts of the A.B. Switch shall clearly
be indicate in the tender and illustrative pamphlet / literature for the same shall be
submitted along with the tender.
07.0

TEST & TEST CERTIFICATE: -

07.01 Type Test: - Certificate for the following type tests conducted on a prototype set of A.B.
Switch in a NABL approved test house/CPRI shall have to be submitted along with
offer.
Dielectric Test (impulse and one minute were power frequency withstand voltage test.)
Temperature rise test (for contracts and terminals)
Shorts Time current and peak withstand current test.
Mainly active load breaking capacity test.
Transformer off-load breaking capacity test.
Line charging breaking capacity test.
Cable charging breaking test.
Operation and mechanical endurance test.

Mechanical strength test for post insulator, as per IS-2444/1937 shall be


furnished.
Test for galvanization of metal (ferrous) parts.

07.02 Routine /Acceptance Test: The inspection may be carried out by the Purchaser at any stage of manufacture. The
successful bidder shall grant free access to the Purchasers representative at a
reasonable time when the work is in progress. The following routine tests shall have
to be conducted on each set and results are to be furnished for consideration of
deputing inspecting officer for inspection and conduction testing of the materials at the
works of the manufacturer. the supplier shall give fifteen days advance intimation to
the Purchaser to enable him to depute his representative for witnessing the tests.
1. Power frequency voltage dry test.
2. Measurement of resistance of main circuit.
3. Tests to prove satisfactory operation.
4. Dimension Check
5. Galvanization test.
6. Operational test.
08.00 Guaranteed Technical Particulars: The bidder shall furnish the guaranteed technical particular duly filled in the format
along with the tender.
09.0

Completeness of Equipment: All fittings, accessories of apparatus which may not have been specifically
mentioned in this specification but which are usual or necessary in equipment of similar
plat shall be deemed to be included in the specification and shall be supplied by
the Tender without extra charge. All plant and equipment shall be completed in all
details whether such details are mentioned in the specification or not.

11 KV 200 Amp 2 / 3 Pole AB Switch


Guaranteed Technical Particulars
Sl.
No

Particulars

Requirement

Makers name & Address

To be specified by the bidder

2
3
4

Type of Switch
Suitable for mounting
No. of Breakers per phase

Rotating Type
Horizontal only
Single Break

No. of Post Insulators per


phase
Post Insulators
Makers
Name
&
Country of Manufacture of
Post Insulator
Type of cementing

2nos. of 12KV Post Insulators as per


IS:2544/73 per phase
To be specified by the bidder as per
CPRI Test Report

6
(a)

(b)

Original Cementing. The insulator to


be cemented with MCI (Hot dip
galvanised
/Al Alloy cap and
MCI/Forged steel
hot
deep
galvanized pedestral) as per IS:
2544/1973

(c)

Power frequency withstand 35 KV RMS


voltage (Dry)

(d)

35 KV RMS

(e)

One minute Power


frequency withstand
voltage (wet)
Visible discharge voltage

(f)

Dry flash over voltage

85 KV

(g)

Power frequency puncture


withstand voltage

1.3 times of actual dry flash over


voltage

(h)

Creapage distance

320 mm minimum (ISS-2544/1973 &


relevant IEC)

(7)

Impulse
withstand
voltage for positive &
negative
polarity
(1.2/50 micro second wave)

9KV RMS

Bidders offer
2 pole
3 pole

(a)

Across the isolating distance 85KV Peak

(b)

To earth & between poles

Rated one minute


Power
frequency
withstand voltage
Across the Isolating
distance
To earth & between poles

(a)
(b)
9(a)

75KV Peak

32KV(RMS)
28KV(RMS)

Rated voltage nominal/


maximum
Rated normal current and
rated frequency
Rated
short-circuit
making capacity

11/12KV

11

Rated Short-time current

10KA

12

Rated peak withstand current

40KA

13

Rated mainly active load 200 Amp.(RMS)


breaking capacity

14

Rated Transformer off load 6.3 Amp.(RMS)


breaking capacity

15

Rated line charging breaking 2.5 Amp(RMS)


capacity

16

Minimum
between

(a)

Switch closed (center to


760mm
center)
Switch opened (Center of
380mm
post insulator to the edge
of the blade)
Temperature
rise
The 650C
Temperature rise
should
not exceed the maximum
limit to 65oC at an ambient
temperature
not
exceeding 40oC

(b)
10

(b)

17

200 Amps. 50hz


25KA (Peak)

clearance
adjacent phase

18

19

Copper contacts silver faced 50oC


terminal of switch intended to
be conducted to external
conductor by bolts or screws
at an ambient temperature
should not exceed.
Vertical
clearance from 254 mm
top of insulator cap to
mounting channel.
Type of contact
a) Self aligned high pressure jaw
type
fixed
contacts
of
electrolytic copper of size
70 mm x 35mm x 6 mm duly
silver plated .Each contact
should be riveted with three
nos. copper rivets with a bunch
( minimum 3 mm thick) of
copper strips /foil each may
vary from 0.15 mm to 0.25 mm
to and total thickness of copper
foil per jaw should be 6 mm .
Jaw assembles are to be bolted
through brass bolts and nuts
with spring washer.
b) Solid rectangular blade type
moving contact of electrolytic
copper of size 35 mm X 6 mm
and length 220 mm duly silver
plated ensuring a minimum
deposit of silver 10 micron on
copper contacts or as may be
prescribed under relevant ISS /
IEC .
c) Pressure springs are to be used
in each jaw contacts should be
phosphorous bronze having
8nos. of turns X28mm heights
X14.4mm diameter with 14
SWG wire .

17

Connectors:-

18

Terminal connectors for both


movable and fixed should be of
copper flat of same size similar to
that of moving contact blades
(minimum
95%
copper
composition). The fixed connector
shall of size 65 mm x 35 mm x 6 mm
and the size of movable connector
shall be size (65 X 35) X (65 X
35) X 6mm with machine finishing
duly silver plated with 2 nos. 12mm
dia holes provided with suitable
brass bolts and double nuts, flat
washers & 2nos. bimetallic solder
less sockets suitable upto 55 mm
conductor.

Moving contact supporting Moving contact is to be supported by


G.I angle of size 45x45x5 mm on each
angle
phase and the moving contact are to be
bolted through 2 nos. stainless steel

bolts and nuts with suitable


stainless steel flat and spring
washers.
19

Galvanization

a) Iron parts shall be ho t dip


galvanized as per IS2633/1972.(Latest Amendment) ,
IS :2629/1985 (1st. Revision),

b) The pipe shall be galvanized as


per IS-4736/1968.(Latest
Amendment)
20
(a)

Phase Coupling Rod

25mm nominal bore G.I. Pipe


(Medium gause)

(b)

Operating Rod

ISI mark 32mm nominal bore G.I. Pipe


(Medium gause) 6 mtr. long
Normal

25 mm
32 mm

Outside Dia. in
mm

Wall
thickness

Max.
34.2
49.9

3.25
3.25

Min.
33.3
42

(c)

Arcing Horn

8 mm dia G.I. rod with spring


assisted operation.

(d)

Force of fixed contact spring

50lbs to 75 lbs

4 nos. self lubricated bearing to


be provided with grease nipple
including 4th bearing being a
axial thrust bearing.

(f)

Bearings

(g)

Locking Arrangement

(h)

Earth terminal

Provided at base channel at opposite


ends.

(i)

Copper braided flexible


tapes

320mm long 2no. tin coated


copper braided flexible tape
both end seated with cupper
sheets duly punched for
fixing having minimum
weight of 450 grams per
meter without sockets.

(j)

Quick break device

(k)

T connector

The T connector provided on


the channel having Moving
Contact shall be of G.I Nut &
Bolt at the bottom end to
facilitate replacement of this unit
only during requirement and
avoid entire change of the arm.

l)

I-Bolt

The I-Bolt shall be longer with


75 mm thread.

21

Supporting Channel

75mmx40mmx 6mm M.S.Channel.


(Hot dip galvanized)

22

Weight of each pole

20 Kg (Approximately) ( to be
specified by bidder)

23

Detailed drawing submitted ?

N.B

Pad Lock and key arrangement


at both ON & OFF position..

Lever mechanism

To be provided by bidders

i) Ferrous parts shall be duly galvanized as per IS :2629/1985 (1st. Revision),


(Amendment-2) and non-ferrous parts shall be silver plated.
st
ii) The G.I pipes and rods shall be galvanized as per IS:4736/1968 (1 . Revision),
(Amendment-1) for hot-dipped zinc coating on M.S. Tube.
iii) Certificate from a Government approved laboratory regarding composition of copper in
electrolytic copper casting of materials should be submitted during inspection of materials at the
cost of tenderer.
iv) Items not covered in the G.T.P, but relevant in Design, manufacturing, quality control
& testing of materials shall be governed by the relevant IS with latest Amendment.

11 KV 200 Amp 3 Pole HG Fuse

Technical Specifications
1.

SCOPE:- This specification covers the manufacture, testing and supply of 11


3 pole 200A H.G. Fuse Sets.

2.

(a) The 11 KV H.G. Fuses shall be suitable for out door operation in
horizontal configuration under the climatic conditions specified. It shall be of
the following ratings:1
2
3
4
5
6
7
8

Number of Poles
No.of Insulator per Pole
Nominal system Voltage
Highest System of Voltage
Rated frequency
System Frequency
Rated normal current
Altitudes of installation

3
2 nos. 12 KV post Insulators
11 KV
12 KV
50 Hz
Effectively earthed
200 Amps
Not exceeding 1000 M.

(b) The post insulator used in the H.G. Fuse set shall have the following ratings :1
2
3
4

3.

Power frequency withstand voltage (dry)


Power frequency withstand voltage (wet)
Impulse withstand voltage (dry)
Power frequency withstand voltage

33 KV (RMS)
35 KV (RMS)
75 KV (Peak)
1.3 times the actual dry
flashover voltage of the
unit

STANDARDS :The H.G. Fuse set shall confirm to the following standards.
IS- 9385-1980 ( for high voltage expulsion fuses and similar fuses).
IS- 2544-1973 ( for porecelain post insulators or its latest amendments if any.). IS2633-1979 ( for Galvanisation of ferrous parts).

4.

INSULATOR MAKE :- 12 KV post insulator complete with pedestal cap


duly cemented to be used in 11 KV H.G. Fuse sets confirming to IS-2544/1973.

5.

TECHNICAL DETAILS :- The H.G. Fuses shall have adjustable arcing


horns made of solid copper rod having 7.62 mm dia. The horns shall be
fitted with screwing devices with flynuts for fixing and tightening the fuse
wire. It shall have robust terminal connectors of size 80 mm x 50 mm x 6 mm
made of copper casting (95 % minimum copper composition) duly silver plated
with two numbers of 12 mm dia brass bolts and double nuts with flat

brass washers. The connectors should be capable of connecting crimpable


conductor upto 80 Sq. mm size( ACSR/ Alloy) with bimetallic solderless
sockets. The H.G Fuse Set shall suitable for horizontal mounting on substation structures. The minimum clearance between the adjacent phases of the
fuse set shall be 760 mm and the centre to centre (distance between two post
insulators of the same phase) shall be 410 mm. All metal (ferrous) parts shall be
galvanized and polished. Only 12 KV post insulator ( orginal cemented and not
pin insulators shall be used for the H.G. Fuse Set.
CLIMATIC CONDITIONS :- The H.G. fuse set shall be suitable for
operation under the following climatic conditions.:-

6.
1
2

Maximum ambient air temperature


Maximum daily average air temperature

3
4

Maximum yearly average ambient air temperature


Maximum temperature attainable by a body
exposed to the sun.
5 Minimum ambient air temperature
6 Maximum relative humidity
7 Average number of thunderstorm days per annum
8 Average number of rainy days per annum
9 Average annual rain fall.
10 Number of months of tropical monsoon conditions
11 Maximum wind pressure
12 Degree of exposure to atmospheric pollution.
7

450 C
350 C
300 C
500 C
00 C
100%
70 days
120
150CM
4
260 Kg/mm
Normally
atmosphere.

polluted

Type Test :Certificate for the following type tests conducted on a prototype set of HG Fuse in a
NABL approved test house/CPRI shall have to be submitted along with offer.
i) Dielectric test (impulse & one minute wet power frequency withstand voltage test.)
ii) Temperature rise test ( for terminals)
iii) Mechanical strength test for the post of insulator as per IS2544/1973 iv) Test for galvanization of metal (ferrous) parts.

8.

ROUTINE/ACEPTANCE TESTS :The inspection may be carried out by the Purchaser at any stage of manufacture.
The successful bidder shall grant free access to the Purchasers
representative at a reasonable time when the work is in progress. The following
routine tests shall have to be conducted on each set and results are to be
furnished for consideration of deputing inspecting officer for inspection and
conduction testing of the materials at the works of the manufacturer. the
supplier shall give fifteen days
advance intimation to
the
Purchaser to enable
him to
depute his representative for
witnessing the tests.

i) Power frequency voltage dry test


ii) Dimension Check
iii) Galvanisation test.
9.

Guaranteed Technical Particulars :


The bidders are required to furnish the guaranteed technical particulars duly filed in
the proforma along with the bid.

10.

Completeness of Equipment :

11.

Any fittings accessories or apparatus which may not have


been
specifically mentioned in this specification but which are usually necessary in
equipment of similar
plant shall be deemed to be included in the
specification and shall be supplied by the
bidder without extra
charge. All plant and equipment shall be complete in all details whether such
details are mentioned in the specification or not.
Inspection :
Routine and acceptance test shall be conducted at the place of manufacturer.
The bidders are requested to furnish details of equipments which will be used
for testing along with the bid. The bids of these manufacturers who do not
have adequate testing facilities for conducting routine and acceptance test are
liable for cancellation. The successful bidder has to furnish routine test certificate
and guarantee certificate for each consignment of materials to be inspected at
the time of offer of materials for inspection.

GUARANTEED TECHNICAL PARTICULARS OF 11 KV 200Amp.

HG Fuse ( 2 / 3 pole)
Sl.
No

1
2
3
4
5

6
7
(a)

Particulars

Makers name & Address


Operating voltage
No. of Post Insulators per
phase
Rated normal current &
normal frequency
Vertical clearance from the top
of insulator to
mounting channel
Height of the riser for carrying
the horn.
Post Insulators :
Makers Name & Country of
Manufacture of Post Insulator

(b)

Type of cementing

(c)

1 minute Power
frequency withstand
1voltage
minute(Dry)
Power
frequency withstand
voltage discharge
(wet)
Visible
voltage
Dry flash over voltage
Power frequency puncture
withstand voltage
Creapage distance

(d)
(e)
(f)
(g)
(h)

8.

(a)
(b)
9.
(a)
(b)

Impulse withstand voltage for


positive & negative polarity
(1.2/50 micro second wave)
Across the isolating distance
To earth & between poles
One minute Power frequency
withstand
Across
thevoltage
Isolating distance
To earth & between poles

Requirement
11 KV 200 Amps.2/ 3 pole H.G
Fuse.
To be specified by the bidder
11 KV
2 nos. of 12 KV Post Insulators per
phase as per ISS:2544/1973
200 Amp., 50 Hz
254 mm (minimum)
150 mm from the cap top of
insulator
To be specified by the bidder ( as per
CPRI Test Report).

Original Cementing only as per IS:


2544/1973 & relevant IEC.
35KV RMS
35KV RMS
9KV RMS
85 KV RMS
1.3 times of actual dry flash over
voltage (110 KV) .
320 mm (minimum). Actual
creepage distance for which type
test has been conducted is to be
supplied.

85KV (Peak)
75KV (Peak)
32KV(RMS)
28KV(RMS)

Bidders offer
2 Pole
3 Pole

10

Details of Arcing Horn

1 SWG (7.62 mm) dia. solid copper rod


silver plated provided with screwing
arrangement on the fuse carrier made of
copper casting for fixing fuse wire (Total
length -635 mm). All the bolts, Nuts and
washers should be made out of Brass.

11

Riser Unit (150 mm height


total)

13.

Galvanization

14

Supporting Channel

a) Riser cum Connector made out of


copper casting (with minimum 95%
copper composition having riser size (80
mm height x30mm width x8 mm
thickness) and connector of size (80
mmx50mmx 8mm) duly silver plated
and machine finishing provided with 2
nios.12 mm dia. brass bolts and double
brass nuts with flat brass washers and 2
nos. solderless bimetallic socket per each
connector suitable upto 80
mmconductor.
b) 100 mm height G.I Riser made of
19 mm nominal bore medium gauge G.I
pipe welded with 2 nos. of G.I flat of
30mmx5mm of both ends fixed with
10mm dia. stainless steel bolts and nuts
with flat & stainless steel spring washer.
a) All ferrous parts shall be hotdipped Galvanized as per
IS.2633/1972 (Latest Amendment) , IS
:2629/1985 (1st. Revision),& all nonferrous parts shouldbe duly electroplated
with silver.
75mmx40mmx6mm M.S.Channel. (Hot
dip galvanized)

15

Weight of each pole

16
N.B

Detailed drawing submitted ? To be provided by bidders


i) Ferrous parts shall be duly galvanized as per IS :2629/1985(1st. Revision),
(Amendment-2) and non-ferrous parts shall be silver plated.
ii) Certificate from a Government approved laboratory(NABL accredited) regarding
composition of copper in electrolytic copper casting of materials should be submitted during
inspection of materials at the cost of Bidder.
iii) Type Test Certificate : The type test certificate , conducted within five years , preceding to
date of opening of the tender from Govt. testing laboratory (NABL accredited / CPRI) shall be
furnished.

16 Kg (Approx.)To be specified by the


Bidder

33KV 3 Pole 200 Amp AB Switch (Horizontal Type)


Type Test: - Certificate for the following type tests conducted (within five years
proceeding to the date of opening of the tender)on a prototype set of A.B. Switch in a
NABL approved test house/CPRI shall have to be submitted along with offer
GUARANTEED TECHNICAL PARTICULARS
Slno.

Description

1
2

Maker's name and Country of origin.


Type of Switches

Suitable for mounting.

Number of support post Insulator per


phase
POST INSULATOR

Specified
Rotating type only.
Horizontal only.
4 Nos. 22 Kv/24 Kv post Insulators per phase
as per IS : 2544/1973.
Reputed make. All the post insulators provided
shall be of same make.
Original Cementing only.

(a)
(b)

Maker's name and Country of origin.


Type of Cementing.

(c)

One minute power frequency withstand


voltage dry.
One minute power frequency withstand
voltage
wet.
Visible Discharge voltage.

95 Kv (rms)

Dry flash over voltage.


Power frequency puncture withstand
voltage.
Impulse withstand voltage (Switch in
position)

95 Kv.
1.3 times of actual dry flash over voltage.

(d)
(e)
(f)
(g)
(h)
(i)

Creepage distance.
6

(a)
(b)
7
(a)
(b)
8
9
10
11
12
13
14
(a)
(b)
15

Impulse withstand voltage for positive &


negative
polarity (1.2/50 micro second wave)
Across the Isolating distance.
To earth and between polles
Rated one minute power frequency
withstand
Voltage.
Across the Isolating distance.
To earth and between polles
Rated normal current and rated
frequency.
Rated short time current.
Rated peak withstand current.
Rated transformer off load breaking
capacity.
Rated line charging breaking capacity.
Rated cable charging breaking capacity.
Minimum clearance between adjacent
phases.
Switch closed (Centre to Centre)
Switch opened (Centre of post Insulator to
the edge
of the blade)
TEMPERATURE RISE.
The temperatyure rise should not exceed
to

75 Kv (rms)
27 Kv (rms)

170 Kv (Peak)
430 mm. However, t he actual creepage d i s t a n c e
f o r which type test has been conducted is to be
supplied.

195 Kv (Peak)
170 Kv (Peak)

80 Kv (rms)
70 Kv (rms)
400 Amps. 50 Hz.
16 KA (rms)
40 KA (Peak)
6.3 A (rms)
6.3 A (rms)
16 A (rms)
1200 mm
640 mm

650C

Bidders
Offer

16

maximum limit as specified below at an


ambient temperature not exceeding
40 0C.
Copper contacts silver faced terminal of
switch
intended to be conducted to external
conductor by bolts or screws at an
ambient temperature should not exceed
Vertical clearance from the top of
Insulator cap to mounting channel

17

Type of Contact

18

Terminal Connector.

19

Moving Contact supporting angle.

20

Galvanisation

21

Details of phase
(a) Coupling Rod.
(b) Operating Rod.

(c ) Arcing Horn.

500C

508 mm. Minimum.


(a) Self-aligned, high pressure jaw type fix contacts
of electrolytic copper of size 80 x 50 x 8 mm duely
silver plated. Each contact should be rivetted with
three nos. copper rivets with a bunch ( minimum
3 mm thick) consisting of copper foils may vary
from 0.15 mm to 0.25 mm ( total thickness of
copper foil per jaw shallbe 6 mm). Jaw assembles
are to be bolted through brass bolts and nuts
with brass flat and spring washer.
(b) Solid rectangular blade type moving contact
of electrolytic copper size 220 mm x 50 mm x 8
mm duly silver plated.
(c ) Pressure springs to be used in Jaw contacts
should be phosphorous bronze having 8 nos. of
turns x 28 mm height x 14.4 mm dia. With 14 SWG
wire (Minimum 6 nos. spring shall be used)
Terminal connector for both movable and fixed
should be of copper casting (minimum 95 %
copper composition). The fixed connector shall be
of size (80 x 50) x 8 mm and the size of the
movable connector (80 x 50) x (80 x 50) x 8mm
with machine finishing duely silver plated with 2
nos. 12mm dia. hole with suitable brass bolts and
double nuts with brass flat washers and 2 nos.
solerless bimettalic 2sockets per each connector
suitable upto 80 mm conductor. The sockets shall
be preferably of "USHA MARTIN" make.
Movable contact is to be supported by G.I Angle of
size 50 x 50 x5mm on each phase and the
moving contact are to be bolted through 2 nos.
stainless flat and spring washers suitably.
(a) Iron parts shall be hot-dipped galvanised
as per IS :2629/1985 (1 st Revision),
(Amendment-2).
(b) The G.I Pipe shall be galvanised as per IS :
4736/1968 (1 st Revision),(Amendment-1)
for
Hot-dipped Zinc Coating on M.S Tubes.
25mm nominal bore G.I Pipe medium gauge.
32mm nominal bore G.I Pipe medium gauge.
Single length 6 mtrs. The detail dimensions of
the G.I Pipe as mentioned below :
Nominal
Outside Diameter
Wall thickness
Max.
Min.
25mm
34.2mm
33.3mm
3.25mm
32mm
42.9mm
42mm
3.25mm
(a) 8mm dia G.I Rod with spring-assisted operation.

(d) Bearing System.


(e) Force of fixed contact spring.

(f) Copper braided flexible tapes.

(g) Quick break Device.


(h) Bearings.
(i) Locking Arrangement.
(j) Earth Terminal.
(k) 'T' Connection.

22
23
N.B

(l)
Supporting Channel.
Weight of each pole complete.

One bearing shall be provided near the


Base Channel to assist in operatio.
50-75 lb.
320mm length of flexible electrolytic copper
tape or braided chordwith tin coated having
minimum weight 450 gms/mtr. And both ends
shall be cripped with copper sockets through brass
bolts and nuts with brass flat washers. Two nos. of
suitable copper sockets shall be used at both
ends. The socket should be preferably of
"DOWEL" make(catalogue
o
CUS/48)
or
equivalent
USHA MARTIN make. The minimum
no. of flexible wires should be 1536 of 36 SWG for
each flexible chord.
Lever Mechanism.
4 nos. self lubricating bearings to be provided
with grease nipple including 4th bearing being a
thrust bearing.
Pad locker and key arrangement at both "ON" and
"OFF" position.
To be provided at base channel.
The 'T' Connection provided on the channel
having 'MovingContact' shall be of G.I Nut &
Bolt at the bottom
end to facilitate
replacement
of this unit only during
requirement & avoid entire change of the arm.
The 'I-Bolt' shall be longer with 75 mm thread.
75 x 40 X6 mm M.S Channel hot-dipped galvanised.
50 Kgs. Approximately.

I) Ferrous parts shall be duly galvanised as per IS:2629/1985 (1 st Revision), (Amendment-2) and nonferrous
II) The G.I Pipes & Rods shall be galvanised as per IS : 4736/1968 (1 st Revision),(Amendment-1) for Hotdipped Zinc Coating on M.S Tubes.
III) Certificate from a Government approved laboratory regarding composition of copper in electrolytic
copper
IV) Items not covered in the G.T.P, but relevant in Design, manufacturing, quality control & testing of
materials shall be governed by the relevant IS with latest Amendments.
V) Type Test report from CPRI or accredited NABL laboratory should be furnished. Same for insulators is to
also to be provided.

TECHNICAL SPECIFICATION OF 33 KV & 11KV 3 Pole, 400


AMP , HORIZONTAL TYPE AB SWITCH

TECHNICAL SPECIFICATIONS FOR AB SWITCH

1.

SCOPE:- This specification covers manufacturing testing and supply of 3 Pole, 400 AMP,
50 Hz, Single break, 33 KV & 11 KV class Air Break switches for outdoor installations to
be used at 33/11 KV Sub-stations and for incoming & outgoing Lines suitable for operation
under off load conditions.

1.1

DESCRIPTION OF THE MATERIALS:-The A.B. Switch sets shall confirm to the following parameters:-

Sl.
No.

Parameters of AB Switch
Description

33 KV

11 KV

i)
ii)

Number of poles
Number of Post insulator per pole

4 nos. 22/24 KV class

3
2 nos. 12 KV class

iii)

Nominal system voltage (KV)

33

11

iv)

Highest System Voltage (KV)

36

12

v)

Rated frequency

50HZ

vI)

System earthing

vII)

Rated nominal current Amp.

400

viii)

Altitude of installation

Not exceeding 1000 M

Effectively earthed.
400

The post insulators used in the A.B. Switches shall have the following ratings
Parameters P.I. of AB Switches for

Sl.
Description

33 KV

11 KV

95
75

35
35

No. Power frequency withstand voltage


i)
ii)

Power
(dry) KVfrequency
(RMS) withstand voltage
(wet) KV (RMS)
Impulse withstand voltage (dry) KV

iii

Power

iv)

(Peak)

frequency

puncture

17 the actual dry flashover voltage


75
1.3 times
of
0

withstand voltage
1.2

the unit

STANDARDS:- The AB Switch Set shall conform to the following standards:-

i)

IS-9920 (Part-I to V.)

ii)

IS-2544/1973 ( for porcelain post insulators)

iii) Is-2633 (for galvanization of ferrous parts.) or its latest amendments if any.

1.3

INSULATORS:12 KV class (for 11 KV AB Switches) and 22 KV / 24 KV class (for 33 KV AB Switches) Post


Insulators complete with pedestal cap duly cemented to be used in the AB Switch Set
conforming to IS-2544/1973
The bidder shall furnish the type test certificate of the post insulators from their
manufacturer for reference.
The bidder shall mention make, type of insulation materials, metal fittings, Creep age
distance, protected Creep age distance, tensile strength, compression strength, torsion
strength and cantilever strength.

1.4

CLIMATIC CONDITIONS:The A.B. Switch set shall be suitable for operation under the following climatic
conditions

1.

Maximum ambient air temperature.

45 C

2.

Maximum daily average air temperature

35 0 C

3.

Maximum yearly average ambient air temperature

30 0 C

4.

Maximum temperature attainable by a body


exposed to the sun.

50 0 C

5.

Minimum ambient air temperature

00 C

6.

Maximum relative humidity.

100%

7.

Minimum number of rainy days per annum

70

8.

Average number of rainy days per annum

120

9.

Average annual rain fall.

150 cm.

10.

Number of months of tropical monsoon conditions

11.

Maximum wind pressure.

260 Kg./ mm

12.

Degree of exposure to atmospheric pollution.

Normally polluted
atmosphere.

1.5

TECHNICAL DETAILS:-

1.5.1

The 33 KV A.B. Switch Set shall be gang operated (with double tandem pipe) single air break
outdoor type horizontal mounting having 4 nos. 22/24 KV post insulator per phase and the 11
KV A.B. Switch Set shall be gang operated single (with double tandem pipe) air break outdoor
type horizontal mounting having 2 nos. 12 KV post insulator per phase. The operating
mechanism shall be suitable for manual operation from the ground level and shall be so
designed that all the three phases shall open or close simultaneously. The Switches shall be
robust in construction, easy in operation and shall be protected against over travel or straining
that might adversely affect any of its parts. The required base M.S. Channel, phase coupling
rod, operating rod with intermediate guide braided with flexible electrolytic copper, tail
piece of required current carrying capacity and operating mechanism with ON & OFF
positions shall be provided. The operating rod shall be medium gauge of 32mm diameter
nominal bore G.I. pipe single piece 6 meters. The phase coupling rod for gang operation shall

medium gauge 25mm dia nominal bore G.I. Pipe. Rotating post insulators shall be provided
with suitable bearing mounted on a base channel with 6 mm thick thrust collar and 6mm split
pin made out of stainless steel. The operating down rod shall be coupled to the spindle
(minimum dia - 32mm) for gang operation through another suitable bearing by two numbers
10mm dia through stainless steel bolts with double nuts. The post insulators should be fixed
with the base channel using Galvanized Nuts and Bolts.
All the bearings shall be provided with grease nipple. All ferrous parts shall be galvanized and
polished. The pipes shall be galvanized in accordance with IS-4736/1968.
1.5.2

Mounting: - The A.B. Switches shall be suitable for horizontal mounting in all type of substation structures.

1.5.3

Switching Blades: - It shall be made out of electrolytic copper with silver plated. The
approximate size shall be 250mm x 50 x 8mm for 11 KV. The switch shall have such a spring
mechanism so as to ensure that the speed of the opening of contact is independent of speed of
manual operation

1.5.4

Fixed Contracts:- The fixed jaw type female contracts (50x8x95 )mm for 11 KV shall be made
of electrolytic copper ( minimum 95 % copper composition) duly electroplated controlled by
Phosphor bronze high pressure spring housed in robust G.I. Cover.
It is essential that provision shall be made in fixed female contracts to take the shock arising
from the closing of moving contract blade without the same being transmitted to the post
insulator. The arrangement made in this regard shall be specifically shown in the drawing.

1.5.5

Arcing Horn:- As the switches are generally meant for isolating transmission line and
distribution transformers, suitable arcing horns shall be provided for breaking the
charging current horn shall be made of 10 mm dia G.I. Rod with spring assisted
operation.

1.5.6

Terminal Connectors:- Terminal connectors shall be robust in design. The size of fixed
connector shall be ( 80 x 50 x8 mm) and size of movable connector shall be of ( 80 x50) x (
80 x 50) x 8 mm of copper casting with uniform machine finishing duly silver plated made
out of minimum

95 %

copper composition with 2 nos. 12 mm dia holes provided

withsuitable brass bolts and double nuts, flat washers & 2 nos. bimetallic solderless sockets
suitable up to ACSR Panther or AAAC 232 mm2 conductor.

1.5.7

Spacing:- The minimum clearance between phase to the switch

shall be 1200 mm. The

operating down rod shall be at a transverse distance of 300 mm from the outer limb of the
switch. The centre spacing between two post insulators of the same phase shall be 560 mm.
In the open position of the A.B. Switches the moving blade shall rotate through anangle of 90 0
. This shall be exhibited in the drawing.
1.5.8

Drawing & Literatures:- Drawings of each item i.e. 11 KV, 400 amp and 33 KV 400 amp, 3
Pole, single break A.B. Switch shall be furnished along with the tender.
The details of construction and materials of different parts of the A.B. Switches shall clearly
be indicated in the tender and illustrative pamphlet / literature for the same shall be
submitted along with the tender.

1.6

TESTS & TEST CERTIFICATE

1.6.1

Type Test:- Certificates for the following type tests conducted within five years
proceeding to the date of opening of tender on prototype set of A.B Switch in a Govt.
Approved Testing Laboratory

preferably at CPRI, Bhopal/ Bangalore shall have to be

submitted for reference and scrutiny.


i.

Impulse voltage dry test

ii.

Power frequency voltage dry test

iii.

Power frequency voltage wet test

iv.

Temperature of resistance.

v.

Measurement of resistance.

vi.
vii.

Test to prove the capability of carrying the rated peak short circuit
current and the rated short time current.
Mainly active load breaking capacity test. viii.
Transformer off-load breaking test.

ix.

Line charging breaking capacity test.

x.

Operation tests.

xi.

Mechanical endurance test.

xii.

Mechanical strength test for the post insulator as per IS-2544/1973.

xiii.

Test for galvanization of metal (ferrous) parts as perm IS-2633/1973.

Besides, mechanical endurance test will have to be conduct on one set in the presence of our
authorized person who shall be deputed to carryout acceptance tests before delivery of the
materials.
1.6.2

1.7

Routine Tests: - The following routine tests shall have to be conducted on each sets and results
are to be furnished for consideration of deputing inspecting officer for inspection and
conducting testing of the materials.
1.

Power frequency voltage dry test

2.

Measurement of resistance of main circuit

3.

Tests to prove satisfactory operation.

4.

Dimension check

5.

Galvanization test.

GUARANTEED TECHNICAL PARTICULARS:The Bidder shall furnish the guaranteed technical particulars duly filled in the format at
Appendix-I along with the tender.

1.8

COMPLETENESS OF EQUIPMENT:Any fittings, accessories for apparatus which may not have been specifically mentioned in this
specification but which are usual or necessary in equipment of similar plant shall be deemed to
be included in the specification and shall be supplied by the Tender without extra charge. All
plant and equipment shall be completed in all details whether such details are mentioned in
the specification or not.

1.9 INSPECTION:-Routine and acceptance tests shall be conducted at the place of manufacturer. The
bidder are requested to furnish details of equipment which will be used for testing along with tender.
The bidder of those manufacturers who do not have adequate testing facilities for conducting routine
and acceptance test are liable for cancellation. The successful bidder has to furnish routine test
certificate and guaranteed certificate for approval prior to offer of materials for inspection for each
consignment of offer.

(To be submitted with offer)


GUARANTEED TECHNICAL PARTICULARS FOR 33KV, 400A, 50 HZ,
3 POLE, SINGLE BREAK TYPE

Sl.
No

Particulars

Desired values

Bidders

Makers name and country


1.
2.

of origin
Type of Switch

To be specified by the tenderer


Rotating type only

3.

Suitable for mounting

4.

Number of supporting post


insulators per phase
Post Insulator.

Horizontal only
4 nos.22 KV / 24 KV Post Insulators per phase
as per ISS-2544/1973.

5.
Makers name and country
a)

To be specified by the tenderer


To be quoted for original cemented only &

of origin

b)

Type of cementing

c)

One minute power frequency


withstand voltage Dry

d)
e)
f)
g)

One minute power frequency


withstand voltage Wet
Visible discharge voltage
Dry Flashover Voltage
Power frequency puncture
with stand voltage
Impulse

h)

i)

as per IS-2544-1973 & relevant IEC.

withstand

95 KV RMS.

75 KV RMS.
27 KV RMS.
To be specified by the tenderer
1.3 times of actual dry flash over voltage

voltage

(switch in position)

Creepage distance (mm)

170 KV (peak)
380 mm minimum. (actual creepage
distance for which type test have been
conducted is to be specified by the tenderer

offer
4

6.

Impulse withstand voltage


for positive and negative
polarity 1.2 / 50 mircrosecond wave

a)

Across the isolating distance

195 KV (peak)

b)

To earth & between poles

170 KV (peak)

7.

One minute power frequency


withstand voltage

a)

Across the isolating distance

80 KV (RMS)

b)

To earth & between poles

70 KV (RMS)

8.

Rated normal current


rated frequency

9.

Rated short time current.

16 KA ( RMS )

10.

Rated short circuit making


capacity

25 KA (RMS)

11.

Rated peak withstand current

40 KA ( Peak )

and
400 amps. 50 Hz

15.

Rated
cable
charging
breaking capacity
Rated Transformer off load
breaking capacity
Rated line charging breaking
capacity
Minimum clearance between
adjacent phases

a)

Switch Closed ( centre to


centre)

1200 mm

b)

Switch Opened ( centre to


edge of blade)

640 mm

16.

Temperature rise

12.
13.
14.

40 KA ( RMS )
16 Amp (RMS)
5.3 Amps ( RMS)

Temperature rise shall not


exceed the maximum limit as
specified
below
at an
ambient temperature not
exceeding in 40 0 C
a)
b)

c)

17.

18.

Copper contacts in air


Terminal of switch intended to
be connected to external
conductor by bolts
Vertical Clearance from top of
insulator cap to mounting
channel

Type of Contact: -

65 0 C

50 0 C

508 mm (minimum)
a) Self aligned, high pressure jaw type fixed
contacts of electrolytic copper of size 80
mm x 50 mm x 8 mm duly silver plated. Each
contact should be revetted with three nos.
Copper rivets with a bunch (minimum
3 mm thick) consisting of copper foils, each
may vary from 0.15 mm to 0.25 mm. These
total thickness of copper foils per jaw
should be 6 mm. Jaw assemblies are to be
bolted through stainless steel bolts and nuts
b)
rectangular
blade
moving
withSolid
stainless
steel flat and
spring type
washer.
contact of electrolytic copper size 250 mm x
50 mm x 8 mm duly silver plated ensuring a
minimum deposit of 10 micron of silver on
copper contacts or as may be prescribed
under
relevant
ISS /to
IEC.be used in jaw contacts
c)
Pressure
spring
shall be Stainless Steel having 8 nos of turn x
28 mm height x 14.4 mm diameter with
14 SWG wire (minimum six nos springs shall
be used)

Terminal connectors for both movable and


fixed should be of copper flats of same size
similar to that of moving contact blades
(minimum 95% copper composition). The
fixed connector shall of size 80 mm x 50 x 8 mm
and the size of movable connector shall be size
80 x 50 x 8 mm with machine finishing
duly silver plated with 2 nos. of
3/8 stainless steel bolts, nuts, plain washers

19.

Connectors:-

20.

Moving Contacts:-

21.

Galvanization

& spring washers should be provided along


with 2 nos solder less bimetallic sockets for
each connector suitable sockets for each
connector suitable up to
Movable
contact
is to be supported by
232 mm AAA
conductor.
galvanized angle of 50 x 50 x 5 mm in each
phase and the moving contact are to be
bolted through 2 no stainless steel bolts and
nuts with suitable stainless steel flat and
spring washers.
a) Iron parts shall be dip galvanized as per
IS-2633/1972.
b) b) The pipe shall be galvanized as per IS4736/1968.

22.
a)

b)

c)

Details of Phase
Coupling Rod

Operating Rod

Arcing Horns

25 mm nominal bore G.I. pipe medium


gauge.
32 mm nominal bore G.I. pipe medium
gauge single length 6 mtrs. The detailed
dimension of the G. I. pipe as per IS-1239 (Pt.
I) as mentioned below :Outside
Nominal
Diameter
diameter
base (mm)
thickness (mm)
Max
Min
(mm)
25

34.2

33.3

3.25

32

42.9

42

3.25

10 mm dia G.I. rod with spring assisted


operation.

d)

Force of Fixed contact spring

e)

Copper
tapes:-

f)

Quick break device

g)

Bearings

braided

flexible

To be specified by the tenderer.


450 mm length of flexible electrolytic
copper tape or braided chord (with tin
coated) having minimum weight 450 gms per
meter and both ends shall be crimped with
copper sockets through brass bolts and nuts
with brass flat washers. Two nos of suitable
copper sockets shall be used at both ends. The
minimum no. of flexible wires should be 1536
of 36 SWG for each flexible chord.
Lever mechanism.
4 nos. self lubricated bearing to be provided
with grease nipple including 4th bearing
being a thrust bearing.
Pad Lock & Key arrangement at both ON

h)

Locking arrangement

i)

Earth Terminal:

23.

Supporting Channels

24.

Weight
of
complete

each

& OFF position.


To be provided at base channels.
100 mm x 50 mm M.S. Channel hot dip
galvanized.
pole
To be specified by the tender

GUARANTED TECHNICAL PERTICULARS OF 11KV 400AMP 3 POLE AB SWITCH

Slno.

Perticulars

Requirement
List of relevant standards :IS
1818,9921,2544,1394,4691,325,
4722, 2629, 4759, 2633,1573,3033,
2016, 3961, 5561, 1554, 5578,
11353,9920

Makers

name

& Address

Bidders Offer

To be specified by the bidder


2

Type of Switch

Rotating Type

Suitable for mounting

Horizontal only

No. of Breakers per phase


Single Break

No. of Post Insulators per phase

2nos. of 12KV Post Insulators as per


IS:2544/73 per phase

6
(a)

Post Insulators
Makers
Name
Manufacture

& Country of

of Post Insulator
(b)

Type of cementing

(c)

Power
frequency withstand
voltage (Dry)

(d)

One

minute
Power frequency
withstand

Techno Ceramic / Allied Ceramic


/JSI/equivalent Type Test certificates to
be provided along with the offer.
Original Cementing. The insulator to be
cemented with MCI (Hot dip galvanised
/Al Alloy cap and MCI/Forged steel hot
deep galvanized pedestral)

65KV RMS

40KV RMS

voltage (wet)
(e)

Visible

discharge voltage
9KV RMS

(f)

Dry flash over voltage

(g)

Power

frequency puncture
withstand

70 KV

110KV

voltage
(h)

Creapage distance

(7)

Impulse withstand voltage for positive


& negative polarity (1.2/50
micro second wave)

320 mm

(a)

Across

the

isolating distance
85KV Peak

(b)

To earth & between poles


75KV Peak

Rated

one

Power
voltage
(a)

Across

minute
frequency withstand

the

Isolating distance
32KV(RMS)

(b)

To earth & between poles


28KV(RMS)

9(a)

(b)

10

11

Rated
voltage
nominal/maximum
Rated normal current and rated
frequency
Rated
capacity

11/12KV

400 Amps. 50hz

short-circuit making
20KA (Peak)

Rated

Short-time current
16KA

12

Rated peak withstand current


40KA

13

14

15

Rated mainly active load


breaking capacity

10KA

Rated transformer off load breaking


capacity

16.3A

Rated

line

charging capacity
2.5A(RMS)

16

Rated cable charging capacity


10A(RMS)

17

Minimum

clearance between

adjacent
phase
(a)

Switch closed (center to center)


Mm

(b)

Switch opened (Center of post


insulator to the

Mm

edge of the blade)


18

Temperature rise The


Temperature rise should not exceed
the
maximum limit to 65oC
at an ambient
exceeding 40oC

temperature

The Temperature rise of contacts &


not

terminals are within permissible limit of


650C & 50oC respectively.

19

Vertical clearance from

Mm

top of insulator cap to mounting


channel
20

Type of connect

a) Self aligned high pressure law


type fixed contacts of hard drawn
copper of size 50X8X70 mm
contact is riveted with three nos.
copper rivets with a bunch of
copper strips suitable to give
desired spring action.
b) Solid rectangular blade type
moving contact of size 50X8 mm
and length 220 mm duly silver
plated.
c) Stainless Steel 4 NOS of
Pressure springs are to be used in
each jaw contacts having 8nos. of

turns X28mm heights


X14.4mm diameter with 14 SWG
wire
21(a)

Terminal

connector

(fixed)

Copper flat of size 50X8 mm and length


95mm duly silver plated with 1
no. long 1/2 dia G.I. Nut Bolt &
Spring washers suitable for 10Sq.mm
conductor.

(b)

Terminal

connector

(Movable)

Copper flat of size 50X8mm and length


100mm duly silver plated with
1no long dia G.I. Nut Bolt & Spring
washers suitable to accommodate
bimetallic socket up to 100 sq mm.
conductor.

22

Terminal supporting flat

Movable terminal contact is


supported by G.I. flat of size 50 X
8mm X 370mm on each phase.

23
(a)

Phase Coupling Rod

ISI mark 25mm nominal bore G.I.


Pipe (Medium) conforming to
IS:1239/Part

(b)

Operating Rod

ISI mark 32mm nominal bore G.I.


Pipe (Medium) conforming to
IS:1239/Part

(c)

Arcing Horn

(d)

Force of fixed contact spring

10mm dia G.I. Rod


30 lbs to 50 lbs

(e)

Copper braided flexible taps

320mm long 2no. tin coated copper


braided flexible tape both end seated
with cupper sheets duly punched for
fixing

(f)

Quick break device

Lever mechanism

26

Fastners

All fastners (nut & bolds) should be


hot-dip galvanished & should be
provided with spring and plane
washers.

27

Material & Dimension of


Coupling Pipe

28

Material & Dimension of


Operating Rod

29

Sockets (Lugs)

Shall be tinned cupper sholder less


crimping type confirming to IS : 8309
& 8394 suitable for aluminium
conductor. The cable lugs shall suit
the type of terminals provided. The
cable lug shall be of Dowel make.

30

Detailed drawing submitted ?


Yes

TECHNICAL SPECIFICATION FOR 33KV, 400 AMP , 3 POLE HG FUSES


SCOPE:This specification covers the design manufacture, shop testing, loading, transportation and
delivery at sub-station site of 33KV, 400Amp, 3Pole & 11KV, 400Amp, 3Pole H.G. Fuse Sets for outdoor
installations to be used at 33/11KV Sub-stations suitable for operation under off load conditions.

The 33KV. 400Amps, 3 Pole H.G Fuse Sets shall confirm to the following parameters:i)

Number of Poles:-

ii) No. of insulator per pole:-

4nos. 22/24KV Post Insulator/ Phase

iii) Nominal system voltage

33 KV

iv) Highest system voltage:-

36KV

v) Rated frequency:-

50 Hz

vi) System earthing:-

Effectively earthed

vii) Rated normal current

400 Amps

viii) Altitude of installation

Not exceeding 1000 M.

The post insulator used in the H.G. Fuse set shall have the following ratings:i) Power frequency withstand voltage (dry)
ii) Power frequency withstand voltage ( wet)

95KV (RMS)
75 KV (RMS)

iii) Impulse withstand voltage (dry)

170 KV (Peak)

iv) Power frequency puncture withstand voltage 1.3 times the actual dry flashover voltage of the
unit.
STANDARDS:- The H.G. Fuse Set shall conform to the following standards:i)

IS- 5792- 1973 (For high voltage expulsion fuses & similar fuses)

ii) IS-2544-1973 ( for porcelain post insulators)

iii) IS-9385-1979 or its latest amendments if any.

iv) IS-2633-1979 ( For Galvanization of ferrous parts )

INSULATORS:The 22KV/ 24KV post insulators complete with pedestal cap duly cemented to be used in
the H.G. Fuse sets confirming to IS-2544/1973.
The bidder shall mention make, type of insulation materials, metal fittings, Creepage
distance, protected Creepage distance, tensile strength compression strength, torsion
strength and cantilever strength.
The bidder shall furnish the type test certificate of the post insulators from their
manufacturer for reference & scrutiny.

TECHNICAL DETAILS:The H.G. Fuses shall have adjustable arcing horns made of solid copper rod having
8.23 mm dia. The horns shall be fitted with screwing devices with flynuts for fixing and tightening
the fuse wire. It shall have robust terminal connector 5s of size 80mm x50 mm x 8 mm made of
copper casting ( 95% minimum copper composition) duly silver plated with two numbers of 12mm dia
brass bolts and double nuts with flat brass washers. The connector should be capable of connecting
crimp able conductor up to 232 Sq.mm. size (ACSR/ AAAC) with bimetallic solder less sockets .The H.G.
Fuse Set shall suitable for horizontal mounting on sub-station structures. The minimum clearance
between the adjacent phases of the fuse set shall be 1200 mm and the centre to centre (distance
between two post insulators of the same phase) shall be 760 mm. All metal (ferrous) parts shall be
galvanized and polished. Only post insulator (original cemented and not pin insulators shall be used
for the H.G. Fuse Set.
DRAWIING & LITERATURES:Three copies of drawings of 33KV, 400Amp, 3 Pole H.G. Fuse shall be
furnished along with the tender for reference. The details of construction and materials of different parts
of the H.G Fuse shall clearly be indicated in the tender and illustrative pamplet/ literature for the same
shall be submitted along with the tender.
TESTS & TEST CERTIFICATE: Type Test:-Certificates for the following type tests conducted within
five years proceeding to the date of opening of tender on a prototype set of H.G. Fuse in a
Govt. Approved Testing Laboratory preferably at CPRI Bangalore shall be submitted along
with the tender.
i)

Impulse voltage dry test

ii)

Power frequency voltage dry test

iii)

Power frequency voltage wet test

iv)

Temperate of resistance.

v)

Test to prove the capability of carrying the rated peak short circuit current and the rated
short time current.

vi)

Mainly active load braking capacity test.

vii)

Transformer off-load breaking test.

viii)

Line charging breaking capacity test.

ix)

Operation tests.

x)

Mechanical endurance test.

xi)

Mechanical strength test for the post insulator as per IS:2544/1973, 5350 (PtII)/1970 & relevant IEC.

xii)

Test for galvanization of metal (ferrous) parts as per IS- 2633/1973.

Besides above, mechanical endurance test will have to be conducted on one set in the
presence of our authorized person who shall be deputed to carryout acceptance test before
delivery of the materials.
Routine Tests:The following routine tests shall have to be conducted on each sets and results are to be
furnished for consideration for acceptance of deputing inspecting Officer for inspection &
conducting testing of the materials
.i) Power frequency voltage dry test.
ii) Tests to prove satisfactory operation.
iii) Dimension check.
iv)Galvanisation test.
GUARANTEED TECHNICAL PARTICULARS: The bidders are required to furnish the guaranteed
technical particulars at Schedules attached to this specification duly filled in along with the
tender.
COMPLETENESS OF EQUIPMENT:Any fittings accessories or apparatus which may not have been specifically mentioned in this
specification but which are usually necessary in equipment of similar plant shall be deemed to
be included in the specification and shall be supplied by the bidder without extra charge. All
plant and equipment shall be complete in all details whether such details are mentioned in the
specification or not.
INSPECTION AND TESTING:The Purchaser shall have free entry at all times, while work on the contract is being
performed, to all parts of the manufacturers works which concern the processing of the
equipment ordered. The manufacturer shall afford the Purchaser without charge, all
reasonable facilities to assure that the equipment being furnished is in accordance with this
specification.
The equipment shall successfully pass all the type tests and routine tests referred to and those
listed in the most recent edition of the standards given in this specification.
The Purchaser reserves the right to reject an item of equipment if the test results do not
comply with the values specified or with the data given in the technical data schedule.
Type tests shall have been / shall be carried out at CPRI / National Govt. approved
Laboratory and be witnessed by a representative of such laboratory or some other
representative acceptable to the Purchaser. Routine tests shall be carried out by the

Supplier at no extra charge at their works.


Adequate facility with calibrated testing equipment must be provided by the
manufacturer free of cost to carry out the tests. Type test certificates must be furnished along
with the tender for reference of the Purchaser.
All costs in connection with the testing, including any necessary re-testing, shall be borne by the
Supplier who shall provide the Purchaser with all the test facilities which the latter may require,
free of charge. The Purchaser shall have the right to select the samples for test and shall also
have the right to assure that the testing apparatus is duly calibrated and correct. Measuring
apparatus for routine tests shall be calibrated at the expense of the Supplier at an approved
laboratory and shall be approved by the Purchaser.
The Supplier shall be responsible for the proper testing of the plant or materials supplied by
sub-suppliers to the same extent as if the work, plant or materials were completed or supplied
by the Supplier.
Any cost, incurred by the Purchaser in connection with inspection and re-testing as a result
of failure of the equipment under test or damage during transport or offloading shall be to the
account of the Supplier.
The supplier shall submit to the Purchaser five signed copies of the test certificates, giving
the results of the tests as required. No materials shall be dispatched until the test certificates
have been received by the Purchaser and the Supplier has been informed that they are
acceptable.
The test certificates must show the actual values obtained from the tests, in the units used in this
specification, and not merely confirm that the requirements have been met.
In the case of components for which specific type tests or routine tests are not given in this
specification, The Supplier shall include a list of the tests normally required for these
components. All materials used in the Contract shall withstand and shall be certified
have satisfactorily passed such tests.

to

The Purchaser at his discretion may re-confirm the Test Results in his own laboratory or
laboratory of his choice.

No inspection or lack of inspection or passing by the Purchasers Representative of


equipment or materials whether supplied by the Supplier or sub-supplier, shall relieve the
Supplier from his liability to complete the contract works in accordance with the contract or
exonerate him from any of his guarantees.

GURANTEED TECHNICAL PARTICULARS FOR 400 AMP, 3 POLE, H.G. FUSES.


Bidders
Sl.
No.

Particulars

Maker's name and


country or origin
Suitable for mounting

4
(a)

Maker's name and


country or origin

(b)

Type of cementing

(d)

One minute power


frequency withstand
voltage dry
One minute power
frequency withstand
voltage wet.
discharge

(e)

Visible
voltage
Dry

Flashover

(f)

33 KV
3

Horizontal only.
Number of supporting
post
insulator per phase
Post Insulator

(c )

Offer

To be specified by the bidder.

Desired Values for

4 nos. 22KV/24KV Post Insulator per phase as per ISS 2544/ 1973

To be specified by the bidder


To be quoted original cemented only.

95KV RMS

75 KV RMS.
27KV RMS

(g)

Voltage
Power
frequency
puncture withstand
voltage

(h)

Impulse
withstand
voltage (switch in
position)

To be specified by the bidder

1.3 times of actual dry flash over voltage.

170KV (peak)

380mm minimum. (actual creepage distance


which type test have been conducted
is
be specified by the bidder)
(I )

Creepage distance

(a)

Impulse
withstand
voltage for positive
and
negative
polarity
(1.2/50
micro second wave)
Across the isolating
distance

195 KV (peak)

(b)

To earth & between


poles

170 KV (peak)

One minute power


frequency withstand
voltage

(a)

Across the isolating


distance

100 KV (RMS)

(b)

To earth & between


poles

75 KV (RMS)

Rated
normal
current and rated
frequency.

Operating Voltage

Vertical
clearance
from top of insulator
cap to mounting
Channel
Height of the riser
for
carrying
the
horns.

10

400 amps, 50 Hz , 3 Pole


33 KV

508 mm (minimum)
250mm

from

(top) of insulator.

the

cap

for
to

Copper rod having 8.32 mm dia Silver-plated provided


with screwing arrangement for fixing use wire made of
copper casting. (Total length 995mm). All the bolts, nuts
and washers should be made out of brass.

Details of Arcing
11

Horns
(a)
The
shape
of connectors may be made of
straight copper Flat of size adequate enough to carry a
current density not ess than 1.5 Amp/ mm .
2 Nos of 3/8 G.I. Bolts, double nuts, plain and spring
washers and 2 nos. solder less bimetallic shockets per each
connector suitable up to 232mm AAA conductor.

Riser Unit
12

13

14

15

(250mm total height).


(b) 170mm height G.I. Risermade of 25mm nominal
bore medium gauge G.I. Pipe welded with 2 nos. G.I.
Flat of 35 x 5 mm at both ends fixed with 10mm dia
stainless steel, bolts and nuts with flat stainless steel
spring washers.

Supporting

100 x 50 x 6 mm M.S. Channel (galvanized)

Channels

All ferrous parts should be galvanized as per IS2633/1972 & all non-ferrous part should be duly
galvanized..

Galvanisation
Weight of each pole
(complete)

To be specified by the tenderer.

33KV 3-Pole 200 Amp H.G Fuse


Technical Specification
1.

SCOPE: - This specification covers the manufacture, testing and supply


of 33 KV 200 Amps 3 pole, H.G. Fuse Sets.

2.

(a) T h e 33 KV H.G. Fuses shall be suitable for out door operation in horizontal
configuration under the climatic conditions specified. It shall be of the following
ratings:1
2

Number of Poles
No.of Insulator per Pole

3
4 nos. 22 KV /24 KVpost Insulators per phase

3
4
5
6
7
8

Nominal system Voltage


Highest System of Voltage
Rated frequency
System Frequency
Rated normal current
Altitudes of installation

33 KV
36 KV
50 Hz
Effectively earthed
200 Amps
Not exceeding 1000 M.

(b) The post insulator used in the H.G. Fuse set shall have the following ratings :1
2
3
4

Power frequency withstand voltage (dry)


Power frequency withstand voltage (wet)
Impulse withstand voltage (dry)
Power frequency withstand voltage

95 KV (RMS)
75 KV (RMS)
170 KV (Peak)
1.3 times the actual dry flashover
voltage of the unit

3.

STANDARDS :The H.G. Fuse set shall confirm to the following standards.
IS- 9385-1980 ( for high voltage expulsion fuses and similar fuses).
IS- 2544-1973 ( for porecelain post insulators or its latest amendments if any.). IS- 26331979 ( for Galvanisation of ferrous parts).

4.

INSULATOR MAKE :- 22/24 KV post insulator complete with pedestal cap duly
cemented to be used in 33 KV H.G. Fuse sets confirming to IS-2544/1973.

5.

TECHNICAL DETAILS :- The H.G. Fuses shall have adjustable arcing horns made
of solid copper rod having 8.23 mm dia. The horns shall be fitted with screwing
devices with fly nuts for fixing and tightening the fuse wire. It shall have robust terminal
connector of size 80 mm x 50 mm x 8 mm made of copper casting ( 95 % minimum
copper composition) duly silver plated with two numbers of 12 mm dia brass bolts
and double nuts with flat brass washers. The connectors should be capable of

connecting crimpable conductor upto 80 Sq. mm size( ACSR/ Alloy) with bimetallic
solderless sockets. The H.G Fuse Set shall suitable for horizontal mounting on sub
station structures. The minimum clearance between the adjacent phases of the fuse set
shall be 1200 mm and the centre to centre (distance between two post insulators of the
same phase) shall be 760 mm. All metal (ferrous) parts shall be galvanized and polished.
Only post insulator ( orginal cemented and not pin insulators shall be used for the H.G.
Fuse Set.
6.

CLIMATIC CONDITIONS :- The H.G. fuse set shall be suitable for operation
under the following climatic conditions.:1
2

Maximum ambient air temperature


Maximum daily average air temperature

450 C
350 C

3
4

Maximum yearly average ambient air temperature


Maximum temperature
attainable by a body
exposed to the sun.
Minimum ambient air temperature
Maximum relative humidity
Average number of thunderstorm days per annum
Average number of rainy days per annum
Average annual rain fall.
Number of months of tropical monsoon conditions
Maximum wind pressure
Degree of exposure to atmospheric pollution.

300 C
500 C

5
6
7
8
9
10
11
12

00 C
100%
70 days
120
50 cm
4
260 Kg/mm
Normally
atmosphere.

polluted

Type Test :-

Certificate for the following type tests conducted (within five years proceeding to
the date of opening of the tender) on a prototype set of H.G. Switch in a NABL
approved test house/CPRI shall have to be submitted along with offer.
i)
ii)
iii)
iv)
8.

Dielectric test (impulse & one minute wet power frequency withstand voltage test.)
Temperature rise test ( for terminals)
Mechanical strength test for the post of insulator as per IS-2544/1973
Test for galvanization of metal (ferrous) parts.

ROUTINE/ACEPTANCE TESTS :The inspection may be carried out by the Purchaser at any stage of manufacture. The
successful bidder shall grant free access to the Purchasers representative at a
reasonable time when the work is in progress. The following routine tests shall have to
be conducted on each set and results are to be furnished for consideration of
deputing inspecting officer for inspection and conduction testing of the materials at the
works of the manufacturer. the supplier shall give fifteen days advance intimation to
the Purchaser to enable him to depute his representative for witnessing the tests.
i) Power frequency voltage dry test
ii) Dimension Check
iii) Galvanization test.

9.

Guaranteed Technical Particulars :


The bidders are required to furnish the guaranteed technical particulars duly filed in the
proforma along with the bid.

10.

Completeness of Equipment :
Any fittings accessories or apparatus which may not have been specifically mentioned in
this specification but which are usually necessary in equipment of similar plant shall be
deemed to be included in the specification and shall be supplied by the bidder without extra
charge. All plant and equipment shall be complete in all details whether such details are
mentioned in the specification or not.

11.

Inspection :
Routine and acceptance test shall be conducted at the place of manufacturer. The bidders are
requested to furnish details of equipments which will be used for testing along with the bid.
The bids of these manufacturers who do not have adequate testing facilities for conducting
routine and acceptance test are liable for cancellation. The successful bidder has to furnish
routine test certificate and guarantee certificate for each consignment of materials to be
inspected at the time of offer of materials for inspection.

GUARANTEED TECHNICAL PARTICULARS of 33 KV 200 Amp

3 Pole HG Fuse
Sl.
No

1
2
3
4
5

6
7
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)

8.

(a)
(b)
9.
(a)

Particulars

Makers name & Address


Operating voltage
No. of Post Insulators per
phase
Rated normal current &
normal frequency
Vertical clearance from the top
of insulator to mounting
channel
Height of the riser for carrying
the horn.
Post Insulators :
Makers Name & Country of
Manufacture of Post Insulator
Type of cementing
1 minute Power frequency
withstand voltage (Dry)
1 minute Power frequency
withstand voltage (wet)
Visible discharge voltage
Dry flash over voltage
Power frequency puncture
withstand voltage
Creapage distance

Impulse withstand voltage for


positive & negative polarity
(1.2/50 micro second wave)
Across the isolating distance
To earth & between poles
One minute Power frequency
withstand voltage
Across the Isolating distance

Requirement
33 KV ,200 Amps.3 pole H.G
Fuse
To be specified by the bidder
33 KV
4nos. of 22KV/24 KV Post
Insulators per phase
200 Amp., 50 Hz
508 mm (minimum)
250 mm from the cap top of
insulator
Reputed make . All the post
insulators provided shall be of
same make.
Original Cementing only.
95KV RMS
75KV RMS
27KV RMS
95 KV
1.3 times of actual dry flash over
voltage.
430 mm(minimum). Actual
creepage distance for which type
test has been conducted is to be
supplied.

195KV (Peak)
170KV (Peak)

100KV(RMS)

Bidders offer

(b)
10
11

To earth & between poles


1.2/50 microsecond wave
impulse flash over voltage
Details of Arcing Horn

12

Riser Unit (250 mm height


total)

13.

Galvanization

75KV(RMS)
To be specified by the bidder
1 SWG (8.23 mm) copper rod silver
plated provided with screwing
arrangement on the fuse carrier made
of copper casting for fixing fuse wire
(Total length -995 mm). All the
bolts, Nuts and washers should be
made out of Brass.
a) Riser cum Connector made out of
copper casting (with minimum 95%
copper composition having riser size
(80 mmx50mmx8 mm) and
connector of size (80 mmx50mmx8
mm) duly silver plated and machine
finishing provided with 2 nios.12
mm dia. brass bolts and double brass
nuts with flat brass washers and 2
nos. solderless bimetallic socket per
each connector suitable upto 80 mm
conductor. The sockets shall be
preferably of Usha Martin make.
b) 170 mm height G.I Riser made of
25 mm nominal bore medium gauge
G.I pipe welded with 2 nos. of G.I flat
of 35mmx5mm of both ends fixed
with 10mm dia. stainless steel bolts
and nuts with flat & stainless steel
spring washer.
a) All ferrous parts shall be hotdipped Galvanized as per
IS.2629/1985 (Latest Amendment)
b)The pipe shall be galvanized as per
IS-4736/1968(Latest Amendment)

14

Supporting Channel

15
16

Weight of each pole

N.B

Detailed drawing submitted ?

100mmx50mm M.S.Channel. (Hot


dip galvanized)
50 Kg (Approximately)

To be provided by bidders
i) Ferrous parts shall be duely galvanized as per IS :2629/1985(1st. Revision),
(Amendment-2) and non-ferrous parts shall be silver plated.
ii) Certificate from a Government approved laboratory regarding composition of copper in
electrolytic copper casting of materials should be submitted during inspection of materials
at the cost of tenderer.

iii) Items not covered in the G.T.P, but relevant in Design, manufacturing, quality control
& testing of materials shall be governed by the relevant IS with latest Amendment.

11KV 2/3 Pole D.O. Fuse 200Amp


01) SCOPE:
This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in
50Hz, 11KV distribution system for protection of H. T. lines and transformer centers, Tap lines. The 11KV D.O.
fuses offered shall be complete with all components necessary for its effective and trouble free operation.
02) APPLICATION:
The distributions fuse Drop outs are intended for use on distribution transformers and have no inherent load break
capacity.
03) APPLICABLE STANDARD:
Unless otherwise modified in this specification, the Drop out fuse shall conform to IS: 9385 (Part-I to III) as
amended from time to time.
04) RATED VOLTAGE:
The rated voltage shall be 12 KV.
05) RATED CURRENT:
The rated current shall be 200 A.
06) RATED LIGHTING IMPULSE WITH STAND VOLTAGE VALUES FOR THE FUSE BASE:
The rated lightning impulse withstands voltage both for positive and negative polarities shall be as given below.
a) To earth and between pole: 75 KV (Peak)
b) Across the isolating distance: 85KV (Peak) of fuse base.
07) RATD ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE (DRY AND WET)
VALUES FOR THE FUSE BASE:
a) To earth and between poles: 28KV (rms)
b) Across the isolating distance: 35KV (rms)
08) TEMPERATURE RISE LIMIT (IN AIR) :
a) Copper contacts silver faced: 65C
b) Terminals: 50C
c) Metal parts acting: The temperature shall not reach as springs such a value that elasticity of the Metal is
changed.
09) BREAKING CAPACITY:
The breaking capacity of D.O. Fuse element shall be 8 KA (asymmetrical).

10) GENERAL REQUIREMENTS/CONSTRUCTIONAL DETAILS:


10.1 The D.O. Fuse shall be of single vent type (downward) having a front connected fuse carrier suitable
for angle mounting.
10.2 All ferrous parts shall be hot dip galvanized in accordance with the latest version of IS: 2633.
Nuts and bolts shall conform to IS:1364. Spring washers shall be electro-galvanized.
11) FUSE BASE TOP ASSEMBLY:
11.1 The top current carrying parts shall be made of a highly conductive copper alloy and the contact
portion shall be silver plated for corrosion resistance and efficient current flow. The contact shall
have a socket cavity for latching and holding firmly the fuse carrier until the fault interruption is
completed within the fuse.
11.2 The top contact shall be actuated by a strong steel spring which keeps it under sufficient pressure
to maintain a firm contact with the fuse carrier during all operating conditions. The spring
shall also provide flexibility and absorbs most of the stresses when the fuse carrier is pushed
into the closing position.
11.3 The current carrying parts of the assembly shall be protected from water and dust formation by
a stainless steel top cover.
11.4

11.5

11.6

The top contact assembly shall have a robust galvanized steel hook to align and guide the fuse
carrier in to the socket latch even when the fuse carrier is closed at an off centre angle.
The top assembly shall have an aluminum alloy terminal connector
(refer clause 19).
The top assembly shall be robust enough to absorb bulk of the forces during the
closing and opening operations and shall not over stress the spring
contact.
prohibit accidental opening of the fuse carrier due to vibrations or impact.

fuse carrier
It shall also

12) FUSE BASE BOTTOM ASSEMBLY:


12.1

The conducting parts shall be made of high strength highly conductive copper alloy and the contact
portion shall be silver plated for corrosion resistance and shall provide a low resistance current
path from the bottom fuse carrier contacts to the bottom terminal connector.

12.2 The bottom assembly shall have hinge contacts made from highly conductive, anti-corrosive copper
alloy and shall accommodate and make a firm contact with the fuse carrier bottom assembly. The
fuse carrier shall be placed easily in or lifted from the hinges without any man handling. In
addition, the bottom assembly shall perform the following functions.
i)

When opened manually or after fault interruption the fuse carrier shall swing through 180 to the vertical
and its further travel shall be prevented by the fuse base bottom assembly
ii) The fuse carrier shall be prevented from slipping out of the self locking hinges during all operating
conditions and only when the fuse carrier has reached its fully open position then only if can be
removed from the hinge support.
12.3 The assembly shall have an aluminum alloy terminal connector (refer clause 19).

13) FUSE CARRIER TOP ASSEMBLY:


13.1 The fuse carrier top contact shall have a solid replaceable cap made from highly conductive, anticorrosive copper ally and the contact portion shall be silver plated to provide a low resistance
current path from the fuse base top contact to the fuse link. It shall make a firm contact with
the button head of the fuse link and shall provide a protective enclosure to the fuse link to
check spreading of arc during fault interruptions.
13.2 The fuse carrier shall be provided with a cast bronze opening eye (pull ring) suitable for operation
with a hook stick from the ground level to pull-out or close-in the fuse carrier by manual
operation.
14) FUSE CARRIER BOTTOM ASSEMBLY:
14.1 The fuse carrier bottom assembly shall be made of bronze castings with silver plating at the
contact points to efficiently transfer current to fuse base. It shall make smooth contact with
the fuse base bottom assembly during closing operation.
14.2 The bottom assembly shall have a lifting eye for the hook stick for removing or replacing the fuse
carrier.
14.3 The bottom assembly shall have a suitable ejector which shall perform the following functions.
i)
It shall keep the fuse link in the centre of fuse tube and keep it tensioned under all operating
conditions.
ii)

iii)

iv)

It shall be capable of absorbing the shock when the fuse carrier is pushed Into the closed
position and shall not allow the fuse link to be damaged. This is specially important when the
fuse link is of low ampere rating.
The ejector at the instant of interruption shall retain the fuse carrier in the closed
position ling enough to ensure that the arc is extinguished within the fuse tube thereby
excluding the possibility of arcing and subsequent damage at the contact surfaces.
The ejector shall help the fuse link separation after fault interruption, allowing the
fuse carrier to drop out and clearing the pigtail of the blown fuse link through the bore of use
tube.

15) FUSE BASE (PORCELAIN):


The fuse base shall be bird-proof, two units porcelain insulator with a creep age distance (to earth) not
less than 320mm. The insulators will be supplied with 10KN as per IS:731
16) FUSE TUBE:
The fuse tube shall be made of fiber glass coated with ultraviolet inhibitor on the outer surface and
having arc quenching bone fiber liner inside. The tube shall have high bursting strength to sustain high
pressure of the gases during fault interruption. The inside diameter of the fuse tube shall be 17.5mm. The
solid cap of the fuse carrier shall clamp the button head of the fuse link, closing the top end of the fuse
tube and allowing only the downward venting during fault interruption.
17) TYPE TESTS :
The Drop out shall be subjected to the following type tests.
i)
Dielectric tests (rated impulse withstand and rated one minute power frequency withstand
test voltages
ii) Temperature rise test. The above tests shall be carried out in accordance with IS: 9385 Parts I and II.
FOR PORCELAIN FUSE BASE ONLY:
iii)
Pull out test for embedded components of the fuse base.
iv) Beam strength of porcelain base.

18)

MOUNTING ARRANGEMENT:
The Drop outs mounting arrangement shall be made of high strength galvanized steel flat and shall
be robust enough to sustain the various stresses encountered during all operating conditions of the
Drop out.

19)

TERMINAL CONNECTIONS:
The Drop out shall be provided with two aluminum alloy as per IS: 617-1994) terminal connectors at top
and bottom of fuse base assemblies to receive aluminum conductors of diameters between 6.3mm to
10.05mm. These terminals shall be easily accessible irrespective of the Drop out location with respect of
the pole. The terminals shall meet the test requirements of REC construction standard E-30.

20)

NAME PLATE:
Aluminum anodized name plate shall be fixed at base of D.O. fuse. The following information shall
be duly punched or engraved on it.
(1)Manufacturers name
(2) P.O. No. and date
(3) Rated voltage
(4) Rated normal current
(5) Frequency
(6) Sr. No. of D. O. fuse
(7) Property of NESCO etc.

21)

22)

INSPECTION :
All tests and inspection shall be made at the place of manufacture unless otherwise especially agreed
upon by the manufacturer and the purchaser at the time of purchase. The manufacturer shall afford the
inspector representing the purchaser all reasonable facilities without charge, to satisfy him that the material
is being furnished in accordance with this specification.
The purchaser has the right to have the tests carried out at his own cost by an independent agency whenever
there is dispute regarding the quality of supply.
ROUTINE TESTS :
The following routine tests shall be carried out by the manufacturer on each unit to check the essential
requirements.
a) Visual inspection.
b) Verification of all dimensions.
c) Power frequency voltage dry test.
Supplier is required to maintain the register for routine tests and will show to the inspector, who comes
for inspection for verification / confirmation purpose.
d) Mechanical operation: 10Nos of open-close operation per unit ON operation can be carried
out with operating rod. OFF operations can be carried out by cutting the fuse wire so that it falls freely
as in actual service condition.

23)

ACCEPTANCE TESTS:
The following tests shall be carried out at suppliers works on the samples selected from the offered lot as
per the sample procedure given at clause No.24 of this specification.
I.
Visual inspection.
II.
Verification of dimensions of all parts as per approved Drawing.
III.
Power frequency voltage dry test as per IS: 73/71 with latest amendment if any.
IV. Mechanical operation test ON-OFF operation (100 Nos. ON-OFF operation) can be carried out with
operating rod. OFF operations can be carried out by cutting the fuse wire so that it falls freely as in
actual service condition.

25)

V. Temperature-rise test.
VI. Galvanizing test
VII. Test on F. R. B. P. Tube.
VIII. Chemical composition test of all current carrying components.
TEST CERTIFICATE FOR POST INSULATOR:
For the offered lot supplier shall have to submit acceptance and routine test certificate received from the
original manufacturer for 11KV post insulator and FRBP tube used in the manufacturing of D.O. fuse.
It is preferred that insulators of same make are used in one lot. However, if insulators of different make are
used in one lot of D. O. fuse then supplier will have to submit Type test certificates (Validity up to 5
Years) received from the respective original manufacturer for the insulators used in D. O. fuse.
11 KV 200 Amp 2 / 3 Pole D.O. Fuse
Guaranteed Technical Particulars

Slno.

Description & Specification

Normal system voltage 11KV

Rated Voltage 12KV

Rated Current-200Amp.

Rated frequency 50 Hz.

Rated 1 (one) inute power frequency withstand voltage.


a) between pole and earth 28 V

Yes

b) across the isolating distance of fuse of base 35 KV

Yes

Lightening Impulse Voltage With stand

a) Earth & between poles - 75 KV (Peak)


b) Across Isolating
7

Bidders Offer

- 85KV (Peak) of fuse base.

Breaking Capacity 8KA

Contact shall be made from phosphorus bronze (Copper Alloy)


Yes i.e. the contact should be silver plated with thickness of
coating not less than 2.5 Micron and the contact points should
efficiently transfer current to fuse base.

The fuse band shall be made from fiber glass tube (FRBP Tube)
made from synthetic resin bounded woven glass fabric grade MF-4
laminated sheet as per BS-3953/1976

10

11KV Solid Core Insulators having 320mm minimum creep age


distance and 10 KN (minimum) mechanical failing load shall be
provided Max Well Ceramics / Vishal Malleable or any other
approved material. The offer with any other make insulators also
are acceptable and in the event of order the same shall have to be
got approved and type tested by selecting samples by the
inspecting officer. .

11

All M. S. Bolts, Nuts, Washer above 10mm, ferrous shall be hot


dip galvanized.