Documente Academic
Documente Profesional
Documente Cultură
The electrical system in TKII scope consists of 1 No MCC panel feeding the
electrical equipment which consists of motor loads (AC squirrel cage type).
While some motors are fixed speed type, few are operated through VFD (6
pulse type – model ACS800 of ABB make) for obtaining variable speed
operation as per process requirement.
For improving the overall power factor to 0.9 at the MCC busbar, 1 No power
factor improvement panel consisting of capacitors and relay for automatic
switching of capacitor banks is also provided. The rating of capacitors in APFC
panel is 300 kVAr.
The data of actual harmonic current and voltage distortion under working
conditions has been made available by M/s ABB. As per the information
furnished the details are as below –
Considering the above data, it is proposed to install reactors in series with few
capacitor banks to work as filters for absorbing the harmonic currents.
Out of total capacitor rating of 300 kVAr, following capacitor banks are
proposed for using as harmonic filter –
Transformer IH
Xx / 0.415V,
1250 kVA VFDs Filter-1 Filter-2
C. Methodology –
Filter-1:
Since filter-1 is required to be common to 5th & 7th harmonic, the tuning
frequency is proposed to be selected as 270 Hz (5.4 times the fundamental
frequency).
Filter-2:
Since filter-2 is required for 11th harmonic, the tuning frequency is proposed to
be selected as 530 Hz (10.6 times the fundamental frequency).
Filter-1:
Filter-2:
For each harmonic frequency, the net impedance will be difference between XL
and XC.
For Filter-1 :
For Filter-2 :
The harmonic currents introduced by the VFD will flow through both filters, with
each filter absorbing current in the inverse proportion of the impedances.
That is, for Filter-1 –
Z-Filter-2 (- 0.4919)
I-Filter-1-250 = I-250 x ---------------------- = 298 x ----------------------
Z-Filter-1 + Z-Filter-2 (- 0.0546 – 0.4919)
= 268.23 A
I-Filter-1-350 = 91.8 A
I-Filter-1-550 = 10.2 A
I-Filter-2-250 = 29.8 A
I-Filter-2-350 = 10.2 A
I-Filter-2-550 = 6.5 A
Note: For simplifying the calculation, the value of resistance in filter circuit is
assumed as zero.
DOUBT –
For each harmonic current introduced by the VFD, the load will comprise of the 2
filter circuits and the distribution transformer & these can be considered as
connected in parallel. Hence the current distribution through the filters will
depend upon the actual value of the transformer impedance also.
Impedance of transformer –
kVA = 1250
Impedance = 5%
Fault kVA = 1250 / 0.05 = 25000
Fault current = 25000 / (1.732 x 0.415) = 34781 A
Transformer impedance = 240 V / 34781 A = 0.0069 Ohm
Since the actual value of transformer impedance is observed as less than the
value of net impedance of Filter-1 & 2 at all harmonic frequencies, will the Filters
be able to absorb the harmonic currents as intended? Or will some part of
harmonic current flow through the transformer also.