Documente Academic
Documente Profesional
Documente Cultură
( Reaffirmed 1997 )
hdian Standard
CURRENT
TRANSFORMERS
PART
PROTECTIVE
(
CURRENT
TRANSFORMERS
Second Revision )
Third Reprint MARCH
UDC
BUREAU
MANAK
OF
BHAVAN,
1997
621314224
BIS 1992
INDIAN
9 BAHADUR
NEW
November 1992
SPECIFICATION
DELHI
STANDARDS
SHAH
ZAFAR
MARG
110002
Price Group 3
Instrument
Transformers
Sectional
Committee,
ETD 34
FOREWORD
This Indian
Standard
(Part 3 ) was adopted
by the Bureau of Indian
finalized
by the Instrument
Transformers
Sectional
Committee
had
Electrotechnical
Division Council.
Standards,
after the draft
been approved
by the
This standard was first published in 1964 and revised in 1981. This revision
to bring it in line with the latest developments
at the international
level.
Indian
Standards
on current
transformers
Part
General
Part
Measuring
Part
Protective
current
transformers
Part
Protective
current
transformers
in four
has
been
undertaken
parts:
requirements
current
transformers
applications
For obtaining
an efficient protection,
it is necessary that the protective current
transformers
The requirements
of protective
maintain
the accuracy up to several times the rated current.
transformers
differ from measuring current transformers
mainly in this respect.
should
current
This specification
applies to protective current trasforrners intended for use in non-balaced
protective
equipment,
for example,
for the operation of overcurrent
devices both of the non-directional
types
and the protective current transformrrs
used for the operation of earth-fault
devices with time lag
characteristics.
When the operation of the protective equipment
is more precisely dependent upon
the magnitude
and phase relationship
of voltage and current, for example, earth-fault
protection
in
instantaneous
earth-fault
resonant earthed networks, or upon the balance of current,
for example,
the current
transformers
may require characteristics
other
protection
and differential
protection,
than those prescribed in this specification.
In such case, the designer of the protective system should
spzcify th: additional
requiremznts
that may be necessary.
in the preparation
of this standard,
assistance
for
Transformers,
Current
published
Transformers
Intermltional
Electrotechnical
published
by
of
Indian Standard
CURRENT TRANSFORMERS
PART 3 PROTECTIVE
-SPECIFICATION
CURRENT TRANSFORMERS
Second Revision )
1 SCOPE
accuracy requirements
rated burden.
2.3.2
of this specification
are met at
2.4 Secondary
to supply protective
2.5 Exciting
2.2 Composite
a) the
instantaneous
cu.&em, and
values
of the primary
b> the
instantaneous
values
of the actual
secondary
current multiplied
by the rated
transformation
ratio.
3 ACCURACY
4 ACCURACY
FACTOR
CLASS
LIMlT
Current
Error
100
EC=-----I
emf
Current Transformer
Limiting
( K.* i - ip)2 dt
J0
4.1 Standard
Accuracy
Classes
where
Kn =
I
rated transformation
ratio,
iP
= instantaneousvalueoftheprimarycurrent,
i8
5, instantaneous
value
current
NOTE -
of the secondary
class followed
current, and
2.3 Accuracy
LIMITS OF ERRORS
Limit Factor
1 Limits of Errors
( Clause 5.1)
Accuracy
Curnat
Cl=
Fi-ror
pbast DisplDces8cnt
aI Rated
Prhay
rt Rated
Cumnt
himary
cumnt
Composite Error
at Rated
Accuracy IhIt
Primary Carreti
(Percent)
(Minuks)
(PcrccnI)
(1)
(2)
(3)
(4)
5P
*1
GCI
1OP
z3
10
i5P
t5
15
6 MARKING
With the primary
winding spen
circuited, the
secondary winding is energized at rated frequency
by a substantially
sinusoidal voltage having an rms
value equal to the secondary limiting ernf. The resulting
exciting current expressed as a percentage of the rated
secondary current multiplied by the accuracy limit
factor shall no1 exceed the limit of composite error
given in 5.1 (see also A-7).
NOTES
1 In calculating the secondary limiting emf used above. the
secondary winding impedance shall be assumed IO be equal IO
the secondary winding resistance measured a1 room temperature
and correacd IO 75T.
7 TESTS
7.1 TypeTest
7.1.1 Current
Composite Error
Direct lest
Compliance
witb the limit of composite error given
in 5.1 shall be demonstrated by a direct test, in which
a substantially
sinusoidal current equal to the rated
accu.racy limit primary current is passed through the
primary winding,
with the secondary winding
connected to the rafed burden. The composite error
may be determined
as given in Annex A (see A-3
and A-6).
This
7.2.2.1
the
NOTE -The
distance of the return primary conductor from the
current transformer shall be Irken inIo accounl from the point of
view of reproducing setvice conditions.
ANNEX A
(Clause 7.1.2.1)
NOTES ON PROTECTIVE CURRENT TRANSFORMERS
A-l
VECTOR DIAGRAM
is present, we
havel less tbanl andsinceit isf that goesinto the
vecto!diagram a&I I is used fort& determination of
the ratio error, it fs seen that turns correction will
have an infbrence on the ratio error (and may be
deliberately used with that purpose). However, the
vectors1 and I have the same directionso that turns
correct&i has no influence on phase displacement.
It is also apparent that turns correction has only a
partial influence on composite error.
tums).
Im
_.
hl
e
rP
FIG.
2 ERRORTRLANGLEOF CURRENT
-bNSFORMEXS
IS 2705(Part 3) : 1992
current ratio and phase displacement depends upon
the power factors of &hetotal burden impedance and
of the exciting current. Zero phase displacement will
result when these two power factors are equal, that is
when I, and I, are in phase.
A-4
COMPOSITE
ERROR
TEST
FOR COMPOSITE
Pl
PZ
Y t
1
52
Pl
51
PZ
52
ERROR
Sl
FIG. 5 ~~JZAWREMENTOF
COMPOSITE
ERRORWITHTHE
USEOF AN AUXKMRY~
CURRENT TRANSFORMER
A-5.3.1 The measurement
is further simplified if a
ratio meter is used as shown in Fig. 6. This ratio meter
measures
the difference
between
currents of transformer N and N.
the secondary
A-6
ALTERNATIVE
METHOD
FOR i-III<
DIRECT
MEASUREMENT
OF COMPOSITE
ERROR
A-6.1 Composite errorofcurrent
transformers may be
measured by an alternative method as shown in Fig. 7.
b)
and
d)
A-6.2 While
the
method
described
for the
measurement
of composite
error
for current
transformer
in Fig. 5 requires a special reference
current
transformer
N of
the
same
rated
transformation
ratio as the transformer X and having
negligible
composite
error at the accuracy limit
primary current. the alternative method as shown in
Fig. 7 enables standard reference current transformer
N and N to be used at or about their rated primary
currents.
It is still essential, however, that these
reference
transformers
should
have
negligible
campsite error.
A-7 JNDJKECT
ERROR
IS 2705(Part3):lWt
of determining tbe composite error. Once tbis re1ation
has been established for a certain type of transformer
(preferably with no turns correction) for a given
burden, and for a given accuracy limit factor, then this
relation may be used in the routine determination of
the composite error by the indirect method as
mentioned in 7.2.2.2.
A-8 USE OF COMPOSITE
ERROR
Date of Issue
Amend No.
BUREAU
OF INDIAN
STANDARDS
Headquarters:
Telegrams: Manaksanstha
(Common to all offices)
Telephone
323 76 17,323 38 41
CALCUTTA
337 84 99,337 85 61
337 86 26,337 9120
700054
Northern
160022
Southern
235 02 16,235 04 42
{ 235 15 19,23523 15
Western
: Manakalaya,
832 92 95,832 78 58
1 832 78 91,832 78 92
Branches
: AHMADABAD.
60 38 43
{ 60 20 25