CONTENTS
Introduction................................................ 2
Main features............................................... 4
Circuit breaker..............................................6
Disconnectors,
maintenance and high
speed earthing switches..........................10
Current transformer....................................12
Voltage transformer....................................13
Joining and expansion units.......................14
Surge arrester.............................................16
Terminations...............................................17
Gas monitoring system
and local control cabinet...........................19
Design and production
facilities......................................................20
Development facilities............................... 21
Quality assurance...................................... 22
Quality control...........................................23
Technical characteristics ...........................26
Typical substation layouts......................... 27
INTRODUCTION
The increased demand for electrical energy in big
cities and industrial areas has made it necessary
to bring high voltage systems directly to the load
centres. It is very difficult, and sometimes
impossible to find a suitable place for installation
of the air insulated switchgear (conventional
type).
At the same time in many areas (cities, industrial
centres, seaside etc.) the air has become very
polluted for using any sort of the open type
insulation.
The SF6 gas insulated switchgear (GIS) guarantees
outstanding advantages for the planning and
operation of high voltage supply networks. For
instance, the space requirement can be less than
10% of the space taken up by an equivalent
conventional installation.
As all live parts are metal enclosed and
hermetically sealed, the SF6 GIS is completely
immune to the atmospheric pollution (fog, sand,
salt...)and industrial pollution (dust, smoke,
gas...). With SF6 GIS all foreign bodies (persons,
animals, tools) are prevented from coming into
contact with live parts. This ensures maximum
safety to personnel and increased continuity of
operation.
Harmful effects, caused by corona and radio
interferences, are totally eliminated and thanks to
the low noise level of the driving mechanisms the
SF6 GIS is very suitable for installation in residental
areas.
All switchgear enclosures and conductors are
made of aluminium. The results of this design are
low enclosure losses and light weight.
The switchgear is shipped as large sub-assemblies
and as complete factory tested package feeders.
The cost of the site erection and commissioning is
minimized.
The well known modular design allows the
switchgear to be adopted to the specific
requirements of each particular case (one line
diagram, layout, section...).
MAIN FEATURES
Single phase enclosed design
Small dimensions allowing economical space
saving
Indoor and outdoor applications
High reliability in service, independence of
ambient influences
Flexibility and optimal arrangement of
equipment, assured by highly modular element
system
Light weight, gastight aluminium enclosures with
low electrical losses and corrosion resistance
Earthed enclosures assuring maximal protection
against electrical shock for the operating
personnel
Low maintenance and long service life
Environmental friendly behaviour
Epoxy-resin barrier and support insulators
Circuit breaker on single pressure principle,
actuated by hydraulic drive
Protection against dangerous overpressure
through bursting membranes
Quick site assembly assured by in-factory
preassembled bays and shipping units
Compliance with relevant international standards
(IEC 517; IEC 694...)
CIRCUIT BREAKER
The circuit breaker is single pressure double flow type, which by
synchronizing puffer, suction, self blast and nozzle ablation effects,
significantly boosts the circuit current breaking performance.
The operating mechanism can allow three-pole operation or singlepole operation according to the Clients' request.
The circuit breaker is operated by a reliable hydraulic mechanism
installed directly on the circuit
breaker supporting structure. The
hydraulic mechanism operates in the
range of +50C and -25C ambient
temperature. The production is
based on 40 years of experience and
- development.
continuous
One closing coil and two trip coils are
normally provided for operation
control.
The circuit breaker can be operated
remotely or locally from the local
control cabinet.
The interrupting chamber is
equipped with facility for filtering the
humidity and absorbing the gas
decomposition products.
All inspection and maintenance
operations can be easily executed
without having to dismantle the
adjacent parts.
Closed position
Arc quenching
Arc quenching
Arc quenching
Open position
Sequence of current interruption
Position: ON
high pressure
8
8
without pressure
10
Section of maintenance or
high speed earthing switch
11
CURRENT TRANSFORMER
The current transformer has toroidal cores
installed concentrically to the primary winding
formed by the inner conductor.
The transformer cores are tensioned in a retaining
frame and are inserted in gas space of the housing
together with an internal screen.
The ends of secondary windings are brought into
the terminal box through gastight bushings.
Cores with secondary windings are designed in
accordance with the requirements for accuracy
class and power rating.
Changing of transformer ratio is carried out in the
terminal box.
12
VOLTAGE TRANSFORMER
The voltage transformer is inductive type.
The main insulation is SF 6 gas, while synthetic foils
are used as insulation between the windings.
It can be arranged in front of or behind the
outgoing feeder disconnector or on the busbar.
The primary conductor, supported by a gastight
bushing, forms the connection to the switchgear.
The secondary connections are accessible via
terminal box.
13
14
15
SURGE ARRESTER
Gas insulated surge arresters can be supplied where the use of
outdoor surge arresters is not practicable (cable bays or connections
to transformers through busduct) or where the overhead line
termination is too far from the GIS to ensure a coordinated protection.
The surge arrester is made from first class ZnO discs protected by
gastight insulating cylinder and inserted in the metal enclosure.
Screens are used for the correct distribution of the electrical field.
16
TERMINATIONS
CABLE END
The cable end facilitates the interconnection of
the HV cable and the GIS. The cable end contains
a cast resin cable end insulator - always supplied
by the cable manufacturer - enclosure and
contact system. The main insulation of the cable
end is SF6 gas and this gas compartment is usually
independent of the other gas compartments in
the switchgear bay.
SF6 - AIR BUSHING
The overhead line is
connected to the GIS
t h r o u g h t h e S F6 - a i r
bushing. Its external cover
is a conventional gastight
porcelain insulator with
suitable screen formation
and with potential control
inside. The bushing
current conducting tube is located in the axis
of the porcelain insulator. The bushings can be
installed in different arrangements according
to the connection possibilities of the overhead lines.
SF6 - OIL BUSHING
This
bushing ensures direct
connection between the transformer and the GIS. The insulating
body of the bushing is made of
epoxy-resin always supplied by the
transformer manufacturer. The GIS
manufacturer supplies the
enclosure of SF6 gas insulated
transformer connection including
the contact system and the antivibration compensator to damp
the vibration of the transformer.
17
18
19
The new plant at Tpiszele, Hungary with the new GIS factory in the front of the picture.
20
DEVELOPMENT FACILITIES
All of the most advanced calculations and
simulation techniques are used during the
development stage of the various components
and in particular:
two-dimension and three-dimension
finite element softwares for evaluation of
the dielectric strength
finite element software for stress analysis
of GIS enclosures
two-dimension and three-dimension
software for gas flow analysis for
evaluation of the performances of the
interrupting chambers during various
network operating and fault conditions
modelling of hydraulic drives
All the calculations and simulations are fully
integrated by experimental data obtained during
type and research tests.
21
QUALITY ASSURANCE
The applied Quality Assurance System for design, development,
manufacturing and testing is in compliance with the standard of:
ISO 9001 (UNI--EN 29001)
22
QUALITY CONTROL
All quality control operations are carried out on all materials,
subcomponents and components up to the final tests on the
shipping units.
Apart from the tests carried out at Ganz Transelektro test rooms,
which are under periodical control of independent institutes, all
materials and subcomponents are subject of the required tests at the
subsupplier's workshop.
In order to allow the End User to control and to participate in the test
program, a Quality Control Plan is prepared during the contract stage.
The 750 kV GIS high voltage test transformer and the coupling capacitor
23
145 kV GIS extension, Malaysia, "Kuala Lumpur East". New line busducts.
24
25
GIS
TECHNICAL CHARACTERISTICS
26
27
28
29
30
31
32