WEIDMANN DIAGNOSTIC SOLUTIONS

8406 SCRANTON STREET + HOUSTON, TX + 77061


(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM

Furanic Compounds in Electrical Insulating Liquids by HPLC


ASTM D-5837 Report
Location: LUFKIN

Mfr: COOPER

Serial #: C0725651
Bank/Ph: 3

HOUSTON, TX

Fluid: MIN

Control #: 6035991

Imp.(% Z):

Breathing: SEAL

PO #:

Order #: 307210

KVA: 15000

Tank: TRANSFORMER

ATTN:

Account: 67

KV: 13.2/7.62

Received: 08/10/2009

Container: R465 3 3 3
Gallons: 106350

Project ID:

Reported: 08/20/2009
Customer ID:

Results:
Furanic Compound

Result (ppb)

Reporting Limit (ppb)

2-Furaldehyde

< 10

10

5-Hydroxy-methyl-furaldehyde

< 10

10

2-Acetylfuran

< 10

10

5-Methyl-2-furaldehyde

< 10

10

2-Furyl alcohol

< 10

10

* BRL = Below Reporting Limit

Diagnostics:
New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) of 1000-1300. "Middle Aged" paper is
approximately 500 and paper with less than 250 is in its "Old Age". Severely degraded insulation with a DP of 150 or less will have very little mechanical
strength and may result in a transformer failure. The following estimations are based on current research of GSU transformers filled with mineral oil.
Estimated Degree of Polymerization (DP): >1003
Estimated Operating Age of the Equipment: <1.0

Notations:

QC Chemist: CN
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does not
imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate
only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. Weidmann Diagnostic
Solutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or
other property for which this report may be used or relied upon for any reason whatsoever.

A Member of the WICOR Group

WEIDMANN DIAGNOSTIC SOLUTIONS


8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM
Location: LUFKIN

Mfr: COOPER

Serial #: C0725651LTC

KV:

Bank/Ph:

HOUSTON, TX

Tank: LTC

ATTN:

Fluid: MIN

Lab Control Number:


Date Sampled:
Order No.:
Oil Temp.(C):

Container: 3A 3A 3A
Gallons: 190

Project ID:

Order #: 307210
Control #: 6036005
Received: 08/10/2009
Reported: 08/20/2009
Customer ID:

6036005
08/07/2009
307210

Moisture in Oil
(ppm):
25
Interfacial Tension
(dynes/cm):
46.1
Acid Number
(mg KOH/g):
0.003
Color Number
(Relative):
L.5
Visual Exam.
(Relative):
CLR&SPRK
Sediment Exam.
(Relative): PARTICULATES
Dielectric Breakdown
(kV):
35
Dielectric Breakdown 1 mm (kV mm-C):
Dielectric Breakdown 2 mm (kV mm-C):
Power Factor @ 25C
(%):
Power Factor @ 100C
(%):
Power Factor @spec.C
(% C):
Specific Gravity
(Relative):
Viscosity @ 100F
(SUS):
Viscosity @ Spec.F
(SUS F):

Metals

D-92
D-92
D-97
WDS
D-2668
D-1807
D-1169

Dissolved
Fault, Wear, and
Contamination
Metals

PCB

Physical, Chemical, and Electrical Tests

ASTM Method

EPA-Method 8082

Diagnostics

Imp.(% Z):

Breathing: SEAL

PO #:

D-1533B
D-971
D-974
D-1500
D-1524
D-1524
D-877
D-1816
D-1816
D-924
D-924
D-924
D-1298
D-445
D-445

KVA:

Account: 67

Flash Point
Fire Point
Pour Point
Passivator
Oxidation Inhibitor
Refractive Index
Resistivity

(C):
(C):
(C):
(ppm):
(wt. %):
(Relative):
(ohm cm):

Aluminum (Al) (ppm):


Copper (Cu) (ppm):
Iron (Fe) (ppm):
Lead (Pb) (ppm):
Silver (Ag) (ppm):
Tin (Sn) (ppm):
Zinc (Zn) (ppm):
Silicon (Si) (ppm):

< 0.5
< 0.5
< 0.5
< 0.5
< 0.5
< 0.5
< 0.5
< 0.5

Concentration (ppm):
PCB Type (Aroclor):

< 1.0 PPM


N

Reporting Limit:

Moisture in Oil:
Interfacial Tension:
Acid Number:
Color Number and Visual:
Dielectric Breakdown D-877:
Dielectric Breakdown D-1816:

Acceptable for equipment > 69 kV for in-service oil - kV not provided (25 ppm max).
Diagnostic not applicable.
Diagnostic not applicable.
Color Number diagnostic not applicable. Visual diagnostic not applicable.
Diagnostic not applicable.

Power Factor @ 25C:


Power Factor @ 100C:
Oxidation Inhibitor:

The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann-ACTI Inc. does not imply that the contents of the sample received by this laboratory are the same as all such
material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann-ACTI. Weidmann-ACTI assumes no
responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever.

A Member of the WICOR Group

TRANSFORMER MAINTENANCE TEST

Electrical Reliability Services Inc.


Houston Area Service Center
1455 E. Sam Houston Pkwy S
Suite 190
Pasadena, TX 77503
Phone 281-241-2800

CUSTOMER

PAGE

1 of 4

ADDRESS

JOB #

3100177

USER
PLANT

NA

DATE LAST INSPECTION

5/13/11

DATE

TEMPERATURE

31

HUMIDITY

53

Transformer Yard

SUBSTATION

C-07256-5-1

EQPT. LOCATION

C-07256-5-1

POSITION

NAMEPLATE DATA
MANUFACTURER
IMPEDANCE
KVA

Cooper Power Systems


10

15,000

20,000

PRIMARY KV

CAPACITY
/

25,000

YR MFR

4930

WINDING MATERIAL

Gallons

1991
TYPE

7,621

OA

FA

B.I.L. RATING

FA
110

WYE

TAP VOLTAGES

141,600

136,800

132,000

127,200

122,400

TAP POSITION

55

DELTA

13,200

TAP SETTING

C-07256-5-1

CLASS

TEMPERATURE RISE

COPPER

132,000

SECONDARY KV

SERIAL NO.

132,000

INSULATING MEDIUM

Mineral Oil

TANK TYPE

VOLTS

Gas Blanketed

DRY TYPE

CONSERVATOR

VISUAL AND MECHANICAL INSPECTION


INSPECTION REPORT

INSPECTION REMARKS

INSPECT PHYSICAL AND MECHANICAL CONDITION

PASS

FAIL

VERIFY FANS OPERATE

PASS

FAIL

Fans not installed because the Xfmr is going to be painted

INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING

PASS

FAIL

N/A

ELECTRICAL TESTS

(OPTIONAL FOR L.V. TRANSFORMERS OR BELOW 500 kVA)

MAINTENANCE

ACCEPTANCE
INSULATION RESISTANCE IN MEGOHMS

WINDING RESISTANCE TEST IN OHMS

MINUTES

PRIMARY TO
GROUND

SECONDARY TO
GROUND

PRIMARY TO
SECONDARY

H1-H2

4.208

X0-X2

0.01510

TEST KV

H2-H3

4.208

X0-X3

0.1511

0.50

3,650

2,056

3,680

H3-H1

4.210

X0-X1

0.01509

1.00

4,060

2,420

4,510

10.00

6,255

4,270

9,076

P. I.

1.54064

1.76446

2.01242

TRANSFORMER TURN RATIO TEST


TAP

PHASE A

WORKING TAP

P.I. = 10 min/1 min

0 COMMENTS:
3

CALC

AF

PHASE B

AL

PHASE C

Core Ground megged at 500 volts 1,690 Mohms

DEFICIENCIES:

EQPT. INVENTORY NO. WR C13-061 AND MEGGER C13-057


COPYRIGHT 2002-2008 POWERDB, INC.

TESTED BY: Vaundrae Ross and Delon Wade


www.powerdb.com

56700, REVISED 4/17/08

INSULATION TESTS
TWO-WINDING TRANSFORMERS

Electrical Reliability Services Inc.


Houston Area Service Center
1455 E. Sam Houston Pkwy S
Suite 190
Pasadena, TX 77503
Phone 281-241-2800

CUSTOMER

PAGE

2 of 4

ADDRESS

JOB #

3100177

USER
PLANT

32.0

NA

DATE LAST INSPECTION

5/13/11

DATE

30

TEMPERATURE

HUMIDITY

46

Transformer Yard

SUBSTATION
Dyn1

Diagram # 5

(ANSI)

VOLTAGE (kV)
PRIMARY: 132
SECOND: 7.621 / 4.400

kVA

25,000
25,000

C-07256-5-1

POSITION

MFR
CPP
YEAR 1991
SER NO
C-07256-5-1
WEATHER SUNNY
LB
WEIGHT
106350
OIL TEMP 30 C
TYPE N2 BLANKETED
BIL 110 kV
3
CLASS
OA/FA/FA
PHASES
COOLANT
OIL
WDG MATERIAL Cu
ACCEPTANCE IMPEDANCE 10 %
REASON
OIL VOLUME
4930 UG
RATED I
109
1,894

C-07256-5-1

EQPT. LOCATION

DSG
H1
H2
H3
HN
L1
L2
# TAPS NOMINAL CHANGER TAP SETTING L3
5
3
Off Load
LN
1
3
On Load

BUSHING NAMEPLATE
SERIAL NUM
MFR.
TYPE/CLASS
1ZUA3S05786308 CPS
1ZUA3S05786304 CPS
1ZUA3S05786306 CPS

kV
115
115
115

AMPS YEAR
80011 2003
800
2003
800
2003

S85694
S85695
S85693
S85696

25
25
25
25

2000
2000
2000
2000

CPS
CPS
CPS
CPS

2003
2003
2003
2003

TRANSFORMER OVERALL TESTS


TEST
NO

INSULATION
TESTED

TEST
MODE

TEST LEAD
CONFIGURATION
ENG

GND
L

CHG + CHL

GST
GND

CHG

GST

CHL

UST

CHL'

CLG + CHL

GST
GND

CLG

GST

UST

CHL
CHL'

9
10

GAR

TEST
kV

L
L

POWER FACTOR %

CAPACITANCE
C (pF)

UST

20 C
%PF

MEASURED

DIRECT

IR
Auto/Man

CORR
FACTOR

mA

WATTS

0.800

22.547

0.6100

10.01

5,980.60

10.00

2,661.60

0.34

0.27

0.800

10.034

0.3410

G/

10.00

3,317.80

0.19

0.15

0.800

12.508

0.2390

G/

3,319.00

0.21

0.17

0.800

12.513

0.269

OK

0.800

55.330

2.0910

TEST 1 MINUS TEST 2

5.00

14,676.4

5.00

11,358.3

0.43

0.34

0.800

42.820

1.8230

G/

5.00

3,317.90

0.18

0.14

0.800

12.508

0.2290

G/

TEST 5 MINUS TEST 6

3,318.10

0.21

0.17

0.800

12.510

0.268

OK

CHG'

CHGMINUS HIGH BUSH.

1,577.03

5.944

0.242

CLG'

CLGMINUS LOW BUSH.

9,569.90

36.078

1.514

H
H
H

BUSHING C1 TESTS
TEST
NO.

BUSHING NAMEPLATE

TEST
MODE

TEST
kV

CAPACITANCE
C (pF)

MEASURED

20 C
%PF

CORR
FACTOR

mA

WATTS

365.00

UST

10.01

360.63

0.24

0.24

1.000

1.360

0.0320

G/

0.23

366.00

UST

10.01

362.75

0.31

0.31

1.000

1.368

0.0420

G/

0.23

365.00

UST

10.01

361.19

0.18

0.18

1.000

1.362

0.0250

G/

NO.

SERIAL #

POWER FACTOR

CAPACITANCE

11

H1

1ZUA3S05786308

0.23

12

H2

1ZUA3S05786304

13

H3

1ZUA3S05786306

14

UST

15

X1

S85694

0.49

620.00

UST

5.00

612.23

0.46

0.46

1.000

2.308

0.1060

G/

16

X2

S85695

0.42

598.00

UST

5.00

590.54

0.46

0.46

1.000

2.226

0.1030

G/

17

X3

S85693

0.46

592.00

UST

5.00

585.63

0.45

0.45

1.000

2.208

0.1000

G/

18

X0

S85696

0.46

529.00

UST

5.00

522.88

0.45

0.45

1.000

1.971

0.0890

G/

19

OIL TEST

EQPT. INVENTORY NO. M4K 0866


COPYRIGHT 2002-2008 POWERDB, INC.

TESTED BY: Vaundrae Ross and Delon Wade


www.powerdb.com

93500, REVISED 5/21/10

INSULATION TESTS
TWO-WINDING TRANSFORMERS

Electrical Reliability Services Inc.


Houston Area Service Center
1455 E. Sam Houston Pkwy S
Suite 190
Pasadena, TX 77503
Phone 281-241-2800

3 of 4

PAGE
BUSHING C2 TESTS
TEST
NO.

BUSHING

NAMEPLATE

NO.

SERIAL #

20

H1

1ZUA3S05786308

21

H2

22

H3

EQUIV

IR
Auto/Man

CAPACITANCE
C (pF)

MEASURED

20 C

CORR
FACTOR

mA

WATTS

3,833.00

0.50

3,810.90

0.36

0.36

1.000

14.367

0.5110

G/

0.25

3,844.00

0.50

3,818.90

0.33

0.33

1.000

14.397

0.4700

G/

0.25

3,833.00

0.50

3,815.40

0.41

0.41

1.000

14.384

0.5920

G/

CAPACITANCE

GRD

0.25

1ZUA3S05786304

GRD

1ZUA3S05786306

GRD

23

% POWER FACTOR

TEST
kV

POWER FACTOR

GRD

24

X1

S85694

GRD

0.50

234.81

0.52

0.52

1.000

0.885

0.0460

I/

25

X2

S85695

GRD

0.50

238.68

0.48

0.48

1.000

0.900

0.0430

I/

26

X3

S85693

GRD

0.50

231.25

0.42

0.42

1.000

0.872

0.0370

I/

27

X0

S85696

GRD

0.50

248.05

0.48

0.48

1.000

0.935

0.0450

I/

TEST MODE

TEST kV

mA

WATTS

IR
Auto/Man

SURGE ARRESTERS
LOCATION

SERIAL #

OVERALL
CATALOG

MFR

UNIT
CATALOG

RATED
kV

TYPE

ORDER

28

29

30

31

32

33

34

35

36

HOT COLLAR TESTS


SERIAL #

DSG

TEST MODE

SKIRT #

TEST kV

mA

WATTS

IR
Auto/Man

37
38
39
40
41
42
43
44
45
46
EXCITING CURRENT TESTS
CONNECTIONS:

H1 - H2

DETC

LTC

kV

mA

47

10.013

3.35

16.53

48

10.017

3.55

49

10.014

3.81

50

10.012

51

10.014

H2 - H3

WATTS Induct. (H)

kV

mA

WATTS Induct. (H)

7,923.72

10.013

7.54

39.39

17.64

7,484.76

10.017

8.01

18.93

6,977.40

10.014

8.48

3.98

20.15

6,672.78

10.012

4.21

21.60

6,309.49

10.014

H3 - H1
kV

mA

WATTS Induct. (H)

3,522.12

10.013

7.54

39.77

3,521.65

G/

IR

41.98

3,317.63

10.017

8.01

42.41

3,319.29

G/

44.85

3,131.69

10.014

8.54

45.17

3,111.87

G/

9.03

48.02

2,942.35

10.012

9.02

48.45

2,943.65

G/

9.61

51.54

2,763.81

10.014

9.59

52.03

2,769.28

G/

NOTE: SHORT EACH WINDING ON ITSELF


INSULATION RATING KEY
G = GOOD
D = DETERIORATED
I
= INVESTIGATE
B = BAD
Q = QUESTIONABLE
COMMENTS:
Test satisfactory.
All Test results are good and comparable
Xfmr has a core ground
COPYRIGHT 2002-2008 POWERDB, INC.

H
L
G
N

=
=
=
=

HIGH VOLTAGE WINDING


LOW VOLTAGE WINDING
GROUND
NEUTRAL BUSHING

www.powerdb.com

EQUIVALENT
CIRCUIT

93500, REVISED 5/21/10

INSULATION TESTS
TWO-WINDING TRANSFORMERS

Electrical Reliability Services Inc.


Houston Area Service Center
1455 E. Sam Houston Pkwy S
Suite 190
Pasadena, TX 77503
Phone 281-241-2800

CUSTOMER

PAGE

4 of 4

ADDRESS

JOB #

3100177

USER
PLANT

32.0

NA

DATE LAST INSPECTION

5/13/11

DATE

30

TEMPERATURE

HUMIDITY

46

Transformer Yard

SUBSTATION
Dyn1

Diagram # 5

(ANSI)

VOLTAGE (kV)
PRIMARY: 132
SECOND: 7.621 / 4.400

kVA

25,000
25,000

C-07256-5-1

POSITION

MFR
CPP
YEAR 1991
SER NO
C-07256-5-1
WEATHER SUNNY
LB
WEIGHT
106350
OIL TEMP 30 C
TYPE N2 BLANKETED
BIL 110 kV
3
CLASS
OA/FA/FA
PHASES
COOLANT
OIL
WDG MATERIAL Cu
ACCEPTANCE IMPEDANCE 10 %
REASON
OIL VOLUME
4930 UG
RATED I
109
1,894

C-07256-5-1

EQPT. LOCATION

DSG
H1
H2
H3
HN
L1
L2
# TAPS NOMINAL CHANGER TAP SETTING L3
5
3
Off Load
LN
1
3
On Load

BUSHING NAMEPLATE
SERIAL NUM
MFR.
TYPE/CLASS
1ZUA3S05786308 CPS
1ZUA3S05786304 CPS
1ZUA3S05786306 CPS

kV
115
115
115

AMPS YEAR
80011 2003
800
2003
800
2003

S85694
S85695
S85693
S85696

25
25
25
25

2000
2000
2000
2000

CPS
CPS
CPS
CPS

2003
2003
2003
2003

TRANSFORMER OVERALL TESTS


TEST
NO

INSULATION
TESTED

TEST
MODE

TEST LEAD
CONFIGURATION
ENG

GND
L

CHG + CHL

GST
GND

CHG

GST

CHL

UST

CHL'

CLG + CHL

GST
GND

CLG

GST

UST

CHL
CHL'

9
10

GAR

TEST
kV

L
L

POWER FACTOR %

CAPACITANCE
C (pF)

UST

20 C
%PF

MEASURED

DIRECT

IR
Auto/Man

CORR
FACTOR

mA

WATTS

0.800

22.547

0.6100

10.01

5,980.60

10.00

2,661.60

0.34

0.27

0.800

10.034

0.3410

G/

10.00

3,317.80

0.19

0.15

0.800

12.508

0.2390

G/

3,319.00

0.21

0.17

0.800

12.513

0.269

OK

0.800

55.330

2.0910

TEST 1 MINUS TEST 2

5.00

14,676.4

5.00

11,358.3

0.43

0.34

0.800

42.820

1.8230

G/

5.00

3,317.90

0.18

0.14

0.800

12.508

0.2290

G/

TEST 5 MINUS TEST 6

3,318.10

0.21

0.17

0.800

12.510

0.268

OK

CHG'

CHGMINUS HIGH BUSH.

1,577.03

5.944

0.242

CLG'

CLGMINUS LOW BUSH.

9,569.90

36.078

1.514

H
H
H

BUSHING C1 TESTS
TEST
NO.

BUSHING NAMEPLATE

TEST
MODE

TEST
kV

CAPACITANCE
C (pF)

MEASURED

20 C
%PF

CORR
FACTOR

mA

WATTS

365.00

UST

10.01

360.63

0.24

0.24

1.000

1.360

0.0320

G/

0.23

366.00

UST

10.01

362.75

0.31

0.31

1.000

1.368

0.0420

G/

0.23

365.00

UST

10.01

361.19

0.18

0.18

1.000

1.362

0.0250

G/

NO.

SERIAL #

POWER FACTOR

CAPACITANCE

11

H1

1ZUA3S05786308

0.23

12

H2

1ZUA3S05786304

13

H3

1ZUA3S05786306

14

UST

15

X1

S85694

0.49

620.00

UST

5.00

612.23

0.46

0.46

1.000

2.308

0.1060

G/

16

X2

S85695

0.42

598.00

UST

5.00

590.54

0.46

0.46

1.000

2.226

0.1030

G/

17

X3

S85693

0.46

592.00

UST

5.00

585.63

0.45

0.45

1.000

2.208

0.1000

G/

18

X0

S85696

0.46

529.00

UST

5.00

522.88

0.45

0.45

1.000

1.971

0.0890

G/

19

OIL TEST

EQPT. INVENTORY NO. M4K 0866


COPYRIGHT 2002-2008 POWERDB, INC.

TESTED BY: Vaundrae Ross and Delon Wade


www.powerdb.com

93500, REVISED 5/21/10

TRANSFORMER LOAD TAP CHANGER


TURNS RATIO TEST
3 Phase Test Method

Electrical Reliability Services Inc.


Houston Area Service Center
1455 E. Sam Houston Pkwy S
Suite 190
Pasadena, TX 77503
Phone 281-241-2800

CUSTOMER

PAGE

4 of 4

ADDRESS

JOB #

3100177

USER
PLANT

NA

DATE LAST INSPECTION

5/13/11

DATE

TEMPERATURE

30

HUMIDITY

28

Transformer Yard

SUBSTATION

C-07256-5-1

EQPT. LOCATION

C-07256-5-1

POSITION

NAMEPLATE DATA
MANUFACTURER

TAP
NO.

Cooper Power Systems

SECONDARY
TAP VOLTAGE

PRIMARY
VOLTAGE

CALCULATED
RATIO

SERIAL NUMBER

C-07256-5-1

MEASURED RATIO
H 3 H

1 /X

0 X 1

H 1 H 2 /X

0 X 2

H 2 H 3 /X

16L

11,880

6,858

132,000

19.2476

19.2610

19.2640

19.2650

15L

11,963

6,906

132,000

19.1138

19.1040

19.1090

19.1120

14L

12,045

6,954

132,000

18.9819

18.9150

18.9140

18.9120

13L

12,128

7,002

132,000

18.8518

18.8330

18.8360

18.8350

12L

12,210

7,049

132,000

18.7261

18.7430

18.7450

18.7450

11L

12,293

7,097

132,000

18.5994

18.5980

18.6050

18.6000

10L

12,375

7,144

132,000

18.4770

18.4090

18.4120

18.4090

9L

12,458

7,192

132,000

18.3537

18.3350

18.3340

18.3360

8L

12,540

7,239

132,000

18.2346

18.2490

18.2490

18.2500

7L

12,623

7,287

132,000

18.1145

18.1120

18.1160

18.1160

6L

12,705

7,335

132,000

17.9959

17.9330

17.9340

17.9340

5L

12,788

7,383

132,000

17.8789

17.8620

17.8660

17.8660

4L

12,870

7,430

132,000

17.7658

17.7780

17.7820

17.7810

3L

12,953

7,478

132,000

17.6518

17.6510

17.6560

17.6570

2L

13,035

7,526

132,000

17.5392

17.4850

17.4850

17.4830

1L

13,118

7,574

132,000

17.4280

17.4140

17.4150

17.4160

13,200

7,620

132,000

17.3228

17.3370

17.3400

17.3380

1R

13,283

7,669

132,000

17.2122

17.2700

17.2700

17.2720

2R

13,365

7,716

132,000

17.1073

17.1960

17.1970

17.1960

3R

13,448

7,764

132,000

17.0015

17.0730

17.0730

17.0780

4R

13,530

7,811

132,000

16.8992

16.9120

16.9140

16.9120

5R

13,613

7,859

132,000

16.7960

16.8490

16.8570

16.8560

6R

13,695

7,906

132,000

16.6962

16.7780

16.7800

16.7790

7R

13,778

7,954

132,000

16.5954

16.6630

16.6650

16.6680

8R

13,860

8,002

132,000

16.4959

16.5140

16.5100

16.5120

9R

13,943

8,049

132,000

16.3996

16.4480

16.4530

16.4530

10R

14,025

8,097

132,000

16.3023

16.3800

16.3850

16.3830

11R

14,108

8,145

132,000

16.2063

16.2700

16.2780

16.2770

12R

14,190

8,192

132,000

16.1133

16.1290

16.1270

16.1270

13R

14,273

8,240

132,000

16.0194

16.0680

16.0700

16.0710

14R

14,355

8,288

132,000

15.9266

16.0020

16.0030

16.0030

15R

14,438

8,336

132,000

15.8349

15.9000

15.9020

15.9060

16R

14,520

8,383

132,000

15.7462

15.7610

15.7600

15.7630

0 COMMENTS:
3

0 X 3

Test satisfactory.

DEFICIENCIES:

EQPT. INVENTORY NO. TTR C30-005


COPYRIGHT 2002-2008 POWERDB, INC.

TESTED BY: Vaundrae Ross and Delon Wade


www.powerdb.com

56400, REVISED 4/17/08

TRANSFORMER
TURNS RATIO TEST

Electrical Reliability Services Inc.


Houston Area Service Center
1455 E. Sam Houston Pkwy S
Suite 190
Pasadena, TX 77503
Phone 281-241-2800

CUSTOMER

PAGE

ADDRESS

JOB #

3100177

USER
PLANT

32.0

NA

DATE LAST INSPECTION

5/13/11

DATE

TEMPERATURE

32

HUMIDITY

30

Transformer Yard

SUBSTATION

C-07256-5-1

EQPT. LOCATION

C-07256-5-1

POSITION

NAMEPLATE DATA
Dyn1

PRIMARY:
SECOND:

MFR
CPP
YEAR 6/1991
SER NO
C-07256-5-1
WEATHER Sunny
LB
WEIGHT
106350
OIL TEMP 32 C
TYPE N2 BLANKETED
BIL 110 kV
3
CLASS
OA/FA/FA
PHASES
COOLANT
OIL
WDG MATERIAL Cu
Acceptance
REASON
IMPEDANCE 10 %
OIL VOLUME
4930 UG ALLOWED ERR 0.5 %

VOLTAGE (kV)
132
13.2 / 7.621

kVA

15,000
15,000

RATED I
66
656

DSG
H1
H2
H3
HN
L1
L2
# TAPS NOMINAL CHANGER TAP SETTING L3
5
3
Off Load
LN
1
3
On Load

SERIAL NUM

BUSHING NAMEPLATE
MFR.
TYPE/CLASS

kV

AMPS YEAR

HIGH SIDE TAPS TO LOW SIDE NOMINAL TURNS RATIO TESTS

PRIMARY
TAP

SEC.
TAP

R2 (1)

Nominal

141,600

R1 (2)

Nominal

136,800

Nominal

Nominal

L1 (4)

L2 (5)

COMMENTS:

HIGH SIDE LOW SIDE


VOLTAGE VOLTAGE

Test
Volt.

H1 - H3 / X1 - X0
CALC
RATIO

Ratio

Error

13,200

18.5802

18.5990

13,200

17.9504

17.9580

132,000

13,200

17.3205

Nominal

127,200

13,200

Nominal

122,400

13,200

Iexc

H2 - H1 / X2 - X0
Ph(min)

Ratio

Error

0.10

18.5970

0.04

17.9560

17.3370

0.10

16.6907

16.7010

16.0608

16.0810

Iexc

H3 - H2 / X3 - X0
Ph(min)

Ratio

Error

0.09

18.5800

0.00

0.03

17.9500

0.00

17.3400

0.11

17.3200

0.00

0.06

16.7080

0.10

16.6900

0.00

0.13

16.0790

0.11

16.0600

0.01

Iexc

Ph(min)

Test Satisfactory

DEFICIENCIES:

EQPT. INVENTORY NO. M4K 0866


COPYRIGHT 2002-2008 POWERDB, INC.

TESTED BY: Vaundrae Ross and Delon Wade


www.powerdb.com

56365, REVISED 3/4/09

WEIDMANN DIAGNOSTIC SOLUTIONS


8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM
Location: LUFKIN

Mfr: COOPER

Serial #: C0725651

KV: 13.2/7.62

Bank/Ph: 3

HOUSTON, TX

Tank: TRANSFORMER

ATTN:

Breathing: SEAL

PO #:

Dissolved Gas Analysis

ASTM D-3612
Report Units: PPM

Oil Screen

D-1533B
D-971
D-974

Fluid: MIN

Gallons: 106350

6035991
08/07/2009
307210
38

Hydrogen (H2):
Methane (CH4):
Ethane (C2H6):
Ethylene (C2H4):
Acetylene (C2H2):
Carbon Monoxide (CO):
Carbon Dioxide (CO2):
Nitrogen (N2):
Oxygen (O2):
Total Dissolved Gas:
Total Dissolved Combustible Gas:
Equivalent TCG Percent:

22
7
9
5
0
22
725
77292
1267
79349
65
0.0721

Moisture in Oil
Interfacial Tension
Acid Number

(ppm):
(dynes/cm):
(mg KOH/g):

4
40.4
0.006

D-1500
D-1524
D-1524
D-877
D-1816
D-1816
D-924
D-924
D-1298

Color Number
Visual Exam.
Sediment Exam.
Dielectric Breakdown
Dielectric Breakdown 1 mm
Dielectric Breakdown 2 mm
Power Factor @ 25C
Power Factor @ 100C
Specific Gravity

(Relative):
(Relative):
(Relative):
(kV):
(kV mm-C):
(kV mm-C):
(%):
(%):
(Relative):

L.5
CLR&SPRK
ND
48

WDS
D-2668

Passivator
Oxidation Inhibitor

(ppm):
(wt. %):

(Most recent sample)

DGA Rogers Ratio Method:


DGA Cellulose (Paper) Insulation:
DGA IEEE/ANSI (C57.104-1991):

Imp.(% Z):
Container: R465 3 3 3

Lab Control Number:


Date Sampled:
Order Number:
Oil Temp.(C):

DGA Key Gas / Interpretive Method:


IEEE (C57.104)

Diagnostics

KVA: 15000

Project ID:

Account: 67
Order #: 307210
Control #: 6035991
Received: 08/10/2009
Reported: 08/20/2009
Customer ID:

0.013
0.524
0.885
< 0.020
Hydrogen within condition 1 limits (100 ppm).
Acetylene within condition 1 limits (2 ppm).
Ethylene within condition 1 limits (50 ppm).
Carbon Monoxide within condition 1 limits (350 ppm).
Overall equipment condition code: 1.

Analyzed gases do not exceed warning thresholds. Rogers Ratios do not apply.
CO2/CO Ratio not applicable - neither gas exceeds its limit.
No previous sample available.

(Two most recent samples)

Moisture in Oil:
Interfacial Tension:
Acid Number:
Color Number and Visual:

Acceptable for in-service oil (35 ppm max).


Acceptable for in-service oil (25 dynes/cm min).
Acceptable for in-service oil (0.2 mg KOH/g max).
Color Number diagnostic not applicable. Visual diagnostic not applicable.

Dielectric Breakdown D-877:


Dielectric Breakdown D-1816:

Acceptable for in-service oil (26 kV min).

Power Factor @ 25C:


Power Factor @ 100C:
Oxidation Inhibitor:

Acceptable for in-service oil (0.5% max).


Acceptable for in-service oil (5% max).
Diagnostic not applicable for Type I. Exceeds limit for in-service oil Type II (0.09% min).

The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same as
all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. Weidmann
Diagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for
any reason whatsoever.

A Member of the WICOR Group

WEIDMANN DIAGNOSTIC SOLUTIONS


8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM
Location: LUFKIN

Mfr: COOPER

Serial #: C0725651LTC
Bank/Ph:

HOUSTON, TX

Fluid: MIN

Lab Control Number:


Date Sampled:
Order Number:
Oil Temp.(C):

Container: 3A 3A 3A
Gallons: 190

Project ID:

Account: 67
Order #: 307210
Control #: 6036005
Received: 08/10/2009
Reported: 08/20/2009
Customer ID:

6036005
08/07/2009
307210

Dissolved Gas Analysis

Hydrogen (H2):
Methane (CH4):
Ethane (C2H6):
Ethylene (C2H4):
Acetylene (C2H2):
Carbon Monoxide (CO):
Carbon Dioxide (CO2):
Nitrogen (N2):
Oxygen (O2):
Total Dissolved Gas:
Total Dissolved Combustible Gas:
Equivalent TCG Percent:
D-1533B
D-971
D-974

Oil Screen

Imp.(% Z):

Breathing: SEAL

PO #:

ASTM D-3612
Report Units: PPM

KVA:

Tank: LTC

ATTN:

KV:

Moisture in Oil
Interfacial Tension
Acid Number

(ppm):
(dynes/cm):
(mg KOH/g):

D-1500
D-1524
D-1524
D-877
D-1816
D-1816
D-924
D-924
D-1298

Color Number
Visual Exam.
Sediment Exam.
Dielectric Breakdown
Dielectric Breakdown 1 mm
Dielectric Breakdown 2 mm
Power Factor @ 25C
Power Factor @ 100C
Specific Gravity

WDS
D-2668

Passivator
Oxidation Inhibitor

25
46.1
0.003

(Relative):
L.5
(Relative):
CLR&SPRK
(Relative): PARTICULATES
(kV):
35
(kV mm-C):
(kV mm-C):
(%):
(%):
(Relative):
(ppm):
(wt. %):

DGA Key Gas / Interpretive Method:


IEEE (C57.104)

Diagnostics

(Most recent sample)

Moisture in Oil:
Interfacial Tension:

Acceptable for equipment > 69 kV for in-service oil - kV not provided (25 ppm max).
Diagnostic not applicable.

Acid Number:
Color Number and Visual:

Diagnostic not applicable.

Dielectric Breakdown D-877:


Dielectric Breakdown D-1816:

Diagnostic not applicable.

Color Number diagnostic not applicable. Visual diagnostic not applicable.

Power Factor @ 25C:


Power Factor @ 100C:
Oxidation Inhibitor:
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same as
all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. Weidmann
Diagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for
any reason whatsoever.

A Member of the WICOR Group

WEIDMANN DIAGNOSTIC SOLUTIONS


8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM

Furanic Compounds in Electrical Insulating Liquids by HPLC


ASTM D-5837 Report
Location: LUFKIN

Mfr: COOPER

Serial #: C0725651
Bank/Ph: 3

HOUSTON, TX

Fluid: MIN

Control #: 6035991

Imp.(% Z):

Breathing: SEAL

PO #:

Order #: 307210

KVA: 15000

Tank: TRANSFORMER

ATTN:

Account: 67

KV: 13.2/7.62

Received: 08/10/2009

Container: R465 3 3 3
Gallons: 106350

Project ID:

Reported: 08/20/2009
Customer ID:

Results:
Furanic Compound

Result (ppb)

Reporting Limit (ppb)

2-Furaldehyde

< 10

10

5-Hydroxy-methyl-furaldehyde

< 10

10

2-Acetylfuran

< 10

10

5-Methyl-2-furaldehyde

< 10

10

2-Furyl alcohol

< 10

10

* BRL = Below Reporting Limit

Diagnostics:
New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) of 1000-1300. "Middle Aged" paper is
approximately 500 and paper with less than 250 is in its "Old Age". Severely degraded insulation with a DP of 150 or less will have very little mechanical
strength and may result in a transformer failure. The following estimations are based on current research of GSU transformers filled with mineral oil.
Estimated Degree of Polymerization (DP): >1003
Estimated Operating Age of the Equipment: <1.0

Notations:

QC Chemist: CN
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does not
imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate
only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. Weidmann Diagnostic
Solutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or
other property for which this report may be used or relied upon for any reason whatsoever.

A Member of the WICOR Group

OMICRON FRAnalyzer 2.0

Tester:

jboney

Date / Time:

7/20/2011 09:31:02 AM

Location:

2217 Aldine Bender Rd

Oil Temperature:

35 C / 95 F

Comment:

Transformer
Serial Number:

C-07258-5-1

Manufacturer:

Cooper

Type Code:
Year:

1991

Location:

Canonsburg PA

Number:
MVA Rating:

1.7E-05MVA

High Voltage:

132kV

Low Voltage:

7.62kV

Tertiary Voltage:

0kV

Phases:

Vector Group:

Dyn0

Test Traces
Name
H1 H2
H2 H3
H3 H1
x0 x1
x0 x2
x0 x3

Date/Time
7/20/2011 09:01:46 AM
7/20/2011 09:08:17 AM
7/20/2011 09:14:01 AM
7/20/2011 09:25:22 AM
7/20/2011 09:28:53 AM
7/20/2011 09:31:02 AM

7/20/2011 9:49:35 AM

Red
H1
H2
H3
x0
x0
x0

Blue
H2
H3
H1
x1
x2
x3

Tap Changer
3
3
3
3
3
3

Tertiary
closed
closed
closed
closed
closed
closed

Other
shorted +
shorted +
shorted +
shorted +
shorted +
shorted +

1/4

OMICRON FRAnalyzer 2.0

Sweep Settings
Start Frequency:

20 Hz

Stop Frequency:

2 MHz

Sweep Mode:

see customized frequency ranges

Points / Sweep:

1000

Receiver Bandwidth:

<adapt automatically>

Attenuator:

<adapt automatically>

Input Impedance:

50

Customized Frequency Ranges:


From Frequency

To Frequency

Sweep Mode

Points

20 Hz

100 Hz

logarithmic

50

100 Hz

1 kHz

logarithmic

210

1 kHz

10 kHz

logarithmic

210

10 kHz

100 kHz

logarithmic

210

100 kHz

1 MHz

logarithmic

210

1 MHz

2 MHz

logarithmic

110

7/20/2011 9:49:35 AM

2/4

Device
DK241K
DK241K
DK241K
DK241K
DK241K
DK241K

7/20/2011 9:49:35 AM

3/4

S-ar putea să vă placă și