Documente Academic
Documente Profesional
Documente Cultură
DC551CS31CS31BusModule
CS31BusModuleDC551CS31withDigitalInputsandOutputs
8digitalinputs24VDC,16configurabledigitalinputs/outputs
Modulewiseelectricallyisolated
FastCounter
XCversionforusageinextremeambientconditionsavailable
Elementsofthemodule
1
I/OBus
AllocationbetweenterminalNo.andsignalname
8yellowLEDstodisplaythesignalstatusesofthedigitalinputsI0to
I7
16yellowLEDstodisplaythesignalstatusesofthedigital
inputs/outputsC8toC23
2rotaryswitchestosetthemodule'saddress(00dto99d)
1greenLEDtodisplaytheprocessvoltageUP
3redLEDstodisplayerrors
4SystemLEDs
Label
10
CS31BusTerminalUnit(TU551CS31orTU552CS31)with40
terminals(screwtypeorspringterminals)
11
DINrail
SignforXCversion
Figure:CS31BusModuleDC551CS31,pluggedonaCS31BusTerminalUnitTU552CS31
Contents
IntendedPurpose
Functionality
ElectricalConnection
CS31BusConnections
InternalDataExchange
Addressing
DC551CS31Limitations
I/OConfiguration
Parameterization
StructureoftheDiagnosisBlockoftheDC551CS31
DiagnosisandDisplay
TechnicalData
TechnicalDataoftheEntireModule
TechnicalDataoftheDigitalInputs
TechnicalDataofConfigurableDigitalInputs/Outputs
TechnicalDataoftheFastCounter
OrderingData
IntendedPurpose
Important:Currently,theCS31BusModuleDC551CS31canonlybeusedtogetherwiththeAC500CPUsanddedicatedPS501ControlBuilder.
TheCS31BusModuleisusedasadecentralizedI/OmoduleonCS31fieldbuses.ThebusconnectionisperformedonaRS485serialinterface,whichallowstheconnectionofthis
moduletoallexistingCS31buses.Inaddition,theCS31BusModuleprovides24I/Ochannelswiththefollowingproperties:
8digitalinputs24VDCinonegroup(2.0...2.7)
16digitalinputs/outputsinonegroup(3.0...4.7),ofwhicheachcanbeused
asaninput,
asatransistoroutputwithshortcircuitandoverloadprotection,0.5Aratedcurrentor
asarereadableoutput(combinedinput/output)withthetechnicaldataofthedigitalinputsandoutputs.
Theinputsandoutputareelectricallyisolatedfromtheotherelectroniccircuitryofthemodule.
Forusageinextremeambientconditions(e.g.widertemperatureandhumidityrange),aspecialXCversionofthedeviceisavailable.
Functionality
Interface
RS485,CS31protocol
Supplyofthemodule'selectroniccircuitry
FromUPandZP(powersupply)
SupplyoftheelectroniccircuitryoftheI/Oexpansionmodules
Throughtheexpansionbusinterface(I/OBus)
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
1/10
3/19/2015
DC551CS31CS31BusModule
attached
Addressswitches
ForsettingtheCS31fieldbusaddress(0to99)
Digitalinputs
8(24VDC)
Digitalinputs/outputs
16(24VDC)
FastCounter
Integrated,manyconfigurableoperatingmodes
LEDdisplays
Forsystemdisplays,signalstatuses,errorsandpowersupply
Externalsupplyvoltage
ViatheterminalsZPandUP(processvoltage24VDC)
ElectricalConnection
TheCS31BusModuleispluggedontheCS31TerminalUnitTU551orTU552.Hereby,itclicksinwithtwomechanicallocks.TheTerminalUnitismountedonaDINrailorwith2
screwsplustheadditionalaccessoryforwallmounting(TA526).
TheelectricalconnectionoftheI/Ochannelsiscarriedoutusingthe40terminalsoftheCS31TerminalUnit.Itispossible,toreplaceCS31BusModulesandI/Omoduleswithout
looseningthewiring.
Note:Mounting,disassemblingandelectricalconnectionfortheTerminalUnits,theFBPInterfaceModulesandtheI/OmodulesaredescribedindetailintheS500System
Datachapters.
Theterminals1.8to4.8and1.9to4.9areelectricallyinterconnectedwithintheCS31BusTerminalUnitandhavealwaysthesameassignment,independentoftheinsertedmodule:
Terminals1.8to4.8:ProcessvoltageUP=+24VDC
Terminals1.9to4.9:ProcessvoltageZP=0V
Theassignmentoftheotherterminals:
Terminals
Signal
Meaning
1.0to1.7
RS485
CS31businterface
2.0to2.7
I0toI7
8digitalinputs
3.0to4.7
C8toC23
16digitalinputs/outputs
Thesupplyvoltage24VDCforthemodule'selectroniccircuitrycomesfromtheZP/UPterminals.
Themoduleprovidesseveraldiagnosisfunctions(seechapterDiagnosisandDisplay).
Caution:Removalofenergizedmodulesisnotpermitted.Allpowersources(supplyandprocessvoltages)mustbeswitchedoffwhileworkingonanyAC500system.
ThefollowingfigureshowstheelectricalconnectionoftheCS31BusModuleDC551CS31.
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
2/10
3/19/2015
DC551CS31CS31BusModule
Figure:ElectricalconnectionoftheCS31BusModuleDC551CS31
CS31BusConnections
TheCS31busisconnectedthroughtheTerminalUnitwiththeterminals1.0to1.7.Theendoflineresistorcanalsobeactivatedbyusingexternalwirejumpers.
ThefollowingfigureshowsaCS31BusmoduleattheendoftheCS31Bus(endoflineresistoractivated).
Figure:CS31BusmoduleattheendoftheCS31Bus
ThefollowingfigureshowsaCS31BusmoduleinthemiddleofaCS31Bus(endoflineresistornotactivated).
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
3/10
3/19/2015
DC551CS31CS31BusModule
Figure:CS31BusmoduleinthemiddleoftheCS31Bus
InternalDataExchange
withouttheFastCounter
withtheFastCounter(onlywithAC500)
Digitalinputs(bytes)
3+expansionmodules(seeabove)
5+expansionmodules(seeabove)
Digitaloutputs(bytes)
2+expansionmodules(seeabove)
4+expansionmodules(seeabove)
Counterinputdata(words)
5(16DI+4AI)
Counteroutputdata(words)
9(16DO+8AO)
Addressing
Anaddressmustbesetateverymodulesothatthefieldbuscommunicationmodulecanaccessthespecificinputsandoutputs.
Adetaileddescriptionconcerning"addressing"canbefoundinthechaptersAddressingoftheCPUsandCommunicationModules.
Theaddress(00to99)issetwithtworotaryswitchesonthefrontpanelofthemodule.
Remark:TheCS31BusModulereadsthepositionoftheaddressswitchesonlyduringtheinitializationafterpowerON,i.e.changesofthesettingduringoperationremainineffective.
DC551CS31Limitations
DigitalI/O:
DC551CS31isabletomanageupto240digitalI/Ochannels.Ituses2digitalbusaddressesinthiscase.
ThephysicaladdresstoidentifytheI/Ois
addressn(switchaddress)forthe1stmodule(120I/O)
addressn+7+bit8/15=1forthe2ndmodule
TobecompatiblewitholdCPUandEC500usingthisphysicaladdress,toaddressI/Oinuserprogram:Useonly6expansionswith32DI.
AnalogI/O:
Analoglimitationto40AI/AOwith4busaddressesused.
CaseofDC551CS31withFastCounter:
Anadditionalbusaddressisusedfor"doubleword"valuesoftheFastCounter.
Themaximumconfigurationisshowninthefollowingtable.
DC551CS31
8DI+16DC
+counter
16AI
16AI
DC532
DC532
DC532
DC532
DC532
Thefollowingconfigurationuses7busaddresses(theFastCounterneeds16DI+16DO+4AI+8AO):
2busaddressesfordigitalI/O(24+16+5x32)DI+(16+16+5x16)DO=200DI(>120)+112DO
5busaddressesforanalogI/O(4+2x16)AI+8AO=36AI+8AO
Smalloverviewoftheaddressingpossibilities
Configurationexamplewith32analoginputswithorwithout32analogoutputs(FastCounternotused)=5busaddressesbythebusmodule
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
4/10
3/19/2015
DC551CS31CS31BusModule
Ifthenumberofanalogoutputsislessthanthenumberofanaloginputs,noadditionaladdressisnecessary.Changethetypefrom"analogin"to"analogI/O".
30busaddressesused,1busaddressfree
192analoginputs(+192analogoutputs)
48DI/96DC(144DI/96DOforCS31anduserprogram)
Switchaddressincrementedtoavoidcontroloverlap.
InCPUtablemoduleswitchaddressnwillbeseenas(idemforAC500oroldCPU):
Addressn,typedigitalI/O,8DI/16DC
Addressn,typeanalogIorI/O,8AI(+8AO)
Addressn+bit8/15=1,typeanalogIorI/O,8AI(+8AO)
Addressn+1,typeanalogIorI/O,8AI(+8AO)
Addressn+1+bit8/15=1,typeanalogIorI/O,8AI(+8AO)
OnlydifferenceinoldCPUI/Ochannelsarestored/updatedaccordingtotheswitchaddress.
InAC500accordingtoCoDeSysconfigurationtable.
I/OConfiguration
TheDC551CS31moduledoesnotstoreconfigurationdataitself.The16configurablechannelsaredefinedasinputsoroutputsbytheuserprogram,i.e.eachoftheconfigurable
channelscanbeusedasinputoroutput(orrereadableoutput)byinterrogationorallocationbytheuserprogram.
Parameterization
Duringsystemstartup,themastercommunicationmoduleautomaticallysendsparameterdatatotheslave.
WhenthemoduleisdefinedinCoDeSys:
ParametersareinCoDeSysandcanbeadaptedtoapplicationbeforetransferinPLC.ThenparameterswillbesenttoDC551CS31whenthemoduleconnectsorreconnectsthe
bus.
ByusingthePLCConfigurator:
DefinitionofCS31MastercommunicationonCOM1,appendofthe1stDC551CS31slavemodule:
TheDC551CS31isnowattachedtotheCOM1:
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
5/10
3/19/2015
DC551CS31CS31BusModule
TheonboardI/OsaredisplayedandautomaticallyknownbytheAC500ControlBuilder.TheI/Oaddressingisautomaticallyperformedasforanyothermodules.
Thebusaddressofthemodule,usedafterthatbyAC500MasterCS31,canbeadaptedtothosesetonthemodulerotaryswitches.
Attention:TheAC500PS501ControlBuilderdoesnotcontrolthevalidity/integrityoftheenteredCS31Busaddressvalueduringtheconfiguration!Thecontrolisdone
duringprojectcompilation,thendownloadedintotheCPUandafterstartingtheCPU.
TheattachedexpansionsmodulesoftheDC551CS31areperformedaslocalexpansionsbyclickingwiththerightmousebuttonontotheDC551CS31busmoduleandusingAppend
Subelement.Seeabove:
TheDC532isaddedasalocalexpansiontotheDC551CS31Busmodule:
Attention:Becareful,theAC500PS501ControlBuilderdoesnotcontrolthevalidity/integrityofamountofexpansionsconfigured(acc.toI/Olimitations)duringthe
configuration!Thecontrolisdoneduringprojectcompilation,thendownloadedintotheCPUandafterstartingtheCPU.
ExampleofaCS31busconfigurationwith2DC551CS31slaves:
forEC500:Specialfunctionsmustbeaddedintheuserprogram
forSeries90:=>useoldCS31CO(write4bytes)orterminalcommandMAIL(write4bytes).
(foroldCPU1timeconfigurationhavebeenloaded=>acommandrestoreconfigfromEEPROMbyCS31COcanbeusedtoavoidresendcompletetable)
ThearrangementoftheparameterdataisperformedbytheControlBuildersoftware.
Theparameterdatadirectlyinfluencesthefunctionalityofmodules.
Fornonstandardapplications,itisnecessarytoadapttheparametersintoyoursystemconfiguration.
Module:
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
6/10
3/19/2015
DC551CS31CS31BusModule
Nr.
Name
Value
Internal
value
Internal
value,type
Default
Min.
Max.
ModuleID
Internal
2715
*1)
Word
2715
0x0a9b
65535
Ignoremodule
No
Yes
0
1
Byte
No
0x00
14
Parameterlength
Internal
8
(7*4)
Byte
8
(7*4)
255
16
Checksupply
Off
on
0
1
Byte
On
0x01
17
Inputdelay
0.1ms
1ms
8ms
32ms
0
1
2
3
Byte
8ms
0x02
18
Fastcounter
0
:
10*3)
0
:
10
Byte
Mode0
0x00
Nr.+1
Detectionshortcircuitatoutputs
off
on
0
1
Byte
on
0x01
Nr.+1
Behaviouroutputsatcommunication
errors
Off
Lastvalue
Substitutevalue
0
1
2
Byte
off
0x00
Nr.+1
Substitutevalueoutputs
Bit15=Output15
Bit0=Output0
0...65535
0...0xffff
Word
*1)WithCS31andaddresseslessthan70,thevalueisincreasedby1
*3)Counteroperatingmodes,seedescriptionoftheFastCounter
*4)WithCS31andaddresseslessthan70,withouttheparameterFastcounter
StructureoftheDiagnosisBlockoftheDC551CS31
IfaDC551CS31moduleisconnectedviaaCS31bus,thenthefieldbusmasterreceivesdiagnosisinformationbyanextendeddiagnosisblock.Thefollowingtableshowsthe
structureofthisdiagnosisblock:
Byte
number
Description
Possiblevalues
Datalength(headerincluded)
18
Diagnosisbyte
0=CommunicationwithDC551CS31OK
1=CommunicationwithDC551CS31failed
DC551CS31diagnosisbyte,modulenumber
0=DC551(e.g.errorattheintegrated8DI/16DC)
1=1stattachedS500I/Omodule
...
7=7thattachedS500I/Omodule
DC551CS31diagnosisbyte,slot
AccordingtotheI/OBusspecification
passedonbymodulestothefieldbusmaster
DC551CS31diagnosisbyte,channel
AccordingtotheI/OBusspecification
passedonbymodulestothefieldbusmaster
DC551CS31diagnosisbyte,errorcode
AccordingtotheI/OBusspecification
Bit7andbit6,codederrorclass
0=E1
1=E2
2=E3
3=E4
Bit0toBit5,codederrordescription
passedonbymodulestothefieldbusmaster
DC551CS31diagnosisbyte,flags
AccordingtotheI/OBusspecification
Bit7:1=comingerror
Bit6:1=leavingerror
Bit5:1=Diagreset
Bit2toBit4:reserved
Bit1:1=explicitacknowledgement
Bit0:1=staticerror
passedonbymodulestothefieldbusmaster
Value=0:staticmessageforothersystems,whichdonothaveacoming/leaving
evaluation
8ff
reserved
DiagnosisandDisplay
Incaseofoverloadorshortcircuit,theoutputsswitchoffautomaticallyandtrytoswitchonagaincyclically.Thereforeanacknowledgementoftheoutputsisnotnecessary.TheLED
errormessage,however,isstored.
Diagnosis:
E1..E4
d1
Class
Comp
Dev
Mod
Ch
Byte3
Byte4
Byte5
Byte6
d2
d3
d4
Identifier
000..063
Err
Byte6
AC500display
PS501PLCbrowser
<Displayin
FBPdiagnosisblock
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
7/10
3/19/2015
DC551CS31CS31BusModule
Bit6..7
Bit0..5
Class
Inter
face
De
vice
Mod
ule
Chan
nel
2)
3)
4)
1)
Error
identifier
Errormessage
Remedy
ModuleerrorDC551CS31
3
11
ADR
31
31
19
ChecksumerrorintheI/Omodule
11
ADR
31
31
TimeoutintheI/Omodule
11
ADR
31
31
40
Differenthard/firmwareversionsinthemodule
11
ADR
31
31
43
Internalerrorinthemodule
11
ADR
31
31
36
Internaldataexchangefailure
11
ADR
31
31
Overflowdiagnosisbuffer
Newstart
11
ADR
31
31
26
Parametererror
Checkmaster
11
ADR
31
31
11
Processvoltagetoolow
Checkprocess
voltage
11
ADR
1...7
31
17
NocommunicationtotheI/Omodule
ReplaceI/O
module
11
ADR
31
31
45
ProcessvoltageON/OFF
Processvoltage
ON
11
ADR
31/1..7
31
34
NoreplyatinitializationoftheI/Omodule
ReplaceI/O
module
11
ADR
31/1.7
31
32
WrongI/Omoduleintheslot
ReplaceI/O
moduleorcheck
configuration
11
ADR
31/1..7
8..23
Shortcircuitatadigitaloutput
Check
connection
ReplaceI/O
module
ChannelerrorDC551CS31
47
Remarks:
1)
InAC500thefollowinginterfaceidentifierapplies:
11=COM1(protocolCS31busonlypossiblewithCOM1)
2)
With"Device"andCS31busmaster,thehardwareaddressoftheDC551CS31(0...69)isoutput.
3)
With"Module"thefollowingallocationapplies:
31=Moduleitself,1...7=Expansion1...7
4)
Incaseofmoduleerrors,withchannel"31=Moduleitself"isoutput.
Displays:
TheLEDsareonthefrontpanelsofthemodules.Therearetwodifferentgroups:
The4systemLEDs(PWR,SERR,CS31andI/OBus)showtheoperatingstatusofthemoduleandindicatepossibleerrors.
The28processLEDs(UP,inputs,outputs,CHERR2toCHERR4)displaythesupplyvoltageandsignalstatusesoftheinputsandoutputsandindicatepossibleerrors.
AlloftheS500moduleshaveLEDstodisplayoperatingstatusesanderrors.
StatusoftheLEDs:
LED
Status
Color
LED=OFF
LED=ON
LEDflashes
PWR
Systemvoltage
green
Missinginternalsystemvoltageor
fieldbussupplyismissing
InternalsystemvoltageisOK
CS31
CS31communication
green
NocommunicationattheCS31
busmodule
CommunicationattheCS31bus
OK
Diagnosismode
SERR
SumError
red
Noerrororsystemvoltageis
missing
Internalerror(storingcanbe
parameterized)
I/OBus
Communicationviathe
I/OBus
green
Noexpansionmodulesconnected
ordataerror
Expansionmodulesconnected
ErrorI/OBus
Reserved
Notdefined
I0...I7
Digitalinputs
yellow
Input=OFF
Input=ON(theinputvoltageis
evendisplayedifthesupply
voltageisOFF)
C8...C23
Digitalinputs/outputs
yellow
Input/output=OFF
Input/output=ON(theinput
voltageisevendisplayedifthe
supplyvoltageisOFF)
UP
Processsupplyvoltage
andinitialization
green
Processvoltageismissing
ProcessvoltageOK
CHERR2
red
Noerror
Seriouserrorwithinthe
correspondinggroup
Errorononechannelofthe
correspondinggroup(e.g.
shortcircuitatanoutput)
CHERR4
ChannelError,error
messagesingroups
(digitalinputs/outputs
combinedintothegroups
2to4)
CHERR*)
ModuleError
red
Noerrororprocessvoltageis
missing
Internalerror
CHERR3
red
red
*)AllLEDsCHERR2toCHERR4lightuptogether
ThestatusoftheLEDsconcerningtheCS31BusModuleinconnectionwiththeI/OexpansionmodulesisdescribedindetailintheS500systemdata.
TechnicalData
TheSystemDataofAC500andS500arevalidforstandardversion.
TheSystemDataofAC500XCarevalidfortheXCversion.
Onlyadditionaldetailsarethereforedocumentedbelow.
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
8/10
3/19/2015
DC551CS31CS31BusModule
TechnicalDataoftheEntireModule
Ratedsupplyvoltageofthemodule
24VDC(UP/ZP)
Currentconsumptionofthemodule(UP)
15mA
ProcessvoltageUP
Ratedvalue
24VDC(forinputsandoutputs)
Max.currentloadabilityforthesupplyterminals
10A
Protectionagainstreversedvoltage
Yes
RatedprotectionfuseatUP
10Afast
Electricalisolation
CS31businterfacefromtherestofthemodule
InrushcurrentfromUP(atpowerup)
0.040As
CurrentconsumptionfromUPatnormaloperation/with
outputs
0.1A+max.0.008Aperinput+max.0.5Aperoutput
Connections
Terminals1.84.8for+24V(UP)and1.94.9for0V(ZP)
Max.powerdissipationwithinthemodule
6W(outputsunloaded)
Numberofdigitalinputs
Numberofconfigurabledigitalinputs/outputs
16
Referencepotentialforalldigitalinputsandoutputs
Minuspoleofthesupplyvoltage,signalnameZP
Addresssetting
With2rotaryswitchesonthefrontpanel
Diagnosis
SeechapterDiagnosisandDisplays
Operatinganderrordisplays
32LEDsaltogether
Weight(withoutTerminalUnit)
Ca.125g
Mountingposition
Horizontal
Orverticalwithderating(outputloadreducedto50%at40Cpergroup)
Cooling
Thenaturalconvectioncoolingmustnotbehinderedbycableductsorotherpartsintheswitchgear
cabinet.
Attention:AllI/Ochannels(digitalandanalog)areprotectedagainstreversepolarity,reversesupply,shortcircuitandcontinuousovervoltageupto30VDC.
TechnicalDataoftheDigitalInputs
Numberofchannelspermodule
Distributionofthechannelsintogroups
1groupof8channels
TerminalsofthechannelsI0toI7
2.0to2.7
TerminalsofthechannelsC8toC23
3.0to4.7
Referencepotentialforallinputs
Terminals1.9...4.9(Minuspoleoftheprocesssupplyvoltage,signalnameZP)
Electricalisolation
FromtheCS31systembus
Indicationoftheinputsignals
1yellowLEDperchannel,theLEDisONwhentheinputsignalishigh(signal1)
Inputtypeacc.toEN611312
Type1
Inputdelay(0>1or1>0)
Typ.8ms,configurablefrom0.1to32ms
Inputsignalvoltage
24VDC
Signal0
3V...+5V
Undefinedsignal
>+5V...<+15V
Signal1
+15V...+30V
Ripplewithsignal0
Within3V...+5V
Ripplewithsignal1
Within+15V...+30V
Inputcurrentperchannel
Inputvoltage+24V
Typ.5mA
Inputvoltage+5V
>1mA
Inputvoltage+15V
>2mA
Inputvoltage+30V
<8mA
Max.cablelength
Shielded
1000m
Unshielded
600m
TechnicalDataoftheConfigurableDigitalInputs/Outputs
EachoftheconfigurableI/Ochannelsisdefinedasinputoroutputbytheuserprogram.Thisisdonebyinterrogatingorallocatingthecorrespondingchannel.
Numberofchannelspermodule
16inputs/outputs(withtransistors)
Distributionofthechannelsintogroups
1groupof16channels
Ifthechannelsareusedasinputs
ChannelsI8...I23
Ifthechannelsareusedasoutputs
ChannelsQ8...Q23
Terminals3.0...4.7
Terminals3.0...4.7
Indicationoftheinput/outputsignals
1yellowLEDperchannel,theLEDisONwhentheinput/outputsignalishigh(signal1)
Electricalisolation
FromtheCS31systembus
Technicaldataofthedigitalinputs/outputsifusedasoutputs
Numberofchannelspermodule
Max.16transistoroutputs
Referencepotentialforalloutputs
Terminals1.9...4.9(minuspoleoftheprocesssupplyvoltage,signalnameZP)
Commonpowersupplyvoltage
Foralloutputs:terminals1.8...4.8(pluspoleoftheprocesssupplyvoltage,signalnameUP)
Outputvoltageforsignal1
UP(0.8V)
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
9/10
3/19/2015
DC551CS31CS31BusModule
Outputdelay(0>1or1>0)
Onrequest
Outputcurrent
Ratedvalue,perchannel
500mAatUP=24V
Maximumvalue(allchannelstogether)
10A
Leakagecurrentwithsignal0
<0.5mA
RatedprotectionfuseonUP
10Afast
Demagnetizationwheninductiveloadsareswitchedoff
Withvaristorsintegratedinthemodule(seefigurebelow)
Switchingfrequency
Withresistiveloads
Onrequest
Withinductiveloads
Max.0.5Hz
Withlamploads
Max.11Hzwithmax.5W
Shortcircuitproof/overloadproof
Yes
Overloadmessage(I>0.7A)
Yes,afterca.100ms
Outputcurrentlimitation
Yes,automaticreactivationaftershortcircuit/overload
Resistancetofeedbackagainst24Vsignals
Yes
Max.cablelength
Shielded
1000m
Unshielded
600m
Thefollowingdrawingshowsthecircuitryofadigitalinput/outputwiththevaristorsfordemagnetizationwheninductiveloadsareswitchedoff.
Figure:Digitalinput/output(circuitdiagram)
Technicaldataofthedigitalinputs/outputsifusedasinputs
Numberofchannelspermodule
Max.16digitalinputs
Referencepotentialforallinputs
Terminals1.9...4.9(minuspoleoftheprocesssupplyvoltage,signalnameZP)
Inputcurrent,perchannel
SeeTechnicalDataoftheDigitalInputs
Inputtypeacc.toEN611312
Type1
Inputdelay(0>1or1>0)
Typ.8ms,configurablefrom0.1to32ms
Inputsignalvoltage
24VDC
Signal0
3V...+5V*
Undefinedsignal
>+5V...<+15V
Signal1
+15V...+30V
Ripplewithsignal0
within3V...+5V*
Ripplewithsignal1
within+15V...+30V
Max.cablelength
Shielded
1000m
Unshielded
600m
*Duetothedirectconnectiontotheoutput,thedemagnetizingvaristorisalsoeffectiveattheinput(seefigure)above.ThisiswhythedifferencebetweenUPxandtheinputsignal
maynotexceedtheclampvoltageofthevaristor.Thevaristorlimitsthevoltagetoapprox.36V.Followingthis,theinputvoltagemustrangefrom12Vto+30VwhenUPx=24V
andfrom6Vto+30VwhenUPx=30V.
TechnicalDataoftheFastCounter
Usedinputs
C16/C17
Usedoutputs
C18
Countingfrequency
Max.50kHz
Detaileddescription
SeechapterFastCounter
Operatingmodes
SeechapterFastCounter,Operatingmodes
OrderingData
OrderNo.
Scopeofdelivery
1SAP220500R0001
DC551CS31,CS31BusModule,8DI/16DC
1SAP420500R0001
DC551CS31XC,CS31BusModule,8DI/16DC,XCversion
1SAP210600R0001
TU551CS31,CS31BusI/OTerminalUnit,screwtypeterminals
1SAP210400R0001
TU552CS31,CS31BusI/OTerminalUnit,springtypeterminals
1SAP410400R0001
TU552CS31XC,CS31BusI/OTerminalUnit,springtypeterminals,XCversion
Copyright20052012ABB.Allrightsreserved.DocumentationRevisionV2.2.0Dateofissue:20120508
http://www.vaeprosys.cz/dokumentace/ac500/English/CHMFiles/CAAMerger2/S500FBP/Bus_Modules/CS31/DC551.htm
10/10