Ri Main

Ring
M i Unit
U it

FOTO

RMSYS
1224kV630A

Generalities
RMSYS is a monobloc switchboard with stainless steel tank containg all the live parts and
switching functions.
functions
The switchboard includes inside three position rotary switch-disconnectors for the line, and
vacuum circuit breaker or fuses for the transformers.
The equipment is mounted on a frame full of curtain panels. A safety valve ensures safety
in case of failure to overpressure of the container, in accordance with the Standard IEC
60694.
In the structure is derived rooms, one for each line, for the cable installation.

Employment
The RMSYS switchboard is designed for use in secondary distribution networks, public or
private, with voltages up to 24kV. The switchboard is also suitable to protect and shunt
station feeders with three position rotary switch disconnector ( in manual or motorized
version); bind together switch-disconnector function and earthing switch function.

Electric characteristics of the switchboard


Rated voltage

kV

12

24

Rated power-frequency withstand voltage 50Hz 1Min (kV r.m.s.)

kV

28 (42)*

50 (65)*

Rated lighting impulse withstand voltage (peak value)

kV

75 (95)*

125
(125)*

Rated current

630

630

Short-time withstand current (rms)

kA

20 3s
25 1s

16 3s
20 3s

kA

50
62,5

40
50

Mainly active load

630

630

Earth leakage fault

95

95

No load cables

30

30

No load transformers

16

16

Making capacity

Breaking capacity

* Data for the Russian market in accordance with rules Gost

S it hb d configuration
Switchboard
fi
ti
Typical diagrams

AF

1 Cable connection + 1 Transformer feeder combined fuse-switch

IIF

2 Incoming/Outgoing switch + 1 Transformer feeder combined fuse-switch

IIIF

3 Incoming/Outgoing + 1 Transformer feeder combined fuse-switch

IFIF

2 Incoming/Outgoing + 2 Transformer feeder combined fuse-switch

AV

1 Cable connection + 1 Line feeder 630 A - Vacuum circuit breaker

IIV

2 Incoming/Outgoing + 1 Line feeder 630 A - Vacuum circuit breaker

IIIV

3 Incoming/Outgoing + 1 Line feeder 630 A - Vacuum circuit breaker

IVIV

2 Incoming/Outgoing +2 Line feeder 630 A - Vacuum circuit breaker

Tipical diagrams

AF

IIF

IIIF

IFIF

INC./OUTGOING SWITCH

TRANSFORMER FEEDER COMBINED FUSE-SWITCH

ACCESSORIES

composed of:
- KS operating mechanism
- Earth switch
-Voltage
Voltage indicators

composed of:
- KP operating mechanism
- Tripping coil
Automatic tripping device when fuse blow-up
blow up
-Automatic
- 3 striker fuses
- Earth switch at the top and at the bottom of the fuses
- Voltage indicators

-Motor operating mechanism


for network switch
- Auxiliary contacts
- Auxiliary contacts for fuse blow-up
blow up
- Key interlocks

AV

IIV

IIIV

IVIV

INC./OUTGOING SWITCH

LINE FEEDER 630A CIRCUIT BREAKER

ACCESSORIES

composed of:
- KS operating mechanism
- Earth switch
-Voltage
Voltage indicators

composed of:
- Tripping coil
- 3 toroidal current reducer
- 1 overcurrent relay 50-51
50 51
- Voltage indicators

-Motor operating mechanism


for network switch
- Motor operating mechanism
f line
for
li feeder
f d circuit
i it breaker
b k
- Auxiliary contacts
- Key interlocks
- Overcurrent relay 50-51-51N
including the third toroidal current reducer

Dimensions

Tipical diagrams

A(mm)

Weight(Kg)

AF

750

200

IIF

1125

420

IIIF

1500

500

IFIF

1500

550

AV

750

250

IIV

1125

470

IIIV

1500

550

IVIV

1500

650

S_RMSYS 001-1009
S

Front

Via del Commercio 12/14 26900 Lodi Italy - Tel 0039 0371-4906.1 Fax 0039 0371- 411.422
E-mail: sarel@tin.it Web address: www.sarel.it