SA Power Networks
www.sapowernetworks.com.au
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Revision Notice:
Date
Explanation
September 2010
3 September 2012
7 December 2012
SA Power Networks:
SA Power Networks means Distribution Lessor Corporation subject to a two hundred year lease to the
partnership of companies trading as SA Power Networks or SA Power Networks in its own right.
SA Power Networks, ABN 13 332 330 749, a partnership of:
Spark Infrastructure SA (No.1) Pty Ltd, ABN 54 091 142 380
Spark Infrastructure SA (No.2) Pty Ltd, ABN 19 091 143 038
Spark Infrastructure SA (No.3) Pty Ltd, ABN 50 091 142 362 each incorporated in Australia.
CKI Utilities Development Limited, ABN 65 090 718 880
PAI Utilities Development Limited, ABN 82 090 718 951 each incorporated in The Bahamas.
1 Anzac Highway, Keswick, South Australia, 5035.
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
Please Note: Appendix F and Appendix G are not included in this document but can be found in a separate
file on the SA Power Networks intranet site.
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
1.
PURPOSE ........................................................................................................ 6
2.
SCOPE............................................................................................................. 6
3.
REFERENCES ................................................................................................... 6
4.
DEFINITIONS................................................................................................... 6
5.
6.
POLES ............................................................................................................. 7
7.
8.
9.
6.1
General ..................................................................................................................... 7
6.2
6.3
6.4
6.5
6.6
FOOTINGS ...................................................................................................... 9
7.1
General ..................................................................................................................... 9
7.2
Soil Types.................................................................................................................. 9
7.3
Footing Types............................................................................................................ 9
7.4
Materials ................................................................................................................ 10
7.5
Formers .................................................................................................................. 10
7.6
CONDUCTORS............................................................................................... 10
8.1
8.2
General ................................................................................................................... 11
8.3
Tension ................................................................................................................... 11
8.4
8.5
9.2
Line Hardware......................................................................................................... 11
9.3
9.4
9.5
9.6
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
Contents
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
10.1 Suspension.............................................................................................................. 12
10.2 Tension ................................................................................................................... 13
10.3 Post (66kV only) ...................................................................................................... 13
10.4 Pin (11kV) ............................................................................................................... 13
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
1.
PURPOSE ...................................................................................................... 32
2.
SCOPE........................................................................................................... 32
3.
REFERENCES ................................................................................................. 32
4.
DEFINITIONS................................................................................................. 32
5.
RESPONSIBILITIES ......................................................................................... 32
6.
DIRECTIVE .................................................................................................... 32
PURPOSE ...................................................................................................... 34
2.
SCOPE........................................................................................................... 34
3.
REFERENCES ................................................................................................. 34
4.
DEFINITIONS................................................................................................. 34
5.
RESPONSIBILITIES ......................................................................................... 34
6.
DIRECTIVE .................................................................................................... 34
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
PURPOSE
The purpose of this Technical Standard is to define the design requirements of new lines in the SA
Power Networks overhead distribution network. The designs must meet all appropriate
regulations, guidelines and standards.
2.
SCOPE
This standard is applicable to overhead lines up to and including 66kV. All mechanical loads and
strengths used in this technical standard are based on working stress, not ultimate stress.
The general design requirements are specified in the General Standard TS-103.
3.
REFERENCES
Line design parameters for conductors and poles (structures) shall comply with the requirements
of the following:
4.
ESAA document Guidelines for Design and Maintenance of Distribution and Transmission
Lines Code HB C(b) 1 1999
SA Distribution Code
DEFINITIONS
NBFRA (Non Bushfire Risk Area) - as defined in the Regulations associated with the Electricity Act
1996 ie the part of the state shown in the maps in schedule 3 as the non-bushfire risk area
excluding the areas shown in those maps as bushfire risk areas.
Bare - Bare Conductor
ABC - Aerial Bundled Cable
CCT - Covered Conductor Thick (equivalent to SA Power Networks - Insulated Unscreened
Conductor, IUC)
LV (Low Voltage Mains) - electricity distribution mains of voltage less than 1000 Volts
HV (High Voltage Mains) - electricity distribution & transmission mains of voltage greater than
1000 Volts.
5.
LAND CATEGORY
In determining the wind loading on structures and cables, the appropriate land category shall be
selected for the conditions when applying wind loads in calculations.
The categories are:
LC1
Valleys, ridges, escarpments and suburban coastal regions or any line where
Increased security is required.
LC2
LC3
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
1.
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Calculation of wind load is based on a nominal working wind speed of 41m/s. For the permissible
method the wind load on overhead conductors, cables and poles are outlined in table 1:
Table - 1
LAND CATEGORY
LC 1 LC 2 LC 3
1500 1200 800
2000 1500 800
1500 1200 800
2200 1800 1300
650 500 400
650 500 400
Where span length exceeds 150m, a span reduction factor (SRF) shall be applied. This must be
determined in accordance with HB C(b)1.
6.
POLES
6.1
General
Poles shall be selected such that the static (permanent) and dynamic (wind) load combination is
within safe limits.
The Stobie Pole consists of two rolled steel sections tapered from a closed spacing at the top to a
maximum spacing just below the top of the footing and reducing to a minimum spacing at the
bottom. The space between the sections is filled with concrete and the steel sections are tied
together through concrete with bolts spaced at suitable intervals.
The steel sections are considered to carry the full bending and compressive loads. The concrete
and bolts provide restraint against buckling of the steel section under compressive load. The bolts
also serve to transmit shear loads from the steel to the concrete.
6.2
Design Information
Strength in the strong direction is limited to a maximum of 4.5 times the weak direction strength.
Wind forces shall be selected accordingly to the worst terrain category likely during the design life
of the pole. If the wind load exceeds the weak direction strength by more than 50% then these
poles shall be temporarily guyed if the conductors are not strung.
Steel sections used are current production structural shapes to AS3678 and the steel rolled to
AS3679 - Grade 250 (Corresponding to 250Mpa ultimate yield stress).
Designations are: Tapered Flange Beams (TFB)
Universal Beams (UB)
Universal Columns (UC)
Top of footing level is nominally 150mm below ground level. In built up areas and in underground
work, the footing level may be 300mm below ground level.
6.3
Pole Selection
Poles are commonly described by the duty they perform. They can be termed line, angle, deadend, brace and transformer poles. Each individual pole must be examined in relation to its duty to
determine that a pole of adequate strength in strong and weak directions is used without the use
of guy wires.
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
6.4
In addition to the above, the combined loading (K) of the pole should not exceed the factor given
in the table below.
The combination loading (K) is expressed as:
K
Where,
K Factor
1.0
1.0
6.5
Longitudinal Wind
The assessment of the pole strength for wind blowing along the line is a difficult assessment and
generally beyond the scope of a basic design process. The significance of the along line wind will
depend on the location of the pole, the size of the pole and along line stiffness of the poles and
conductor. Many Stobie poles will not be self-supporting and will require the interaction with the
conductor to be structurally adequate.
Experience gained on transmission lines built throughout South Australia over a 50 year period
has demonstrated good performance for wind along the line using the standard methods of
design provided the crossarms and extension pieces are capable of resisting some basic
longitudinal loads generated by wind on the pole. However, this does not guarantee that the
same level of security has been achieved in the transverse and longitudinal direction for all poles.
As a minimum, it is recommended that for poles over 12 m total length where the wind on the
pole exceeds the capacity, a longitudinal load equivalent to 50% of the published SA Power
Networks load (working) on the pole is a minimum design load to be resisted by any component
connecting the pole to the conductors.
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
The design loadings reflected to the pole top in both strong and weak direction, should not
exceed the strength of the pole in either direction.
This load should be shared between each of the conductors. This along line load is not required
to be applied to the pole to determine adequacy in the direction along the line. For poles where
the conductor does not deviate, the pole capacity need only be checked against strength in the
transverse (strong) direction provided the ratio of strong to weak strength does not exceed 4.5 to
1.
The designer should give individual consideration to every pole and make some assessment on
the effect of wind in the direction along the line and how the pole is supported. Use of a previous
successful standard pole/conductor/crossarm/span length arrangement is considered a
reasonable assessment criterion for a basic line design. SA Power Networks may request that the
design is given a more sophisticated assessment by an independent designer.
6.6
7.
FOOTINGS
7.1
General
Poles shall be selected such that they can withstand loads without the assistance of guy wires.
The footing selection shall also be based on the correct assessment of the soil type.
7.2
Soil Types
Soils are grouped into three classes, A, B, and C as follows;
Class A
Gravel, compacted sand and rock soils not subject to large variations in volume with
moisture content, which offer appreciable resistance to boring and which remain
stable after boring.
Note: If the excavation is in rock, the hole should be just large enough to take the
pole at the recommended depth, and no reinforcement is necessary in the concrete.
7.3
Class B
Soils subject to large variations in volume with changing moisture content. Soils
which offer little cohesion, ie clay.
Class C
Low bearing soil. Requires caisson to support sides during excavation. Examples are
swamps, saturated soil and drift sands.
Footing Types
The footing type shall be selected from the SA Power Networks Construction Manual (Drawing E1800 series). Alternative footing arrangements may be used if certified by an appropriately
qualified civil engineer.
The types are:
1. Full strength
a. In Situ
b. Two Block
c. Cylindrical
d. Deep Type
2. Unformed Footings
The Unformed footing is acceptable where it can be certified by an appropriately qualified
civil engineer that loads on the pole will not exceed the strength of the pole and cause
movement.
An unformed footing may be used when :
a. a pole is not to be loaded at more than 50% of its strong direction strength, or
b. exceed half the design factor, ie 1.5 for terminal pole equates to 0.75.
An unformed footing may NOT be used when for a terminal pole.
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
7.4
Materials
7.5
Formers
Formers shall be used for cored footings. Formers are numbered on size order from 0 to U5,
where 0 is the smallest. Refer to SA Power Networks WC series drawings for former dimensions.
7.6
Footing Orientation
All pole footings shall be orientated correctly in relation to the centre line of the mains, and shall
be positioned so that the pole will have the direction of the resultant forces acting along the
strong direction of the pole.
8.
CONDUCTORS
8.1
ST
T9
T 11
T 14
Everyday Load means the tension in the conductor at a temperature which is the mean of the
twelve month period. This Load is considered to be applied with no wind.
Table - 4
EDT
T 13
T 16
T 20
Short Duration Load means the tension in the conductor and applied to the pole in the most
severe of the following conditions:
a. A conductor temperature equal to the average minimum winter temperature in still air
conditions (+ 1 deg C), or
b. A conductor temperature of +15 deg C with the maximum wind pressure on the projected
area of the conductor.
Minimum Sag occurs in the conductor at a temperature of 1 deg C in still air.
Maximum Sag occurs in the conductor at a temperature of:
50C
80C
100C -
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
Concrete for footings shall have a minimum compressive strength of 12 MPa at 7 days and
20 MPa at 28 days.
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
General
Vibration induced into the line shall be limited by careful selection of a tension at which the
conductor operates for the majority of its design life to ensure that the fatigue endurance limit of
the conductor wires is not reached.
8.3
Tension
The design conductor tension under the everyday load condition is that the horizontal tension
shall be no greater than the percentage of its calculated breaking load as derived from HB C(b)1.
Under the short duration load, the tangential tension in the conductor should not exceed 50% of
its calculated breaking load.
It must be stressed that this is a maximum tension which should be used to avoid damage to the
conductor over its expected service life. Lesser tensions may be used accordingly to pole
capacities or other considerations. Design constants for bare conductors are contained in
Appendix A
8.4
Side Swing
All designs must include a check to ensure that the conductor will not swing, under the influence
of wind, outside the requirements of the Electricity Act and Regulations. This design shall be
checked at the conditions stated in clause 2 and 3, eg for rural application in terrain category 2,
- T50 + 500pa wind.
8.5
9.
9.1
9.2
Line Hardware
Table - 5
Item
11kV, LV
33kV
None
None
Conductor protection
Vibration dampers
Warning markers
TS-107
66kV
70kN per string as
per AS1154
Armour grip
suspension style
clamps to be used
at all post and
suspension
positions.
As per HB C(b)1
Aircraft warning markers to be installed on river crossings
and adjacent spans and as otherwise directed by AS3891.
Authorised: Jehad Ali
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
8.2
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
9.3
Network Directive ND J4
9.4
9.5
9.6
10.
INSULATORS
In all cases, SA Power Networks Standard insulators are to be used.
10.1
Suspension
Table - 7
TS-107
Type
Minimum strength
Corona Ring
No
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
All new power lines constructed must conform to the Network Directive, ND J4: Construction of
New Power Lines. A copy of ND J4 can be found in Appendix D.
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
10.2
Tension
10.3
Type
Minimum strength
Corona Ring
No
10.4
Type
Material
Aerodynamic profile
Minimum leakage
distance
Minimum strength
Corona Ring
No
Pin (11kV)
Table - 10
Type
Line Pin,
Material
Aerodynamic profile
Minimum leakage
distance
Minimum strength
11.
ELECTRICAL REQUIREMENTS
11.1
Rated Voltage
The maximum continuous rated voltage shall be:
Table - 11
TS-107
11kV lines
11kV + 10 % = 12kV
33kV lines
33kV + 10 % = 36kV
66kV lines
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
Table - 8
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
11.2
Table - 12
11kV lines
95kV
33kV lines
170kV
66kV lines
325kV
11.3
I2t Rating
Table - 13
Max 20kA for 1 second (400M A2.sec),
11kV lines
11.4
33kV lines
66kV lines
Electrical Clearances
The following minimum clearances shall be maintained to supporting structures, under all
conditions:
Table - 14
Clearance
11kV
33kV
66kV
Phase to Earth
255mm
350mm
690mm
Phase to Phase
255mm
400mm
800mm
The minimum clearances defined in the Electricity (General) Regulations 1997 and associated
schedules shall be maintained, under all conditions.
12.
OTHER CONSIDERATIONS
12.1
Ferro-resonance
On 33kV be aware of the potential for Ferro-resonance and consider the availability of
appropriate three phase switching devices to isolate transformers that are supplied by short
lengths of 33kV cable.
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
The lightning impulse withstands voltage under full wave dry conditions using the standard 1.2/50
microsecond impulse shall be:
1
Equiv.
Alum
Area
mm2
41.10
76.30
122.00
180.00
301.00
495.00
2
Stranding
and
Wire
Diameter
mm
7/2.75
7/3.75
7/4.75
19/3.50
37/3.25
61/3.25
UTS
Resistance
at 20C
Total
Diameter
Cross Sectional
Area
(A)
kN
6.72
11.80
18.90
28.70
48.20
75.20
Ohms/km
0.6890
0.3700
0.2320
0.1570
0.0940
0.0572
mm
8.3
11.3
14.3
17.5
22.8
29.3
mm2
41.6
77.3
124.0
182.8
307.0
506.1
Mass
and C2 =
kg/m
W
W100
W500
0.113 1.099 1.377 4.293
0.211 2.080 2.367 6.021
0.339 3.335 3.629 7.890
0.503 4.925 5.226 10.041
0.845 8.289 8.594 14.055
1.400 18.247 18.480 23.400
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
11
Modulus
of Elasticity
(E)
Conductor Load
N/m
Notes:
1. Conductor Loads in Column 9 and 10 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Values taken from AS1531 1991, Table 3.2
3. C1 =
10
kPa
59 x 106
59 x 106
59 x 106
56 x 106
56 x 106
54 x 106
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
12
Coefficient
of
Expansion
(a)
per C x 10-6
23.0
23.0
23.0
23.0
23.0
23.0
13
14
Constants
C1
319.7
436.0
552.1
650.9
846.2
1067.0
C2
56.4
104.9
168.3
233.9
395.3
628.5
1
Equiv
Copper
Area
in2
.014
.024
.037
.07
.117
.183
.28
.497
.57
2
Equiv
Alum
Area
mm2
14.34
26.50
38.75
72.60
121.13
191.21
292.24
518.71
595.25
3
Stranding
and Wire
Diameter
inches
7/.064
7/.087
7/.1052
7/.144
7/.186
37/.102
37/.1261
37/.168
61/.1403
4
UTS
kN
2.62
4.76
6.63
11.79
18.86
31.58
45.59
77.18
91.63
10
Conductor Load
N/m
W
0.391
0.719
1.052
1.970
3.298
5.253
8.114
14.346
16.535
W100
0.625
0.977
1.323
2.254
3.589
5.557
8.418
14.653
16.843
Notes:
1. Conductor Loads in Column 10 and 11 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Design figures in column 4 to 13 are direct conversions for values shown on SA Power Networks drawing P-30750
3. C1 =
and C2 =
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
11
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
12
13
Constants
W500
2.470
3.392
4.149
5.829
7.817
10.495
13.842
20.709
23.037
C1
191.9
261.5
314.3
430.3
566.8
691.8
852.1
1136.8
1206.4
C2
20.3
37.6
54.8
102.9
171.2
263.4
402.7
714.2
807.1
1
Equiv
Alum
Area
mm2
35.2
65.2
105.0
144.0
244.0
373.0
508.0
2
3
Stranding and
Wire Diameter
mm
Alum
6/2.75
6/3.75
6/4.75
30/2.5
30/3.25
54/3.0
54/3.5
Steel
1 /2.75
1/3.75
7/1.6
7/2.5
7/3.25
7/3.0
7/3.5
4
UTS
kN
12.5
21.5
31.9
61.6
104.0
115.0
153.0
Notes:
1. Conductor Loads in Column 10 and 11 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Values taken from AS1220, Part 1 and 2. 1973 except for conductor marked *
3. C1 =
and C2 =
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
13
Coefficient
of Expansion
(a)
per C x 10-6
19.3
19.3
19.9
18.4
18.4
19.9
19.9
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
14
15
Constants
C1
370.0
504.4
617.5
778.0
1011.4
1105.3
1289.5
C2
63.4
117.9
182.1
267.3
451.8
583.5
794.2
1
Equiv
Copper
Area
in2
.03
.06
.10
.125
.15
.225
.35
.5
2
Equiv
Alum
Area
mm2
33.14
62.10
103.60
128.58
154.67
236.40
372.35
516.92
Notes:
1. Conductor Loads in Column 11 and 12 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Design figures in column 5 to 14 are direct conversions for values shown on SA Power Networks drawing P-30750
3. C1 =
and C2 =
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
13
14
Constants
C1
360.7
493.5
596.9
723.4
793.0
980.7
1098.8
1292.9
C2
59.1
111.3
167.3
221.8
266.6
408.3
560.5
777.5
Equiv
Alum
Area
mm2
2.95
2.32
6.26
9.79
Stranding
and Wire
Diameter
UTS
Resistance
at 20C
Total
Diameter
Cross
Sectional
Area (A)
Mass
mm
3/2.75
7/1.60
19/1.60
19/2.00
kN
22.2
17.5
47.6
74.4
Ohms/km
9.7
12.4
4.5
2.9
mm
5.93
4.80
8.00
10.00
mm2
17.8
14.1
38.2
59.7
kg/m
0.139
0.113
0.309
0.483
Conductor Load
N/m
W
1.364
1.109
3.031
4.738
W100
1.487
1.208
3.135
4.842
Notes:
1. Conductor Loads in Column 9 and 10 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Values taken from AS1220, Part 1 1973 except for conductor marked *
3. C1 =
and C2 =
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
10
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
W500
3.264
2.644
5.019
6.888
11
Modulus
of
Elasticity
(E)
kPa
193 x 106
193 x 106
193 x 106
193 x 106
12
Coefficient of
Expansion
(a)
per C x 10-6
11.5
11.5
11.5
11.5
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
13
14
Constants
C1
378.6
336.4
554.2
692.8
C2
39.6
31.2
84.8
132.5
1
Equiv
Copper
Area
in2
0.0026
0.0090
0.0096
2
Equiv
Alum
Area
mm2
2.72
9.57
10.10
3
Stranding
and Wire
Diameter
inches
3/.104
7/.128
19/.080
4
UTS
kN
20.51
72.51
76.95
10
Conductor Load
N/m
W
1.270
4.787
4.860
W100
1.392
4.885
4.965
Notes:
1. Conductor Loads in Column 10 and 11 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Design figures in column 4 to 13 are direct conversions for values shown on SA Power Networks drawing P-30750
3. C1 =
and C2 =
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
11
W500
3.115
6.834
7.030
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
12
13
Constants
C1
362.8
685.5
689.7
C2
36.4
128.1
131.3
1
Equiv
Copper
Area
in2
.0125
.0225
.035
.06
.10
.15
.20
.25
.25
.30
.30
.50
.60
2
Equiv
Alum
Area
mm2
3
Stranding
and Wire
Diameter
inches
7/.048
7/.064
7/.080
7/.104
7/.136
19/.101
19/.116
37/.093
19/.131
19/.144
37/.103
19/.185
37/.144
4
UTS
kN
3.44
6.09
9.43
15.75
26.11
39.59
51.60
64.05
64.94
77.40
80.51
123.22
150.35
10
Conductor Load
N/m
W
0.744
1.277
2.014
3.371
5.765
8.727
11.442
14.390
14.579
17.629
17.994
29.042
34.354
W100
0.829
1.366
2.104
3.462
5.857
8.820
11.536
14.484
14.673
17.723
18.088
29.136
34.449
Notes:
1. Conductor Loads in Column 10 and 11 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Design figures in column 4 to 13 are direct conversions for values shown on SA Power Networks drawing P-30750
3. C1 =
and C2 =
11
W500
1.974
2.753
3.653
5.202
7.751
10.830
13.608
16.596
16.786
19.860
20.231
31.328
36.662
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
12
13
Constants
C1
199.9
265.7
333.2
434.5
567.3
700.2
797.2
890.0
898.5
987.1
984.9
1267.6
1377.2
C2
16.3
28.7
45.0
76.1
130.5
198.6
257.0
321.1
327.5
395.5
393.9
654.2
774.3
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
A-8: All Aluminium Clad Steel Conductors (SC/AC) - Metric & Imperial
Equiv
Alum
Area
Stranding
and Wire
Diameter
UTS
Cross
Resistance
Total
Sectional
Diameter
at 20C
Area (A)
mm2
5.91
mm
3/2.75
kN
22.7
Ohms/km
4.8
1
Equiv
Copper
Area
in2
.005
.012
2
Equiv
Alum
Area
mm2
5.24
12.16
mm
5.93
Mass
10
Conductor Load
N/m
mm2
kg/m
W
W100
17.82
0.118
1.157
1.3
Values taken from AS1222, Part 2 - 1973
W500
3.183
11
Modulus
of
Elasticity
(E)
kPa
162 x 106
and C2 =
Coefficient
of Expansion
(a)
per C x 10-6
12.9
Notes:
1. Conductor Loads in Column 10 and 11 are the result of conductor load + wind load on projected area.
W100 for 100 pascal wind and W500 for 500 pascal wind
2. Design figures in column 4 to 13 are direct conversions for values shown on SA Power Networks drawing P-30750
3. C1 =
12
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
13
14
Constants
C1
346.8
12
C2
37.2
13
Constants
C1
325.4
496.0
C2
32.8
76.2
Where, E = Final modulus of Elasticity, A = Cross sectional area and a = Coefficient of Linear Expansion
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
A-9: All Aluminium Alloy Conductors - 1120 (AAAC/1120) Metric & 6201A (AAAC/6201) - Metric
3
Equiv
Alum
Area
Stranding
and Wire
Diameter
UTS
(CBL)
Cross
Resistance Conductor
Sectional
Diameter
at 20C
Area (A)
mm2
39.7
73.7
118
mm
7/2.75
7/3.75
7/4.75
kN
9.91
17.6
27.1
Ohms/km
0.713
0.383
0.239
mm
8.25
11.3
14.3
mm2
41.58
77.28
124.0
Conductor Load
N/m
Mass
kg/m
0.113
0.211
0.339
W
1.099
2.080
3.335
W100
1.377
2.367
3.629
W500
4.290
6.021
7.890
11
Final
Modulus
of
Elasticity
(E)
kPa
59 x 106
59 x 106
59 x 106
12
Coefficient
of Linear
Expansion
(a)
per C
23 x 10-6
23 x 10-6
23 x 10-6
2
Stranding
and Wire
Diameter
3
UTS
(CBL)
4
5
6
Resistance Conductor
Cross
Diameter Sectional
at 20C
Area
(A)
7
Mass
9
Conductor Load
N/m
10
11
Final
Modulus
of
Elasticity
(E)
kPa
59 x 106
59 x 106
59 x 106
12
Coefficient
of Linear
Expansion
(a)
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
13
14
Constants
C1
319.7
436.0
552.1
C2
56.4
104.9
168.3
13
14
Constants
mm2
mm
kN
Ohms/km
mm
mm2
kg/m
W
W100
W500
C1
C2
per C
-6
35.4
7/2.75
11.6
0.799
8.25
41.58
0.113
1.099
1.377
4.290
23 x 10
319.7
56.4
-6
65.8
7/3.75
21.7
0.430
11.3
77.28
0.211
2.080
2.367
6.021
23 x 10
436.0
104.9
-6
106
7/4.75
34.8
0.268
14.3
124.0
0.339
3.335
3.629
7.890
23 x 10
552.1
168.3
Notes:
1. Values taken from AS1531 - 1991, Table 3.2
2. Conductor Loads in Column 9 and 10 are the result of conductor load + wind load on projected area. W100 for 100 pascal wind and W500 for 500 pascal wind
3. C1 =
and C2 =
; are conductor constants used in temperature change calculations. Where, E = Final modulus of Elasticity, A = Cross sectional
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
Pole
Size
Strength
In
Newtons
Lifting Details
Steel Section
Designation
mm-mm-kg/m
Bend
Position
from
Bottom
mm
Nominal
Ground
Line
From
Bottom
mm
Depth
of Pole
in
Footing
mm
535
797
1053
1600
1900
1900
Strong
Direction
Weak
Direction
TC1
1500
Pa
TC2
1200
Pa
TC3
800
Pa
TC1
2000
Pa
TC2
1500
Pa
TC3
800
Pa
9-100-288
9-125-308
9-155-318
4700
10500
14800
1300
3200
5400
560
670
830
450
540
660
300
360
440
1560
1760
1900
1170
1320
1430
630
710
760
100x45x7.2 TFB
125x65x13 TFB
150 UB 18.0
1450
1450
1450
Centre
of
Gravity
From
Bottom
mm
4169
4222
4240
11-100-325
3900
870
690
550
370
1950
1460
780
100x45x7.2 TFB
1550
5003
681
11-125-345T
8600
2070
860
690
460
2310
1740
930
125x65x13 TFB
1550
5132
11-155-355T
12150
3490
1060
850
570
2500
1870
1000
150 UB 18.0
1550
12-100-299
12-125-319T
3500
7700
14900
11000
17300
26000
7300
10600
15000
27000
31000
900
2300
4030
3800
5800
7550
2100
3500
5200
6850
12800
760
950
1180
1180
1330
1200
1050
1290
1460
1320
1680
610
760
940
940
1060
960
840
1040
1170
1060
1350
410
510
630
630
710
640
560
690
780
710
900
2170
2570
2770
2770
3210
4240
2920
3140
3480
4760
5500
1630
1930
2080
2080
2410
3180
2190
2360
2610
3570
4130
870
1030
1110
1110
1290
1700
1170
1260
1390
1910
2200
100x45x7.2 TFB
125x65x13 TFB
150 UB 18.0
150 UB 18.0
180 UB 22.2
150 UC 37
125x65x13 TFB
150 UB 18.0
180 UB 22.2
150 UC 37
200 UC 52
1550
1550
1550
1550
1550
1550
1550
1550
1550
1550
1750
Distribution Poles
WB 0905
WB 0910
WB 0915
WA
1105
WA
1110
WA
1115
WB 1205
WB 1210
WB 1214
WB 1215
WB 1220
WB 1227
WB 1310
WB 1315
WB 1320
WB 1327
WB 1330
R12-155-355
12-155-329T
12-179-417T
12-162-434
13-125-338
13-155-348T
13-179-396T
13-162-459T
13-206-405
Steel Face
Concrete Face
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Total
Mass
of
Pole
kg
Steel
Former
Number
Std.
Extra
1450
1750
1750
0
1
1
1
2
2
1900
1750
1011
1900
1750
5158
1332
1900
1750
5474
5556
5419
5548
5504
5703
5966
5997
5925
6136
6318
731
1084
1548
1432
1949
2305
1213
1599
2056
2560
3364
1900
1900
1900
1900
2150
2150
1900
1900
2150
2150
2150
1750
1750
1750
1750
2000
2000
1750
1750
2000
2000
2000
0
1
1
1
3
3A
1
1
3
3A
U1
1
2
2
2
3A
U2
2
2
3A
U2
U3
Rectangular T/F
1200 Pa
Cylindrical T/F
750 Pa
Sheltered Situations Rectangular T/F
720 Pa
Cylindrical T/F
450 Pa
Wind Loadings on T/F as an Equivalent Force at the Top of Pole (Newtons)
(1) Strong Direction FT/F = X Y/h [h - (p - X/2)] x Wind Pressure
M
Z
X
Y
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Z
Fs
Fw
Fs
Fw
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Single Phase
11 kV
20
185
(11/7.6kV)
50
LA5119
335
50
LA5182
335
25
LA5316
265
30
345
50
410
63
LA5327
485
Three Phase
11 kV
(11/7.6kV)
100
LA5336
740
(Wilson T/F)
150
1100
200
LA5346
1220
200
1011348
1175
315
LA5356
1450
10
265
20
300
33 kV
Single Phase
25
LA6116
260
50
LA6117
400
25
LA6499
600
30
710
50
830
33 kV
Three Phase
63
LA6503
830
100
LA6504
1255
150
1555
200
LA6508
1725
10
LA0110
135
Single Phase
19 kV SWER
SWER Dist
25
1012328
200
11 / 19 kV
Single Phase SWER Isol
150
LA5196
1090
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
Shape
Cylindrical
Cylindrical
Cylindrical
Cylindrical
Cylindrical
Rectangular
Cylindrical
Cylindrical
Rectangular
Rectangular
Rectangular
Rectangular
Rectangular
Rectangular
Cylindrical
Cylindrical
Cylindrical
Cylindrical
Rectangular
Cylindrical
Cylindrical
Rectangular
Rectangular
Rectangular
Rectangular
Cylindrical
Cylindrical
Rectangular
Height *
mm
900
840
900
1090
1040
1075
1250
1420
1175
1240
1400
1410
TBA
1290
950
950
1050
1070
1030
960
1060
1030
1225
1425
1425
840
840
1500
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Width *
mm
520
570
520
725
725
960
720
620
960
1180
1230
1210
TBA
1290
800
845
630
700
1210
1110
1110
1210
1145
1105
1185
570
570
970
Depth *
mm
510
580
510
710
710
580
610
640
630
950
750
905
TBA
945
1130
1020
960
1030
1200
1190
1150
1200
1250
1340
1320
950
1000
1230
Description
Capacity
kVA
Supply Item
Number
Current
Contract
Mass
kg
Shape
Single Phase
200
LA5197
1265
Rectangular
SWER Isol
33 / 19 kV
Single Phase
150
LA6196
1120
Rectangular
SWER Isol
200
LA6197
1270
Rectangular
* The dimensions quoted for the sizes of the transformers are overall dimensions, which include bushings, lifting lugs etc.
11 / 19 kV
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Height *
mm
Width *
mm
Depth *
mm
1430
1070
1300
1400
1430
1040
1070
1250
1250
Supply
Item No.
1011246
WB1515
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
6.60
Fw
(kN)
1.47
1011247
10.30
2.98
15-155x18-425
150UB18
15.0m
WB1520
1011248
12.90
4.30
15-179x22-440
180UB22
15.0m
WB1526
1011249
18.50
7.10
15-207x30-460
200UB30
15.0m
U1
WB1532
1011250
21.50
7.00
15-162x37-430
150UC37
15.0m
3A
WB1536
1011251
29.50
13.40
15-206x52-397
200UC52
15.0m
U1
WB1540
1011252
41.50
11.80
15-203x46-645
200UC46
15.0m
U4
WB1550
1011253
53.50
15.30
15-205x60-640
200UC60
15.0m
U4
WB1555
1011254
59.00
23.50
15-254x73-580
250UC73
15.0m
U4
WB1565
1011255
71.50
28.90
15-260x89-575
250UC89
15.0m
U4
WB1615
1011256
16.70*
4.80*
150UB18/14
16.5m
WB1640
1011465
30.90
10.60
16.5-203x46-535
200UC46
16.5m
U3
WB1645
1011466
38.00
12.00
16.5-206x52-585
200UC52
16.5m
WB1660
1011467
64.00
25.80
16.5-260x89-575
250UC89
16.5m
U4
WB1815
1011257
9.10
2.50
150UB18/14
18.0m
WB1820
1011258
11.60
3.63
18-179x22-465
180UB22
18.0m
WB1826
1011259
17.10
5.92
18-207x30-510
200UB30
18.0m
U1
WB1830
1011260
23.00
9.20
18-256x37-550Compound Section
250UB37/25
18.0m
U2
WB1840
1011261
31.00
10.50
18-203x46-500
200UC46
18.0m
U3
WB1845
1011262
34.50
10.80
18-206x52-585
200UC52
18.0m
WB1850
1011263
45.00
13.90
200UC60/46
18.0m
U4
Yes
WB1855
1011264
47.50
* = Ultimate Strength Values
19.00
18-254x73-580
250UC73
18.0m
U4
No
TS-107
Fs (kN)
Pole Designation
Steel Section
Overall Length
Former
15-125x13-415
125x65x13TFB
15.0m
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
Final Design
Complete
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
B-7: WB Sub-Transmission Poles (Design Strength & Supply Item Numbers) - Continued
Pole Drg
No.
WB1860
WB1862
Supply
Item No.
1011265
1011266
58.00
70.00
Fw
(kN)
23.30
23.30
WB2020
WB2025
WB2040
WB2045
WB2055
WB2060
WB2062
1011267
1011268
1011269
1011270
1011271
1011272
1011273
10.50
19.00
25.50
36.00
43.50
60.00
64.00
3.30
6.50
8.70
11.00
17.40
22.20
21.30
WB2070
1011274
84.00
34.10
WB2075
1011275
112.00
41.50
WB2120
WB2125
WB2130
WB2140
1011276
1011277
1011278
1011279
12.00
17.00
18.50
26.00
3.30
5.75
7.70
8.80
19.5-179x22-465
19.5-207x30-500 Compound Section
19.5-203x46-535
19.5-206x52-575 Compound Section
19.5-254x73-580
19.5-260x89-575 Compound Section
19.5-260x89-700 Compound Section
19.5-314x118-700 Compound
Section
19.5-320x137-700 Compound
Section
21-179x22-465 Compound Section
21-207x30-500
21-256x37-525 Compound Section
21-203x46-500
WB2150
WB2155
WB2160
WB2162
WB2170
WB2172
1011280
1011281
1011282
1011283
1011292
1011293
31.75
40.00
48.50
59.00
77.50
168.4*
9.75
16.00
19.60
19.60
31.30
63.3*
21-210x 60-508
21-254x73-580
21-260x89-575 Compound Section
21-260x89-700 Compound Section
21-315x118-700 Compound Section
21-321x137-700 Compound Section
TS-107
Fs (kN)
Pole Designation
Steel Section
Overall Length
Former
250UC89/73
250UC89/73
18.0m
18.0m
U4
U5
180UB22
200UB30/22
200UC46
200UC52/46
250UC73
250UC89/73
250UC89/73
19.5m
19.5m
19.5m
19.5m
19.5m
19.5m
19.5m
3
U1
U3
5
U4
U4
U5
310UC118/97
19.5m
U5
310UC137/97
19.5m
U5
180UB22/18
200UB30
250UB37/31
200UC46
21.0m
21.0m
21.0m
21.0m
3
U1
U2
U3
200UC60
250UC73
250UC89/73
250UC89/73
310UC118/97
310UC137/97
21.3m
21.0m
21.0m
21.0m
21.0m
21.0m
U3
U4
U4
U5
U5
U5
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Final Design
Complete
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
No
Yes
No
Yes
Yes
B-8: WB Sub-Transmission Poles (Design Strength & Supply Item Numbers) - Continued
Pole Drg
No.
Supply
Item No.
Fs (kN)
Fw
(kN)
Pole Designation
Steel Section
Overall Length
Former
WB2325
1011294
12.40
4.60
200UBx10.5m
200UB30x12m
22.5m
U1
WB2326
1011295
13.00
4.50
22.5-162x37-400
150UC37
22.5m
WB2330
1011297
21.00
7.20
250UB37/31
22.5m
U2
WB2340
1011299
21.50
7.40
22.5-203x46-535
200UC46
22.5m
U3
WB2350
1011300
27.00
9.60
200UC60/46
22.5m
U3
WB2355
1011301
37.50
14.80
22.5-254x73-590
250UC73
22.5m
U4
WB2360
1011302
45.00
18.10
250UC89/73
22.5m
U4
WB2370
1011303
72.00
29.00
22.5-315x118-700 Compound
Section
310UC97x12m
310UC118x10.5m
22.5m
U5
WB2371
1010386
19.00
10.80
22.5-307x46-470
310UB46
22.5m
WB2375
1011304
84.10
33.50
U5
1011305
96.60
39.00
310UC97x10.5m
310UC137x12m
310UC118x12m
310UC158x10.5m
22.5m
WB2376
22.5-320x137-700 Compound
Section
22.5-327x158-700 Compound
Section
22.5m
U5
WB2430
1011306
15.90
6.60
250UB37/31
24.0m
U2
WB2440
1011307
20.00
6.90
24-203x46-535
200UC46
24.0m
U3
WB2625
1011308
10.80
4.00
200UB30/22
25.5m
U1
WB2630
1011309
14.90
6.00
250UB37/31
25.5m
U2
WB2641
1011537
13.00
6.00
26 - 203 x 46 - 400
200UC46
25.5
U1
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is lo
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
Final Design
Complete
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet
Location
FEATURES TO BE MEASURED
Conductor tie-off tension
RESULT
REMARKS
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
Page 37 of 38
TS-107 - Overhead Line Design Standard for Transmission & Distribution Systems
TS-107
The use of this Technical Standard is subject to the conditions stated in SA Power Networks disclaimer in front of this document.
Page 38 of 38
WARNING: Printed copies of this document ARE DEEMED UNCONTROLLED. The most up-to-date version is located on the Intranet/Internet