SCOPE
The air conditioning contractor shall take all necessary precautions to have
minimum noise generation and its transmission. Minimum vibration as permitted
by ISO standard shall be followed. A few points for guidance only are given
below:
a)
b)
c)
d)
e)
All conduit connection where conduits are 60mm or larger shall be made
of 1.2 meters minimum length conduit installed in the shape of U and
grossly slack to provide maximum vibration isolation.
f)
All end suction pumps shall be bolted and grouted to the inertia base
which in turn shall be supported on suitable vibration isolation rubber pads
duly sandwitched with 24G GI sheets. Concrete inertia blocks shall be
formed of suitable thickness and of adequate mass.
g)
The floor supported piping shall be mounted on pipe supports with min.
7.5mm ribbed neoprene pads between the base plate of the pipes and the
floors.
h)
i)
In case of ducts, conduits, pipes & tubes the annular space between
construction and penetrating element shall be sealed with sand cement
plaster/suitable other material.
j)
The supply duct starting from air handling unit & plenum shall be
provided with 15 mm thick acoustic lining (140 kg/m 3) as indicated in the
P-4.3, 1 out of 2
schedule of quantities. All Fan Coil Units (wherever used) collar shall also
be lined with 12 mm thick acoustically lined. The duct lining shall be done
with closed cell nitrile rubber based material having min. density of 140
kg/cubic meter.
k)
l)
-----x-----