Report on

Design of Air-Conditioning System for


Main Auditorium
Submitted by

1. Swapnil Vasant Awate

(MIS NO- 121425001)

2. Pradip Dnyaneshwar Bhambure

(MIS NO- 121425002)

M.Tech First Year (Thermal)

Under the Guidance of


Prof. Dr. S.N. Sapali
Department of Mechanical Engineering
College of Engineering, Pune-5
(2014-2015)
1

INDEX
SR.

CONTENTS

NO.
1.

2.

3.

4.

PAGE
NO.

1.Design Conditions

2. Cooling Load Calculation


2.1. Heat Gain through Structure
2.1.1. Wall
2.1.2 Calculation for all Walls
2.1.3 Roof
2.1.4 Door
2.2 Occupancy Heat Load
2.3 Lighting Load
2.4 Equipment Load
2.5 Ventilation Load
2.6 Supply Condition
3. Duct Design
3.1 Ducting for stage and Front Sitting
3.2 Ducting for Back Sitting
3.3 Ducting for Balcony
4. Equipment Selection
4.1Blower Selection:
4.2 Compressor Selection

5
6
6
9
9
10
10
10
10
11
12
13
13
14
14

References

17

15
15
15

LIST OF FIGURES

SR. NO.

NAME OF FIGURES

PAGE NO.

Fig. 1: Plan of the Building

Fig.2: Stage Wall structure.

Fig.3: Wall structure with plywood

Fig.4: Wall structure without plywood

Fig.5: Mixing of air streams.

12

Fig.6: Front sitting duct

13

Fig.7: Balcony duct

14

Fig.8: Specification Details of compressor

16

LIST OF TABLE
SR.
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13

NAME OF TABLE
Table 1: Dimensions of Walls
Table 2: Properties of material of stage wall
Table 3: Dimensions of wall with plywood
Table 4: Properties of material of wall with plywood
Table 5: Dimensions of wall without plywood
Table 6: Properties of material for wall without
plywood
Table 7: Total heat transfer through walls
Table 8: Properties of material of roof
Table 9: Properties of material of door
Table 10: Lighting load
Table 11: Equipment load
Table 12: Duct dimension
Table 13: Duct dimension
Table 14: Duct dimension

PAGE
NO.
6
6
7
7
8
8
9
9
10
10
10
13
13
14

14
4

15
16
17

Table 15: Blower Specification


Table 16: Temperature Condition for compressor
Table 17: Compressor Specification

15
15
16

1. Design Conditions:
Design Day: 21 May

[2]

Time: 1400 hrs

A. Outdoor Conditions:
DBT: 37.1 0C WBT: 27 0C
V =4.02 m/s

ho=80.2 W/m2K

B. indoor Conditions:
DBT: 24 0C

RH: 50%

V =0.2 m/s

hi=4 W/m2K

LM = 180 N altitude.

Stage

Balcony

18 m

10m

20 m

9.5m

Fig. 1: Plan of the Building

2. Cooling Load Calculation:


2.1. Heat Gain through Structure:
2.1.1. WALL
a. Stage:
Sr. No.

Wall Name

1.
2.
3.

North wall
South wall
West wall

Dimensions(lxb)
(m)
10x8
(10x8)-2.73
18x8

Area(m2)
80
77.27
144

Table 1: Dimensions of Walls

StructureCalculation for overall heat transfer coefficientPlaster

Plywood

Glass wool

Stone

Fig.2: Stage Wall structure

Material
Plywood
Glass wool
Plaster
Stone

Conductivity(W/mK)
0.15
0.0372
0.79
1.77
Table 2: Properties of material of stage wall

Overall heat transfer coefficient (U)

Thickness(m)
0.0254
0.0508
0.013
0.45
[8]
[1]

U=

1 1
l
+
+
hi ho K

( )

( Kl )

+
plywood

( Kl )

+
glasswool

2+
plaster

( Kl )

stone

U = 0.6464 W/m2K.
b. Walls with Plywood:
Sr. No.
1.
2.
3.

Wall Name
North wall
South wall
East wall

Dimensions(l x b )(m)
29.5x4
(29.5x4)-(2.73x3)
(18x4)-(2.73x2)

Area(m2)
118
109
66.5

Table 3: Dimensions of wall with plywood

StructureCalculation for overall heat transfer coefficientPlaster

Plywood Air Gap Stone


Fig.3: Wall structure with plywood

Material

Conductivity(W/mK)

Thickness(m)

Plywood
0.15
Air gap
0.0276
Plaster
0.79
Stone
1.77
Table 4: Properties of material of wall with plywood

0.0254
0.1016
0.013
0.45
[8]

Overall heat transfer coefficient (U)


1

U=

1 1
l
+
+
hi ho K

( )

( Kl )

+
plywood

air gap

( Kl )

2+
plaster

( Kl )

stone

U = 0.2272 W/m2K.

c. Walls without Plywood:


Sr. No.

Wall Name

1.
2.
3.

North wall
South wall
East wall

Dimensions(lxb)
(m)
29.5x4
(29.5x4)
(18x4)-(2.73x2)

Area(m2)
118
118
66.5

Table 5: Dimensions of wall without plywood

StructureCalculation for overall heat transfer coefficientPlaster

Stone
Fig.4: Wall structure without plywood

Material

Conductivity(W/mK)

Plaster
0.79
Stone
1.77
Table 6: Properties of material for wall without plywood

Thickness(m)
0.013
0.45
[8]

Overall heat transfer coefficient (U)


1

U=

1 1
l
+
+
hi ho K

( )

2+
plaster

( Kl )

stone

U = 1.81 W/m2K.

10

2.1.2 Calculation for all Walls


Name
of wall

Area(m )

North
South
West
North
South
East
North
South
East

80
77.27
144
118
109
66.5
118
118
66.5

Stage
Walls
with
Plywood
Walls
without
Plywood

Overall Heat
Temperature
Transfer
Difference(0C)
2
coefficient(W/m K)
0.6464
(37.1-24)
0.6464
(31.1-24)
0.6464
(37.1-24)
0.2272
(37.1-24)
0.2272
(31.1-24)
0.2272
(37.1-24)
1.81
(37.1-24)
1.81
(31.1-24)
1.81
(37.1-24)
Total

Heat
Transfer
Rate (W)
677.42
354.60
660
351.21
175.83
197.92
2797.89
1516.418
1576.78
8308.068

Table 7: Total heat transfer through walls

2.1.3 Roof:
Material

Conductivity
(W/mK)

Thickness(m)

Dimension
(lxb)(m)

Area(m2)

Cement Sheets
Air Column
Asbestos

0.166
0.0276
0.177

0.0127
0.3
0.0127

39.5x18
39.5x18
39.5x18

711
711
711

Table 8: Properties of material of roof

U=

1 1
l
+
+
hi ho K

( )

asbestos

( Kl ) +( Kl )
air

cement sheet

U = 0.088 W/m2K.
Q = UAT
= 0.088 711 (31.1-24)
= 444.23 W.

11

12

2.1.4 Door:
Material

Conductivity(W/mK
)

Wood

1.5

Thickness(m)

Dimension(lxb)
(m)

0.0381
1.3 x 2.1
Table 9: Properties of material of door

Area
2.73

U=

1 1
l
+
+
hi ho K

( )

wood

U = 3.47 W/m2K
Q = U A no of doors T
= 3.47 2.73 8 (31.1-24)
= 538.0 W.

2.2 Occupancy Heat Load:


Seating Capacity = 972 + 20(stage)
= 992 avg. person
Rates of heat gains from occupants of conditioned space Seated in theater:
Sensible Heat
= 75 W
Latent Heat
= 40 W
Sensible Heat Gain
= 992 75
= 74,400 W
Latent Heat Gain
= 992 40
= 39,680 W

2.3 Lighting Load:

[1]

[5]

Type

Wattage Total Quantity

Working
Equipment

Total (W)

CFL
Halogen Bulb
Fluorescent Tube

35
400
40

52
12
5

1820
4800
200
6820

76
16
5

Total
Table 10: Lighting load

2.4 Equipment Load:

[5]

Type

Wattage per
quantity

Total Quantity

Total (W)

Mini-Computer

200

400
13

Sound System

2500

2
Total
Table 11: Equipment load

5000
5400

14

2.5 Ventilation Load:


Flow rate of air per person is taken as 7 cfm from the design considerations.

[4]

Sensible cooling load from ventilation = 1.1 cfm/person no. of person


Temperature change
[3]

= 1.1 7 992 (98.2-75.2)


= 175683.2 Btu/hr
= 51.52 KW.
Latent cooling load (ventilation) = 0.68 cfm/person no. of person (Wo - Wi)
= 0.68 7 992 (76.76-54.54)
= 104921.06 Btu/hr
= 30.768 KW.
Total load

= Heat Gain through Structure + Roof + Door +


Occupancy Heat Load + Lighting Load +
Equipment Load + Ventilation

Load
=8308+444.23+538+74,400+39,680
+6820+5400+51520+30768
= 217478 W.
Total load = 61.83 TR.

15

2.6 Supply Condition

Conditioned Space
5

75% Re-circulated Air


4.

1.

2.

3.

25 % Fresh air
Cooling coil
Fig.5: Mixing of air streams.

Outside Conditions (1): 37.10C DBT, 270C WBT


Inside Conditions (5): 24 0C DBT, 50% RH
Assuming 25% fresh air is mixed with 75% return air.
Mixing condition (2): 28.10C DBT, 47.5%RH
Room Sensible Heat = 95.91 KW
Room Latent Heat = 39.68 KW
RSH

RSHF = RSH + RLH


=

95.91
95.91+ 39.68

= 0.707
Grand Sensible Heat = 147.43 KW
Grand Latent Heat = 70.448 KW
Grand Total Heat =217.878 KW
GSHF =
=

GSH
GSH +GLH
147.43
147.43+70.448

16

= 0.6766
Apparatus Dew Point Temperature of cooling coil: 140C

17

Blower
A

Supply Air Conditions (3): 20 0C 3. Duct Design:

1m

(ab)0.625
D=1.3 (a+ b)0.25

[1]

2.5 m m
C 1.5 mD 1.5 m E

9m

Where a and b are length


and width of equivalent
section.
We will assume aspect ratio (b/a)=1.2

F
4m

3.1 Ducting for stage and Front Sitting:

Sectio
n

Length(m
)

AB
BC
CD
DE
BF
FG

1
2.5
1.5
1.5
9
4

Q(m3/s
)

f
(Pa/m)

V(m/s
)

D(m
)

Fig.6: Front sitting duct


Pressure
Drop(Pa)

2.6
0.2
4
0.9
1.5
0.2
3.8
0.75
1
0.2
3.1
0.65
0.5
0.2
2.9
0.48
1.1
0.2
3.3
0.65
0.55
0.2
3
0.47
Total pressure drop(Pa)
Table 12: Duct dimension

0.2
0.5
0.3
0.3
1.8
0.8
3.9

Equivalent
Rectangular
Section
( l x b)(m)
a
b
0.4682
0.5618
0.2879
0.3454
0.1969
0.2362
0.0875
0.105
0.1969
0.2362
0.0828
0.0993

3.2 Ducting for Back Sitting:

E
5m

D
5m

Sectio
n

Length(m
)

Q(m /s)

f
(Pa/m)

V(m/s
)

D(m
)

Pressure
Drop(Pa
)

AB

2.6

0.2

0.90

0.2

BC

1.95

0.2

3.9

0.83

Equivalent
Rectangular
Section
( l x b)(m)
a
b
0.468
0.5618
2
0.377
0.45276
3

5m

B
1m

A
Blower

18

CD

1.3

0.2

3.6

0.70

DE

0.65

0.2
2.95
0.53
1
Total Pressure Drop
3.2
Table 13: Duct dimension

0.239
5
0.1140

0.2874
0.1368

3.3 Ducting for Balcony:


R

J
2m

2m

E
2m

P
O

B 2m

1m

2.5 m

2m

D
C

2m
5m

BlowerA

Fig.7: Balcony duct

Sectio
n

Length(m
)

Q(m3/s
)

f
(Pa/m)

AB
BC
CD
DE
EF
CG
GH
HI
IJ

1
2.5
2
2
2
5
2
2
2

2.6
1.3
0.65
0.433
0.216
0.65
0.65
0.433
0.2166

0.2
4
0.9
0.2
3.6
0.70
0.2
2.95
0.53
0.2
2.8
0.48
0.2
2.3
0.35
0.2
2.95
0.53
0.2
2.95
0.53
0.2
2.8
0.48
0.2
2.3
0.35
Total pressure drop(Pa)
Table 14: Duct dimension

V(m/s
)

D(m
)

Pressure
Drop(Pa)
0.2
1
0.4
0.4
0.4
1
0.4
0.4
0.4
4.6

Equivalent
Rectangular
Section
( l x b)(m)
a
b
0.4682
0.5612
0.2395
0.2874
0.1140
0.1368
0.0875
0.105
0.03773
0.0452
0.1140
0.1368
0.1140
0.1368
0.0875
0.105
0.03773
0.0452

19

4. Equipment Selection:
4.1Blower Selection:

[6]

Total Maximum pressure drop:


P

= 4.6 Pa
= 0.0184 in. WG.

Considering the losses per fitting, bend, damper is 0.08 in WG.


Bends: 5
Damper: 1
Pmax = P + losses
= 0.4984 in WG.
According to Dayton catalogue,

Model Name

Flow
Power
Rate
RPM Diameter(m) Input
(cfm
(hp)
)

Static
Pressure
(in.WG)

4YU98(7A665)

5969

0.5

1200

0.5461

Table 15: Blower Specification

4.2 Compressor Selection:


Refrigerant

Evaporator
Temp.

Condenser
Temp

Cooling
Capacity

R-22

43

21.7

Table 16: Temperature Condition for compressor

20

21

4.2.1 Specification of selected compressor:

[7]

There will be five number of units placed at five locations with each unit cooling capacity
of (62/5) 12.4 TR. For this cooling load two refrigeration circuits will be used. So, the individual
unit capacity for cooling will be 6.2 TR.
So, the components selection for the refrigeration circuit will be done on the basis of
above cooling load.
From the Scroll Compressor catalogue of Danfoss we can select the following model of
compressor with min and max cooling capacity.

Model
Name

SM084-4

Condenser
Temperature
(0C)
Min
Max

37.7
54.44

Evaporator
Temp.
(0C)
7.22
7.22

Cooling
capacit
y
Btu/hr
97900
84000

Power
input
KW
5.2
7.4

Table 17: Compressor Specification

Fig.8: Specification Details of compressor

22

REFERENCES:
[1] C.P. Arora, Refrigeration and Air Conditioning, third edition, McGraw Hill Education
private limited, page No. 446-464,574-606, 705-720.
[2] Manohar Prasad, Refrigeration and Air conditioning Data book, Wiley Eastern Limited,
page No.118-127,154.
[3] G. Pita, Air Conditioning Principles and Systems: An Energy Approach,
page No.124-200.
[4] ASHRAE hand Book (1997).
[5] ISHRAE hand Book.
[6] Ventilation Fundamentals of Dayton.
[7] Scroll compressor manufacture catalogue of Danfoss.
[8] Heat and Mass Transfer Data Book, New age international publication.

23