1.
OBJECTIVE
To provide a guide on how to recover an FCS with a load file that causes loads and tuning parameter saves to fail with the
error;
ERR:ERROR= 11186:The Generation time of master data base and FCS image is different.
This indicates that the time stamp in the master copy of the FCS program, which is stored on the EWS, no longer matches
the time stamp in the actual FCS. This is normally caused by an EWS crash or severe network failure during an online
load.
The conventional solution to this (and the recommended Yokogawa Solution) is to wait until the FCS can be offline loaded.
Where this is not possible, the FCS master file time stamp can be edited to match the FCS time stamp. This will allow
tuning parameter saves and further loads.
When it is suspected that a load has failed and as a result the FCS/EWS timestamp does not match, rather than
attempting another load to prove this it is preferable to select a tuning parameter save. This will preserve the working files
from the failed load. If this completes successfully then there is no problem with the load look elsewhere than this
procedure! However, if the parameter save fails, then you need to follow this procedure (note - the Tuning parameter save
may not complete if there is a time stamp difference, and an engineering restart of the EWS will be required).
Note; This procedure will only work as long as there have been no tags added or deleted and are consequentially different
between the EWS copy and the running FCS master.
This procedure has been used many times to successfully enable online loads to be performed after a time stamp
mismatch. It will not provide a full solution when tags lists mismatch between the EWS and the FCS. In this circumstance
the FCS will not allow online loads to the FCS Area or station with the mismatched tag list (the FCS will reject the load).
The FCS will allow online loads to other Areas within the FCS. The good news is that an Area offline load can be completed
in a minute or less and the I/O does not fail safe on an Area offline load.
Though Areas with mismatching tag lists cannot be online loaded, once the time stamp has been repaired tuning parameter
saves can be carried out.
2.
3.
RECOVERY STEPS
Depending on the circumstance of the crash use the following checklist as a recovery guide;
1.
2.
3.
4.
4.
/var/www/apps/conversion/tmp/scratch_6/265225175.doc
Page 1 of 4
Locate the EWS utility dbdump, ie; find / -name dbdump print should return
/opt/ydcs/eng/bin/hp9k700/dbdump (several versions will exist in different paths this version works for
HPUX 10.20)
#su [root password]
#cd /opt/ydcs/eng/bin/hp9k700
#ls al dbdump
-r-xr-xr-x
1 root
root
518184 May 8 1996 dbdump
#./dbdump h E0321 16 3
(Gateway to use, Station of FCS, Domain of FCS)
Data base start logical address = 0x01000000
(Takes about five ten minutes to access the FCS database)
03-16-main:area=all>mds #StnCns
1: SEBOLXe[Ve[u
utclStnCns 00000000 000200(
512)
2: Xe[Ve[u
StnCnstTbl 01000100 000280(
640)
Select NO ?(1-2) =2 (Select the area which corresponds to StnCnstTbl)
Xe[Ve[u StnCnstTbl 01000100 000280(
640)
01000100
5354 4E20 434E 5354 36CB 6DB2 C4F7 0000
STN CNST6.m.....
01000110
0000 0000 0000 0000 0000 07D0 003C 003C
.............<.<
01000120
0000 0000 0000 0000 0310 0040 0001 0000
...........@....
01000130
0000 0000 0000 0000 0000 0000 0000 0000
................
01000140
0001 0005 0004 0001 0258 0000 0000 0000
.........X......
01000150
0000 0000 0000 0000 0000 0000 0000 0000
................
01000160
0000 0000 0000 0000 0000 0000 0022 0400
............."..
01000170
0020 012C 0008 0000 0000 0000 0000 0000
. .,............
01000180
0000 4000 0100 0000 0000 03E8 1388 0002
..@.............
01000190
003C 0000 0000 0000 0000 0000 0000 0000
.<..............
010001A0
42C8 0000 0000 000A 01F4 01F4 1000 03E8
B...............
010001B0
003C 0008 000A 000A 0032 0000 0000 0000
.<.......2......
010001C0
0001 9000 0100 0200 0000 0000 0000 0000
................
010001D0
0000 0000 0000 0000 0000 0000 0000 0000
................
010001E0
0040 0007 0001 000A 0000 0000 0000 0000
.@..............
010001F0
0000 0000 0000 0000 0000 0000 0000 0000
................
03-16-main:area=all>mds #A1-areaCns
GAe[u A1-areaCnstTbl 01100200 000100(
256)
01100200
4143 4E53 5420 3031 4853 3131 0000 0000
ACNST 01FCS1....
01100210
36CD 5200 0955 0000 0000 0000 0000 0000
6.R..U..........
01100220
0000 0000 0000 0000 0000 0000 0000 0000
................
01100230
0000 0000 0000 0000 0000 0000 0000 0000
................
01100240
0DAC 068B 07D0 066A 0067 0016 03E8 0100
.......j.g......
01100250
0000 0000 000A 000A 0014 0007 0064 0000
.............d..
01100260
0006 0100 0000 0000 0000 0032 0064 0000
...........2.d..
01100270
0000 0000 0000 0000 0000 0000 0000 0000
................
01100280
00C8 01F4 3F00 0000 3F40 0000 3F60 0000
....?...?@..?`..
01100290
42C8 0000 4100 0000 0000 0000 0000 0258
B...A..........X
011002A0
0002 0001 003C 0000 0000 0000 0000 0000
.....<..........
011002B0
0000 0000 0000 0000 0000 0000 0000 0000
................
011002C0
0000 0000 0000 0000 000A 000A 000A 000A
................
011002D0
0000 0000 0000 0000 0000 0000 0000 0000
................
011002E0
0000 0000 0000 0000 0000 0000 0000 0000
................
011002F0
0000 0000 0000 0000 0000 0000 0000 0000
................
03-16-main:area=all>quit
The sections in BOLD contain the unix time stamps / checksums in the header hang on to these listings theyll be
need in the next sections.
2.
/var/www/apps/conversion/tmp/scratch_6/265225175.doc
6DB2
07D0
0040
0000
0000
0000
0000
0000
03E8
C4F7
003C
0001
0000
0000
0000
0022
0000
1388
0000
003C
0000
0000
0000
0000
0400
0000
0002
STN CNST6.m.....
.............<.<
...........@....
................
.........X......
................
............."..
. .,............
..@.............
Page 2 of 4
3.
ACNST 01FCS1....
6.R..U..........
................
................
.......j.g......
.............d..
...........2.d..
................
....?...?@..?`..
B...A..........X
.....<..........
................
................
................
................
................
ACNST 01FCS1....
6.R..U..........
................
................
Check the entered data to confirm the undate has been successful, note 36CD 5200 is hex for the number of seconds
since 1/1/70 GMT and refers to the last compile time of this file.
One or the other, or both, of the two calculated dates above will correspond to the date on the ICS system page for the
FCS.
This procedure must be carried out for each Area in the FCS Station.
4.
/var/www/apps/conversion/tmp/scratch_6/265225175.doc
Page 3 of 4
ONLINE LOAD
The FCS should now accept an online load. Prove this by selecting a tuning parameter save.
Before carrying out the online load please re-read section 2 DISCLAIMERS AND WARNINGS.
6.
ICS UPDATES
The ICS Master File update will not have completed with the modifications. This update is incremental and is normally
conducted at the end of an FCS load. To ensure that the ICS are kept up to date;
1.
OR
2.
Undo/modify slightly each function block, or tag source (I/O, Switches, Alarms) that was changed in the previous
failed load. This will force the next load to do an ICS master file update for these files.
OR
3.
Carry out item 1. For a single ICS and use this as a template for other ICSs by copying files at a unix level
experienced users only !!!