Sunteți pe pagina 1din 14

Chemical Engineering Laboratory

SEGI University
Experiment: Air Conditioning Module
Candidates Name: M Asfand Yar

Student ID: SCM-027033

Lecturer: Ms. Chan Yi Shee


Dr Wong

Submission date: 25/3/2015

1.0 Abstract:

The primary objective of this experiment is to study the principle capacities and working
standards of an air conditioning system. The experiment determines, what effects the progression
in temperature and dampness have on the viability of the system. There are 4 basic process
carried out within an air-condition system namely heating, cooling, humidifying and
dehumidifying process. The temperature and humidity for inlet and outlet for all these processes
were recorded and the results were used for comparison between theoretical and experimental
data. The changes in the state of air caused by these process is plotted using the psychometric
charts. The heating power, cooling power and enthalpy is then calculated.

2.0 Introduction:

The basic job of an air conditioner is to move heat from inside your home to the outside, thereby
cooling you and your home. Air conditioners blow cool air into your home by pulling the heat
out of that air. This heat is removed in many different stages. There are four basic processes in
an air conditioning unit. Heating, cooling, humidifying and dehumidifying.

Figure 1.0 basic circuit for an air conditioner

Inside a split Air conditioner there are following parts:1. Compressor


2. Condenser
3. Evaporator
3

4. Refrigerant
Compressor function is to circulate refrigerant through outdoor unit and converts the same from
gas to liquid. The liquid is then forced through the indoor evaporator coil or cooling
compartment.
The indoor units fan circulates the inside air to pass across the evaporator fins. The evaporators
metal fins exchange the thermal energy with the air around it. In Evaporator the refrigerant turns
from liquid into vapor, removing any heat from the surrounding air. That heated air is removed
from house/shop is replaced with cooled air. From that point, the condenser or outdoor unit then
turns the refrigerant vapor back into a liquid, removing any heat. By the time the fluid leaves the
evaporator again, it is a cool, low-pressure gas, eventually returning to the condenser to begin its
trip all over again. This process continues again and again until your home reaches the cooling
temperature you want, as programmed and sensed by your thermostat setting.
There are two types of graphs we use in air conditioning calculation
1) psychometric chart for air
2) pressure enthalpy chart for refrigerant
Psychometric charts are used for calculating values of relative humidity, absolute humidity and
dew point from pyschrometer readings

3.0 Experimental Procedure :


General start-up procedures

1) The air conditioner unit was installed to the base condensing unit and the quick coupling was
connected to the refrigerator supply and return lines
2) The inclined manometer was connected to the pitot tube located near the orifice using the
flexible tube provided
3) The power supply wires of the air conditioning unit were connected to the base condensing
unit.
4) The power supply switch was turned on.
5) The main power switch on the base condensing unit was switched on.
6) The temperature set point of the pre-heater and re-heater was checked that they are set to
150C.
7) The experiment was ready to carry on.

General shut-down procedure


1) The pre-heater and re-heater were switched off and the heaters were allowed to cool down
with the blower on.
2) The blower speed control knob was turned off.
3) Make sure all other switches on the control panel were switched off.
4) The main switch and power supply was switched off.
Experiment 1 Heating process:
1) The blower was switched on and ran at maximum air speed.
2) The pre-heater was switched on
3) Temperature and relative humidity at the inlet (AT1, AH1) and outlet (AT2, AH2) of the preheater was recorded after the process stabilizes.
4) The differential pressure reading of the pitot tube was recorded.
Experiment 2 cooling process:
1) Made sure that the Solenoid Valve with Receiver was selected.
2) The Expansion Valve (SV3) was selected on Solenoid Valve Selector.
3) The blower was switched on and run at maximum air speed.
4) Temperature and relative humidity at the inlet (AT1, AH1) and outlet (AT2, AH2) of the
5

cooling coil was recorded when a steady state was reached.


5) The differential pressure reading of the pitot tube was recorded.
6) The refrigerant temperatures (TT1, TT2, TT3, TT4) and the pressure (P1. P2) was recorded.

Experiment 3: Humidification Process


1) The blower was switched on and ran at 15% of the maximum air speed.
2) The steam humidifier was switched on.
3) Temperature and relative humidity at the inlet (AT1, AH1) and outlet (AT2, AH2) of the fan
was recorded when a steady state is achieved.
Experiment 4: Dehumidification Process
1) Make sure that the Solenoid Valve with Receiver was selected.
2) The Expansion Valve (SV3) was selected on Solenoid Valve Selector.
3) The blower was switched on and run at 15% maximum air speed.
4) The condensing unit was switched on.
5) Temperature and relative humidity at the inlet (AT1, AH1) and outlet (AT2, AH2) of the
cooling coil was recorded when a steady state was reached.
6) The differential pressure reading of the pitot tube was recorded.
7) The refrigerant temperatures (TT1, TT2, TT3, TT4) and the pressure (P1. P2) was recorded.

4.0 Experimental Apparatus:

Figure 2.0: Schematic Diagram of Air Conditioning Module


4.1 Specifications:
A) Air duct:
Air Duct with a cross-sectional dimension of 150mm x 150mm is used.
B) Radial Fan:
A capacity of 255m3/ hour is used.
C) Pre-heater:
Preheater type finned is used. It has a power of 150 Watt. The preheater is protected from overheating by the mean of a temperature controller.
D) Reheater:
Reheater type finned is used. It can provide a power of 150 Watt. The reheater is protected from
over-heating by the mean of a temperature controller.
Temperature Sensor/ Transmitter:
7

E) Temperature sensor/transmitter
Temperature sensor/transmitter type RTD with a range of 0-100C and an output range of 420mA is used.
F) Humidifier:
Heater type steam generator with axial fan is used.
G) Inclined Manometer:
Inclined Manometer with a range of 0 to 1 WC is used.
H) Combined Temperature and Humidity Sensor
A range of 0 to 50C and 5% to 95% RH, with an output range of 0-10V is used.
I) Orifice
The orifice has a diameter of 40mm. Pitot tube is used to calculate the velocity of the orifice as
follow:
V=0.598
4.2 Overall Dimensions
Height: 0.60 m
Width: 1.00 m
Length: 0.35 m

5.0 Results:
Differential Pressure Reading: 370Pa
Experiment 1: Heating Process
Temperature ( )

Relative Humidity (%)

Inlet

Outlet

Inlet

Outlet

AT1

AT2

AH1

AH2

25.7

28.0

49.6

42.9

Table 1.0

Experiment 2: Cooling Process

Expansion Valve (SV3) on Solenoid Valve Selector (Module)


Temperature (

Relative

Humidity (%)

Inlet
AT1
26.4

Outlet
AT2
14.1

Inlet
AH1
41

Outlet
AH2
84.2

Refrigerant Temperature ( )

Pressure
(kgf/cm2)

TT1
11.8

TT2
36.0

Table 2.0

Experiment 3: Humidification Process


9

TT3
36.6

TT4
9.3

P1
9

P2
2.6

Temperature ( )
Inlet
AT1
25.3

Relative Humidity (%)

Outlet
AT2
30.3

Inlet
AH1
40.9

Outlet
AH2
34.3

Table 3.0

Experiment 4: Dehumidification Process


Expansion Valve (SV3) on Solenoid Valve Selector (Module)
Temperature (

Relative

Humidity (%)

AT1
26.2

AT2
13.2

AH1
40.9

AH2
88.0

Refrigerant Temperature ( )

Pressure
(kgf/cm2)

TT1
TT2
26.2
13.2
Table 4.0

TT3
40.9

TT4
88.0

P1
9.25

P2
2.60

Experiment 5: Humidity Regulation


Expansion Valve (SV3) on Solenoid Valve Selector (Module)
Temperature (

Relative

Humidity (%)

AT1
26.0

AT2
22.4

AH1
39.5

AH2
22.4

Refrigerant Temperature ( )

Pressure
(kgf/cm2)

TT1
10.6

TT2
35.2
Table 5.0

Calculations:
Unit Conversion:
Converting temperature unit C to K:
For example, (26C +273) K = 299K
10

TT3
36.8

TT4
9.0

P1
8.50

P2
2.30

Density of air, :1.2kg/m3


Differential Pressure: 370 Pa
To calculate velocity of air across orifice,
Velocity, v = 0.598

= 0.598

2 P

2(370 kg /m2 s)
1.2 kg/m3

= 14.7m/s
To calculate the cross sectional area of orifice,
2
Area, A= r
2
= X (0.04 m/2)

= 1.2566X 10-3m2
To calculate mass flow rate of air,
Mass flow rate , m=V A
1.2kg/m3 X 14.7m/s X 1.2566X 10-3m2
= 0.02262kg/s
Experiment 1: Heating Process
To calculate heat transferred to the air,
m(h
2h1 )
Q=

= 0.02262kg/s (54kJ/kg- 50kJ/kg)


= 0.2601kW
Experiment 2: Cooling Process
To calculate cooling power of the cooling coil,
Power=m
( h 1h2 )
=0.02262/s (46.5kJ/kg-35kJ/kg)
=0.3168 kW
11

COP of cooling power(SV 3)=

m
( h1 h2 )
=1.21
0.2601

Experiment 3.0: Humidification Process


Absolute humidity:
w 1 = 0.009
w 2= 0.0091
To calculate enthalpy of vaporization,
m
Cp T
Q=

= 0.02262kg/s X 1.005kJ/kg.K X (303.3K-298.3K)


= 0.1137kW
To calculate cooling power of the cooling coil,
Power=m
( h 1h2 )
= 0.02262kg/s (54kJ/kg- 48.5kJ/kg)
= 0.1241 kW

Experiment 4: Dehumidification Process


Absolute humidity:
w 1= 0.009
w 2=0.0082
To calculate cooling power for cooling coil,
Power=m
( h 1h2 )
= 0.02262kg/s (49kJ/kg- 34kJ/kg)
= 0.3393kW

12

Experiment 5: Humidity regulation


COP of humidification=

m
( h1 h2 ) 0.02262( 44.530)
=
=2.64
0.1241 kW
0.1241

98

6.0 Discussions:

Starting off with the heating process, the readings show that the inlet temperature is less
compared to the outlet temperature while its opposite for the humidity which is less at the outlet
compared to the inlet. Now in theory temperature shouldnt have any effect on the absolute
humidity but the absolute humidity increases here, which may result from the fault in the sensors
for reading. In the experiment both the enthalpy and pressure increases while relative humidity
decreases as it is the ratio between the vapors in atmosphere compared to the saturation amount.
In the cooling process both the temperature and enthalpy decreases while relative humidity
increases rapidly. Absolute humidity remains constant here. So in contrast cooling process has
the total opposite readings compared to the heating process. The relative humidity increases due
to the difference degree of saturation. So lower the temperature, lower the amount of humidity
absorbed.
In the humidifying process, the temperature and enthalpy rises while the relative humidity
decreases. The absolute humidity increases by an insignificant amount of 0.0001 from 0.009 to
0.0091.Now in theory the relative humidity should be increasing during the humidifying process
but its decreases which can be put down to experimental error or maybe a cause of malfunction
in the humidifier.
In the dehumidifying process, the temperature and enthalpy decreases while the relative humidity
increases, and the absolute humidity decreases.
The results would be more accurate if the experiment had been repeated. The values would have
been more accurate. Along with repetition shutting down of the conditioning unit for at least 15
min before conducting the next process would result in much more accurate readings but this
action could not be completed due to the time constraints.

7.0 Conclusion:
13

From the experiment, we can conclude as the temperature and enthalpy increases, the relative
humidity decreases. The graph plotted on the psychrometric chart and experimental data support
the conclusion. The result also prove that it is the complete opposite, as to when temperature and
enthalpy decreases, the relative humidity increases. The absolute humidity should remain
constant for heating and cooling process but that was not the case in the heating process that
might be a result of a fault in sensors. For the humidifier the absolute and relative humidity
should increase with increase in temperature but that didnt happen for the latter ,which can be
put down to experimental error. For dehumidifier its the opposite of humidifier.

8.0 References:

1). What is Dehumidification? Cooling & Dehumidification, Heating & Dehumidification .


[ONLINE] Available at:http://www.brighthubengineering.com/hvac/41505-psychrometricprocesses-cooling-heating-and-dehumidification/. [Accessed 22 March 2015].
2) How Does Air Conditioning Work | Airconco [ONLINE] Available
at:http://www.airconco.com/how_does_air_conditioning_work/. [Accessed 20 March 2015]
3) Yunus A. Cengel, Michael A. Boles (7th edition)2011, Thermodynamics, An Engineering
Approach, McGrawhill.

14

S-ar putea să vă placă și