Sunteți pe pagina 1din 22

ZAR ZALAU

SYSTEM 01 -CONFORMITY SHEET

Technical
Specification

RCD01 LOAD BREAK SWITCH Q1 Q2

Sheet N :1

By : TERRISSE/HAUTA

Order N :

Date : 14.12.O4

ST

Gs1

Folio 1

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01


N

ACCEPTED

CHECKS CARRIED OUT

01

- Impulse withstand voltage

125 kV peak

02

- Power frequency withstand voltage

50 kV rms/1 min

03

- Internal arc withstand (kA 1s)


sec

12.5kA rms/1

04

- rated current

400 A

05

- busbar rated current

400 A

06

- index of protection IP 215

07

State of cleanliness

08

3 Voltage indicator presence

09

Switch test : open / close

11

Open and Closed position contacts remote control of the switch

12

Homopolar fault remote control

14

Tor captor homopolar presence

15

Homopolar fault

16

Mechanical interlock (safety) devices presence and test

17

Wiring control.

18

Peephole of thermographie

19

On voltage

10

13

20
21

REFUSED

ZAR ZALAU

SYSTEM 01 -CONFORMITY SHEET

Technical
Specification

RCD01- PROTECTION TRANSFORMER Q3;Q4;Q5;Q6.

Sheet N : 2

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Gs1

Folio 2

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01


N

ACCEPTED

CHECKS CARRIED OUT

01

Verification of characteristics : operating voltage 20kV rated voltage 24kV

02

- Impulse withstand voltage

125 kV peak

03

- Power frequency withstand voltage


min

50 kV rms/1

04

- Internal arc withstand (kA 1s)

12.5 kA rms/1 sec

05

- rated current

400 A

06

- busbar rated current

400 A

07

- index of protection IP 215

08

State of cleanliness

09

3 Voltage indicator presence

10

Switch test : open / close

11

Manual tripp push button

12

Presence of coil to triping

13

Temperature alarm first stage (140) separate box

14

Temperature triping second stage (150) separate box

15

Triping on H.V. mealting fuse

16

Wiring control. LV monitoring cables -

17

Open and Closed position contacts remote control of the switch

18

Temperature alarm remote control + local

19

Temperature triping remote control + local.

20

Triping remote control.

21

Presence of fuse with hammer

22

Presence of 3 spare fuse

23

Mechanical interlock (safety) devices presence and test

24

H.V. & L.V. wiring

25

On voltage

REFUSED

ZAR ZALAU

SYSTEM 01 -CONFORMITY SHEET

Technical
Specification

RCD01 DRY TRANSFORMER T1;T2;T3;T4.

Order N : 6168 on 13/02/2004

Project N A130050 R

Sheet N : 3

Date : 14.12.O4

By : TERRISSE/HAUTA

ST

Gs1

Folio 3

Item and location : UNIT SUBSTATION RCD01


N

CHECKS CARRIED OUT

ACCEPTED

01

Verification of the characteristics on the identification plate

02

Conformity with the data sheet TRIHAL type from Scneider

03

Transformer power

04

Primary voltage

20 kV

05

No load secondary voltage

410/230 V

06

Frequency

50 Hz

07

Insulation level

125/50 kV

08

Coupling

Dyn 11

09

Setting taps

0 /+ 2.5 / + 5 %

10

Manufacturer Schneider

11

Year of manufacture 2004

12

Serial Number

13

Verification of the equipment and accessories

14

Stage of cleanliness

15

Presence of temperature indicator + contact temperatureC

16

temperature adjustment :

1600 kVA

17

alarm

140C

tripping

150C

18

faults simulation Temperature alarm

19

faults simulation Temperature tripping of the protection transformer cell

20

Voltage adjustment position ............. value .......... % 20KV

21

Presence of lifting rings

22

Presence of rollers

23

Test reports available

24

Presence of fault transformer signalisation in the separate box

25

Presence of grill protection to avoid direct contact with the other

26

Presence of the key on the door

27

On voltage

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB01

Sheet N : 4

By : TERRISSE/HAUTA

Date : 14.12.O4

Order N : 6168 on 13/02/2004

ST

Gs1

Folio 4

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09520 B


N

CHECKS CARRIED OUT

ACCEPTED

General characteristics
01

Okken type from Schneider

02

Earthing :

03

Marking

04

Tightening

05

General appearance (cleanliness, paint, finish)

Earthing connection (door, envelop..)

General circuit breaker CB01


06

2500 A ICC 50 kA - 3 poles adjustment setting

07

adjustment setting IR

08

Current transformers :

09

Mesure device : PM 500 (A V P ) + remote control

10

Measurement socket

11

Open and Closed position contacts remote control of the main circuit breaker

12

Operating handle

13

Draw out on carriage type circuit breaker

14

Mechanical interlock HT BT (safety) devices presence and test

15

On voltage

2500

Im

7000 A 0.2s

Number 4 class 1

16
17
18
19
20
21

Secondary feeder circuit breakers

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB01

Sheet N : 5

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Gs1

Folio 5

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09520 B


N
20

Padlock interlocking

21

Outgoing feeder No 330 BD 01

22

23

24

25

26

27

ACCEPTED

CHECKS CARRIED OUT

X
CB02

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 Ka

Outgoing feeder No 330 BD 03

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

CB05

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 Ka

X
Dec STR23

CB06

X
X

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 Ka

X
Dec STR23

CB07

X
X

Mark :Schneider

Type :NS100 H

N Poles : 3

Setting Ir : 63 A

setting Im 630A

ICC 70 Ka

Outgoing feeder No 125 DPB 02

Dec STR23

Type :NS630 N

Outgoing feeder No RCD1 DPB 02

CB04

Mark :Schneider

Outgoing feeder No 330 BD 13

X
X

Type :NS400 N

Outgoing feeder No 330 BD 10

Dec STR23

CB03

Mark :Schneider

Outgoing feeder No 330 BD 07

X
Dec STR22

CB08

X
X

Mark :Schneider

Type :NS800 N

N Poles : 3

Setting Ir : 800 A

setting Im 5600A

ICC 50 Ka

X
Dec microl

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB01

Sheet N : 6

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Folio 6

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09520 B

28

29

Outgoing feeder No Capacitor bank

CB09

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

Outgoing feeder No SPARE

Dec STR23

CB10

X
X

Mark :Schneider

Type :NS160 N

N Poles : 3

Setting Ir :

setting Im A

ICC 36 kA

X
Dec STR22

Gs1

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB02

Sheet N : 7

By : TERRISSE/HAUTA

Date : 14.12.O4

Order N : 6168 on 13/02/2004

ST

Gs1

Folio 7

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09521 B


N

CHECKS CARRIED OUT

ACCEPTED

General characteristics
01

Okken type from Schneider

02

Earthing :

03

Marking

04

Tightening

05

General appearance (cleanliness, paint, finish)

Earthing connection (door, envelop..)

General circuit breaker CB01


06

2500 A ICC 50 kA - 3 poles adjustment setting

07

adjustment setting IR

08

Current transformers :

09

Mesure device : PM 500 (A V P ) + remote control

10

Measurement socket

11

Open and Closed position contacts remote control of the main circuit breaker

12

Operating handle

13

Draw out on carriage type circuit breaker

14

Mechanical interlock HT BT (safety) devices presence and test

15

On voltage

2500

Im

7000 A 0.2s

Number 4 class 1

16

Coupling circuit breaker


17

Fixe part supplied only to avoid to put 2 transformers in parralelle

Power connection with MDB 01

18
19

Secondary feeder circuit breakers

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB02

Sheet N : 8

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Gs1

Folio 8

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09521 B


N
20

Padlock interlocking

21

Outgoing feeder No 330 BD 02

22

23

24

25

26

27

ACCEPTED

CHECKS CARRIED OUT

X
CB02

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

Outgoing feeder No 330 BD 04

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

Dec STR23

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

CB05

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

CB06

Mark :Schneider

Type :NS160 N

N Poles : 3

Setting Ir 160 A

setting Im 1600A

ICC 36 kA

Outgoing feeder No 330 DPB02

X
X

Mark :Schneider

Type :NS160 N

N Poles : 3

Setting Ir 160 A

setting Im 1600A

ICC 36 kA

X
X
X

Dec STR22

CB07

Mark :Schneider

Outgoing feeder No 125A GF 01

CB04

Outgoing feeder No 330 DPB01

X
X

Type :NS400 N

Outgoing feeder No 330 BD 11

Dec STR23

CB03

Mark :Schneider

Outgoing feeder No 330 BD 08

X
X
X

Dec STR22

CB08

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB02

Sheet N : 9

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Folio 9

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09521 B

28

29

30

Outgoing feeder No Capacitor bank

CB09

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

Outgoing feeder No 125 DPB 01

X
X

Type :NS800 N

N Poles : 3

Setting Ir : 800 A

setting Im 5600A

ICC 50 kA

X
Dec microl

CB11

X
X

Mark :Schneider

Type :NS160 N

N Poles : 3

Setting Ir :

setting Im A

ICC 36 kA

Dec STR23

CB10

Mark :Schneider

Outgoing feeder No SPARE

X
Dec STR22

Gs1

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB03

Sheet N : 10

By : TERRISSE/HAUTA

Date : 14.12.O4

Order N : 6168 on 13/02/2004

ST

Gs1

Folio10

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09522 B


N

CHECKS CARRIED OUT

ACCEPTED

General characteristics
01

Okken type from Schneider

02

Earthing :

03

Marking

04

Tightening

05

General appearance (cleanliness, paint, finish)

Earthing connection (door, envelop..)

General circuit breaker CB01


06

2500 A ICC 50 kA - 3 poles adjustment setting

07

adjustment setting IR

08

Current transformers :

09

Mesure device : PM 500 (A V P ) + remote control

10

Measurement socket

11

Open and Closed position contacts remote control of the main circuit breaker

12

Operating handle

13

Draw out on carriage type circuit breaker

14

Mechanical interlock HT BT (safety) devices presence and test

15

On voltage

2500

Im

7000 A 0.2s

Number 4 class 1

16

Coupling circuit breaker


17

Fixe part supplied only to avoid to put 2 transformers in parralelle

Power connection with MDB 04

18
19

Secondary feeder circuit breakers

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB03

Sheet N : 11

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Gs1

Folio11

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09522 B


N
20

Padlock interlocking

21

Outgoing feeder No 330 BD 05

22

23

24

25

26

27

ACCEPTED

CHECKS CARRIED OUT

X
CB02

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

Outgoing feeder No 330 BD 06

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

CB04

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

CB05

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

CB06

X
X

Mark :Schneider

Type :NS100 H

N Poles : 3

Setting Ir 100 A

setting Im 1000A

ICC 70 kA

X
Dec STR22

CB07

Mark :Schneider

Type :NS250 N

N Poles : 3

Setting Ir 250 A

setting Im 1750A

ICC 36 kA

Outgoing feeder No 330DPB 04

X
X

Mark :Schneider

Outgoing feeder No 330 DPB03

X
X

Mark :Schneider

Outgoing feeder No RCD1 DPB01

X
X

Type :NS630 N

Outgoing feeder No 330 BD 12

Dec STR23

CB03

Mark :Schneider

Outgoing feeder No 330 BD 09

X
X
Dec STR22

CB08

Mark :Schneider

Type :NS100 H

N Poles : 3

Setting Ir 100 A

setting Im 1000A

ICC 70 kA

X
X
X

Dec STR22

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board MDB03

Sheet N : 12

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Folio12

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09522 B

28

29

30

31

Outgoing feeder No 125 GF 02

CB09

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 Ka

Outgoing feeder No 330 LP 01

X
X

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

X
Dec STR23

CB11

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

Outgoing feeder No SPARE

Dec STR23

CB10

Mark :Schneider

Outgoing feeder No Capacitor bank

X
Dec STR23

CB12

X
X

Mark :Schneider

Type :NS250 N

N Poles : 3

Setting Ir A

setting Im A

ICC 36 kA

X
Dec STR22

Gs1

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification

RCD01 Main distribution board

Sheet N : 13

By : TERRISSE/HAUTA

Gs1

MDB04

Date : 14.12.O4

Order N : 6168 on 13/02/2004

ST

Folio 13

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09523 B


N

CHECKS CARRIED OUT

ACCEPTED

General characteristics
01

Okken type from Schneider

02

Earthing :

03

Marking

04

Tightening

05

General appearance (cleanliness, paint, finish)

Earthing connection (door, envelop..)

General circuit breaker CB01


06

2500 A ICC 50 kA - 3 poles adjustment setting

07

adjustment setting IR

08

Current transformers :

09

Mesure device : DIRIS PM 500 (A V P ) + remote control

10

Measurement socket

11

Open and Closed position contacts remote control of the switch

12

Auxiliary cabling contacts

13

Operating handle

14

Draw out on carriage type circuit breaker

15

Mechanical interlock HT BT (safety) devices presence and test

16

On voltage

2500

Im

22800 A

Number 4 class 1

17
Coupling circuit breaker
18

Fixe part supplied only to avoid to put 2 transformers in parralelle

19

Auxiliary contacts cabling

Secondary feeder circuit breakers

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification
Sheet N : 14

RCD01 Main distribution board


By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

ST

Gs1

MDB04

Date : 14.12.O4

Folio 14

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09523 B


N

CHECKS CARRIED OUT

20

Padlock interlocking

21

Outgoing feeder No 330 BD 50

22

23

24

25

26

27

ACCEPTED
X

CB02

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

Outgoing feeder No 330 BD 51

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

N Poles : 3

Setting Ir : 630 A

setting Im 4410A

ICC 45 kA

X
Dec STR23

CB05

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4410A

ICC 45 kA

X
Dec STR23

CB06

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4410A

ICC 45 kA

X
Dec STR23

CB07

X
X

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

Outgoing feeder No 330 BD 56

Dec STR23

Type :NS630 N

Outgoing feeder No 330 BD 55

CB04

Mark :Schneider

Outgoing feeder No 330 BD 54

X
X

Type :NS400 N

Outgoing feeder No 330 BD 53

Dec STR23

CB03

Mark :Schneider

Outgoing feeder No 330 BD 52

X
Dec STR23

X
X

CB08

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4410A

ICC 45 kA

X
Dec STR23

REFUSED

ZAR ZALAU

SYSTEM 02 -CONFORMITY SHEET

Technical
Specification
Sheet N : 15

RCD01 Main distribution board


By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

ST

MDB04

Date : 14.12.O4

Folio 15

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09523 B

28

29

30

Outgoing feeder No 330 BD 57

CB09

Mark :Schneider

Type :NS400 N

N Poles : 3

Setting Ir : 400 A

setting Im 2800A

ICC 45 kA

Outgoing feeder No 330 BD 58

Dec STR23

X
X

CB10

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4410A

ICC 45 kA

Outgoing feeder No Capacitor bank

X
Dec STR23

CB11

X
X

Mark :Schneider

Type :NS630 N

N Poles : 3

Setting Ir : 630 A

setting Im 4400A

ICC 45 kA

X
Dec STR23

Gs1

ZAR ZALAU

SYSTEM 01 -CONFORMITY SHEET

Technical
Specification

RCD01 CAPACITOR BANK 01 02 03 04

Sheet N : 16

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

Gs1

Folio 16

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01 CAPACITOR BANK 01 02 03 - 04


N

CHECKS CARRIED OUT

ACCEPTED

Presence of capacitor bank 01

Presence of capacitor bank 02

Presence of capacitor bank 03

Presence of capacitor bank 04

State of cleanliness of equipment

Cabinet with front doors

Ventilation grills or other

Circuit protection devices

Presence and rating of three pole contactor ( 5 pieces )

10

Connection space

11

Presence of slow discharge devices

12

Presence of fast discharge devices

13

Position varimetric adjuster accessible on the front face with doors closed

14

Wiring connections

15

Fixation of device inside the panel

16

Presence of earth terminal

17

Cabling and equipment marking

18

Presence of Danger - Electric Shock placard on front face

19

Presence of lifting rings

20

Presence of drawing inside the panel

21

Check correct operation of varimetric adjuster in manual and automatic

22

Setting power factor 0,95

23

Connection and setting of Capacitor bank N04

24

On voltage batteries 1 2 3

25

On voltage Battery 4

REFUSED

ZAR ZALAU

SYSTEM 01 -CONFORMITY SHEET

Technical
Specification

RCD01 - SUBSTATION BUILDING

Sheet N : 17

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 25 01O5

ST

Gs1

Folio 17

Project N A130050 R

Item and location : UNIT SUBSTATION RCD01


N

CHECKS CARRIED OUT

ACCEPTED

01

State of cleanliness inside aspect :

02

Exterior wall aspect

03

Roof waterproof

04

Insolation of building (water in the gutter)

05

Painting walls and ceiling

06

Soil paint with anti dust paint

07

Presence of Anti panic barre on the door

08

Safty equipment following data scheet

09

Presence of Danger - Electric Shock placard on the doors

10

Presence and good location of normal Inside lighting (lighting panel + installation)

11

Presence and good location of Emergency lighting

12

Presence , good location and characteristic of UPS for workshop Emergency lighting

13

Presence and good location of outlet

14

Presence and good location of ventilation transformers room

15

Presence and good location of ventilation in the substation

16

Presence of extingwisher

17

Presence of fire detection installation

18

Presence of outside lighting panel

19

Earthing installation and connection around the substation

20

Gutter cover ( to be installed )

21

State of cleaness of the floor

22
23
24

REFUSED

ZAR PROJECT

SYSTEM 01 -CONFORMITY SHEET

Technical
Specification

20 KV SPECIAL LINKS RCD01

Sheet N : 18

By : TERRISSE/HAUTA

Date : 14.12.O4

ST

PG

Folio : 18

Order N : 6168 on 13/02/2004


Item and location : High voltage installation
N
1

CHECKS CARRIED OUT

ACCEPTED

HV cable tray and HV conducts :

- laying

HV cable 20 kV 3 x 1 x 185 copper 24 kV + ground (no insulated copper) :

- laying in distribution manhool

- marking in distribution manhool

- laying on cable trays

- marking on cable trays

- connection to substation

- On voltage

REFUSED

To be done

ZAR ZALAU

SYSTEM 04 - CONFORMITY SHEET

Technical
Specification

LIGHTING EXTERIOR CABINET RCD 01 LP 01

Sheet N : 19

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

ST

Date : 14.12.O4

GS1

Folio : 19

Project N A130050 R:

Item and location :Outside lighting panel


N

CHECKS CARRIED OUT

ACCEPTED

General appearance

Cabinet dimensions, extension possibility 30%

Cladding protection index IP 55

Presence of padlockable door or fascias

Presence of document pocket

Attachment of cladding

Rating of general switch 63A

Presence of padlockable interlock system on general load break switch


(possibility of 3 padlocks)

Presence of protection of general load break switch against direct contacts

10

Busbar rating

11

Presence of protection of busbar against direct contacts

12

Verification of number of circuit breaker outgoing feeders

13

Verification of ratings in relation to the diagram

14

Circuit breaker breaking capacity ( 10 20 KA )

15

Type of circuit breaker

16

Verification of wire colours

17

Verification of wire tightening

18

Verification of wire marking

19

Incoming feeder cables connection space

20

Outgoing feeder cable connection space

21

Verification of protection conductors connections to earth bar

22

Verification of correct earthing continuity

23

Attachment and marking of switchgear

24

Marking and colour of cabinet

25

On voltage

REFUSED

ZAR PROJECT

SYSTEM 03 - CONFORMITY SHEET

Technical
Specification

UPS SUBSTATIONS UNIT FOR EMERGENCY LIGHTING

Sheet N : 20

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

PG

Folio : 20

Project N :

Item and location : RCD O1.

CHECKS CARRIED OUT

ACCEPTED

1
2

Verification of earthing to terminals

Verification of battery type

Verification of number of items

Verification of correct battery connection

Verification of dry battery

General fault inverter reported to terminals

Verification of conformity of cabling and connections

Test report available

10

Verification of correct operation of assembly

11

On voltage

REFUSED

ZAR ZALAU

SYSTEM 02 - CONFORMITY SHEET

Technical
Specification

LOW VOLTAGE DISTRIBUTION PANEL BOARDDPB 01

Sheet N : 21

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

GS1

Fol 21

Project N :

Item and location : RCD01 substation


N

CHECKS CARRIED OUT

ACCEPTED

General appearance, paint, marking

Dimensions, extension possibilities 30 %

Incoming / outgoing feeder cables connection space

Cladding protection index IP55

Door closing, padlock system

Cable glands

Cabinet attachment device

Attachment and marking of switchgear

Load break switch :

- breaking capacity , rating, direct contacts protection, padlocking possibility

Outgoing feeder circuit breakers :

- quantity

- breaking capacity

- rating

- type

Cabling :

- colour

- cross-section

- tightening

- marking

13

Earthing bar, protection conductors connections

14

Earthing

15

Busbar

16

On voltage

10

12

REFUSED

ZAR ZALAU

SYSTEM 02 - CONFORMITY SHEET

Technical
Specification

LOW VOLTAGE DISTRIBUTION PANEL BOARDDPB 02

Sheet N : 22

By : TERRISSE/HAUTA

Order N : 6168 on 13/02/2004

Date : 14.12.O4

ST

GS1

Fol 22

Project N :

Item and location : RCD01 substation


N

CHECKS CARRIED OUT

ACCEPTED

General appearance, paint, marking

Dimensions, extension possibilities 30 %

Incoming / outgoing feeder cables connection space

Cladding protection index IP55

Door closing, padlock system

Cable glands

Cabinet attachment device

Attachment and marking of switchgear

Load break switch :

- breaking capacity , rating, direct contacts protection, padlocking possibility

Outgoing feeder circuit breakers :

- quantity

- breaking capacity

- rating

- type

Cabling :

- colour

- cross-section

- tightening

- marking

13

Earthing bar, protection conductors connections

14

Earthing

15

Busbar

16

On voltage

10

12

REFUSED

S-ar putea să vă placă și