Medium power busbar trunking

Canalis KS (100 to 800 A)


For high density distribution in industrial and commercial buildings

Presentation

Run components

Connection components,
feed units and end covers

7 ratings : 100, 160, 250, 400, 500, 630 and 800 A


4 live conductors. Straight lengths
in fixed lengths of 1.5, 2. 3 and 5 m,
cut to length for 0.5 to 2 m.

Feed the KS trunking


from either end
or along a run.

11030/2

Te

Components for
changing direction
For adapting the Canalis KS
to installation requirements :
elbows, tees, crosses.

4
3
4

1
5

Fixing brackets

Tap-off units

Accessories

For fixing
KS trunking.

25 to 400 A connectors and


fused tap-off units, circuit-breakers
or modular equipment.

Dust and damp proofing accessories.

Te

11030/3

Medium power busbar trunking


Selection guide:
pages 11032/2 to 11032/4
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Description

General
Canalis KS is designed for medium power distribution with high tap-off density in industrial and commercial buildings
(exhibition halls, hypermarkets, office blocks, etc.).
The range is available in 7 ratings from 100 to 800 A.
The standard IP 52 degree of protection makes KS suitable for the majority of locations. It can be increased to IP 54 by
the addition of dust and damp proof blanking plates on the tap-off outlets.
Tapping off is via tap-off units. These units, from 25 to 400 A, can be safely removed while live.
100 to 250 A trunking can take connectors and tap-off units up to 250 A.
Higher rated trunking can take any tap-off unit from the range.

Run components
Straight distribution lengths
2
1

3 4

Straight lengths are designed to carry current and feed loads with low or medium power. The straight lengths form the
structure of the run. They comprise :
1 A casing of galvanised sheet steel, which is crimped closed.
This casing, shaped and ribbed by rolling, provides excellent resistance to bending and twisting.
Three casing widths cover the whole range. Casings are available in two finishes :
- 54 mm wide galvanised sheet steel for 100, 160 and 250 A ratings (sheet steel with RAL 7032 grey finish available
as an option).
- 75 mm wide sheet steel with RAL 7032 grey finish for 400 and 500 A ratings.
- 113 mm wide sheet steel with RAL 7032 grey finish for 630 and 800 A ratings.
2 4 live conductors of the same cross-section :
- Bimetal silver-plated copper/aluminium laminate for 100, 160 A ratings.
- Aluminium fitted with bimetal silver-plated copper/aluminium laminate riders electrically welded to junctions and tapoff positions for 250 to 800 A ratings.
The lamination is a patented process by which the copper and aluminium molecules are fused together under extreme
pressure.
3 Fibreglass reinforced polyester isolators, at 250 mm intervals.
These hold the conductors securely within the casing.
4 A special protected earth (PE) conductor of the same type as the live conductors with a cross-section 1/2 of the phase
cross-section. It is connected to the casing at each junction.
5 Tap-off outlets on both sides of the trunking, at 1 m intervals.
They are connected to the isolators to form a block, holding the bars. They have a shuttered outlet which is opened
and closed automatically when connectors or tap-off units are plugged in or removed.
6 A mechanical and electrical jointing device.
Electrical connection is via a block with spring and silver graphite contacts. This block absorbs the differential
conductor/casing expansion of each length equally.
For 100, 160 and 250 A ratings, it automatically and simultaneously connects all the live conductors, ensures
continuity of the protective earth conductor and its connection with the casing. For higher ratings (315 to 800 A), the
electrical connection is made by a 1/4 screw turn for each conductor.

11031/2

Te

Medium power busbar trunking


Selection guide:
pages 11032/2 to 11032/4
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Description

Special components
i Fire barrier length
To cross a fire partition, between two areas of a building. Fire resistance : 2 h (A120) conforming to ISO 834.
i Made to measure length
To alter the length of a run (for example, between two components for changing direction). These components are
manufactured, on request, from 500 mm to 1995 mm, in multiples of 5 mm. They do not have tap-off outlets.

Connection components and feed units


Feed units
To feed a KS run by cables or directly from a distribution panel. The feed can be from one end (end feed) or along a run
(centre feed). They can be connected by aluminium or copper cables fitted with suitable cable lugs. There is an undrilled
aluminium gland plate which will accept cable glands. This plate can be replaced by a plate fitted with 1 to 3 cable clamps
depending on the rating (to be ordered separately).
1 End feed box
For 100 A busbar trunking only. It
is mounted to the left or right of a
straight length and fitted with a
no. 29 cable gland.

2 End feed units


For 100 to 250 A ratings : mounted
to the left or right of a straight
length, by inverting the initial
section of the trunking.
For 400 to 800 A ratings : available
in left or right hand versions.
3 Centre feed unit
Through run type (1 cable feeds
the right and left sections). It is
mounted along the run, between 2
straight lengths.
4 Flange feed unit
Fitted with splayed bars and a
mounting plate. It is used for
connection to a distribution panel.
It can be mounted at either end of
a component.

Te

11031/3

Medium power busbar trunking


Selection guide :
pages 11032/2 to 11032/4
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Description

Connection components and feed units (continued)


KV-KS connector
The KV-KS connector is fitted with a
KV end length at one end and a KS
end length at the other.
Due to its flexible design, it ensures
direct connection from a feed run to a
distribution run and reduces any risk
caused by alignment faults.

End cover
The end cover protects and isolates
the ends of the conductors. It is
mounted on the last length.
Three products cover the entire KS
range : 100 to 250 A, 400 and 500 A,
630 and 800 A.

Components for changing direction


2

1 Edgewise elbow.
One model for each size of
casing for turning to left or right.
2 Flat elbow
Two models for each size of
casing (one ascending, one descending).
Flat and edgewise elbows can
be manufactured, on request,
with made to measure connection lengths, with multiple
angles, with built-in fire barrier,
etc. (please consult your Regional Sales Office).
3

3 Edgewise tee and cross


For vertical branches on the main
run.

Fixing devices
(630
- 800)
1 (630
- 800)
(400500)
(315500)
(100250)
(100250)

1 Universal brackets
These brackets are used to fix the
distribution run to the structure of
the building, directly or via a
threaded rod, a bracket, etc.
There is one model for each size of
casing which can be used for all
mounting methods : ceilingmounted, suspended, wallmounted, etc.
Suspension on chains or steel cables is not recommended.
It is advisable to leave a space of 3
m between each bracket.

11031/4

Te

Medium power busbar trunking


Selection guide :
pages 11032/2 to 11032/4
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Description

Tap-off units
These are used for instant connection of loads or secondary runs (for example, for low power distribution using Canalis
KN). The connectors and tap-off units conform to installation standards and regulations whatever type of neutral point
connection is used (TT, IT, TNS or TNC).
i They can be removed and moved whilst live, with no load.
i The tap-off outlets are opened and closed automatically when units are plugged in or removed.
i With the cover open, no live part can be accessed. Degree of protection IP 2X.
i Connectors and tap-off units are made in two versions :
- Protected version, degree of protection IP 40, suitable for most industrial and commercial applications,
- Dust and damp proof version, degree of protection IP 54, for very dusty locations and environments, or those subject
to water splashes.
A Tap-off unit
- Isolation is achieved by
unplugging the tap-off.
- The electrical equipment and
connection terminals can only be
accessed with the tap-off
unplugged.
- A safety device prevents the tapoff being plugged into the trunking
if the cover is not in place.
A
B
B Tap-off units with isolator
Isolation (AC22 to AC 20) is
achieved by opening the cover of
the unit. A number of safety devices
prevent the following :
- Connection of the tap-off unit if
the cover is closed,
PE =
- Opening of the cover if the unit is
not locked to the trunking,
- Removal of the unit if the cover is
closed,
- Opening of the cover to position
I (by locking) on units which have
a switch or circuit-breaker.
These tap-off units will take
accessories such as an early break
contact on the cover, a sealing kit,
etc. (see page 11043/3).

Tap-off
1 Tap-off with fuse carrier
The tap-off is protected by means of
fuses (not supplied).
They can be fitted with carriers for the
following fuses :
- NF 10 x 38
- BS type 88A1
- DIN type Neozed DO1
1
2

2 Tap-off for modular equipment


This tap-off will take most 17.5 mm
modular equipment.
- Nominal current : 25 A,
- Capacity : 4 modules,
- With window in front panel (equipment
can be seen and accessed).

Te

11031/5

Medium power busbar trunking


Selection guide :
pages 11032/2 to 11032/4
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Description

Tap-off units (continued)


Fused tap-off units

These fused tap-off units are designed


to protect the tap-off by means of
fuses (not supplied).
They can be fitted with carriers for the
following fuses :
- NF and DIN, 50 to 630 A,
- BS, 30 to 160 A,
- VDE and DIN, 25 to 400 A.
Versions for NF fuses can be fitted
with a single phase protection device.
1 25 to 125 A fused off-load tap-off unit.
2 160 A fused off-load tap-off unit.
3 250 to 400 A fused off-load tap-off
unit.
These units can only be mounted on
trunking which is installed horizontally
on edge.
To make installation easier, it is
performed in two stages :
- The unit is hooked onto the trunking,
then automatically located in front of
the tap-off outlet by moving it
sideways.
- The fixing brackets are then locked
and the mobile power block plugged
in, using an internal device.

Tap-off units with isolator for modular equipment


These units will take most 17.5
modular equipment. They have a
window in the front panel (equipment
can be seen and accessed).
There are two ratings :
- 50 A nominal current, capacity 7.5
modules,
- 100 A nominal current, capacity 11
modules.

11031/6

Te

Medium power busbar trunking


Selection guide :
pages 11032/2 to 11032/4
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Description

Tap-off units for Merlin Gerin circuit-breaker


These units are designed to take Merlin
Gerin Compact NS circuit-breakers :
- 100 to 400 A rating,
- Fixed, with front sockets,
- Version N, H or L,
- With or without residual differential
device,
- With rotary switch.
For other types of circuit-breaker :
please consult your Regional Sales
Office.
Tap-off unit for integral contactor-breaker
This unit is designed to take
Telemecanique integral contactorbreakers and inverters.

Isolating tap-off unit for industrial control and monitoring equipment


This unit has a Telequick mounting
plate and will take industrial control
and monitoring equipment (for
example, for controlling lighting in
hypermarkets).
Nominal current : 125 A.
Two sizes :
- With 300 x 300 mm mounting plate,
- With 400 x 600 mm mounting plate.

IP 54 dust and damp proofing accessories


In normal mounting position (edgewise,
horizontal installation) the degree of
protection of the KS range is IP 52.
In other positions (flat and vertical
installation) the degree of protection is
reduced to IP 50.
To achieve a higher degree of
protection, IP 54, the following
accessories must be added to the
straight lengths.

Edgewise horizontal installation


1 Each tap-off outlet which is not
being used should be fitted with a
sealed tap-off blanking plate.
Flat and vertical installation
1 Each tap-off outlet which is not
being used should be fitted with a
sealed tap-off blanking plate.
2 Each
junction
between
components should be fitted with a
jointing sleeve.

Te

11031/7

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Selection guide

Information required
i The types of load, and their characteristics and locations.
i The power source, and its characteristics and location.
i The structure of the premises (availability of fixing points
for trunking).
i Any influences external to the installation site.
(ambient temperature, dust, water, etc).

Distribution run layout


The siting of distribution runs depends on the position of the loads, the location of the general power supply and the
availability of fixing points.
A single distribution run can serve an area 5 to 8 metres wide.
Selection of the trunking according to the rated operating current Ib
Ib = total current x k1
Applications

Total current = sum of currents drawn by the loads on a run


k1 = average demand coefficient
k1
Rated operating current Ib
Selected trunking

Lighting, heating

0...100 A
100...160 A
160...250 A
315...400 A
400...500 A
500...630 A
630...800 A

Distribution (Engineering shop floors)


2 or 3 loads
0.9
4 or 5 loads
0.8
6...9 loads
0.7
10...40 loads
0.6
40 or more
0.5

KSi-10
KSi-16
KSi-25
KSi-40
KSi-50
KSi-63
KSi-80

Permissible current Iz according to the ambient temperature (at the installation site)
The nominal current Inc of the trunking is specified for an average daily ambient temperature of 35 C (and a maximum
of 40C). Depending on the actual temperature, an uprating or derating coefficient (f1) may be applied to the nominal
current Inc : see the characteristics on page 11032/5.
Checking the voltage drop
The voltage drop in Canalis KS is given in V/100m/A in the characteristics table on page 11032/5.
Polarity selection
3-pole distribution + N + PE (IT-TT-TNS)
i KSA-iiED4ii trunking
3-pole + N + PE
tap-offs possible, type 3-pole + PE
or 3-pole + N + PE

3L + PE
(IT-TT-TNS)

3L + N + PE
(IT-TT-TNS)
3-pole distribution + PEN (TNC)
i KSA-iiED4ii trunking
3-pole + PEN
tap-offs possible, type 3-pole + PEN (TNC) or 3-pole +
N + PE (TNS)..

3L + PEN
(TNC)

11032/2

Te

3L + N + PE
(TNS)

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Characteristics :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Selection guide

Protecting the trunking against overloads


To enable it to be extended, prefabricated busbar trunking is generally protected to its nominal current Inc (or to its
permissible current Iz if the f1 coefficient is applied according to the ambient temperature).
Protection using fuses
i Calculate the standard nominal current In of the fuse so that : In Inc
1
i Select the standard rating In which is equal to or immediately below.
Check that In Ib. If this is not the case, select the next highest rating of trunking.
Note : Protecting trunking using fuses is the same as limiting the rated operating current.
Protection using a circuit-breaker
i Select the circuit-breaker setting current Ir so that : Ib Ir Inc
Note : Protecting trunking using a circuit-breaker makes it possible to use the trunking at full capacity.

Electrodynamic protection against short-circuit currents


The electrodynamic withstand of the trunking should be taken into account when selecting a protective device
(permissible rated peak current).
i Determine (1) the 3-phase short-circuit current, prospective lcc 3 (KA) at the start of the Canalis KS.
i Check, on the current limitation curve of the selected protective device, that this limits the peak current (k) to a value
below the permissible rated peak current of the KS trunking.
Limited current Canalis current
Protection using a Merlin Gerin Compact circuit-breaker
The circuit-breaker/Canalis coordination table below gives the maximum short-circuit current for which the KS trunking
is protected, according to the type of circuit-breaker.
Prospective Icc 3, max (Ka rms) voltage 380/415 V
Canalis KS : rating (A)
Type of
Merlin Gerin
circuit-breaker

NS100

N
H

NS160

N
H
L

NS250

N
H
L

NS400

N
H
L

NS630

N
H
L

C801

N
H
L

C1001

N
H
L

100

160

25
25
L

25

20
20
20

36
70
70
36
55
55

250

400

500

630

45
70
150

45
70
150

800

36
70
150
45
45
45

45
70
150
45
70
150

40
40
55

50
50
50
50
50
80

(1) By calculation or using graphs, precalculated tables, etc.

Te

11032/3

Medium power busbar trunking


Selection guide :
page 11032/2
Caracteristiques :
page 11032/5
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3

Canalis KS (100 to 800 A)


Selection guide

Selection of IP degree of protection


External influences are taken into consideration when siting the installation.
The IP 52 degree of protection of Canalis KS means that it is suitable for installation in most industrial and commercial
locations.
For locations or sites which may be subject to water splashes in any direction the degree of protection should be raised
to IP 54, by installing KSE-80YB2 sealed tap-off blanking plates (see page 11043/2).

Changing levels in horizontal distribution

KSA-LP42
KSE-YAi
KSA-LP41

When trunking is mounted vertically,


the degree of protection at a junction
is IP 50.
To maintain a degree of protection
higher than IP 50, if required, each
junction installed vertically must be
fitted with a sealed jointing sleeve
(IP 54).
(See page 11043/2).

Tap-off units
n
There are 2 ranges of tap-off units.
i IP 40 protected range, low-cost and
suitable for normal industrial and
commercial environments.
i IP 54 dust and damp proof range, for
very dusty or damp environments.

KSA-ii IP 40

KSE-ii IP 54n

Mounting position
The preferred mounting position (for
horizontal distribution) is edgewise.
In some installation configurations
(false ceiling, false flooring, locations
with very little space, etc.) it may be
necessary to install trunking flat.
There are several suggestions for this.
Please consult your Regional Sales
Office.
Edgewise

Flat

Selecting the power supply


i 100 A end feed and 250 A (160 A)
feed unit
- mounted at either end of a run,
- all types of neutral system.

11032/4

Te

i 500 and 800 A feed unit.


Two types depending on position :
- right hand mounting (fig. A),
- left hand mounting (fig. B).
All types of neutral system. Connected
by means of lugs.

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
References :
pages 11033/3 to 11038/3
Dimensions :
pages 11040/2 to 11042/3
Type of trunking

Canalis KS (100 to 800 A)


Characteristics (1)

KSA-10

KSA-16

KSA-25

KSA-40

KSA-50

KSA-63

KSA-80

3 or 4

3 or 4

3 or 4

3 or 4

3 or 4

3 or 4

3 or 4

General Characteristics
Number of live conductors
Rated thermal current lth

100

160

250

400

500

630

800

Rated insulation voltage


conforming to IEC 158-1

660

660

660

660

660

660

660

Rated operating voltage

660

660

660

660

660

660

660

Rated frequency

Hz

50/60

50/60

50/60

50/60

50/60

50/60

50/60

m/m

1.059

0.490

0.216

0.142

0.091

0.074

0.045

Rb1phAverage resistance per


conductor at Ith
(ambient temperature 35 C)

m/m

1.395

0.661

0.294

0.190

0.123

0.101

0.061

XphAverage reactance per


conductor

m/m

0.457

0.233

0.192

0.112

0.116

0.070

0.071

ZphAverage impedance per


conductor

m/m

1.468

0.701

0.351

0.221

0.170

0.123

0.094

mm2

66

78

78

127

127

247

247

m/m

0.270

0.230

0.230

0.142

0.142

0.074

0.074

m/m

3.384

1.708

0.811

0.541

0.428

0.279

0.237

m/m

2.090

1.139

0.720

0.512

0.439

0.317

0.289

kA

13.6

22

28

49.2

55

67.5

78.7

Permissible rated short time current


(0.1 s)

kA rms

11

14

24.6

27.1

32.5

38.3

Maximum thermal limit

A 2s

6.8.106

20.2.106

100.106

354.106

733.106

1096.106

1798.106

IP 52
IP 54

IP 52
IP 54

IP 52
IP 54

IP 50
IP 54

IP 50
IP 54

IP 50
IP 54

Conductor characteristics
Live conductors
Rb0phAverage resistance per
conductor, cold state
(ambient temperature 20 C)

Protective conductor
Cross-section (copper equivalent)
Average resistance, cold state
(ambient temperature 20 C)
Fault loop impedance at 6 Ith
Between live conductors
Between live conductors and PE

Other Characteristics
Short-circuit withstand capacity
Permissible rated peak current
(3-phase)

Degree of protection
Standard
With sealing accessories
Standard
With sealing accessories
Voltage drop
For a power factor
cos of

0.7
0.8
0.9
1.0

Determination of permissible current


lz for a busbar trunking system,
according to ambient temperature
Average ambient temperature
Factor f1

In normal mounting position. Horizontal, edgewise installation.


IP 52
IP 52
IP 52
IP 52
IP 54
IP 54
IP 54
IP 54
Other positions : horizontal installation, flat, vertical installation.
IP 50
IP 50
IP 50
IP 50
IP 54
IP 54
IP 54
IP 54

Composite voltage drop, hot state, expressed in V/100 m/A for 3-phase 50 Hz current, with load distributed along the
run. Where the load is concentrated at the end of the feed run, the voltage drops are twice the values indicated in the
table.
V/100 m/A
0.112
0.055
0.030
0.0184
0.0146
0.0104
0.0081
V/100 m/A
0.120
0.058
0.030
0.0190
0.0146
0.0106
0.0079
V/100 m/A
0.126
0.060
0.030
0.0190
0.0140
0.0105
0.0074
V/100 m/A
0.121
0.057
0.025
0.0164
0.0107
0.0087
0.0053
Derating or uprating factor to be applied to the rated thermal current of the trunkingwhere the average daily ambient
temperature is other than 35 C.

10
15
20
25
30
35
40
45
50
1,10
1,08
1,06
1,04
1,02
1,00
0,97
0,94
0,91
(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2

55
0,88

Te

60
0,85

11032/5

KSA-iiEDiii

KSA-iiEF4ii

KSA-iiAB4ii

KSA-iiTC40
KSA-iiEZi
KSA-iiLC40
KSA-iiEDiii
KSB-iiFA2

KSE-80YB2

KSA/KSE-05SFii
KSA/KSE-iiDBi11
KSA-iiLC40
KSA-iiES4A
KSA-iiLP42

KSA-iiLP41
11033/2

Te

KSE-iiYAi

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
pages 11040/2 to 11040/5

Canalis KS (100 to 250 A)


References

Run components (IP 52/IP 54) (1)


Description

Rating
A

Length
mm

Number of
tap-offs

3L + N + PE and 3L + PEN
Reference

Weight
kg

Straight
lengths

100

5000

10

KSA-10EA450

19.050

3000

KSA-10EA430

11.900

5000

10

KSA-16EA450

21.200

3000

KSA-16EA430

13.200

5000

10

KSA-25EA450

25.000

3000

KSA-25EA430

15.500

2000

KSA-25ED420

10.650

1500

KSA-25ED415

8.350

Straight length 250 (2)


cut to length

5001995

KSA-25ES4A (3)

8.000/m

Fire barrier
length

12002200

KSA-25EF4A (3)

8.000/m

160

250

250 (2)

250(2)

Connection components and feed units (2)

N
KV0-25ER41001

Description

Rating
A

Connection
Mounting
Type/Max.cross-sect.

Reference

Weight
kg

End
feed unit

100

Terminals/
5 x 16 mm2

Left or right

KSA-10AB451

1.850

250 (2)

Lugs/240 mm2
(M10 screw)

Left or right

KSA-25AB42

7.200

Centre
feed unit

250 (2)
Lugs/240 mm2
(M10 screw)

Along the run

KSA-25BT42

12.00

Flange
feed unit

250 (2)

Bars
(M10 screw)

Left or right

KSA-25ER4

1.700

KV-KS
connector

250 (2)

KV0-25ER41001

End
cover

250 (2)

Left or right

KSB-25FA3

0.150

Components for changing direction (4)


Type

Rating
A

Mounting

Reference

Weight
kg

Elbows

250 (2)

Edgewise

KSA-25LC40

3.150

Flat upwards (1)

KSA-25LP41

5.000

Flat downwards (1)

KSA-25LP42

5.000

Tee

250 (2)

Edgewise

KSA-25TC40

4.300

Cross

250 (2)

Edgewise

KSA-25XC40

5.000

KSA-25EZ1

0.300

Fixing Device (Order in multiples of10)


Bracket

250 (2)

(1) IP 54 with sealing accessory : see page 11043/2.


(2) This reference is suitable for 100 and 160 A ratings.
(3) When ordering, state the required length in mm (in multiples of 5 mm) after the reference. Example : KSA-25ES4A L = 1250 mm.
(4) Other components IP 54 as standard, common to versions of 3L+N+PE and 3L+PEN straight lengths.

Te

11033/3

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
pages 11040/2 to 11040/5

Canalis KS (400 and 500 A)


References

Run components (IP 52/IP 54) (1)


Description

Rating
A

Length
mm

Number of
tap-offs

3L + N + PE and 3L + PEN
Reference

Weight
kg

Straight
lengths

400

5000

10

KSA-40ED450

40.000

3000

KSA-40ED430

25.000

5000

10

KSA-50ED450

44.500

3000

KSA-50ED430

28.000

2000

KSA-50ED420

20.000

1500

KSA-50ED415

15.900

Straight length 500 (400)


cut to length

500 to 1995

KSA-50ES4A (3)

15 kg/m

Fire barrier
length

1200 to 2340

KSA-50EF4A (3)

15 kg/m

500

KSA-40ED450

500 (400)

500 (400)

Connection components and feed units (2)


Description

Rating
A

Connection
Mounting
Type/Max cross-sect.

Unit
reference

Weight
kg

End
feed unit

500 (400)

Lugs/2 x 300 mm2


(M12 screw)

Right

KSA-50AB452

22.000

Left

KSA-50AB462

22.000
39.000

KSA-50AB452
Centre
feed unit

500 (400)

Lugs/2 x 300 mm2


(M12 screw)

Along the run

KSA-50BT402

Flange
feed unit

500 (400)

Bars
(M12 screw)

Left or right

KSA-50ER4

KV-KS
connector

500 (400)

KV0-50ER41001

End
cover

500 (400)

Left or right

KSB-50FA2

4.100

0.440

Components for changing direction (2)


Description

Rating
A

Mounting

Reference

Elbows

500 (400)

Edgewise

KSA-50LC40

9.860

Flat upwards (1)

KSA-50LP41

10.000

Flat downwards (1)

KSA-50LP42

10.000

N
KV0-50ER41001

Weight
kg

Tee

500 (400)

Edgewise

KSA-50TC40

15.000

Cross

500 (400)

Edgewise

KSA-50XC40

16.500

KSA-50EZ3

Fixing device (Order in multiples of10)


Bracket

500 (400)

(1) IP 54 with sealing accessory : see page 11043/2.


(2) Other run components IP 54 as standard, common to versions of 3L+N+PE and 3L+PEN straight lengths.
(3) When ordering, state the required length in mm (in multiples of 5 mm) after the reference.
Example : KSA-50ES4A L = 1250 mm.
11033/4

Te

0.330

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
pages 11040/2 to 11040/5

Canalis KS (630 and 800 A)


References

Run components (IP 52/IP 54) (1)


Description

Rating
A

Length
mm

Number of
tap-offs

3L + N + PE and 3L + PEN
Reference

Weight
kg

Straight
lengths

630

5000

10

KSA-63ED450

58.500

3000

KSA-63ED430

36.200

5000

10

KSA-80ED450

70.000

3000

KSA-80ED430

43.500

2000

KSA-80ED420

30.600

1500

KSA-80ED415

24.000

Straight length 800 (630)


cut to length

500 to 1995

KSA-80ES4A (3)

19.600/m

Fire barrier
length

1200 to 2340

KSA-80EF4A (3)

19.600/m

800
KSA-63ED450
800 (630)

800 (630)

Connection components and feed units (2)


Description

Rating
A

Connection
Mounting
Type/Max cross-sect.

Reference

Weight
kg

End
feed unit

800 (630)

Lugs/3 x 300 mm2


(M12 screw)

Right

KSA-80AB452

36.200

Left

KSA-80AB462

36.200
40.000

KSA-80AB452
Centre
feed unit

800 (630)

Lugs/3 x 300 mm2


(M12 screw)

Along the run

KSA-80BT402

Flange
feed unit

800 (630)

Bars
(4 x M10 screw)

Left or right

KSA-80ER4

KV-KS
connector

800 (630)

KV0-80ER41001

End
cover

800 (630)

KSB-80FA2

6.150

0.510

Components for changing direction (2)


Description

Rating
A

Mounting

Reference

Weight
kg

Elbows

800 (630)

Edgewise

KSA-80LC40

15.000

Flat upwards (1)

KSA-80LP41

13.700

Flat downwards (1)

KSA-80LP42

13.700

N
KV0-80ER41001

Tee

800 (630)

Edgewise

KSA-80TC40

18.240

Cross

800 (630)

Edgewise

KSA-80XC40

20.000

KSA-80EZ3

Fixing device (Order in multiples of 10)


Bracket

800 (630)

0.400

(1) IP 54 with sealing accessory : see page 11043/2.


(2) Other run components IP 54 as standard, common to versions of 3L+ N + PE and 3L+ PEN straight lengths.
(3) When ordering, state the required length in mm (in multiples of 5 mm) after the reference.
Example : KSA-80ES4A L = 1250 mm.

Te

11033/5

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11041/2

Canalis KS (100 to 800 A)


IP 40 protected tap-off units for NF fuses
References

Tap-off unit
Number of Conductors
Scheme (1)

3L + N + PE
Trunking
Tap-off

3L + Np + PE

TT TNS
TT TNS

3L + PEN

3L + PE

TNC
TNS

IT TT TNS
IT TT TNS

Tap-off scheme

(2)
Rating
A

Fuse
size

Connection
mm2

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

25

10 x 38

KSA-02CF5
0.400

KSA-02CF5
0.400

KSA-02CF5
0.400

KSA-02CF5

Tap-off units with isolator and base units for fuses


Number of Conductors
Scheme (1)

Trunking
Tap-off

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC TNC
TNC TNS

IT TT TNS
IT TT TNS

(2)

IT (3)
TT, TNS (3) (4)

Tap-off scheme

KSA-05SF41

KSA-16SF3

Rating
A

Fuse
size

Connection
mm2

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

50

14 x 51

10

KSA-05SF41
2.500

KSA-05SF41 (5)
2.500

KSA-05SF5
2.500

KSA-05SF41
2.500

100

22 x 58

35

KSA-10SF41
4.250

KSA-10SF41 (5)
4.250

KSA-10SF5
4.250

KSA-10SF41
4.250

125

00

50

KSA-12SF41
4.250

KSA-12SF5
4.250

KSA-12SF41
4.250

160

70

KSA-16SF41
8.900

KSA-16SF41 (5)
8.600

KSA-16SF5
8.900

KSA-16SF3
8.400

250

150

KSA-25SF41
16.700

KSA-25SF41 (5)
16.700

KSA-25SF5
17.000

KSA-25SF3
16.000

400

240

KSA-40SF41
36.000

KSA-40SF41 (5)
36.000

KSA-40SF5
36.000

KSA-40SF3
34.800

630
(6)

2 x 120

KSA-63SF41
75.000

KSA-63SF41 (5)
75.000

KSA-63SF5
75.000

KSA-63SF3
71.000

Np : Neutral protected.
(1) Conforming to publication IEC 364-3-1/section 3 and UTE NF C 15-100.
(2) If cross-section N is equal to the phase cross-sections.
(3) For use with a breaker placed upstream or downstream of the tap-off.
(4) If cross-section N is less than the phase cross-sections.
(5) For use with a single phase protection device.
(6) Tap-off units fixed on KSA-80 component, length 1 m.
11034/2

Te

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11041/3

Canalis KS (100 to 800 A)


IP 54 dust and damp proof tap-off units for NF fuses
References

Tap-off unit
Number of Conductors
Scheme (1)

3L + N + PE
Trunking
Tap-off

3L + Np + PE

TT TNS
TT TNS

3L + PEN

3L + PE

TNC
TNS

IT TT TNS
IT TT TNS

Tap-off scheme

(2)
Rating
A

Fuse
size

Connection
mm2

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

25

10 x 38

KSE-02CF5
0.430

KSE-02CF5
0.430

KSE-02CF5
0.430

KSE-02CF5

Tap-off units with isolator and base units for fuses


Number of Conductors
Scheme (1)

Trunking
Tap-off

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC TNC
TNC TNS

IT TT TNS
IT TT TNS

(2)

IT (4)
TT, TNS (3) (4)

Tap-off scheme

KSE-05SF41

KSE-25SF3

Rating
A

Fuse
size

Connection
mm2

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

50

14 x 51

10

KSE-05SF41
2.600

KSE-05SF41 (5)
2.600

KSE-05SF5
2.600

KSE-05SF41
2.600

100

22 x 58

35

KSE-10SF41
5.800

KSE-10SF41 (5)
5.800

KSE-10SF5
4.250

KSE-10SF41
5.800

00

50

KSE-10SD41
5.000

KSE-10SD5
5.000

KSE-10SD41
5.000

160

70

KSE-16SF41
7.400

KSE-16SF41 (5)
7.400

KSE-16SF5
7.400

KSE-16SF3
7.400

250

150

KSE-25SF41
18.000

KSE-25SF41 (5)
18.000

KSE-25SF5
18.000

KSE-25SF3
17.400

400

240

KSE-40SF41
37.000

KSE-40SF41 (5)
37.000

KSE-40SF5
37.000

KSE-40SF3
36.200

Np : Neutral protected.
(1) Conforming to publication IEC 364-3-1/section 3 and UTE NF C 15-100.
(2) If cross-section N is equal to the phase cross-sections.
(3) If cross-section N is less than the phase cross-sections.
(4) For use with a breaker placed upstream or downstream of the tap-off.
(5) For use with a single phase protection device.

Te

11034/3

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11041/3

Canalis KS (100 to 800 A)


IP 54 dust and damp proof tap-off units for DIN and BS fuses
References

Tap-off units
Number of conductors
Scheme (1)

3L + N + PE

3L + PEN

3L + PE

Trunking
Tap-off

TT TNS
TT TNS

TNC
TNS

IT TT TNS
IT TT TNS

Tap-off scheme

For
fuses

Rating
A

Type of
fuses

Connection
mm2

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

DIN

16

D01
Neozed E14

KSE-02CD5
0.450

KSE-02CD5
0.450

KSE-02CD5
0.450

BS

20

BS88A1

KSE-02CG5
0.350

KSE-02CG5
0.350

KSE-02CG5

(1) Conforming to publications IEC 364-3-1/section 3 and UTE NF C 15-100.

11035/2

Te

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11041/3

Canalis KS (100 to 800 A)


IP 54 dust and damp proof tap-off units for DIN and BS fuses
References

Tap-off units with isolator and base units for fuses


Number of conductors
Scheme (1)

Trunking
Tap-off

3L + N + PE

3L + PEN

3L + PE

TT TNS
TT TNS

TNC
TNC

IT TT TNS
IT TT TNS

TNC
TNS

Tap-off scheme

(2)
For
fuses

Rating
A

Type of
fuses

Connection
mm2

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

DIN

25

Diazed E27

KSE-02SD41
2.720

KSE-02SD5
2.720

KSE-02SD41
2.720

50

D02
Neozed E18

10

KSE-05SD41
2.600

KSE-05SD5
2.600

KSE-05SD41
2.600

63

Diazed E33

16

KSE-06SD41
5.300

KSE-06SD5
5.300

KSE-06SD41
5.300

100

Size 00

50

KSE-10SD41
5.000

KSE-10SD5
5.000

KSE-10SD41
5.000

160

Size 00

50

KSE-16SD41
7.400

KSE-16SD5
7.400

KSE-16SD3
7.400

250

Size 1

150

KSE-25SF41
18.000

KSE-25SF5
18.000

KSE-25SF3
17.400

400

Size 2

240

KSE-40SF41
37.000

KSE-40SF5
37.000

KSE-40SF3
36.200

30 (3)

BS88A1

KSE-03SG41
2.600

KSE-03SG41
2.600

60

BS88A1 or A3

35

KSE-06SG41
5.000

KSE-06SG41
5.000

160

BS88B1 or B2

70

KSE-16SG41
7.400

KSE-16SG41
7.400

KSE-16SD3

BS

KSE-03SG41

(1) Conforming to publications IEC 364-3-1/section 3 and UTE NF C 15-100.


(2) If the neutral cross-section is equal to the phase cross-sections.
(3) Do not use with scheme TNC
TNC

Te

11035/3

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11042/2

Canalis KS (100 to 800 A)


Tap-off units for IP 40 protected equipment
References

Tap-off units for modular equipment (not supplied)


Number of conductors

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC
TNS

IT TT TNS
IT TT TNS

Tap-off scheme
(Example with circuit-breaker)

(2)
Rating
A

Number
of modules

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

25

KSA-02DA50010
0.500

KSA-02DA50010
0.500

KSA-02DA50010
0.500

KSA-02DA50010
0.500

Number of conductors

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC
TNC

IT TT TNS
IT TT TNS

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

KSA-02DA50010

Tap-off units with isolator


TNC
TNS

Tap-off scheme
(Example with circuit-breaker)

(2)
KSA-05DA40010
For modular equipment (not supplied)
Rating
Number
Reference
A
of modules
Weight (kg)
50

7.5

KSA-05DA40010
2.400

KSA-05DA40010
2.400

KSA-05DA50010
2.400

KSA-05DA40010
2.400

100

11

KSA-10DB40030
5.000

KSA-10DB40030
5.000

KSA-10DB50030
5.000

KSA-10DB40030
5.000

For contact breakers (not supplied)


With Telequick plate
Reference
Type
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

AM1-PA3030

KSA-12SU411

KSA-12SU511

AM1-PA6040

KSA-12SU412

KSA-12SU512

KSA-12SU411

Np : Neutral protected.
(1) Conforming to publications IEC 364-3-1/section 3 and UTE NF C 15-100.
(2) If the neutral cross-section is equal to the phase cross-sections.
11037/2

Te

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11042/3

Canalis KS (100 to 800 A)


Tap-off units for IP 54 dust and damp proof equipment
References

Tap-off units with isolator for modular equipment (not supplied)


Number of conductors

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC TNC
TNC TNS

IT TT TNS
IT TT TNS

Tap-off scheme
(Example with circuit-breaker)

(2)
Rating
A

Number
of modules

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

50

7.5

KSE-05DA4
2.400

KSE-05DA4
2.400

KSE-05DA5
2.400

KSE-05DA4
2.400

100

7.5

KSE-10DA4
3.400

KSE-10DA4
3.400

KSE-10DA5
3.400

KSE-10DA4
3.400

KSE-05DA4

Np : Neutral protected.
(1) Conforming to publications IEC 364-3-1/section 3 and UTE NF C 15-100.
(2) If the neutral cross-section is equal to the phase cross-sections.

Te

11037/3

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11042/2

Canalis KS (100 to 800 A)


Tap-off units for IP 40 protected circuit-breakers
References

Tap-off units for Merlin Gerin Compact NS fixed circuit-breakers

(3)

Number of conductors

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC TNC
TNS TNC

IT TT TNS
IT TT TNS

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Tap-off scheme

(2)
With MCC type rotary handle (1)
Rating
Type of
Reference
A
circuit-breaker
Weight (kg)
100

NS 100 N, H, L

KSA-16DB411
9.000

KSA-16DB411
9.000

KSA-16DB511
9.000

KSA-16DB511
9.000

160

NS 160 N, H, L

KSA-16DB411
9.000

KSA-16DB411
9.000

KSA-16DB511
9.000

KSA-16DB511
9.000

With extended rotary handle, short axis


KSA-16DB411

250

NS 250 N, H, L

KSA-25DB411
13.500

KSA-25DB411
13.500

KSA-25DB511
13.500

KSA-25DB511
13.500

400

NS 400 N, H, L

KSA-40DB411
13.500

KSA-40DB411
13.500

KSA-40DB511
13.500

KSA-40DB511
13.500

Tap-off units with isolator for integral 18, 32 and 63 contactor-breakers (3)
Number of conductors

3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

TT TNS
TT TNS

IT TT TNS
IT TT TNS

TNC TNC
TNC TNS

IT TT TNS
IT TT TNS

Tap-off scheme

(2)
Rating
A

Device

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

18

integral 18

KSA-02DL4

KSA-02DL5
4.000

KSA-02DL4
4.000

32

integral 32

KSA-03DL4
4.000

KSA-03DL4
4.000

KSA-03DL5
4.000

KSA-03DL4
4.000

63

integral 63

KSA-06DL4

KSA-06DL5
7.800

KSA-06DL4
7.800

KSA-02DL4

Np : Neutral protected.
(1) Conforming to publications IEC 364-3-1/section 3 and UTE NF C 15-100.
(2) If the neutral cross-section is equal to the phase cross-sections.
(3) Equipment not supplied.

11038/2

Te

Medium power busbar trunking


Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
Dimensions :
page 11042/3

Canalis KS (100 to 800 A)


Tap-off units for IP 54 dust and damp proof circuit-breakers
References

Tap-off units for Merlin Gerin Compact NS fixed circuit-breaker (3)


With extended rotary handle, short axis (1)
Number of conductors
3L + N + PE

3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

IT TT TNS
IT TT TNS

TNC TNC
TNS TNC

IT TT TNS
IT TT TNS

TT TNS
TT TNS

Tap-off scheme

(2)

KSE-16DB411

Rating
A

Type of
circuit-breaker

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

100

NS 100 N, H, L

KSE-16DB411
11.000

KSE-16DB411
11.000

KSE-16DB511
11.000

KSE-16DB511
11.000

160

NS 160 N, H, L

KSE-16DB411
11.000

KSE-16DB411
11.000

KSE-16DB511
11.000

KSE-16DB511
11.000

250

NS 250 N, H, L

KSE-25DB411
13.500

KSE-25DB411
13.500

KSE-25DB511
13.500

KSE-25DB511
13.500

400

NS 400 N, H, L

KSE-40DB411
13.500

KSE-40DB411
13.500

KSE-40DB511
13.500

KSE-40DB511
13.500

Tap-off units with isolator for integral 18, 32 and 63 contactor-breakers (3)
With non-adjustable handle on door, for dust and damp proof units (1)
Number of conductors
3L + N + PE
3L + Np + PE

3L + PEN

3L + PE

Scheme (1) Trunking


Tap-off

IT TT TNS
IT TT TNS

TNC TNC
TNC TNS

IT TT TNS
IT TT TNS

TT TNS
TN TNS

Tap-off scheme

(2)
KSE-02DL4

Rating
A

Device

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

Reference
Weight (kg)

18

integral 18

KSE-02DL4

KSE-02DL5
4.000

KSE-02DL4
4.000

32

integral 32

KSE-03DL4
4.000

KSE-03DL4
4.000

KSE-03DL5
4.000

KSE-03DL4
4.000

63

integral 63

KSE-06DL4

KSE-06DL5
7.800

KSE-06DL4
7.800

Np : Neutral protected.
(1) Conforming to publications IEC 364-3-1/section 3 and UTE NF C 15-100.
(2) If the neutral cross-section is equal to the phase cross-sections.
(3) Equipment not supplied.

Te

11038/3

Medium power busbar trunking


Canalis KS (100 to 800 A)
Dust and damp proofing accessories and additional components
Description :
page 11031/7
Dimensions :
page 11040/5

References

IP 54 dust and damp proofing accessories for trunking installed edgewise


Description

Rating
A

Use

Reference

Tap-off
blanking plate

100 to 800

1 per unused
tap-off outlet

KSE-80YB2

Weight
kg
0.080

KSE-80YB2

IP 54 dust and damp proofing accessories for trunking installed flat or vertically
Sealed jointing
sleeve

250
(100 to 160)

For straight lengths


KSA-iiEDiii
(1 per length)

KSE-25YA2

1.280

For any other


length
(1 per length)

KSE-25YA3

1.280

500
(400)

For any length


(1 per length)

KSE-50YA2

2.250

800
(630)

For any length


(1 per length)

KSE-80YA2

2.600

100 to 800

1 per unused
tap-off outlet

KSE-80YB2

0.080

KSE-80YB2

KSE-iiYAi

Tap-off
blanking plate

11043/2

Te

Medium power busbar trunking


Canalis KS (100 to 800 A)
Dust and damp proofing accessories and additional components
References

Additional accessories for tap-off units


Description

For unit

For NF blade
fuses

Reference

Single phase
protection device
(3L or 3L + N)
For NF blade
fuses

KSi-05SFii

14 x 51

KSA-05EZ20

0.020

KSi-10SFii

22 x 58

KSA-10EZ20

0.020

KSi-16SFii

T0

KSA-16EZ20

0.050

KSi-25SFii

T1

KSA-25EZ20

0.050

KSi-40SFii

T2

KSA-40EZ20

0.100

KSi-63SFii

T3

KSA-63EZ20

0.100

Description

For unit

Cable clamps
min. - max.

Unit
reference

Gland plate with


cable clamps (IP 40)

KSA-05Siiii

8...20 mm

KSA-05AZ1

0.150

KSA-06Siiii
KSA-12SFiii

25...40 mm

KSA-12AZ1

0.200

KSA-16Siiii

30...55 mm

KSA-16AZ1

0.250

KSA-25SFiii
KSA-40SFiii

30...70 mm

KSA-40AZ1

1.100

Cable clamp only

30...70 mm

KSA-80AZ1

0.950

Gate switch

KSA-05Siii to
KSA-12Siii

KSA-12AZ40

0.015

KSA-16Siii

KSA-16AZ40

0.030

KSA-12AZ2

0.010

Sealing kit
for unit end
(Order in multiples of 20)

Weight
kg

Weight
kg

Te

11043/3

Medium power busbar trunking


Canalis KS (100 to 800 A)

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
pages 11033/3 to 11033/5

Dimensions

146

Trunking lengths 100, 160 and 250 A


KSA-10EAiii, KSA-16EAiii and KSA-25EAiii

250

1000
750

1000
1000

1000
1000

750

1000
1000

54

250

1000

5000

146

Trunking lengths 400, 500, 630 and 800 A


KSA-40EDiii, KSA-50EDiii, KSA-63EDiii and KSA-80EDiii

250

1000
750

1000
1000

1000
1000

750

1000
1000

250

1000

Rating (A)
400/500
630/800

5000

Straight lengths cut to length


ii
KSA-i
iES4A

Fire barrier lengths


KSA-i
iEF4A
ii

(1)

(1)

(1)
1200 2340

Rating (A)
100250
400500
630 and 800
(1) Minimum 500, maximum 1995

11040/2

Te

a
75
113

a
54
75
113

Rating (A)
100250
400500
630 and 800

a
54
75
113

(1) Minimum 600.


(indicate the position of the fire barrier)

Medium power busbar trunking


Canalis KS (100 to 800 A)

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
pages 11033/3 to 11033/5

Dimensions

Feed units for 100 and 250 A trunking


KSA-10AB451

KSA-25AB42

315

212

(1)

112

284

126

400

390

170

505
(1) 60 mm minimum
Cable outlet : cable gland 29

294

90 105

45
81

600

14

20

143

126

390

37

61
49

270

430

280

61
43

Flange feed unit


KSA-25ER4

KSA-25BT42

253

170

Cable outlet.
Feed units for 400 and 800 A trunking
KSA-iiAB4i2

KSA-iiBT402

b-20

C-20

177

D1

11

11

a1

300
660

170

1000

Rating (A)
A
400/500
600
630/800
680
Cable outlet.

B
770
850

C
406
556

D
230
310

D1
175
236

F
300
300

G
150
190

Rating (A)
400/500
630/800

Flange feed unit


KSA-50ER4

a
290
390

a1
235
316

b
510
556

KSA-80ER4

N
80 80 80

370

340

40

143

170
220
250

315

14

20

166

210
260

338

16

40
72

37

290

80 80 80

370

340

290

11

290

Te

11040/3

Medium power busbar trunking


Canalis KS (100 to 800 A)

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
pages 11033/3 to 11033/5

Dimensions

146

KV-KS connector
KV0-iiER41001

2000

Rating (A)
250
500
800

a
54
75
113

End covers
KSB-25FA3

KSB-50FA2

15

KSB-80FA2

20

20

Elbows, tee and cross for 100 and 250 A trunking


KSA-25LC40
KSA-25LP41

54

165

KSA-25LP42

165

250

250

165

250

250

165

165
165

165

165
165

11040/4

Te

165

KSA-25XC40

165

KSA-25TC40

165

54

Medium power busbar trunking


Canalis KS (100 to 800 A)

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
pages 11033/3 to 11033/5

Dimensions

Elbows, tee and cross for 400 to 800 A trunking


KSA-iiLC40
KSA-iiLP41
146

KSA-iiLP42

290

290

290

290

290

a
290

KSA-iiXC40
146

580

290

146

290

KSA-iiTC40

290

a
290

290
580
a
290

a
75
113

Fixing brackets
KSA-25EZ1

40 50 50 36

KSE-50YA2

30

8x14

KSE-80YA2

185
210

152

8x14

190

Sealing and joining kits (IP 54)


KSE-25YA2

30

176

176

115

8x14

323

85

105

200

30

KSA-80EZ3

40 50 50 36

KSA-50EZ3

40 50 50 36

80

290
580

176

Rating (A)
400500
630 and 800

323

140

155

Tap-off blanking plate


KSE-80YB2

95
Rating (A)
100250
400500
630 and 800

a
a
70
90
125

Te

11040/5

Medium power busbar trunking


Canalis KS (100 to 800 A)
Tap-off units with/without isolator and fuse carriers

Description :
pages 11031/2 to 11031/7
Selection guide
page 11032/2
Characteristics :
page 11032/5
References :
pages 11034/2 and 11035/2

Dimensions

Tap-off units with/without isolator and fuse carriers


KSA-02CF5

183

160

KSA-05SFii

50

43*

50 113*

8-20

93

270

25-40

285

310

KSA-16SFii

193

KSA-10SFii, KSA-12SFii

50 113*

380

30-55
430

130* 55
230

455

KSA-40SFii

100
565

460

415

90

KSA-25SFii

45

430

200*

55

255
610

610

190

36

KSA-63SFii

165

670
1000

(*) Side projection


Cable outlets
11041/2

Te

71
290

63

220*

63

Medium power busbar trunking


Canalis KS (100 to 800 A)
Dust and damp proof tap-off units with/without isolator and fuse carriers
Dimensions

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
pages 11034/3 and 11035/3

KSE-02CD5

160

160

Dust and damp proof tap-off units with/without isolator and fuse carriers
KSE-02CF5
KSE-02CG5

43*

50 90*

50

93

93

KSE-10SFii, KSE-10SDii
KSE-06SDii
KSE-06SG41

195

183

KSE-05SFii
KSE-02SDii, KSE-05SDii
KSE-03SG41

50 113*

270

395

100

40

190

KSE-25SFii

430

130* 55

455

230

460

415

285

90

KSE-16SFii
KSE-16SDii
KSE-16SGii

45

430

200*

55

255

KSE-63SFii

610

610

565

190

100

36

KSE-40SFii

220*

63

165

670
1000

71
290

63

(*) Side projection


Cable outlet

Te

11041/3

Medium power busbar trunking


Canalis KS (100 to 800 A)
Miscellaneous tap-off units with/without isolator

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
page 11037/2

Dimensions

Tap-off units with/without isolator for modular equipment


i 0010
KSA-02DA50010
KSA-05DAi

KSA-10DBi
i 0030
11 modules (205 x 47)

56

50 90*

50 113*

8-20

93

270

195

183

160

7,5 modules (140 x 47)

228

4 modules (79.5 x 47)

48

100

395

Tap-off units with isolator for contact breakers


i 11
KSA-12SUi

40

48

190

675

375

188

235

KSA-12SUi
i 12

453

126* 55

470

231

155*
260

330

250

163

368

110

15

KSA-25DBi
i 11

15

Tap-off units for Merlin Gerin circuit-breaker


i 11
KSA-16DBi

565
582

590

207

300

580

368

163

18

KSA-40DBi
i 11

257

780

275
325

(*) Side projection.


Cable outlet.

Te

230

40

195*
500

300

55

255

230
140

400

11042/2

KSA-06DLi
i

215

200

Tap-off units for integral contactor-breaker


i , KSA-03DLi
i
KSA-02DLi

55

Medium power busbar trunking


Canalis KS (100 to 800 A)
Miscellaneous dust and damp proof tap-off units with/without isolator

Description :
pages 11031/2 to 11031/7
Selection guide :
page 11032/2
Characteristics :
page 11032/5
References :
page 11037/3

Dimensions

KSE-10DAi
i
7.5 modules (140 x 47)

50 113*

270

195

183

Dust and damp proof tap-off units with/without isolator for modular equipment
i
KSE-05DAi
7.5 modules (140 x 47)

70

100

395

163

15
163

368

368

147

590

197

465

52

KSE-25DBi
i 11

15

Dust and damp proof tap-off units for Merlin Gerin circuit-breaker
i 11
KSE-16DBi

40

190

207
257

368

163

18

KSE-40DBi
i 11

780

275
325

200

215

Dust and damp proof tap-off units for integral contactor-breaker


i , KSE-03DLi
i
KSE-02DLi

140

400

40

230

230

KSE-06DLi
i

195*
500

(*) Side projection.


Cable outlets.

55

300

Te

11042/3

Medium power busbar trunking


Canalis KVA (200 to 800 A)
For feeding and connections in :
industry, commercial and service buildings and infrastructures
Presentation

Run components
6 ratings : 200 - 315 - 400 - 500 - 630 and 800 A.
4 live aluminium conductors in fixed lengths of 4 metres
or in 0.35 to 2 metre lengths as required.

1/4

Te

Connection components and feed units

For connecting busbar trunking to switchboard connections,


generators and transformers. Also for feeding distribution busbar trunking
and for feeding feed trunking from the distribution trunking.
These components are only available in copper.

Components for changing direction


For adapting to all the trunking runs.
They are available as rigid units (elbow, tee)
or flexible units.
These components are only available in copper.

Fixing brackets
There are two types of fixing : horizontal and vertical.

Te

1/5

Medium power busbar trunking


Canalis KVA (200 to 800 A)
For low density horizontal distribution in :
industry, commercial and service buildings and infrastructures
Presentation

Run components
6 ratings : 200 - 315 - 400 - 500 - 630 and 800 A.
4 live aluminium conductors in fixed lengths of 4 metres
or in 0.35 to 2 metre lengths as required.

1/6

Te

Connection components and feed units


For connecting busbar trunking to switchboard connections.
These components are only available in copper.

Components for changing direction

For adapting to all the trunking runs.


They are available as rigid units (elbow, tee)
and flexible units.
These components are only available in copper.

Fixing brackets
There are two types of fixing : horizontal and
vertical.

Tap-off units

These bolted units can only be mounted at the


junction of two feeder lengths (ET). They are
designed to take Merlin Gerin Compact NS
circuit-breakers.

Te

1/7

Medium power busbar trunking


Canalis KVA (200 to 800 A)
For rising main distribution in :
service buildings and infrastructures
Presentation
1

Run components
6 ratings : 200 - 315 - 400 - 500 - 630 and 800 A.
4 live aluminium conductors in fixed
lengths of 1, 2 or 3 metres or in 2.50 to 4 metre
lengths according to the height between floors.

Connection components and feed


units
For connecting busbar trunking to
switchboard connections.
These components are only available in copper.

Components for changing direction


For adapting to all the trunking runs.
They are available as rigid units (elbow, tee)
or flexible units.
These components are only available in copper.

1/8

Te

Fixing brackets

There are two types of fixing : horizontal and vertical.

Tap-off units
These bolted units can only be mounted, with the
power off, at the junction of two components.
There are two types : single feeder and multi-feeder.

Single feeder tap-off unit for Compact NS circuit-breaker.


Available in 2 ratings (250 and 400 A).

Multi-feeder tap-off unit : has the distribution


switchboard function which will allow several feeders
per floor. This distribution principle relies on the
extensive Prisma range.

Te

1/9

Medium power busbar trunking


Selection :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Description

General
Canalis KVA trunking is designed to feed medium power in industrial, commercial or service buildings. It can also be used
to tap off directly from the joint, between two lengths, for rising main distribution or low density distribution applications.
This trunking has a compact design, namely with plated conductors inside a metal enclosure. The standard range is IP 52
(IP 54 as an option). The isolated conductor bars are made of nickel plated aluminium. The range is divided into 6 ratings
from 200 to 800 A. The insulation used on the conductors is halogen-free 130C class B polyester.
The trunking has :
- 4 conductors for the 3-pole + neutral version (crosssection of the neutral equal to the cross-section of the
phases). Recommended for TNC scheme.
The metal enclosure in prelacquered galvanised sheet
steel (RAL 7032) provides protection and mechanical
resistance for the conductors along their entire length.
Moreover, the metal enclosure is used as a protective
conductor (conforming to NF C15-100) with continuity
ensured at each junction along the length of the installation.
As an option, Canalis KVA can be fitted with an additional
copper protective conductor (cross-section equal to half
the cross-section of the phase).Recommended for TNS
scheme. With its compact design (no free space within the
trunking), Canalis KVA can be mounted horizontally, edgewise or vertically without derating the rated current Ith.
Moreover, this design does not require the mounting of a
fire barrier joint to pass through floors and walls. Canalis
KVA is designed to be fire-resistant for up to 2 hours.

Run components
ET Type
These are designed to feed current through horizontal or
vertical runs. A joint between two lengths can be replaced
by a special joint which can be used as a tap-off point.
These lengths are produced in fixed lengths of 4 metres or
in 0.35 m to 2 metre lengths as required.
EV Type
These are designed for rising main distribution. The joint
between two lengths can be used as a tap-off point. These
lengths are produced in fixed lengths of 1, 2 and 3 metres
or in 2.50 m to 4 metre lengths as required.
They should be mounted with the neutral on the left.
Junction block
1

1/10

Te

1 This is supplied with the ET run components and the


components for changing direction. It provides an
electrical and mechanical joint. When the run has a feed
unit at both ends, an additional junction block must be
ordered.
2 This is supplied with the EV run components. It can be
ordered separately if ET components are used to replace
the junction block and enable tap-off. It provides an
electrical and mechanical joint as well as a tap-off point.
The electrical junction is ensured by a single junction block
(1 to 2 bolts per bar) which provides continuity for all the
conductors. The bolt is made up of a screw and a contraction
nut, the external head of which breaks when the tightening
torque is reached. When the head of the nut breaks, a red
washer is released, showing that the electrical junction
operation has been completed successfully. For disassembly
or maintenance operations, a second head is available.
The recommended torque is thus 3 daNm. The junction
block contacts are silver-plated copper.

Medium power busbar trunking


Selection :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Description

Connection components and feed units


Connection components can be mounted at either end of the run. If there is a feed unit at both ends of the run, an additional
junction block should be ordered.
Flange feed unit
The flange feed unit is fitted with a mounting plate (on the
switchboard or transformer cover) and bars. These bars
are spread along the axis of the trunking and enable direct
connection, by flexible or rigid bars, or by cables, to the low
voltage terminals of a transformer or the connections of a
low voltage switchboard.

Switchboard connection component


The switchboard connection component is fitted with a
plate for fixing to the switchboard. Its flexible construction
means that it can be connected directly to the connections
or the protection device, and provides a multidirectional
feeder at the switchboard outlet.
The fixing plate, which runs along the length of the flexible
bar, can be connected directly to the protection device
inside the switchboard, wherever it is situated.
Warning : for connection by braid, a fixer must be provided
every 300 mm (maximum value) inside the switchboard. To
do this, use the Prisma P cable tray.

KH - KV connector
The KH - KV connector supplies a feed run directly from a
KH high power distribution tap-off unit. Its flexible design
accommodates any changes in alignment, level and axis.
It is fitted at one end with an SB or SD tap-off unit outlet
plate from the KH range with flexible braids for connection
to the protection device and, at the other end, with a KV
connector end.

Te

1/11

Medium power busbar trunking


Selection :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Description

Connection components and feed units (continued)


KV - KS connector
The KV - KS connector is fitted with a KV connector end at
one end and a KS connector end at the other.
Due to its flexible design, it ensures direct connection from
a feed run to a distribution run and reduces any risk caused
by alignment faults.

Feed unit casings


Feed unit casings are available in two versions, no. 1 and
no. 2, which allow the run to be fed to the right or to the left
respectively. They can be used for connecting by cables up
to a rating of 800 A.

End cover
The end cover protects and isolates the ends of the
conductors and is mounted on the last length.

Components for changing direction


These components adapt the trunking direction to the contours of the building by changing direction and level. There are
two types :
1 Rigid :
- Flat or edgewise elbows, upwards or downwards, to the left or right
- Edgewise or flat tees
2 Flexible :
EF type flexible components are available for all ratings up to 800 A. These components are made of copper. They are
produced in 2 metre and 1 metre lengths and are designed for changing direction and going round obstacles and can
be used as end of site components.

1
2

1/12

Te

Medium power busbar trunking


Selection :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Description

Fixing devices
1 Universal bracket
This device is used to fix the run to the structure of the building, directly or via a threaded rod, a bracket, etc. There
is one model for all casing sizes in the KV range which can be used for ceiling-mounting, suspended mounting, wallmounting, etc. The maximum recommended fixing centre is 4 metres.
2 Fixing support
Suitable for fixing the vertical run component to the structure of the building, this type of fixing support has the following
advantages :
- The height can be adjusted to correct positioning errors.
- The spring can be adjusted to ensure the load is distributed at each level.
- The constraints of the building (expansion, vibration, etc) are not transmitted to the trunking.

Tap-off units
The tap-off units which are mounted on the KV range are bolted type, tightened by a single bolt with breakable head. They
are mounted in place of a junction block. They must be installed or removed with the power off.
There are 2 types :
1 Single feeder tap-off unit for Compact NS circuit-breaker. Designed for rising main distribution or low density
distribution applications, it has the following characteristics :
- It is available in 2 ratings (250 and 400 A).
- The door can only be opened after a load break.
- Degree of protection IP 52/54.
- When the door is open, no live part can be accessed, degree of protection IP 2X.
2 Multi-feeder tap-off unit for Compact NS and multi 9 Merlin Gerin circuit-breakers. Designed for rising main distribution
applications, it has the following characteristics :
- It has a distribution switchboard function which will allow several feeders per floor.
- It is available up to a maximum power rating of 250 A.
- Degree of protection IP 30 as standard and IP 40 with door.
This distribution principle relies on the extensive Prisma range.

2
1

Te

1/13

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Selection guide

Determining the rating according to the temperature rise


The rating of a busbar trunking, in amps, represents the maximum intensity of the constant current which the trunking can
continuously support, for an average ambient temperature of 35 C, and in accordance with standard temperature rises
(IEC 439.2).
Determining the rating according to the temperature rise consists of selecting the busbar trunking rating immediately
above the operating current of the installation. However, as a rule, the intensity of the current which crosses a busbar
trunking is constantly fluctuating. The operating current is therefore defined as that of the constant current which produces
the same thermal effects as the actual current.
It is sometimes difficult to determine the operating current, especially when there is no reading for the installation or for
an equivalent installation. The operating current can be estimated with sufficient precision by calculating the product of
the nominal currents of receivers connected to the busbar trunking by a coefficient known as the average demand
coefficient. The average demand coefficient is empirically determined by comparison with existing installations. It is
dependent upon :
- the average quantity of receivers operating
- the load variation of each receiver (a receiver rarely absorbs its maximum power, as peak periods alternate with those
of no-load operation)
- whether several receivers are operating at the same time, whether peaks are superimposed and the duration of these
peaks
As an example, here are a few coefficients for a general mechanical engineering workshop.
Number of receivers

Average demand coefficient

2 or 3

0.9

4 or 5

0.8

6 to 9

0.7

10 to 40

0.6

40 plus

0.5

Depending on the ambient temperature, the trunking must be derated (see characteristics pages 11003/2 and 11003/3).

Checking the rating according to the permissible voltage drop


The permissible voltage drop is that which is compatible with the correct operation of receivers (refer to the manufacturers'
manuals).
i Read the voltage drop in mV/m/A in the tables on page 11003/3 for the busbar trunking selected according to the
temperature rise.
i Determine the voltage drop for the most disadvantaged receivers, namely those which are the furthest from the source
and for the highest current. If the voltage drop is not permissible, select the rating immediately above.
i Repeat the checking procedure for the new rating.

Checking the rating according to withstand to short-circuit currents


i Calculate the intensity of the short-circuit current at the points which are considered to be unfavourable.
i Check, by referring to the tables on pages 11003/2 and 11003/3, that the selected rating of the trunking enables it to
withstand this short-circuit current. If this is not the case, there are two possible solutions :
- Select trunking of a higher rating and repeat the checking procedure.
- Provide a protection system which limits current peaks upstream of the trunking.

1/14

Te

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Selection guide

Example of selecting the rating of the busbar trunking


The table below can be used to determine the rating of the KVA busbar trunking (aluminium conductors) according to the
power of the transformer.
Transformer (U2 = 410 V)
Power
Nominal
current
kVA
A

Short-circuit
current
kA

Canalis busbar trunking


Type
Nominal
current
A

Short-circuit
current
kA rms

100

141

KVA-20

200

7.2

160

225

KVA-31

315

17

250

352

KVA-40

400

19

400

563

14

KVA-63

630

31

500

704

17.6

KVA-80

800

41

Calculation assumptions
The following calculation assumptions have been made :
- the short-circuit power of the upstream supply : 500 MVA
- the voltage ratio of the transformers : 20 kV/400 V

Level of short-circuit protection in kA rms (voltage 380/415V)


The circuit-breaker/trunking coordination table below gives directly the maximum short-circuit current for which the KVA
trunking is protected, according to the type of circuit-breaker.

Type of trunking

KVA-20

KVA-31

KVA-40

KVA-50

KVA-63

KVA-80

Rating (A)

200

315

400

500

630

800

45
70
150

45
70
150

45
70
150

45
70
150

45
70
150

45
70
150

45
70
150

45
70
150

Merlin-Gerin
Compact
circuit-breaker

Masterpact
circuit-breaker

NS250

N
H
L

35
70
100

NS 400

N
H
L

35
35
35

NS 630

N
H
L

C 801
C1001

N
H
L

40
40
70

50
60
110

M 08
M 10

N1
H1
H2
L1

33
33
33
40

40
40
40
55

Te

1/15

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Characteristics

Type of trunking

KVA-20

KVA-31

KVA-40

KVA-50

KVA-63

KVA-80

General characteristics
Conforming to standards

IEC 439.2

Number of live conductors

Type of live conductors

Aluminium

Type of current

Hz

c 50/60 - (1)

Rated insulation voltage

1000

Rated operating voltage

1000

Degree of protection (IEC 529)


(as standard)

IP 52, IP 54 for horizontal, edgewise installation and vertical installation


IP 52 for horizontal, flat installation

Permissible currents
Rated current Ith (2)
conforming to IEC 439

200

315

400

500

630

800

Rated peak current

kA

25

49

51

55

76

84

Permissible rated short time


current (1 s)

kA rms 7.2

17

19

20.5

30

40

Multiplying
Temperature C
factors of the
rated current
Ith depending
Factor
on the average
ambient temperature

35

40

45

50

0.95

0.90

0.84

Conductor characteristics
Live conductors
Rb0phAverage resistance per
conductor, cold state
(ambient temperature 20 C)

m/m

0.575

0.23

0.205

0.137

0.125

0.083

Rb0phAverage resistance per


conductor at Ith
(ambient temperature 35 C)

m/m

0.71

0.284

0.254

0.169

0.154

0.103

XphAverage reactance per


conductor

m/m

0.01

0.01

0.01

0.01

0.005

0.0075

ZphAverage impedance per


conductor

m/m

0.71

0.284

0.254

0.169

0.154

0.103

(1) For 60 to 400 Hz AC or for DC : please consult your Regional Sales Office.
(2) Rated currents Ith are given for an average ambient temperature of 35C and for a casing temperature rise of no more
than 55K according to the test conditions of standard IEC 439.2.

1/16

Te

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
References :
pages 11004/2 to 11004/13
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Characteristics

Type of trunking

KVA-20

KVA-31

KVA-40

KVA-50

KVA-63

KVA-80

Other characteristics
Live conductors
Rb1ph ph or phN Average resistance
of fault loops between
live conductors

m/m

1.42

0.568

0.508

0.338

0.308

0.206

Rb2ph ph or phN Average resistance


of fault loops between
live conductors

m/m

1.704

0.682

0.609

0.406

0.37

0.247

Rb1ph PE Average resistance


of fault loops between
live conductors and PE

m/m

1.374

0.948

0.793

0.708

0.482

0.431

Xb1ph ph or phN Average reactance


of fault loops between
live conductors

m/m

0.02

0.02

0.02

0.02

0.01

0.015

Xb1ph PE Average reactance


of fault loops between
live conductors and PE

m/m

0.02

0.02

0.02

0.02

0.01

0.015

Voltage drop

Composite voltage drop, hot state, in millivolts per metre and per amp, for three-phase 50 Hz current, with load
concentrated at the end of the run (feed run). If the load is distributed along the run, voltage drops are half the values
indicated in the table below.
For a power factor
of 0.7

mV/m/A 0.872

0.356

0.32

0.218

0.192

0.134

For a power factor


of 0.8

mV/m/A 0.994

0.404

0.362

0.244

0.218

0.15

For a power factor


of 0.9

mV/m/A 1.114

0.45

0.404

0.27

0.244

0.166

For a power factor


of 1

mV/m/A 1.23

0.492

0.44

0.292

0.266

0.178

Equivalent
copper
cross-section

mm2

26

26

32

32

42

42

Average resistance,
cold state (ambient
temperature 20C)

m/m

0.664

0.664

0.539

0.539

0.328

0.328

Equivalent
copper
cross-section

mm2

40

40

102

102

165

165

Average resistance,
cold state (ambient
temperature 20C)

m/m

0.298

0.298

0.145

0.145

0.11

0.11

3L + N + PE

kg/m

2.7

3.8

4.5

6.1

7.6

10.8

3L + N + PER

kg/m

4.3

5.3

6.8

8.6

11.8

Protective conductor
Casing

Additional
conductor

Average weight

Te

1/17

KVA-iiEViii

KVA-iiETiii
KVA-iiEViii

KVA-iiETiii
KVA-iiEViii

KVA-iiETiii
KVA-iiETiii

1/18

Te

KVA-iiEViii

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Run components for horizontal and vertical feeding, IP 52
References

Straight lengths (1)


Rating

Type

Length
MinMax
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

200

Fixed

4000

KVA-20ET440
10.80

KVA-20ET740
12.00

315

Fixed

4000

KVA-31ET440
15.20

KVA-31ET740
16.40

Made to measure

3502000

KVA-31ET42B
8.20

KVA-31ET72B
8.80

400

Fixed

4000

KVA-40ET440
17.80

KVA-40ET740
21.00

500

Fixed

4000

KVA-50ET440
24.20

KVA-50ET740
27.20

Made to measure

3502000

KVA-50ET42B
13.00

KVA-50ET72B
14.60

630

Fixed

4000

KVA-63ET440
30.20

KVA-63ET740
34.20

800

Fixed

4000

KVA-80ET440
43.00

KVA-80ET740
47.00

Made to measure

3502000

KVA-80ET42B
23.00

KVA-80ET72B
25.00

Junction block, IP 54 (2)


Busbar trunking rating

3L + N + PE
3L + N + PER
Reference

Weight
kg

200 and 315

KV0-31YA4

1.20

400 and 500

KV0-63YA4

1.80

630 and 800

KV0-80YA4

3.00

(1) To order a made to measure component, see the procedure on pages 11006/2 and 11006/3.
(2) Only order if the run has a feed unit at each end.

N : position of neutral

Te

1/19

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Run components for rising main distribution, IP 52
References

Straight lengths (1)


Rating

Type

Length
MinMax
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

Fixed

3000

KVA-20EV430
8.40

KVA-20EV730
9.30

2000

KVA-20EV420
6.00

KVA-20EV720
6.60

1000

KVA-20EV410
3.60

KVA-20EV710
4.05

25003000

KVA-20EV43D
8.40

KVA-20EV73D
9.30

30013500

KVA-20EV43E
9.20

KVA-20EV73E
10.55

35014000

KVA-20EV44F
10.80

KVA-20EV74F
12.00

3000

KVA-31EV430
11.70

KVA-31EV730
12.60

2000

KVA-31EV420
8.20

KVA-31EV720
8.80

1000

KVA-31EV410
5.70

KVA-31EV710
6.15

25003000

KVA-31EV43D
11.70

KVA-31EV73D
12.60

30013500

KVA-31EV43E
12.40

KVA-31EV73E
14.50

35014000

KVA-31EV44F
15.20

KVA-31EV74F
16.40

3000

KVA-40EV430
11.70

KVA-40EV730
12.60

2000

KVA-40EV420
8.20

KVA-40EV720
8.80

1000

KVA-40EV410
5.80

KVA-40EV710
6.60

25003000

KVA-40EV43D
11.70

KVA-40EV73D
12.60

30013500

KVA-40EV43E
13.40

KVA-40EV73E
14.50

35014000

KVA-40EV44F
15.20

KVA-40EV74F
16.40

A
200

Made to measure

315

Fixed

Made to measure

400

Fixed

Made to measure

N : position of neutral
1/20

Te

(1) To order a made to measure component, see the procedure on pages 11006/2 and 11006/3.

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Run components for rising main distribution, IP 52
References

Straight lengths (1)


Rating

Type

Length
MinMax
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

Fixed

3000

KVA-50EV430
18.60

KVA-50EV730
20.80

2000

KVA-50EV420
13.00

KVA-50EV720
14.40

1000

KVA-50EV410
7.40

KVA-50EV710
8.00

25003000

KVA-50EV43D
18.60

KVA-50EV73D
20.80

30013500

KVA-50EV43E
21.40

KVA-50EV73E
24.00

35014000

KVA-50EV44F
24.20

KVA-50EV74F
27.20

3000

KVA-63EV430
23.40

KVA-63EV730
26.40

2000

KVA-63EV420
16.60

KVA-63EV720
18.60

1000

KVA-63EV410
10.60

KVA-63EV710
11.60

25003000

KVA-63EV43D
23.40

KVA-63EV73D
26.40

30013500

KVA-63EV43E
26.80

KVA-63EV73E
30.30

35014000

KVA-63EV44F
30.20

KVA-63EV74F
34.20

3000

KVA-80EV430
33.00

KVA-80EV730
36.00

2000

KVA-80EV420
23.00

KVA-80EV720
25.00

1000

KVA-80EV410
13.00

KVA-80EV710
14.00

25003000

KVA-80EV43D
33.00

KVA-80EV73D
36.00

30013500

KVA-80EV43E
38.00

KVA-80EV73E
41.50

35014000

KVA-80EV44F
43.00

KVA-80EV74F
47.00

Rating

3L + PEN

Reference
Weight (kg)

3L + N + PER
3L + N + PE
Reference
Weight (kg)

200 and 315

KV0-25YA4
1.50

KV0-25YA4
1.50

400 and 500

KV0-40YA41
2.40

KV0-40YA41
2.40

630 and 800

KV0-40YA42
3.10

KV0-40YA42
3.10

A
500

Made to measure

630

Fixed

Made to measure

800

Fixed

Made to measure

Junction/tap-off blocks, IP 54 (2)

N : position of neutral

(1) To order a made to measure component, see the procedure on pages 11006/2 and 11006/3.
(2) Only order for transforming a feed run in low density distribution.

Te

1/21

KV0-iiERii200
KV0-iiERii200

KV0-iiERii1004

KV0-iiABi000i

KV0-iiER41001
KV0-iiER4100i

1/22

Te

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Connection components and feed units, IP 52
End covers

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

References
Feed units
End feed box
Rating
e

a
N

Lengths
a, e
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

200 and 315

150

400 and 500

150

630 and 800

150

KV0-31ER40200
2.70
KV0-63ER40200
5.10
KV0-80ER40200
10.00

KV0-31ER70200
2.90
KV0-63ER70200
5.50
KV0-80ER70200
10.50

KV0-31AB40001
3.80
KV0-63AB40001
7.20
KV0-80AB40001
14.00

KV0-31AB70001
4.00
KV0-63AB70001
7.70
KV0-80AB70001
14.70

KV0-31AB40002
3.80
KV0-63AB40002
7.20
KV0-80AB40002
14.00

KV0-31AB70002
4.00
KV0-63AB70002
7.70
KV0-80AB70002
14.70

N1 feed unit with connection via cable

N1

200 and 315

400 and 500

630 and 800

N2 feed unit with connection via cable


200 and 315

400 and 500

630 and 800

Switchboard connection component


N2

Rating

3L + N + PE
3L + N + PER
Reference

Weight
kg

315

KV0-31ER71004

12.60

630

KV0-63ER71004

23.80

800

KV0-80ER71004

55.00

KV - KS connector (3L + N + PE)


KV = 315/KS = 250

KV = 500/KS = 500

KV = 800/KS = 800

KV0-25ER41001
12.60

KV0-50ER41001
23.80

KV0-80ER41001
43.00

KV = 315
KH SB400 unit

KV = 315
KH SD400 unit

KV = 500
KH SB1000 unit

KV = 800
KH SB1000 unit

KV0-25ER41002
12.60

KV0-50ER41003
12.60

KV0-63ER41002
23.80

KV0-80ER41002
43.00

KH - KV connector (3L + N + PE)


N

End cover IP 54 (3L + N + PE ou 3L + N + PER)

Busbar trunking rating


A

Reference

Masse
kg

200 and 315

KV0-31FA

1.00

400 and 500

KV0-63FA

1.10

630 and 800

KV0-80FA

1.20

Ni : position of neutral

Te

1/23

KV0-iiEFii0

KV0-iiLCi05

KV0-iiLCi05

KV0-iiLPi042

KV0-iiLPi042
KV0-iiLPi041
KV0-iiLPi041

1/24

Te

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Components for changing direction : flexible components, simple elbows, IP 52

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

References

Flexible components
Rating

Length

mm

200 and 315

1000

KV0-31EF710

7.10

2000

KV0-31EF720

12.60

1000

KV0-63EF710

12.80

2000

KV0-63EF720

23.80

1000

KV0-80EF710

23.00

2000

KV0-80EF720

43.00

400 and 500

630 and 800

Weight
kg

3L + N + PE
3L + N + PER
Reference

Elbows

N1

Lengths a, b

mm

200 and 315

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

250

KV0-31LC005
1.00

KV0-31LC005
1.00

400 and 500

250

KV0-63LC405
6.90

KV0-63LC705
7.30

630 and 800

250

KV0-80LC405
13.00

KV0-80LC705
13.50

200 and 315

200

KV0-31LP4041
3.40

KV0-31LP7041
3.50

400 and 500

200

KV0-63LP4041
5.90

KV0-63LP7041
6.20

630 and 800

200

KV0-80LP4041
11.00

KV0-80LP7041
11.40

200 and 315

200

KV0-31LP4042
3.40

KV0-31LP7042
3.50

400 and 500

200

KV0-63LP4042
5.90

KV0-63LP7042
6.20

630 and 800

200

KV0-80LP4042
11.00

KV0-80LP7042
11.40

N1 flat LP

a
N2

Edgewise LC
Rating

N2 flat LP

Ni : position of neutral

Te

1/25

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Component for changing direction : Tees, IP 52
Fixing devices

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

References
Tees, IP 52
c
b

c
b

N1

N2

c
b

Edgewise TC
Rating

Lengths a. b. c

mm

200 and 315

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

250

KV0-31TC407
5.30

KV0-31TC707
5.50

400 and 500

250

KV0-63TC407
9.50

KV0-63TC707
10.10

630 and 800

250

KV0-80TC407
18.00

KV0-80TC707
18.80

200 and 315

300

KV0-31TP4091
6.10

KV0-31TP7091
6.40

400 and 500

300

KV0-63TP4091
11.00

KV0-63TP7091
11.70

630 and 800

300

KV0-80TP4091
21.00

KV0-80TP7091
21.90

200 and 315

300

KV0-31TP4092
6.10

KV0-31TP7092
6.40

400 and 500

300

KV0-63TP4092
11.00

KV0-63TP7092
11.70

630 and 800

300

KV0-80TP4092
21.00

KV0-80TP7092
21.90

Description
A

Rating

Reference

Horizontal fixing bracket

200...800

KV0-80ZA1

0.50

Vertical fixing for


rising main distribution

200 and 315

KV0-31ZA2

1.00

400 and 500

KV0-63ZA2

1.00

630 and 800

KV0-80ZA2

1.00

N1 flat TP

N2 flat TP

Fixing Devices
Weight
kg

Ni : position of neutral

Te

1/27

KV0-iiCB71103
KV0-iiDB06

KV0-iiCB71103
KV0-iiYAii

KV0-iiCB71103

KV0-iiDB06

1/28

Te

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
Dimensions :
pages 11005/2 to 11005/5

Canalis KVA (200 to 800 A)


Tap-off units
References

Single feeder tap-off unit


Type

Rating

Degree of
protection

3L + N + PE
Reference

IP 52

KV0-25CB71103

5.50

IP 54

KV0-25CB71103E

5.50

IP 52

KV0-40CB71103

7.00

IP 54

KV0-40CB71103E

7.00

Weight
kg

A
For Compact NS circuit-breaker

250

400

KV0-25CB71103

Junction/tap-off blocks, IP 54
Rating

3L + N + PE
Reference

Weight
kg

A
200 and 315

KV0-25YA4

1.50

400 and 500

KV0-40YA41

2.40

630 and 800

KV0-40YA42

3.10

Multi-feeder tap-off unit, IP 30


Type

Rating
A

Reference

Weight
kg

For Compact NS circuit-breaker


+ modular

250

KV0-01DB06

15.00

Accessories for multi-feeder tap-off units (250 A)

KV0-01DB06

Description

Reference

Weight
kg

Solid door

KV0-00PP06

3.00

Transparent door

KV0-00PT06

5.00

Te

1/29

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Run components
Connection components and feed units

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Dimensions

h (1)

Straight length
KVA-iiEiiii

L
Fixed
L = 4000
L = 1000, 2000 and 3000

Made to measure
L = 350...2000
L = 25004000
Junction/tap-off block
KV0-iiYAii

200

84

280

90

280

End feed box


KV0-iiERi0200

Dimensions of
connector ranges

13

13 13

13

92

Type of length
For horizontal feeding and distribution
For rising main distribution
Junction block
KV0-iiYAi

Cross-section of trunking
according to its rating

h (1)

20

40

9 x 14

h (1)

60

350

67

h (1)

60

9 x 14 33,5

60

50
110

h (1)

150

9 x 14 33,5

70

70

70

190

60

400

200

h (1)

Switchboard connection component


KV0-iiERi1004

200

400 2500
3000
(1) Height of the trunking according to its rating
Rating (A)
200 and 315
h
44
1/30

Te

400 and 500


71

630 and 800


114

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Connection components and feed units

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Dimensions

h (1)

15

Cable feed unit


KV0-iiABi000i

10

20

10

20

30

20

60

60

50

67

70

20
40

8,5

Dimensions of the unit according to the rating


Rating (A)
h
a
b
c
200 and 315
44
200
650
300
400 and 500
71
200
700
400
630 and 800
114
200
700
450

a
b

d
450
500
500

y
150
170
190

146

h (1)

KV - KS connector
KV0-iiER41001

2000

Rating KV
(A)
315
500
800

44
71
114

54
75
113

KH - KV connector
KV0-iiER41002

h (1)

Plate for SB or SD unit

2000

(1) Height of the trunking according to its rating


Rating (A)
200 and 315
h
44

400 and 500


71

630 and 800


114

Te

1/31

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Components for changing direction

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Dimensions

h (1)

Flexible component
KV0-iiEFiii

1000 ou 2000

Edgewise elbow
KV0-31LC005

(1) Rating (A)


200 / 315
h
44
Flat elbow
KV0-iiLPiiii

630 / 800
114

40

h (1)

200

250

KV0-63LCi05, KV0-80LCi05

400 / 500
71

40

Rating (A)

60

250

200 and 315

(1) Rating (A)


h

400 and 500


71

630 and 800


114

200

(1) Rating (A)


h

90

h (1)

200 / 315
44

400 / 500
71

630 / 800
114

(1) Rating (A)


h

200 / 315
44

400 / 500
71

630 / 800
114

(1) Rating (A)


h
a
b

200 / 315
44
115
50

400 / 500
71
169
77

630 / 800
114
255
120

250

h (1)

Edgewise tee
KV0-iiTCiii

250

60

250

Flat tee
KV0-iiTPiiii
h (1)

300

300

1/32

Te

300

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Tap-off units

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Dimensions

Single feeder tap-off unit


KV0-iiCB71103

b
200
300

c
210
230

Rating (A)
a
250
525
400
600
Multi-feeder tap-off unit
KV0-iiDB06

Rating (A)
250
400

a
550
550

b
600
600

c
200
200

Te

1/33

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Canalis KVA (200 to 800 A)


Options, procedure for ordering a made to measure component

Options
The degree of protection for standard references is IP 52. To obtain degree IP 54, A1 should be added at the end of the
standard reference (degree IP 54 can only be obtained by factory assembly).
Similarly, if the trunking is to be mounted outside, A2 should be added at the end of the standard reference. The product
is supplied as IP 54 with an aluminium cover.

IP 52

+ option A1

= IP 54
(Edgewise only)

IP 52

+ option A2

= IP 54 + Cover
(Mounted outside
edgewise only)

Procedure for ordering a made to measure component


Position of neutral
Cover fixing sockets
(for locating)

Upper joint cover

A
a

Neutral

Lower
joint cover

Junction block

The neutral is located next to the socket closest to the end of the panel work (a).
Definition of a component
Shape
Each shape is characterised by a group of two letters (example : ET for a feed length).
Dimensions
Dimensions are always given in alphabetical order of the measurements (a, b, c, etc).
How to order
The order should be made on two lines :
i First line
Write the reference found in this catalogue.
i Second line
Write the dimensions for the made to measure component and any of the options selected :
- If the reference corresponds to a made to measure product, there are one or more variable values : you should
write a x b x etc in alphabetical order.
- If the reference ends in A followed by a number, an option is available (see above).

1/34

Te

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Canalis KVA (200 to 800 A)


Procedure for ordering a made to measure component

Procedure for ordering a made to measure component (continued)


Straight lengths
There are two types of component :
- ET components designed for feeding current along horizontal or vertical runs, available in 0.35 to 2 metre lengths.
- EV components designed for rising main distribution with tap-off at joints, available in 2.50 metre to 4 metre lengths.
They are defined according to floor height.
For feeding, a standard joint can be replaced by a special joint known as a junction/tap-off block which can be used as
a tap-off point. To take advantage of this option with ET components, there is a space on the order form to show :
- a junction/tap-off block reference (for example KV0-25YA4)
- a single feeder unit reference (for example KV0-25CB71103)
The nominal length L of a straight length is measured, from joint axis to joint axis, in millimetres (the joint axis is located
20 mm beyond the end of the bars).
Example :

Joint axis
L1
L2
L3
N
PE

40
=

=
206
L

A KVA straight length, rating 800 A, 3L + N + PE, 1820 mm long, has the following reference :
KVA - 80ET42B
L = 1820

Te

1/35

Medium power busbar trunking


Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Canalis KVA (200 to 800 A)


Installation precautions

2-metre flexible component


The 2-metre flexible component can be used to make the changes in direction shown on the diagrams below :
- edgewise (diagram A)
- flat (diagram B)
1

Max 300

Diagram A : edgewise flexible component

Max 700

Diagram B : flat flexible component

1
1

Min. radius 100

1 Fixing

1-metre flexible component


The 1-metre flexible component can be used to make the
changes in direction shown in the diagram opposite.
Fixing

Min. angle 60

1/36

Te

Medium power busbar trunking


Canalis KVA (200 to 800 A)
Installation precautions (continued)

Vertical mounting for rising main distribution

Floor height






If you use floor height lengths (from 2.50 to 4 metres),


position the 1st joint at around 1.70 metres above the floor.
This operation requires a made to measure component L1.

Level 2

1700

L1

Description :
pages 11001/2 to 11001/5
Selection guide :
pages 11002/2 and 11002/3
Characteristics :
pages 11003/2 and 11003/3
References :
pages 11004/2 to 11004/13

Level 1

Te

1/37

Medium power busbar trunking


Canalis KVC (200 to 800 A)
For feeding and connections in :
industry, commercial and service buildings and infrastructures
Presentation

Run components
5 ratings : 200 - 315 - 400 - 630 and 800 A.
4 live copper conductors in fixed lengths of 4 metres
or in 0.35 to 2 metre lengths as required.

1/4

Te

Connection components and feed units

For connecting busbar trunking to switchboard connections,


generators and transformers. Also for feeding distribution busbar trunking
and for feeding feed trunking from the distribution trunking.
These components are only available in copper.

Components for changing direction


For adapting to all the trunking runs.
They are available as rigid units (elbow, tee)
or flexible units.
These components are only available in copper.

Fixing brackets
There are two types of fixing : horizontal and vertical.

Te

1/5

Medium power busbar trunking


Canalis KVC (200 to 800 A)
For low density horizontal distribution in :
industry, commercial and service buildings and infrastructures
Presentation

Run components
5 ratings : 200 - 315 - 400 - 630 and 800 A.
4 live copper conductors in fixed lengths of 4 metres
or in 0.35 to 2 metre lengths as required.

1/6

Te

Connection components and feed units


For connecting busbar trunking to switchboard connections.
These components are only available in copper.

Components for changing direction

For adapting to all the trunking runs.


They are available as rigid units (elbow, tee)
and flexible units.
These components are only available in copper.

Fixing brackets
There are two types of fixing : horizontal and
vertical.

Tap-off units

These bolted units can only be mounted at the


junction of two feeder lengths (ET). They are
designed to take Merlin Gerin Compact NS
circuit-breakers.

Te

1/7

Medium power busbar trunking


Canalis KVC (200 to 800 A)
For rising main distribution in :
service buildings and infrastructures
Presentation
1

Run components
5 ratings : 200 - 315 - 400 - 630 and 800 A.
4 live copper conductors in fixed
lengths of 1, 2 or 3 metres or in 2.50 to 4 metre
lengths according to the height between floors.

Connection components and feed


units
For connecting busbar trunking to
switchboard connections.
These components are only available in copper.

Components for changing direction


For adapting to all the trunking runs.
They are available as rigid units (elbow, tee)
or flexible units.
These components are only available in copper.

1/8

Te

Fixing brackets

There are two types of fixing : horizontal and vertical.

Tap-off units

These bolted units can only be mounted, with the power


off, at the junction of two components.
There are two types : single feeder and multi-feeder.

Single feeder tap-off unit for Compact NS circuit-breaker.


Available in 2 ratings (250 and 400 A).

Multi-feeder tap-off unit : has the distribution


switchboard function which will allow several feeders
per floor. This distribution principle relies on the
extensive Prisma range.

Te

1/9

Medium power busbar trunking


Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Description

General
Canalis KVC trunking is designed to feed medium power in industrial, commercial or service buildings. It can also be used
to tap off directly from the joint, between two lengths, for rising main distribution or low density distribution applications.
This trunking has a compact design, namely with plated conductors inside a metal enclosure. The standard range is IP 52
(IP 54 as an option). The isolated conductor bars are made of copper. The range is divided into 6 ratings from 200 to 800
A. The insulation used on the conductors is halogen-free 130C class B polyester.
The trunking has :
- 4 conductors for the 3-pole + neutral version (crosssection of the neutral equal to the cross-section of the
phases).Recommended for TNC scheme.
The metal enclosure in prelacquered galvanised sheet
steel (RAL 7032) provides protection and mechanical
resistance for the conductors along their entire length.
Moreover, the metal enclosure is used as a protective
conductor (conforming to NF C15-100) with continuity
ensured at each junction along the length of the
installation.Recommended for TNS scheme. Canalis KVC
can be fitted with an additional copper protective conductor
(cross-section equal to half the cross-section of the
phase).Recommended for TNS scheme. With its compact
design (no free space within the trunking), Canalis KVC
can be mounted horizontally, edgewise or vertically without
derating the rated current Ith. Moreover, this design does
not require the mounting of a fire barrier joint to pass
through floors and walls. Canalis KVC is designed to be
fire-resistant for up to 2 hours.

Run components
ET Type
These are designed to feed current through horizontal or
vertical runs. A joint between two lengths can be replaced
by a special joint which can be used as a tap-off point.
These lengths are produced in fixed lengths of 4 metres or
in 0.35 m to 2 metre lengths as required.
EV Type
These are designed for rising main distribution. The joint
between two lengths can be used as a tap-off point. These
lengths are produced in fixed lengths of 1, 2 and 3 metres
or in 2.50 m to 4 metre lengths as required.
They should be mounted with the neutral on the left.
Junction block

1/10

Te

1 This is supplied with the ET run components and the


components for changing direction. It provides an
electrical and mechanical joint. When the run has a feed
unit at both ends, an additional junction block must be
ordered.
2 This is supplied with the EV run components. It can be
ordered separately if ET components are used to replace
the junction block and enable tap-off. It provides an
electrical and mechanical joint as well as a tap-off point.
The electrical junction is ensured by a single junction block
(1 to 2 bolts per bar) which provides continuity for all the
conductors. The bolt is made up of a screw and a contraction
nut, the external head of which breaks when the tightening
torque is reached. When the head of the nut breaks, a red
washer is released, showing that the electrical junction
operation has been completed successfully. For disassembly
or maintenance operations, a second head is available.
The recommended torque is thus 3 daNm. The junction
block contacts are silver-plated copper.

Medium power busbar trunking


Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Description

Connection components and feed units


Connection components can be mounted at either end of the run. If there is a feed unit at both ends of the run, an additional
junction block should be ordered.
Flange feed unit
The flange feed unit is fitted with a mounting plate (on the
switchboard or transformer cover) and bars. These bars
are spread along the axis of the trunking and enable direct
connection, by flexible or rigid bars, or by cables, to the low
voltage terminals of a transformer or the connections of a
low voltage switchboard.

Switchboard connection component


The switchboard connection component is fitted with a
plate for fixing to the switchboard. Its flexible construction
means that it can be connected directly to the connections
or the protection device, and provides a multidirectional
feeder at the switchboard outlet.
The fixing plate, which runs along the length of the flexible
bar, can be connected directly to the protection device
inside the switchboard, wherever it is situated.
Warning : for connection by braid, a fixer must be provided
every 300 mm (maximum value) inside the switchboard. To
do this, use the Prisma P cable tray.

KH - KV connector
The KH - KV connector supplies a feed run directly from a
KH high power distribution tap-off unit. Its flexible design
accommodates any changes in alignment, level and axis.
It is fitted at one end with an SB or SD tap-off unit outlet
plate from the KH range with flexible braids for connection
to the protection device and, at the other end, with a KV
connector end.

Te

1/11

Medium power busbar trunking


Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Description

Connection components and feed units (continued)


KV - KS connector
The KV - KS connector is fitted with a KV connector end at
one end and a KS connector end at the other.
Due to its flexible design, it ensures direct connection from
a feed run to a distribution run and reduces any risk caused
by alignment faults.

Feed unit casings


Feed unit casings are available in two versions, no. 1 and
no. 2, which allow the run to be fed to the right or to the left
respectively. They can be used for connecting by cables up
to a rating of 800 A.

End cover
The end cover protects and isolates the ends of the
conductors and is mounted on the last length.

Components for changing direction


These components adapt the trunking direction to the contours of the building by changing direction and level. There are
two types :
1 Rigid :
- Flat or edgewise elbows, upwards or downwards, to the left or right
- Edgewise or flat tees
2 Flexible :
EF type flexible components are available for all ratings up to 800 A. These components are made of copper. They are
produced in 2 metre and 1 metre lengths and are designed for changing direction and going round obstacles and can
be used as end of site components.
1

1/12

Te

Medium power busbar trunking


Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Description

Fixing devices
1 Universal bracket
This device is used to fix the run to the structure of the building, directly or via a threaded rod, a bracket, etc. There
is one model for all casing sizes in the KV range which can be used for ceiling-mounting, suspended mounting, wallmounting, etc. The maximum recommended fixing centre is 4 metres.
2 Fixing support
Suitable for fixing the vertical run component to the structure of the building, this type of fixing support has the following
advantages :
- The height can be adjusted to correct positioning errors.
- The spring can be adjusted to ensure the load is distributed at each level.
- The constraints of the building (expansion, vibration, etc) are not transmitted to the trunking.

Tap-off units
The tap-off units which are mounted on the KV range are bolted type, tightened by a single bolt with breakable head. They
are mounted in place of a junction block. They must be installed or removed with the power off.
There are 2 types :
1 Single feeder tap-off unit for Compact NS circuit-breaker. Designed for rising main distribution or low density
distribution applications, it has the following characteristics :
- It is available in 2 ratings (250 and 400 A).
- The door can only be opened after a load break.
- Degree of protection IP 52/54.
- When the door is open, no live part can be accessed, degree of protection IP 2X.
2 Multi-feeder tap-off unit for Compact NS and multi 9 Merlin Gerin circuit-breakers. Designed for rising main distribution
applications, it has the following characteristics :
- It has a distribution switchboard function which will allow several feeders per floor.
- It is available up to a maximum power rating of 250 A.
- Degree of protection IP30 as standard and IP 40 with door.
This distribution principle relies on the extensive Prisma range.

2
1

Te

1/13

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Selection guide

Determining the rating according to the temperature rise


The rating of a busbar trunking, in amps, represents the maximum intensity of the constant current which the trunking can
continuously support, for an average ambient temperature of 35 C, and in accordance with standard temperature rises
(IEC 439.2).
Determining the rating according to the temperature rise consists of selecting the busbar trunking rating immediately
above the operating current of the installation. However, as a rule, the intensity of the current which crosses a busbar
trunking is constantly fluctuating. The operating current is therefore defined as that of the constant current which produces
the same thermal effects as the actual current.
It is sometimes difficult to determine the operating current, especially when there is no reading for the installation or for
an equivalent installation. The operating current can be estimated with sufficient precision by calculating the product of
the nominal currents of receivers connected to the busbar trunking by a coefficient known as the average demand
coefficient. The average demand coefficient is empirically determined by comparison with existing installations. It is
dependent upon :
- the average quantity of receivers operating
- the load variation of each receiver (a receiver rarely absorbs its maximum power, as peak periods alternate with those
of no-load operation)
- whether several receivers are operating at the same time, whether peaks are superimposed and the duration of these
peaks
As an example, here are a few coefficients for a general mechanical engineering workshop.
Number of receivers

Average demand coefficient

2 or 3

0.9

4 or 5

0.8

6 to 9

0.7

10 to 40

0.6

40 plus

0.5

Depending on the ambient temperature, the trunking must be derated (see characteristics pages 11013/2 and 11013/3).

Checking the rating according to the permissible voltage drop


The permissible voltage drop is that which is compatible with the correct operation of receivers (refer to the manufacturers'
manuals).
i Read the voltage drop in mV/m/A in the tables on page 11013/3 for the busbar trunking selected according to the
temperature rise.
i Determine the voltage drop for the most disadvantaged receivers, namely those which are the furthest from the source
and for the highest current. If the voltage drop is not permissible, select the rating immediately above.
i Repeat the checking procedure for the new rating.

Checking the rating according to withstand to short-circuit currents


i Calculate the intensity of the short-circuit current at the points which are considered to be unfavourable.
i Check, by referring to the tables on pages 11013/2 and 11013/3, that the selected rating of the trunking enables it to
withstand this short-circuit current. If this is not the case, there are two possible solutions :
- Select trunking of a higher rating and repeat the checking procedure.
- Provide a protection system which limits current peaks upstream of the trunking.

1/14

Te

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Selection guide

Example of selecting the rating of the busbar trunking


The table below can be used to determine the rating of the KVC busbar trunking (copper conductors) according to the
power of the transformer.
Transformer (U2 = 410 V)
Power
Nominal
current
kVA
A

Short-circuit
current
kA

Canalis busbar trunking


Type
Nominal
current
A

Short-circuit
current
kA rms

100

141

KVC-20

200

7.2

160

225

KVC-31

315

17

250

352

KVC-40

400

19

400

563

14

KVC-63

630

31

500

704

17.6

KVC-80

800

41

Calculation assumptions
The following calculation assumptions have been made :
- the short-circuit power of the upstream supply : 500 MVA
- the voltage ratio of the transformers : 20 kV/400 V
The circuit-breaker/trunking coordination table below gives directly the maximum short-circuit current for which the KVC
trunking is protected, according to the type of circuit-breaker.

Type of trunking

KVC-20

KVC-31

KVC-40

KVC-63

KVC-80

Rating (A)

200

315

400

630

800

45
70
150

45
70
150

45
70
150

45
70
150

45
70
150

45
70
150

Merlin-Gerin
Compact
circuit-breaker

Masterpact
circuit-breaker

NS250

N
H
L

35
70
100

NS 400

N
H
L

35
35
35

NS 630

N
H
L

C 801
C1001

N
H
L

40
40
70

50
60
110

M 08
M 10

N1
H1
H2
L1

33
33
33
40

40
40
40
55

Te

1/15

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Characteristics

Type of trunking

KVC-20

KVC-31

KVC-40

KVC-63

KVC-80

General characteristics
Conforming to standards

IEC 439.2

Number of live conductors

Type of live conductors

Copper

Type of current

Hz

c 50/60 - (1)

Rated insulation voltage

1000

Rated operating voltage

1000

Degree of protection (IEC 529)


(as standard)

IP 52, IP 54 for horizontal, edgewise installation and vertical installation


IP 52 for horizontal, flat installation

Permissible currents
Rated current Ith (2)
conforming to IEC 439

200

315

400

630

800

Rated peak current

kA

26

48

52

76

82

Permissible rated short time


current (1 s)

kA rms 7.2

18

19

31

35

Multiplying
Temperature C
factors of the
rated current
Ith depending
Factor
on the average
ambient temperature

35

40

45

50

0.95

0.90

0.84

Conductor characteristics
Live conductors
Rb0phAverage resistance per
conductor, cold state
(ambient temperature 20 C)

m/m 0.539

0.216

0.198

0.086

0.078

Rb1phAverage resistance per


conductor at Ith
(ambient temperature 35 C)

m/m 0.666

0.266

0.245

0.106

0.0967

Xph Average reactance per


conductor

m/m 0.01

0.01

0.01

0.01

0.005

ZphAverage impedance per


conductor

m/m 0.666

0.266

0.245

0.106

0.0967

(1) For 60 to 400 Hz AC or for DC : please consult your Regional Sales Office.
(2) Rated currents Ith are given for an average ambient temperature of 35C and for a casing temperature rise of no more
than 55K according to the test conditions of standard IEC 439.2.

1/16

Te

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
References :
pages 11014/2 to 11014/13
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Characteristics

Type of trunking

KVC-20

KVC-31

KVC-40

KVC-63

KVC-80

Other characteristics
Live conductors
Rb1ph ph or phN Average resistance
of fault loops between
live conductors

m/m

1.332

0.532

0.49

0.212

0.193

Rb2ph ph or phN Average resistance


of fault loops between
live conductors

m/m

1.598

0.638

0.588

0.254

0.232

Rb1ph PE Average resistance


of fault loops between
live conductors and PE

m/m

1.33

0.93

0.784

0.645

0.425

Xb1ph ph or phN Average reactance


of fault loops between
live conductors

m/m

0.02

0.02

0.02

0.02

0.01

Xb1ph PE Average reactance


of fault loops between
live conductors and PE

m/m

0.02

0.02

0.02

0.02

0.01

Voltage drop

Composite voltage drop, hot state, in millivolts per metre and per amp, for three-phase 50 Hz current, with load
concentrated at the end of the run (feed run). If the load is distributed along the run, voltage drops are half the values
indicated in the table below.
For a power factor
of 0.7

mV/m/A 0.820

0.336

0.308

0.144

0.124

For a power factor


of 0.8

mV/m/A 0.934

0.38

0.35

0.160

0.139

For a power factor


of 0.9

mV/m/A 1.046

0.422

0.388

0.178

0.154

For a power factor


of 1

mV/m/A 1.154

0.462

0.424

0.188

0.168

Equivalent
copper
cross-section

mm2

26

26

32

32

42

Average resistance,
cold state (ambient
temperature 20C)

m/m

0.664

0.664

0.539

0.539

0.328

Equivalent
copper
cross-section

mm2

40

40

102

102

165

Average resistance,
cold state (ambient
temperature 20C)

m/m

0.298

0.298

0.145

0.145

0.11

3L + N + PE

kg/m

5.7

6.6

10.7

15.8

3L + N + PER

kg/m

4.2

7.2

11.5

16.8

Protective conductor
Casing

Additional
conductor

Average weight

Te

1/17

KVC-iiETiii
KVC-iiEViii

KVC-iiETiii
KVC-iiEViii

KVC-iiETiii
KVC-iiETiii

1/18

Te

KVC-iiEViii

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Run components for horizontal and vertical feeding. IP 52
References

Straight lengths (1)


Rating

Type

Length
MinMax
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

200

Fixed

4000

KVC-20ET440
15.60

KVC-20ET740
16.50

315

Fixed

4000

KVC-31ET440
22.80

KVC-31ET740
24.00

Made to measure

3502000

KVC-31ET42B
12.00

KVC-31ET72B
12.60

400

Fixed

4000

KVC-40ET440
26.20

KVC-40ET740
29.40

630

Fixed

4000

KVC-63ET440
42.60

KVC-63ET740
45.80

Made to measure

3502000

KVC-63ET42B
22.20

KVC-63ET72B
23.80

Fixed

4000

KVC-80ET440
63.00

KVC-80ET740
67.00

Made to measure

3502000

KVC-80ET42B
33.00

KVC-80ET72B
35.00

800

Junction block, IP 54 (2)


Busbar trunking rating

3L + N + PE
3L + N + PER
Reference

Weight
kg

200 and 315

KV0-31YA4

1.20

400 and 630

KV0-63YA4

1.80

800

KV0-80YA4

3.00

(1) To order a made to measure component, see the procedure on pages 11016/2 and 11016/3.
(2) Only order if the run has a feed unit at each end.

N : position of neutral

Te

1/19

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Run components for rising main distribution, IP 52
References

Straight lengths (1)


Rating

Type

Lengths
MinMax
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

Fixed

3000

KVC-20EV430
12.00

KVC-20EV730
12.60

2000

KVC-20EV420
8.40

KVC-20EV720
8.40

1000

KVC-20EV410
4.80

KVC-20EV710
5.10

25003000

KVC-20EV43D
12.00

KVC-20EV73D
12.60

30013500

KVC-20EV43E
13.80

KVC-20EV73E
13.50

35014000

KVC-20EV44F
15.60

KVC-20EV74F
16.50

3000

KVC-31EV430
17.40

KVC-31EV730
18.30

2000

KVC-31EV420
12.00

KVC-31EV720
12.60

1000

KVC-31EV410
6,60

KVC-31EV710
7.05

25003000

KVC-31EV43D
17.40

KVC-31EV73D
18.30

30013500

KVC-31EV43E
20.10

KVC-31EV73E
21.15

35014000

KVC-31EV44F
22.80

KVC-31EV74F
24.00

3000

KVC-40EV430
20.10

KVC-40EV730
22.50

2000

KVC-40EV420
14.00

KVC-40EV720
15.60

1000

KVC-40EV410
7.90

KVC-40EV710
8.70

25003000

KVC-40EV43D
20.10

KVC-40EV73D
22.50

30013500

KVC-40EV43E
23.15

KVC-40EV73E
25.95

35014000

KVC-40EV44F
26.20

KVC-40EV74F
29.40

A
200

Made to measure

315

Fixed

Made to measure

400

Fixed

Made to measure

N : position of neutral
1/20

Te

(1) To order a made to measure component, see the procedure on pages 11016/2 and 11016/3.

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Run components for rising main distribution, IP 52
References

Straight lengths (1)


Rating

Type

Lengths
MinMax
mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

Fixed

3000

KVC-63EV430
32.40

KVC-63EV730
34.80

2000

KVC-63EV420
22.20

KVC-63EV720
23.80

1000

KVC-63EV410
12.20

KVC-63EV710
12.80

25003000

KVC-63EV43D
32.40

KVC-63EV73D
34.80

30013500

KVC-63EV43E
37.40

KVC-63EV73E
39.30

35014000

KVC-63EV44F
42.60

KVC-63EV74F
45.80

3000

KVC-80EV430
48.00

KVC-80EV730
51.00

2000

KVC-80EV420
33.00

KVC-80EV720
35.00

1000

KVC-80EV410
18.00

KVC-80EV710
19.00

25003000

KVC-80EV43D
48.00

KVC-80EV73D
51.00

30013500

KVC-80EV43E
55.50

KVC-80EV73E
59.00

35014000

KVC-80EV44F
63.00

KVC-80EV74F
67.00

Rating

3L + PEN

Reference
Weight (kg)

3L + N + PER
3L + N + PE
Reference
Weight (kg)

200 and 315

KV0-25YA4
1.50

KV0-25YA4
1.50

400 and 630

KV0-40YA41
2.40

KV0-40YA41
2.40

800

KV0-40YA42
3.10

KV0-40YA42
3.10

A
630

Made to measure

800

Fixed

Made to measure

Junction/tap-off blocks, IP 54 (2)

N : position of neutral

(1) To order a made to measure component, see the procedure on pages 11016/2 and 11016/3.
(2) Only order for transforming a feed run in low density distribution.

Te

1/21

KV0-iiERii200
KV0-iiERii200

KV0-iiERii1004

KV0-iiABi000i

KV0-iiER41001
KV0-iiER4100i

1/22

Te

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Connection components and feed units, IP 52
End covers

Description :
pages 11011/2 to 11101/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

References
Feed units

a
N

End feed box


Rating

Lengths a, e

mm

200 and 315

150

400 and 630

150

800

150

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

KV0-31ER40200
2.70
KV0-63ER40200
5.10
KV0-80ER40200
10.00

KV0-31ER70200
2.90
KV0-63ER70200
5.50
KV0-80ER70200
10.50

KV0-31AB40001
3.80
KV0-63AB40001
7.20
KV0-80AB40001
14.00

KV0-31AB70001
4.00
KV0-63AB70001
7.70
KV0-80AB70001
14.70

KV0-31AB40002
3.80
KV0-63AB40002
7.20
KV0-80AB40002
14.00

KV0-31AB70002
4.00
KV0-63AB70002
7.70
KV0-80AB70002
14.70

N1 feed unit with connection via cable

N1

200 and 315

400 and 630

800

N2 feed unit with connection via cable


200 and 315

400 and 630

800

Switchboard connection component


N2

Rating

3L + N + PE
3L + N + PER
Reference

Weight
kg

315

KV0-31ER71004

12.60

630

KV0-63ER71004

23.80

800

KV0-80ER71004

55.00

KV - KS connector (3L + N + PE)


KV = 315/KS = 250

KV = 630/KS = 500

KV = 800/KS = 800

KV0-25ER41001
12.60

KV0-50ER41001
23.80

KV0-80ER41001
43.00

KV = 315
KH SB400 unit

KV = 315
KH SD400 unit

KV = 630
KH SB1000 unit

KV = 800
KH SB1000 unit

KV0-25ER41002
12.60

KV0-50ER41003
12.60

KV0-63ER41002
23.80

KV0-80ER41002
43.00

KH - KV connector (3L + N + PE)


N

End cover IP 54 (3L + N + PE ou 3L + N + PER)

Busbar trunking rating


A

Reference

Weight
kg

200 and 315

KV0-31FA

1.00

400 630

KV0-63FA

1.10

800

KV0-80FA

1.20

Ni : position of neutral

Te

1/23

KV0-iiEFii0

KV0-iiLCi05

KV0-iiLCi05

KV0-iiLPi042

KV0-iiLPi042
KV0-iiLPi041
KV0-iiLPi041

1/24

Te

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Components for changing direction : flexible components, simple elbows, IP 52

Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

References

Flexible components
Rating

Length

mm

200 and 315

1000

KV0-31EF710

7.10

2000

KV0-31EF720

12.60

1000

KV0-63EF710

12.80

2000

KV0-63EF720

23.80

1000

KV0-80EF710

23.00

2000

KV0-80EF720

43.00

Edgewise LC
Rating

Lengths a, b

mm

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

200 and 315

250

KV0-31LC005
1.00

KV0-31LC005
1.00

400 and 630

250

KV0-63LC405
6.90

KV0-63LC705
7.30

800

250

KV0-80LC405
13.00

KV0-80LC705
13.50

200 and 315

200

KV0-31LP4041
3.40

KV0-31LP7041
3.50

400 and 630

200

KV0-63LP4041
5.90

KV0-63LP7041
6.20

800

200

KV0-80LP4041
11.00

KV0-80LP7041
11.40

200 and 315

200

KV0-31LP4042
3.40

KV0-31LP7042
3.50

400 and 630

200

KV0-63LP4042
5.90

KV0-63LP7042
6.20

800

200

KV0-80LP4042
11.00

KV0-80LP7042
11.40

400 and 630

800

Weight
kg

3L + N + PE
3L + N + PER
Reference

Elbows

N1

N1 flat LP

a
N2

N2 flat LP

Ni : position of neutral

Te

1/25

KV0-80ZA1
KV0-iiTCi07

KV0-80ZA1
KV0-iiTCi07

KV0-80ZA1
KV0-iiTPi092

KV0-80ZA1
KV0-iiTPi091

1/26

Te

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Component for changing direction : Tees, IP 52
Fixing devices

Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

References
Tees
c

Edgewise TC
Rating

Lengths a, b, c

mm

200 and 315

3L + N + PE
Reference
Weight (kg)

3L + N + PER
Reference
Weight (kg)

250

KV0-31TC407
5.30

KV0-31TC707
5.50

400 and 630

250

KV0-63TC407
9.50

KV0-63TC707
10.10

800

250

KV0-80TC407
18.00

KV0-80TC707
18.80

200 and 315

300

KV0-31TP4091
6.10

KV0-31TP7091
6.40

400 and 630

300

KV0-63TP4091
11.00

KV0-63TP7091
11.70

800

300

KV0-80TP4091
21.00

KV0-80TP7091
21.90

200 and 315

300

KV0-31TP4092
6.10

KV0-31TP7092
6.40

400 and 630

300

KV0-63TP4092
11.00

KV0-63TP7092
11.70

800

300

KV0-80TP4092
21.00

KV0-80TP7092
21.90

Description
A

Rating

Reference

Horizontal fixing bracket

200...800

KV0-80ZA1

0.50

Vertical fixing for


rising main distribution

200 and 315

KV0-31ZA2

1.00

400 and 630

KV0-63ZA2

1.00

800

KV0-80ZA2

1.00

c
b

N1 flat TP
N1

N2

c
b

N2 flat TP

Fixing devices
Weight
kg

Ni : position of neutral

Te

1/27

KV0-iiCB71103
KV0-iiDB06

KV0-iiCB71103
KV0-iiYAii

KV0-iiCB71103

KV0-iiDB06

1/28

Te

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
Dimensions :
pages 11015/2 to 11015/5

Canalis KVC (200 to 800 A)


Tap-off units
References

Single feeder tap-off unit


Type

Rating

Degree of
protection

3L + N + PE
Reference

IP 52

KV0-25CB71103

5.50

IP 54

KV0-25CB71103E

5.50

IP 52

KV0-40CB71103

7.00

IP 54

KV0-40CB71103E

7.00

Weight
kg

A
For Compact NS circuit-breaker

250

400
KV0-25CB71103

Junction/tap-off blocks, IP 54
Rating

3L + N + PE
3L + PEN
Reference

Weight
kg

A
200 and 315

KV0-25YA4

1.50

400 and 500

KV0-40YA41

2.40

630 and 800

KV0-40YA42

3.10

Multi-feeder tap-off unit, IP 300


Type
A

Rating

Reference

Weight
kg

For Compact NS circuit-breaker


+ modular

250

KV0-01DB06

15.00

Accessories for multi-feeder tap-off units (250 A)


Description

Reference

Weight
kg

Solid door

KV0-00PP06

3.00

Transparent door

KV0-00PT06

5.00

KV0-01DB06

Te

1/29

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Run components
Connection components and feed units

Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Caractristiques :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Dimensions

h (1)

Straight length
KVC-iiEiiii

L
Fixed
L = 4000
L = 1000, 2000 and 3000

Made to measure
L = 350...2000
L = 25004000
Junction/tap-off block
KV0-iiYAii

200

84

280

90

280

End feed box


KV0-iiERi0200

Dimensions of
connector ranges

Cross-section of trunking
according to its rating

h (1)

40

h (1)

20

60

67

9 x 14

60

50
110

60

60

350

h (1)

9 x 14 33,5

150

h (1)

9 x 14 33,5

70

70

13

13 13

13

92

Type of length
For horizontal feeding and distribution
For rising main distribution
Junction block
KV0-iiYAi

70

190

400

200

h (1)

Switchboard connection component


KV0-iiERi1004

200

400 2500
3000
(1) Height of the trunking according to its rating
Rating (A)
200 and 315
h
44
1/30

Te

400 and 630


71

800
114

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Connection components and feed units

Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Dimensions

h (1)

15

Cable feed unit


KV0-iiABi000i

10

20

30

20

70
3

67
3

2
c

60

10

20

20

40

8,5

Dimensions of the unit according to the rating


Rating (A)
h
a
b
c
200 and 315
44
200
650
300
400 and 630
71
200
700
400
800
114
200
700
450

a
b

60

50

d
450
500
500

y
150
170
190

146

h (1)

KV - KS connector
KV0-iiER41001

2000

KV rating
(A)
315
630
800

44
71
114

54
75
113

KH - KV connector
KV0-iiER41002

h (1)

Plate for SB or SD unit

2000

(1) Height of the trunking according to its rating


Rating (A)
200 and 315
h
44

400 and 630


71

800
114

Te

1/31

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Tap-off units

Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Dimensions

Single feeder tap-off unit


KV0-iiCB71103

b
200
300

c
210
230

Rating (A)
a
250
525
400
600
Multi-feeder tap-off unit
KV0-iiDB06

Rating (A)
250
400

a
550
550

b
600
600

c
200
200

Te

1/33

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Canalis KVC (200 to 800 A)


Options, procedure for ordering a made to measure component

Options
The degree of protection for standard references is IP 52. To obtain degree IP 54, A1 should be added at the end of the
standard reference (degree IP 54 can only be obtained by factory assembly).
Similarly, if the trunking is to be mounted outside, A2 should be added at the end of the standard reference. The product
is supplied as IP 54 with an aluminium cover.

IP 52

+ option A1

= IP 54
(Edgewise only)

IP 52

+ option A2

= IP 54 + Cover
(Mounted outside
edgewise only)

Procedure for ordering a made to measure component


Position of neutral
Upper joint cover

Cover fixing sockets


(for locating)

A
a

Neutral

Lower
joint cover

Junction block

The neutral is located next to the socket closest to the end of the panel work (a).
Definition of a component
Shape
Each shape is characterised by a group of two letters (example : ET for a feed length).
Dimensions
Dimensions are always given in alphabetical order of the measurements (a, b, c, etc).
How to order
The order should be made on two lines :
i First line
Write the reference found in this catalogue.
i Second line
Write the dimensions for the made to measure component and any of the options selected :
- If the reference corresponds to a made to measure product, there are one or more variable values : you should
write a x b x etc in alphabetical order.
- If the reference ends in A followed by a number, an option is available (see above).

1/34

Te

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Canalis KVC (200 to 800 A)


Procedure for ordering a made to measure component

Procedure for ordering a made to measure component (continued)


Straight lengths
There are two types of component :
- ET components designed for feeding current along horizontal or vertical runs, available in 0.35 to 2 metre lengths.
- EV components designed for rising main distribution with tap-off at joints, available in 2.50 metre to 4 metre lengths.
They are defined according to floor height.
For feeding, a standard joint can be replaced by a special joint known as a junction/tap-off block which can be used as
a tap-off point. To take advantage of this option with ET components, there is a space on the order form to show :
- a junction/tap-off block reference (for example KV0-25YA4)
- a single feeder unit reference (for example KV0-25CB71103)
The nominal length L of a straight length is measured, from joint axis to joint axis, in millimetres (the joint axis is located
20 mm beyond the end of the bars).
Example :
Joint axis
L1
L2
L3
N
PE

40
=

=
206
L

A KVC straight length, rating 800 A, 3L + N + PE, 1820 mm long, has the following reference :
KVC - 80ET42B
L = 1820

Te

1/35

Medium power busbar trunking


Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Canalis KVC (200 to 800 A)


Installation precautions

2-metre flexible component


The 2-metre flexible component can be used to make the changes in direction shown on the diagrams below :
- edgewise (diagram A)
- flat (diagram B)
1

Max 300

Diagram A : edgewise flexible component

Max 700

Diagram B : flat flexible component

Min. radius 100

1 Fixing

1-metre flexible component


The 1-metre flexible component can be used to make the
changes in direction shown in the diagram opposite.
Fixing

Min. angle 60

1/36

Te

Medium power busbar trunking


Canalis KVC (200 to 800 A)
Installation precautions (continued)

Vertical mounting for rising main distribution

Floor height







If you use floor height lengths (from 2.50 to 4 metres),


position the 1st joint at around 1.70 metres above the floor.
This operation requires a made to measure component L1.

Level 2

1700

L1

Description :
pages 11011/2 to 11011/5
Selection guide :
pages 11012/2 and 11012/3
Characteristics :
pages 11013/2 and 11013/3
References :
pages 11014/2 to 11014/13

Level 1

Te

1/37