DATA POINT SUMMARY FOR BUILDING AUTOMATION SYSTEM


Sr. No.

Description

AI

DI

AO

DO

Schedule

Trend

Alarm

Grahics

Bacnet / Modbus Interface


License

Chiller (3 Nos.)

Chillers - ON / OFF

Chiller run status

Chiller Auto / Manual switch

Chillers Trip / Fault

CHW supply / return temp.

Common Header CHW supply / return temp.

Ambient Temperature & Humidity

Chiller
isolation
Mortised
command & status.

valves

BMS
BMS
BMS

Immersion temperature sensor

Immersion temperature sensor

12

Ambient temp/Humidity sensor

ON/OFF

3
#

Differential pressure sensor and transmitter across


chilled water header

10

Chilled Water Flow Status

Primary Chilled Water Pumps

Pump ON / OFF

Pump run status

Pump Auto / Manual switch status

CHW pump trip status.

Condenser Water Pumps

Condenser Water pump ON / OFF Command.

Condenser Water pump ON / OFF status.

Condenser Water pump Auto / Manual status.

Condenser Water pump trip status.

Cooling Tower

Cooling Tower sump outlet temperature.

Cooling Tower fan ON/OFF command.

Cooling Tower fan trip status.

Cooling Tower fan Auto/ Manual status.

Sump level monitoring low

Make up water tank

CHW Motorised Valve

CHW Motorised Valve Open/ Close Command

CHW Motorised Valve Open/ Close Status

#
3

#
3

3
24

49

#
#

#
0

AHU ON/OFF

AHU blower status

25

AHU Auto / Manual status

25

AHU filter status

25

Return Air Temperature

25

#
25

Potential Free Contact from BMS


to Pump Starter panel
Differential pressure switch across
the CHW pumps for ON/OFF
status.
Signal from A/M switch.

potential

Potential Free Contact to BMS Potential Free Contact in Chiller


from Chiller MCC panel
Panel
Potential Free Contact to BMS Potential Free Contact in Chiller
from Chiller MCC panel
Panel

Differential Switch across Fans

Duct Temperature Sensor

Suitable Insertion Provision in AHU

0-10 V DC Signal

2 / 3 Way Control Valve by


HVAC, with acceptance of 0-10
V DC Signal

Fan Air Flow status

Differential Switch across Fans

Fan Auto / Manual status

Potential
Free
Contact
Auto/Manual Switch

Ventillation/ Exhuast Fans

Fan ON/OFF

Data Point Summary

Suitable Insertion Provision in AHU

Potential
Free
Contact
at Potential Free Contact in AHU
Auto/Manual Switch
Panel
Differential Pressure Switch across
Suitable Insertion Provision in AHU
filter

Fan ON/OFF

in

#
#
#

4
4

#
#
#
#

4
7

14

Provision

4
4
4
12

Suitable Insertion
Water Line

Imm type temp sensor.


Potential Free Contact from BMS Acceptance of Potential Free
to CT Starter panel
Output in CT Panel
Signal
from
potential
free Potential Free Contact in CT
contact.
Panel
Signal
from
potential
free Potential Free Contact in CT
contact.
Panel
Suitable Insertion Provision in
Signal from level switch
Cooling Tower
Suitable Insertion Provision in
Signal from level switch
Cooling Tower

Sub Total (K)

Acceptance of Potential Free


Output in Pump Panel

25
4

4
4
4
12

in

Potential Free Contact in Pump


Panel
free Potential Free Contact in Pump
Panel

25

Provision

Potential Free Contact from BMS Acceptance of Potential Free


to Pump Starter panel
Output in Pump Panel
Suitable Insertion Provision in
Differential Switch across Pumps
Water Line
Potential
Free
Contact
at Potential Free Contact in Pump
Auto/Manual Switch
Panel
Signal
from
potential
free Potential Free Contact in Pump
contact.
Panel

Sub Total (F)


Plant Roof Ventilation
Fan ON/OFF Command
Fan ON/OFF Status
Fan Trip
Fan Auto/ Manual Status
Sub Total (I)
TFA Units
Fan ON/OFF Command
Fan ON/OFF Status
Fan Trip
Fan Auto/ Manual Status
Sub Total (J)
Pressurization Fans

75

in

Potential Free Contact from BMS Acceptance of Potential Free


to fan Starter panel
Output in AHU Panel

25

25

Provision

18

Air Handling Units - (25 Nos.)

Motorised Valve Cooling

Potential Free Contact from BMS Butterfly Valves


to motorised butter fly valve with
limit switch for position status.
Suitable Insertion
Differential Pressure Sensor
Water Line
Suitable Insertion
Suitable insertion provision
Water Line

Signal
from
contact.

BMS

Sub Total (A+B+C+D+E)

Potential Free Contact from


to Chiller MCC panel
Potential Free Contact to
from Chiller MCC panel
Potential Free Contact to
from Chiller MCC panel
Potential Free Contact to
from Chiller MCC panel

HVAC Vendor to provide RS 485


MODBUS / Bacnet interface in
each chiller. HVAC Vendor to
show the parameters on the
MODSCAN /Bacstack/Cimetrics
software before integrating to
IBMS. All mapping details & the
Master/slave ID setting in the
Chillers to be done by the HVAC
Contractor
Acceptance of Potential Free
Output in Chiller Panel
Potential Free Contact in Chiller
Panel
Potential Free Contact in Chiller
Panel
Potential Free Contact in Chiller
Panel
Suitable Insertion Provision in
Water Line
Suitable Insertion Provision in
Water Line

Potential Free Contact from BMS Acceptance of Potential Free


to fan Starter panel
Output in AHU Panel

Suitable Insertion Provision in AHU


at Potential Free Contact in AHU
Panel

39

Potential Free Contact from BMS Acceptance of Potential Free


to fan Starter panel
Output in AHU Panel

DPS- 2

DATA POINT SUMMARY FOR BUILDING AUTOMATION SYSTEM


Sr. No.

Description

AI

DI

AO

DO

Schedule

Trend

Alarm

Grahics

Fan Air Flow status

39

Differential Switch across Fans

Fan Auto / Manual status

39

Potential
Free
Contact
Auto/Manual Switch

CO Level Monitoring in Parking Areas

CO Sensors

Sub Total (L)


Fire Fighting System
Hydrant pressure monitroing

Pressure Sensor

Sprinkler pressure monitroing

Pressure Sensor

1
2
3
4
5
6
7

#
78

Jockey Pump run status

Sprinkler Pump run status

Fire Pump Run Status (Electrically driven)

Sprinkler / Hydrant header flow status

Suitable insertion provision

Potential Free Contact water DP


switch

Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line

#
#
#

1
4

at Potential Free Contact in AHU


Panel

39

Fire Pump Run Status (Diesel driven)


Sub Total (M)

Suitable Insertion Provision in AHU

Potential Free Contact water DP


switch
Potential Free Contact water DP
switch
Potential Free Contact water DP
switch

Provision

in

Provision

in

Provision

in

Provision

in

Provision

in

Provision

in

Provision

in

Water Supply System

Fire Water Tank High / Low Level

Level Switch

Suitable Insertion Provision

Raw Water Tank High / Low Level

Level Switch

Suitable Insertion Provision

Treated Water Tank High / Low Level

Level Switch

Suitable Insertion Provision

Soft Water Tank High / Low Level

Level Switch

Suitable Insertion Provision

Fire Pump Auto/Manual Status

Fire Pump run status

Raw Water Pump Auto/Manual Status

Raw Water Pump run status

Soft Water Pump Auto/Manual Status

10

Soft Water Pump run status

Potential Free Contact to BMS


from fan Starter panel
Differential pressure switch across
the pumps
Potential Free Contact to BMS
from fan Starter panel
Differential pressure switch across
the pumps
Potential Free Contact to BMS
from fan Starter panel
Differential pressure switch across
the pumps

Potential Free Contact in Pump


Panel
Suitable Insertion Provision in
Water Line
Potential Free Contact in Pump
Panel
Suitable Insertion Provision in
Water Line
Potential Free Contact in Pump
Panel
Suitable Insertion Provision in
Water Line

Sub Total (N)

28

Electrical System - HT Panels , LT Panels

HT / LT Panel Phase Voltage Monitoring

HT / LT Panel Phase Current Monitoring

HT / LT Panel Frequency Monitoring

HT / LT Panel KW Monitoring

HT / LT Panel KWH Monitoring

6
7
8

HT / LT Breaker On/Off status


Bus Coupler On/Off Status
HT / LT Panel Trip Status
Sub Total (O)

Through Modbus Output of Multi data


meters

#
#
#

10
10
10
0

30

Diesel Generator

DG Start/Stop Stauts

DG AMF Breaker Status

3
4

Bulk Storage Tank level Monitoring


DG Oil Day Tank Level
Sub Total (P)

Lifts / Escalators

UPS Nos on Modbus RTU / Bacnet

Fire Alarm System

VFD
Grand Total (A to T)

Data Point Summary

#
4

310

25

of suitable rating CT in
of suitable rating CT/PT
of suitable rating CT/PT
of suitable rating CT/PT
Free Contact in Panel
Free Contact in Panel
Free Contact in Panel

#
#

DG Panel vendor to provide RS


485 MODBUS RTU. The electrical
vendor to show the parameters
on the MODSCAN software
Integration
through
Modbus
before integrating to IBMS. All
Protocol
mapping
details
&
the
Master/slave ID setting in the
meter to be done by the DG
vendor
Potential Free Contact from BMS
to DG Starter panel
Potential Free Contact from BMS
to DG Starter panel
Flame Proof Level Transmitter
Flame Proof Level Transmitter

0
Integration of Lifts through
Modbus Protocol.
Integration of UPS through
Modbus Protocol / Bacnet
Integration of FAS through
Modbus/Bacnet/OPC Protocols of
all devices/detectors
Integration of VFD through
Modbus/Bacnet protocol

62

of suitable rating PT in

2
2
4

Provision
Panel
Provision
Panel
Provision
in Panel
Provision
in Panel
Provision
in Panel
Potential
Potential
Potential

97