Modicon Quantum Processors

Unity Operating Systems Compatibility Rules


This document concerns Operating Systems compatibility, exceptions and recommendations for native Unity Pro Processors.
Please refer to the Whats New documentation in Unity Pro for information about compatibility between Operating System versions,
application program versions and Unity Pro versions.

Definitions
Copro = Coprocessor: embedded Ethernet port.
PV =
Product Version: the PV increases by one digit when a functional change is made in an Operating System, in a Copro or in a
Hardware part.
SV =
Software Version: the version of the Operating System (OS) delivered with the Processor module.

Compatibility Rules & Recommendations


1. Processor Operating Systems are upward compatible: updating a processor with a higher Operating System version is always allowed.
2. It is recommended to always upgrade the OS version of a processor with the latest available version.
3. It is recommended that the Copro version is associated with the OS version indicated in the QUANTUM - Launch History tables below
(mandatory for HotStandby Systems).
4. It is mandatory to upgrade the Ethernet Coprocessor before the Processor OS.
5. It is not recommended to downgrade the OS of a Processor:

Attention
Do not download an OS version V2.31 or lower in the
processors listed below. Otherwise, it will no longer be
possible to change the OS version:
Quantum
140CPU65150

PV
>= 15

140CPU65150C

>= 15

140CPU65160

>= 15

140CPU65160C

>= 15

140CPU67160

>= 13

140CPU67160C

>= 13

140CPU67160C

>= 13

Minimum version required to update Quantum from Concept to


Unity:
Quantum

PV

140CPU43412A

>=04

140CPU53414A

>=04

CPUs with PV < 04 include RAM Memory chip whose characteristics


are not totally adapted to the Unity program execution.
According to the used memory size, these CPUs can work in Unity
range but can also present defects in case of Online changes,
configuration changes or programs size increase.
The consequences that can have are:
- No start of the CPU
- Some modules are not working in the configuration.

1/4
EIO000000005602

Quantum HotStandby
A Unity Quantum Hot Standby system must have strictly identical configurations for both PLCs:
Same Copro version
Same Operating System (also called EXEC) version.
Note: It is possible to upgrade the CPU (OS and Copro) of a Quantum HSBY configuration with a higher version without stopping the system.
Please refer to the Modicon Quantum Hot Standby with Unity Pro" User Manual for complete information and recommendations.
Also, please refer to the online documentation in Unity Pro to check the executable compatibility (and the exceptions) of an application program
with the Operating System version.

Limitations on the online upgrade procedure

For the Operating System, it is not recommended to upgrade an OS Version V2.xx to version V2.40 or V2.41.
For the Coprocessor, it is not recommended to upgrade a Copro version V0.80 to version V2.50.
It is strongly recommended to use the latest versions of OS V2.80 and the Copro V2.80.
Recommendations on the OS V2.80 upgrade:
The OS version V2.80 brings a better stability of the HSBY system by synchronizing the cycle time of the 2 PLCs.
However, for some StandBy application the cycle time may be increased and become greater than the configured period. Due to the
new synchronization mechanism, an Overrun is more controlled in V2.80, and therefore this will lead the standBy PLC to go to
HALT mode.
In this case, it is enough to adjust the StandBy PLC period time to find a normal functioning.

Change Configuration On The Fly functionality on Quantum High End and Low End
The version V2.80 of Quantum HE and LE CPU contains all features to perform CCOTF functionalities.
It requires an UnityPro Application built with UnityPro V5.0 and the binary files of 140CRP 93100/93200 /140CRA93100/93200 in version V2.0,
available under RIO_modules folder in this eCD.
The Quantum OS V2.80 is compatible with the previous versions of the CRP/CRA modules and with UnityPro Application < V5.0.
To upgrade CRA / CRP modules please refer to the Quantum_Upgrade_Procedure document available on this eCD.

2/4
EIO000000005602

140 NOE 771 11 Upgrade


Due to hardware changes (ROHS compliance), two different firmware files are delivered for the 140 NOE 771 11 module, depending on
the PV version.
Use the appropriate file to upgrade the 140 NOE 771 11 module:
NOE Module

PV

File Name

140 NOE 771 11


140 NOE 771 11

>= 10
<= 9

140NOE77111_V460.BIN
140NOE77111_INF_OR_EQ_PV09_V460.BIN

140CRA93x0 and 140CRP93x0 Upgrade


Due to hardware changes (ROHS compliance), two different firmware files are delivered for 140CRP93x0 and 140CRA93x0 modules,
depending on the PV version.
Use the appropriate file to upgrade the 140CRA93x0 and 140CRP93x0 modules:
CRA Modules
140 CRA 93100
140 CRA 93200
140 CRA 93100
140 CRA 93200
CRP Modules
140 CRP 93100
140 CRP 93200
140 CRP 93100
140 CRP 93200

PV

File Name

>= 9

RCRAV200.BIN

<= 8

QCRAV200.BIN

PV

File Name

>= 8

RCRPV200.BIN

<= 7

QCRPV200.BIN

3/4
EIO000000005602

QUANTUM - Launch History


140CPU67160 (HSBY)
140CPU67160C (HSBY)

140CPU65150 (C)
140CPU65160 (C)

140CPU65260

140CPU65260C
Copro

140CPU31110

140CPU31110C

OS

OS

OS

OS

Copro HSBY

OS

Copro

OS

Copro

PV01

SV2.41

V2.20 (IE69)

SV2.0

SV1.0

SV2.0

PV02

SV2.40

V2.20 (IE69)

SV2.41

V2.20 (IE69)

SV2.01

SV2.0

SV2.01

PV03

SV2.0

V2.0 (IE78)

SV2.41

V2.20 (IE69)

SV2.50

V2.50 (IE77)

SV2.02

SV2.01

SV2.02

PV04

SV2.01

V2.0 (IE78)

SV2.41

V2.20 (IE69)

SV2.60

V2.60 (IE 78)

SV2.10

SV2.02

SV2.10

PV05

SV2.02

V2.0 (IE78)

SV1.0

SV2.41

V2.20 (IE69)

SV2.61

V2.60 (IE 78)

SV2.10

SV2.10

SV2.10

PV06

SV2.10

V2.0 (IE78)

SV2.0

V2.0 (IE56)

SV2.50

V2.50 (IE77)

SV2.70

V2.70 (IE82)

SV2.11

SV2.10

SV2.11

PV07

SV2.11

V0.79

SV2.01

V2.0 (IE56)

SV2.60

V2.60 (IE78)

SV2.70

V2.70 (IE82)

SV2.30

SV2.11

SV2.30

PV08

SV2.11

V0.80

SV2.02

V2.0 (IE56)

SV2.61

V2.60 (IE78)

SV2.80

V2.80 (IE83)

SV2.31

SV2.30

SV2.31

PV09

SV2.11

V0.80

SV2.10

V2.10 (IE62)

SV2.70

V2.70 (IE82)

SV2.40

SV2.31

SV2.40

PV010

SV2.23

V0.80

SV2.11

V2.10 (IE62)

SV2.70

V2.70 (IE82)

SV2.50

SV2.40

SV2.50

PV011

SV2.30

V0.80

SV2.11

V2.10 (IE62)

SV2.80

V2.80 (IE83)

SV2.60

SV2.50

SV2.60

PV012

SV2.31

V0.80

SV2.23

V2.10 (IE62)

SV2.70

SV2.60

SV2.70

PV013

SV2.32

V0.80

SV2.30

V2.20 (IE69)

SV2.70

SV2.70

SV2.70

PV014

SV2.40

V0.80

SV2.31

V2.20 (IE69)

SV2.80

SV2.70

SV2.80

PV015

SV2.41

V0.80

SV2.32

V2.20 (IE69)

SV2.80

PV016

SV2.50

V2.50 (IE04)

SV2.40

V2.40 (IE72)

V1.0 (IE46)

OS

140CPU43412U(C)
140CPU53414U(C)

PV017

SV2.50

V2.50 (IE04)

SV2.41

V2.40 (IE72)

PV018

SV2.50

V2.51 (IE06)

SV2.50

V2.50 (IE77)

PV019

SV2.60

V2.60 (IE08)

SV2.50

V2.50 (IE77)

PV020

SV2.61

V2.60 (IE08)

SV2.60

V2.60 (IE78)

PV021

SV2.70

V2.70 (IE10)

SV2.61

V2.60 (IE78)

PV022

SV2.80

V2.80 (IE22)

SV2.70

V2.70 (IE82)

PV023

SV2.70

V2.70 (IE82)

SV2.80

V2.80 (IE83)

PV024

Note: To get the version of OS, Copro or Ethernet modules please refer to the Quantum_Upgrade_Procedure document available on this eCD.
4/4