FORM:YCA-A-CATL-102002

HIGH PERFORMANCE SCROLL COMPRESSOR


AT YOUR FINGER TIPS

YCA20 - YCA115 (A Series)


(R22/R407C)
20 - 115 TON
70 - 400 kW
AIR-COOLED SCROLL CHILLER

TABLE OF CONTENTS
PAGE
INTRODUCTION ........................................................................................................................................... 3
SPECIFICATIONS ........................................................................................................................................ 4
MILLENNIUM CONTROL CENTER ...............................................................................................................5
DESIGN PARAMETER ................................................................................................................................. 6
WATER FLOW (GPM) AGAINST PRESSURE DROP (FT) .......................................................................... 6
OPTIONS AND ACCESSORIES .................................................................................................................. 7-8
SELECTION DATA ...................................................................................................................................... 8-10
RATINGS DATA ......................................................................................................................................... 11-18
PHYSICAL DATA ........................................................................................................................................ 19-20
DIMENSIONS ............................................................................................................................................ 21-32
SPRING LOCATIONS ................................................................................................................................ 33-36
ELECTRICAL NOTES ................................................................................................................................... 37
ELECTRICAL DATA ................................................................................................................................... 37-39
SINGLE POINT WIRING DIAGRAM ............................................................................................................. 39
APPLICATION DATA ..................................................................................................................................... 40
GUIDE SPECIFICATIONS ......................................................................................................................... 40-44

050

YORK
A Generation
Chiller
Air-Cooled

Nominal Cooling
Capacity

INTRODUCTION

YORK Millennium Air-Cooled Scroll Chillers provide chilled water for all air conditioning
applications using central station air handling units or terminal units. They are completely
self-contained and are designed for outdoor (roof or ground level) installation. Each unit
includes hermetic scroll compressors, a liquid cooler, air cooled condenser, and a weather
proof microprocessor control center, all mounted on a formed steel base.

SPECIFICATIONS
GENERAL
The 20-115 Ton (70-400 kW) YCA Models are shipped
complete from the factory ready for installation and
use.
The unit is pressure-tested, evacuated, and fully
charged with Refrigerant-22 (HCFC-22) or optional
R-407C and includes an initial oil charge. After
assembly, a complete operational test is performed
with water flowing through the cooler to ensure that
the refrigeration circuit operates correctly.

The operating program is stored in non-volatile


memory (EPROM) to eliminate chiller failure due to
AC powered failure/battery discharged. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.

COMPRESSORS

POWER PANEL

The chiller has suction-gas cooled, hermetic, scroll


compressors. The compressors features are nocontact scroll design utilizing floating tip seals. High
efficiency is achieved through a controlled orbit and
the use of an advanced scroll geometry. All rotating
parts are statically and dynamically balanced. A large
internal volume and oil reservoir means greater liquid
tolerance.

Each panel contains:


Compressor power terminals
Compressor motor soft starters or across-the-line
starting contactors per I.E.C.
Control power terminals to accept incoming for
115-1-50 / 60 control power
Fan contactors & overload current protection

COOLER
The cooler is covered with 19mm (3/4) flexible,
closed-cell, foam insulation (K=0.25).
The water baffles are constructed of galvanized steel
to resist corrosion.

CONDENSER
Coils -The condenser coils are seamless copper
tubes arranged in staggered rows, mechanically
expanded into aluminum fins. Integral subcooling
is included. The testing pressure of the coil is 450PSIG
(31 bar).
Fans - The condenser fans consist of corrosion
resistant aluminum hub and glass fiber reinforced
composite blades molded into a low noise design. They
are designed for maximum efficiency and are statically
and dynamically balanced for vibration free operation.
They are directly driven by independent motors, and
positioned for vertical air discharge. The fan guards
are constructed of heavy-gauge, rust-resistant and
oven baked polyester coating.
Motors - The fan motors are Totally Enclosed Force
Cooling, squirrel-cage type. They feature ball bearings
that are double-sealed and permanently lubricated.

Provisions are included for: pumpdown at shutdown;


optional remote chilled water temperature reset and
two steps of demand load limiting from an external
building automation system. Unit alarm contacts are
standard.

The power wiring is routed through liquid-tight conduit


to the compressors and fans.

MILLENNIUM CONTROL CENTER

MILLENNIUM CONTROL CENTER


All controls are contained in a weather proof cabinet
with hinged outer door and includes:
Liquid Crystal Display with Light Emitting Diode backlighting for outdoor viewing:Two display lines
Twenty characters per line
Color coded 12-button non-tactile keypad with
sections for:
DISPLAY/PRINT of typical information:
Chilled liquid temperatures
Ambient temperature
System pressures (each circuit)
Operating hours and starts (each compressor)
Operating data for the systems
History of fault shutdown data for up to the last
six fault shutdown conditions.
An RS-232 port, in conjunction with this press
to-print button, is provided to permit the capability
of hard copy print-outs via a separate printer.
ENTRY section to:
ENTER setpoints or modify system values
SETPOINTS updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (Compressor start cycle time)
Anti-coincident timer (delay compressor starts)

UNIT SECTION TO:


Set Time
Set unit options
UNIT ON/OFF switch
The microprocessor control center is capable of
displaying the following:

Return and leaving liquid temperature


Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Outdoor air temperature
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure (optional)
Liquid Temperature Reset via a YORK ISN DDC
or Building Automation System (by others) via:
- a pulse width modulated (PWM) input as standard
- a 4-20 milliamp or 0-10 VDC input, or contact
closure with the optional B.A.S. interface option
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system definition
Compressor starts & operating hours (each
compressor)
Status of hot gas valves and fan operation
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load & unload timer status
Water pump status

DESIGN PARAMETER
Leaving water temp (F)
MIN
MAX

YCA
20
25
30
40
50
60
70
80
95
115

40
40
40
40
40
40
40
40
40
40

Air on condenser (F)


MIN
MAX

Cooler Flow (GPM)


MIN
MAX

50
50
50
50
50
50
50
50
50
50

29
37
49
61
75
94
121
124
147
182

67
84
112
140
173
217
257
284
334
419

0
0
0
0
0
0
0
0
0
0

105
105
105
105
105
105
105
105
105
105

Notes:
1 For leaving brine temp below 40F(4.4C), contact your nearest YORK office for application requirements.
2 For leaving water temp higher than 50F(12.8C), contact the nearest YORK office for application guidelines.
3 For operation at temp below 25F(-3.9C), the optional low ambient kit will need to be installed on the system.

WATER FLOW (GPM) AGAINST PRESSURE DROP (FT)


WATER FLOW (GPM) AGAINST
PRESSURE DROP (FT)

80

YC

30

70

20
A

A
YC

YC

PRESSURE DROP (FT)

60
50

A
YC

25

YC

40

60

YC

30

A7

50
YCA
95
YCA
15
A
YC 1
0
8
YCA

20
10
0.00
50.00

100.00

125.00

150.00

175.00

WATER FLOW (GPM)

200.00

225.00

250.00

OPTIONS AND ACCESSORIES


POWER OPTIONS:
COMPRESSOR POWER CONNECTIONS - See
electrical data for specific voltage and options availability.
(Factory-mounted.)
SINGLE-POINT NON-FUSED DISCONNECT
SWITCH - A disconnect switch with external, lockable
handle can be supplied by others to isolate the unit
power voltage for servicing. Separate external fusing
must be supplied, by others in the power wiring, which
must comply with the National Electrical Code and/
or local codes.
SINGLE-POINT CIRCUIT BREAKER - A circuit
breaker with external, lockable handle can be
supplied by others to isolate the power voltage for
servicing.
POWER FACTOR CORRECTION CAPACITORS Will correct unit compressor power factors to a
0.90-0.95. (Factory-mounted)
CONTROLS OPTIONS:
AMBIENT KIT (LOW) - Standard units will operate
to 25F(4C). This accessory includes all necessary
components to permit chiller operation to 0F (-18C).
(This option includes the Discharge Pressure
Transducer/Readout Capability option). For proper
head pressure control in applications below 25F
(-4C) where wind gusts may exceed 5 mph., it is
recommended that optional Condenser Louvered
Enclosure Panels also be included. (Factory-mounted.)

BUILDING AUTOMATION SYSTEM INTERFACE The factory addition of a Printed Circuit Board to
accept a 4-20 milliamp, 0-10VDC or contact closure
input to reset the leaving chiller liquid temperature
from Building Automation System. (Only one of
following options can be offered on a unit at a time:
BAS, Remote Control Panel or Multiunit Sequence
Control). (Factory-mounted)
- The standard unit capabilities include remote
startstop, remote water temperature reset via a
PWM input signal or up to two steps of demand
(load) limiting depending on model.
- The standard control panel can be directly
connected to a YORK Building Automated System
via the standard on board RS485 communication
port.
DISCHARGE PRESSURE TRANSDUCERS AND
READ OUT CAPABILITY - The addition of pressure
transducers allows models to sense and display
discharge pressure.This is recommended for brine
chilling applications. (This option as included with
either the low or high ambient kits). (Factory-mounted)
COMPRESSOR, PIPING, EVAPORATOR OPTIONS:
LOW TEMPERATURE BRINE - For brine chilling
applications below 30F (-1C) LCWT. Standard units
will operate down to 40F (4.4C). Option Includes
resized thermal expansion valves. (Factory-mounted)
DX COOLER 21 Bar (300 PSIG) DWP WATERSIDE
- The waterside will be of 300 PSIG (21 bar) instead
of the standard 150 PSIG (10.5 bar) DWP. 300 PSIG
(216mm) R.F. flanges are included on the DX cooler
nozzles. (Factory-mounted.) The companion flanges
will be field-supplied by others.

OPTIONS AND ACCESSORIES (Continued)


DIFFERENTIAL PRESSURE SWITCH - Alternative
to the above mentioned flow switch.
COPPER FIN CONDENSER COILS - The unit
constructed with condenser coils which have copper
fins. (This is not recommended for units in areas
where they may be exposed to acid rain)

COMPRESSOR ACOUSTIC SOUND BLANKET Each compressor is individually enclosed by an


acoustic sound blanket. The sound blankets are made
with one layer of acounstical absorbent textile
fiber of 5/8 (15mm) thickness; one layer of
anti-vibrating material, reinforced for temperature and
UV resistance. (Factory-mounted)

GRILL (Condenser Coil Only) - Grille are mounted


on the sides and ends of the condenser coils for
protection. (Factory-mounted)

SELECTION DATA
GUIDE TO SELECTION
Capacity ratings for YORK YCA Packaged Air-Cooled
Liquid Chillers, shown on pages 11 cover the majority
of design applications for these units. For unusual
applications or uses beyond the scope of this catalog,
please consult your nearest YORK Office or
representative.
SELECTION RULES
1. RATINGS - Ratings may be interpolated, but must not
be extrapolated. The Ratings given on pages 11
and the DESIGN PARAMETERS given on the
page 6 indicate the limits of application for these
chillers.
2. COOLER WATER - Ratings are based upon 2.4 GPM
per ton (0.15L/S per cooling kW) which is equal to
a 10F (5.6C) chilled water range and a 0.0001
fouling factor for the cooler at sea level.
Tables on pages 10 give capacity, and compressor
kW required.

3. CONDENSER - Ratings are given in terms of air on


condenser in degrees Fahrenheit (Celcius)
4. COPPER FIN CONDENSER RATINGS - Since
the thermal conductivity of copper is slightly higher
than aluminum, apply the following corrections to
the standard ratings. Capacity x1.01 compressor
kW x 0.99.
5. PERFORMANCE DATA CORRECTION
FACTORS - Ratings are based on 0.0001
cooler fouling factor, 10F (5.6C) chilled water
range and at sea level. For operation at different
conditions, apply the appropriate correction factor
from the following table.

SELECTION DATA (Continued)


ALTITUDE

CHILLED

FOULING FACTOR

WATER

.0001

.00075

.00175

T(F)

TONS

kW

TONS

.995

.997

.967

.987

.920 .965

SEA

10

1.000 1.000

.975

.989

.927 .968

LEVEL

12

1.005 1.002

.981

.991

.933 .970

14

1.010 1.004

.985

.993

.939 .973

.985

1.005

.961

.993

.912 .972

10

.989

1.007

.965

.995

.917 .975

12

.995

1.009

.971

.999

.925 .977

14

1.000 1.011

.975

1.001 .930 .981

.974

1.012

.949

1.001 .903 .979

10

.979

1.014

.955

1.004 .909 .983

12

.984

1.017

.961

1.006 .914 .985

14

.988

1.019

.962

1.008 .920 .988

2000 FT

4000 FT

6000 FT

kW TONS kW

.963

1.020

.939

1.009 .893 .988

10

.968

1.022

.945

1.011 .898 .990

12

.972

1.024

.949

1.013 .904 .993

14

.976

1.025

.955

1.016 .910 .995

Determine capacity requirements from the following


formula:
GPM =
TR x 24
RANGE (F)
or
L/S
= kW (CAPACITY) x .239
RANGE (C)
EXAMPLE-WATER CHILLING
1. GIVEN: Provide a capacity of 48 Tons at 44F leaving
water 10F range, 0.0001FF, 85F air on the
condenser, at sea level and 50 Hz.
2. FIND: Unit Size
Compressor kW input
3. From the Ratings on pages 11.
SELECT: YCA50, R22 (English Units)
49.9 Tons
46.7 Compressor kW
4. Calculate Compressor kW at 48 Tons:

6. ETHYLENE GLYCOL CORRECTION FACTORS The following factors are to be applied to the
standard ratings for units cooling ethylene glycol.

kW

= 48 x 46.7kW = 44.9kW
49.9

5. Calculate GPM :
% WT

FACTORS

FREEZE

ETHYLENE
GLYCOL

POINT
TONS COMPR.

DELTA

GPM/F/

(F)

KW

TON

10

.994

.997

1.03

24.1

26.6

20

.986

.993

1.06

24.9

16

30

.979

.990

1.09

25.9

40

.970

.985

1.13

27.3

-10

50

.959

.980

1.16

29.0

-32

METHOD OF SELECTION
To select of YORK Packaged Air-Cooled Liquid Chiller,
the following data must be known:
1. Design Capacity in tons cooling kW or refrigeration
(TR).

GPM = 48 Tons x 24 = 115.2GPM


10F Range
6. From page 6, read 3.5ft. of water cooler pressure
drop for GPM:
7. A YCA50SC is suitable.
EXAMPLE -BRINE CHILLING
1. GIVEN: Provide a capacity of 65 tons cooling 30%
by weight Ethylene Glycol from 50F to 40F,
0.0001FF, 95F air on the condenser, 50 Hz and
4000ft. altitude.
2. DETERMINE: Unit Size
kW Input
Ethylene Glycol GPM
Cooler Pressure Drop

2. Entering and Leaving Liquid Temperatures.


3. Outside ambient air temperature in degrees F (or C).
4. L/S or GPM of chilled liquid.

SELECTION DATA (Continued)


3. See Ethylene Glycol correction factors, for 30%
by weight Ethlene Glycol.
READ:

.979 Tons factor


.990 Compr.kW factor
25.9 Gal./F/Tons factor

4. See performance Data Correction Factors for


0.0001 fouling factor and 4000 ft. altitude.
READ:

.979 Tons factor


1.014 kW factor

5. From RATINGS on pages 12:


SELECT:

YCA70, R22 (English Units)


70 Tons
77.3 Compressor kW

6. Determine YCA70, R22 brine cooling capacity and


compressor kW requirement:

8. Determine Ethylene Glycol GPM:


GPM = Tons x Gal. F/min/Ton factor
Range
GPM =

67 x 25.9
10

GPM =

173.53

9. Determine Cooler Pressure Drop:


A. See Ethylene Glycol correction factors for 30%
by weight Ethylene Glycol.
READ : 1.09 Pressure Drop Factor
B. See page 6 at 173.53 GPM for YCA70, R22.
READ : 17.5 Ft. H2O Pressure Drop
C. Cooler Pressure Drop = 17.5 x 1.09 or 19.07 Ft H2O
10.YCA70, R22 is suitable.

A. Tons = 70 x .979 x .979 = 67


B. Compr. kW = 77.3 x .990 x 1.014 = 77.6
7. Determine average full load Compressor kW at
65 tons:
65 tons x (77.3kW) = 74.9 Compressor kW
67 tons

10

RATINGS DATA
YCA 50Hz, R22 Performance Rating
Air on condenser F
Model

20

25

30

40

50

LCWT (F)

75

80

85

90

95

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

18.8

16.1

18.5

16.9

18.1

17.8

17.6

18.8

17.2

19.8

16.7

20.9

16.2

22.1

42

19.5

16.2

19.1

17.1

18.7

18.0

18.3

19.0

17.8

20.0

17.3

21.1

16.8

22.2

44

20.2

16.4

19.8

17.2

19.4

18.2

19.0

19.1

18.5

20.1

18.0

21.2

17.4

22.4

45

20.6

16.4

20.2

17.3

19.7

18.2

19.3

19.2

18.8

20.2

18.3

21.3

17.7

22.5

46

20.9

16.5

20.5

17.4

20.1

18.3

19.6

19.3

19.1

20.3

18.6

21.4

18.1

22.6

48

21.7

16.7

21.2

17.5

20.8

18.4

20.3

19.4

19.8

20.4

19.3

21.6

18.7

22.7

50

22.4

16.8

22.0

17.7

21.5

18.6

21.0

19.6

20.5

20.6

20.0

21.8

19.4

22.9

40

23.5

20.1

23.1

21.2

22.6

22.3

22.0

23.5

21.5

24.8

20.9

26.1

20.3

27.6

42

24.4

20.3

23.9

21.3

23.4

22.5

22.8

23.7

22.3

25.0

21.7

26.3

21.0

27.8

44

25.2

20.5

24.8

21.5

24.2

22.7

23.7

23.9

23.1

25.2

22.5

26.5

21.8

28.0

45

25.7

20.6

25.2

21.6

24.7

22.8

24.1

24.0

23.5

25.3

22.9

26.6

22.2

28.1

46

26.1

20.6

25.6

21.7

25.1

22.8

24.6

24.1

23.9

25.4

23.3

26.8

22.6

28.2

48

27.1

20.8

26.5

21.9

26.0

23.0

25.4

24.3

24.8

25.6

24.1

27.0

23.4

28.4

50

28.0

21.0

27.5

22.1

26.9

23.2

26.3

24.5

25.6

25.8

24.9

27.2

24.2

28.7

40

31.4

26.9

30.8

28.2

30.1

29.8

29.4

31.4

28.7

33.1

27.9

34.9

27.1

36.8

42

32.5

27.1

31.9

28.5

31.2

30.0

30.5

31.6

29.8

33.3

28.9

35.1

28.0

37.0

44

33.7

27.3

33.1

28.7

32.3

30.3

31.6

31.9

30.8

33.6

30.0

35.4

29.1

37.4

45

34.3

27.4

33.6

28.8

32.9

30.4

32.2

32.0

31.4

33.7

30.5

35.5

29.6

37.5

46

34.9

27.5

34.2

29.0

33.5

30.5

32.8

32.1

31.9

33.8

31.0

35.7

30.1

37.7

48

36.1

27.8

35.4

29.2

34.7

30.7

33.9

32.4

33.1

34.1

32.1

36.0

31.2

37.9

50

37.4

28.0

36.6

29.5

35.9

31.0

35.0

32.6

34.2

34.4

33.3

36.3

32.3

38.2

40

39.2

33.5

38.4

35.3

37.6

37.2

36.7

39.2

35.8

41.3

34.8

43.6

33.8

45.9

42

40.6

33.8

39.8

35.5

39.0

37.5

38.1

39.5

37.2

41.6

36.1

43.9

35.0

46.3

44

42.1

34.1

41.3

35.9

40.4

37.8

39.5

39.8

38.4

41.9

37.4

44.2

36.3

46.7

45

42.8

34.2

42.0

36.0

41.1

37.9

40.2

39.9

39.2

42.1

38.1

44.4

37.0

46.8

46

43.6

34.4

42.7

36.2

41.8

38.1

40.9

40.1

39.9

42.3

38.8

44.6

37.6

47.0

48

45.1

34.7

44.2

36.5

43.3

38.4

42.3

40.4

41.3

42.6

40.1

44.9

39.0

47.4

50

46.7

35.0

45.7

36.8

44.8

38.7

43.7

40.8

42.7

43.0

41.5

45.3

40.3

47.8

40

48.5

41.5

47.5

43.6

46.5

45.9

45.4

48.4

44.3

51.1

43.1

53.9

41.8

56.8

42

50.3

41.8

49.2

43.9

48.2

46.3

47.1

48.8

45.9

51.5

44.7

54.3

43.3

57.2

44

52.0

42.2

51.1

44.3

49.9

46.7

48.8

49.2

47.5

51.9

46.3

54.6

44.9

57.7

45

53.0

42.3

51.9

44.5

50.8

46.9

49.7

49.4

48.4

52.1

47.1

54.9

45.7

57.9

46

53.9

42.5

52.8

44.7

51.7

47.1

50.6

49.6

49.3

52.3

47.9

55.1

46.5

58.2

48

55.8

42.9

54.6

45.1

53.5

47.5

52.3

50.0

51.1

52.7

49.6

55.5

48.2

58.6

50

57.7

43.3

56.6

45.5

55.4

47.9

54.1

50.4

52.8

53.1

51.4

56.0

49.9

59.0

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

11

RATINGS DATA
YCA 50Hz, R22 Performance Rating
Air on condenser F
Model

60

70

80

95

115

LCWT (F)

75

80

85

90

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

60.7

51.9

59.5

54.6

58.2

57.5

56.8

60.6

55.4

63.9

53.9

67.4

52.3

71.1

42

62.9

52.3

61.6

55.0

60.3

58.0

58.9

61.1

57.5

64.4

55.9

67.9

54.2

71.6

44

65.1

52.8

63.9

55.5

62.5

58.5

61.1

61.6

59.5

64.9

57.9

68.4

56.2

72.2

45

66.3

53.0

65.0

55.7

63.6

58.7

62.2

61.8

60.6

65.2

59.0

68.7

57.2

72.5

46

67.4

53.2

66.1

56.0

64.7

58.9

63.3

62.1

61.7

65.4

60.0

69.0

58.2

72.8

48

69.8

53.7

68.4

56.5

67.0

59.4

65.5

62.6

63.9

65.9

62.1

69.5

60.3

73.3

50

72.2

54.2

70.8

57.0

69.3

59.9

67.7

63.1

66.1

66.5

64.3

70.1

62.4

73.9

40

71.8

61.0

70.3

64.5

68.5

68.2

66.8

72.1

65.1

76.3

63.3

80.7

61.3

85.4

42

74.4

61.4

72.8

65.0

71.2

68.6

69.4

72.6

67.5

76.8

65.6

81.2

63.7

85.9

44

77.2

62.0

75.4

65.4

73.7

69.2

71.9

73.1

70.0

77.3

68.0

81.6

66.0

86.4

45

78.5

62.2

76.9

65.6

75.0

69.4

73.2

73.3

71.3

77.6

69.3

81.9

67.2

86.6

46

79.9

62.4

78.2

65.9

76.4

69.6

74.5

73.5

72.5

77.8

70.6

82.1

68.4

86.9

48

82.7

62.9

80.9

66.3

79.1

70.1

77.2

74.0

75.1

78.3

73.1

82.6

70.9

87.4

50

85.6

63.3

83.8

66.8

81.8

70.6

79.8

74.5

77.8

78.8

75.6

83.2

73.4

87.9

40

79.7

68.2

78.1

71.7

76.4

75.5

74.6

79.6

72.8

83.9

70.8

88.5

68.7

93.4

42

82.6

68.7

80.9

72.2

79.2

76.2

77.4

80.2

75.5

84.6

73.4

89.2

71.2

94.0

44

85.5

69.3

83.9

72.9

82.1

76.8

80.2

80.9

78.1

85.2

76.0

89.8

73.8

94.8

45

87.1

69.6

85.4

73.2

83.5

77.1

81.7

81.2

79.6

85.6

77.5

90.2

75.1

95.2

46

88.5

69.9

86.8

73.6

85.0

77.4

83.1

81.6

81.0

85.9

78.8

90.6

76.4

95.6

48

91.7

70.5

89.8

74.2

88.0

78.0

86.0

82.2

83.9

86.6

81.6

91.3

79.2

96.3

50

94.8

71.2

93.0

74.9

91.0

78.7

88.9

82.9

86.8

87.3

84.5

92.1

82.0

97.1

40

95.0

81.2

93.1

85.5

91.1

90.0

88.9

94.9

86.7

100.0

84.4

105.5

81.9

111.3

42

98.5

81.9

96.4

86.1

94.4

90.8

92.2

95.6

90.0

100.8

87.5

106.3

84.8

112.1

44

101.9

82.7

100.0

86.9

97.8

91.6

95.6

96.4

93.1

101.6

90.6

107.1

88.0

113.0

45

103.8

83.0

101.7

87.2

99.6

91.9

97.4

96.7

94.9

102.1

92.4

107.5

89.5

113.5

46

105.5

83.3

103.5

87.7

101.3

92.2

99.1

97.2

96.6

102.4

93.9

108.0

91.1

114.0

48

109.3

84.1

107.1

88.4

104.9

93.0

102.5

98.0

100.0 103.2

97.2

108.8

94.4

114.7

50

113.0

84.8

110.8

89.2

108.5

93.8

106.0

98.8

103.5 104.1

100.7 109.7

97.7

115.7

40

117.2

100.2 114.9

105.5

112.4 111.1

109.7 117.0

107.0 123.4

104.1 130.2

101.0

137.3

42

121.5

101.0 119.0

106.2

116.5 112.0

113.8 118.0

111.1 124.4

108.0 131.1

104.7

138.3

44

125.7

102.0 123.4

107.2

120.7 113.0

118.0 119.0

114.9 125.4

111.8 132.1

108.5

139.5

45

128.1

102.4 125.5

107.6

122.8 113.4

120.1 119.4

117.0 125.9

114.0 132.7

110.5

140.0

46

130.2

102.8 127.7

108.2

125.0 113.8

122.3 119.9

119.2 126.3

115.9 133.3

112.4

140.6

48

134.8

103.7 132.1

109.1

129.4 114.7

126.5 120.9

123.4 127.3

119.9 134.2

116.5

141.6

50

139.5

104.7 136.7

110.1

133.9 115.7

130.8 121.9

127.7 128.4

124.2 135.4

120.5

142.7

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

12

95

RATINGS DATA
YCA 60Hz, R22 Performance Rating
Air on condenser F
Model

20

25

30

40

50

LCWT (F)

75

80

85

90

95

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

18.6

15.9

18.3

16.8

17.9

17.7

17.4

18.6

17.0

19.6

16.6

20.7

16.1

21.8

42

19.3

16.1

18.9

16.9

18.5

17.8

18.1

18.8

17.7

19.8

17.2

20.9

16.6

22.0

44

20.0

16.2

19.6

17.0

19.2

18.0

18.8

18.9

18.3

19.9

17.8

21.0

17.3

22.2

45

20.4

16.3

20.0

17.1

19.5

18.0

19.1

19.0

18.6

20.0

18.1

21.1

17.6

22.3

46

20.7

16.3

20.3

17.2

19.9

18.1

19.4

19.1

19.0

20.1

18.4

21.2

17.9

22.4

48

21.4

16.5

21.0

17.4

20.6

18.2

20.1

19.2

19.6

20.2

19.1

21.3

18.5

22.5

50

22.2

16.6

21.7

17.5

21.3

18.4

20.8

19.4

20.3

20.4

19.8

21.5

19.2

22.7

40

24.0

20.5

23.5

21.6

23.0

22.7

22.5

24.0

21.9

25.3

21.3

26.7

20.7

28.1

42

24.9

20.7

24.4

21.8

23.8

22.9

23.3

24.2

22.7

25.5

22.1

26.9

21.4

28.3

44

25.7

20.9

25.3

21.9

24.7

23.1

24.2

24.4

23.5

25.7

22.9

27.1

22.2

28.6

45

26.2

21.0

25.7

22.0

25.2

23.2

24.6

24.4

24.0

25.8

23.3

27.2

22.6

28.7

46

26.7

21.0

26.1

22.1

25.6

23.3

25.0

24.6

24.4

25.9

23.7

27.3

23.0

28.8

48

27.6

21.2

27.1

22.3

26.5

23.5

25.9

24.8

25.3

26.1

24.6

27.5

23.8

29.0

50

28.6

21.4

28.0

22.5

27.4

23.7

26.8

25.0

26.1

26.3

25.4

27.7

24.7

29.2

40

29.2

25.0

28.6

26.3

28.0

27.7

27.3

29.2

26.7

30.7

25.9

32.4

25.2

34.2

42

30.3

25.2

29.6

26.5

29.0

27.9

28.3

29.4

27.7

31.0

26.9

32.7

26.1

34.5

44

31.3

25.4

30.7

26.7

30.1

28.1

29.4

29.6

28.6

31.2

27.9

32.9

27.0

34.7

45

31.9

25.5

31.3

26.8

30.6

28.2

29.9

29.7

29.2

31.4

28.4

33.1

27.5

34.9

46

32.4

25.6

31.8

26.9

31.1

28.3

30.5

29.9

29.7

31.5

28.9

33.2

28.0

35.0

48

33.6

25.8

32.9

27.2

32.2

28.6

31.5

30.1

30.7

31.7

29.9

33.4

29.0

35.3

50

34.7

26.1

34.1

27.4

33.3

28.8

32.6

30.4

31.8

32.0

30.9

33.7

30.0

35.6

40

38.4

32.9

37.7

34.6

36.9

36.4

36.0

38.4

35.1

40.5

34.1

42.7

33.1

45.0

42

39.8

33.1

39.0

34.8

38.2

36.7

37.3

38.7

36.4

40.8

35.4

43.0

34.3

45.3

44

41.2

33.4

40.5

35.1

39.6

37.0

38.7

39.0

37.7

41.1

36.7

43.3

35.6

45.7

45

42.0

33.6

41.2

35.3

40.3

37.2

39.4

39.1

38.4

41.3

37.4

43.5

36.2

45.9

46

42.7

33.7

41.9

35.5

41.0

37.3

40.1

39.3

39.1

41.4

38.0

43.7

36.9

46.1

48

44.2

34.0

43.3

35.8

42.4

37.6

41.5

39.6

40.5

41.7

39.3

44.0

38.2

46.4

50

45.7

34.3

44.8

36.1

43.9

37.9

42.9

40.0

41.9

42.1

40.7

44.4

39.5

46.8

40

48.5

41.5

47.5

43.6

46.5

45.9

45.4

48.4

44.2

51.0

43.0

53.8

41.8

56.8

42

50.2

41.8

49.2

43.9

48.2

46.3

47.0

48.8

45.9

51.4

44.6

54.2

43.3

57.2

44

52.0

42.2

51.0

44.3

49.9

46.7

48.8

49.2

47.5

51.8

46.2

54.6

44.9

57.7

45

53.0

42.3

51.9

44.5

50.8

46.9

49.7

49.4

48.4

52.1

47.1

54.9

45.7

57.9

46

53.8

42.5

52.8

44.7

51.7

47.0

50.6

49.6

49.3

52.2

47.9

55.1

46.5

58.1

48

55.7

42.9

54.6

45.1

53.5

47.4

52.3

50.0

51.0

52.6

49.6

55.5

48.2

58.5

50

57.7

43.3

56.5

45.5

55.3

47.8

54.1

50.4

52.8

53.1

51.4

56.0

49.8

59.0

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

13

RATINGS DATA
YCA 60Hz, R22 Performance Rating
Air on condenser F
Model

60

70

80

95

115

LCWT (F)

75

80

85

90

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

59.3

50.68

58.1

53.32

56.8

56.1

55.5

59.2

54.1

62.4

52.6

65.8

51.1

69.4

42

61.4

51.07 60.15

53.71

58.9

56.6

57.5

59.7

56.1

62.9

54.6

66.3

52.9

69.9

44

63.6

51.56

54.2

61.0

57.1

59.7

60.2

58.1

63.4

56.5

66.8

54.9

70.5

62.4

45

64.7

51.75 63.47

54.39

62.1

57.3

60.7

60.3

59.2

63.7

57.6

67.1

55.9

70.8

46

65.8

51.95 64.55

54.68

63.2

57.5

61.8

60.6

60.3

63.9

58.6

67.4

56.8

71.1

48

68.2

52.44 66.79

55.17

65.4

58.0

64.0

61.1

62.4

64.4

60.6

67.9

58.9

71.6

50

70.5

52.93 69.14

55.66

67.7

58.5

66.1

61.6

64.5

64.9

62.8

68.5

60.9

72.2

40

70.8

60.2

69.3

63.6

67.6

67.3

65.9

71.1

64.2

75.2

62.4

79.6

60.5

84.2

42

73.4

60.6

71.8

64.1

70.2

67.7

68.4

71.6

66.6

75.7

64.7

80.1

62.8

84.7

44

76.1

61.1

74.4

64.5

72.7

68.2

70.9

72.1

69.0

76.2

67.1

80.5

65.1

85.2

45

77.4

61.3

75.8

64.7

74.0

68.4

72.2

72.3

70.3

76.5

68.3

80.8

66.3

85.4

46

78.8

61.5

77.1

65.0

75.3

68.6

73.5

72.5

71.5

76.7

69.6

81.0

67.5

85.7

48

81.6

62.0

79.8

65.4

78.0

69.1

76.1

73.0

74.1

77.2

72.1

81.5

69.9

86.2

50

84.4

62.4

82.6

65.9

80.7

69.6

78.7

73.5

76.7

77.7

74.6

82.1

72.4

86.7

40

78.7

67.3

77.2

70.8

75.5

74.6

73.7

78.6

71.9

82.9

69.9

87.4

67.8

92.2

42

81.6

67.8

79.9

71.3

78.2

75.2

76.4

79.3

74.6

83.5

72.5

88.1

70.3

92.9

44

84.5

68.5

82.9

72.0

81.1

75.9

79.3

79.9

77.2

84.2

75.1

88.7

72.9

93.7

45

86.0

68.8

84.3

72.3

82.5

76.1

80.7

80.2

78.6

84.6

76.5

89.1

74.2

94.1

46

87.4

69.0

85.7

72.6

83.9

76.4

82.1

80.6

80.0

84.8

77.8

89.5

75.5

94.4

48

90.5

69.7

88.7

73.3

86.9

77.1

85.0

81.2

82.9

85.5

80.6

90.2

78.2

95.1

50

93.7

70.3

91.8

73.9

89.9

77.7

87.8

81.9

85.7

86.3

83.4

90.9

80.9

95.9

40

91.0

77.8

89.2

81.8

87.2

86.2

85.1

90.8

83.0

95.8

80.8

101.0

78.4

106.6

42

94.3

78.4

92.3

82.4

90.4

86.9

88.3

91.6

86.2

96.5

83.8

101.8

81.2

107.3

44

97.6

79.1

95.8

83.2

93.7

87.7

91.6

92.3

89.2

97.3

86.8

102.5

84.2

108.2

45

99.4

79.4

97.4

83.5

95.3

88.0

93.2

92.6

90.8

97.7

88.4

103.0

85.7

108.7

46

101.0

79.7

99.1

83.9

97.0

88.3

94.9

93.1

92.5

98.0

89.9

103.4

87.2

109.1

48

104.6

80.5

102.5

84.7

100.4

89.0

98.2

93.8

95.8

98.8

93.1

104.2

90.4

109.9

50

108.2

81.2

106.1

85.4

103.9

89.8

101.5

94.6

99.1

99.7

96.4

105.1

93.5

110.8

40

115.8

99.0

113.5

104.2

111.0 109.7

108.4 115.6

105.7 121.9

102.8 128.6

99.8

135.7

42

120.0

99.8

117.5

104.9

115.1 110.7

112.4 116.6

109.7 122.9

106.7 129.6

103.4

136.6

44

124.2

100.7 121.9

105.9

119.3 111.6

116.6 117.5

113.5 123.8

110.5 130.5

107.2

137.8

45

126.5

101.1 124.0

106.3

121.3 112.0

118.7 117.9

115.6 124.4

112.6 131.1

109.1

138.3

46

128.6

101.5 126.1

106.8

123.4 112.4

120.8 118.5

117.7 124.8

114.5 131.7

111.0

138.9

48

133.2

102.5 130.5

107.8

127.8 113.3

125.0 119.4

121.9 125.7

118.5 132.6

115.1

139.9

50

137.8

103.4 135.1

108.8

132.2 114.3

129.2 120.4

126.1 126.9

122.7 133.8

119.1

141.0

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

14

95

RATINGS DATA
YCA 50Hz, R407C Performance Rating
Air on condenser F
Model

20

25

30

40

50

LCWT (F)

75

80

85

90

95

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

18.0

16.2

17.5

17.1

17.0

18.1

16.5

19.2

15.9

20.3

15.4

21.5

14.8

22.8

42

18.7

16.3

18.2

17.2

17.7

18.2

17.2

19.3

16.6

20.4

16.0

21.6

15.4

22.9

44

19.5

16.4

19.0

17.3

18.4

18.3

17.9

19.4

17.3

20.5

16.7

21.7

16.1

23.0

45

19.9

16.4

19.3

17.4

18.8

18.4

18.2

19.4

17.6

20.6

17.0

21.8

16.4

23.1

46

20.2

16.5

19.7

17.4

19.2

18.4

18.6

19.5

18.0

20.6

17.4

21.9

16.7

23.1

48

21.0

16.6

20.5

17.5

19.9

18.5

19.3

19.6

18.7

20.8

18.0

22.0

17.4

23.3

50

21.8

16.7

21.2

17.7

20.7

18.7

20.1

19.7

19.4

20.9

18.7

22.1

18.0

23.4

40

22.6

20.3

22.0

21.5

21.4

22.7

20.7

24.1

20.0

25.5

19.3

27.0

18.6

28.5

42

23.5

20.4

22.9

21.6

22.2

22.9

21.5

24.2

20.8

25.6

20.1

27.1

19.3

28.7

44

24.5

20.5

23.8

21.7

23.1

23.0

22.4

24.3

21.7

25.7

20.9

27.3

20.1

28.9

45

24.9

20.6

24.3

21.8

23.6

23.1

22.9

24.4

22.1

25.8

21.4

27.3

20.5

28.9

46

25.4

20.7

24.7

21.9

24.0

23.1

23.3

24.5

22.6

25.9

21.8

27.4

20.9

29.0

48

26.4

20.8

25.7

22.0

25.0

23.3

24.2

24.6

23.4

26.1

22.6

27.6

21.8

29.2

50

27.4

21.0

26.6

22.2

25.9

23.4

25.2

24.8

24.3

26.2

23.5

27.7

22.6

29.3

40

30.0

27.0

29.3

28.6

28.4

30.3

27.6

32.1

26.6

33.9

25.7

35.9

24.7

38.0

42

31.3

27.2

30.5

28.7

29.6

30.5

28.7

32.2

27.8

34.1

26.8

36.1

25.7

38.2

44

32.6

27.4

31.7

28.9

30.8

30.6

29.8

32.4

28.9

34.3

27.9

36.3

26.8

38.4

45

33.2

27.5

32.3

29.0

31.4

30.7

30.5

32.5

29.5

34.4

28.4

36.4

27.4

38.5

46

33.8

27.6

32.9

29.1

32.0

30.8

31.0

32.6

30.0

34.5

29.0

36.5

27.9

38.6

48

35.1

27.8

34.2

29.3

33.3

31.0

32.3

32.8

31.2

34.7

30.1

36.7

29.0

38.9

50

36.5

27.9

35.5

29.5

34.6

31.2

33.5

33.0

32.4

34.9

31.3

36.9

30.1

39.1

40

37.4

33.7

36.4

35.6

35.4

37.7

34.3

39.9

33.2

42.2

32.0

44.8

30.8

47.3

42

39.0

33.9

37.9

35.8

36.8

37.9

35.7

40.1

34.6

42.4

33.3

45.0

32.1

47.6

44

40.6

34.1

39.5

36.0

38.4

38.1

37.2

40.3

36.0

42.7

34.7

45.2

33.4

47.9

45

41.3

34.2

40.2

36.1

39.1

38.2

37.9

40.4

36.7

42.8

35.4

45.3

34.1

48.0

46

42.1

34.3

41.0

36.2

39.9

38.3

38.6

40.6

37.4

43.0

36.1

45.5

34.7

48.1

48

43.7

34.6

42.6

36.5

41.4

38.6

40.2

40.8

38.8

43.2

37.5

45.7

36.1

48.4

50

45.4

34.8

44.2

36.8

43.0

38.8

41.7

41.1

40.4

43.5

39.0

46.0

37.5

48.6

40

46.4

41.7

45.2

44.1

43.9

46.7

42.5

49.5

41.1

52.4

39.6

55.5

38.1

58.7

42

48.3

42.0

47.0

44.4

45.6

47.0

44.3

49.7

42.8

52.6

41.3

55.7

39.7

59.0

44

50.3

42.2

48.9

44.6

47.6

47.2

46.0

50.0

44.6

52.9

43.0

56.0

41.4

59.3

45

51.2

42.4

49.9

44.8

48.4

47.4

47.0

50.1

45.5

53.1

43.9

56.2

42.2

59.5

46

52.2

42.5

50.8

44.9

49.4

47.5

47.9

50.3

46.4

53.2

44.8

56.3

43.0

59.6

48

54.2

42.8

52.8

45.2

51.3

47.8

49.8

50.6

48.1

53.6

46.5

56.7

44.8

59.9

50

56.3

43.1

54.8

45.6

53.3

48.1

51.7

50.9

50.0

53.9

48.3

57.0

46.5

60.3

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

15

RATINGS DATA
YCA 50Hz, R407C Performance Rating
Air on condenser F
Model

60

70

80

95

115

LCWT (F)

75

80

85

90

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

58.0

52.2

56.5

55.2

54.9

58.4

53.2

61.9

51.4

65.5

49.6

69.4

47.7

73.4

42

60.4

52.5

58.8

55.5

57.1

58.8

55.4

62.2

53.6

65.8

51.7

69.7

49.7

73.8

44

62.9

52.8

61.2

55.8

59.5

59.1

57.6

62.5

55.8

66.2

53.8

70.1

51.8

74.2

45

64.1

53.0

62.4

56.0

60.6

59.3

58.8

62.7

56.9

66.4

54.9

70.3

52.8

74.4

46

65.3

53.2

63.6

56.2

61.8

59.4

59.9

62.9

58.0

66.6

56.0

70.5

53.8

74.6

48

67.8

53.6

66.0

56.6

64.2

59.8

62.3

63.3

60.2

67.0

58.2

70.9

56.0

75.0

50

70.4

53.9

68.5

57.0

66.7

60.2

64.7

63.7

62.6

67.4

60.4

71.3

58.2

75.4

40

68.2

61.4

66.5

64.9

64.6

68.7

62.6

72.8

60.5

77.0

58.3

81.6

56.1

86.3

42

71.0

61.8

69.2

65.3

67.2

69.2

65.2

73.2

63.0

77.4

60.8

82.0

58.5

86.8

44

74.0

62.1

72.0

65.6

70.0

69.5

67.8

73.5

65.6

77.9

63.3

82.5

60.9

87.3

45

75.4

62.3

73.4

65.9

71.3

69.8

69.2

73.8

66.9

78.1

64.6

82.7

62.1

87.5

46

76.8

62.6

74.8

66.1

72.7

69.9

70.5

74.0

68.2

78.3

65.9

82.9

63.3

87.7

48

79.7

63.0

77.6

66.6

75.5

70.3

73.3

74.5

70.8

78.8

68.5

83.4

65.9

88.2

50

82.8

63.4

80.6

67.0

78.5

70.8

76.1

74.9

73.6

79.3

71.0

83.9

68.5

88.7

40

76.1

68.5

74.2

72.4

72.1

76.6

69.8

81.2

67.5

86.0

65.1

91.1

62.6

96.3

42

79.3

68.9

77.2

72.8

74.9

77.2

72.7

81.6

70.3

86.4

67.9

91.5

65.2

96.9

44

82.6

69.3

80.3

73.2

78.1

77.6

75.6

82.0

73.2

86.9

70.6

92.0

68.0

97.4

45

84.1

69.6

81.9

73.5

79.5

77.8

77.2

82.3

74.7

87.1

72.1

92.3

69.3

97.6

46

85.7

69.8

83.5

73.8

81.1

78.0

78.6

82.6

76.1

87.4

73.5

92.5

70.6

97.9

48

89.0

70.3

86.6

74.3

84.3

78.5

81.8

83.1

79.0

87.9

76.4

93.1

73.5

98.4

50

92.4

70.7

89.9

74.8

87.5

79.0

84.9

83.6

82.2

88.5

79.3

93.6

76.4

99.0

40

90.8

81.7

88.5

86.4

85.9

91.4

83.3

96.9

80.5

102.5

77.6

108.6

74.7

114.9

42

94.6

82.2

92.1

86.9

89.4

92.1

86.7

97.4

83.9

103.0

80.9

109.1

77.8

115.5

44

98.5

82.7

95.8

87.4

93.1

92.5

90.2

97.8

87.4

103.6

84.2

109.7

81.1

116.2

45

100.3

83.0

97.7

87.7

94.9

92.8

92.1

98.2

89.1

103.9

85.9

110.1

82.7

116.5

46

102.2

83.3

99.6

88.0

96.7

93.0

93.8

98.5

90.8

104.3

87.7

110.4

84.2

116.8

48

106.1

83.9

103.3

88.6

100.5

93.6

97.5

99.1

94.2

104.9

91.1

111.0

87.7

117.4

50

110.2

84.4

107.2

89.2

104.4

94.2

101.3

99.7

98.0

105.5

94.6

111.6

91.1

118.0

40

111.9

100.7 109.0

106.5

106.0 112.7

102.7 119.5

99.2

126.4

95.7

133.9

92.1

141.7

42

116.6

101.3 113.5

107.1

110.2 113.5

106.9 120.0

103.4 127.0

99.8

134.5

95.9

142.4

44

121.4

101.9 118.1

107.7

114.8 114.1

111.2 120.6

107.7 127.8

103.8 135.3

100.0

143.2

45

123.7

102.3 120.4

108.1

117.0 114.4

113.5 121.0

109.8 128.2

106.0 135.7

101.9

143.6

46

126.0

102.7 122.7

108.5

119.3 114.6

115.6 121.4

111.9 128.5

108.1 136.1

103.8

144.0

48

130.9

103.4 127.4

109.2

123.9 115.4

120.2 122.2

116.2 129.3

112.3 136.8

108.1

144.8

50

135.9

104.0 132.2

110.0

128.7 116.2

124.9 122.9

120.8 130.1

116.6 137.6

112.3

145.5

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

16

95

RATINGS DATA
YCA 60Hz, R407C Performance Rating
Air on condenser F
Model

20

25

30

40

50

LCWT (F)

75

80

85

90

95

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

17.8

16.0

17.3

16.9

16.8

17.9

16.3

19.0

15.8

20.1

15.2

21.3

14.6

22.5

42

18.5

16.1

18.0

17.0

17.5

18.0

17.0

19.1

16.4

20.2

15.9

21.4

15.3

22.6

44

19.3

16.2

18.8

17.1

18.3

18.1

17.7

19.2

17.1

20.3

16.5

21.5

15.9

22.8

45

19.7

16.3

19.2

17.2

18.6

18.2

18.0

19.2

17.5

20.4

16.8

21.6

16.2

22.8

46

20.0

16.3

19.5

17.2

19.0

18.2

18.4

19.3

17.8

20.4

17.2

21.6

16.5

22.9

48

20.8

16.4

20.3

17.4

19.7

18.4

19.1

19.4

18.5

20.6

17.9

21.8

17.2

23.0

50

21.6

16.5

21.0

17.5

20.5

18.5

19.9

19.5

19.2

20.7

18.5

21.9

17.9

23.1

40

23.0

20.7

22.4

21.9

21.8

23.2

21.1

24.5

20.4

26.0

19.7

27.5

18.9

29.1

42

24.0

20.8

23.3

22.0

22.6

23.3

22.0

24.7

21.3

26.1

20.5

27.6

19.7

29.3

44

24.9

20.9

24.3

22.1

23.6

23.4

22.8

24.8

22.1

26.3

21.3

27.8

20.5

29.4

45

25.4

21.0

24.7

22.2

24.0

23.5

23.3

24.9

22.6

26.3

21.8

27.9

20.9

29.5

46

25.9

21.1

25.2

22.3

24.5

23.6

23.8

24.9

23.0

26.4

22.2

28.0

21.3

29.6

48

26.9

21.3

26.2

22.4

25.5

23.7

24.7

25.1

23.9

26.6

23.1

28.1

22.2

29.7

50

27.9

21.4

27.2

22.6

26.5

23.9

25.7

25.3

24.8

26.7

24.0

28.3

23.1

29.9

40

27.9

25.1

27.2

26.6

26.4

28.1

25.6

29.8

24.8

31.6

23.9

33.4

23.0

35.4

42

29.1

25.3

28.3

26.7

27.5

28.3

26.7

30.0

25.8

31.7

24.9

33.6

23.9

35.6

44

30.3

25.4

29.5

26.9

28.7

28.5

27.7

30.1

26.9

31.9

25.9

33.8

25.0

35.7

45

30.9

25.5

30.1

27.0

29.2

28.6

28.3

30.2

27.4

32.0

26.4

33.9

25.4

35.8

46

31.5

25.6

30.6

27.1

29.8

28.6

28.9

30.3

27.9

32.1

27.0

34.0

25.9

35.9

48

32.7

25.8

31.8

27.3

30.9

28.8

30.0

30.5

29.0

32.3

28.0

34.2

27.0

36.1

50

33.9

26.0

33.0

27.5

32.1

29.0

31.2

30.7

30.2

32.5

29.1

34.3

28.0

36.3

40

36.7

33.0

35.7

34.9

34.7

36.9

33.6

39.1

32.5

41.4

31.4

43.9

30.2

46.4

42

38.2

33.2

37.2

35.1

36.1

37.2

35.0

39.3

33.9

41.6

32.7

44.1

31.4

46.6

44

39.8

33.4

38.7

35.3

37.6

37.4

36.4

39.5

35.3

41.8

34.0

44.3

32.7

46.9

45

40.5

33.5

39.4

35.4

38.3

37.5

37.2

39.6

36.0

42.0

34.7

44.4

33.4

47.0

46

41.3

33.6

40.2

35.5

39.1

37.5

37.9

39.8

36.7

42.1

35.4

44.6

34.0

47.2

48

42.9

33.9

41.7

35.8

40.6

37.8

39.4

40.0

38.1

42.4

36.8

44.8

35.4

47.4

50

44.5

34.1

43.3

36.0

42.2

38.1

40.9

40.3

39.6

42.6

38.2

45.1

36.8

47.7

40

46.3

41.7

45.1

44.1

43.9

46.7

42.5

49.5

41.1

52.3

39.6

55.4

38.1

58.6

42

48.3

41.9

47.0

44.3

45.6

47.0

44.3

49.7

42.8

52.6

41.3

55.7

39.7

59.0

44

50.3

42.2

48.9

44.6

47.5

47.2

46.0

49.9

44.6

52.9

43.0

56.0

41.4

59.3

45

51.2

42.3

49.9

44.7

48.4

47.4

47.0

50.1

45.5

53.1

43.9

56.2

42.2

59.4

46

52.2

42.5

50.8

44.9

49.4

47.5

47.9

50.3

46.3

53.2

44.7

56.3

43.0

59.6

48

54.2

42.8

52.7

45.2

51.3

47.8

49.8

50.6

48.1

53.5

46.5

56.6

44.7

59.9

50

56.2

43.1

54.7

45.5

53.3

48.1

51.7

50.9

50.0

53.9

48.3

57.0

46.5

60.2

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

17

RATINGS DATA
YCA 60Hz, R407C Performance Rating
Air on condenser F
Model

60

70

80

95

115

LCWT (F)

75

80

85

90

100

105

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

Tons

kW

40

56.6

50.9

55.1

53.9

53.6

57.0

51.9

60.4

50.2

63.9

48.4

67.7

46.6

71.6

42

59.0

51.2

57.4

54.2

55.7

57.4

54.1

60.7

52.3

64.2

50.5

68.0

48.5

72.0

44

61.4

51.5

59.7

54.5

58.1

57.7

56.2

61.0

54.5

64.6

52.5

68.4

50.6

72.4

45

62.6

51.7

60.9

54.7

59.1

57.9

57.4

61.2

55.5

64.8

53.6

68.6

51.5

72.6

46

63.7

51.9

62.1

54.9

60.3

58.0

58.5

61.4

56.6

65.0

54.7

68.8

52.5

72.8

48

66.2

52.3

64.4

55.2

62.7

58.4

60.8

61.8

58.8

65.4

56.8

69.2

54.7

73.2

50

68.7

52.6

66.9

55.6

65.1

58.8

63.1

62.2

61.1

65.8

59.0

69.6

56.8

73.6

40

67.3

60.5

65.5

64.0

63.7

67.7

61.7

71.8

59.6

76.0

57.5

80.5

55.3

85.1

42

70.1

60.9

68.2

64.4

66.2

68.2

64.3

72.1

62.2

76.3

60.0

80.8

57.6

85.6

44

73.0

61.2

71.0

64.7

69.0

68.5

66.8

72.5

64.7

76.8

62.4

81.3

60.1

86.1

45

74.3

61.5

72.4

65.0

70.3

68.8

68.2

72.7

66.0

77.0

63.7

81.5

61.2

86.3

46

75.7

61.7

73.8

65.2

71.7

68.9

69.5

73.0

67.3

77.2

65.0

81.8

62.4

86.5

48

78.6

62.2

76.6

65.6

74.5

69.4

72.3

73.4

69.8

77.7

67.5

82.2

65.0

87.0

50

81.7

62.5

79.5

66.1

77.4

69.8

75.0

73.9

72.6

78.2

70.1

82.7

67.5

87.5

40

75.2

67.7

73.2

71.6

71.2

75.7

69.0

80.2

66.6

84.9

64.3

90.0

61.8

95.1

42

78.3

68.1

76.2

71.9

74.0

76.2

71.8

80.6

69.5

85.3

67.0

90.4

64.4

95.7

44

81.5

68.4

79.3

72.3

77.1

76.6

74.7

81.0

72.3

85.8

69.7

90.9

67.1

96.2

45

83.1

68.7

80.9

72.6

78.6

76.9

76.2

81.3

73.8

86.1

71.2

91.1

68.4

96.4

46

84.6

69.0

82.4

72.9

80.1

77.0

77.6

81.5

75.2

86.3

72.6

91.4

69.7

96.7

48

87.9

69.5

85.6

73.4

83.2

77.5

80.8

82.1

78.0

86.9

75.4

91.9

72.6

97.2

50

91.3

69.9

88.8

73.9

86.5

78.0

83.9

82.6

81.1

87.4

78.3

92.4

75.4

97.7

40

87.0

78.3

84.7

82.8

82.3

87.6

79.8

92.8

77.1

98.2

74.4

104.0

71.5

110.0

42

90.5

78.7

88.2

83.2

85.6

88.2

83.1

93.2

80.4

98.6

77.5

104.5

74.5

110.6

44

94.3

79.2

91.7

83.7

89.2

88.6

86.4

93.7

83.7

99.2

80.7

105.1

77.7

111.2

45

96.1

79.5

93.5

84.0

90.8

88.9

88.2

94.0

85.3

99.5

82.3

105.4

79.2

111.5

46

97.9

79.8

95.3

84.3

92.6

89.1

89.8

94.3

87.0

99.8

84.0

105.7

80.7

111.8

48

101.6

80.4

98.9

84.9

96.2

89.6

93.4

94.9

90.2

100.4

87.3

106.3

84.0

112.4

50

105.5

80.8

102.7

85.5

100.0

90.2

97.0

95.5

93.8

101.0

90.5

106.9

87.3

113.0

40

110.6

99.5

107.7

105.2

104.7 111.3

101.4 118.0

98.0

124.9

94.6

132.3

90.9

139.9

42

115.2

100.1 112.1

105.8

108.9 112.1

105.6 118.6

102.2 125.4

98.6

132.9

94.8

140.7

44

119.9

100.7 116.7

106.4

113.4 112.7

109.8 119.2

106.4 126.2

102.6 133.6

98.8

141.5

45

122.2

101.0 119.0

106.8

115.5 113.1

112.1 119.5

108.5 126.6

104.7 134.0

100.7

141.8

46

124.5

101.4 121.3

107.1

117.8 113.2

114.2 119.9

110.6 127.0

106.8 134.4

102.6

142.2

48

129.3

102.2 125.8

107.9

122.4 114.0

118.8 120.7

114.8 127.7

111.0 135.2

106.8

143.0

50

134.2

102.8 130.6

108.7

127.2 114.8

123.4 121.4

119.3 128.5

115.2 135.9

111.0

143.8

Notes :
1. kW = compressor input power
2. LCWT = leaving chilled water temperature
3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

18

95

PHYSICAL DATA
YCA Physical Data (50Hz)
Model

YCA 20

YCA 25

YCA 30

YCA 40

YCA 50

YCA 60

YCA 70

YCA 80

YCA 95

YCA 115

18.5
17.3
1

23.1
21.7
1

30.8
28.9
1

38.4
36
2

47.5
44.6
2

59.5
55.8
2

70
65.6
2

78.1
73.2
2

93.1
87.4
2

114.9
107.7
2

2
2
100-50

2
2
100-50

2
2
100-50

2
4
100-75-

2
4
100-75-

3
6
100-83-67-

3
6
100-83-67-

2
4
100-75-

3
6
100-83-67-

3
6
100-83-67-

50-25

50-25

50-33-17

50-33-17

50-25

50-33-17

50-33-17

GENERAL
Nominal Tons, R22
Nominal Tons, R407C
No. of Refrigerant Circuits
Compressors/Circuit
Compressors/Unit
Capacity Steps of Compressor %
COMPRESSOR
Type

scroll

scroll

scroll

scroll

scroll

scroll

scroll

scroll

scroll

scroll

Compressor Hp/Each
Nominal Total Comp.kW Input, R22
Nominal Total Comp.kW input, R407C

13
20.1
20.5

15
25.2
25.7

20
33.6
34.3

13
41.9
42.7

15
51.9
52.9

13
64.9
66.2

15
77.3
77.9

25
85.2
86.9

20
101.6
103.6

25
125.4
127.8

RLA/Each (380V/3ph/50Hz), R22


RLA/Each (380V/3ph/50Hz), R407C
Locked Rotor Amps/Each

17.1
20.7
167

23.6
24.5
198

29.6
29.5
225

17.1
20.7
167

23.6
24.5
198

17.1
20.7
167

23.6
24.5
198

36
35.7
250

29.6
29.5
225

36
35.7
250

342-462V
380/415V/3ph/50Hz
2900
2900

2900

2900

2900

2900

Voltage Range
Power Supply
Nominal Speed

2900

2900

2900

2900

CONDENSER COIL
Shape
Tube Height

s
42

s
42

v
42

v
42

v
42

w
44

w
44

w
44

w
44

w
45

Number of Rows
Fins/Inch
Tube Dia

3
12
3/8"

4
12
3/8"

3
12
3/8"

4
12
3/8"

4
14
3/8"

3
12
3/8"

4
12
3/8"

4
14
3/8"

3
12
3/8"

4
14
3/8"

Fins Length
COOLER
WPD, ft W.G.

81"

81"

93"

93"

93"

81"

81"

81"

110"

110"

13

13

17

16

15

17

Max. Water Side Pressure, Psig


Max. Ref. Side Pressure, Psig
Water Connection
CONDENSER FANS, STANDARD

150
300
2.5"

150
300
2.5"

150
300
3"

150
300
3"

150
300
4.5"

150
300
4.5"

150
300
4.5"

150
300
6.6"

150
300
5.5"

150
300
6.6"

3 X 600
12700
5/8

3 X 600
12700
5/8

2 X 900
26000
2

2 X 900
28000
3

2 X 900
32600
4

4 X 900
52000
2

4 X 900
49500
2

4 X 900
54400
3

6 X 900
74000
2

6 X 900
75600
3

No. of Fans X Dia, mm


Total cfm
Fan Motor Hp/Each
Fan Motor Poles
SHIPPING WEIGHT
AL Fin Coils, kg

875

904

1386

1468

1568

2414

2640

2740

4025

4500

Cu Fin Coils, kg
OPERATING WEIGHT
AL Fin Coils, kg

975

1029

1586

1693

2393

2687

2999

3099

4534

4600

918

955

1454

1545

1645

2547

2780

2880

4240

4740

Cu Fin Coils, kg
Ref. Charge, ckt1/ckt2, kg
DIMENSION

1018
10

1080
14

1654
20

1770
12/12

2502
16/16

2821
17/17

3139
23/23

3239
24/24

4739
30/30

4830
36/36

Height, mm
Width, mm
Depth, mm

1339
2680
1515

1339
2680
1515

1720
2894
1911

1720
2894
1949

1820
2894
1944

2055
2290
2516

2055
2290
2516

2055
2290
2516

2055
3322
2302

2055
3322
2302

Note: Nominal info based on LWCT of 44F and 95F ambient temp.
All the model come with York Controller, control box without York Controller can be the optional item.

19

PHYSICAL DATA
YCA Physical Data (60Hz)
Model

YCA 20

YCA 25

YCA 30

YCA 40

YCA 50

YCA 60

YCA 70

YCA 80

YCA 95

YCA 115

18.3
17.1
1

23.5
22.1
1

28.6
26.9
1

37.7
35.3
1

47.5
44.6
2

58.1
54.5
2

69.0
64.1
2

77.2
72.3
2

89.2
83.7
2

113.5
106.4
2

2
2
100-50

2
2
100-50

2
2
100-50

2
2
100-50

2
4
100-75-

2
4
100-75-

3
6
100-83-67-

2
4
100-75-

2
4
100-75-

3
6
100-83-67-

50-25

50-25

50-33-17

50-25

50-25

50-33-17

GENERAL
Nominal Tons, R22
Nominal Tons, R407C
No. Of Refrigerant Circuits
Compressors/Circuit
Compressors/Unit
Capacity Steps Of Compressor %
COMPRESSOR
Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Compressor Hp/Each
Nominal Total Comp.kW Input, R22
Nominal Total Comp.kW Input, R407C

10
19.9
20.3

13
25.7
26.3

15
31.2
31.9

20
41.1
41.8

13
51.8
52.9

15
63.4
64.6

13
76.2
76.8

20
84.2
85.8

25
97.3
99.2

20
123.8
126.2

RLA/Each (460V/3ph/60Hz), R22


RLA/Each (460V/3ph/60Hz), R407c
Locked Rotor Amps/Each

16.3
17
125

17.1
20.7
167

23.6
24.5
198

30.6
30.7
225

17.1
20.7
167

23.6
24.5
198

17.1
20.7
167

30.6
30.7
225

36.7
37.2
250

30.6
30.7
225

415 - 506 V
460V/3ph/60Hz
3500
3500

3500

3500

3500

3500

Voltage Range
Power Supply
Nominal Speed

3500

3500

3500

3500

CONDENSER COIL
Shape
Tube Height

S
42

S
42

V
42

V
42

V
42

W
44

W
44

W
44

W
44

W
45

Number of Rows
Fins/Inch
Tube Dia

3
12
3/8"

4
12
3/8"

3
12
3/8"

4
12
3/8"

4
14
3/8"

3
12
3/8"

4
12
3/8"

4
14
3/8"

3
12
3/8"

4
14
3/8"

Fins Length
COOLER
WPD, ft W.G.

81"

81"

93"

93"

93"

81"

81"

81"

110"

110"

13

13

17

16

15

17

Max. Water Side Pressure, Psig


Max. Ref. Side Pressure, Psig
Water Connection
CONDENSER FANS, STD

150
300
2.5"

150
300
2.5"

150
300
3"

150
300
3

150
300
4.5"

150
300
4.5"

150
300
4.5"

150
300
6.6"

150
300
5.5"

150
300
6.6"

3 X 600
12700
5/8

3 X 600
12700
5/8

2 X 900
26000
3

2 X 900
28000
3

2 X 900
32600
5.5

4 X 900
52000
3

4 X 900
49500
3

4 X 900
54400
3

6 X 900
74000
2

6 X 900
75600
3

No. Of Fans X Dia, mm


Total cfm
Fan Motor Hp/Each
Fan Motor Poles
SHIPPING WEIGHT
Al Fin Coils, Kg

855

884

1356

1436

1538

2384

2610

2700

4025

4500

Cu Fin Coils, Kg
OPERATING WEIGHT
Al Fin Coils, Kg

955

1009

1556

1663

2363

2667

2969

3059

4534

4600

918

955

1454

1545

1645

2547

2780

2880

4240

4740

Cu Fin Coils, Kg
Ref. Charge, Ckt1/Ckt2,Kg
DIMENSION

1018
10

1080
14

1654
20

1770
24

2502
16/16

2821
17/17

3139
23/23

3239
24/24

4739
30/30

4830
36/36

Height, mm
Width, mm
Depth, mm

1339
2680
1515

1339
2680
1515

1720
2894
1911

1720
2894
1911

1820
2894
1944

2055
2290
2516

2055
2290
2516

2055
2290
2516

2055
3322
2302

2055
3322
2302

Note: Nominal info based on LWCT of 44F and 95F ambient temp.

20

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 20 50Hz & 60Hz

21

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 25 50Hz & 60Hz

22

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 30 50Hz & 60Hz


YCA 40 60Hz

23

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 40 50Hz

24

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 50 50Hz & 60Hz

25

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 60 50Hz

26

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 60 60Hz

27

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 70 50Hz & 60Hz

28

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize operation
without nuisance high-pressure safety cutouts; however,
the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 80 50Hz & 60Hz

29

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize
operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 95 50Hz

30

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize
operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 95 60Hz

31

Note:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. YORKs unit controls will optimize
operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential
performance degradation. Access to the unit control
center assumes the unit is no higher than on spring
isolators. Recommended minimum clearances: Side to
wall - 2m; rear to wall - 2m; control panel to end wall 1.2m; top - no obstructions allowed; distance between
adjacent units - 3m. No more than one adjacent wall
may be higher than unit.

DIMENSIONS

YCA 115 50Hz & 60Hz

32

SPRING LOCATIONS
X1

X2

CONTROL PANEL

Y1

CG

Y2

C
Z

MODEL: YCA 20 / 50

ISOLATOR MODEL/POINT LOAD


MODEL

YCA 20

YCA 25

YCA 30

YCA 40

YCA 50

AL/HYP
FIN
(918kg)
COPPER
FIN
(1018kg)
AL/HYP
FIN
(955kg)
COPPER
FIN
(1080kg)
AL/HYP
FIN
(1454kg)
COPPER
FIN
(1654kg)
AL/HYP
FIN
(1545kg)
COPPER
FIN
(1770kg)
AL/HYP
FIN
(1645kg)
COPPER
FIN
(2502kg)

CENTRE OF GRAVITY (IN)

X1

X2

Y1

Y2

250kg
TRS-C1-900i

219kg
TRS-C1-750

240kg
TRS-C1-750

209kg
TRS-C1-650

28

32

48

50

20

277kg
TRS-C1-900i

242kg
TRS-C1-900i

266kg
TRS-C1-900i

233kg
TRS-C1-750

28

32

48

50

18

256kg
TRS-C1-900i

232kg
TRS-C1-750

245kg
TRS-C1-900i

222kg
TRS-C1-750

28

32

48

50

20

294kg
TRS-C1-900i

257kg
TRS-C1-900i

282kg
TRS-C1-900i

247kg
TRS-C1-900i

28

32

48

50

18

436kg
TRS-C1-1260i

298kg
TRS-C1-900i

428kg
TRS-C1-1260i

292kg
TRS-C1-900i

30

44

53

54

20

496kg
TRS-C1-1470

338kg
TRS-C1-1040

488kg
TRS-C1-1470

332kg
TRS-C1-1040

30

44

53

54

18

464kg
TRS-C1-1260i

316kg
TRS-C1-900i

454kg
TRS-C1-1260i

311kg
TRS-C1-900i

30

44

53

54

20

531kg
TRS-C1-1470

362kg
TRS-C1-1040

522kg
TRS-C1-1470

355kg
TRS-C1-1040

30

44

53

54

18

494kg
TRS-C1-1470

336kg
TRS-C1-1040

484kg
TRS-C1-1470

331kg
TRS-C1-1040

30

44

53

54

20

751kg
TRS-C1-1880i

512kg
TRS-C1-1470

737kg
TRS-C1-1880i

502kg
TRS-C1-1470

30

44

53

54

20

33

SPRING LOCATIONS (Continued)


X1

X2

A
CONTROL PANEL

Y1

CG

Y2
Y

C
Z

MODEL: YCA 60 / 70
ISOLATOR MODEL/POINT LOAD
MODEL
AL/HYP
FIN
(2547kg)
COPPER
FIN
2821(kg)
AL/HYP
FIN
(2780kg)
COPPER
FIN
(3139kg)

YCA 60

YCA 70

CENTRE OF GRAVITY (IN)

X1

X2

Y1

Y2

723 kg
TRS-C1-1880i

692kg
TRS-C1-1880i

579kg
TRS-C1-1470

553kg
TRS-C1-1470

44

46

40

50

28

801kg
TRS-C1-2080i

766kg
TRS-C1-1880i

641kg
TRS-C1-1720i

613kg
TRS-C1-1720i

44

46

40

50

26

789kg
TRS-C1-1880i

755kg
TRS-C1-1880i

632kg
TRS-C1-1720i

604kg
TRS-C1-1720i

44

46

40

50

29

891kg
TRS-C1-2080i

853kg
TRS-C1-2080i

713kg
TRS-C1-1720i

682kg
TRS-C1-1720i

44

46

40

50

27

X1

X2

CONTROL PANEL

Y1

CG

Y2

C
Z

MODEL: YCA 80
ISOLATOR MODEL/POINT LOAD
MODEL

YCA 80

34

AL/HYP
FIN
(2880kg)
COPPER
FIN
(3239kg)

CENTRE OF GRAVITY (IN)

X1

X2

Y1

Y2

782 kg
TRS-C1-1880i

818kg
TRS-C1-2080i

626kg
TRS-C1-1720i

654kg
TRS-C1-1720i

46

44

40

50

29

880kg
TRS-C1-2080

920kg
TRS-C1-2330

703kg
TRS-C1-1720i

736kg
TRS-C1-1720i

46

44

40

50

27

SPRING LOCATIONS (Continued)


X1

X2

CONTROL PANEL

Y1

CG

Y2
Y

C
Z

MODEL: YCA 95 / 115

ISOLATOR MODEL/POINT LOAD


MODEL

YCA 95

YCA 115

AL/HYP
FIN
4240
COPPER
FIN
4739
AL/HYP
FIN
4740
COPPER
FIN
4830

CENTRE OF GRAVITY (IN)

X1

X2

Y1

Y2

1094
TRS-C1-2510

1026
TRS-C1-2510

1094
TRS-C1-2510

1026
TRS-C1-2510

60

64

45

45

30

1223
TRS-C2-2940

1147
TRS-C2-2940

1222
TRS-C2-2940

1147
TRS-C2-2940

60

64

45

45

28

1223
TRS-C2-2940

1147
TRS-C2-2940

1223
TRS-C2-2940

1147
TRS-C2-2940

60

64

45

45

32

1246
TRS-C2-2940

1169
TRS-C2-2940

1246
TRS-C2-2940

1169
TRS-C2-2940

60

64

45

45

30

35

SPRING LOCATIONS (Continued)

MODEL

36

TRS-C1

L
225

W
90

C
195

TRS-C2

300

90

270

DIMENSION (MM)
M
N
170
90
245

90

T
16
16

LS
5/8
BSW
5/8
BSW

SW
12.5
12.5

ELECTRICAL NOTES
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on
125% of the rated load amps for the largest
motor plus 100% of the rated load amps for all
other loads included in the circuit. Add the following
MCA values to the electrical tables for the system
providing power to the transformer: 460V/3ph/
60Hz, add 1.3 amps; 380-415/3ph/50Hz, add
1.75 amps.
2.

Minimum fuse size is based upon 150% of the


rated load amps for the largest motor plus 100%
of the rated load amps for all other loads included
in the circuit to avoid nuisance trips at start-up
due to lock rotor amps. It is not recommended
in applications where brown outs, frequent starting
and stopping of the unit, and/or operation at
ambient temperatures in excess of 35C
(95F) is anticipated.

3.

Maximum fuse size is based upon 225% of the


rated load amps for the largest motor plus 100%
of the rated load amps for all other loads included
in the circuit.

4.

The minimum recommended disconnect switch


is based on 115% of the rated load amps for all
loads included in the circuit.

5.

Circuit breakers must be UL listed and CSA


certified and maximum size is based on 225%
of the rated load amps for the largest motor plus
100% of the rated load amps for all other loads
included in the circuit.

6.

A ground lug is provided for each compressor


system to accommodate a field grounding
conductor. A control circuit grounding lug is also
supplied.

7.

The supplied disconnect is a Disconnecting


Means and is intended for isolating the unit for the
available power supply to perform maintenance
and troubleshooting. This disconnect is not intended
to be a Load Break Device.

8.

Field Wiring by others which complies to the


National Electrical Code & Local Codes.

ELECTRICAL DATA
STANDARD POWER CONNECTIONS
YCA 20-115 - R22/50Hz
FIELD SUPPLIED WIRING
MODEL

VOLT

Hz

MCA

MIN N/F

YCA
20
25
30
40
50
60
70
80
95
115

380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415

50
50
50
50
50
50
50
50
50
50

46
60
77
86
117
125
166
177
212
260

DISC SW
50
75
100
100
150
150
200
200
250
300

SYSTEM # 1 COMPRESSOR & FAN

D.E FUSE
MIN
50
75
100
100
125
150
175
200
225
300

CKT.BKR.

MAX
75
100
125
125
150
150
200
225
250
300

MAX
75
100
125
125
150
150
200
225
250
300

SYSTEM # 2 COMPRESSOR & FAN


COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
17.1
23.6
17.1
23.6
36.0
29.6
36.0

RLA
17.1
23.6
17.1
23.6
36.0
29.6
36.0

RLA
17.1
23.6
29.6
36.0

LRA
167
198
167
198
250
225
250

LRA
167
198
167
198
250
225
250

LRA
167
198
225
250

FANS
QTY
1
1
2
2
2
3
3

RLA(EA)
5.6
7.4
4.2
4.2
5.6
4.2
5.6

COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
17.1
23.6
29.6
17.1
23.6
17.1
23.6
36.0
29.6
36.0

RLA
17.1
23.6
29.6
17.1
23.6
17.1
23.6
36.0
29.6
36.0

RLA
17.1
23.6
29.6
36.0

LRA
167
198
225
167
198
167
198
250
225
250

LRA
167
198
225
167
198
167
198
250
225
250

LRA
167
198
225
250

FANS
QTY
3
3
2
1
1
2
2
2
3
3

LEGEND

VOLTAGE- 380-415/3/50HZ

CKT.BKR.
D.E.
DISC SW
HZ
MAX
MCA
MIN
MIN NF
RLA
LRA

Circuit Breaker
Dual Element Fuse
Disconnect Switch
Hertz
Maximum
Minimum Circuit Ampacity
Minimum
Minimum Non Fused
Rated Load Amps
Locked Rotor Amps

RLA(EA)
1.83
1.83
4.2
5.6
7.4
4.2
4.2
5.6
4.2
5.6

37

ELECTRICAL DATA
YCA 20-115 - R22/60Hz
FIELD SUPPLIED WIRING
MODEL

VOLT

YCA
20
25
30
40
50
60
70
80
90
115

Hz

460
460
460
460
460
460
460
460
460
460

60
60
60
60
60
60
60
60
60
60

MCA

MIN N/F

43
45
66
82
94
125
132
155
182
228

DISC SW
50
50
75
100
125
150
150
175
200
300

SYSTEM # 1 COMPRESSOR & FAN

D.E FUSE
MIN
50
50
75
100
100
150
150
175
200
250

CKT.BKR.

MAX
60
75
100
125
125
150
150
200
225
300

MAX
60
50
100
125
125
150
150
200
225
300

SYSTEM # 2 COMPRESSOR & FAN


COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
16.3
17.1
23.6
30.6
17.1
23.6
17.1
30.6
36.7
30.6

RLA
16.3
17.1
23.6
30.6
17.1
23.6
17.1
30.6
36.7
30.6

RLA
17.1
30.6

LRA
125
167
198
225
167
198
167
225
250
225

LRA
125
167
198
225
167
198
167
225
250
225

FANS

LRA
167
225

QTY
1
1
2
2
2
3
3

RLA(EA)
5.94
10.1
5.94
5.94
5.94
4.18
5.94

COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
16.3
17.1
23.6
30.6
17.1
23.6
17.1
30.6
36.7
30.6

RLA
16.3
17.1
23.6
30.6
17.1
23.6
17.1
30.6
36.7
30.6

RLA
17.1
30.6

LRA
125
167
198
225
167
198
167
225
250
225

LRA
125
167
198
225
167
198
167
225
250
225

LRA
167
225

FANS
QTY
3
3
2
1
1
2
2
2
3
3

LEGEND

VOLTAGE- 460V/60HZ

CKT.BKR.
D.E.
DISC SW
HZ
MAX
MCA
MIN
MIN NF
RLA
LRA

Circuit Breaker
Dual Element Fuse
Disconnect Switch
Hertz
Maximum
Minimum Circuit Ampacity
Minimum
Minimum Non Fused
Rated Load Amps
Locked Rotor Amps

RLA(EA)
1.83
1.83
5.94
5.94
10.1
5.94
5.94
5.94
4.18
5.94

YCA 20-115 - R407C/50Hz


FIELD SUPPLIED WIRING
MODEL

VOLT

Hz

MCA

MIN N/F

YCA
20
25
30
40
50
60
70
80
95
115

380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415

50
50
50
50
50
50
50
50
50
50

54
62
77
101
121
148
172
176
211
258

DISC SW
60
75
100
125
150
175
200
200
250
300

SYSTEM # 1 COMPRESSOR & FAN

D.E FUSE
MIN
60
75
100
125
150
175
200
200
225
300

CKT.BKR.

MAX
75
100
125
125
150
175
200
225
250
300

MAX
75
100
125
125
150
175
200
225
250
300

SYSTEM # 2 COMPRESSOR & FAN

38

COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
20.7
24.5
20.7
24.5
35.7
29.5
35.7

RLA
20.7
24.5
20.7
24.5
35.7
29.5
35.7

RLA
20.7
24.5
29.5
35.7

LRA
167
198
167
198
250
225
250

LRA
167
198
167
198
250
225
250

LRA
167
198
225
250

FANS
QTY
1
1
2
2
2
3
3

RLA(EA)
5.6
7.4
4.2
4.2
5.6
4.2
5.6

COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
20.7
24.5
29.5
20.7
24.5
20.7
24.5
35.7
29.5
35.7

RLA
20.7
24.5
29.5
20.7
24.5
20.7
24.5
35.7
29.5
35.7

RLA
20.7
24.5
29.5
35.7

LRA
167
198
225
167
198
167
198
250
225
250

LRA
167
198
225
167
198
167
198
250
225
250

LRA
167
198
225
250

FANS
QTY
3
3
2
1
1
2
2
2
3
3

LEGEND

VOLTAGE- 460V/60HZ

CKT.BKR.
D.E.
DISC SW
HZ
MAX
MCA
MIN
MIN NF
RLA
LRA

Circuit Breaker
Dual Element Fuse
Disconnect Switch
Hertz
Maximum
Minimum Circuit Ampacity
Minimum
Minimum Non Fused
Rated Load Amps
Locked Rotor Amps

RLA(EA)
1.83
1.83
4.2
5.6
7.4
4.2
4.2
5.6
4.2
5.6

ELECTRICAL DATA
YCA 20-115 - R407C/60Hz
FIELD SUPPLIED WIRING
MODEL

VOLT

YCA
20
25
30
40
50
60
70
80
95
115

460
460
460
460
460
460
460
460
460
460

Hz
60
60
60
60
60
60
60
60
60
60

MCA

MIN N/F

45
53
68
82
109
129
154
156
184
229

DISC SW
50
60
75
100
125
150
175
175
225
300

SYSTEM # 1 COMPRESSOR & FAN

D.E FUSE
MIN
50
60
75
100
125
150
175
175
200
250

CKT.BKR.

MAX
75
75
100
125
150
175
175
200
225
300

MAX
75
75
100
125
150
175
175
200
225
300

SYSTEM # 2 COMPRESSOR & FAN


COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
30.7
20.7
24.5
20.7
30.7
37.2
30.7

RLA
30.7
20.7
24.5
20.7
30.7
37.2
30.7

RLA
20.7
30.7

LRA
225
167
198
167
225
250
225

LRA
225
167
198
167
225
250
225

LRA
167
225

FANS
QTY
1
1
2
2
2
3
3

RLA(EA)
5.94
10.1
5.94
5.94
5.94
4.18
5.94

COMPR. # 1

COMPR. # 2

COMPR. # 3

RLA
17
20.7
24.5
30.7
20.7
24.5
20.7
30.7
37.2
30.7

RLA
17
20.7
24.5
30.7
20.7
24.5
20.7
30.7
37.2
30.7

RLA
20.7
30.7

LRA
125
167
198
225
167
198
167
225
250
225

LRA
125
167
198
225
167
198
167
225
250
225

LRA
167
225

FANS
QTY
3
3
2
1
1
2
2
2
3
3

LEGEND

VOLTAGE- 460V/60HZ

CKT.BKR.
D.E.
DISC SW
HZ
MAX
MCA
MIN
MIN NF
RLA
LRA

Circuit Breaker
Dual Element Fuse
Disconnect Switch
Hertz
Maximum
Minimum Circuit Ampacity
Minimum
Minimum Non Fused
Rated Load Amps
Locked Rotor Amps

RLA(EA)
1.83
1.83
5.94
5.94
10.1
5.94
5.94
5.94
4.18
5.94

SINGLE POINT WIRING DIAGRAM


Power Panel

Control Panel

2
L

1L3

GRD

1L2

1L1

Micropanel

CTB2

Flow Switch
13

14

CTB1
Field 115-1-50/60 Micropanel
Power Supply if control
transformer not supplied

Field Unit Power Supply

39

APPLICATION DATA
CHILLED LIQUID PIPING
The chilled liquid piping system should be laid out so
that the circulating pump discharges into the cooler.
The inlet and outlet cooler liquid connections are given
in DIMENSIONS.
Hand stop valves are recommended for use in all lines
to facilitate servicing. Drain connections should be
provided at all low points to permit complete drainage
of the cooler and system piping. Additionally, a strainer
(40 mesh) is recommended for use on the INLET line
to the cooler.

Pressure gauge connections are recommended for


installation in the inlet and outlet water lines. Gauges
are not furnished with the unit and are to be furnished
by others.
The chilled liquid lines that are exposed to outdoor
ambients should be wrapped with a supplemental
heater cable and covered with insulation. As an
alternative, ethylene glycol should be added to protect
against freeze up during low ambient periods.
A flow switch is available as an accessory on all units.
The flow switch (or its equivalent) must be installed in
the leaving water piping of the cooler and must not be
used to start and stop the unit.

GUIDE SPECIFICATIONS
PART 1 - GENERAL
1.01

SCOPE

A. The requirements of the General Conditions,


Supplementary Conditions and Drawings apply
to all Work herein.
B. Provide Microprocessor controlled, multiple-scroll
compressor, air-cooled, liquid chillers of the scheduled
capacities as shown and indicated on the Drawings,
including but not limited to:
1. Chiller package
2. Charge of refrigerant and oil
3. Electrical power and control connections
4. Chilled water connections
1.02

QUALITY ASSURANCE

A. Products shall be Designed, Tested, in accordance


with, and installed in compliance with applicable
sections of the following Standards and Codes:
1. ANSI/ASHRAE Standard 15 - Safety Code for
Mechanical Refrigeration.
2. ANSI/NFPA Standard 70-National Electrical
Code (N.E.C.)
3. ARI Standard 550/590 - Positive Displacement
Compressors and Air Cooled Rotary Screw
Water-Chilling Packages.

40

B. Factory Test: Chiller shall be pressure-tested,


evacuated and fully charged with refrigerant and
oil, and shall be factory operational run tested with
water flowing through the vessel.
C. Warranty: Manufacturer shall Warrant all equipment
and material of its manufature against defects in
workmanship and material for a period of one year
from date of initial start-up or eighteen (18) months
from date of shipment, whichever occurs first.
1.03 DELIVERY AND HANDLING
A. Unit shall be delivered to job site fully assembled, and
charged with refrigerant and oil by the manufacturer.
B. Unit shall be stored and handled per Manufacturers
instructions.
PART 2 -PRODUCTS
2.01

CHILLER MATERIALS AND COMPONENTS

A. General: Install and commission, as shown on the


schedules and plans, factory assembled, charged,
and tested air cooled scroll compressor chiller(s)
as specified herein. Chiller shall be designed,
selected, and constructed using a refrigerant with
Flammability rating of 1, as defined by ANSI/
ASHRAE STANDARD-34 Number Designation

GUIDE SPECIFICATIONS (CONTINUED)


and Safety Classification of Refrigerants. Chiller
shall consist of scroll compressors, direct
expansion type evaporator, air-cooled condenser,
refrigerant, lubrication system, interconnecting
wiring, safety and operating controls including
capacity controller, control center, motor starting
components, and special features as specified
herein or required for safe, automatic operation.
B. The design of the units is in accordance with
ISO9001.
2.02 COMPRESSORS
Compressors: Shall be hermetic, scroll-type,
including:
1. Tip seals to provide efficient axial sealing while
preventing scroll tip to base contact.
2. Controlled Orbit Design for radial sealing to
incorporate minimum flank to flank contact for long
service life.
3. Refrigerant flow through the compressor with 100%
suction cooled motor.
4. Large suction side free volume and oil sump to
provide liquid handling capability.
5. Initial Oil charge
6. Oil level sightglass.
7. Vibration isolator mounts for compressors.
8. Brazed-type connections for fully hermetic
refrigerant circuits.
2.03

REFRIGERANT CIRCUIT COMPONENTS

Each refrigerant circuit shall include: liquid line shutoff


valve with charging port, filter-drier, solenoid valve,
sight glass with moisture indicator, thermostatic
expansion valves, and flexible, closed-cell foam
insulated suction line.

2.04

HEAT EXCHANGERS

A. Evaporator
1. Direct expansion type with refrigerant inside
high efficiency copper tubes, chilled liquid
forced over the tubes by galvanized steel
baffles.
2. Constructed and tested in accordance with
applicable pressure vessel code for maximum
300 PSIG (24 bar) refrigerant side design
working pressure and 150 PSIG (10 bar) water
side design working pressure.
3. Shell covered with 3/4" (19mm), flexible, closed
cell insulation, thermal conductivity of
0.28 Btu.in/hr.ft2.F maximum. Water nozzles
with grooves for mechanical couplings and
insulated by Contractor after installation.
4. Provide vent and drain fittings.
B. Air Cooled Condenser:
1. Coils: seamless copper tubes, mechanically
expanded into aluminum fins with full
height collars. Subcooling coil an integral part
of condenser. Testing pressure shall be 450
PSIG (31 bar).
2. Fans: Shall be dynamically and statically
balanced, direct drive, corrosion resistant glass
fiber reinforce composite blades molded into
low noise, providing vertical air discharge from
extended orifices for efficiency and low sound.
Guards of heavy gauge, steel wire epoxy oven
baked painting.
3. Fan Motors: High efficiency, direct drive, 6
pole 3 phase, insulation class F, current
protected, Totally Enclosed Force Cooling
(TEFC), rigid mounted, with double sealed,
permanently lubricated, ball bearings.

41

GUIDE SPECIFICATIONS (CONTINUED)


2.05

CONTROLS

A. General: Automatic start,stop,operating, and


protection sequences across the range of
scheduled conditions and transients.
B. Microprocessor Enclosure: Rain and dust tight
powder painted steel cabinet with hinged, latched,
and gasket sealed door.
C. Microprocessor Control Center:
1. Automatic control of compressor start/stop, anticoincidence and anti-recycle timers, automatic
pump-down shut-down, condenser fans,
evaporator pump, unit alarm contacts, and chiller
operation from 0F to 125F ambient. Automatic
reset to normal chiller operation after power failure.
2. Remote water temperature reset via a Pulse
Width Modulated (PWM) input signal or up to
two steps of demand (load) limiting.
3. Software stored in non-volatile memory, with
programmed set-points retained in lithium
battery backed real time clock (RTC) memory
for minimum 5 years.
4. Forty character liquid crystal display,
descriptions in English, numeric data in English
(or Metric) units. Sealed keypad with sections
for Setpoints, Display/Print, Entry, Unit Options
& clock, and On/Off Switch.
5. Programmable Set-points (within Manufacturer
limits): display language; chilled liquid temperature
setpoint and range, remote reset temperature
range, set daily schedule/holiday for start/stop,
manual override for servicing, low and high
ambient cutouts, number of compressors, low
liquid temperature cutout, low suction pressure
cutout, high discharge pressure cutout, antirecycle timer (compressor start cycle time), and
anti-coincident timer (delay compressor starts).
6. Display Data: Return and leaving liquid
temperatures, low leaving liquid temperature cutout
setting, low ambient temperature cutout setting,
outdoor air temperature, English or metric data,
suction pressure cutout setting, each system suction
pressure discharge pressure (optional), liquid
temperature reset via a YORK ISN DDC or
Building Automation System (by others) via PWM

42

input as standard or at a 4-20 milliamp or 0 10VDC


input or contact closure with optional BAS interface,
anti-coincident system start timer condition,
compressor run status, no cooling load condition,
day, date and time, daily start/stop times, holiday
status, automatic or manual system lead/lag
control, lead system definition, compressor starts/
operating hours (each), status of hot gas valves,
evaporator heater and fan operation, run permissive
status, number of compressors running, liquid
solenoid valve status, load and unload timer
status, water pump status (optional).
7. System Safety: Shall cause individual
compressor systems to perform auto shut
down; manual reset required after the third trip
in 90 minutes. Includes: high discharge
pressure, low suction pressure, high pressure
switch, and motor protector. Compressor motor
protector shall protect against damage due to
high input current or thermal overload of windings.
8. Unit Safety: Shall be automatic reset and cause
compressors to shut down if low ambient, low
leaving chilled liquid temperature, under
voltage, and flow switch operation. Contractor
shall provide flow switch and wiring per chiller
manufacturer requirements.
9. Alarm Contacts: Low ambient, low leaving
chilled liquid temperature, low voltage, low
battery, and (per compressor circuit): high
discharge pressure , and low suction pressure.
D. Manufacturer shall provide any controls not listed
above, necessary for automatic chiller operation.
Mechanical Contractor shall provide field control
wiring necessary to interface sensors to the chiller
control system.
2.06

POWER CONNECTION AND DISTRIBUTION

A. Power Panels:
1. Rain/dust tight, powder painted steel cabinets
with hinged, latched, and gasket sealed outer
doors. Provide main power connection(s), control
power connections, compressor and fan motor start
contactors, current overloads, and factory wiring.
2. Power supply shall enter unit at a single
location, be 3-phase of scheduled voltage, and
connect to unit terminal blocks.

GUIDE SPECIFICATIONS (CONTINUED)


B. Exposed compressor, control and fan motor
power wiring shall be routed through liquid tight conduit.

D. Pressure Transducers and Readout Capability


1. Discharge Pressure Transducers: Permits unit to
sense and display discharge pressure.

2.07 ACCESSORIES AND OPTIONS


Some accessories and options supercede standard
product features. Your YORK representative will be
pleased to provide assistance.
A. Microprocessor controlled, Factory installed
Across-the-Line type compressor motor starters as
standard.
B. Outdoor Ambient Temperature Control.
1. Low Ambient Control: Permits unit operation to 0F
ambient. Standard unit controls to 25F ambient.
C. Power Supply Connections:
1. Single Point Power Supply: Single point Terminal
Block for field connection and interconnecting
wiring to the compressors. Separate external
protection must be supplied, by others, in the
incoming power wiring, which must comply with
the National Electric Code and /or local codes.
2. Single Point Circuit Breaker: Single point Terminal
Block with Circuit Breaker can be supplied to
isolate power voltage for servicing. Incoming
power wiring must comply with the National
Electric Code and/or local codes.

E. Power Factor Correction Capacitors: Provided to


correct unit compressor factor to a 0.90-0.95.
F. Condenser Coil Environmental Protection:
1. Copper Fin: Provide copper fins in lieu of aluminum.
G. Protective Grille for condenser coil (Factory or
Field-Mounted)
H. Evaporator options:
1. Provide 1 1 / 2 cooler insulation in lieu of
standard 3/4.
2. Provide DX Cooler with 300 PSIG water-side
design working pressure in lieu of standard
150 PSIG.
3. Provide Flanges for field installation on cooler
nozzles and field piping:
a. 150 PSIG, welded Flanges.
b. 300 PSIG, welded Flanges.

43

GUIDE SPECIFICATIONS (CONTINUED)


L. Thermal Storage: Leaving chilled liquid setpoint
range for charge cycle from 25F to 20F minimum,
with automatic reset of the leaving brine temperature
up to 40F above the setpoint.

3.01

INSTALLATION

M. Low Temperature Process Brine: Leaving chilled


liquid setpoint range 20F to 50F

A. General: Rig and install in full accordance with


Manufactures requirements, Project drawings,and
Contract documnets.

N. Building Automation System (EMS) Reset


interface: Chiller to accept 4 to 20mA,0 to 10 VDC,
or discrete contact closure input to reset the leaving
chilled liquid temperature.

B. Location: Locate chiller as indicated on drawings,


including cleaning and service maintenance
clearance per Manufacturer instructions. Adjust
and level chiller on support structure.

O. Remote Control Panel (Field Mounted): Auxiliary


panel for remote user interface for functions
normally made at the unit control center.

C. Components: Installing Contractor shall provide


and install all auxiliary devices and accessories
for fully operational chiller.

P. Sound Reduction (Factory Mounted):


1. Low speed, reduced noise fans
2. Compressor Acoustic Sound Blankets

D. Electrical: Coordinate electrical requirements and


connections for all power feeds with Electrical
Contractor.

Q. Vibration Isolation (Field Mounted):


1. Neoprene Pad Isolators.
2. 1 Inch Deflection Spring Isolators: Level
adjustable, spring and cage type isolators for
mounting under the unit base rails.
3. 2 Inch Deflection restrained Isolators: Level
adjustable, restrained mounts in rugged
welded steel housing with vertical and
horizontal limit stops. Housings shall be
designed to withstand a minimum 1.0g
accelerated force in all directions to 2 inches.

E. Controls: Coordinate all control requirements and


connections with Control Contractor.

Jalan Pengapit 15/19, P.O. Box 7196, 40706 Shah Alam, Selangor Darul Ehsan, Malaysia.
Copyright by O.Y.L. - Condair Industries Sdn. Bhd., 2003. All rights reserved.
FORM:- YCA-A-CATL-102002

44

PART 3 - EXECUTION

F. Finish: Installing Contractor shall paint damaged and


abraded factory finish with touch-up paint matching
factory finish.