Sunteți pe pagina 1din 16

Maintenance Manager’s Guide

Power Quality

The Maintenance Manager’s Guide


to circuit protection

Hydraulic-magnetic CB operation; a, b, c - overcurrent; d - fault current


Power Quality
Power Quality
www.leonardo-energy.org

1. Why is circuit protection installed?

The primary objective of Electrical Installation Practice is to provide an


installation that is safe and functional. Since it is inevitable that faults will
sometimes occur in electrical systems and the appliances that they
supply, steps need to be taken to ensure that the safety of people and
property is maintained. For the protection of people, exposure to
dangerous voltages must be prevented by, for example, good insulation of
live parts, proper earthing and earth fault detection. For property
protection it is necessary to prevent over-currents that could cause
overheating and fire and fault current, i.e. the uncontrolled flow of energy
that might lead to ignition or explosion. This document is concerned
primarily with protection against the effects of over-currents and fault
currents, but, of course, the rapid disconnection of faults enhances safety
by reducing the risk of exposure of people to dangerous voltages.

Typically, electrical installations follow a tree architecture, the root of


which is the point of common coupling (PCC) where there is a protective
device provided by the energy supplier. At this point, the supply is defined
in terms of capacity – the maximum power that can be normally drawn –
and the prospective short circuit current – the maximum short circuit
current that could flow through a solid short circuit applied at the PCC.
Next in line are the installations main switch and distribution board where
the supply splits into a number of sub-circuits, which may be final circuits
or feeders to other sub-distribution boards, each with a protective device,
as shown in Figure 1.

Figure 1 – Generic installation topology

2
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

2. How are protective devices selected?

At every point where the current carrying capacity of the conductor


changes (e.g. points a to d), there is a circuit breaker, for which there are
three specific requirements:

• it must be capable of breaking the maximum prospective fault current


at that point

• it must respond to over-current in such a way as to disconnect the


circuit before the excess heat generated in the load circuit cable is
sufficient to damage the cable or materials in contact with it

• it must limit potential damage to the load circuit by limiting the


magnitude, duration or energy of a fault current to a safe level while
disconnecting the circuit from the supply.

In an ideal situation, only the breaker for the faulted circuit will open,
disconnecting the fault and leaving the rest of the installation unaffected.
This is essential for critical loads, but it is often difficult to achieve
completely at an affordable cost, so alternative strategies are also used.

3. Prospective fault current

The prospective fault current is the maximum current that could flow at a
particular point of the installation if a solid short circuit were to be applied
there. The prospective fault current depends on the supply impedance at
that point, including the source impedance and all cables and accessories
in the circuit, so, assuming that there are no transformers, it decreases as
electrical distance from the source increases.

The prospective fault current is very important in the selection of the


protection strategy and of the individual protection devices. Every
protective device must be either capable of breaking this current (at its
position in the installation) without excessive arcing and without being
damaged in the process or must be assisted to do so by an upstream
circuit breaker. This is discussed further under ‘Selectivity or
discrimination’.

3
Power Quality
www.leonardo-energy.org
4. Circuit breakers

There are three main types of circuit breaker used within installations:

• Miniature circuit breakers, MCBs, are used in residential, commercial


and industrial applications for final sub-circuit protection. They are
relatively cheap, compact and available in a wide range of ratings (5
to 100 A), but have limited breaking capacity, typically 6, 10 or 15 kA.

• Moulded case circuit breakers, MCCBs, are designed to high


breaking current capacity with low let-through energy. They are
available in frame sizes from 100 A up to about 3000 A for
installations where the prospective short circuit fault currents could be
as high as 100 kA. The characteristics are not standardised and the
trip levels and trip times are often adjustable to provide the desired
type and level of discrimination.

• Air circuit breakers, ACBs, are more correctly defined as Power


Circuit Breakers, with the fundamental difference being that the short
time withstand current of the ACBs is equal to the interrupting rating.

5. Characteristics

A typical CB characteristic curve is shown in Figure 2.

Figure 2 – Characteristic curve of a circuit breaker

4
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

The so-called ‘inverse time’ part of the characteristic is designed to protect


against over-current. It allows for substantial short overloads without
tripping, because the rate at which the cable conductor temperature rises
due to the extra heat generated is relatively slow due to the high specific
heat of the copper conductors. As the over-current level increases, the
time to respond reduces rapidly to restrict the rise in temperature and
reduce the risk of damage. The characteristic takes advantage of the
inherent short time over-current tolerance of the cable and allows short
duration inrush currents to flow without tripping the breaker.

The instantaneous characteristic is intended to respond very rapidly to


fault current. Fast action is needed because fault currents are high
enough to pose a high risk of damage to load circuits.

The most common to achieving these characteristics is the thermal-


magnetic breaker. The thermal characteristic is provided passing the
load current through an element including a bi-metal strip which deflects
according to its temperature. Once a set deflection has been reached, the
mechanism is tripped, disconnecting the load circuit. Since the trip is
sensitive to temperature, a relatively small over-current will build up heat
and eventually cause tripping over an extended time, while a larger over-
current will heat up and cause tripping in a shorter time. In this area of
operation, the device will not respond to very short duration over-currents.

The magnetic characteristic is intended to protect against fault currents. It


is provided by a small solenoid which exerts a force on the release
mechanism. At a predetermined multiple of the rated current, the force is
sufficient to operate the trip mechanism, and the load circuit is
disconnected.

Breaking fault current rapidly is not easy. Without special measures, an


arc will form as the contacts separate which will be sustained until the next
current zero crossing point. It is possible that a half cycle of fault current
will flow, feeding a relatively large amount of energy into the fault.
Reducing the energy supplied to the fault requires rapid opening of the
contacts and fast quenching of the arc.

5
Power Quality
www.leonardo-energy.org

To ensure rapid opening, the contacts are designed (Figure 3) so that the
magnetic force generated by the current flowing up one contact and down
the other tends to push the contacts apart.

Figure 3 MCB construction

As the contacts part, an arc is formed and current continues to flow. The
arc suppressor, a stack of U-shaped steel plates forming a channel
around the contacts, extinguishes the arc. The magnetic field produced
by the arc forces the ionised gasses into the plates, rapidly cooling and
dividing the gasses and so breaking the arc.

Figure 4 – Arc quenching during MCB operation

6
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

An alternative method to achieving the inverse-time operating


characteristic in circuit breakers, is to use a hydraulic-magnetic principle.

The device consists of a solenoid with a moving core which is normally


displaced by a spring so that it is outside the magnetic circuit. The core is
sealed within a cylinder filled with viscous silicone oil so that its movement
is rate limited or ‘damped’. The moving armature is coupled to the tripping
mechanism such that when the armature is attracted to the solenoid pole
piece, the breaker will trip.

Under normal load current the magnetic force generated by the air cored
coil is insufficient to overcome that exerted by the spring, so no movement
takes place (a).

Upon the occurrence of an over-current, the magnetic force induced in the


coil exceeds that of the opposing spring. The magnetic core moves
towards the pole piece at a rate determined by magnetic force, the
viscosity of the silicone oil and the mechanical clearance between the
magnetic core and the enclosing tube (b). In due course, the magnetic
circuit is completed and the armature is attracted, tripping the circuit
breaker (c). The actual time-current characteristic in such devices is
easily controllable through a combination of the opposing spring force and
the viscosity of the silicone oil that is sealed inside the tube assembly.

At very high currents, such as a fault current, the magnetic field generated
by the air-cored coil is sufficiently strong to attract the moving armature
without the core being in the energised position, so the breaker trips
instantaneously (d).

Figure 5 – Hydraulic-magnetic CB operation; a, b, c - overcurrent; d - fault


current

7
Power Quality
www.leonardo-energy.org

Electronic sensing for over-current and fault circuit protection in circuit


breakers is generally restricted to higher current devices for the present,
mainly due to cost considerations. On the other hand, electronic sensing
has resulted in a step-function improvement in both the reliability and
performance of sensitive earth leakage protection, whilst costs have been
held within affordable limits.

The use of electronic sensing allows much more accurate protection and
enables developments such as annunciators, true RMS protection and
communication between circuit breakers. Once cost restrictions have
been overcome, technologies such as load and fault signature recognition
could become a reality. Intelligent circuit protection is likely to have
applications in future ‘Smart homes’.

6. Practical Characteristics

In practice, as with any other manufactured device, the performance


characteristics of circuit breakers are subject to variation. For MCBs, the
thermal characteristic – which provides protection against over-current –
the following test points are given in Standards EN 60898:

Current I (A) Nominal trip Result


current
In (A)
I = 1.13 x In All Must not trip within 1 hour

I = 1.45 x In < 63A Must trip within 1 hour

I = 1.45 x In > 63 A Must trip within 2 hours

I = 2.55 x In < 32A Must trip between 1 and 60 seconds

I = 2.55 x In > 32A Must trip between 1 and 120 seconds

This relates to practice as follows. The circuit is designed to provide


power to a load or group of loads and so has an expected maximum
current, Ib. The nominal MCB rating, In, must be greater than Ib. The
conductor size for the circuit is selected to have a current carrying
capacity, Iz, that is greater than In. In addition, the current that causes
effective operation of the device within the required time, I2, must not be
greater than 1.45 times the current carrying capacity of any part of the

8
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

circuit. As can be seen from the table, for an MCB meeting EN 60898, a
current of 1.45 x In will trip in less than one or two hours, so this condition
is deemed to be satisfied.

The magnetic trip provides protection against the effects of fault current.
Since it operates within one cycle, MCBs are sensitive to inrush, starting
and surge currents. To avoid a high level of nuisance tripping, MCBs are
available with nominal magnetic trip ratings of 5, 10 and 20 times the trip
rating as shown in Figure 2. Fault current protection must operate within a
prescribed time, which, for 230 V circuits, is 0.4 seconds. This places
another requirement on conductor sizing – a short circuit at the far end of
the circuit must cause a fault current large enough to operate the
magnetic trip. Consequently, there is a maximum limit on the circuit loop
impedance according to the class of the breaker. So, if Class D MCBs are
used (to avoid nuisance tripping on inrush currents, for example), the loop
impedance must be lower than if a Class B device is used. Where the
load is concentrated, the loop impedance required by a Class D device
should be met if the circuit voltage drop has been correctly taken into
account when sizing the cable. However, this may not be the case for
distributed loads so it should always be checked.

Figure 6 shows the overall responses of Class B, C and D MCBs.

Figure 6 – MCB Characteristics, showing minimum and maximum instantaneous


tripping currents

9
Power Quality
www.leonardo-energy.org

Since circuit breakers are thermally operated devices, they are sensitive
to temperature with the nominal trip current decreasing as the ambient
temperature rises. Devices are designed and tested to operate singly in a
vertical orientation at 30° C. At higher temperatures or where the circuit
breakers are mounted in groups (as is typical in a distribution board),
derating factors must be applied. It must be remembered that circuit
breakers also generate heat due to their internal resistance.
Manufacturers publish power dissipation values and derating tables for
ambient temperatures above 30° C and for grouping factors.

As can be seen from Figure 6, the tolerances on circuit breaker


characteristics are rather wide. In overload conditions, for example, the
time to trip at 1.5 x In is a minimum of 40 seconds and a maximum of 400
seconds – at 30° C. In fault conditions, a Class C device may trip at a
minimum current of 5 x In or may not trip until the current exceeds 10 x In.
These tolerances must be taken into account in design by using the worst
case. For example, when considering the required value of loop
impedance, the highest value of tripping current must be used, but when
considering resilience to inrush current, the lowest value is the relevant
one.

7. Selectivity or Discrimination

Ideally, when a fault occurs, only the circuit breaker immediately upstream
of the fault should open, thereby isolating the fault without disconnecting
any other circuit. In Figure 7, the fault should result in only the breaker C3
opening. In order to achieve that, the discrimination between the breakers
at levels A, B and C must be total and breaker C3 must be capable of
breaking the prospective fault current at C3.

Where resilience is important, total discrimination is essential. In other


circumstances it is often necessary to compromise and adopt a less
stringent strategy such as ‘backup protection’.

10
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

Figure 7 – Typical system topology

Discrimination between breakers in a system can be achieved either on


the basis of current difference or time difference. A co-ordination study
must be undertaken to ensure predictable behaviour.

Current discrimination is achieved if the downstream device has a lower


current trip level, under all circumstances, than the upstream device.
Figure 8 shows an example of this. Since there is no overlap, the
downstream breaker will always disconnect the fault and perfect
discrimination is achieved. The difficulty is that the downstream breaker
must be capable of breaking the full prospective short circuit current,
which will often mean that a more expensive device must be used.

11
Power Quality
www.leonardo-energy.org

Figure 8 – Breaker combination giving complete current discrimination

Figure 9 – Breaker combination giving limited current discrimination

8. Cascade or Backup protection

Cascade protection is intended to allow the use of lower cost circuit


breakers in positions where their current breaking capacity might be less
than the prospective fault current. Figure 9 illustrates a case where the
breaker characteristics are allowed to overlap at a high fault current level.

12
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

Here, the upstream breaker will operate first if the fault current exceeds
the current at which the curves cross – about 2700 A in this example –
otherwise the downstream breaker will operate. In practice this means
that fault currents less than 2700 A will be disconnected by the
downstream device while larger fault currents, which might exceed the
breaking capacity of the downstream device, are disconnected by the
upstream device. Many faults will result in a current considerably less
than the full prospective fault current, perhaps because the fault has some
resistance, or because it occurs (and operates the breaker) at less than
full voltage, and will be cleared solely by the downstream breaker. Note
that the characteristics in the overload area do not overlap so, for overload
conditions, the downstream breaker will always be responsible for clearing
overload currents.

The disadvantage of this approach is that a high fault current will cause
the upstream breaker to operate, removing power from healthy circuits
and increasing business disruption.

Breaker manufacturers publish comprehensive performance data for


cascade protection systems. However, it must be remembered that
cascade protection always introduces the probability that power will be
removes from a much greater part of the installation than is strictly
necessary.

Time discrimination is achieved by delaying the action of the upstream


breaker until the downstream breaker has had time to open, as shown in
Figure 10. This scheme requires the use of suitable breakers; the
upstream breaker must be designed for this purpose and the downstream
breaker must be capable of breaking the full prospective fault current.

13
Power Quality
www.leonardo-energy.org

Figure 10 – Delaying the operation of the upstream breaker to achieve complete


discrimination

Energy selectivity is a relatively modern concept. Since circuit breakers


are current and time sensitive, it follows that, for the fault current region,
there is a maximum amount of energy that can flow through the breaker
before it trips. This is referred to as the ‘energy let-through’ and is
expressed in kA2t. Energy discrimination is achieved if the downstream
breaker has a lower energy let-through than the upstream breaker.

Wiring codes recommend that specific testing should be carried out to


verify that discrimination is achieved while manufacturers publish let-
through data on all their devices.

9. What issues are likely to arise in maintenance?

9.1. ‘Early-life’ problems

Often new installations experience numerous random protection issues,


usually in the form of nuisance tripping or lack of discrimination. These
problems can often be traced to incomplete commissioning, where
adjustable breakers have been specified by the designers, but the

14
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org

prescribed adjustments have not been correctly carried out – often


installed breakers are found in the ‘as shipped’ state. It is important that
these problems are rectified by reference to the design documentation
rather than trial and error – the erroneous operation may be delayed, but it
may also be catastrophic.

9.2. Post commissioning issues and modifications

The most common problems are, as for new installations, nuisance


tripping and a perceived lack of discrimination, but the cause is different –
the use of the installation has changed.

Nuisance tripping usually becomes apparent following a change in the


nature, number or use of the loads connected to the network. In one
case, a tutorial room in an academic institution had been converted into a
small computer suite housing 42 personal computers. For software
management purposes, these computers were audited and updated
overnight, using ‘Wake on Lan’ or ‘magic packet’ instructions to bring them
out of standby and into full power mode. These instructions were sent in
rapid succession, resulting in a virtually simultaneous power-up of all the
computers. The result was a large inrush current, retrospectively
measured at >500 A in the worst case, resulting in the MCBs operating.
The ‘corrective action’ taken was to replace the Class B MCBs – which trip
at 5 times their nominal rating – with Class D devices that would trip at 20
times their nominal rating. This would have been a reasonable response,
if the loop impedance had been checked to ensure that a true fault current
would have been high enough to trip a Class D breaker. No such check
had been made, so the nuisance tripping issue was resolved, but the
circuit may not be protected in the event of a real fault! The moral is that
any maintenance action that could alter the behaviour of the protection
system should be carefully checked.

Where there is a perceived lack of discrimination it is usually brought


about by a change of function in that area of the installation, such as the
installation of more mission critical equipment, for example, or simply a
change in the perception of the criticality of the existing equipment.
Complete discrimination schemes can be more costly and may have been
implemented only in areas where they were considered essential for

15
Power Quality
www.leonardo-energy.org

critical operations. When changes of use occur, it is possible that the


protection scheme will need to be readjusted or upgraded.

10. Conclusions

The design of the protection scheme requires a systems approach. It


should not be assumed that additional circuits can be added to a
distribution board without some consideration of the possible effects on
upstream protection devices and their settings.

Any change of wiring that could affect the loop impedance – such as
conductor upsizing or re-routing via a longer or shorter path – must be
considered in conjunction with the effect it could have on prospective fault
currents and on clearing times for up and downstream protection devices.

Even the apparently innocuous change of substituting, say, a Class D


MCB in place of a Class B MCB requires reconsideration of loop
impedance.

16

S-ar putea să vă placă și