Documente Academic
Documente Profesional
Documente Cultură
Power Quality
2
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
In an ideal situation, only the breaker for the faulted circuit will open,
disconnecting the fault and leaving the rest of the installation unaffected.
This is essential for critical loads, but it is often difficult to achieve
completely at an affordable cost, so alternative strategies are also used.
The prospective fault current is the maximum current that could flow at a
particular point of the installation if a solid short circuit were to be applied
there. The prospective fault current depends on the supply impedance at
that point, including the source impedance and all cables and accessories
in the circuit, so, assuming that there are no transformers, it decreases as
electrical distance from the source increases.
3
Power Quality
www.leonardo-energy.org
4. Circuit breakers
There are three main types of circuit breaker used within installations:
5. Characteristics
4
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
5
Power Quality
www.leonardo-energy.org
To ensure rapid opening, the contacts are designed (Figure 3) so that the
magnetic force generated by the current flowing up one contact and down
the other tends to push the contacts apart.
As the contacts part, an arc is formed and current continues to flow. The
arc suppressor, a stack of U-shaped steel plates forming a channel
around the contacts, extinguishes the arc. The magnetic field produced
by the arc forces the ionised gasses into the plates, rapidly cooling and
dividing the gasses and so breaking the arc.
6
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
Under normal load current the magnetic force generated by the air cored
coil is insufficient to overcome that exerted by the spring, so no movement
takes place (a).
At very high currents, such as a fault current, the magnetic field generated
by the air-cored coil is sufficiently strong to attract the moving armature
without the core being in the energised position, so the breaker trips
instantaneously (d).
7
Power Quality
www.leonardo-energy.org
The use of electronic sensing allows much more accurate protection and
enables developments such as annunciators, true RMS protection and
communication between circuit breakers. Once cost restrictions have
been overcome, technologies such as load and fault signature recognition
could become a reality. Intelligent circuit protection is likely to have
applications in future ‘Smart homes’.
6. Practical Characteristics
8
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
circuit. As can be seen from the table, for an MCB meeting EN 60898, a
current of 1.45 x In will trip in less than one or two hours, so this condition
is deemed to be satisfied.
The magnetic trip provides protection against the effects of fault current.
Since it operates within one cycle, MCBs are sensitive to inrush, starting
and surge currents. To avoid a high level of nuisance tripping, MCBs are
available with nominal magnetic trip ratings of 5, 10 and 20 times the trip
rating as shown in Figure 2. Fault current protection must operate within a
prescribed time, which, for 230 V circuits, is 0.4 seconds. This places
another requirement on conductor sizing – a short circuit at the far end of
the circuit must cause a fault current large enough to operate the
magnetic trip. Consequently, there is a maximum limit on the circuit loop
impedance according to the class of the breaker. So, if Class D MCBs are
used (to avoid nuisance tripping on inrush currents, for example), the loop
impedance must be lower than if a Class B device is used. Where the
load is concentrated, the loop impedance required by a Class D device
should be met if the circuit voltage drop has been correctly taken into
account when sizing the cable. However, this may not be the case for
distributed loads so it should always be checked.
9
Power Quality
www.leonardo-energy.org
Since circuit breakers are thermally operated devices, they are sensitive
to temperature with the nominal trip current decreasing as the ambient
temperature rises. Devices are designed and tested to operate singly in a
vertical orientation at 30° C. At higher temperatures or where the circuit
breakers are mounted in groups (as is typical in a distribution board),
derating factors must be applied. It must be remembered that circuit
breakers also generate heat due to their internal resistance.
Manufacturers publish power dissipation values and derating tables for
ambient temperatures above 30° C and for grouping factors.
7. Selectivity or Discrimination
Ideally, when a fault occurs, only the circuit breaker immediately upstream
of the fault should open, thereby isolating the fault without disconnecting
any other circuit. In Figure 7, the fault should result in only the breaker C3
opening. In order to achieve that, the discrimination between the breakers
at levels A, B and C must be total and breaker C3 must be capable of
breaking the prospective fault current at C3.
10
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
11
Power Quality
www.leonardo-energy.org
12
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
Here, the upstream breaker will operate first if the fault current exceeds
the current at which the curves cross – about 2700 A in this example –
otherwise the downstream breaker will operate. In practice this means
that fault currents less than 2700 A will be disconnected by the
downstream device while larger fault currents, which might exceed the
breaking capacity of the downstream device, are disconnected by the
upstream device. Many faults will result in a current considerably less
than the full prospective fault current, perhaps because the fault has some
resistance, or because it occurs (and operates the breaker) at less than
full voltage, and will be cleared solely by the downstream breaker. Note
that the characteristics in the overload area do not overlap so, for overload
conditions, the downstream breaker will always be responsible for clearing
overload currents.
The disadvantage of this approach is that a high fault current will cause
the upstream breaker to operate, removing power from healthy circuits
and increasing business disruption.
13
Power Quality
www.leonardo-energy.org
14
The Maintenance Managers’ Guide to circuit protection
www.leonardo-energy.org
15
Power Quality
www.leonardo-energy.org
10. Conclusions
Any change of wiring that could affect the loop impedance – such as
conductor upsizing or re-routing via a longer or shorter path – must be
considered in conjunction with the effect it could have on prospective fault
currents and on clearing times for up and downstream protection devices.
16