Documente Academic
Documente Profesional
Documente Cultură
AQ Series
Air and Water Cooled
Operation and Installation Manual
Thermal Care, Inc.
7720 N. Lehigh Ave.
Niles, IL 60714-3491
Phone
Fax
E-mail
Website
(847) 966-2260
(847) 966-9358
info@thermalcare.com
www.thermalcare.com
Customer Service
Phone
(847) 966-2636
Fax
(847) 966-2906
Parts
Phone
Fax
(847) 966-8560
(847) 966-6065
TABLE OF CONTENTS
Page No.
Foreword
3
Pre-Installation
5
Receiving Inspection
5
Rigging, Handling & Locating Equipment
5
Installation
7
Electrical Power
7
Air Cooled Condenser (Air Cooled Chillers Only)
7
8
Condenser Water Lines (Water Cooled Chillers Only)
Required Condenser Water Flow Table
9
Chilled Water Lines
9
Suggested Chilled Water Flow Table
10
Suggested Pipe Sizing Table
11
Overhead Piping Diagram
11
Chiller Start-Up
12
Recommended Glycol Mixtures Table
13
Control Panel Operation
15
Control Panel Diagram
15
Microprocessor Control Fault Logic Table
15
Control Buttons
16
Diagnostic LEDs
18
Diagnostic Error Codes
21
Control Options
22
Chiller Operation
26
Typical Piping Schematic Diagram
26
Coolant Circuit
27
Refrigerant Circuit
28
Chiller Construction
30
Refrigeration Components
30
Wet-Side Components
34
Operating and Safety Controls
36
Standard Options
38
Preventive Maintenance
40
Preventive Maintenance Checklist
42
Troubleshooting
43
Pump Curves
47
Diagrams
48
AQ0A0H Wiring Diagram
48
AQ0A01 Wiring Diagram
49
AQ0A02 - AQ0A10 Wiring Diagram
50
AQ0W02 - AQ0W05 Wiring Diagram
51
AQ0W08 - AQ0W10 Wiring Diagram
52
AQ1W05 - AQ1W15 Wiring Diagram
53
AQ1W20 - AQ1W30 Wiring Diagram
54
AQ1W35 - AQ1W40 Wiring Diagram
55
Air Cooled Dimensions
56
Page 2 Cooled Dimensions
Water
57
Warranty
58
FOREWORD
The intent of this manual is to serve as a guide for placing your portable chiller in service, and operating and maintaining it properly.
This manual will be supplemented as required to accommodate any
special items which may have been provided for a specific application.
The written information contained in this manual, as well as
various drawings, are intended to be general in nature. The
schematics included in this manual are typical only. Actual schematics are included in the electrical enclosure of the chiller and should be
referred to for troubleshooting and servicing of the unit. Additional
copies of wiring diagrams are available upon request. We strive to
maintain an accurate record of all equipment during the course of its
useful life. While every effort is made to standardize the design
features of these chillers, the various options may make it necessary
to rearrange some of the components; therefore, some of the general
drawings in this manual may differ from your specific unit.
Specific references to current applicable codes, ordinances, and other
local laws pertaining to the use and operation of this equipment are
avoided due to their ever changing nature. There is no substitute for
common sense and good operating practices when placing any mechanical equipment into operation. We encourage all personnel to
familiarize themselves with this manuals contents. Failure to do so
may unnecessarily prolong equipment down time.
Our chilling equipment uses chemical refrigerants for heat transfer
purposes. This chemical is sealed and tested in a pressurized system
containing ASME coded vessels; however, refrigerant gas can be
released if there is a system failure. Refrigerant gas can cause toxic
fumes if it is exposed to fire. These units must be placed in a well
ventilated area, especially if open flames are present. Failure to
follow these instructions could result in a hazardous condition.
The standard refrigerant used in these units is a hydrochloro-fluorocarbon (HCFC) trade named R-22. The EPA has enacted laws regarding the handling of refrigerants and eventual phaseout of HCFC
refrigerants. HCFC refrigerant production will continue until January 1, 2010 for new equipment and until January 1, 2020 for service
purposes. Customers are advised to immediately implement a refrigerant management program including a survey of all equipment to
document the type and quantity of refrigerant in each machine. All
refrigeration service technicians must be certified by an EPA approved organization.
Page 3
Page 4
PRE-INSTALLATION
Receiving Inspection
Each unit is skid mounted and either boxed or crated prior to shipment. Before accepting delivery, check the overall equipment condition for any visible damage. If damage is evident, it should be properly documented on the delivery receipt. Shipping damage is the
responsibility of the carrier. In order to expedite payment for damages, it is important that proper procedures be followed and records
kept. Photographs of damaged equipment are excellent for your
records.
Once the unit is removed from the box or crate, it should be inspected
for hidden damage. Refrigerant lines can be susceptible to damage in
transit. Check for broken lines, oil leaks, damaged controls, or any
other major component torn loose from its mounting point.
Note: Any sign of damage should be recorded and a claim filed
immediately with the shipping company. We will provide assistance in preparation and filing of your claims, including arranging for an estimate and quotation on repairs; however,
filing the claim is the responsibility of the receiving party.
Page 5
! Ethylene Glycol
! Propylene Glycol
Page 6
INSTALLATION
Electrical Power
Note: Main power to the chiller should remain connected during off hours to energize the compressor's crankcase heater.
Disconnect main power only when servicing the chiller. The
crankcase heater should remain on at all times to ensure
liquid refrigerant does not accumulate in the compressor
crankcase.
The control panel and safeties are interwired such that connecting the
appropriate power source to the main terminal block energizes the
entire electric circuitry of a chiller. A control transformer has been
factory wired to step down the incoming power to the 115 volt control
power.
Note: Electric power at the main disconnect should be shut off
before opening access panels for repair or maintenance.
Page 7
The standard rated cooling capacity of our air cooled chiller is based
upon 95F (35C) ambient air temperature. If the air temperature
entering the condenser is above 95F (35C), the capacity will be
reduced approximately 1% per 1F (0.5C). Entering air temperatures
above 110F (43C) may result in high refrigerant pressure problems
which would shut the unit down. For this reason, it is very important
that the chiller be located where the warm discharge air will not be
recirculated back into the condenser inlet.
These chillers are designed for indoor usage with normal indoor
ambient air temperature entering the condenser. Air temperatures
below 60F (15C) entering the condenser may result in low refrigeration pressure "cold start-up" problems.
tain the refrigerant pressure at the factory set level. The condenser
water regulating valve is standard on models AQ0W02 through
AQ1W15 and optional on all other models. The following chart shows
condenser water requirements and pipe sizing for the different size
chillers. Please note that a condenser water supply temperature
below 75F (24C) will not necessarily result in reduced flow
requirements.
Model #
AQ0W02
AQ0W03
AQ0W05
AQ0W08
AQ0W10
AQ1W15
AQ1W20
AQ1W25
AQ1W30
AQ1W35
AQ1W40
Condenser
Water
Connection
(FNPT)
1"
1"
1"
1"
1 1/2"
2"
2"
2 1/2"
2 1/2"
2 1/2"
3"
and water cooled models AQ0W02 through AQ0W05, the bypass line is
fixed and requires no adjustment. On air cooled models AQ0A06
through AQ0A10 and water cooled models AQ0W08 through AQ1W40,
there is a cock valve on the bypass line which may require adjustment
if the chiller is not operated using the nominal flow rate. This valve is
located where the bypass line enters the reservoir.
Model #
AQ0A0H
AQ0A01
AQ0A02
AQ0A03
AQ0A06
AQ0A08
AQ0A10
AQ0W02
AQ0W03
AQ0W05
AQ0W08
AQ0W10
AQ1W15
AQ1W20
AQ1W25
AQ1W30
AQ1W35
AQ1W40
Nominal
Flow
Rate
(GPM)*
1
2
4
7
12
16
20
5
8
12
19
25
40
46
54
63
80
96
Maximum
Flow
Rate
(GPM)*
2
4
8
14
24
32
40
10
16
24
38
50
80
92
108
126
160
160
Page 10
Maximum
Flow Rate
(GPM)*
2
5
10
20
30
50
90
160
*Based on standard
weight schedule 40 black
iron or PVC schedule 80
pipes.
Overhead Piping
SPA-0121
Page 11
CHILLER START-UP
All chillers are fully tested prior to shipping. Readings of voltage,
amperage, compressor suction and discharge pressures, water inlet
and outlet temperatures, water flow rates, etc., are recorded to make
sure that all system components are performing up to their specifications. Every unit is factory set to deliver chilled water in accordance
with the standard operating specifications for that particular chiller.
Due to variables involved with different applications and different
installations, minor adjustments may be required during the initial
start-up to ensure proper operation.
The following start-up procedure should be followed in sequence. If
trouble is encountered in putting a chiller in operation, the fault can
usually be traced to one of the control or safety devices. This outline
can be used as a checklist for the initial start-up and for subsequent
start-ups if the chiller is taken out of service for a prolonged period of
time.
1. Assure the main power source is connected properly and that it
matches the voltage shown on the nameplate of the unit. Once
proper power connection and grounding have been confirmed, turn
the main power on.
Page 12
5. Make sure that the Freezestat is set appropriately for the operating conditions of the chiller. The Freezestat is located inside the
main electrical control panel. It should be set at 10F (5C) below
the minimum chilled water temperature setting that the chiller
will be operated at. Be sure that there is sufficient glycol in the
system to handle at least 10F (5C) below the freezestat setting.
All chillers are shipped from the factory with the Freezestat set at
40F (4C). This is done to protect against a possible freeze-up if
no glycol has been added to the system. Once the proper glycol
solution has been added, the freezestat can be adjusted to the
appropriate setting.
Note: Our warranty does not cover the evaporator from
freezeups. It is vital that the freezestat is set properly.
9.
Check the rotation of the pump. If the pump is running backwards, switch two of the main power leads, after shutting off the
disconnect switch. The pressure gauge on the back of the unit
should be reading at least 20 PSI.
10. The coolant flow out to process can be adjusted by using the cock
valve on the supply line just inside the chiller cabinet. If the
process does not create much of a pressure drop, the cock valve
may have to be throttled in order to maintain the flow through the
chiller at an acceptable level. If the flow is more than double the
nominal flow rating, the cooling capacity of the chiller may be
reduced.
11. Temperature adjustment is the next step in putting the chiller in
operation. Adjust the controller set point to the desired temperature. The chiller should now be controlling to that temperature.
Please note that if there is no load on the chiller, the compressor
will cycle on and off causing swings in temperature of up to 10F
(5C).
12. Once proper flow and temperature are achieved, press the Stop
button and allow the water level in the tank to stabilize. Fill the
tank, replace the screw cap, and replace the top panel on the
cabinet.
The unit is now ready to be placed into service.
Page 14
Alarm
Manual
Remote
Alarm
Compressor Pump
Reset
Reset
Alarm
Indication Shutdown Shut Off Required Required Activated
LED
Yes
Yes
No
No
Yes
LED
Yes
Yes
Yes
No
Yes
LED
Yes
No
Yes
No
Yes
LED
Yes
No
Yes
Yes
Yes
LED
Yes
Yes
Yes
Yes
Yes
LED
No
No
No
No
Yes
LED
Yes
No
Yes
No
Yes
LED
No
No
No
No
No
LED
No
No
No
No
No
LED
Yes
Yes
Yes
No
Yes
Pr OFF
Yes
Yes
Yes
No
Yes
Err 126
Yes
Yes
Yes
Yes
Yes
Err 127
Yes
Yes
Yes
No
Yes
Err 128
Yes
Yes
Yes
No
Yes
Page 15
Control Buttons
This unit was either shipped to display temperatures in F or C. Do
the following to change the display.
1. With the power connected and the control power off, hold the Stop
button. While holding the Stop button press the Power button.
When the controller illuminates, release both buttons.
2. The To Process display will read "Unt". The Set Point display will
show either "F" or "C" depending on the current display units
selected. If the current selected units are "F" press the down key.
If the current selected units are "C" press the up key.
3. The Set Point display should now indicate the desired display
units. Press the Start button to store the new selection into the
controller memory.
4. Press the Power button once to exit this function then press the
Power button again to restore controller power.
! Power
Depressing the Power button will switch the control power on or off.
Control power must be initiated before the chiller can be started by
the Start button or by remote on/off contacts.
! Start
Depressing the Start button will start the pump and enable the compressor. The compressor will start only if the microprocessor is calling
for cooling because the actual To Process temperature is higher than
the Set Point temperature.
Note: Once the compressor has cycled off, it will not restart for
two minutes because of an internal anti-cycle time delay.
! Stop
Depressing the Stop button will shut off the compressor and pump,
and clear all fault signals.
Page 16
! Alarm Reset
Depressing the Alarm Reset button will reset any fault indicator that
has been activated on the control board. This includes any LED
indicators or alarm codes. The Freezestat, Low Oil Pressure, and
Pump Overload require a mechanical safety to be manually reset
before the control board can be reset.
Note: If the condition still exists that originally caused the
alarm indication, the alarm may be reactivated as soon as it is
reset.
! Alarm Silence
The Alarm Silence button is not functional unless the Alarm Horn
option or the Remote Alarm contacts option has been purchased. If
the Alarm Horn option has been purchased, depressing the Alarm
Silence button will disable the horn. The horn will not reactivate until
the alarm has been reset and a subsequent alarm has been triggered.
If the Remote Alarm contacts option has been purchased, depressing
the Alarm Silence button will reopen the contacts which were closed
when the alarm occurred. The contacts will not close again until the
alarm has been reset and a subsequent alarm has been triggered.
Page 17
Diagnostic LEDs
! No Flow
The No Flow LED will be illuminated if the flow through the chiller is
below the preset acceptable level. When the Start button is depressed,
this safety is defeated for a period of 20 seconds in order for the pump
to establish flow. The No Flow LED may remain illuminated during
this 20 second period. This safety will shut off the pump and the
compressor. If the chiller has been shut down by the No Flow safety,
the Start button must be depressed in order to restart the pump and
reset the 20 second time delay.
! Freezestat
If the coolant temperature being delivered to the process drops below
the setting on the Freezestat, the compressor will shut off, the pump
will remain running, and the Freezestat LED will be illuminated. The
Freezestat should be set 10F (5C) above the freezing point of the
glycol solution and 10F (5C) below the minimum operating temperature. The Freezestat is factory set at 40F (4C). In order to reset the
Freezestat fault, press the Alarm Reset button after resetting the
mechanical thermostat (labeled Freezestat) inside the electrical
enclosure.
Page 18
! Pump On
The Pump On LED will be illuminated whenever the pump is running. If the pump is shut off due to a safety, the Pump On LED will
turn off. The Start button must be pressed in order to restart the
pump.
Page 19
! Compressor On
The Compressor On LED will be illuminated whenever the compressor is running. The Compressor On LED will cycle on and off with the
compressor. The compressor will not come on unless the pump is
already running and the To Process temperature is above the Set
Point temperature.
! Partial Load
The Partial Load LED will be illuminated whenever the microprocessor energizes the hot gas bypass solenoid valve. This valve is cycled in
order for the chiller to maintain a constant To Process temperature
even when there is only a partial load. The longer that this LED stays
on, the more unused excess capacity is available from the chiller. If
the Partial Load LED stays off, the chiller is fully loaded by the heat
from the process. If the Partial Load LED stays on, the chiller has a
very small load on it from the process. If this low load condition
persists, the To Process temperature may begin to drop below the Set
Point temperature, and when it reaches 7F (or 4C) below the Set
Point temperature, the compressor will cycle off. The compressor will
come back on when the To Process temperature rises back up to the
Set Point temperature and the anti-cycle two minute time delay relay
has timed out.
! Water Make-Up
The Water Make-Up LED is only functional if the Water Make-Up
option is purchased with the chiller. When the water level in the
reservoir drops below the lower limit of the float switch, the water
make-up solenoid valve is opened and the Water Make-Up LED is
illuminated. When the water level rises to the upper limit of the float
switch, the water make-up solenoid is closed and the Water Make-Up
LED turns off. The microprocessor will also close the water make-up
solenoid valve if it has been open for a period of ten minutes. This is
done to help prevent further problems if a water leak has developed in
the system. If this occurs, the Water Make-Up LED will turn off, but
the Low Water Level LED will remain illuminated.
Page 20
! Probe Fault
The Probe Fault LED will illuminate if the signal from the thermocouple is out of tolerance. This fault will also shut off the compressor
and the pump. It can be reset by pressing the Alarm Reset button.
! Pr Off
If the chiller is running and main power is discontinued or drops more
than 10% below the normal operating voltage, the unit will shut down
and the Pr OFF fault will be indicated on the digital displays. This
fault condition can be cleared by pressing the Stop button.
Page 21
! Err 126
The Err 126 fault code will be indicated on the digital displays if the
pump has gone off due to the pump overload. In order to reset this
fault, press the Alarm Reset button after resetting the pump overload
inside the electrical enclosure.
! Err 127
Some units equipped with a semi-hermetic compressor include this
function. The Err 127 fault code will be indicated on the digital displays if the compressor has gone off due to the internal compressor
thermal overload. This fault will also shut off the pump. The thermal
overload will automatically reset when the compressor motor winding
temperature drops back into the normal operating range. Once this
occurs, the fault can be reset by pressing the Alarm Reset button.
! Err 128
The Err 128 fault code will be indicated on the digital displays if the
chiller has been shut off due to the high temperature safety. This
safety will shut off both the pump and compressor. This safety is
triggered if the To Process temperature rises more than 10F (or 5C)
above the maximum operating temperature for that particular chiller.
The maximum operating temperature for each chiller is noted on the
nameplate. The To Process temperature must be over the limit for
three minutes before this safety will be triggered, and the fault is
defeated for a period of 30 minutes from the time the Start button is
pressed or the Set Point temperature is changed. This fault can be
reset by pressing the Alarm Reset button.
Control Options
! Return Water Temperature Display
If the Return Water temperature display option is purchased, the To
Process digital display can be used to view To Process temperature or
Return Water temperature. To view the Return Water temperature,
hold down the ! and # buttons simultaneously. Once the buttons are
released, the display will return to To Process temperature.
Page 22
! Alarm Horn
If the Alarm Horn option is purchased, the control panel will be fitted
with an alarm horn which will be activated by certain faults. Reference the Microprocessor Control Fault Logic table to determine which
faults will trigger the horn. The horn can be silenced by clearing the
Page 23
fault or by pressing the Alarm Silence button. If this option is selected in conjunction with the remote control panel, the horn will be
mounted on the chiller and not the panel.
! SPI Communications
If the SPI Communications option is included, an RS-485 communication port will be located below the control panel on the front of the
chiller. The serial communications will be multi-drop, half duplex, SPI
3.01 compatible. This option allows the chiller to communicate with
another piece of equipment that also has SPI protocol capabilities.
The following SPI communications are supported by the
microprocessor.
$
$
$
$
$
Page 24
In order to activate the SPI protocol, DIP switch #8 must be set to the
On position. To deactivate the SPI communication, set DIP switch
#8 to the Off position.
If more than one piece of equipment is going to be on the same communications network, the base address will have to be changed so that
each unit has a unique address. This is done by changing one or more
of the DIP switches to the Off position. The base address is 32
decimal. Changing these switches causes the following address
change.
DIP Switch 1 OFF
DIP Switch 2 OFF
DIP Switch 3 OFF
DIP Switch 4 OFF
DIP Switch 5 OFF
The BAUD rate can be adjusted to the appropriate setting by using the
following chart.
BAUD Rate
1,200
2,400
4,800
9,600
DIP Switch #6
ON
OFF
ON
OFF
DIP Switch #7
ON
ON
OFF
OFF
Page 25
CHILLER OPERATION
The following diagram illustrates the basic operation of a water cooled
portable chiller. There is a brief description of the coolant circuit and
the refrigerant circuit. Keep in mind that this drawing is general in
nature and that some of the components and piping may change
depending on which options have been selected.
Page 26
Coolant Circuit
The pump draws coolant from the reservoir and circulates it through
the evaporator. It is in the evaporator where the heat is transferred
from the coolant to the refrigerant. The temperature of the coolant
being delivered to the process is controlled by adjusting the amount of
heat transferred in the evaporator.
After leaving the evaporator, the coolant passes through a manifold
which includes a freezestat sensing bulb, flow switch (or pressure
switch), thermocouple and process supply throttling valve. The
freezestat sensing bulb, flow switch and pressure switch are safety
controls that are connected to the microprocessor. The thermocouple
senses the temperature of the coolant being delivered to process and
communicates this temperature to the microprocessor. The process
supply throttling valve can be used to adjust the flow out to process.
Opening this valve will increase the flow to process while closing it
will result in a reduction of flow.
This manifold is connected directly to the process water supply connection on the back of the chiller. Once the coolant passes through
this manifold, it is delivered out to process where it picks up the
process heat before returning to the process water return connection.
From this connection, the coolant returns directly to the reservoir
where the whole sequence starts over.
A small coolant bypass line tees off of the manifold between the thermocouple and the supply throttling valve. This line allows the chiller
to operate with sufficient flow through the evaporator even if the flow
is restricted or completely shut off through the process. On air cooled
models AQ0A0H through AQ0A03 and water cooled models AQ0W02
through AQ0W05 chillers, the bypass is a small copper line running
from the process supply manifold to the process return line. On air
cooled models AQ0A06 through AQ0A10 and water cooled models
AQ0W08 through AQ1W40, the bypass is a hose that runs from the
process supply manifold directly back into the reservoir. There is a
cock valve located in this line right where it connects to the reservoir.
This valve can be adjusted depending on how much flow is required by
the process.
Note: Closing this valve off too far may result in a situation
that could damage components in the chiller. The main purpose of the bypass line is to avoid deadheading of the pump and
reduce the possibility of a freeze-up.
!
Page 27
Refrigerant Circuit
The heat that is transferred in the evaporator from the coolant to the
refrigerant is used to change the state of the refrigerant from a liquid
to a gas. After leaving the evaporator, the refrigerant passes through
the suction accumulator. The purpose of the suction accumulator is to
trap any liquid refrigerant that may exit the evaporator during startup. The refrigerant gas passes through to the compressor. The
trapped liquid in the suction accumulator will eventually boil off and
move on to the compressor.
The compressor is the heart of the refrigeration circuit. It takes the
cool, low pressure gas entering the compressor and compresses it
which creates the hot, high pressure gas that exits the compressor.
Since the compressor is not 100% efficient, some extra heat is added to
the refrigerant as it is being compressed.
The hot, high pressure gas that exits the compressor is delivered to
the condenser. In the condenser, the heat is transferred from the
refrigerant into the air stream or water stream that is passing
through in the opposite direction. As the heat is transferred, the
refrigerant changes from a gas to a liquid. The condenser has been
sized to remove the heat from the process load and the heat that was
added by the compressor.
After leaving the condenser, the liquid refrigerant passes through the
receiver (air cooled units only), the filter drier and sight glass. The
filter drier filters out any particles and/or moisture from the refrigerant. The sight glass is used to monitor the stream of liquid refrigerant. The liquid refrigerant then passes through the thermal expansion valve (TXV) which meters the flow into the evaporator where the
process starts all over again.
Capacity and temperature control is accomplished with a hot gas
bypass system on these chillers. If the chiller is catering to a partial
load from the process, the coolant supply temperature would normally
tend to drop. The microprocessor senses this drop in temperature, and
opens the hot gas bypass solenoid valve. When this valve is open,
some of the hot compressor discharge gas is directed to the inlet of the
evaporator instead of going through the condenser. This puts an
additional heat load on the evaporator which brings the coolant temperature back up to set point. With PID control from the microprocessor and the solenoid cycling as much as once every ten seconds, coolant temperature is usually controlled within 1F (0.5C) of set point
even with loads as low as 10% - 25% of full capacity.
Page 28
If the process heat load is extremely low, or even nonexistent, the hot
gas bypass system may not be able to put enough of a false load on the
evaporator, and the coolant temperature will begin to drop. When the
coolant temperature drops to 7F (4C) below the set point temperature, the controller will shut the compressor off. When the coolant
temperature rises back to the set point temperature, the compressor
comes back on.
The compressor will remain off for at least two minutes to prevent
short cycling.
Page 29
CHILLER CONSTRUCTION
Refrigeration Components
! Compressor
Hermetic
If the model number of the chiller begins with AQ0, then the chiller is
equipped with a hermetically sealed compressor. Both the compressor
and the motor are encased together in the enclosure. Inside the
casing, the compressor is spring mounted which extends compressor
life and provides quiet operation. The motor windings are cooled by
the cool refrigerant suction gas, and there is an internal thermal
overload to protect the windings from overheating. The compressor
also includes a crankcase heater which will boil off any liquid refrigerant that may have migrated into the compressor crankcase while the
chiller was shut off. The compressor is lubricated with oil that travels
throughout the system with the refrigerant.
Semi-Hermetic
If the model number of the chiller begins with AQ1, then the chiller is
equipped with a semi-hermetic compressor. A semi-hermetic compressor has all of the features of the hermetic compressor except that the
semi-hermetic compressor has removable heads so that it can be
taken apart to be serviced or rebuilt. The semi-hermetic compressor is
not internally spring mounted like the hermetic compressor, so it
tends to run a little louder.
Scroll
If the model number of the chiller begins with AQ2, then the chiller is
equipped with a scroll compressor(s). Both the compressor and the
motor are encased together and solidly mounted in the enclosure. The
compressor is unidirectional and will only pump refrigerant when
properly phased. The motor windings are cooled by the cool refrigerant suctions gas, and there is an internal thermal overload to protect
the windings from overheating. The compressor is lubricated with oil
that travels throughout the system with the refrigerant.
Page 31
! Evaporator
There are three different types of evaporators used in these chillers.
Air cooled models AQ0A0H through AQ0A03 and water cooled models
AQ0W02 and AQ0W03 use a tube-in-tube style evaporator. Air cooled
models AQ0A06 through AQ0A10 and water cooled models AQ0W05
through AQ1W30 use a brazed plate style evaporator. Water cooled
models AQ1W35 and AQ1W40 use a shell-and-tube evaporator.
The tube-in-tube evaporators have a steel outer tube with a copper
inner tube. The refrigerant passes between the steel and the copper,
while the coolant flows through the copper tube in the opposite direction from the refrigerant.
The brazed plate evaporators are constructed with stainless steel
plates and copper brazing. The refrigerant passes between every
other set of plates, while the coolant flows on the other side of the
plates in the opposite direction.
The shell-and-tube evaporators are constructed with a steel shell
around a bundle of copper tubes. The refrigerant passes through the
copper tubes, while the coolant passes in the opposite direction around
the tubes.
The sight glass can also be used to check if there is moisture in the
refrigeration system. If there is moisture in the system, the green dot
in the center of the sight glass will turn yellow. If this occurs, the
chiller should be serviced immediately.
! Suction Accumulator
The suction accumulator is the refrigerant vessel located in the suction line between the evaporator and the compressor. The purpose of
the suction accumulator is to trap any liquid refrigerant before it can
enter the compressor. The refrigerant gas is allowed to pass through,
while the liquid will remain in the bottom of the vessel. The trapped
liquid will eventually boil off and move on to the compressor.
Wet-Side Components
! Reservoir
On chillers up to 30 HP, the coolant reservoir is mounted on top of the
shelf in the chiller and is easily accessible by removing the top panel.
The reservoir is made of polyethylene and is fully insulated. A slot
has been made in the insulation so that the coolant level can be observed without removing any panels. There is a six inch screw cap on
the top of the reservoir that can be used for filling and cleaning. There
is a small hole in this cap so that air can vent to the atmosphere.
!
Page 34
Air cooled models AQ0A0H through AQ0A03 and water cooled models
AQ0W02 through AQ0W05 are equipped with an eight gallon reservoir, air cooled models AQ0A06 through AQ0A10 have a 20 gallon
reservoir, while water cooled models AQ0W08 through AQ1W30 have
a 45 gallon reservoir. During chiller operation, these reservoirs should
be at least half full. For most installations, these tanks have sufficient
capacity to handle the coolant that drains back from the piping when
the chiller is shut off. For overhead piping runs of more than 50 feet,
special precautions will have to be made during installation. See
details on Overhead Piping diagram for overhead piping installations.
Water cooled models AQ1W35 and AQ1W40 are equipped with a 40
gallon cylindrical galvanized steel reservoir mounted inside the
cabinetry above the pump. This reservoir is filled using the fill-port
that extends through the top of the cabinet. There is a sight glass
located at one end of the tank. These tanks cannot be pressurized,
and it is very likely that overhead piping will require the special
precautions illustrated on the Overhead Piping Diagram.
! Coolant Pump
The close-coupled centrifugal pump is equipped with a mechanical
seal. The 1 HP pumps are constructed of bronze, while all other
sizes are bronze-fitted cast iron construction. Each pump is factory
tested for the specified operating conditions. The ODP motor meets
NEMA specifications and industry standards.
! Pressure Gauge
A pressure gauge is mounted on the back panel of the chiller. This
gauge displays the pressure of the coolant at the discharge of the
pump. It can be used to determine the approximate point on the
pump curve in which the pump is operating.
Page 35
Note: Although partially closing this valve will raise the pressure reading on the pressure gauge, the pressure being delivered to the process will actually be reduced. Throttling this
valve will always reduce the flow out to process.
The fan cycling controls are designed to turn the condenser fans on
and off in order to maintain a constant compressor discharge refrigerant pressure. During normal operation, the fans will cycle on and off
based upon the process heat load and ambient air conditions.
Note: It is possible that a condenser fan will continue to operate after the chiller has been shut-off. This fan will automatically shut off as soon as the refrigerant pressure drops below
the preset level on the fan cycling control.
Page 36
! Freezestat
The freezestat control is a mechanical thermostat which senses the
coolant temperature separately from the microprocessor controller.
This safety is designed to limit the temperature of the coolant leaving
the evaporator and prevent any possible freeze-up situations. This
control should be set 10F (5C) below the minimum coolant supply
temperature, and there should be a sufficient glycol concentration for
10F (5C) below the freezestat setting. Manual reset is required.
Note: It is critical that the freezestat is set properly and that
there is sufficient glycol in the system to correspond with the
freezestat setting. Freeze-ups can cause extensive damage to
several components in the chiller, and the warranty does not
cover repairs required due to a freeze-up.
Page 37
STANDARD OPTIONS
There are many different combinations of options available on portable chillers. Many special options are provided so that the chiller
can meet the special requirements of a particular process. It is not
practical to include all of the special options in this manual; therefore,
in instances where these options have been included, it may be necessary to refer to separate documentation for the specifics of the special
features. The following are the most common standard options.
Page 38
! Nonferrous Construction
Standard chillers have several components in contact with the coolant
that are made of mild steel. This is acceptable for most applications;
however, for applications that require extremely clean water, distilled
water, or deionized water, the nonferrous construction option is
strongly recommended. With this option, all components in contact
with the process fluid are constructed of nonferrous materials. These
materials include stainless steel, bronze, brass, copper, plastic and
rubber.
! Upgraded Pumps
The standard pumps that have been selected for each size chiller will
meet the requirements of most applications; however, in certain instances, larger pumps may be required to provide the desired flow and
pressure for a specific application. The horsepower of the pump will
be indicated on the nameplate on the chiller.
Page 39
PREVENTIVE MAINTENANCE
Once your portable chiller has been placed into service, the following
maintenance procedures should be adhered to as closely as possible.
The importance of a properly established preventive maintenance
program cannot be overemphasized. Taking the time to follow these
simple procedures will result in substantially reduced downtime,
reduced repair costs, and an extended useful lifetime for the chiller.
Any monetary costs of implementing these procedures will almost
always more than pay for itself.
To make this as simple as possible, a checklist should be prepared
which lists the recommended service operations and the times at
which they are to be performed. On the following page, we have
included a checklist that can be used for this purpose. Notice that
there are locations for voltage readings, amperages, etc. so that they
can be monitored over time. With this information, maintenance
personnel may be able to correct a potential problem before it causes
any downtime. For best results, these readings should be taken with a
full heat load from process, preferably with similar operating conditions each time.
The following is a list of suggested periodic maintenance.
! Once a Week
1. (Air Cooled Units Only) Check the surface of the air cooled
condenser coil for dirt and debris. Clean out with compressed air
if necessary.
2. Check to make sure that the To Process temperature is maintained
reasonably close to the Set Point temperature. If the temperature
stays more than 5F (3C) away from the set point, there may be a
problem with the chiller. If this is the case, refer to the Troubleshooting Chart or contact the Service Department.
3. Check the pump discharge pressure on the gauge on the back
panel of the chiller. Investigate further if the pressure starts to
stray away from the normal operating pressure.
4. Check the coolant level in the reservoir. Replenish if necessary
making sure to take proper precautions to maintain the appropriate glycol concentration.
5. Check coolant circulation pump for leaks in the seal area. Replace
pump seal if necessary.
Page 40
6. Check refrigerant sight glass for air bubbles or moisture indication. If the sight glass indicates that there is a refrigeration
problem, have the unit serviced as soon as possible.
Repeat items 1 through 6 as listed above and continue with the
following.
! Once a Month
7. With the main disconnect shut off, check the condition of electrical
connections at all contactors, starters and controls. Check for loose
or frayed wires.
8. Check the incoming voltage to make sure it is within 10% of the
design voltage for the chiller.
9. Check the amp draws to each leg of the compressor and pump to
confirm that they are drawing the proper current.
Repeat items 1 through 9 listed above and continue with the
following.
Page 41
Maintenance Activity
Date
Temperature Control
Pump Discharge Pressure
Coolant Level
Glycol Concentration
Pump Seal
Refrigerant Sight Glass
Electrical Connections
Incoming Voltage
Compressor L1 Amps
Compressor L2 Amps
Compressor L3 Amps
Pump L1 Amps
Pump L2 Amps
Pump L3 Amps
Clean Y-strainer
Refrigerant Circuit Check
Refrigerant Suction Pressure
Refrigerant Discharge Pressure
Refrigerant Superheat
Clean Out Condenser
Page 42
Week Number
6
7
8
10
11
12
13
TROUBLESHOOTING
Problem
Possible Cause
Remedy
Compressor contactor
Replace if faulty
Replace if faulty
Compressor failure
Problem
Possible Cause
Remedy
Pump overload
Pump contactor
Replace if faulty
Replace if faulty
Pump failure
Replace if faulty
Problem
Possible Cause
Remedy
Low refrigerant
pressure
Refrigerant leak
Replace if faulty
Page 43
Problem
Possible Cause
Remedy
High refrigerant
pressure
Replace if faulty
Clean out
Replace if faulty
Replace if faulty
Replace if faulty
Page 44
Problem
Possible Cause
Remedy
Freezestat
Freezestat control
Replace if faulty
Thermocouple
Replace if faulty
Problem
Possible Cause
Remedy
No restriction in process or
piping
Pressure gauge
Replace if faulty
Pump failure
Replace if faulty
Problem
Possible Cause
Remedy
High pump
discharge pressure
Open valves
Open valve
Clear obstruction
Clogged Y-strainer
Clean strainer
Pressure gauge
Replace if faulty
Page 45
Problem
Possible Cause
Remedy
Insufficient cooling
(temperature
continues to rise
above set point)
Replace if faulty
Thermocouple
Replace if faulty
Problem
Possible Cause
Remedy
Intermittent overloading of
chiller capacity
Replace if faulty
Thermocouple
Replace if faulty
Page 46
PUMP CURVES
Portable Chiller
Pump Curves
Flow (GPM)
3500 RPM pumps. Curves represent pump discharge. Correct for unit discharge.
SPA-1791
Page 47
DIAGRAMS
AQ0A0H
Electrical Wiring Diagram
EWC-0767
Page 48
AQ0A01
Electrical Wiring Diagram
EWC-0771
Page 49
AQ0A02 - AQ0A10
Electrical Wiring Diagram
EWC-0731
Page 50
DIAGRAMS
AQ0W02 - AQ0W05
Electrical Wiring Diagram
EWC-0751
Page 51
AQ0W08 - AQ0W10
Electrical Wiring Diagram
EWC-0755
Page 52
AQ1W05 - AQ1W15
Electrical Wiring Diagram
EWC-0763
Page 53
AQ1W20-AQ1W30
Electrical Wiring Diagram
EWC-0884
Page 54
AQ1W35 - AQ1W40
Electrical Wiring Diagram
EWC-0894
Page 55
Pressure Gauge
Electrical
Knock-Out
Sight Glass
SPA-2537
Pressure
Gauge
Electrical
Knock-Out
Chilled Water
Supply
Chilled Water
Return
SPB-2439
Page 56
Pressure Gauge
Electrical
Knock-Out
Sight Glass
Chilled Water Return
Chilled Water Supply
SPA-2549
SPB-2550
Condenser
Water Out
Condenser
Water In
SPD-1780
Page 57
WARRANTY
Thermal Care warrants its equipment to be free from defects in material and workmanship
when used under recommended operating conditions.
Thermal Care's obligation is limited to repair (i.e. rewind a motor) or replacement (not
adjustment or maintenance), F.O.B. the factory of any parts supplied by Thermal Care for a
period of eighteen months (twelve months for 1/2 and 1 HP compressor units) from date of
shipment to the original purchaser. The microprocessor is provided with a five year parts
warranty. All units with 2 HP or larger compressors include a labor warranty in the continental United States, Canada, Puerto Rico and select portions of Mexico. Refrigerant and any
labor associated with its evacuation or replacement are not covered by this warranty.
This warranty does not cover the cost of labor during overtime hours (after normal working
hours or during weekends and holidays). Any cost differential for overtime labor will be the
responsibility of the customer. Thermal Care is not responsible for any sales, use, excise or
other applicable taxes associated with the replacement of parts under this warranty. This
warranty will be voided when, in Thermal Cares opinion, the equipment and/or system has
been subject to misuse, negligence or operation in excess of recommended limits, including
freezing, or has been altered, and/or repaired without express factory authorization. If
equipment is installed in hostile environments, unless such conditions were specified at the
time of purchase; or the serial number has been removed or defaced this warranty shall not
apply. This warranty is not transferrable.
Under no circumstances shall Thermal Care be liable for loss of prospective or speculative
profits, or special, indirect, incidental or consequential damages.
All warranty service must be authorized by Thermal Care prior to work being performed and
have a Thermal Care purchase order issued. All defective parts become the property of
Thermal Care and must be returned as advised by Thermal Care.
Thermal Care neither assumes, nor authorizes any person to assume for it, any liability not
expressed in this warranty. There is an implied warranty of merchantability and of fitness for
particular purpose; all other implied warranties, and any liability not based upon contract are
hereby disclaimed and excluded by this warranty. This warranty is part of the standard
conditions and terms of sale of Thermal Care.
Form 1-407
Page 58
Customer Service
Phone
847/966-2636
Fax
847/966-2906
Form 2-325.1
5/00