1. A three-phase three-wire transmission system (Fig. 1)
has its conductors situated at the vertices of a triangle of
sides 4, 6 and 9 meters, each conductor having a radius
of 1cm. Assuming line to be completely transposed and
carrying balanced load current, calculate the line
inductance per phase per km.
(Ans: 1.33 mH/phase/km)
Fig. 1
2. If the radius of single strand in a 7-strand ACSR conductor is r. Find the equivalent radius
conductor (GMR or self GMD).
(Ans: 2.176r)
3. A 500 kV line has a bundling arrangement of two conductors per phase as shown in Fig.
2. Compute the reactance per phase of this line at 50 Hz. Each conductor carries half of
the total phase current. Assume that the line is transposed.
(Ans: 0.346 /km)
Fig.2
Fig. 3
7. Determine the capacitance of arrangement shown in Fig. 4 when (a) the effect of earth is
neglected and (b) the effect of earth is considered if the heights of conductors from
ground are 10 meters. Radius of the conductors is 2cm.
(Ans: (a)10.04 pF/m/phase (b)19.94 pF/m/phase)
Fig.4
9. A three-phase overhead line 200 km long has resistance=0.16 /km and conductor
diameter of 2 cm with spacing 4 m, 5 m and 6m transposed. Find:
a. The ABCD Constants
b. The Vs, Is, pfs, Ps when the line is delivering full load of 50 MW at 132 kV and 0.8
lagging p.f.
c. Efficiency of transmission and receiving-end voltage regulation of transmission line.
(Ans: (a)A=0.978<0.50, B=86.4<68.60, C=0.00056<90.20, D=0.978<0.50 (b) Vs=165.44kV, Is=0.244<28.30 kA, pfs=0.808 lagging, Ps= 56.49 MW (c) Efficiency=70.8%, Regulation=28.15% )
10. A 50 Hz, three-phase, 275 kV, 400 km transmission line has the following parameters
(per phase)
Resistance = 0.035 /km
Inductance = 1 mH/km
Capacitance = 0.01 F/km
If the line is supplied at 275 kV determine the MVA rating of a shunt reactor having
negligible losses that would be required to maintain 275 kV at the receiving-end, when
the line is delivering no-load. Use nominal- method.
(Ans: 47.56 MVAr)