SECTION 15130

PUMPS
GENERAL
1
.A
.1
.2

SUMMARY
Section Includes:
Base mounted pumps.
Twin In-Line Pumps

.B
Related Sections:
.1
Section 15070 - Mechanical Sound,
Vibration, and Seismic Control: Product requirements for
vibrations isolators installed with pumps.
.2
Section 15120 - Piping Specialties:
Product and execution requirements for piping specialties
installed in hydronic systems adjacent to pumps.
Note: For electrical requirements, refer to the
electrical specifications under separate cover
of the Contract Documents.
2

PERFORMANCE REQUIREMENTS

.A
Provide pumps to operate at system fluid
temperatures indicated on Drawings without vapor binding and
cavitation, are non-overloading in parallel or individual operation,
and operate within 25 percent of midpoint of published maximum
efficiency curve.
3

SUBMITTALS

.A
Product Data: Submit certified pump curves showing
performance characteristics with pump and system operating point
plotted. Include NPSH curve when applicable. Include electrical
characteristics and connection requirements. Submit also,
manufacturer model number, dimensions, service sizes, and
finishes.
.B
Manufacturer's Installation Instructions: Submit
application, selection, and hookup configuration with pipe and
accessory elevations. Submit hanging and support requirements
and recommendations.
.C
Manufacturer's Certificate: Certify products meet or
exceed specified requirements.
4

CLOSEOUT SUBMITTALS

.A
Operation and Maintenance Data: Submit installation
instructions, servicing requirements, assembly views, lubrication
instructions, and replacement parts list.

61

ROYAL HOSPITAL
15130-

.B
5

Maintain one copy of each document on site.


DELIVERY, STORAGE, AND HANDLING

.A
Protect systems from entry of foreign materials by
temporary covers, completing sections of the work, and isolating
parts of completed system.
6

FIELD MEASUREMENTS

.A
7

Verify field measurements prior to fabrication.


EXTRA MATERIALS

.A
pumps.

Furnish one set of mechanical seals for each pump

.B

Furnish one set of motor bearings for each pump.

PRODUCTS
1

BASE MOUNTED PUMPS

.A

Type: Horizontal shaft, single stage, direct connected,


end suction close complesed or base mounted , for 1600 kPa
maximum working pressure.
.B
Casing: Cast iron, with suction and discharge gage
ports, renewable bronze casing wearing rings, seal flush
connection, drain plug, flanged suction and discharge.
.C

Impeller: Bronze, fully enclosed, keyed to shaft.

.D
bearings.

Bearings: Permanently lubricated roller or ball

.E

Shaft: Stainless steel with bronze shaft sleeve.

.F
Seal: Carbon rotating against stationary ceramic seat,
100 degrees C maximum continuous operating temperature.
.G

Drive: Flexible coupling with coupling guard.

.H
drain rim.

Baseplate: Cast iron or fabricated steel with integral

.I
Electrical Characteristics and Components:
.1
Motors: 1450 rpm unless specified
otherwise. Totally enclosed fan cooled, IP55.
.2
Wiring Terminations: Furnish terminal
lugs to match branch circuit conductor quantities, sizes, and
materials indicated. Enclose terminal lugs in terminal box
sized to NFPA 70.

62

ROYAL HOSPITAL
15130-

TWIN IN-LINE PUMPS

.A
Type: Two single stage, low pressure, centrifugal
pumps of monobloc construction mounted on a common body
hydraulically separated by a changeover flap, for 1600 kPa
maximum working pressure.
.B
Casing: Cast iron, with suction and discharge gage
ports, renewable bronze casing wearing rings, seal flush
connection, drain plug, flanged suction and discharge.
.C

Impeller: Bronze, fully enclosed, keyed to shaft.

.D
bearings.

Bearings: Permanently lubricated roller or ball

.E

Shaft: Stainless steel with bronze shaft sleeve.

.F
Seal: Carbon rotating against stationary ceramic seat,
100 degrees C maximum continuous operating temperature.
.G
Furnish concrete foundation and vibration isolators as
shown on drawings.
.H
Furnish blank cover plate to close off opening when
one of the pumps is removed for maintenance.
.I
Electrical Characteristics and Components:
.1
Motors: 1450 rpm unless specified
otherwise. Totally enclosed fan cooled, IP55.
.2
Wiring Terminations: Furnish terminal
lugs to match branch circuit conductor quantities, sizes, and
materials indicated. Enclose terminal lugs in terminal box
sized to NFPA 70.
EXECUTION
1

INSTALLATION

.A
Provide pumps to operate at specified system fluid
temperatures without vapor binding and cavitations, are nonoverloading in parallel or individual operation, and operate within
25 percent of midpoint of published maximum efficiency curve.
.B
Install long radius reducing elbows or reducers
between pump and piping. Support piping adjacent to pump so no
weight is carried on pump casings. For base mounted pumps, install
supports under elbows on pump suction and discharge line sizes
100 mm and over.
.C
15070.

63

Install pumps on vibration isolators. Refer to Section

ROYAL HOSPITAL
15130-

.D
Install flexible connectors at or near pumps on
suction and discharge pipes.
.E
Provide line sized shut-off valve and strainer on pump
suction, and line sized soft seat check valve and shut-off valve on
pump discharge.
.F
Decrease from line size with long radius reducing
elbows or reducers. Support piping adjacent to pump so no weight
is carried on pump casings. Provide supports under elbows on pump
suction and discharge line sizes 100 mm and larger.
.G

Provide drains for bases and seals.

.H
Check, align, and certify alignment of base mounted
pumps prior to start-up.
.I
Install base mounted pumps on concrete
housekeeping base, with anchor bolts, set and level, and grout in
place.
.J

Lubricate pumps before start-up.

***END OF SECTION***