Documente Academic
Documente Profesional
Documente Cultură
earth-fault relay
SPAJ 140 C
1MRS 750361-MBG
Page 1
Issued: April 1999
Status: New
Data subject to change without notice
Features
Powerful software support for parameterization of the relay, for reading measured
and recorded values, events, etc., and for
storing readings
Application
overcurrent protection. The combined overcurrent and earth-fault relay includes a circuit-breaker failure protection unit.
The combined overcurrent and earth-fault
relay SPAJ 140 C is part of ABBs Distribution Automation concept, which is a product
segment of Panorama, the complete ABB
solution for the control and management of
electric power systems.
SPAJ 140 C
1MRS 750361-MBG
Page 2
Design
Data communication
The relay is provided with a serial interface
on the rear panel. By means of a bus connection module type SPA-ZC 17 or SPA-ZC 21
the relay can be connected to the fibre-optic
SPA bus. The bus connection module type
SPA-ZC 21 is powered from the host relay,
whereas the bus connection module SPAZC 17 is provided with a built-in power unit,
which can be fed from an external secured
power source. The relay communicates with
higher-level data acquisition and control systems over the SPA bus.
Self-supervision
The relay incorporates a sophisticated selfsupervision system with auto-diagnosis,
which increases the availability of the relay
and the reliability of the system. The selfsupervision system continuously monitors the
hardware and the software of the relay. The
system also supervises the operation of the
auxiliary supply module and the voltages
generated by the module.
When a permanent internal relay fault is
detected, the IRF indicator on the relay front
panel is lit. At the same time the output relay
of the self-supervision system operates and a
fault message is transmitted to the higherlevel system over the serial bus. Further, in
most fault situations, a fault code is shown in
the display of the protection relay module.
The fault code indicates the type of the fault
that has been detected.
SPAJ 140 C
1MRS 750361-MBG
Page 3
Technical data
Rated current In
1A
5A
Thermal withstand
capability
continuously
4A
20 A
for 10 s
25 A
100 A
for 1 s
100 A
500 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
50 Hz or 60 Hz
Dynamic current
withstand capability
25-26
25-27
Rated current In
1A
5A
Thermal withstand
capability
continuously
4A
20 A
for 10 s
25 A
100 A
for 1 s
100 A
500 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
50 Hz or 60 Hz
Dynamic current
withstand capability
Tripping
Signalling
Terminals
65-66, 74-75
70-71-72, 68-69,
77-78, 80-81
Rated voltage
250 V ac/dc
Continuous carry
5A
30 A
10 A
15 A
8A
220 V dc
1A
0.15 A
110 V dc
3A
0.25 A
48 V dc
5A
1A
AgCdO2
5A
SPAJ 140 C
1MRS 750361-MBG
Page 4
Data communication
Terminals
10-11
18265 V dc or
80265 V ac
220 mA
Transmission mode
Data code
ASCII
4800 or 9600 Bd
SPA-ZC 21BB
SPA-ZC 21MM
SPA-ZC 17BB
SPA-ZC 17MM
SPTU 240R1
110/120/230/240 V ac,
110/125/220 V dc,
80265 V ac/dc
SPTU 48R1
24/48/60 V dc,
1880 V dc
under quiescent
conditions
~4 W
under operating
conditions
~6 W
Power consumption
at definite time
Stage I>
Stage I>>
0.55.0 In
0.540.0 In and
0.52.5 In
50 ms
40 ms
0.05300 s
0.04300 s
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
RI type inverse
RXIDG type inverse
at inverse time
Time multiplier k
0.051.0
40 ms
40 ms
Retardation time
<30 ms
0.96
2% of set value or 25 ms
Operation accuracy
3% of set value
3% of set value
SPAJ 140 C
1MRS 750361-MBG
Page 5
Stage I0>
Stage I0>>
Start current
0.10.8 In
0.110.0 In and
60 ms
40 ms
0.05300 s
0.05300 s
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
RI type inverse
RXIDG type inverse
Time multiplier k
0.051.0
40 ms
40 ms
Retardation time
<30 ms
0.96
0.96
2% of set value or 25 ms
Operation accuracy
3% of set value
3% of set value
Interference tests
>100 M, 500 V dc
High-frequency (1 MHz)
disturbance test (IEC 255-22-1),
common mode
2.5 kV
High-frequency (1 MHz)
disturbance test (IEC 255-22-1),
differential mode
1.0 kV
4 kV, 5/50 ns
2 kV, 5/50 ns
Electrostatic discharge
(IEC 255-22-2 and IEC 801-2,
class III), air discharge
8 kV
Electrostatic discharge
(IEC 255-22-2 and IEC 801-2,
class III), contact discharge
6 kV
Variation voltage
68265 V
Interruption 80 V - 50%
0200 ms
Interruption 80 V - 100%
030 ms
0160 ms
SPAJ 140 C
1MRS 750361-MBG
Page 6
Environmental conditions
0.55.25 g
0.57.5 g
Vibration test
20 g, 1000 bumps/direction
Corrosion test
Battelle test
-10+55C
-40+70C
<95%, +40C, 96 h
IP 54
Weight
~3.5 kg
Block diagram
L1
L2
L3
-
0
+
+ (~)
U aux
- (~)
EXTERNAL
CONTROL
11
10
62 61 70 71 72
5A
1A
7 8 9 25 26 27
5A
1A
5A
1A
1 23 4 5 6
START 1
START 2
SIGNAL 1
SIGNAL 2
TRIP
74 75
77 78
80 81
68 69
65 66
+
F
SERIAL
PORT
+ -
U2
TS1
SS1
1
SS2
1
SS3
1
TS2
1
LATCHING
U3
SGR2/8
SGR2/6
SGR2/4
SGR2/2
SGR2/7
SGR2/5
SGR2/1
T1
SGR2/3
SGR1/7
SGR1/5
SGR1/3
SGR1/1
SGR3/8
SGR3/7
SGR3/6
SGR3/5
SGR3/4
IRF
3I>
SGR3/3
U1
SGB/1
SGR3/2
SGB/6
SGB/7
TRIP
R
SGR1/2
SGR1/4
SGR1/6
SGR1/8
5A
1A
63
IRF
Tx
SPA-ZC_
Rx
SGR3/1
T2
SGB/2
3I>>
T3
Io>
T5
Io>>
T7
T4
SGB/3
SGB/4
SGB/5
SPAJ 140 C
Fig. 1
SGB/8
T6
T8
RC SETTINGS
RESET
I/O
T9
SGF/4
0.1...1s
U1
SPAJ 140 C
1MRS 750361-MBG
Page 7
Flush mounting
250
142
216
34
139 1
136
162
129 1
186
30
Panel cutout
dim100
Fig. 2
Semi-flush mounting
a
Raising frame
SPA-ZX 111
SPA-ZX 112
SPA-ZX 113
176
136
96
74
114
154
SFM100_1
Fig. 3
Projecting mounting
When projecting mounting is preferred, a
relay case type SPA-ZX 110 is used. The
relay case for projecting mounting is provided with front connectors.
SPA-ZX110
SPA-ZX115
158
115
+0,4
10
263
6
21,5
312
292
+0,4
177 0 (4U)
482,6 0 (19")
101,6
Mounting and
dimensions
6
115
98
104_6_10
Fig. 4
SPAJ 140 C
1MRS 750361-MBG
Page 8
Ordering
Ordering example
2. Order number
RS 611 006-AA
3. Rated values
In=5 A, fn=50 Hz
4. Auxiliary voltage
Uaux =110 V dc
5. Accessories
6. Special requirements
Order numbers
Combined overcurrent and earth-fault relay
SPAJ 140 C without test adapter
References
Additional information
Brochure Combined overcurrent and earth-fault
relays
1MRS 750190-MDS EN
1MRS 750629-MUM EN