TECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
M - 00- D 07
REVISION NO
00
PAGE NO.
PAGE 1 OF 11
REVISION HISTORY
REVISION
00
File Location
EFFECTIVE DATE
02-01-2014
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
M - 00- D 07
REVISION NO
00
PAGE NO.
PAGE 2 OF 11
TABLE OF CONTENTS
1.0
APPROVAL SIGNATURES
2.0
OVERVIEW
3.0
4.0
5.0
PACKING
6.0
SPARES
7.0
DATASHEET
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
M - 00- D 07
REVISION NO
00
PAGE NO.
PAGE 3 OF 11
Designation
Prepared By
Rajesh Yerawar
Checked By
Akhilesh Verma
Manager - Mechanical
Approved By
Sanjay Katkade
GM-Engineering
Name
Designation
Signature
Date
Signature
Date
CLIENT
Approved By
Authorized By
2.0 OVERVIEW
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
M - 00- D 07
REVISION NO
00
PAGE NO.
PAGE 4 OF 11
Navin Flourine International Limited has envisioned setting up an Manufacturing plant No.2
facility at Dewas along with the necessary utilities
Nearest railway station
DEWAS
Nearest airport
INDORE
Ambient conditions:
Summer ( DB / WB / % RH)
40 C / 24.4 C / 28 %
Monsoon ( DB / WB / % RH)
28 C / 26 C / 82 %
Winter ( DB / WB / % RH)
10 C / 5.6 C / 50 %
The vendor shall supply to purchaser 3 sets of the certificates of Internal routine tests.
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
21116
PROJECT NO
DOCUMENT NO
-
System schematics
M - 00- D 07
REVISION NO
00
PAGE NO.
PAGE 5 OF 11
5.0 PACKING
Equipment shall be dispatched to site packed in full wooden case (Sea Worthy). It shall be
wrapped in polythene sheets before putting in cases and it shall be ensured that damage to
the equipment does not occur during handling/transportation. Lifting hooks shall be provided
for unloading at site.
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
21116
PROJECT NO
DOCUMENT NO
REVISION NO
00
PAGE NO.
PAGE 6 OF 11
M - 00- D 07
6.0 SPARES
Commissioning Spares The vendors shall include in the quoted price sufficient quantities of commissioning spares
required for erection and commissioning of the equipment. These shall include such items as
Bolts and other miscellaneous parts.
Essential Spares The vendor shall supply spares required for two years trouble free operation & furnish list of
spare considered with offer.
7.0 DATASHEET
DESIGN PARAMETER
REQUIRED SPECIFICATION
PROCESS DATA
Equipment
Tag No.
TFH-102
Construction
Vertical
Quantity, No(s)
2,00,000
Thermic Fluid
Vendor to specify
Final Temperature, C
300
Inlet Temperature, C
270 280
Vendor to specify
Fuel
Coil Pipe diameter
Vendor to specify
Vendor to specify
Shell Thickness
Vendor to specify
File Location
TYPE
MOC
Vendor to specify
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
M - 00- D 07
REVISION NO
00
PAGE NO.
PAGE 7 OF 11
DESIGN PARAMETER
REQUIRED SPECIFICATION
Vendor to specify
Make of Blower
Vendor to specify
H.P. of Motor
Vendor to specify
Make of Motor
Vendor to specify
IP 55
Vendor to specify
Inlet Damper
Dynamic Balancing
Vendor to specify
Vendor to specify
Mesh
Vendor to specify
MOC
Vendor to specify
Make
Vendor to specify
Gear
Vendor to specify
MOC
Vendor to specify
Number of Pumps
Type of coupling between Motor & Pump
1 Working + 1 Stand-by
Vendor to specify
Make of Pump
Vendor to specify
H.P. of Motor
Vendor to specify
Make of Motor
Vendor to specify
IP-55
Dynamic Balancing
To be provided
Duplex
Mesh
Vendor to specify
MOC
Vendor to specify
Make
Vendor to specify
BURNER ASSEMBLY
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
21116
PROJECT NO
DOCUMENT NO
M - 00- D 07
DESIGN PARAMETER
REVISION NO
00
PAGE NO.
PAGE 8 OF 11
REQUIRED SPECIFICATION
Min 1:3
Ignition Electrode
To be provided
Photocell
To be provided
Ignition Transformer
To be provided
Spray Diffuser
To be provided
To be provided
Make of Photocell
Vendor to Specify
Vendor to Specify
Vendor to Specify
Type
BUFFER TANK
Capacity
Vendor to specify
Quantity
MOC
Vendor to specify
Design Temperature, C
Vendor to specify
Design Pressure
Vendor to specify
Insulation
Vendor to specify
Insulation Cladding
SS 304
SS 304
EXPANSION TANK
File Location
Capacity
Vendor to specify
Quantity
MOC
Vendor to specify
Design Temperature, C
Vendor to specify
Design Pressure
Vendor to specify
Insulation
Vendor to specify
Insulation Cladding
SS 304
SS 304
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
REVISION NO
00
PAGE NO.
PAGE 9 OF 11
M - 00- D 07
DESIGN PARAMETER
REQUIRED SPECIFICATION
CIRCULATION PUMP
Make
Vendor to specify
Model
Vendor to specify
Quantity, No(s)
Capacity, m3/hr
Circulation pipe length
(supply & return), m
Static head, m
Vendor to specify
Vendor to specify
VFD
Required
Mechanical Seal
Vendor to specify
Vendor to Confirm
Vendor to specify
Design Pressure
Vendor to specify
SS 304
200
Later
SKID
Overall Dimension
Vendor to specify
MOC
SS 304
SS 304
Vendor to specify
Dry Weight
ACCESSORIES
Fuel pressure guage mounted on oil filter.
Fuel piping between oil filter ,fuel pump
and Burner
Inlet header with isolation SS needle valve
for inlet pressure sensing. Thermo well for
temp sensing inlet pressure gauge
mounted on control panel
Outlet header with low flow safety isolation
SS needle valves Thermo well for outlet
temp.sensing .Outlet pressure guage
mounted on control panel.
Oil pressure sencing line of copper tubing
and its hardware.
Standard Tool Kit
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
To be provided
To be provided
To be provided
To be provided
To be provided
To be provided
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
M - 00- D 07
DESIGN PARAMETER
REVISION NO
00
PAGE NO.
PAGE 10 OF 11
REQUIRED SPECIFICATION
CONTROL PANEL
Control Panel Box to house all necessary & Sturdy Mild Steel fabricated with three
electrical & instrumentation to perform said coats of primers & epoxy painting oven
safety interlocks & indications
backed rubber sealing for dustproof
enclosure of instruments as per standard
norms.
Panel Isolation Switch
To be provided
Start/Stop/Fill/Cooling mode selection
To be provided
rotary switch
Fuel circulation inching press button
To be provided
Indicating bulbs with name plates for visual
indication of various control modes
To be provided
mentioned above, mounted on panel front
Wiring completely made from solid
conductor single core for systematic layout To be provided
of wiring
Electric Wire Protection Pipes to protect
various connections going to Motors,
To be provided
Instruments, etc.
Audio Alarm
To be provided
Contractor and Overload protection relays
To be provided
for pump motor and blower motor
Burner prepurge timer
To be provided
Rotary selector switches
Inlet temp indicator cum burner controller
Digital type
Outlet temperature indicator cum safety
controller
Flame failure safety cum burner sequence
controller
Low flow safety controller
To be provided
To be provided
To be provided
To be provided
Ignition Transformer.
To be provided
To be provided
To be provided
To be provided
File Location
Required
Required
Temperature Indicator
Digital, Required
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013
TECHNICAL SPECIFICATION
THERMIC FLUID HEATER
PROJECT NO
DOCUMENT NO
21116
REVISION NO
00
PAGE NO.
PAGE 11 OF 11
M - 00- D 07
DESIGN PARAMETER
REQUIRED SPECIFICATION
Pressure Indicator
Digital, Required
Vendor to specify
Control Panel
Required
Required
Vendor to specify
Type of pipe
Seamless
Rating, (lb)
300
MOC
CS
Total length, m
150
Lot
Insulation
Required
CHIMNEY
EXISTING
Connection Size
Vendor to specify
ADDITIONAL SCOPE
Installation Assistance
To be included in scope
Commissioning Assistance
To be included in scope
Training
To be included in scope
File Location
Z:\PRJ1\API\NFIL 21113\PROCUREMENT\UTILITY\URS\Floated\Thermic
Fluid system\21113 M-00-D07 URS THERMIC FLUID HEATER-R0.docx
Format No:
SOP/ENG/005/02
Rev. 00 01/01/2013