Efficient energy
management and
continuity of service with
source-changeover system
To ensure continuity of service for critical applications,
LV electrical installations need to be connected to
at least two independent power sources:
A normal
And a replacement
source (N)
source (R)*
The source-changeover
system switches the
load (partly or fully)
between these
two sources.
circuit breakers,
switch-disconnectors
or contactors.
> A source-changeover
system comprises
* The replacement source (R) can be: a second power source (with possibly different
characteristics from the normal source) or an electrical generator
I
313E0105.indd 1
14/11/2011 11:53:48
ways
System
Applications
The most commonly used system for devices with high ratings. No direct human
intervention is required. Source-changeover is controlled electrically.
System
Applications
System
Applications
II
313E0105.indd 2
14/11/2011 11:53:48
Interpact
From 40 A to 630 A
Maximum continuity
of service
> Energy availability is ensured whatever
the external requirements (e.g. high
power demand).
> Maintenance and replacement of the sources
(N or R) can be done with no interruption
of service.
You can maintain a continuous level of service
and customer satisfaction.
Compact NSX
Masterpact NT / NW
Maximum safety
For LV electrical installations where safety and
continuity of service are critical for people
and/or equipment such as hospitals, airports,
banks, malls, etc.
Optimized energy
management
> Transfer the load to a replacement source
according to external requirements.
> Manage power sources according to power
quality and power costs.
> Perform system regulation.
> Switch to an emergency replacement source.
You are no longer dependent on your power
supply (and supplier)!
UA Controller
Compact NSX
From 100 A to 630 A
III
313E0105.indd 3
14/11/2011 11:53:50
Managing
energy
efciently
Power Cost
Safety
IV
313E0105.indd 4
14/11/2011 11:53:53
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Interpact, Masterpact
General content
Presentation
Functions
and characteristics
A-1
Dimensions
B-1
Electrical diagrams
C-1
Catalogue numbers
and order forms
D-1
313E.indb 1
14/11/2011 11:44:23
Presentation
DB101543
PB105014
Currents
From 630 to 6300 A.
PB390385_SE_R_35
Power distribution
Currents
From 250 to 3200 A.
PB104782_R
Loads
Currents
From 40 to 400 A.
313E.indb 2
14/11/2011 11:44:25
QN
0
1
0
QR
QS1
0
0
1
2 normal sources
1 replacement source
DB101540
DB101539
DB101538
1 normal source
1 replacement source
QC
QS2
0
0
0
1
0
1
1
1
0
0
1
1
1
0
0 (1)
0
0
1 (1)
(1) possible by forcing
operation.
QN1
0
1
0
1
0
QN2
QR
0
1
0
0
1
0
0
1
0
0
Generator or permanent
source
QN
DB101541
0
1
0
Generator or permanent
source
Typical applications:
b continuous production processes
b operating rooms
b computer rooms...
Generator or permanent
source
DB101544
QN
DB101541
QR
0
0
1
0
1
0
QR
0
0
1
Typical applications:
b large electrical installations (e.g. airports)
b refrigeration units
b special electricity tariffs
b pumping stations...
313E.indb 3
14/11/2011 11:44:25
TOOLS
schneider-electric.com
This international site allows you
to access all the Schneider Electric
Solution and Product information
via :
p comprehensive descriptions
p range data sheets
p a download area
p product selectors
p ..
You can also access the information
dedicated to your business and get
in touch with your Schneider Electric
country support.
313E.indb 2
14/11/2011 11:44:26
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Interpact, Masterpact
Presentation
Overview of solutions
Manual source-changeover systems
InterpactINS/INV40 to 630 A, Compact NSX100/630 A
Manual source-changeover systems Compact NS
and Masterpact NT/NW 630 A to 6300 A
Remote-operated source-changeover systems
Compact NSX100/630, Compact NS630b/1600 A
Remote-operated source-changeover systems
Masterpact NT/NW 630 A to 6300 A
Associated controllers
Controller selection
Controller installation
BA controller
BA controller, Operating sequences
UA controller
UA controller, Operating sequences, Forced operation mode
UA controller, Operating sequences, Special-tariff mode
UA controller, Operating sequences, Test mode and automatic operation
Operating sequences
IVE unit
BA/UA controller
A-2
A-2
A-3
A-4
A-5
A-6
A-6
A-10
A-10
A-11
A-12
A-13
A-14
A-15
A-16
A-17
A-18
A-18
A-19
A-20
A-21
A-22
A-23
A-24
A-25
A-26
A-26
A-27
A-28
B-1
C-1
D-1
A-1
313E2100TDM.indd 1
17/11/2011 08:30:48
Functions
and characteristics
Overview of solutions
Range
Interpact
Models
INS40 to INS80
INS100 to INS160
40 to 160
Switch-disconnectors with
extended handles
Rating (A)
Type of device
INS250 to INS630
INV250 to INV630
100 to 630
Switch-disconnectors
NSX100 to NSX250
NSX400 to NSX630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors
DB101545
DB126589
2 devices side-by-side.
3 devices side-by-side.
DB101547
DB101546
DB126590
.4
2 devices side-by-side.
ON
I
ON
I
O
OFF
O
OFF
DB101550
DB101549
DB126588
DB101551
DB126587
2 devices side-by-side.
DB101552
DB126586
2 devices side-by-side.
A-2
313E.indb 2
14/11/2011 11:44:28
Compact
Masterpact
NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors
NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors
NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit
breakers
NA/HA/HF switchdisconnectors
DB101553
DB126590
2 devices side-by-side.
I ON
OOFF
push
push
discharged
O OFF
I ON
OOFF
push
push
DB101556
DB101555
DB101554
DB126588
discharged
O OFF
sup
degr
ahcs
id
DB101559
NO h
DB101562
hsup
DB101558
FFO
FFO
DB101561
DB101557
DB126585
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
DB101560
DB126584
DB126583
(1)
2 or 3 devices side-by-side.
(2)
DB126580
A-3
313E.indb 3
14/11/2011 11:44:32
Functions
and characteristics
Overview of solutions
Range
Compact
Models
Rating (A)
Type of device
Remote-operated source-changeover
systems Compact NSX100/630,
Compact NS630b/1600 A
NSX100 to NSX630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors
NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors
DB101563
DB126587
DB101557
DB126585
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
DB101560
DB126581
DB126582
DB126581
DB125972
BA controller
DB125963
DB126582
A-4
313E.indb 4
14/11/2011 11:44:33
Remote-operated source-changeover
systems Masterpact NT/NW
630 A to 6300 A
Range
Masterpact
Models
Rating (A)
Type of device
NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors
NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit breakers
NA/HA/HF switch-disconnectors
DB101559
DB101558
DB126585
DB101562
DB101561
DB126584
DB126583
DB125972
BA controller
DB125963
DB126582
DB126581
A-5
313E.indb 5
14/11/2011 11:44:35
Manual source-changeover
systems
Functions
and characteristics
Possible combinations
A manual source-changeover system can be installed
on two or three manually-operated and mechanically
interlocked circuit breakers or switch-disconnectors.
Interlocks prevent connection to both sources at the
same time, even momentarily.
Complete
assembly
Interpact switch-disconnectors
Keylock
Direct rotary
handle
Extended
rotary handle
INS40 to INS160
b
INS250-100 to INS630
INV100 to 630
b r
b r
b r
b rr
b
INS/INV630b to 2500
Legend:
r Possible but visible break function disabled.
r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
Type of device
Keylock
Direct rotary
handle
Extended rotary
handle
On base plate
On base plate
(toggle or direct extended (motor mechanism)
rotary control)
bb
bbp
bb
bb
bbb
bbb
NSX400 to NS630
bb
bbp
bb
bb
bbb
bbb
bbp
bbp
bbp
bbbp
bbbp
NSX100 to 630
bb
NS630b to 1600 with
bbp
rotary handle
Legend:
b Fixed devices only.
b Fixed or withdrawable devices.
b Devices must be either both fixed or both withdrawable.
p With NSX400/630 rotary handle interlocking system.
p Possible with NSX400/630 base plate + NSX100-250 adaptation kit.
p Devices equipped with rotary handles.
Type of device
bb
Cable-type,
Cable-type,
Cable-type,
2 devices side-by3 devices side-by2 devices one
side
side
above the other
Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism
Cable-type,
3 devices one
above another
b
b
b
NS630b to 1600
Masterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism
NT06 to 16
NW08 to 63
NT06 to NW63
b
b
Rod-type,
3 devices one
above another
b
b
A-6
313E.indb 6
14/11/2011 11:44:35
Possible combinations
Complete source-changeover assembly for two switch-disconnectors
All possibilities for manual source-changeover systems
DB101571
Normal N
Replacement R
INS250-100
INS250-100
Ratings 100 A
INS250-160
Ratings 160 A
INS200-200
Ratings 200 A
INS250-250
Ratings 250 A
INS320
Ratings 320 A
INS400
Ratings 400 A
INS500
Ratings 500 A
INS630
Ratings 630 A
INS250-160
INS200-200
INS250-250
INS320
INS400
INS500
INS630
b
b
b
b
b
b
b
b
DB101566
Two devices can be interlocked using this system. Two identical interlocking systems
can be used to interlock three devices installed side by side, in which case one
device is in the ON position and the two others are in the OFF position. Devices must
all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout.
The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).
Two interlocking system models are available for:
b Compact NSX100 to 250
b Compact NSX400 to 630.
Normal N
NSX100
Ratings 16... 100 A
NSX160
Ratings 80...160 A
NSX250
Ratings 125...250 A
NSX400
Ratings 150... 400 A
NSX630
Ratings 630 A
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
A-7
313E.indb 7
14/11/2011 11:44:35
Manual source-changeover
systems
Functions
and characteristics
Possible combinations
Interlocking of a number of devices using keylocks (captive keys)
Combination of Normal and Replacement devices
DB101569
DB101568
The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
ON
I
ON
I
O
OFF
O
OFF
Normal N
Compact NSX100/630 (1)
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
NSX100
Ratings 16... 100 A
b
b
b
v
v
NSX160
b
b
b
v
v
Ratings 80...160 A
NSX250
b
b
b
v
v
Ratings 125...250 A
NSX400
v
v
v
b
b
Ratings 160... 400 A
NSX630
Ratings 630 A
v
v
v
b
b
v 250 A and 630 A ratings can be mixed by using NSX400/630 rotary handle interlocking
system.
Normal N
Replacement R
NS800
Compact NS630b/1600 (1) NS630b
NS1000
NS1200
NS1600
NS630b
Ratings 250... 630 A
b
b
b
b
b
NS800
b
b
b
b
b
Ratings 320... 800 A
NS1000
b
b
b
b
b
Ratings 400... 1000 A
NS1200
b
b
b
b
b
Ratings 480... 1200 A
NS1600
b
b
b
b
b
Ratings 640... 1600 A
(1) When mixing NSX100/250 and NSX400/630 circuit breakers, use the NSX400/630
interlocking system.
A-8
313E.indb 8
14/11/2011 11:44:36
Possible combinations
Interlocking of two devices with rotary handles
Possible combinations of Normal and Replacement source switch-disconnectors
DB107742
The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
Normal N
Interpact INS (1)
Replacement R
INS40
INS63
INS80
INS100
INS40
Ratings 40 A
b
b
b
b
INS63
Ratings 63 A
b
b
b
b
INS80
Ratings 80 A
b
b
b
b
INS100
Ratings 100 A
b
b
b
b
INS125
Ratings 125 A
b
b
b
b
INS160
Ratings 160 A
b
b
b
b
(1) With extended rotary handles only.
(2) Possible with INV, but visible-break function is significantly impaired.
Normal N
Interpact INS /INV (2)
INS125
INS160
Replacement R
INS250-100/
INV100
INS250-160/
INV160
INS250-200/
INV200
INS250-250/
INV250
INS250-100/INV100
b
b
b
b
Ratings 100 A
INS250-160/INV160
Ratings 160 A
b
b
b
b
INS250-200/INV200
Ratings 200 A
b
b
b
b
INS250-250/INV250
Ratings 250 A
b
b
b
b
INS320/INV320
Ratings 320 A
v
v
INS400/INV400
Ratings 400 A
INS500/INV500
Ratings 500 A
INS630/INV630
Ratings 630 A
v
v
v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
INS320/
INV320
INS400/
INV400
INS500/
INV500
INS630/
INV630
DB101570
push
to
trip
push
to
trip
NSX100
Ratings 16... 100 A
NSX160
Ratings 80... 160 A
NSX250
Ratings 125... 250 A
NSX400
Ratings 150... 400 A
NSX630
Ratings 630 A
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
DB101903
Interlocking uses two identical keylocks with a single key. This solution enables
interlocking between two devices that are physically distant or that have significantly
different characteristics.
A-9
313E.indb 9
14/11/2011 11:44:37
Functions
and characteristics
Remote-operated
source-changeover systems
PB103832_51
Normal N
NSX100
Ratings 12,5... 100 A
NSX160
Ratings 12,5...160 A
NSX250
Ratings 12,5...250 A
NSX400
Ratings 160... 400 A
NSX630
Ratings 250... 630 A
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
DB126268
Normal N
Replacement R
NS630b to
NS1600
NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
A-10
313E.indb 10
14/11/2011 11:44:38
Mechanical interlocking
Compact NS or Masterpact NT/NW
PB100842-68_SE
Normal N
Replacement R
NS630b to
NS1600
NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
Normal N
Replacement R
NS630b to
NS1600
NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
A-11
313E.indb 11
14/11/2011 11:44:39
Remote-operated
source-changeover systems
Functions
and characteristics
General characteristics
Compact NSX
Range
Compact NSX
Types of devices
Types of circuit breakers
Switch-disconnector version
Mixing possibilities
NSX100 to NSX250
N/H/L
NA
all devices
NS100 to NS250
N/H/L/NA
fixed or plug-in
NSX400 to NSX630
N/H/L
NA
all devices
NS100 to NS630
N/H/L/NA
fixed or plug-in
Rating
Insulating voltage Ui (V AC)
Positive break indication
Number of poles
(N and R devices must have the same number of poles)
15 to 250 A
750
b
3, 4
15 to 630 A
750
b
Electrical durability
Operating temperature
Electrical characteristics
Control characteristics
Control voltage
AC
Maximum consumption
DC
AC
DC
48 V - 50 Hz
110/130, 220/240, 380/440 V - 50/60 Hz
24-250 V
500 VA
500 W
800 ms
48 V - 50 Hz
110/130, 220/240, 380/440 V - 50/60 Hz
24-250 V
500 VA
500 W
800 ms
b
b
1 OF + 1 SDE
b
b
1 OF + 1 SDE
b
b
b
b
b
b
b
b
b
OF + SD (+ SDV)
b
b
b
b
b
b
3 OF + SD (+ SDV)
b
b
b
b
b
b
Interlocking
Mechanical (see page A-10)
Electrical
by diagram (without IVE)
with IVE unit
auxiliary contacts used by circuit breaker
long time
short time
instantaneous
by Vigi module
by control unit
by add-on Vigirex relay
Current measurements
Voltage, frequency, power measurements, etc.
Source-changeover controller
With permanent replacement source
With standby generator set
b BA controller
b UA controller
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
A-12
313E.indb 12
14/11/2011 11:44:39
General characteristics
Compact NS, Masterpact NT/NW
Compact NS
Masterpact
NS630b to NS1600
N/H/L
NA
all devices
NS630b to 1600
N/H/L/NA
fixed or plug-in
NT06 to 16
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
(fixed, drawout or fixed + drawout)
N1/H1/H2/H3/L1/NA/HA/HF
NW08 to 63
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
(fixed, drawout or fixed + drawout)
N1/H1/H2/H3/L1/NA/HA/HF
250 to 1600 A
750
600 to 1600 A
1000
b
3, 4
800 to 6300 A
1000
b
24-250 V
180 VA
180 W
800 ms
48 to 415 V - 50/60 Hz
440 V - 60 Hz
24-250 V
180 VA
180 W
800 ms
24-250 V
180 VA
180 W
800 ms
b
b
1 OF + 1 CE (+ SDE)
b
only with UA or BA
1 OF + 1 CE + 1 PF
b
only with UA or BA
1 OF + 1 CE + 1 PF
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
2 OF + SD
b
b
2 OF + SD
b
b
b
b
b
b
2 OF + SD
b
b
b
b
b
b
b BA controller
b UA controller
b
b
b
b
b
b
b
b
b
b
b (vertical or horizontal)
b (drawout)
b (vertical or horizontal)
b (drawout)
b (vertical or horizontal)
b (drawout)
b
b
b
b
b
b
b
b
b
b
b
A-13
313E.indb 13
14/11/2011 11:44:39
Remote-operated
source-changeover systems
Functions
and characteristics
Durability (category A)
(ON-CR-OR-CN cycles)
Number of poles
Conventional thermal current (A)
Rated operational current (A)
Durability (category A)
(ON-CR-OR-CN cycles)
lth at 60 C
Ie Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V
lth
Ie
at 60 C
Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V
3, 4
100
AC22A
100
100
15000
AC22A
1500
1500
AC23A
100
100
AC23A
1500
1500
3, 4
160
AC22A
160
160
15000
AC22A
1500
1500
AC23A
160
160
AC23A
1500
1500
3, 4
200
AC22A
200
200
15000
AC22A
1500
1500
AC23A
200
200
AC23A
1500
1500
INS250
3, 4
250
AC22A
250
250
15000
AC22A
1500
1500
INS320
INS400
INS500
INS630
3, 4
320
AC22A
320
320
10000
AC22A
1500
1500
3, 4
400
AC22A
400
400
10000
AC22A
1500
1500
3, 4
500
AC22A
500
500
10000
AC22A
1500
1500
3, 4
630
AC22A
630
630
10000
AC22A
1500
1500
AC23A
320
320
AC23A
1500
1500
AC23A
400
400
AC23A
1500
1500
AC23A
500
500
AC23A
1500
1500
AC23A
250
250
AC23A
1500
1500
AC23A
630
630
AC23A
1500
1500
3, 4
100 to 250
20000 - 40000 50000
3, 4
400 to 630
15000
3, 4
630 to 1600
8000
4000 - 6000
2000
2000 - 3000
1500
3, 4
630 to
1600
8000
3, 4
1250 to
1600
8000
3, 4
800 to
1600
10000
3, 4
2000
10000
3, 4
2500 to
4000
10000
3, 4
5000 to
6300
5000
6000
10000
8000
5000
1500
Electrical durability at In 6000
NT16:
(ON-CR-OR-CN cycles)
for y 440 V and 480 V
3000
NEMA (2)
Electrical durability at In 3000
2000
10000
6000
2500
1500
(ON-CR-OR-CN cycles)
NT16:
(2)
for U = 500 V to 690 V
1000
(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.
(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.
Note:
ON: opening of Normal source
CR: closing of Replacement source
OR: opening of Replacement source
CN: closing of Normal source
A-14
313E2200.indd 14
15/11/2011 14:29:23
The coupling accessory can be fitted with the same connection and insulation
accessories as the circuit breakers and switch-disconnectors.
Possible uses
Downstream coupling
Possible
Outgoing pitch
(mm)
b
b
b
b
b
b
35
35
35
52.5
52.5
52.5
b
b
35
52.5
b
b
35
52.5
1
2
3
4
A-15
313E.indb 15
14/11/2011 11:44:40
Functions
and characteristics
Remote-operated
source-changeover systems
Electrical interlocking
DB101573
IVE unit.
Necessary equipment
For Compact NSX100 to 630, each circuit breaker must be equipped with:
b a motor mechanism
b an OF contact
b an SDE contact.
The components are supplied ready for assembly and the circuit breakers prewired.
The prewiring must not be modified.
For Compact NS630b to 1600, each circuit breaker must be equipped with:
b a motor mechanism
b an available OF contact
b a CE connected-position contact (carriage switch) on withdrawable circuit breakers
b an SDE contact.
For Masterpact NT and NW, each circuit breaker must be equipped with:
b a remote-operation system made up of:
v MCH gear motor
v MX or MN opening release
v XF closing release
v PF ready to close contact
b an available OF contact
b one to three CE connected-position contacts (carriage switches) on drawout
circuit breakers (depending on the installation).
A-16
313E.indb 16
14/11/2011 11:44:40
Standard configurations
Compact NS, Masterpact NT and NW
Types of mechanical interlocking
Diagram no.
QN
0
1
0
51201177
51201178
DB101574
2 devices
QR
0
0
1
51201179
51201180
51201181
51201182
51201183
51201184
51201185
51201186
51201187
51201139
51201140
51201141
51201142
51201143
51201144
51156226
51156227
51156904
51156905
51156903
Masterpact NW only
Types of mechanical interlocking
Diagram no.
DB101576
DB101575
QN1
0
1
0
QN2
0
1
0
QR
0
0
1
b electrical interlocking:
v without lockout after fault
v with lockout after fault
51156906
51156907
51156908
51156909
b electrical interlocking:
v without lockout after fault
v with lockout after fault
51156910
51156911
QS1
0
1
0
0
QS2
0
0
1
0
QS3
0
0
0
1
DB101578
51156912
51156913
51156914
A-17
313E.indb 17
14/11/2011 11:44:41
Functions
and characteristics
Associated controllers
Controller selection
Controller
BA
UA
4-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources off)
b
b
b
b
b
b
b
b
b
b
b
b
b
Automatic operation
Monitoring of the Normal source and automatic transfer
Generator set startup control
Delayed shutdown (adjustable) of generator set
Load shedding and reconnection of non-priority circuits
Transfer to the Replacement source if one of the phases
of the Normal phase is absent
Test
By opening the P25M circuit breaker supplying the controller
By pressing the test button on the front of the controller
b
b
DB403809
Indications
Circuit breaker status indication on the front of the controller:
on, off, fault trip
Automatic mode indicating contact
Other functions
BA controller.
b
b
b
b
Options
Communication option
DB403810
Power supply
Control voltages (2)
110 V
220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz
and 440 V 60 Hz
b
b
b
b
b
b
b
b
b
Operating thresholds
Undervoltage
Phase failure
Voltage presence
UA controller.
Front
Side
Connectors
Front
IP40
IP30
IP20
IK07
b
b
b
b
b
b
b
b
b
b
b
AC
DC
Utilisation category (IEC 947-5-1)
AC12 AC13 AC14 AC15 DC12 DC13
8
7
5
5
8
2
Operational current (A)
24 V
48 V
8
7
5
5
2
8
6
4
4
0.6
110 V
8
6
4
3
220/240 V
0.4
250 V
5
380/415 V
440 V
4
660/690 V
(1) For example, 220 V single-phase or 220 V three-phase.
(2) The controller is powered by the ACP control plate. The same voltage must be used for the ACP
plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the same as
the source voltage, then the Normal and Replacement sources can be used directly for the
power supply. If not, an isolation transformer must be used.
A-18
313E.indb 18
14/11/2011 11:44:41
Controller installation
PB100857_SE
DB126269
DB126270
A-19
313E.indb 19
14/11/2011 11:44:42
Functions
and characteristics
Associated controllers
The BA controller is used to create simple sourcechangeover systems that switch from one source to
another depending on the presence of voltage UN on
the Normal source.
It is generally used to manage two permanent sources
and can control Compact NS, Compact NSX and
Masterpact NT/NW circuit breakers and switchdisconnectors.
Operating modes
BA controller
DB403841
Test
DB403838
BA Controller
A-20
313E.indb 20
14/11/2011 11:44:42
BA controller
operating sequences
Switch set to the N position (forced
operation on the Normal source)
DB126548
DB126547
DB126550
DB126549
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
WAITING The system exits this mode when the operating mode is modified or
when an external event occurs (e.g. failure or return of UN).
1
1 The number sends to the indicated step when
A-21
313E.indb 21
14/11/2011 11:44:43
Associated controllers
The UA controller is used to create a sourcechangeover system integrating the following automatic
functions:
b transfer from one source to another depending on
the presence of voltage UN on the Normal source
b startup of an engine generator set
b shedding and reconnection of non-priority circuits
b transfer to the Replacement source if one of the
phases on the Normal source fails.
The UA controller can control Compact NS,
Compact NSX and Masterpact NT/NW devices.
Operating modes
DB403842
Functions
and characteristics
UA controller
DB403837
Distribution-system settings
UA Controller
Test
A pushbutton on the front of the controller may be used to test transfer from the
Normal source to the Replacement source, then the return to the Normal source.
The test lasts approximately three minutes.
Using the internal bus protocol, this option may be used to remote the following
information:
b circuit breaker status (ON, OFF, fault trip)
b presence of the Normal and Replacement voltages
b presence of an order for forced operation (e.g. special tariffs)
b settings and configuration information
b status of non-priority circuits (loads shed or not)
b position of the switch (stop, auto, forced operation on the Normal source, forced
operation on the Replacement source).
A-22
313E.indb 22
14/11/2011 11:44:44
UA controller
Operating sequences
Forced operation mode
Switch set to the N position (forced operation on
the Normal source)
DB126552
DB126551
DB126553
A-23
313E.indb 23
14/11/2011 11:44:45
Functions
and characteristics
Associated controllers
UA controller
Operating sequences
Special-tariff mode
DB126554
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1
A-24
313E.indb 24
14/11/2011 11:44:45
UA controller
Operating sequences
Test mode and automatic operation
DB126555
Switch set to the Auto position (automatic operation and test mode).
A-25
313E.indb 25
14/11/2011 11:44:45
Functions
and characteristics
Operating sequences
IVE unit
DB126594
IVE unit
Symbols
QN : Normal Compact circuit breaker equipped
for remote operation (motor mechanism)
QR : Replacement Compact circuit breaker
equipped for remote operation (motor
mechanism)
ON : Circuit breaker QN opening order
OR : Circuit breaker QR opening order
IN : Circuit breaker QN closing order
IR : Circuit breaker QR closing order
L1 : Faulty Normal indication LED
L2 : Faulty Replacement indication LED
Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.
Note:
Following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on
the front of the motor mechanism is required.
A-26
313E.indb 26
14/11/2011 11:44:46
BA/UA controller
DB126595
BA controller
Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
QN : Normal source circuit breaker
QR : Replacement source circuit breaker
DB126599
UA controller
Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
KG : order to the genset
SH : load-shedding order
QN : Normal source circuit breaker
QR : Replacement source circuit breaker
Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.
Important
If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.
If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is
carried out later when KR status becomes I.
A-27
313E.indb 27
14/11/2011 11:44:46
Functions
and characteristics
DB404157
Electrical-installation management
Communication
interface
RS 232, Ethernet
RS 485
Communication bus
ON / OFF
Fault trip
Connected / disconnected position
BBus
error
JBus
com.
com.
OK
error
24V
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
7
9
13
N1
N2
b
b
b
N
DC150
DC150 data
concentrator
ON / OFF
Fault trip
Connected / disconnected position
b
b
b
b
b
IVE
Masterpact
Masterpact
Modbus
Measurement
Current
A
E
P
H
Voltages, power...
E
P
H
Frequency
P
H
Power quality: fundamental, harmonics
H
Programming of demand metering
E
P
H
Fault readings
Type of fault
A
E
P
H
Interrupted current
P
H
Waveform capture
On faults
H
On demand or programmed
H
Histories and logs
Trip history
E
P
H
Alarm history
P
H
Event logs
P
H
Indicators
Counter operation
A
E
P
H
Contact wear
P
H
Maintenance register
P
H
Note:
see the description of the Micrologic control units for further details on protection and alarms,
measurements, waveform capture, histories, logs and maintenance indicators.
A-28
313E.indb 28
14/11/2011 11:44:48
Controller
UA150
Status indications
Normal source
ON / OFF
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Replacement source
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Status of R voltage contact
Controller
Automatic mode
Normal mode
Replacement mode
Stop mode
Testing
Replacement engine generator set
Genset failure
Genset OFF
Genset ON
Shedding of non-priority circuits
Reconnection of non-priority circuits
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
Settings
Time delay t1 for validation of UN absence
b
b
b
b
b
b
Main characteristics
N
DC150
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
b Power supply:
110 V AC to 240 V AC
115 V DC to 125 V DC.
b Weight: 1.5 kg.
b Installation: on panel with the DC150 box which must be earthed on metal
part of the installation.
b Over dimensions H x W x D (mm): 138.5 x 100 x 192.8.
7
9
N1
N2
13
A-29
313E.indb 29
14/11/2011 11:44:49
TOOLS
schneider-electric.com
This international site allows you
to access all the Schneider Electric
Solution and Product information
via :
p comprehensive descriptions
p range data sheets
p a download area
p product selectors
p ..
You can also access the information
dedicated to your business and get
in touch with your Schneider Electric
country support.
313E.indb 2
14/11/2011 11:44:50
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Interpact, Masterpact
Dimensions
Presentation
Functions and characteristics
2
A-1
B-2
B-2
B-3
B-5
B-6
B-7
B-9
B-9
B-13
B-15
B-20
Electrical diagrams
Catalogue numbers and order forms
C-1
D-1
B-1
313E.indb 1
14/11/2011 11:44:50
Manual source-changeover
systems
Dimensions
DB126609
Front-panel cutout
DB126608
DB126607
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
A
325
416
B
90
115
C
87.5
100
D
175
200
F
156
210
G
133
157
H
9.25
5
J
9
24.6
K
295
386
L
75.5
100
M
150
175
N
75
74.5
P
155
179
DB101611
Front-panel cutout
DB101610
DB101609
Dimensions
Dimensions (mm)
Type
A
B
C
INS/INV250 - 100/160/200/250 325
90
87.5
INS/INV320/400/500/630
416
115
100
Note: X and Y are the symmetry planes for a 3-pole device.
D
175
200
F
156
210
G
106
130
H
17.5
22.5
K
295
386
L
75.5
100
M
150
175
N
75
74.5
P
131
160.4
B-2
313E.indb 2
14/11/2011 11:44:51
DB126611
Front-panel cutout
DB126608
DB126610
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
A
325
416
B
90
115
C
87.5
100
D
175
200
F
156
210
G min
171
195
G max
600
600
H
9.25
5
J
9
24.6
P
25.5
30.8
Q
25.5
30.8
DB107756
Front-panel cutout
DB101615
DB101614
Dimensions
Dimensions (mm)
Type
INS40/63/80
INS100/125/160
INS/INV250 - 100/160/200/250
INS320/400/500/630
A
325
325
325
416
B
90
90
90
115
C
87.5
87.5
87.5
100
D
175
175
175
200
F
156
156
156
210
G min
155
200
185
204
G max
396
441
600
600
H
0
0
17.5
22.5
P
25.5
25.5
25.5
30.8
Q
25.5
25.5
25.5
30.8
B-3
313E.indb 3
14/11/2011 11:44:52
Manual source-changeover
systems
Dimensions
DB101618
DB101617
Dimensions
DB101619
Front-panel cutout
Dimensions (mm)
Type
NS630b/800/1000/1200/1600
A
411
B
63.5
C
98
D
175
F
280
G min
218
G max
605
H
25
J
24
P
25.5
Q
25.5
R
64
B-4
313E.indb 4
14/11/2011 11:44:52
Interlocking of toggles
Compact NSX100 to 630
4 poles
4 poles on left
DB101624
3 poles on left
DB101623
Front-panel cutout
DB126614
3 poles
DB126613
DB126612
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
C2
54
92.5
C3
108
182
L
52.5
70
L16
140
185
L17
245
325
L18
280
370
R2
54
71.5
R18
89
116.5
R19
140
185
P5
83
107
P
120
150
B-5
313E.indb 5
14/11/2011 11:44:53
Manual source-changeover
systems
Dimensions
DB101625
Dimensions
DB101627
Front-panel cutout
Dimensions (mm)
Type
INS250 - 100/160/200/250
INS320/400/500/630
A
60.4
82.5
B
130.4
175
C
296
395
D
68
102.5
E
136
205
F
131
155
G
61.8
87
H
279.3
383.7
I
42
64
J
84
128
K
156
210
L
186.5
213
M
5.5
8
N
50
50
DB101651
DB101650
Dimensions (mm)
DB107743
Type
A
INS250 - 100/160/200/250 60.4
INS320/400/500/630
82.5
B
130.4
175
C
295
395
E
136
205
K
156
210
L
138.5
162.5
M
631
658
N
50
75
Dimensions (mm)
Type
P
INS250 - 100/160/200/250 100
INS320/400/500/630
150
Mmax Mmin
567.5 195
593
220.5
Q
64
64
B-6
313E.indb 6
14/11/2011 11:44:54
DB126616
DB126615
Dimensions
Connection
DB101630
DB101631
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
G2
118
165.9
G3
181.5
265.7
G28
238
339.5
G29
96
143.5
G30
140
188.5
G52
156
227.5
K1
35
45
K2
35
52.5
K3
51
75
K4
156
210
K8
70
113.5
K9
170
250.7
K16
8
3.75
L28
320
420
L29
99.5
127.5
L30
300
400
L31
89.5
117.5
L32
1
11.2
L33
123
187.5
L34
139.5
-
L35
74.5
96.5
L36
19.5
26
L37
87.5
115
L39
9.5
22.5
L40
140
210
T
6
6
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.
B-7
313E.indb 7
14/11/2011 11:44:55
Manual source-changeover
systems
Dimensions
DB101633
DB101632
Dimensions
DB101902
Connection
DB101901
Dimensions
Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630
G2
105.5
141
G3
169
240.7
G28
225.5
315
G29
83.5
119
G30
127.5
163.5
G52
143.5
202.5
K1
35
45
K2
35
52.5
K3
51
75
K4
156
210
K8
57.5
88.5
K9
157.5
225.7
K16
25.5
26.25
L28
320
420
L29
82
105
L30
300
400
L31
72
95
L32
16.5
11.2
L33
123
187.5
L34
139.5
-
L35
74.5
98.5
L36
21.5
26
L37
70
92.5
L39
8.5
0
L40
140
210
T
6
6
Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630
B-8
313E.indb 8
14/11/2011 11:44:56
Remote-operated
source-changeover systems
Interlocking on a base plate
Compact NSX100 to 250
DB126619
Withdrawable device
DB126618
Fixed device
DB126617
Dimensions, 3 or 4 poles
DB101638
Horizontal mounting
DB101637
Vertical mounting
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
G50
137.5
180
G51
285
360
H20
62.5
100
H21
97
152
H22
45.5
83
H23
73
123
H42
60
60
H43
120
120
H44
144.5
189
H45
300
378
H46
37
77
K25
156
210
K35
210.5
282.5
L31
110.5
150.5
L32
354
466
P7
25
25
P8
45
45
P9
75
100
P32
182
256
P33
143
215
P50
25
25
P52
99.5
123
P54
21
21
T9
9
9
T10
6
6
U
y 32
y 32
K36
300
400
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.
B-9
313E.indb 9
14/11/2011 11:44:57
Remote-operated
source-changeover systems
Dimensions
DB126620
DB126621
Dimensions, 3 or 4 poles
DB126622
Withdrawable device
Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX
circuit breakers.
Horizontal mounting
DB101638
DB101637
Dimensions
Vertical mounting
B-10
313E.indb 10
14/11/2011 11:44:58
Front-panel cutout
DB404134
DB126626
95
95
47.5
47.5
77
29.5
NSX100
to
NSX250
156
NSX100
to
NSX250
145
177
DB404135
Front-panel cutout
DB126625
Dimensions
127
127
63.5
63.5
127
42
NSX400
to
NSX630
210
NSX400
to
NSX630
217
249
B-11
313E.indb 11
14/11/2011 11:44:59
Remote-operated
source-changeover systems
Dimensions
NSX400 to NSX630 as the Normal device, NSX100 to NSX250 as the Replacement device
Front-panel cutout
DB404136
DB126623
Dimensions
NSX400
to
NSX630
NSX100
to
NSX250
B-12
313E.indb 12
14/11/2011 11:44:59
DB107747
Fixed devices
DB101656
Fixed devices
B-13
313E.indb 13
14/11/2011 11:45:00
Dimensions
Remote-operated
source-changeover systems
Interlocking using connecting rods
DB107748
Fixed devices
B-14
313E.indb 14
14/11/2011 11:45:00
DB101661
Fixed devices
DB101663
DB101662
Fixed devices
DB101664
Fixed devices
B-15
313E.indb 15
14/11/2011 11:45:01
Dimensions
Remote-operated
source-changeover systems
Interlocking using cables
DB101666
Fixed devices
DB101668
Fixed devices
DB101669
Drawout devices
B-16
313E.indb 16
14/11/2011 11:45:02
DB107750
DB101671
Fixed devices
DB101672
Fixed devices
B-17
313E.indb 17
14/11/2011 11:45:02
Dimensions
Remote-operated
source-changeover systems
Interlocking using cables
DB107751
Fixed devices
DB107753
Fixed devices
B-18
313E.indb 18
14/11/2011 11:45:03
DB107754
Fixed devices
B-19
313E.indb 19
14/11/2011 11:45:05
Remote-operated
source-changeover systems
Dimensions
DB101678
DB101680
DB101681
DB101683
DB101679
IVE unit
B-20
313E.indb 20
14/11/2011 11:45:05
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Interpact, Masterpact
Electrical diagrams
Presentation
Functions and characteristics
Dimensions
2
A-1
B-1
C-2
C-2
C-3
C-6
C-14
C-24
C-33
C-35
C-36
D-1
C-1
313E.indb 1
14/11/2011 11:45:06
Electrical diagrams
Remote-operated
source-changeover systems
DB401804
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order
FR Replacement source closing order
L1 Normal source fault-trip signal
L2 Replacement source fault-trip signal
N Normal source auxiliary wiring connector
R Replacement source auxiliary wiring connector
Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.
C-2
313E.indb 2
14/11/2011 11:45:06
DB401805
DB101660
Automatic reset
Legends
QN Normal source Compact NSX equipped with motor mechanism
QR Replacement source Compact NSX equipped with motor
mechanism
SDE fault-trip indication contact
IVE electrical interlocking and terminal block unit
MT motor mechanism
OF2 breaker ON/OFF indication contact
RN reset order for breaker QN
RR reset order for breaker QR
C-3
313E.indb 3
14/11/2011 11:45:07
Electrical diagrams
Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201178
DB401806
Automatic reset
Legends
QN Normal source Compact NSX equipped with
motormechanism
QR Replacement source Compact NSX equipped with motor
mechanism
MN undervoltage release
OF2 breaker ON/OFF indication contact
SDE fault-trip indication contact
MT motor mechanism
IVE electrical interlocking and terminal block unit
BP emergency off button with latching
KA3 auxiliary relay
F1 auxiliary power supply circuit breaker
C-4
313E.indb 4
14/11/2011 11:45:07
DB401807
Automatic reset
C-5
313E.indb 5
14/11/2011 11:45:08
Electrical diagrams
Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201180
DB404153
Electrical interlocking
ATTENTION
Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MT...).
C-6
313E.indb 6
14/11/2011 11:45:08
DB404154
ATTENTION
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
MX shunt release
BP
emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
C-7
313E.indb 7
14/11/2011 11:45:08
Remote-operated
source-changeover systems
Electrical diagrams
DB404155
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
MN undervoltage release
BP
emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-8
313E.indb 8
14/11/2011 11:45:09
DB401811
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
ON Normal source opening order
OR Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-9
313E.indb 9
14/11/2011 11:45:09
Remote-operated
source-changeover systems
Electrical diagrams
DB401812
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MX shunt release
BP
emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
BK
VT
YE
red
green
black
violet
yellow grey
GY
WH
BN
white
brown
C-10
313E.indb 10
14/11/2011 11:45:10
DB401813
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MN undervoltage release
BP
emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-11
313E.indb 11
14/11/2011 11:45:10
Electrical diagrams
Remote-operated
source-changeover systems
DB401814
ATTENTION
Legends
QN Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KM1 contactors with 0.25 second delay (for transfer
to Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal
source)
MT
Motor Mechanism
C-12
313E.indb 12
14/11/2011 11:45:11
DB404156
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer
to Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal
source)
MT
Motor Mechanism
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-13
313E.indb 13
14/11/2011 11:45:11
Electrical diagrams
Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201139
DB401816
ATTENTION
Legends
Normal source Masterpact NT or NW
QN
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
ON
Normal source opening order
OR
Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
C-14
313E.indb 14
14/11/2011 11:45:11
2 Masterpact NT or NW devices
Diagram no. 51201140
DB401817
Electrical interlocking with lockout after a fault and emergency off by shunt release
ATTENTION
Legends
KA3 time delay for genset startup order to avoid starting
the genset for transient UN disturbances
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
MX2 shunt release
BP
emergency off button with latching
ON
Normal source opening order
OR
Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
BP
emergency off button with latching
C-15
313E.indb 15
14/11/2011 11:45:12
Electrical diagrams
Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201141
DB401819
Electrical interlocking with lockout after a fault and emergency off by undervoltage release
ATTENTION
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
KA3 auxiliary relay
Normal source opening order
ON
OR
Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
C-16
313E.indb 16
14/11/2011 11:45:13
2 Masterpact NT or NW devices
Diagram no. 51201142
DB401820
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.
(4) See section IMPORTANT here after.
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
ON
Normal source opening order
OR
Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-17
313E.indb 17
14/11/2011 11:45:13
Remote-operated
source-changeover systems
Electrical diagrams
0=
2 Masterpact NT or NW devices
Diagram no. 51201143
DB401821
Electrical interlocking by IVE unit with lockout after a fault and emergency off by shunt release
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.
(4) See section IMPORTANT here after.
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
KA3 auxiliary relay
Normal source opening order
ON
OR
Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-18
313E.indb 18
14/11/2011 11:45:14
2 Masterpact NT or NW devices
Diagram no. 51201144
DB401822
Electrical interlocking by IVE unit with lockout after a fault and emergency off by undervoltage release
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.
(4) See section IMPORTANT here after.
IMPORTANT
The relays controlling the normal and replacement
circuit breakers must be mechanically and/or
electrically interlocked to prevent them from giving
simultaneous closing commands.
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
KA3 auxiliary relay
Normal source opening order
ON
OR
Replacement source opening order
FN
Normal source closing order (0.25 second delay)
FR
Replacement source closing order (0.25 second delay)
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-19
313E.indb 19
14/11/2011 11:45:14
Electrical diagrams
Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156226
DB401823
Automatic-control system without IVE unit for permanent replacement source with lockout after a fault
ATTENTION
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KM1 contactors with 0.25 second delay (for transfer to
Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal
source)
C-20
313E.indb 20
14/11/2011 11:45:15
2 Masterpact NT or NW devices
Diagram no. 51156227
DB401824
Automatic-control system for replacement source generator set with lockout after a fault
ATTENTION
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer to
Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal
source)
C-21
313E.indb 21
14/11/2011 11:45:15
Remote-operated
source-changeover systems
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51156904
DB401825
Automatic-control system for permanent replacement source with lockout after a fault (with MN)
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
F2
circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.
C-22
313E.indb 22
14/11/2011 11:45:16
2 Masterpact NT or NW devices
Diagram no. 51156905
DB401826
Automatic-control system for replacement source generator set with lockout after a fault (with MN)
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard closing voltage release
XF
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
F2
circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting
the genset for transient UN disturbances
KA3 auxiliary relay
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.
C-23
313E.indb 23
14/11/2011 11:45:17
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906
DB101734
2 normal sources and 1 replacement source: electrical interlocking without lockout after a fault
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE
connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2 to R
(QR closing time delay = 0.25 sec. minimum)
C-24
313E.indb 24
14/11/2011 11:45:17
3 Masterpact NW devices
Diagram no. 51156907
DB101766
2 normal sources and 1 replacement source: electrical interlocking with lockout after a fault
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
t1
order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2 to R
(QR closing time delay = 0.25 sec. minimumm)
C-25
313E.indb 25
14/11/2011 11:45:17
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908
DB101737
2 normal sources and 1 replacement source: automatic-control system for generator set without lockout
after a fault (with MN)
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
standard closing voltage release
XF
MN
undervoltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
C-26
313E.indb 26
14/11/2011 11:45:18
3 Masterpact NW devices
Diagram no. 51156909
DB101739
2 normal sources and 1 replacement source: automatic-control system for generator set with lockout after
a fault (with MN)
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
standard closing voltage release
XF
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relay
KA8 auxiliary relay
C-27
313E.indb 27
14/11/2011 11:45:18
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910
DB101741
3 sources with only 1 device closed: electrical interlocking without lockout after a fault
Legends
QS... Source Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3
(QS3 closing time delay = 0.25 sec. minimum)
C-28
313E.indb 28
14/11/2011 11:45:18
3 Masterpact NW devices
Diagram no. 51156911
DB101743
3 sources with only 1 device closed: electrical interlocking with lockout after a fault
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QS... Source Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3
(QS3 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays
C-29
313E.indb 29
14/11/2011 11:45:19
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912
DB101745
Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure
(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored
(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum)
C-30
313E.indb 30
14/11/2011 11:45:19
3 Masterpact NW devices
Diagram no. 51156913
DB101747
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure
(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored
(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays
C-31
313E.indb 31
14/11/2011 11:45:19
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914
DB101749
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relays with 10 to 180 sec. time delay
KA2 auxiliary relays with 0.1 to 30 sec. time delay
KA3 auxiliary relays with 10 to 180 sec. time delay
KA4 auxiliary relays with 0.1 to 30 sec. time delay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relays with 0.25 sec. time delay
C-32
313E.indb 32
14/11/2011 11:45:20
Source-changeover systems
with automatic controllers
DB101753
DB101751
Coupling
DB101755
Transfer conditions
Legends
Q1
circuit breaker supplying and protecting the automatic
control circuits for the Normal source
Q2
circuit breaker supplying and protecting the automatic
control circuits for the Replacement source
ACP control plate
BA
automatic controller
electrical interlocking and terminal block unit
IVE
Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.
C-33
313E.indb 33
14/11/2011 11:45:20
Electrical diagrams
Source-changeover systems
withautomaticcontrollers
DB101758
DB101757
DB101759
Transfer conditions
DB101761
Legends
Q1
circuit breaker supplying and protecting the automatic
control circuits for the Normal source
Q2
circuit breaker supplying and protecting the automatic
control circuits for the Replacement source
ACP control plate
automatic controller
UA
electrical interlocking and terminal block unit
IVE
Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.
C-34
313E.indb 34
14/11/2011 11:45:21
Controller settings
Using communication functions
DB101763
DB101762
Controller settings
C-35
313E.indb 35
14/11/2011 11:45:21
Source-changeover systems
withautomaticcontrollers
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51156903
DB401827
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard opening voltage release
MX
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.
C-36
313E.indb 36
14/11/2011 11:45:22
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Interpact, Masterpact
Catalogue numbers
and order forms
Presentation
Functions and characteristics
Dimensions
Electrical diagrams
2
A-1
B-1
C-1
D-2
D-2
D-3
D-5
D-7
D-8
D-8
D-10
D-10
D-12
D-14
D-16
D-18
D-18
D-1
313E.indb 1
14/11/2011 11:45:22
Catalogue numbers
and order forms
Source-changeover systems
for2devices
Interpact INS40 to INS2500
and INV100 to INV2500
DB404077
DB107710
5...8
31073
31074
DB107711
DB404078
3P
With Interpact INS250-100A
31140
With Interpact INS250-160A
31144
31142
With Interpact INS250-200A
31146
With Interpact INS250
31148
With Interpact INS320
With Interpact INS400
31150
With Interpact INS500
31152
With Interpact INS630
31154
Locking for INS complete source changeover assembly
Handle locking by 1 to 3 padlocks (in OFF position)
By keylock
Keylocking device
+ Ronis 1351B.500 keylock
or + Profalux KS5 B24 D4Z keylock
4P
31141
31145
31143
31147
31149
31151
31153
31155
Built in
31097
41940
42888
DB404079
Rotary handle
Extended front control for complete source changeover assembly
31055
Manual source-changeover systems Interpact INS250 to INS2500 and INV250 to INV2500 by keylock
DB404080
DB101549
Interlocking
Locking device for Ronis/Profalux keylocks
on INS250-100 to INS250/INV100 to INV250
Locking device for Ronis/Profalux keylocks
on INS/INV320 to INS/INV630
2x
3/4P
31087
2x
31088
2x
31291
41950
42878
Connection accessories
Downstream coupling accessories
INS250 (1 pair)
INS320 to INS630 (1 pair)
3P
29322
32563
4P
29322
32563
Normal source /
replacement source
INS250
INS320 to INS630
29358
32619
29359
32620
INS250 (1 pair)
INS320 to INS630 (1 pair)
29324
32583
29324
32583
DB403921
DB404082
DB101062
D-2
313E.indb 2
14/11/2011 11:45:25
DB404084
DB404083
Mechanical interlocking
For toggle controlled circuit breakers
NSX100...250
NSX400...630
29354
32614
NSX100...250
NSX400...630
29369
32621
41950
42878
24 to 250 V DC
48 to 415 V AC 50/60 Hz
440 V 60 Hz
29351
29349
29356
4 x 29450
29365
29350
29349
29352
4 x 29450
29365
(2)
(2)
(2)
(2)
32611
32609
29356
4 x 29450
29365
(2)
(2)
(2)
1 x 32618
32610
32609
29352
4 x 29450
29365
(2)
1 x 32618
110/127 V AC 50/60 Hz
GERIN
MERLIN
multi
GERIN
MERLIN
multi
0 . OFF
220/240 V AC 50/60 Hz
0 . OFF
P25M
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
29470
29363
29376
29472
29363
29378
29474
29363
29379
380/415 V AC 50/60 Hz
440 V 60 Hz
29471
29364
29377
29473
29364
29380
29475
29364
29381
29368
29368
Communication module
DB403922
50823
N
DC150
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
N1
7
9
N2
13
(1) The supply voltages BA/UA controller, ACP plate, IVE unit and the remote control must be identical whatever the source changeover type.
(2) See products pages.
D-3
313E.indb 3
14/11/2011 11:45:27
Catalogue numbers
andorderforms
Source-changeover systems
for 2 devices
Compact NSX100 to NS630 (cont.)
Connection accessories
Downstream coupling accessories
NSX100...250/NSX100...250
NSX400...630/NSX400...630
Source normal/source
replacement
NSX100...250/ 250 A
NSX100...250
NSX400...630/ 630 A
NSX400...630
DB404802
DB101062
DB403921
3P
29321
32562
4P
29322
32563
29358
29359
32619
32620
NSX100...250/NSX100...250
NSX400...630/NSX400...630
29324
32565
DB404089
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
0 . OFF
D-4
313E.indb 4
14/11/2011 11:45:28
33890
DB404090
33910
33913
FFO
hsu p
NO h
FFO
sup
O
degr
ahcs
i
F FO
hsup
NO h
sup
FFO
O
degr
ahcs
i
FFO
hsup
NO h
FFO
33911
33914
33915
sup
O
degr
ah
csid
F FO
hsup
NO h
sup
FFO
O
degr
ah
csid
D-5
313E6100.indd 5
14/11/2011 11:48:53
Catalogue numbers
andorderforms
Source-changeover systems
for2devices
48/415 V AC 50/60 Hz
440 V 60 Hz
DB404093
For 2 devices
Wiring kit for connection of 2 fixed/withdrawable devices to the IVE unit
DB404087
GERIN
MERLIN
multi
110/127 V AC 50/60 Hz
ACP + controller BA (1)
Plate ACP
Controller BA
29448
ACP + controller UA (1)
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
29352
54655
220/240 V AC 50/60 Hz
380/415 V AC 50/60 Hz
440 V 60 Hz
29470
29363
29376
29472
29363
29378
29474
29363
29379
29471
29364
29377
29473
29364
29380
29475
29364
29381
Communication module
DB403922
50823
N
DC150
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
N1
7
9
N2
13
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
D-6
313E.indb 6
14/11/2011 11:45:30
33912
33913
33200
33201
33209
Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.
DB404093
for 2 devices
wiring kit for connection of 2 fixed/drawout devices to the IVE unit
DB404087
48/415 V AC 50/60 Hz
440 V 60 Hz
GERIN
MERLIN
multi
110/127 V AC 50/60 Hz
ACP + controller BA (1)
Plate ACP
Controller BA
29448
ACP + controller UA (1)
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
29352
54655
220/240 V AC 50/60 Hz
380/415 V AC 50/60 Hz
440 V 60 Hz
29470
29363
29376
29472
29363
29378
29474
29363
29379
29471
29364
29377
29473
29364
29380
29475
29364
29381
Communication module
DB403922
50823
N
DC150
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
N1
7
9
N2
13
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type
of source-changeover system.
D-7
313E.indb 7
14/11/2011 11:45:31
Catalogue numbers
andorderforms
Source-changeover systems
for2or 3devices
Masterpact NW circuit breakers
andswitch-disconnectors
48612
48612
47926
47926
33209
DB404093
for 2 devices
wiring kit for connection of 2 fixed/drawout devices to the IVE unit
DB404087
48/415 V AC 50/60 Hz
440 V 60 Hz
110/127 V AC 50/60 Hz
29352
54655
220/240 V AC 50/60 Hz
380/415 V AC 50/60 Hz
440 V 60 Hz
MERLIN
multi
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
D-8
313E6100.indd 8
15/11/2011 14:47:50
Communication module
DB403922
50823
N
DC150
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
N1
7
9
N2
13
48610
48609
48608
D-9
313E6100.indd 9
15/11/2011 14:47:51
Catalogue numbers
and order forms
Source-changeover systems
for2devices
Interpact INS40 to INS630
Switch-disconnectors
INS250
INS320/400/500/630
INS250
INS320/400/500/630
INS250-160 A
INS250-200 A
INS250-250 A
INS320
INS400
INS500
INS630
D-10
313E.indb 10
14/11/2011 11:45:33
For INS250
Rating
100 A
150 A
250 A
Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Switch-disconnector
Interpact type
For INS250
Rating
400 A
600 A
INS40/63/80
INS100/125/160
INS250
INS320/400/500/630
A
3 or 4
Rating
Number of poles
For INS320/630
4P current-transformer
module
Auxiliary contact
Connections
100 A
For INS320/630
Rating
For INS40/160
1OF/CAF/CAO
For INS250/630
1 OF/CAM
150 A
250 A
400 A
600 A
Standard
Low level
Standard
Low level
Rotary handles
Rear connection
INS40/80
connectors
INS100/160
connectors
INS250
2 short
2 long
Distribution 3x16v rigid/10v flexible
connectors
Snap-on y 95v
Distribution 4x25v rigid/16v flexible
Snap-on 1.5v to 95v (< 160 A)
Set of 10
INS40 to INS160
Black
INS250
Black
Black
INS320 to INS630
For complete changeover assembly
Installation accessories
Front-panel escutcheon
For switch-disconnectors
For ammeter module, IP40
Distribution
blocks
Distribloc
125 A
160 A
160 A
Multi-stage
125 A
250 A
Polybloc
160 A
630 A
Rt-angle extension Set of 3 or 4
250 A
Straight extension INS250
Edgewise ext.
INS630
Spreader
INS250 (45 mm)
Front alignment base
70 mm
INS320/630 52.5 mm
INS630
One-piece
INS250
For 95v cable
CU cable lugs
INS100/160
For 120v cable
supplied with
INS250
2 or 3 inter-phase
For 150v cable
barriers
For 185v cable
INS320/630
For 240v cable
For 300v cable
For 150v cable
AL cable lugs
INS250
supplied with
For 185v cable
2 or 3 inter-phase INS320/630
For 240v cable
barriers
For 300v cable
Terminal shrouds INS40/63/80
INS100/125/160
Terminal shields
INS40/63/80
INS100/125/160
Long
INS250
Short
Long
INS320/630
Short
Long for 52.5 mm spreaders
Interphase
INS100/160
Set of 6
Set of 6
barriers
INS250
INS320/630
Set of 6
D-11
313E.indb 11
14/11/2011 11:45:33
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact NSX100 to NSX630 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
(no. 51201177)
(no. 51201178)
(no. 51201179)
Automatic-control option
Power supply 220/240 V - 50/60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
D-12
313E.indb 12
14/11/2011 11:45:33
Plug-in
ME, MH, MB
NSX400/630
Front connections
Withdrawable
Voltage
4P option on 3P NSX
Extended
3P
3P
3P
3P
3P
SDE
SDE
AC
AC
AC
AC
AC
4P
4P
4P
4P
Standard
Low level
SDV
SDV
DC
DC
DC
DC
DC
V
V
V
V
V
Indication auxiliary
1 early-break switch
2 early-make switches
Locking
Toggle (1 to 3 padlocks) Removable
Fixed
Rotary handle
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Motor mechanism
Keylock adapter + keylock Ronis (special)
NSX100/250
Keylock adapter (keylock not included)
NSX400/630
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Interlocking
Mechanical
Toggle operated
Rotary Handle
By key (2 keylocks,
Locking kit without locks
1 key) for rotary handle Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Installation accessories
IP30 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP30 escutcheon (with access to toggle + trip unit)
IP30 escutcheon for Vigi module
IP40 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP40 escutcheon for Vigi module
IP40 escutcheon for Vigi or ammeter module
Toggle cover
Sealing accessories
DIN rail adapter
3P 60 mm busbar adapter
Plug-in / withdrawable configuration accessories
Auxiliary connections
1 automatic connector fixed part with 9 wires (for base)
1 automatic connector moving part with 9 wires (for circuit breaker)
1 sup. for 3 auto. conn. moving parts
1 sup. for 2 auto. conn.
9-wire manual auxiliary connector (fixed + moving)
Plug-in base
Long insulated terminals
Set of 2
accessories
2 IP4 shutters for base
Chassis accessories
Escutcheon collar
Toggle
Vigi
Locking kit (keylock not included)
2 carriage switches (conn./disconnected position indication)
Parts or plug-in
Plug-in base FC/RC
2P
3P
4P
Withdrawable kits
Set of two power connections
Standard
Vigi
Safety trip for advanced opening
For 3P/4P chassis
Moving part
Fixed part
Adaptateur pour socle (pour cache-bornes ou sparateurs de phases)
Communication
NSX Cord L = 0.35 m
NSX Cord L = 1.3 m
NSX Cord U > 480 V CA L = 0.35 m
NSX Cord L = 3 m
BSCM (NSX400/630)
Communicating motor mechanism 220-240V
Switchboard front display module FDM121
FDM mounting accessory
Modbus interface
Stacking accessory
ULP line termination
RJ45 connectors
Wire length RJ45 L = 0.3 m
Wire length RJ45 L = 0.6 m
female/female
Wire length RJ45 L = 1 m
Wire length RJ45 L = 2 m
Wire length RJ45 L = 3 m
Wire length RJ45 L = 5 m
D-13
313E.indb 13
14/11/2011 11:45:34
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact NS630b to NS1600 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
(no. 51201180)
(no. 51201181)
(no. 51201182)
(no. 51201183)
(no. 51201184)
(no. 51201185)
(no. 51201186)
(no. 51201187)
Automatic-control option
Power supply 110 V - 50/60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
D-14
313E.indb 14
14/11/2011 11:45:34
Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Compact type
Rating
Circuit breaker
Switch-disconnector
Number of poles
Device
Indication contacts
SD trip indication (maximum 1)
6 A-240 V AC
Low level
SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices)
6 A-240 V AC
Low level
OF ON/OFF indication contacts (maximum 3)
6 A-240 V AC
NS630b to NS1600
A
N, H, L
NA
3 or 4
Fixed
qty
CE - connected position
6 A-240 V AC
qty
CD - disconnected position
6 A-240 V AC
qty
CT - test position
6 A-240 V AC
Auxiliary terminals for chassis alone
3-wire terminal (30 parts)
Withdr. chassis
Withdr. without chassis
(moving part only)
Electrical operation
Voltage releases
Direct
Extended
Indication auxiliary
Communicating
AC
AC
AC
DC
DC
DC
Adjustable
V
V
V
Nonadjustable
Manual operation
Electrical operation
Manual operation
Electrical operation
Connections
Horizontal rear
connections
Top
Bottom
Top
Top
NS - FC fixed
Bottom
Bottom
NS - FC fixed
NS - FC fixed, withdr.
Cable-lug adapters
Arc chute screen
Interphase barriers
Spreaders
NS - FC fixed, withdr.
NS - FC fixed
NS - FC fixed, withdr.
NS - FC fixed, withdr.
VO - safety shutters on
chassis
NS - FC fixed
Black
Locking
Toggle (1 to 3 padlocks)
Rotary handle using
a keylock
Communication
Digipact
Standard
Power supply
MX
MN
MN delay unit
qty
Low level
qty
Low level
qty
Low level
Jumpers (set of 10)
6-wire terminal (10 parts)
5.0
2.0
5.0
6.0
7.0
V
AD - external power-supply module
TCE - external sensor (CT) for neutral protection
Rectangular sensor
280 x 115 mm
TCW - external sensor for SGR protection
LR - long-time rating plug Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
COM module
qty
Low level
Remote operation
qty
Removable system
OFF position
Ronis 1351B.500
Fixed system
ON and OFF positions
Profalux KS5 B24 D4Z
Profalux
Ronis
Ronis
Ronis
Profalux
Ronis
Kirk
Castell
1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis
Accessories
CDM - mechanical operation counter
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Mounting brackets for fixed NS
Test kits
D-15
313E.indb 15
14/11/2011 11:45:34
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
(no. 51201139)
(no. 51201140)
(no. 51201141)
(no. 51201142)
(no. 51201143)
(no. 51201144)
(no. 51156226)
(no. 51156227)
(no. 51156904)
(no. 51156905)
(no. 51156903)
Interlocking using connecting rods (NT/NW devices one above the other)
Select a complete set including two adaptation fixtures and the connecting rods
2 fixed NT devices
Complete set for:
2 drawout NT devices
2 drawout NW devices
2 fixed NW devices
1 fixed NT device + 1 fixed NW devices
1 drawout NT device + 1 drawout NW device
Interlocking using cables (NT/NW devices one above the other or side-by-side)
Select two adaptation fixtures (one for each device) and a set of two cables
Adaptation fixture for:
1 fixed NT device
(NT/NW fixed and drawout 1 drawout NT device
devices may be mixed)
1 fixed NW device
1 drawout NW device
1 set of 2 cables (for two devices)
qty
qty
qty
qty
Automatic-control option
Power supply 220/240 V - 50/60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
D-16
313E.indb 16
14/11/2011 11:45:34
Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Masterpact type
Rating
Sensor rating
Circuit breaker
Switch-disconnector
NT
A
A
N1, H1, H2, H3, L1
NA, HA, HF, ES,
HA10 (NW)
Number of poles
Option: neutral on right side
Device
3 or 4
Indication contacts
OF - ON/OFF indication contacts
Standard
4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW)
qty
Additional
1 block of 4 OF for NW
max. 2
EF - combined connected/closed contacts
1 EF 6 A-240 V AC for NW
max. 8
1 EF low-level for NW
max. 8
Standard
1 SDE 6 A-240 V AC
Additional
1 SDE 6 A-240 V AC
1 SDE Low level
Programmable contacts
2 M2C contacts
6 M6C contacts
Carriage switches
6 A-240 V AC
Low level
CE - connected position max. 3 for NW / NT
CD - disconnected position max. 3 for NW, 2 for NT
CT - test position
max. 3 for NW, 1 for NT
AC - NW actuator for 6 CE - 3 CD - 0 CT additionnal carriage switches
Remote ON/OFF
qty
qty
qty
qty
Remote operation
Fixed
Withdr. chassis
Withdr. without chassis
(moving part only)
2.0
qty
qty
7.0
7.0
7.0
V
Remote tripping
Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LT OFF
PTE - external voltage measurement input (required for
reverse supply)
Communication
Eco COM module
Modbus
(for switchboard display units)
Connections
Top
Bottom
Top
Bottom
Top
Bottom
NT - FC fixed, draw.
NT - FC fixed, draw.
NT - FC fixed
NT, NW fixed, draw.
NT fixed, drawout
NW fixed
NT fixed, draw.
NT, NW
NW
Low level
6 A-240 V AC
V
V
Locking
Horizontal
Vertical
Front
Vertical-connection adapters
Cable-lug adapters
Arc chute screen
Interphase barriers
Spreaders
Disconnectable front
connection adapter
V
V
V
Profalux
Kirk
Ronis
Castell
Ronis
Ronis
Ronis
Ronis
Castell
1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis
Accessories
CDM - mechanical operation counter
CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Brackets for mounting NW fixed
Test kits
Mini test kit
on backplates
Portable test kit
D-17
313E.indb 17
14/11/2011 11:45:35
Catalogue numbers
and order forms
Source-changeover systems
for 3 devices
Masterpact NW / Circuit breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
Interlocking using cables (NW devices one above the other or side-by-side)
Select a complete set including three adaptation fixtures and the cables
1 complete set for:
3 sources / 1 device ON, fixed or drawout
2 sources + 1 coupling, fixed or drawout
2 sources + 1 replacement source, fixed or drawout
D-18
313E.indb 18
14/11/2011 11:45:35
Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Masterpact type
Rating
Sensor rating
Circuit breaker
Switch-disconnector
Number of poles
Option: neutral on right side
Device
Indication contacts
OF - ON/OFF indication contacts
Standard
4 OF 6 A-240 V AC (10 A-240 V AC and low-level)
Additional
1 block of 4 OF
max. 2
EF - combined connected/closed contacts
qty
1 EF 6 A-240 V AC
max. 8
qty
1 EF low-level
max. 8
qty
Standard
1 SDE 6 A-240 V AC
Additional
1 SDE 6 A-240 V AC
1 SDE Low level
Programmable contacts
2 M2C contacts
6 M6C contacts
Carriage switches
6 A-240 V AC
Low level
CE - connected position
max. 3
CD - disconnected position max. 3
CT - test position
max. 3
AC - NW actuator for 6 CE - 3 CD - 0 CT additionnal carriage switches
A
A
N1, H1, H2, H3, L1
NA, HA, HF
3 or 4
Fixed
Drawout with chassis
Remote operation
Remote ON/OFF
2.0
5.0
6.0
P - power meter
5.0
6.0
H - harmonic meter
5.0
6.0
AD - external power-supply module
TCE - external sensor (CT) for neutral protection
Rectangular sensor
470 x 160 mm
for earth-leakage protection
7.0
7.0
7.0
V
Remote tripping
Locking
Communication
Low level
6 A-240 V AC
BPFE - electrical closing pushbutton
Res - electrical reset option
RAR - automatic reset option
MN - undervoltage release
R - delay unit (non-adjustable)
Rr - adjustable delay unit
2eme MX - shunt release
Connections
Top
Top
Top
Fixed, drawout
Fixed
V
V
V
Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LT OFF
PTE - external voltage measurement input (required for
reverse supply)
Horizontal
Vertical
Front
Interphase barriers
Disconnectable front
connection adapter
Bottom
Bottom
Bottom
VPEC - door interlock
qty
qty
qty
qty
Profalux
Kirk
V
V
Ronis
Castell
Ronis
Ronis
Ronis
Ronis
Castell
1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis
Accessories
313E5100.indd 19
on backplates
Portable test kit
17/11/2011 08:21:17
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.