Documente Academic
Documente Profesional
Documente Cultură
n
a
p
m
o
After a bushing failed in service, the decision was made to perform aC
forensic teardown analysis of it and two
identical bushings from the same bank of transformers. The bushings
were transported to the Doble High Voltage
g
in and inspected. The combined findings
Laboratory in Watertown, Massachusetts where they were disassembled
r
e
from of a dielectric stress analysis of the design, visual inspection
e during disassembly, and chemical and electrical
n
tests of samples taken from the bushings were used to
determine the cause of failure for the bushing that failed and
i
the condition of the other two bushings.
ng
E
BACKGROUND
le
b
oUnit 2 at AES Alamitos experienced a failure of A-phase Main Transformer. An
On July 16, 2010 at 10:56 p.m.
D
Allis Chalmers 180kV
transformer bushing failed violently, causing some damage to nearby equipment and
unscheduled down time. The top portion of the bushing exploded leaving only the center conductor rod and cap.
INTRODUCTION
The bottom portion of the bushing stayed together and the internal components of the transformer were not
damaged. The bushing was installed in a single phase generator step up (GSU) transformer connected to the APhase, in a bank of three transformers. The explosion caused some superficial damage to the C-Phase, but the BPhase was not damaged. Nameplate information for the bushing and transformer information are as follows:
Bushing
Manufacturer
Type
Voltage Class
BIL
Current Rating
C1 Power Factor
Manufactured
Transformer
Ohio Brass
Class-G-53X
180kV
825kV
800A
1.0%
1956
Manufacturer
Type
Capacity
Cooling Class
Temperature Rise
Voltage
Manufactured
Allis Chalmers
Single Phase GSU
56/74.6 MVA
ONAN/ONAF
55C
18,000 127,017GRDY/220,000
1956
It was decided to perform a tear down and forensic analysis of all three bushings. The serial number of the bushing
that failed (A-Phase) was 49310-8. The serial number of the B-Phase bushing was 49310-9, and C-Phase was
49310-7.
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
AES Alamitos, in the City of Long Beach, is a 2,000 MW natural gas-fueled power plant, one of the largest in
Southern California.
measured values were very similar for all three bushing and showed a 56% increase over the factory nameplate
values. The measured results are listed here in Table 1.
Table 1
Power Factor Test Results November 2007
Connected
Phase
A (failed)
B
C
Serial
Number
41390-8
41390-9
41390-7
A query of historical test records using Doble DTA Web for the C1 measurements of Ohio Brass Type G bushings
rated from 115 to 230 kV yielded 405 test results. Based on these test results, the acceptable range for the C1 power
factor, corrected to 20 C, is between 0.12 0.64 percent. Figure 1 displays the historical power factor distribution.
m
o
C
e
n
i
g
50
n
E
le
b
o
40
30
20
ng
i
r
e
n
a
p
10
0
0.12 to
0.377
0.377 to
0.634
0.634 to
0.891
0.891 to
1.148
1.919 to
2.176
2.176 to
2.433
2.433 to
2.69
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
2 -12
m
o
C
n
a
p
g
n
i
r
The two inner concentrically arranged porcelain sleeves were
eseparated by wedges cemented at the ends between the
e
sleeves. The ground shield porcelain was attached to the
mounting flange by wedges in a similar manner.
n
i
g
n
It is well recognized that the radial electrical stresses are highest in the space between the bushing stud and the
E upon the strike distance between the live electrodes at the top and
ground shield. The axial stresses are dependent
e
l ground shield.
bottom ends of the bushing and theb
fired-on
o
D
It is evident that this was a graded insulation bushing design where a series of porcelain barriers were used to control
radial stresses in the space between the bushing stud and the ground shield. Since the oil gaps between these barriers
were the weakest dielectric medium, the radial stresses at the outer diameters of each solid dielectric were calculated
to check the integrity of the dielectric system. Table 3 shows dimensions and dielectric constants used to calculate
the dielectric stresses.
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
3 -12
Table 2
Dielectric Constants and Dimensions
Component
Bushing
Stud
Tape Layer
I
Oil Duct I
Inner
Porcelain
Tape Layer
II
Oil Duct II
Inner
Porcelain II
Oil Duct III
Shield
Porcelain
Ground
Shield
Material
Dielectric
Constant
Inside
Radius
[in]
Outside
Radius
[in]
Copper
1.25
Distance
to Stud
[in]
Effective
Distance
[in]
Effective
Radius
[in]
Gradient
At OR
[kV/in]
79.90
Cambric
Cloth
Oil
2.32
1.25
1.55
0.30
0.30
1.55
64.44
2.32
1.55
1.75
0.50
0.50
1.75
57.07
Porcelain
1.75
1.88
1.63
1.03
2.28
43.74
Cambric
Cloth
Oil
2.32
2.88
3.00
1.75
1.14
2.39
41.77
2.32
3.00
3.40
2.15
1.06
2.33
42.80
Porcelain
3.40
4.50
3.25
2.04
3.29
30.35
Oil
2.32
4.50
5.19
3.94
2.62
3.87
25.81
Porcelain
5.19
6.45
5.2
3.19
4.44
22.49
Conductive
Coating
6.45
5.2
e
n
i
g
n
E
le
b
o
ng
i
r
e
m
o
C
n
a
p
-
of the bushing, this gives an average axial stress level of 36 kV per inch. These stress levels are well below the
recommended design limits for reliable bushings.
VISUAL INSPECTION
All of the porcelain above the ground sleeve of bushing that failed was gone, leaving only the center stud and top
cap of the bushing. Photo 1 shows the condition of the bushing when it arrived at the lab. All of the porcelain
above the flange was blown away in the failure.
m
o
Top End of Failed BushingC
Photo 1
ng
i
r
e
Photos 2 and 3 show burn marks on the porcelain.
e
n
gi
n
E
e
bl
o
D
n
a
p
Photos 4 and 5 show burn marks on the center stud and outer flange respectively. The shape of the crater and the
burn marks indicate that this was an external flashover between the bushing stud and the bushing flange. The draw
lead and its insulation had no involvement in this failure. It appears that an internal flashover created high pressure
inside the bushing, causing the porcelain to rupture. This was likely followed by subsequent arcing Due to the
extent of the damage, the precise cause and initiation point of the failure is not evident.
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
5 -12
The impregnated paper layers taped over the bushing stud were examined and significant evidence of partial
discharge (PD) activity was observed. These marks were not located near the areas where the flashover damage was
observed. This indicates that a general problem existed throughout the bushing, such as contamination in the oil.
Similar marks were found in the other two bushings, as they were disassembled. Photos 12 - 14 show black marks
and burn holes in the insulation that are characteristic of partial discharge activity.
e
n
i
g
n
E
le
b
Black Hole ino
D Insulation
Photo
6
ng
i
r
e
m
o
C
n
a
p
They are representative of what was found in all three bushings. Many of the spots showed a tree like pattern
typical of partial discharge damage when examined under a microscope, while others did not. These spots were
determined to be inclusions from the manufacturing process,
The innermost layer of the insulation had a dark greenish appearance where it came in contact with the copper bar
running through the center of the bushing, as can be seen in Photo 8. This appears to be a copper oxide deposits
resulting from moisture on the copper. This coating was very uniform, indicating that they were caused by a
reaction that had been taking place over a long period of time.
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
6 -12
e
n
i
g
n
E
ble
DeterioratedoGasket
Photo
D 9
ng
i
r
e
m
o
C
n
a
p
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
7 -12
LABORATORY ANALYSIS
Samples of materials were extracted from each bushing during the teardown and labeled appropriately. These
samples were analyzed at the Doble Material Laboratory by Scanning Electron Microscopy (SEM) and Energy
Dispersive X-ray (EDX) analysis.
Scanning Electron Microscopy (SEM) Energy Dispersive X-ray (EDX) analysis are two separate tests conducted
at the same time. EDX is a technique in which an electron beam of the scanning electron microscope enters the bulk
of a sample producing an x-ray emittance. The X-ray peak positions, along the energy scale, identify the elements
present in the sample and can provide the percent concentrations of each of these elements thus providing an
elemental breakdown of the material or particles.
SEM is an analysis in which a beam of electrons, a few hundred angstroms in diameter, systematically sweeps over
the specimen. The intensity of secondary electrons generated at the point of impact on the specimen surface is
measured, and the resulting signal fed into a cathode-ray-tube display which is scanned in synchronism with the
scanning of the specimen to produce a picture.
The cellulose insulation primarily used in these three bushings is cambric cloth. Cambric cloth is open weave cloth
impregnated with varnish and was used quite extensively in the electric industry in the first half of the twentieth
century. The material shown in Photo 39 was chosen for testing as there seems to be a residue accumulating at the
edges of the cloth layer overlap. A sample of cambric cloth that had a blackened edge was analyzed. An SEM
micrograph of the edge of the cloth is shown Photo 13.
e
n
i
g
n
E
le
b
o
ng
i
r
e
m
o
C
n
a
p
Table 3
Composition of Cambric Cloth Edge
Element
Carbon
Oxygen
Aluminum
Silicon
Composition, wt. %
57.3
40.6
0.9
1.2
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
8 -12
Most of what was found was just carbon and oxygen so it is most likely thermal degradation of the oil, paper and
varnish that collected in area. Edges of paper which still have individual fiber ends exposed tend to collect carbon
more readily than smooth, non-porous surfaces.
Because of the green discoloration observed on the center copper rod, a wipe sample was taken for analysis. The
EDX composition of the two predominant particles from the wipe sample is provided in the Table 4.
Table 4
Composition of Particles from Wipe Sample
Element
Particle 1, %
Particle 2, %
Carbon
Oxygen
Chlorine
Potassium
Calcium
Iron
Copper
Zinc
Silicon
61.8
26.4
1.6
0.8
0.5
0.9
5.0
3.0
--
21.9
2.9
0.4
---74.1
-1.1
n
a
p
The copper is most likely from the conductor. The presence of potassium, calcium and chlorine would suggest salts
from seawater although they are in a very low percentage. The wipe sample was taken because of the green hue
which usually indicates corrosion of the copper surface. It appears that some moisture from the external
environment did enter the bushing containing some salt water and did react with the copper to a small degree.
ng
i
r
e
m
o
C
A sample of the innermost layer of insulation next to the conductor with green deposits was analyzed. SEM
Micrograph of insulation sample is shown in photo 14.
e
n
i
g
n
E
le
b
o
Table 5
Composition of Green Deposits
Element
Carbon
Oxygen
Copper
Composition, wt. %
67.7
22.1
10.3
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
9 -12
A large amount of the copper was present in the cambric cloth and most likely combined with carbon and oxygen to
form copper carbonate (CuCO3) on the cambric cloth surface giving it the green coloration. The formation of copper
carbonate is a result of the slow chemical alteration of copper in which a humid (water) environment would have to
exist so that the reaction could take place.
A razor blade was used to remove some black material from one of the porcelain sleeves. Photo 15 shows the SEM
micrograph of the black material.
m
o
C
e
n
i
g
ng
i
r
e
n
a
p
Table 6
Composition of Black Material
n
E
le
b
o
Element
Carbon
Oxygen
Sodium
Magnesium
Aluminum
Silicon
Sulfur
Chlorine
Potassium
Calcium
Iron
Copper
Composition, wt. %
43.4
25.2
3.2
0.5
1.0
5.0
8.4
1.1
2.4
4.0
1.9
4.0
Copper and a large amount of sulfur are present. There is no suspicion of corrosive sulfur being an issue as the
copper was quite clean. There is a good percentage of copper away from the copper conductor itself. This may be a
combination of sludge and other materials. Sludge usually contains carbon, oxygen, sulfur, copper and other
elements to a lesser degree and is the byproduct of oxidation within the bushing. This would confirm that possible
outside environmental contaminants such as air and water were diffusing into the system over time.
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
1 0-12
[V/mil]
1400
1060
1190
970
The voltage breakdown tests show reasonably good insulation strength, giving no evidence that deteriorated cambric
cloth contributed to the failure.
B-Phase
66
35
109
68
1
459
e
n
i
g
n
E
le
b
o
ng
i
r
e
C-Phase
69
40
167
74
1
356
m
o
C
n
a
p
The elevated levels of ethylene and presence of acetylene indicate localized overheating was occurring within the
bushings. Elevated levels of carbon monoxide indicate overheating of the cambric insulation material. Given the
evidence of moisture air ingress observed, less soluble gasses have likely leaked out. Generation of hydrogen and
carbon monoxide was likely higher than indicated by the DGA samples, which would support the evidence of partial
discharge observed.
The levels of dissolved non-combustible gasses present are given here along with the moisture content.
B-Phase
20471
79821
6495
C-Phase
19556
79255
9722
Moisture in Oil
20
17
Oxygen and water content were lower than anticipated, given the evidence of moisture air ingress observed. This
suggests that they were likely consumed in the chemical reactions, and that the process had occurred steadily over
a long period of time.
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
1 1-12
CONCLUSION
The radial and axial electrical stress analysis of these bushings indicates that the design was adequate and didnt
expose any particular weakness that could have led to the failure of S/n: 41390-8. The teardown observations from
all three bushings indicate that the failure of S/n: 41390-8 was most likely caused by moisture, oxygen, salt and
other contaminates entering the bushing through deteriorated gasket seals that compromised the dielectric integrity
of the internal bushing insulation. The elevated power factor readings from November 2007 were likely caused by
this deteriorating condition inside the bushings. The results from dielectric breakdown strength tests on solid
insulation samples taken from the bushings were quite high. This suggests that dielectric deterioration was
occurring mainly in the bushing oil. It is possible that the evidence of partial discharge activity observed during the
teardown was the result of decreased dielectric breakdown strength of the oil. The oil from bushings S/n: 41390-9
and S/n: 41390-7 was drained before they were shipped to Doble. Therefore it was not available for dielectric
strength or partial discharge testing.
BIOGRAPHY
Mr. Darin D. Mitton. Mr. Mitton is a Transformer Engineer with Doble Engineerings Global Power Services. He
has 13 years of experience in power transformer and shunt reactor design, followed by 8 years of consulting. He has
been with Doble Engineering for 3-1/2 years, providing consulting services, including Design Reviews, Factory
Inspections, Factory Test Witnessing, Forensic Analysis, and Condition Assessments. He holds a B.Sc. in
Engineering from Idaho State University and is a registered Professional Engineer.
n
a
p
m
o
Mr. Santiago E. Chavez. Mr. Chavez is the Team Leader of IC&E of C
AES Alamitos. He has 30 years of power
g
generation experience. He has been with AES for 12 years; first as
Project
Support then 11 years as a Team Leader.
nas an Industrial
i
r
He previously worked at Southern California Edison for 18 years
Electrician, Maintenance Planner
e
and Safety Environmental Specialist III (CMMS) (REP 5973).
He
worked
11
years
at Magma Copper Company as
e
n
i
an Industrial Electrician.
ng
E
le
b
Do
2012 Doble Engineering Company -78th Annual International Doble Client Conference
All Rights Reserved
1 2-12