Sunteți pe pagina 1din 4

Accessing the REDUNDANCY object

The REDUNDANCY object provides status information about the redundancy system.
Attribute

Data
Type

Instruction

Description

ChassisRedundancyState

INT

GSV

redundancy status of the entire chassis

GSV

If:
Then:
16#1
power-up or undetermined
16#2
primary with qualified secondary
16#3
primary with disqualified secondary
16#4
primary with no secondary
16#8
qualified secondary
16#9
disqualified secondary with primary
16#A
disqualified secondary with no partner
results of the compatibility checks with the partner controller

CompatibilityResults

KeyswitchAlarm

INT

DINT

GSV

If:
Then:
0
undetermined
1
no compatible partner
2
fully compatible partner
keyswitch settings of the controller and its partner match or do
not match
If:
0

ModuleRedundancyState

INT

GSV

Then:
one of the following:
the keyswitches match
no partner is present
1
keyswitches do not match
redundancy status of the controller
If:
16#1
16#2
16#3
16#4
16#6
16#7
16#8

Then:
power-up or undetermined
primary with qualified secondary
primary with disqualified secondary
primary with no secondary
primary with qualifying secondary
qualifying secondary
qualified secondary

PartnerChassisRedundancyState

PartnerKeyswitch

PartnerMinorFaults

PartnerMode

INT

DINT

DINT

DINT

GSV

16#9
disqualified secondary with primary
16#A
disqualified secondary with no partner
redundancy state of the partner chassis

GSV

If:
Then:
16#1
power-up or undetermined
16#2
primary with qualified secondary
16#3
primary with disqualified secondary
16#4
primary with no secondary
16#8
qualified secondary
16#9
disqualified secondary with primary
16#A
disqualified secondary with no partner
16#D
no partner present
position of the keyswitch of the partner

GSV

GSV

If:
Then:
0
unknown
1
RUN
2
PROG
3
REM
status of the minor faults of the partner (if the
ModuleRedundancyState indicates that a partner is present)
This bit:
Indicates:
4
problem with an instruction (program)
6
periodic task overlap (watchdog)
9
problem with the serial port
10
low battery
mode of the partner
If:
16#0
16#1
16#2
16#3
16#4
16#5
16#6

Then:
power up
program
run
test
faulted
run-to-program
test-to-program

PartnerModuleRedundancyState

PhysicalChassisID

QualificationInProgress

INT

INT

INT

GSV

GSV

GSV

16#7
program-to-run
16#8
test-to-run
16#9
run-to-test
16#A
program-to-test
16#B
into faulted
16#C
faulted-to-program
redundancy state of the partner
If:
Then:
16#1
power-up or undetermined
16#2
primary with qualified secondary
16#3
primary with disqualified secondary
16#4
primary with no secondary
16#6
primary with qualifying secondary
16#7
qualifying secondary
16#8
qualified secondary
16#9
disqualified secondary with primary
16#A
disqualified secondary with no partner
16#D
no partner present
in a pair of redundant chassis, identification of a specific
chassis without regard to the state of the chassis
If:
Then:
0
unknown
1
Chassis A
2
Chassis B
status of the qualification process
If:
-1
0
1-99

50
100

Then:
qualification is not in progress
unsupported
for modules that can measure their completion
percentage, the percent of qualification that is
complete
for modules that cannot measure their completion
percentage, qualification is in progress
qualification is complete

SRMSlotNumber

INT

GSV

slot number of the 1757-SRM module in this chassis

S-ar putea să vă placă și