whyEMVTispreferredformeteringpurpose(tariff)inpowerplants?EventhoughCVTishavingmoreadvantagesthanEMVTlikecompact
size,economicaletc.,
__________________
krishna
Interestedinthistopic?ByjoiningCR4youcan"subscribe"to
thisdiscussionandreceivenotificationwhennewcommentsareadded.
JoinCR4,TheEngineer'sPlaceforNewsandDiscussion!

Tornado

#1

Re:EMVTVsCVT
03/01/20112:20AM

Guru

BadAcronymAlert!

__________________
InvinoveritasincervisiacarmeninaquaE.coli.

JoinDate:May2009
Location:Ketchikan,AK,
USA
Posts:16435
GoodAnswers:653

pvkrishnaji
electricalexpert65

Re:EMVTVsCVT
03/01/20113:00AM

#2
Inreplyto#1
#3

Re:EMVTVsCVT

Guru

03/01/20113:17AM

JoinDate:Oct2009
Posts:2016
GoodAnswers:164

Itisthequestionoffeasibility&costingofinsulationofEMVTsforvoltageshigherthan110kV.ThisiswhereaCVThelps,asitisa
CapacitorPotentialDivider.
Asfarasaccuracyisconcernde,byStandards,CVTsmustcomplywiththeaccuracyclassesaspecifiedforEMVTsaswell.

pvkrishnaji

Re:EMVTVsCVT

Member

03/01/20113:40AM

JoinDate:Jan2011
Location:bangalore,india
Posts:5

FirstofallThanksforyouranswer...

#4
Inreplyto#3

ButnowadaysEMVTsareusinginpowerplantsofrating400Kv(suppliers:CGL)onlyformeteringpurpose(classofaccuracy:0.2)
idontknowtheexactreasonbutihearedthatsomeDriftproblemisthereinCVTasfarasaccuracyisconcerned&preciseaccuracyis
notavailablewithCVT.
canyouexplainmeinthisregard...?
__________________
krishna

67model
Guru

JoinDate:Dec2010
Posts:795
GoodAnswers:56

Re:EMVTVsCVT
03/01/20117:10AM

#5
Inreplyto#4

1. ForCVTyoumusthave2capacitors2variablestoaffectratio.
2. Capacitancedependsondimensionsandpermittivity.
3. DimensionsandcapacitanceareverydifferentinHVsideandearthsidecapacitors,makingthemtracktokeepratioovertimeand
temperaturechangeisdifficult.
4. Waterhaspermittivity80comparedto~4forsoliddielectricanytinypenetrationhasbigeffect.
5. Resistiveleakagecurrentsareunstable,butcaneffectratio.
6. CVTusuallyhavetofinishupwithanEMVTforsafetyisolationwhichaddsitsownerrors.
InEMVTifprimaryhas10000turnsandsecondary100turnsthereisverylittlethatcanalterthatratio.Leakageinductanceaffects
effectiveratio,butisnotveryvariable.Magnetizingcurrent,vialeakagereactance,affectsreadingbutisfairlystableandcanevenbe
monitoredinservice.SotheaccuracyargumentsfavourEMVT.AlsoinEMVT,itispossibletoearthcore,windLVwindingoverearthed

http://cr4.globalspec.com/thread/66516/EMVTVsCVT

1/2

6/1/2015

CR4Thread:EMVTVsCVT
endofprimary,addearthedscreensandinsulationoverLVwindingallforpersonnelsafetyineventofbreakdowninHVside.
IncapacitorVT,considersafetyeffectofbreakdownofHVcapacitor......doyouwanttobemeasuringLVcircuitifthathappens??

RegistertoReply

5comments

Backtotop
Interestedinthistopic?ByjoiningCR4youcan"subscribe"to
thisdiscussionandreceivenotificationwhennewcommentsareadded.
JoinCR4,TheEngineer'sPlaceforNewsandDiscussion!

Userswhopostedcomments:
67model(1)electricalexpert65(1)pvkrishnaji(2)Tornado(1)

CopytoClipboard

PreviousinForum:ugcables NextinForum:InstrumentsneededforIlluminanceTestingLab
Youmightbeinterestedin:MeteringPumps,ConstantVoltageTransformers(CVTs),SinglePhaseTransformers

"Challengeisadragonwithagiftinitsmouth.Tamethedragonandthegiftisyours."NoelaEvans
AlltimesaredisplayedinUS/Eastern(EDT)(Registertochangetimezone)
2015IHS.Allrightsreserved.Reproductioninwholeorinpartwithoutpermissionisprohibited.Theinformationcontainedonthissiteisbyusersforusersandisprovidedforinformation
purposesonlyanddoesnotconstituteadvice.AnyviewsoropinionsexpressedbyusersarepersonaltothemanddonotrepresenttheviewsoropinionsofIHS.Youshouldcheckany
informationanduseyourownjudgmentorseekexpertadvicebeforedoingornotdoinganythingonthebasisofwhatyoureadhere.IHSdoesnotverifyorwarranttheaccuracyor
completenessofanyinformationonthissiteand,totheextentpermittedbylaw,IHSshallnotbeliableforanyloss,damageorexpenseincurredbyrelianceonitorforanydealingsyou
havewithusersorotherthirdpartiesthattakeplaceusingorfacilitatedbythissite.

http://cr4.globalspec.com/thread/66516/EMVTVsCVT

2/2

S-ar putea să vă placă și