HYDROPOWER STATION
AUTOMATION SYSTEM

OPERATION MANUAL

GUODIAN NANJING AUTOMATION CO.LTD.

SD 200
Hydropower Station Automation System

Operation Manual

Prepared by S.M.LI S.B.Deng


Checked by J.Chen
Approved by X.J.Guo

Guodian Nanjing Automation Co., Ltd.

2005

Contents

1.

Summary..........................................................................................................1
1.1.

Installation introduction......................................................................................1

1.2.

Communication management software package............................................1

1.3.

Database management software package........................................................1

1.4.

Interface design software package.....................................................................2

1.5.

Graphics display (online monitoring) software package..............................2

1.6.

Report software package.....................................................................................2

1.7.

History data search software package..............................................................2

2.

Communication Management Software Package................................3


2.1.

Communication server.........................................................................................3

2.2.

Communication server configuration...............................................................4

3. Database Management Software Package...............................................25


3.1.

Function introduction.........................................................................................25

3.2.

Running program................................................................................................25

3.3.

Usage method.......................................................................................................25

3.4.

Operating illustration.........................................................................................32

4.

Interface design software package.........................................................33


4.1.

Introduction..........................................................................................................33

4.2.

Basic usage............................................................................................................37

4.3.

File management.................................................................................................46

4.4.

Graphical primitive editor................................................................................49

5.

Graphics Display (online monitoring) Software Package...............51


5.1.

Picture display.....................................................................................................51

5.2.

Picture print.........................................................................................................51

5.3.

Alarm.....................................................................................................................51

5.4.

Remote Control....................................................................................................52

5.5.

Events record.......................................................................................................52

5.6.

Events print..........................................................................................................53

5.7.

Master and slave machine switch....................................................................53

5.8.

LCU locking and unlocking..............................................................................53

5.9.

History data store................................................................................................53

5.10.

5.10. Self-check and reset...............................................................................53

5.11.

Mutual-check....................................................................................................53

5.12.

Option................................................................................................................54

6.

Report Software Package..........................................................................55


6.1.

Report system basic concept.............................................................................55

6.2.

Report system access..........................................................................................55

6.3.

Report design.......................................................................................................55

6.4.

Report display......................................................................................................57

7.

History Data Search Software Package................................................59


7.1.

Interface component and basic usage.............................................................59

7.2.

Curve search for daily history data.................................................................62

7.3.

Curve search for monthly history data...........................................................64

7.4.

Form search of daily history data....................................................................64

7.5.

Form search of monthly history data..............................................................64

1 Summary

SD200

1. Summary

1.1. Installation introduction


1.1.1. Installation
Installing WINDOWS 2000
Installing drivers of display card and network card
Installing the SETUP.EXE of SD200, under the setup wizard, user selects the
monitoring software package or communication software package to install,
then the setup program will automatic complete the installation.
Installing EXCEL in OFFICE 2000.
1.1.2. System components
SD200 system is a full graphical interface hydraulic power plant computer monitoring
software package, which is processing on the WINDOWS NT/2000 system. This
system includes:
Communication management software package
Database management software package
Interface design software package
Graphics display (online monitoring) software package
Report software package
History data search software package
1.2. Communication management software package
Communication management software is the component of communication in SD200 monitoring
software package, which according to a great lot of project application experience, then make the
frequent used communication specification to develop into the variable configuration module. The
communication management software package includes all the data communications.

1.3. Database management software package


Database management software is the component which to manage and service the offline realtime database in SD200 monitoring software package. Under the provided interface, the slave
machine can easily amend various data property, which include the telemetry variable, telesignal
variable, telecontrol variable, teleadjust variable, computing formula, operator, password, network
computer, spot control cell and so on, the program can automatic write amended data property into
the real-time database.
1

1 Summary

SD200

1.4. Interface design software package


Interface design software is the component of picture design in SD200 monitoring software
package, which may redesign the monitoring picture according to the different requirement by
clients. It can add various lines, paints, time for the beautified picture, add the telemetry and
telesignal variable for monitoring the operating information of power plant, the telecontrol and
teleadjust variable for controlling the operating condition of power plant, and add Picture Index
for fast searching the picture.

1.5. Graphics display (online monitoring) software package


Graphics display software is the main component in SD200 monitoring software package. It can
perform the function such as picture display, picture print, data acquisition, data processing, alarm,
time display, time adjustment, remote control, events record, mater and slave machine switch, selfcheck, mutual-check, reset, and events print and so on.

1.6. Report software package


Report display and print software is the component of searching the history data report in SD200
monitoring software package. Through the report design program, it can design all kinds of history
data report and printing the report according to the client requirement.

1.7. History data search software package


History data search software package is the component of searching history data in SD200
monitoring software package. It can perform the curve search and data form search of history data
(include daily history data and monthly history data), also switch between the curve interface and
the form interface, and display the curve interface and the form interface in the same interface.

2 Communication Management Software Package

SD 200

2. Communication Management Software Package

2.1. Communication server


Run comserve.exe, then the communication server program can minimize to little mouse icon
which display on the taskbar of WINDOWS, as Figure 2-1 shows. Double click little mouse
icon, it can open the window of communication server program as Figure 2-2 shows. Click the
minimize button of window, the communication server program can re-minimize as Figure 2-1
shows.

Figure 2-1
In Figure 2-2, there are Port information box, Send and receive data box, Save data box,
Message stop roll select box and Port select pull-down list box in the window of program.

Figure 2-2
In Port information box, it can display some basic information of Ethernet and serial port. Select
the port in Port select, which basic information can display in Port information. Send and
3

2 Communication Management Software Package

SD 200

receive data box can display the data of sending and receiving, it can analyze the information of
communication protocol according to these data. If the different port corresponds to the different
protocol, it can separate to display the sending data and receiving data when select the port in
Port select.
Save data button is for saving the data in Send and receive data box, as Figure 2-3 shows,
clients can select a file name or input a file name by self, the data in Send and receive data box
can save to the file. We suggest saving as the text file type .text.

Figure 2-3
Message stop roll select box is for clients to select the roll message or not, stop the roll message
can observe the message better. The quit password of communication server is xxxx.

2.2. Communication server configuration


Run comserverconfig.exe, display as Figure 2-4, click running position configuration, display the
dialog box as Figure 2-5, in this dialog box clients can configure the communication server
running position: Run on Host, Run on the communication machine, Run on the all-in-one
machine, Run on the pre-machine, and Run on the mainframe terminal. If communication server is
running on Host, but this Host used as backup machine, it cannot collect data.

Figure 2-4

2 Communication Management Software Package

SD 200

Figure 2-5

2.2.1. Communication server configuration


Click Communication server configuration, then open the dialog box as Figure 2-6. The first
column of this dialog box indicates the port of computers. Now computers in electric power
automation system usually adopt the serial port (COM1-COM10) and Ethernet port (ENET). If the
port does not connect any necessary communication device, it cannot select this port from COM2
COM10 port as Figure 2-6 shows. If the port needs to connect the communication device, it can
select the relevant port COM1 and ENET as Figure 2-6 shows.
Each port needs to process the parameter configuration, it needs to configure the baud rate on the
Serial port, and configure the IP address on the Ethernet port. Click Port configure button in the
dialog box, then display the port configuration dialog box as Figure 2-7 shows. Serial port
configuration include baud rate, data bit, start bit, stop bit, calibration method, data stream control,
synchronous and asynchronous communication mode, etc. The customary setups are: baud rate
(9600), data bit (8 bit), start bit (1 bit), stop bit (1 bit), calibration method (none), data stream
control (none), synchronous and asynchronous communication mode (asynchronous), etc. But
some protocols on the configuration requirement to ports are different. Such as the communication
protocol of electric meters (DL/T 645 and V41) which appeal the calibration method is even,
baud rate is 1200. Notice that ports configuration and protocol requirement are discord,
communication cannot connect.
Device number in the dialog box indicates the number of communication devices connect to this
port. For example: if there are 2 PLC LCU and 2 PS6000 devices connect to the Ethernet port,
then Device number will display 4. If there are 3 electric meters connect to COM1 port, then
Device number will configure as Figure 2-6.
After setting the number of devices, then need to configure the protocol of each device, Click
Protocol configuration button, then display the protocol configuration dialog box as Figure 2-8,
In the dialog box, the device number is the quantity of devices for the port protocol configuration,
which defined as Device number: if Device number is 4, then each device number as 0, 1, 2,
3. There are Device type list and Protocol type list in the dialog box. Such two lists configure
for the device in the Device number. If No. 0 device is GEPLC, which adopt MODBUSTCP
protocol, then select PLC in Device type, select MODBUSTCP protocol in Protocol type.
After select the protocol type, click Device protocol parameter configuration button, then we
5

2 Communication Management Software Package

SD 200

can configure the corresponding protocol.

Figure 2-6

2 Communication Management Software Package

SD 200

Figure 2-7

Figure 2-8

2.2.2. Protocol configuration

2.2.2.1. MODBUS TCP Protocol

Range of complication: MOBBUS TCP protocol applies to the PLC Ethernet module of
MODICON serial, the PLC Ethernet module of GEPLC serial (mantissa number is GH and
anon). Others apply to this protocol of PLC network module. Only apply to the network port
ENET.
Setting method and parameter illustration as Figure 2-9 shows.

IsOnlan: it indicates whether PLC Ethernet module connect to the network, and configure the IP
address. If match two criteria, then select it. If do not select it, all uplink machines cannot collect
the data in PLC.
Double network: the uplink machine whether communicates to PLC through the double network
and process as the backup for each other.
PLC number: PLC number such as LCU1 numbers 1, LCU2 numbers 2.
PLC type: PLC type, it is GEPLC or MODICONPLC, etc. Because different PLC of
MODBUSTCP protocol has the different access, it keeps these options.
PLC IP address 1: the first IP address of Ethernet module in PLC. Caution this IP address must
configure in the same network field with the downlink machine of Host.
PLC IP address 2: the second IP address of Ethernet module in PLC. Caution this IP address must
configure in the same network field with the downlink machine of Host.
7

2 Communication Management Software Package

SD 200

Timing configuration: timing configuration between the uplink machine and PLC, include two
timing approaches: Up timing PLC is timing to uplink machine; down timing uplink machine
is timing to PLC. Time can store in the register cell of PLC as timing.
PLC memory address distribution: Start address is start address of all contents store in R register
in PLC. Length is the length of different board. Different boards contain different quantity of
contents.
Telesignal content: each board contains 24 telesignal contents;
Communication content: each board contains 24 telemetry contents;
Simulation content: each board contains 16 telemetry contents;
Temperature content: each board contains 16 telemetry contents;
Synthesis switch content: each board contains 24 telesignal contents;.
SOE content: each board contains 5 words;
Control record: each board contains 5 words;
Other telemetry content: each board contains 24 telemetry contents;
Other telesignal content: each board contains 24 telesignal contents;
Telecontrol content: each board contains 32 telecontrol contents;
Teleadjust content: each board contains 32 teleadjust contents.

Figure 2-9

2 Communication Management Software Package

SD 200

2.2.2.2. GE HCT Protocol

Range of complication: apply to PLC Ethernet of GE PLC serial; only apply on the network
port ENET.
Setting method and parameter illustration as Figure 2-10 shows.

Figure 2-10
This configuration of protocol is same as MODBUS TCP protocol; the difference is the Title of
PLC, because adopting GE HCT protocol need to HCT drivers, in HCT configuration need to
configure PLC1, PLC2, etc. Here the title should accord to the title of HCT. Material
configurations are: No.1 LCU configure to PLC1, No.2 LCU configure to PLC2, by analogy.

2.2.2.3. CDT Protocol.

Range of complication: monitoring system receive the data that the sending device adopting
the CDT protocol send to (Host); monitoring system sends data to the control terminal (slave
machine). Only apply on the serial ports COM1 COM10.
Setting method and parameter illustration as Figure 2-11 shows (Host), as Figure 2-12 shows
(slave machine).

Adopting CDT protocol coding data usually include: main telemetry, minor telemetry, general
telemetry, telesignal, electric energy. In Figure 2-11 and Figure 2-12, it needs to configure the
number of these contents. Other devices send the number of data to monitoring system as Host;
Monitoring system send the number of data to other devices (such as control terminal) as the slave
9

2 Communication Management Software Package

SD 200

machine.
Local address and Opposite terminal address: they configure by monitoring system when
monitoring system as Host; they configure by the control terminal then monitoring system as the
slave machine.
A: Monitoring system receive the data other devices sending as Host
After receiving these data store to the database of monitoring system, so it needs to configure the
start address in the database. For example, if SD200 monitoring system receives 124 main
telemetry variables, the start address in database is 10120011, and then these variables occupy the
database from 10120011 to 10125041. Other telemetry variables cannot occupy these cells in the
database.
As Host mentions whether it needs to run the command such as timing, reset, setup, etc. from
clients. If select the corresponding check box it can run such commands on the slave machine.

Figure 2-11
B: Monitoring system sends the data to other devices as the slave machine.
What the data sending need to confirm by the control terminal, the data usually is discontinuous in
monitoring system, so it needs to set up the address for each telemetry and telesignal variable. And
because each telemetry variable transfer by 12 bit in CDT, the transferring maximum of each
telemetry variable cannot more than 0x07FF, so it needs to process the proportional action
10

2 Communication Management Software Package

SD 200

coefficient product for each telemetry variable without being out of limit. Different telemetry
variable adopt different coefficient, if adopt too small coefficient, then the precision of transferring
data would decline at last.

Figure 2-12

2.2.2.4. DL/T 645 Protocol

Range of complication: apply to the electric meter adopting DL/T 645 protocol, such as
WeiSheng electric meter; this protocol only applies on the serial ports COM1 COM10.
Setting method and parameter illustration as Figure 2-13 shows.

Electric meter address: because monitoring system and electric meter usually adopt No. 485
communication method, it needs to set the address to each table. The setting method of each
electric meter refer to their instruction, therefore special write the electric setting program
DianDuAddressSet.exe to work in.
Monitoring system collect the data from each electric meter as Table 2-1 shows. The data from
each table in monitoring database occupy 20 telemetry cells. The start address in database can
configure in the dialog box of DLT645 protocol configuration.
11

2 Communication Management Software Package

SD 200

If it needs to time the electric meter, then select the timing check box.

Figure 2-13
NOO

NAME

NOO

NAME

10220011

Total positive active power of


Generator 3#

10220111

Total positive reactive power of


Generator 3#

10220021

Positive peak-peak
power of Generator 3#

active

10220121

Positive peak-peak
power of Generator 3#

10220031

Positive peak active power of


Generator 3#

10220131

Positive peak reactive power of


Generator 3#

10220041

Positive off-peak active power


of Generator 3#

10220141

Positive off-peak reactive power


of Generator 3#

10220051

Positive valley active power of


Generator 3#

10220151

Positive valley reactive power of


Generator 3#

10220061

Total reverse active power of


Generator 3#

10220161

Total reverse reactive power of


Generator 3#

10220071

Reverse peak-peak
power of Generator 3#

active

10220171

Reverse peak-peak
power of Generator 3#

10220081

Reverse peak active power of


Generator 3#

10220181

Reverse peak reactive power of


Generator 3#

10220091

Reverse off-peak active power


of Generator 3#

10220191

Reverse off-peak reactive power


of Generator 3#

10220101

Reverse valley active power of


Generator 3#

10220201

Reverse valley reactive power of


Generator 3#

reactive

reactive

Table 2-1

2.2.2.5. V41 Protocol (WeiSheng user-defined protocol of electric communication)

Range of complication: WeiSheng electric meter, only apply on the serial ports COM1
COM10.
Setting method and parameter illustration as Figure 2-14 shows.

Electric meter address: because monitoring system and electric meter usually adopt No. 485
12

2 Communication Management Software Package

SD 200

communication method, it needs to set the address to each table. The setting method of each
electric meter refer to their instruction, therefore special write the electric setting program
DianDuAddressSet.exe to work in.
Monitoring system collect the data from each electric meter as Table 2-2 shows. The data from
each table in monitoring database occupy 64 telemetry cells. The start address in database can
configure in the dialog box of V41 protocol configuration.

Figure 2-14
NOO
10220011

NAME
Active power of Generator 3#

10221091

10220021

Reactive power of Generator

10221101

10220031

Voltage of Generator 3#

10221111

10220041

Current of Generator 3#

10221121

10220051

Total positive active power of


Generator 3#

10221131

10220061

Peak of positive active power


of Generator 3#

10221141

10220071

Off-peak of positive active


power of Generator 3#

10221151

10220081

Valley of positive active


power of Generator 3#
Peak-peak of positive active
power of Generator 3#
Total reactive power of
Generator 3#

10221161

Peak of reactive power of

10221191

10220091
10220101

10220111

NOO

10221171
10221181

NAME
Valley of reverse reactive
power of Generator 3# in this
month
Peak-peak of reverse reactive
power of Generator 3# in this
month
Total capacitive reactive
power of Generator 3# in this
month
Peak of capacitive reactive
power of Generator 3# in this
month
Off-peak of capacitive reactive
power of Generator 3# in this
month
Valley of capacitive reactive
power of Generator 3# in this
month
Peak-peak of capacitive
reactive power of Generator
3# in this month
Total reverse active power of
Generator 3# in this month
Peak of reverse active power
of Generator 3# in this month
Off-peak of reverse active
power of Generator 3# in this
month
Valley of reverse active power
13

2 Communication Management Software Package

10220121

10220131
10220141
10220151

Generator 3#
Off-peak of reactive power of
Generator 3#
Valley of reactive power of
Generator 3#
Peak-peak of total reactive
power of Generator 3#
Total capacitive reactive
power of Generator 3#

SD 200

10221201

10221211
10221221
10221231

Peak of capacitive reactive


power of Generator 3#
Off-peak of capacitive reactive
power of Generator 3#

10221241

Valley of capacitive reactive


power of Generator
Peak-peak
of
capacitive
reactive power of Generator
3#
Total reverse active power of
Generator 3#
Peak of reverse active power
of Generator 3#
Off-peak of reverse active
power of Generator 3#3
Valley of reverse active power
of Generator 3#
Peak-peak of reverse active
power of Generator 3#

10222021

10221011

Positive active power of


Generator 3# in this month

10222091

10221021

Peak of positive active power


of Generator 3# in this month

10222101

10221031

Off-peak of positive active


power of Generator 3# in this
month
Valley of positive active
power of Generator 3# in this
month
Peak-peak of positive active
power of Generator 3# in this
month
Reactive power of Generator
3# in this month

10222111

10220161
10220171

10220181
10220191

10220201
10220211
10220221
10220231
10220241

10221041

10221051

10221061

10221071

Peak reactive power of

10222011

10222031

10222041
10222051
10222061
10222071
10222081

10222121

10222131

10222141

10222151

of Generator
Peak-peak of reverse active
power of Generator 3# in this
month
Total positive active power of
Generator 3# in last month
Peak of positive active power
of Generator 3# in last month
Off-peak of positive active
power of Generator 3# in last
month
Valley of positive active power
of Generator 3# in last month
Peak-peak of positive active
power of Generator 3# in last
month
Total reactive power of
Generator 3# in last month
Peak of reactive power of
Generator 3# in last month
Off-peak of reactive power of
Generator 3# in last month
Valley of reactive power of
Generator 3# in last month
Peak-peak of reactive power
of Generator 3# in last month
Capacitive reactive power of
Generator 3# in last month
Peak of capacitive reactive
power of Generator 3# in last
month
Off-peak of capacitive reactive
power of Generator 3# in last
month
Valley of capacitive reactive
power of Generator 3# in last
month
Peak-peak of capacitive
reactive power of Generator
3# in last month
Reverse active power of
Generator 3# in last month
Peak of reverse active power
of Generator 3# in last month
Off-peak of reverse active
power of Generator 3# in last
month
Valley of reverse active power
14

2 Communication Management Software Package

10221081

Generator 3# in this month


Off-peak reactive power of
Generator 3# in this month

SD 200

10222161

of Generator 3# in last month


Peak-peak of reverse active
power of Generator 3# in last
month

Table 2-2

2.2.2.6. SYMIMIC Protocol

Range of complication: double mimic screen, only apply on the serial ports COM1
COM10.
Setting method and parameter illustration as Figure 2-15 shows.

Double mimic screen communication method is: each telesignal box drives 16 telesignal statuses;
each telemetry box drives 1 telemetry status. Each telesignal box address is different to each
telemetry box address. So it needs to evaluate for each telesignal and telemetry address from 1 to
255. It can configure the color of combination and discerption for the telesignal display.
According to Figure 2-15, for example: if it needs to display 75 telesignal statuses (The telesignal
status is green as discerption with 0; is red as combination with -1), and 12 telemetry statuses.
First select 0 is green; 1 is red. Number of the telesignal box is 5 (75/16=5), number of telemetry
is 12; configure address for each telesignal and telemetry box; set 16 telesignal addresses in the
database, such as 10101012, 10101052, etc. total is 75; set 1 telemetry database address for each
telemetry box, such as 10135018, etc.

Figure 2-15

15

2 Communication Management Software Package

SD 200

2.2.2.7. No. 94 Agreement

Range of complication: No. 94 agreement applies to exchange the information between the
protector and the background monitor, which usually adopt serial port. It only applies on the
serial ports COM1 COM10. The monitoring system collects the data of No. 94 agreement
device when the monitoring system as the mainframe. For requirement of update, it keeps the
port for No. 94 agreement as the slave machine.
Setting method and parameter illustration as Figure 2-16 shows.
The data adopting No. 94 agreement commonly involve: telemeter, telesignal, Event telesignal,
Fixed Value and Time. It configures for these data as below:

A. Parameter setting method


Principle: select the data type need to collect, and then configure other parameter of the data, if
do not select the data, this correlative parameter of the data is gray, cannot configure. For
example if it needs to collect telemeter variable of protector, then click Demand telemeter,
the option about telemeter demand setting turn to bright from gray, then configure the option.
Parameter setting dialog box is as below shows. (Such as WPD243 protector, uplink machine
as the mainframe)
B. Parameter illustration
As the mainframe in communication: when communicate to devices, usually monitoring
system is as the mainframe, must select this option.
Demand time: when need to time devices, must select this option.
Demand value: when need to value from devices, must select this option.
Select corresponding check box when it needs other traffic,
Setting address: corresponding setting address is from 1 to 254.
Number of CPU: the number is 1 commonly; maximum is 2 without other remarks.
Fixed value type: select transferring Fixed value type, usually is compression BCD code, but
WPD243 adopts HEX to transfer.
Fixed value serial number: select corresponding Fixed value serial number to configure, and
begin at 1.
Fixed value proportion coefficient: write corresponding Fixed value proportion coefficient, all
write 1 without any explanation.
Database address: it is the start address in Fixed value database. It occupies the telemeter
address of LCU.
In a similar way configure the database address for telemeter, telesignal, etc. telemeter is same
as Fixed value, telesignal is similar to Fixed value, only the unit of telesignal occupying the
database address is1 byte, for example 7 telesignal occupy 1 byte, and 9 telesignal occupy 2
byte. telesignal occupy the telesignal address of LCU.

16

2 Communication Management Software Package

SD 200

Figure 2-16
Notice: each CPU needs to configure options as above.
CPU serial number: select corresponding CPU serial number to configure, begin at 1.
Main parameter setting of the typical device adopting No. 94 protocol as below:
A. NanZi WMZ-41A differential protector TongZiHAo project
Baud rate: 9600; 8 bit as data bit; 1 bit as stop bit; unverity; WMZ-41A setting as the slave
machine; CPU number: 2; each Fixed value number is: 11, 11; telesignal variable number is:
15, 15.
B. NanZi WPD243 line protector JiaoJiaoHe project
Baud rate: 9600; 8 bit as data bit; 1 bit as stop bit; unverity; WPD243 setting as the slave
machine; CPU number: 1; Fixed value number is: 31; telemeter variable number is: 12;
telesignal variable number is 16.
The table of measuring point of typical device adopting No. 94 protocol is as annexed Table 1,
2.

2.2.2.8. MODBUS Agreement


Range of complication: apply to the communication between the device adopting common
MODBUS agreement and monitoring system. The character is that telemeter frame and
telesignal frame are descriptions. Common MODBUS agreement usually applies on the serial
port COM1 COM10. Adopt this agreement, the monitoring system is as the mainframe or
the slave machine. Regard as the mainframe or the slave machine needs to arrange by
communication parts. Whatever the mainframe or the slave machine, two parts can read-write
the data each other.
Setting method and parameter illustration as Figure 2-17 shows.
The data of adopting common MODBUS agreement commonly involve: telemeter, telesignal,
Fixed Value, Telecontrol Variable, Teleadjust Variable and Time. It configures for these data as
below:

17

2 Communication Management Software Package

SD 200

A. Parameter setting method


Principle: select the data type need to collect, and then configure other parameter of the data,
if do not select the data, this correlative parameter of the data is gray, cannot configure. For
example if it needs to collect telemeter variable of protector, then click Demand telemeter,
the option about telemeter demand setting turn to bright from gray, then configure the option.
Parameter setting dialog box is as below shows. (Such as KeYuan DCS communication, the
uplink machine as the slave machine)

Figure 2-17
B. Parameter illustration
As the mainframe in communication: if the circulation collect the data from devices, must
select this option. And as the mainframe or the slave machine arrange by both parts.
Demand time: when need to time devices, must select this option.
Demand telemeter: when need to attain telemeter from the device, must select this option.
When need other traffic, select corresponding check box.
Setting address: corresponding setting address is from 1 to 255.
Telemeter number: read telemeter number is from 0 to 125.
Telemeter protocol address: read the start address of telemeter data in MODBUS agreement.
Telemeter data type: select telemeter data type for transferring, usually it is HEX, but CD194E
adopt floating point numbers to transfer.
Telemeter serial number: select corresponding telemeter serial number to configure.
Telemeter proportion coefficient: infill corresponding serial number to telemeter proportion
coefficient. The infilling is 1 without any explanation.
18

2 Communication Management Software Package

SD 200

Telemeter database address: the start address in telemeter database. Occupy telemeter address
of LCU.
Telemeter request frame data length type: default is the number of R occupied. But some
factories do not adopt canonical protocol; date length is the number of byte.
telesignal request frame data length type: default is the number of R occupied. But the data
length of some factories is the number of byte or the number of telesignal from 0 to 250.
telesignal data denotation format: default 1 byte = 8 telesignal, sometime 1 byte = 1 telesignal.
In a similar way configure the database address for Fixed value, telesignal, etc. telemeter is
same as Fixed value, telesignal is similar to Fixed value, only the unit of telesignal occupying
the database address is 1 byte, for example 7 telesignal occupy 1 byte, and 9 telesignal occupy
2 byte. telesignal occupy the telesignal address of LCU.
Confirm: confirm modification, close dialog box.
Cancel: cancel modification.
Notice: read means that read the data from devices or system as the slave machine to devices
or system as the mainframe.
The setting of typical devices adopting the standard MODBUS protocol is as below:
A. NanZi nep988/nep983 device
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; nep988/nep983 device as the slave
machine.
B. KeYuan DCS system
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; monitoring system as the slave
machine.
Telesignal number: 8; telesignal protocol address: 0; telesignal function code: 3; remote
control number: 8; remote control protocol address: 0; remote control function code: 16.
Notice: unconfiguration option default 0.
Yangtse River SiFeiEr plating meter.
ChangKongSuo speed regulator.

2.2.2.9. NARI MODBUS Agreement


Range of complication: apply to communicate between the device adopting NARI MODBUS
protocol and monitoring system. Its character is that telemeter and telesignal locate the same
frame, remote control and YT is 1. NARI MODBUS agreement usually adopts the serial port;
only apply on serial ports COM1 COM10. Adopt this agreement, monitoring system as
the mainframe.
Setting method and parameter illustration as Figure 2-18 shows.
The exchange data of adopting NARI MODBUS agreement commonly involve: telemeter,
telesignal, Telecontrol Variable, and Teleadjust Variable, It configures for these data as below:
A. Parameter setting
Principle: infill the number of data size need to collect, then set other parameter of such data.
When the number of some data is 0, it indicate need not to exchange the data. For example
need to exchange telemeter variable, and infill the telemeter number need to exchange after
telemeter number, and then configure the option about telemeter.

19

2 Communication Management Software Package

SD 200

Parameter setting dialog box is as below figure shows. ( such as NARI speed regulator
communication)
B. Parameter illustration:
Setting address: corresponding setting address is from 1 to 254.
Telemeter number: the number of telemeter variable need to collect. Because different options
are for the different device, this option setting is from 0 to 125.
telesignal number: the number of telesignal variable need to collect. Because different options
are for the different device, this option setting is from 0 to 250.
Standby byte number: the number of standby byte need to collect. Because different options
are for the different device, this option setting is from 0 to 125.
Reading data protocol address: the start address of reading date in MODBUS agreement.
Because different options are for the different factory, this option setting is for it.
Reading data function code: the function code of reading data in MODBUS agreement.
Because different options are for the different factory, this option setting is for it.
Modify telemeter protocol address: write the start address of telemeter data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
Modify telemeter function code: write the function code of telemeter data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.

Figure 2-18
Modify telesignal protocol address: write the start address of telesignal data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
Modify telesignal function code: write the function code of telesignal data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
20

2 Communication Management Software Package

SD 200

Telemeter database start address: the start address of telemeter in database. Occupy the
telemeter address of LCU. Because different options are for the different project, this option
setting is for it.
Telesignal database start address: the start address of telesignal in database. Occupy the
telesignal address of LCU. The unit of telesignal occupying the database address is 1 byte, for
example 7 telesignal occupy 1 byte, and 9 telesignal occupy 2 byte. telesignal occupy the
telesignal address of LCU.
Confirm: confirm modification, close dialog box
Cancel: cancel modification.
Notice: The setting of typical devices adopting the NARI MODBUS protocol is as below:
A. NARI speed regulator:
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; speed regulating as the slave machine.
Name

Value

Name

Value

Address of the
device

2(Given by the
supplier )

Address of setting
telemeter protocol

10

Quantity of
telemeter

Code of writing
telemeter data function

16

Quantity of
telesignal

32

Address of writing
telesignal protocol

Quantity of standby
word

Code of writing
telesignal function

Address pf reading
data protocol

Starting address of
telemeter database

Undetermined

Code of reading
data function

Starting address of
telesignal database

Undetermined

B. GuangKongSuo excitation
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; excitation as the slave machine.
Name

Value

Name

Value

Address of the
device

2(Given by the
supplier)

Address of setting
telemeter protocol

Quantity of
telemeter

Code of writing
telemeter function

Quantity of
telesignal

4*16

Address of writing
telesignal protocol

Quantity of standby
word

Code of writing
telesignal function

Address of reading
data protocol

Starting address of
telemeter database
telemeter

Undetermined

Code of reading
function

Starting address of
telesignal database

Undetermined

21

2 Communication Management Software Package

SD 200

2.2.2.10. No. 103 agreement


Range of complication: No. 103 agreement applies to communicate between the device
adopting SAC TCP 103 protocol and monitoring system, which usually adopt Ethernet. It
only applies on the network ports ENET. The monitoring system collects the data of No.
103 agreement device when monitoring system as the mainframe. For requirement of update,
it keeps the port for No. 103 agreement as the slave machine.
Setting method and parameter illustration as Figure 2-19 shows.
The exchange data of adopting TCP103 agreement commonly involve: telemeter, telesignal,
Event telesignal, Alarm telesignal, Fixed value, Electric variable, Telecontrol Variable and
Time. It configures for these data as below:
A. Parameter setting
Principle: infill the number of data size need to collect, then set other parameter of such data.
When the number of some data is 0, it indicate need not to exchange the data. For example
need to exchange telemeter variable, and infill the telemeter number need to exchange after
telemeter number, and then configure the option about telemeter.
Parameter setting dialog box is as below figure shows. (Such as psl646 protector, the uplink
machine as the mainframe)
B. Parameter illustration:
As the mainframe in communication: usually monitoring system as the mainframe when
communicating to protector, must select this option.
Usage network: adopt TCP 103 to communicate in network, must select this option.
Demand Timing: need to time with devices, must select this option.
Demand control: when control the device must select this option.
Device serial number: the taxis of ports of the device begin at 1.
Setting IP address: Correspondingly set IP address.
TCP port: the TCP port of SAC TCP 103 fixup 1048.
UDP port: the UDP port of SAC TCP 103 fixup 1032.
CPU number: usually the number is 1, and maximum is 2 without any explanation.
telemeter serial number: select corresponding telemeter serial number to configure, and begin
at 1.
telemeter agreement code: the start address of telemeter in database, occupy the telemeter
address of LCU.
In a similar way, it can configure the database address of remote control, telesignal, alarm
telesignal, electric variable, Fixed value, and so on. telesignal is similar to telemeter, only the
unit of telesignal occupying the database address is 1 byte, for example 7 telesignal occupy 1
byte, and 9 telesignal occupy 2 byte. telesignal occupy the telesignal address of LCU.

22

2 Communication Management Software Package

SD 200

Figure 2-19
Notice: it needs to configure each above option for each CPU.
CPU serial number: select corresponding CPU serial number to configure, begin at 1.

2.2.2.11. SC 1801 agreement


Range of complication: apply to communicate between the device adopting SC 1801
agreement and monitoring system. SC 1801 agreement usually adopts the serial port; only
apply on serial ports COM1 COM10. Adopt this agreement, usually communicate to the
dispatch, monitoring system as the slave machine. For requirement of update, it keeps the
port for SC 1801 agreement as mainframe.
Setting method and parameter illustration as Figure 2-20 shows.
The exchange data of adopting SC 1801 agreement commonly involve: telemeter, telesignal. It
configures for these data as below:
A. Parameter setting
Principle: infill the number of data size need to collect, then set other parameter of such data.
When the number of some data is 0, it indicate need not to exchange the data. For example
need to exchange telemeter variable, and infill the telemeter number need to exchange after
telemeter number, and then configure the option about telemeter.
Parameter setting dialog box is as below figure shows.

23

2 Communication Management Software Package

SD 200

Figure 2-20
B. Parameter illustration:
Terminal number: order by dispatching terminals.
telemeter number: the number of telemeter needs to collect. Because different options are for
the different project, this option setting is from 0 to 180.
telesignal number: the number of telesignal needs to collect. Because different options are for
the different project, this option setting is from 1 to 240.
telemeter serial number: select corresponding telemeter serial number to configure.
telemeter maximum: the corresponding maximum of telemeter.
telemeter minimum: the corresponding minimum of telemeter. Usually with the maximum to
buildup the range of telemeter, and according to the actual range of telemeter. Modify with
dispatching terminals.
telemeter database address: the telemeter need to communicate in database is uncontinuous, so
need address of each telemetry variable in database. Because different options are for the
different project, this option setting is for it.
telesignal database address: the telesignal need to communicate in database is uncontinuous, so
need address of each telesignal variable in database. Because different options are for the
different project, this option setting is for it.

24

3 Database management Software Package

SD 200

3. Database Management Software Package

3.1. Function introduction


Database management software package apply to the management and maintenance of offline
real-time database (Such as RtimeDB.MDB). Under the provided interface, the slave machine can
easily amend various data property, which include telemetry variable, telesignal variable,
telecontrol variable, teleadjust variable, computing formula, operator, password, network
computer, on-site control cell and so on, the program can automatic load amended data property
into the real-time database.

3.2. Running program


Run SD200 installation program of monitoring software package, when finish the installation,
then SD 200 automatic software icon display in the Start Program menu, Database
management display below SD 200 automatic software, Click this icon to run the database
management software package; or DatabaseManager.EXE locate under the directory of C:\NR1001\BIN, double click it to run database management software package. As running the software
package, it can search the real-time database (RtimeDB.MDB) under the directory of C:\NR1001\DATAS, confirm this database to exist; otherwise database management software package
will abend.

3.3. Usage method


Run Database management, open the database management window as below figure shows, the
window includes three components: the left is Configuration area, the right top is Cartoon
area, and right bottom is Configuration display area. Configuration area include Measuring
point configuration configure the original variable of telemetry, telesignal, telecontrol and
teleadjust, etc; Account configuration configure according to the demand of account; Project
configuration system computer configuration, operator configuration, LCU configuration.
Double click any one option in Configuration area, Configuration display area in the left
bottom will display the content of configuration, click any one grid for editing in Configuration
display area will configure the content need.
There is a tool bar in the window, there are three buttons on it, which are Save, Add row and
Delete row, and Add row and Delete row can not apply on Measuring point configuration
and Account configuration, only apply on Project configuration. If add the corresponding row
in Project configuration, first click the display area by the mouse, select Add row and Delete
row.
When edit Configuration display area, it can use Copy and Paste.

25

3 Database management Software Package

SD 200

3.3.1. Measuring point configuration illustration

3.3.1.1. Telemetry variable


It involves electric variable, simulation variable, temperature variable and other variable. Electric
variable has 10 LCU, each LCU has 10 boards, and each board has 24 channels. Simulation
variable has 10 LCU, each LCU has 10 boards, and each board has 16 channels. Temperature
variable has 10 LCU, each LCU has 10 boards, and each board has 16 channels. Other variable
has 10 LCU, each LCU has 10 boards, and each board has 24 channels. The property of telemetry
variable include title, unit, upper limit, more upper limit, lower limit, more lower limit, dead zone,
grads, proportion coefficient (transformation ratio), survey range limit, project variable limit,
upper limit alarm, lower limit alarm, grads alarm, measuring point blockage, record, transmitting,
and teleadjust serial number.
A. Serial number and title
Serial number indicate the serial number of telemetry in database, the last number of serial
number of electric variable can edit, other serial number of simulation variable, temperature
variable and other telemetry variable cannot edit.
Title the title of telemetry variable.
B. Unit and transformation ratio
26

3 Database management Software Package

SD 200

It is measurement unit and transformation ratio of telemetry.


About AC, conversion coefficient is the transformation ratio of PT and CT for pressure and
current; about power, conversion coefficient is the product of transformation ratio for pressure and
current; the conversion coefficient of frequency and power is 1.
For temperature variable, the conversion coefficient confirm by the position of radix point.
For simulation variable, the conversion coefficient is 1. The conversion of simulation variable
confirm by measurement and project limit.
For other telemetry variable, sometime the conversion coefficient is 1, sometime it is not 1, it
confirm by material variable. The conversion coefficient of other telemetry variable confirms by
survey and project limit when conversion coefficient is 1.
For account telemetry, the conversion coefficient is 1.
Notice: It must be consider the influence of the measurement units to the conversion coefficient.
For example, when the unit of pressure is V, the conversion coefficient is 60, and then the unit
turns to KV, correspondingly the conversion coefficient may turn to 0.06.
C. Dead zone
In order to avoid the frequent alarm of telemetry variable undulating near the limit, it needs to set
the parameter of dead zone.
When the range of telemetry variable undulating greater than the width of dead zone, it considers
this telemetry variable exceed the limit. In a similar way, the telemetry variable going beyond the
limit greater than the width of dead zone, it considers this telemetry variable resume the limit.
D. Grads, grads alarm
It is the transformation of the telemetry variable per second. When the transformation of the
telemetry variable greater than the grads limit, select whether need grads alarm.
E. Upper limit, more upper limit, lower limit, more lower limit.
They are the limit of the telemetry variable.
F. Upper limit alarm, lower limit alarm
Demarcate the telemetry whether alarm when it exceed the limit.
G. Survey range limit, project variable limit
They are the survey range limit and project variable limit of the telemetry variable. Apply to the
survey range limit and project variable limit; transform survey variable to project variable for the
simulation variable and other telemetry variable.
H. Record, save interval
Demarcate whether store the telemetry variable in history database, save interval indicates how
long the telemetry variable store in history database.
I. Measuring point blockage
Do not collect and process the data when the measuring point blanks off.
27

3 Database management Software Package

SD 200

J. Transformation
The measuring point whether transform to other systems, such as dispatching, SYMIMIC, etc.
K. Teleadjust serial number
If need teleadjust for the measuring point by right button, input the corresponding serial number in
the teleadjust list.

3.3.1.2. Telesignal variable


Telesignal variables involve general telesignal, integrated telesignal and other telesignal. General
telesignal has 10 LCU, each LCU 1 board, and each board has 21.4 channels. Integrated telesignal
has 10 LCU, each LCU has 1 board, and each board has 21.4 channels. Other telesignal has 10
LCU, each LCU has 1 board, and each board has 21.4 channels. The properties of the telesignal
include title, normalcy, action description, reset description, reset alarm type, alarm picture,
manual position, telesignal statistic, measuring point blockage, double point information, action
alarm, action alarm type, action landing, action statistic, action flare, transformation, and
telecontrol serial number. And the definition of title and measuring point is same as the telemetry.
The property illustrates as below:
A. Serial number, title, normalcy
Serial number is the serial number of telemetry of the measuring point.
Title is the title of the measuring point.
Normalcy is the state of the corresponding physical device of the measuring point without
electrification.
B. Action description, reset description
The state of telesignal is action which normalcy change to unnormalcy, and is reset which
unnormalcy change to normalcy. The description for them is action description or reset
description.
C. Reset alarm type, action alarm type
Reset alarm type and action alarm type include state alarm, trouble alarm and event alarm.
D. Alarm picture
Select a picture number from the pull-down list. According to the definition, automatic open the
number of the picture. Select 99 indicates cannot quit picture as alarm.
E. Measuring point blockage
Do not collect and process the data when the measuring point blank off.
F. Telesignal statistic, action statistic, reset statistic
They count the quantity of telesignal statistic, action statistic and reset statistic.
28

3 Database management Software Package

SD 200

G. Action flare, reset flare


There is flaring hint the client as action or reset, after click the flare will disappear.
H. Action register, reset register
It whether needs to record as action or reset.
I. Measuring point blockage
Do not collect and process the data when the measuring point is locking.
J. Transformation
The measuring point whether transform to other systems, such as dispatching, SYMIMIC, etc.
K. Telecontrol serial number
If need teledcontrol for the measuring point by right button, input the corresponding serial number
in the teledcontrol list.

3.3.1.3. Telecontrol variable


Telecontrol variable has 10 LCU, each LCU has 5 boards, and each board has 21.4 channels. The
properties of telecontrol include: title, telecontrol condition, telecontrol condition satisfied,
telecontrol condition picture, relativity, corresponding telecontrol, waiting time, telecontrol flow
picture, protocol type, channel number, operation type, operation type, device number and
password.
A. Telecontrol condition, telecontrol condition satisfied, telecontrol condition picture
The three properties relate whether process the telecontrol. According to the telecontrol variable
and the relativity, judge the telecontrol condition whether to achieve the request, if not quit the
telecontrol condition picture.
For example, to No. 1 machine opening, its closedown telesignal is No. 1 machine opening
telecontrol condition. After sending out the command, monitoring program will judge the current
value of No. 1 machine opening telecontrol condition, if the telesignal variable to telecontrol is
positive correlation blockage, the value of telesignal variable is 1, means the telecontrol condition
is satisfied, contrarily the value is 0, means the operating condition cannot achieve; if the
telesignal variable to telecontrol is negative correlation blockage, the value of telecontrol variable
is 0, means the telecontrol condition is satisfied, contrarily the value is 1, means the operating
condition cannot achieve.
B. Relativity
This property relates to the success of telecontrol operating of the telecontrol variable. According
to the return telesignal variable and return relativity judge the telecontrol operating whether to
succeed.
29

3 Database management Software Package

SD 200

For example, to No. 1 machine opening, its return telesignal is No. 1 machine incorporate in
network. After sending out the command, monitoring program will judge the current value of
No. 1 machine incorporate in network, if the telesignal to telecontrol is positive correlation
blockage, the value of telesignal variable is 1, means the telecontrol operating succeed, contrarily
the value is 0, means the operating cannot succeed; if the telesignal to telecontrol is negative
correlation blockage, the value of telecontrol variable is 0, means the telecontrol operating
succeed, contrarily the value is 1, means the operating cannot succeed.
C. Telecontrol flow picture
When the telecontrol operating condition is satisfied, and the command succeeds in sending to
LCU, open the telecontrol flow picture. The flow picture indicates whether succeed in the
telecontrol operating.
D. Waiting time
It is the time of waiting complete operating by monitoring program. If pass the waiting time, the
return telesignal still unchanged, means fail to regulate.
E. Protocol type
It includes MODBUSTCP protocol, GEHCT protocol, TCP103 protocol, MODBUS protocol, and
CDT protocol.
F. Operating type, operating object, device number
Operating type means the number of telecontrol, device number means the number of LCU, and
operating object means that as using CDT protocol, 0 means disport, 1 means joint.
G. Channel number
When using Ethernet communication, serial ports are COM1 COM10.
H. Password
It whether need confirm the password as the telecontrol.

3.3.1.4. Teleadjust variable


The teleadjust variable has 10 LCU, each LCU has 1 board and 32 channels. The properties of
teleadjust variable include title, corresponding telemetry variable, waiting time, protocol type,
channel number, operating object, operating type, device number, password. The definition of title
is same as the telemetry variable.
A. Corresponding telemetry variable
It means the regulating object of the teleadjust variable, for example the regulating object No. 1
machine power regulating for the teleadjust variable is No. 1 machine power regulating for the
telemetry variable. As online running, monitoring program take the current value of the telemetry
variable as the basic value of the power regulating.
30

3 Database management Software Package

SD 200

B. Waiting time
It is the time of waiting complete operating by monitoring program. If pass the waiting time, the
return teleadjust still cannot achieve the target value, means fail to regulate.
C. Protocol type
They include MODBUSTCP protocol, GEHCT protocol, TCP103 protocol, MODBUS protocol
and CDT protocol.
D. Operating type, operating object, device number
Operating type means the number of teleadjust, device number means the number of LCU, and
operating object means that as using CDT protocol, 0 means disport, 1 means joint.
E. Channel number
When using Ethernet communication, serial ports are COM1 COM10.
F. Password
It whether need confirm the password as the teleadjust.

3.3.2. Computation configurations illustration


Computation configuration illustration includes computation telemetry configuration, the
computation telesignal configuration and computation formula configuration. The properties of the
computation telemetry configuration include: title, unit, upper limit, more upper limit, lower limit,
more lower limit, dead zone, grads, proportion coefficient (transformation ratio), survey range
limit, project variable limit, upper limit alarm, lower limit alarm, grads alarm, measuring point
blockage, record, transmitting, and teleadjust serial number. The properties of the computation
telesignal configuration include title, normalcy, action description, reset description, reset alarm
type, alarm picture, manual position, telesignal statistic, measuring point blockage, double point
information, action alarm, action alarm type, action landing, action statistic, action flare,
transformation, and telecontrol serial number. Each property sees as measuring point
configuration.

3.3.3. Project configuration illustration

3.3.3.1. Node computer configuration


Note computer property configuration include title, uplink machine IP address, downlink machine
IP address, operating position, host/reserve machine, using network, and quit password.
A. title, uplink machine IP address, downlink machine IP address
Title the title of several uplink machines
31

3 Database management Software Package

SD 200

Uplink machine IP address it is the IP address of network card communicating among several
uplink machines.
Downlink machine IP address it is the IP address of network card communicating between the
uplink machine and PLC.
B. Running position
Running position the running position of SD200 software, include all-in-one machine, master
machine, communication machine, information center/master terminal.
C. Host/reserve machine
It is the running method as master machine start up, select host machine or reserve machine, if do
not master machine, then unnecessary select.
D. Using network, quit password
Using network it is whether the computer using network.
Quit password it whether need password when quit from SD 200 software running on the
computer.

3.3.3.2. Authority password configuration


The properties of authority password configuration include serial number, name, login and
authority. It can select super administrator, system administrator, operator, running engineer,
general user in the authority.

3.3.3.3. LCU configuration


The illustrations of LCU configuration include serial number, title, blockage and IP address.

3.4. Operating illustration


It can click the Add or Delete button on the tool bar when need to do in the project
configuration, it needs to click the save button for saving after all operation.

32

4 Interface Design Software Package

4.

Interface design software package

4.1.

Introduction

SD200

Graphics software (interface design program) GE, may redesign the monitoring picture
according to the different requirement of clients. It can add various lines, paints, time for the
beautified picture, add the telemetry and telesignal variable for monitoring the operating
information of power plant, the telecontrol and teleadjust variable for controlling the operating
condition of power plant, and add Picture Index for fast searching the picture.

4.1.1.

Summarize

Interface design program GE bases on WINDOWS NT/95/98/2000 operating system, it and


graphics display (online monitoring) program, form design, display, print software package,
communication management database management package, data management database
management software package and graphics edit database management software package consist
of a full graphics-interface computer monitoring software package for hydraulic power plant
SD200.

4.1.2.

User interface

UI is the important component in the whole monitoring system, through the graphics it indicates
the condition of real-time devices and parameters, User can inspect the spot operating
information. UI produces by the graphics software GE, through using the standard object and the
denotation by some objects, user can build the UI indicates the collect data.

4.1.3.

Startup

User can click Start Program SD 200 automatic software Graphics software GE to
open in WINDOWS NT/95/98/2000, also double click c:\nr-1001\bin\ge.exe to open the graphics
software GE.

4.1.4.

Interface illustration

The interface produced by the graphics software GE adopts many file operating method provided
by Windows. The frame includes title bar, menu bar, standard tool bar, SD 200 tool bar, drawing
area, status bar and so on.

33

4 Interface Design Software Package

4.1.5.

4.1.5.1.

SD200

Menu introduction

Main menu

Main menu is that user performs their operation through the mouse and keyboard selection. The
main menu of graphics software GE includes file, edit, view, insert, rank, option, data definition
and help. Some operations carry out through the menu item in main menu, also through the
button in tool bar.

34

4 Interface Design Software Package

4.1.5.2.

SD200

Submenu

File menu includes new, open, save, save as, print, print preview, print setting, latest
opened 1.4. file and quit.
Edit menu
Edit menu include cut, copy, paste, delete object, cancel link, graphics edit, form edit, and
all select.

View menu
View menu include standard tool bar, SD 200 tool bar, status bar, roam, regulate screen and
zoom.

Insert menu
Insert menu include mark object, line, rectangle, ellipse, polygon, polyline, camber line, text,
time, telemetry, pulse, telesignal statistic, control, bar graph, strobe, curve, meter graph, standard
graphics, bitmap, animation, retrospect, protect value and setting value.

35

4 Interface Design Software Package

SD200

Rank menu include flush left, flush top, flush right and flush bottom.

Option menu include gridding, Terminal, background, line color, infill color, font, line width
and color configuration.

Data definition menu include definition formula and definition counting formula.
36

4 Interface Design Software Package

SD200

Help menu include about interface design.

4.2.

Basic usage

Graphics software (interface design program) GE, may redesign the monitoring picture
according to the different requirement of clients. It can add various lines, paints, time for
beautifying picture, add the telemetry and telesignal variable for monitoring the operating
information of power plant, the telecontrol and teleadjust variable for controlling the operating
condition of power plant, and add Picture Index for fast searching the picture.
The method of adding various lines, paints, time for beautifying picture is similar to the general
graphics edit software. Here mostly introduce telemetry (include curve, bar graph and meter),
pulse, telemcommand variable, telecontrol variable, teleadjust variable and adding picture
quoting method.

4.2.1.

Window management

Window management includes the management of display status of graph edit window, standard
tool bar, SD200 tool bar and status bar. It can display or hide the standard tool bar through
clicking the option in standard tool bar under the view menu; It can display or hide SD 200 tool
bar through clicking the option in SD 200 tool bar under the view menu; it can display or hide
the status bar through clicking the option in status bar under the view menu.
Drawing area can set or cancel the gridding, click the gridding option under option menu by
mouse, or use Alt + O to open the option menu, and then use Crtl + G to set or cancel the
gridding; the aim of using gridding can easily regular the drawing. When user wish to see the
part effect of drawing, click the roam option under the view menu, press left button in the red
line box in the ejecting roam window, then put the red line box to daggle the appoint position.
Because fresh the screen by WINDOWS, it will leave some tracks on the screen, for example
drawing a rectangle on the screen, latter move the rectangle, but leave some lines on the original
position, it can clear by regulating the screen. In addition, this software provides the function of
screen zooming display, click the zoom option under the view menu, it ejects a zoom dialog box,
it can select eight display proportions of system provided, and input the arbitrary display
proportion in the percent box.

4.2.1.1.

Drawing parameter selection

Before drawing user needs to confirm some necessary parameters: screen background color, line
color, infill color, font, line width and color setting. After confirm the parameter of background
37

4 Interface Design Software Package

SD200

color, line color, infill color, font, and line width, it will display the current color, line width and
font on the graphics of user drawing.
When user needs to amend the property of the graphic primitive, first select one or more graphic
primitive, through the parameter under the selection option, it can change the property of the
graphic primitive. The method of selecting some graphic primitives: first click the graphic
primitive by mouse, when press the Ctrl button, click the other selection graphic primitive by
mouse.

4.2.1.2.

Display or hide Terminal

Through clicking the Terminal option under the option menu, it can display or hide
Terminal as drawing.

4.2.1.3.

Selection screen background color

Select the background option under option menu, system eject the dialog box of color selection,
in the basic color and self-defined color, after select the color, press Confirm. The defined
screen background of system is dark green. RGB (61.4.,128,128)

38

4 Interface Design Software Package

4.2.1.4.

SD200

Select color

When user select the line color, can click line option under the selection option to select the
color. In the basic color or self-defined color of ejecting color selection dialog box, select the
color, press Confirm. To the finished graphic primitive, if change the color, first select the
graphic primitive, and change the line color; if select some graphic primitives, and involve multicolor, here need to all selected line color of the graphic primitive turn to the current line color.

4.2.1.5.

Selection infill color

When draw infill circularity and infill rectangle, need select the infill color, click the infill color
option under the selection menu to select infill color. In the basic color or self-defined color of
ejecting color selection dialog box, select the color, press Confirm. To the finished graphic
primitive, if change the color, first select the graphic primitive, and change the infill color; if
select some graphic primitives, and involve multi-color, here need to all selected infill color of
the graphic primitive turn to the current infill color.

4.2.1.6.

Font

Click the font option under the option menu to eject the dialog box for selection font, select the
proper font, font type and size. When user needs to amend the existent literal font, font type and
size, select these characters, then select font, it can amend the font, font type and size as need.

4.2.1.7.

Selection line width

The line width submenu in option menu provides 5 kinds of line width to select: single line
width, double line width, triple line width, quadruple line width, and quintuple line width. When
draw the line, circularity, rectangle and polygon, confirm the size of line and frame, select the
proper line width. System default is single line width.
Click the option under the line width submenu of option menu to select the corresponding line
width. Once select the type, users beeline, rectangle and circularity drew will display as the
current line width type. When user needs to amend the existent line width of beeline, rectangle
and circularity, first select these graphic primitive, then select the line width, it can turn the line
width type of beeline, rectangle and circularity as need.

4.2.1.8.

Selection color setting

Click the color setting option under the option menu to display the user self-defined color for
error and exceeding telemetry and telesignal. These items include: telemetry blockage,
temecommand blockage, telemetry exceeding upper limit, telemetry exceeding more upper limit,
telemetry exceeding lower limit, telemetry exceeding more lower limit and error data.
39

4 Interface Design Software Package

4.2.2.

SD200

Basic graphic primitive

Graphics edit software GE provides several basic elements for user selection as below:
Line: include horizontal line, vertical line, polyline, camber line and random beeline
between two points.
Rectangle: include infill and uninfill rectangle.
Ellipse: include infill and uninfill ellipse
Polygon: include infill and uninfill polygon
Text: the character string consist of Chinese and English
Time: system time
Standard graphic primitive: the graphic primitive editor produces the graphic primitive.
Telemetry
Telesignal
Telecontrol
Control
User needs to select the drawing properties such as color, line width, font and infill color before
drawing. These realize through clicking the submenu option under the option menu. If amend
existent the property of the graphic primitive, first select these graphic primitives, control the
operating to amend the property of the graphic primitive.

4.2.2.1.

Line

Beeline
Before user draw the beeline, first select line color and width to select the color and width of the
beeline. Then click one of general line, horizontal line and vertical line in the submenu under the
eject menu (according to the different beeline select different choice), here cursor change to +,
in the drawing area, press the left mouse button, confirm the start point, loose the mouse after
dragging mouse to another end point.
Polyline
Before user draw the polyline, first select line color and width to select the color and width of the
polyline. Then click polyline option under the eject menu or select the button of SD 200 tool bar,
here cursor change to +, in the drawing area, press the left mouse button, confirm the start
point, loose the mouse after dragging mouse to another end point, and press the mouse button
until to the last end point, click the fight mouse button to complete in the drawing area.
Camber line
Before user draw the camber line, first select line color and width to select the color and width of
the camber line. Then click camber line option under the eject menu or select the button of SD
200 tool bar, here cursor change to +, in the drawing area, press the left mouse button, confirm
the start point, loose the mouse after dragging mouse to another end point.

40

4 Interface Design Software Package

4.2.2.2.

SD200

Rectangle and infill rectangle

Before user draw the rectangle, first select line color and width to select the color and width of
the rectangle; if drawing infill rectangle, may select the infill color of infill rectangle.
Click uninfill or infill option under the eject menu or select the button of SD 200 tool bar, here
cursor change to +, in the drawing area, press the left mouse button, confirm the start point,
drag the mouse, there is a dummy box follow the mouse, loose the mouse at another end point.

4.2.2.3.

Ellipse and infill ellipse

Drawing method is similar to the rectangle.

4.2.2.4.

Polygon and infill polygon

Before user draw the polygon, first select line color and width to select the color and width of the
polygon; if drawing infill polygon, may select the infill color of infill rectangle.
Click uninfill or infill option under the eject menu or select the button of SD 200 tool bar, here
cursor change to +, in the drawing area, press the left mouse button, confirm the start point,
drag the mouse to the next point, and press the left mouse button to the next point until to the end
point, loose the right mouse button to complete.

4.2.2.5.

Text

User can input characters, add character string (Chinese or English) in the current display
drawing. The size, font and color of character string can select in the tool bar or menu option.
Select the existent character string to amend the property.
Click the text option under eject menu or the button of selecting under SD 200 tool bar, then the
cursor turn to +, input the character position in drawing area, press the left mouse button,
confirm the start position, there is a vertical line display in the drawing area, then input the
character.

4.2.2.6.

Time

Click the time option under eject menu, the cursor turn to +, display the time position in the
drawing area, press the mouse left button, drag the mouse, there is the simulating box follow the
mouse, loose the mouse at another point, system eject a time setting dialog box, select the
specific format for time display, then press confirm button to complete.

4.2.2.7.

Telemetry

Select Telemetry option under Insert menu, the cursor turn to +, press the left mouse
41

4 Interface Design Software Package

SD200

button where you need to display position, drag the mouse to draw a proper rectangle, loose the
mouse, select the proper integer and decimal fraction to add a telemetry variable. In this
telemetry drawing rectangle, press the right mouse button to amend the color, font of the
telemetry, and can cut and copy to the telemetry.

4.2.2.8.

Histogram

From Histogram submenu in Insert menu, insert the group histogram and single histogram.
Group histogram
Select Group histogram in Histogram submenu under Insert menu, the cursor turn to +,
press the left mouse button where you need to display position, drag the mouse to draw a proper
rectangle, loose the mouse, select the proper group count, each histogram, variable, maximum
and minimum to add a group histogram. Press the right mouse button in rectangle range of each
histogram to amend the line color, infill color of the histogram, and can cut or copy to whole
histogram.
Single histogram
Single histogram includes two kinds: coordinate and uncoordinated, insert method is same as
group histogram.

4.2.2.9.

Curve

From Curve submenu in Insert menu, insert general curve, real-time curve and group curve.
General curve
General curve can display the telemetry for yesterday 21.4. hours curve, today 21.4. hours plan
curve and today changeable curve until current time.
Select General curve option in Curve submenu under Insert menu, the cursor turn to +,
press the left mouse button where you need to display position, drag the mouse to draw a proper
rectangle, loose the mouse, select the proper display property, variable, maximum and minimum
to add a general curve. Press the right mouse button in a general curve to amend the line color of
the curve, and can cut or copy to whole curve.
Group curve
The group curve can display today changeable curve of some telemetry until current time. The
minimum time definition of the curve is 5 minutes.
Select Group curve option in Curve submenu under Insert menu, the cursor turn to +,
press the left mouse button where you need to display position, drag the mouse to draw a proper
rectangle, loose the mouse, select the proper curve number, variable, maximum and minimum to
add a group curve. Press the right mouse button in a group curve to amend the line color of the
curve, and can cut or copy to whole curve.
Real-time curve
Real-time curve can display the changeable curve of some telemetry in 300 seconds. The time
definition of the curve is 6 seconds.

42

4 Interface Design Software Package

SD200

4.2.2.10. Meter
Select Meter graphics submenu under Insert menu, the cursor turn to +, press the left
mouse button where you need to display position, drag the mouse to draw a proper rectangle,
loose the mouse, select the variable, maximum and minimum to add a meter graphics. Press the
right mouse button to amend the color of dial and line, and can cut or copy to whole meter
graphics.

4.2.2.11.

Strobe

It is a graphical interface mainly displays the opening of strobe.

4.2.2.12.

Pulse

The insert method of pulse is similar to the telemetry. And it can select apex, vale, calm and
different times as formula definition.

4.2.2.13. Telesignal
Insert-Standard graphical primitive, eject NR-1001 standard graphical primitive dialog
box, select Switch or Strobe, press Confirm, in the eject window, press left button to put
the graphical primitive selected to drag into design picture. Press the right mouse button to define
the formula for the telesignal, and can cut and copy for it.
Telesignal statistic
Insert-Telesignal, it can define the telesignal statistic information.

4.2.2.14.

Telecontrol

Insert-Telecontrol, the cursor turn to +, press the left mouse button where you need to
display position, drag the mouse to draw a proper rectangle, loose the mouse to add a telecontrol
variable. Press the right mouse button to amend the color infill color and font of the telecontrol,
define the formula for it, and can cut or copy.

4.2.2.15.

Teleadjust

Insert-Teleadjust, the cursor turn to +, press the left mouse button where you need to
display position, drag the mouse to draw a proper rectangle, loose the mouse to add a teleadjust
variable. Press the right mouse button to amend the color infill color and font of the teleadjust,
define the formula for it, and can cut or copy.

43

4 Interface Design Software Package

4.2.2.16.

SD200

Picture index

Insert-Picture index, the cursor turn to +, press the left mouse button where you need to
display position, drag the mouse to draw a proper rectangle, loose the mouse, infill the proper
title and hit to add a picture index. Press the right mouse button to amend the color infill color
and font of the picture index, and can cut or copy for it.

4.2.2.17.

Color configuration

Option-Color configuration, it can define the exceed telemetry variable display in the
graphic display program and the measuring point color being blanked.

4.2.2.18.

Definition formula

Date definition-Definition formula, it can define the formula of the telemetry variable and
telesignal variable.

4.2.3.

Standard graphical primitive

Click standard graphical primitive under the eject menu, system will eject the nr-1001 standard
graphical primitive dialog box, select needed single or double graphical primitive and click
confirm button, system will eject another dialog box, it can select more specific graphical
primitive in it. Click the graphical primitive by the left mouse button to select, if it is double
graphical primitive, press F8 to preview the difference as different value for the graphical
primitive. After click the graphical primitive by left mouse button, press the left mouse button to
drag to the drawing area.

4.2.3.1.

Bitmap

Click the bitmap option under eject menu, the cursor turn to +, at the position of display
bitmap in the drawing area, press the mouse left button, drag the mouse, there is the simulating
box follow the mouse, loose the mouse at another point of the rectangle, system eject a open
(file) dialog box, select the bitmap need to add into the drawing area (suffix is bmp) and press
confirm button to complete. The bitmap file is built by users who use the bitmap editor Paint
provided by Windows.

4.2.3.2.

Animation

It applies to display the revving graphical interface, select three pictures and define the formula
as ejecting, the graphic display program will alternate display pictures with 3 different speeds
according to the definitional revving signal. Notice the definitional revving signal must define
44

4 Interface Design Software Package

SD200

the limit.
Click the bitmap option under eject menu, the cursor turn to +, at the position of display
bitmap in the drawing area, press the mouse left button, drag the mouse, there is the simulating
box follow the mouse, loose the mouse at another point of the rectangle, system eject first
selection dialog box, select a bitmap which suffix is bmp, press the confirm button, system eject
second selection dialog box, reselect a bitmap which suffix is bmp, press the confirm button,
system eject third selection dialog box, reselect a bitmap which suffix is bmp, press the confirm
button to complete.

4.2.3.3.

Setting value

Click the setting value option under eject menu, the cursor turn to +, at the position of display
bitmap in the drawing area, press the mouse left button, drag the mouse, there is the simulating
box follow the mouse, loose the mouse at another point of the rectangle, system eject first setting
value dialog box to select the integer digits and decimal digits of display the telemetry variable,
press the confirm button to complete.

4.2.4.

4.2.4.1.

Graphics edit

Select the object

The processing of graphics edit, first must select the object, the method is:
1. Click the button on SD200 tool bar, and then click the left mouse button to select the object
needed.
2. Move the mouse to the left top of the object, press the left mouse button, pull a simulating box
involve the object, all objects in the box will be selected.
3. If it needs to add objects out of the selection, move the mouse to new object, press CTRL
button and left mouse button.
4. Click all select option under edit menu to select all graphical primitives in the selection
picture.
If it needs to cancel the selection object, move the mouse out of the object, press the left mouse
button, all selection object boxes will disappear, indicates selection is cancelled.

4.2.4.2.

Change size

When it needs to change the size of a graphical primitive, select the graphical primitive, move
the mouse to the four squares of box, the cursor turn to double arrowheads, press the left mouse
button, drag the mouse, loose the mouse as adjusting the proper size, press left mouse button out
of the graphical primitive to complete.
Notice: when change the size, it can cause the bitmap distortion because of the operation error.
So the bitmap size cannot change too much, and reduce the changeable times.
45

4 Interface Design Software Package

4.2.4.3.

SD200

Move

When it needs to move the position of a graphical primitive, select the graphical primitive, when
press the CRTL, press the direction button on the keyboard, the object will move; or move the
mouse to the graphical primitive, press the left mouse button to drag the mouse to the new
position, the object will move.

4.2.4.4.

Cut

If it needs to copy the graphical primitive, must put the object copy to the cutting board, Cut is to
delete the selection graphical primitive, and copy it to the cutting board. The method of Cut is
same as WORD.

4.2.4.5.

Copy

Copy is to copy the selection graphical primitive to the cutting board. The method of Copy is
same as WORD.

4.2.4.6.

Paste

Paste is to copy the content in cutting board to the picture. The content in cutting board can copy
from the graphics software GE, also from other graphics software. The method of Paste is same
as WORD.

4.2.4.7.

Delete

Delete object is to delete the graphical primitive from the picture. The method of Delete is same
as WORD.

4.2.4.8.

Picture regulation

It is to regulate the relation between graphical primitives. The method of Delete is same as
WORD.

4.3.

File management

The graphics file built by the graphical software GE can provide the real-time monitoring
software to display the graphics. The graphical file save as directory c:\nr-1001\pic, the suffix
is .ng. The system has a graphical file for main graphics main graphics.ng, when the system
startup, it automatic transfer the graphical file for main graphics display the main picture. When
the system display any picture, it can return to the main graphics by the graphics tool bar.
46

4 Interface Design Software Package

4.3.1.

SD200

Build new file

This menu is to build new graphical file. Select the new option under the file menu, or press new
file button on the standard tool bar, or press Alt+F, Ctrl+N to build a new graphics window.

4.3.2.

Open file

When user needs to amend current graphics, select the open option under file menu, or press
open file button on the standard tool bar, or press Alt+F, Ctrl+O, system will eject a graphical
dialog box, according to the title to select the file needed to open a current graphics.

4.3.3.

Save file

After finish graphics edit, it can save the result, click the save option or save as option under file
menu, or click the save button under standard tool bar, or press Alt+F, Ctrl+S, system will eject
save file dialog box, it can input the new file name, also select existent file names. When select
the existent file name, the current graphic will cover the old one.

47

4 Interface Design Software Package

4.3.4.

SD200

Print

Click the printer option under file menu or the print button under standard tool bar, or press
Alt+F, Ctrl+P, system will eject the print dialog box; user can select the printer, set the property
of print, select print range and copy.

4.3.5.

Print preview

After set the material and medium of printer, it can click the print preview option under file
menu, or press Alt+F, Ctrl+V, to preview the printing effect, it can to preview the printing effect,
it can forward turn or back turn preview for some pages.

4.3.6.

Print setting

Click the print setting option under file menu, or press Alt+F, Ctrl+R, system will eject the print
setting dialog box, user can select the printer, according to the selection printer to select the size,
source of paper and the print direction.

4.3.7.

Quit

Click the quit option under file menu, or press Alt+F, Ctrl+X, it can close all opened files, quit
48

4 Interface Design Software Package

SD200

the graphical software GE. For the unsave file, it will eject a dialog box for user selection or not.

4.4.

Graphical primitive editor

The graphical primitive editor nb.exe applies to edit the graphical primitives album. The
system default provides a set of graphical primitives, such as the transformer, switch, strobe, tide,
etc. The system can use editor self-define the graphical primitive and add it to the graphical
primitives album.

4.4.1.

Open graphical primitive editor

Click the graphical primitive editor option under edit menu, or press Alt+E, Ctrl+F to open the
graphical primitive editor.

4.4.2.

Produce graphical primitive

Produce a new graphical primitive, first click the new option under editor file menu, then select
the proper parameter of view, proportion, line width menu, it can use every option under picture
menu and left shortcut tool bar to complete the new graphical primitive. After drawing click save
or save as to save the graphical primitive. It will eject the dialog box as saving, if drawing is
single graphical primitive, select single value in the sort and select the transformer, input the file
49

4 Interface Design Software Package

SD200

name. (The suffix of file is 0); if drawing is double graphical primitive, select double value in the
sort and select the corresponding kind, input the file name. Notice: if the double graphical
primitive of drawing is 1, the suffix of file name is .1, if the double graphical primitive of
drawing is .0, the suffix of file name is .0. So a graphical primitive respond to two file names, .0
and .1, which delegate the display this double graphical primitive as 0 and 1.

4.4.3.

Usage graphical primitive

The graphical primitive after editing provides for drawing. Click the standard graphical primitive
option under eject menu, the system eject nr-1001 standard dialog box, select needed single
value or double value and press confirm button, the system will eject another dialog box, it can
select specific graphical primitive in there. Click the left mouse button to select the graphical
primitive, if it is the double value, press F8 to preview the display difference as the different
value. Click the left mouse button to select the graphical primitive, press the left mouse button to
drag to the drawing area.

4.4.4.

Link and cancel graphical primitive

The link and cancel the graphical primitive is build the connection between the dynamic
graphical primitive and the measuring point in database, after that, the dynamic graphical
primitive can indicate the spot actual operating information, it changes as the actual operating
information.
To build the connection of the graphical primitive, select the graphical primitive, click the
definition formula option under data definition dialog box ejecting, select the measuring point in
the database, press confirm button to complete the connection. To cancel the connection, first
select the graphical primitive, and then click the cancel option under edit menu to complete.

50

5 Graphics Display Software Package

SD200

5. Graphics Display (online monitoring) Software Package

5.1. Picture display


After the program startup and the slave machine update to the master machine, it will automatic
show the main graphics. Press the button on the left tool bar of the screen to close the current
window, and to zoon or roam the current window. It can directly open some important graphics of
the main graphics, picture index, main simulation graphics, and power plant information.
When the simulation in the graphics exceed to the limit, the value will display as the userdefinition color, to notice the man on duty.
When the interruptions switch change, the switch will flash to notice the man on duty. Press
Telesignal confirm option on the right mouse button menu for the switch, it can stop the flash.
Press Telesignal all confirm option on the right mouse button menu on the blank of graphics, it
can confirm the flash telesignal in the graphics.

5.2. Picture print


File Print setting, Print preview Print, it can complete the setting printer and the
current picture preview and print. It can change the size of paper from zooming of the picture.

5.3. Alarm
Click the alarm button on the left of screen to open the alter widow. Alarm information divides
three sorts: alarm for simulation exceeds the limit, alarm for changeable switch (include
information, trouble and accident) and alarm for self-check.
The downlink machine program information is on the right screen of bottom status bar, display
newest alarm information.

5.3.1. Alarm for simulation exceed the limit


Its information includes time, measuring point description, value, source and property. For
example:
1999/01.4./01 12:23:31.4.:000; No.1 machine pressure Uab; Exceed the lower limit; 5.9 LCU1;
Exceed the limits.
Indicate: 1999 year 1.4. month 1 day 12 hour 23 minute 31.4 second, No.1 machine exceed the
limit of the pressure Uab, value is 5.9, source is No.1 machine.

5.3.2. Alarm for changeable switch


Its information includes time, description, source, and property.

51

5 Graphics Display Software Package

SD200

5.3.3. Alarm for self-check


Its information includes trouble time, error information and error code.

5.4. Remote Control


Press the right mouse button on the remote control, eject the confirm box whether process,
confirm the operation, eject the input box for number and password of operator, input the proper
code and password and attain the condition, the uplink machine will send the operating command
to LCU. After that eject flow picture. If do not attain the condition, eject the picture for blocking
condition of operation, for checking the specific reason.
When the uplink machine sends the command to LCU, it is possible to failing send because of the
network communication. Then the program will enquire whether retry to connect, press Confirm
to retry to communication once more.

5.5. Events record


Select Events schedule button from the left tool bar, it can select the events record. It includes
register alarm information and operating record. When open the schedule, default display is all
events of current day, if only check the operating record, it can select Operating record button
by the mouse, press Fresh button. If check the events record of all the time, it can delete X in
Current day record box and Time limit box, press Fresh button. If check the events record
of the moment, it can click Time limit box, confirm the selection time in the ejecting dialog box,
then press Fresh button.
After opening the events schedule, if there is new event happen, press Fresh button to add the
newest record to the list.
The limit of events record is 1000 pieces. The man on duty stores the events to the file from
Save button, for checking after then.

5.5.1. Uplink machine operating record


It includes the command record and operating result record.
The command record involves operating time, operator name and operating content.
The operating result record involves operating content and operating result.
When the operating command send to LCU, maybe because of the communication or other reason,
the result cannot reply after delay, then the program will record the events for XXXX operating
result not reply or XXXX operating delay.

5.5.2. Spot (LCU) operating record


When the operator presses the LCU button to operate, the program will record the spot events. The
record content cannot include the operator name, other is similar to the uplink machine.

52

5 Graphics Display Software Package

SD200

5.5.3. Record
1998/01.4./02 12:21.4.:11.4. line 110 , close 1001 switching-out operation
It is denotes closing command 1001 at the line 110 sent to CB by the PLC in 1998/01.4./02
12:21.4.:11.4.

5.6. Events print


Except the alarm information display on the screen, it also can print by the printer. See also in
4.13. Option
In the events schedule, press Print to print the current events record in the schedule.

5.7. Master and slave machine switch


The alarm information can display on the screen, also update to the master machine through
Update to master menu in System configuration menu. Another machine turns to the slave
machine.
If the computer is as the master machine, then Update to master option cannot select. When the
master machine close or trouble, the slave machine automatic updates to the master machine.
In two machines, CONTROL1 startup is automatic as the master machine; CONTROL2 startup is
automatic as the slave machine. Then if CONTROL1 cannot startup, CONTROL2 will automatic
updates to the master machine. If two machines cannot compete for the master machine,
CONTROL1 priority is as the master machine, CONTROL2 is as the slave machine.

5.8. LCU locking and unlocking


Press LCU setting option on the right mouse button shortcut menu to lock or unlock the LCU.
When LCU is locking, the uplink machine cannot collect or process the data of LCU.

5.9. History data store


Main computer automatic save the necessary real-time data to the database per 10 minutes.

5.10. 5.10. Self-check and reset


SD200 graphics display program has the self-check function. Because adopting the multithreading
programme technology, when the accident causes the trouble, it can make the computer to
automatic reset, recover to the order.

5.11. Mutual-check
In the double systems, the master machine will automatic checkout the operating condition termly.
When the master machine cannot work or quit with the accident, the slave machine automatic
updates to the master machine, ensure the system not to break.

53

5 Graphics Display Software Package

SD200

5.12. Option
Press Option on Switch to select the monitoring program to work.

5.12.1. Password check mode


SD 200 system provides 2 kinds of operating password check mode: Connect and Single.
When select Connect mode, the system keeps the name of operator on duty, it automatic regards
the man on duty as the operator when registering the operating record. It can connect through the
left side PASS button on the screen.
When select Single mode, the system needs to request the number and password of the operator
when each operation. The man on duty regards as the operator when registering the operating
record.
Notice: the password of system operator divides two sorts: the operator who owning the first sort
password has priority to amend system parameters, include LCU blockage and measuring point,
but it cannot operate the spot device. The operator who owning the second sort password has
priority to operate the spot device, but it cannot amend the system parameter.

5.12.2. Print alarm information


When selecting the option, the necessary alarm information needs to send the printer to print, or
all the alarm information cannot print. See also 4.6. Events print.

5.12.3. Automatic show alarm picture


When selecting the option, the corresponding alarm picture shown when the telesignal change.
When the operator does not want to automatic show the alarm picture disturbing the monitoring
picture, it can cancel this option.

5.12.4. Subwindow maximization


When select this option, the new open picture will automatic maximize. Then the screen only
shows a picture.
When the man on duty wants to display several pictures on the screen at the same time, it can
cancel this option. Then the new open sub-picture cannot automatic maximize, the operator can
adjust the size and position.

54

6 Report Software Package

6.

Report Software Package

6.1.

Report system basic concept

SD200

Report system program includes report design, display, and print program. SD200 software
report system is base on EXCEL.

6.2.

Report system access

REPORT
BUTTON

Startup SD200 interface display software package, the left picture will display the tool bar, the
report button as shown as above. Press the report button, appear Use macro, click yes, then
access the report design interface based on EXCEL. And appear the report tool bar as below
figure shows.

There are five buttons on the report tool bar; they are Access report design status, Report data
inquire, Events inquire, Report management, and Hide display EXCEL menu from left to
right.

6.3.
6.3.1.

Report design
Access report design status

Click Access report design status button, appear password input dialog box as below shows,
input password sd200, then access report design status.

55

6 Report Software Package

6.3.2.

SD200

Report management

Access report design status, click Report management button, appear the report management
dialog box as below shows. User can do several things as below through the report management
dialog box:
1. Create a new report: input the repot name as wanted in new report name:, such as 3# unit
report, set the property of report such as height of row, col width, whether automatic draw form
and so on, click new button, the new report has built. EXCEL will display the name of new
report.
2. Delete a report: select the name of report in the report list, click Delete button to complete.
3. Amend the report: if user wants to amend the property of report such as height of row, col
width, select the name of report in the report list, set the property of report such as height of row,
col width, whether automatic draw form and so on, click Amend button

56

6 Report Software Package

6.3.3.

SD200

Data definition

Access the report design status, double click any grid in the form, appear data definition dialog
box as below shows. User can do several things as below through the report management dialog
box:
1. Define a data point: if want to start to display any point history data report in the grid, it can
select the measuring point, select the measuring point in the selection box, define the display
property of measuring point, such as Start point, Continuous point, Time interval, Up or
down, press Confirm button to complete.
2. Amend the point property: if user wants to amend the point or the property of point, such as
Start point, Continuous point, Time interval, Up or down, etc. Then click the defined
grid, re-select the point or re-amend the property, press Amend button to complete.
3. Delete the defined point: if user wants to delete the defined point, then click the defined grid,
press Delete button to complete.

6.4.

Report display

After defining the report, if want to view the content of history data report, then click report
data search button, and appear the dialog box as below figure shows.
57

6 Report Software Package

SD200

Press the confirm button, and then can appear the history data of defined point, as below figure
shows.
Remark: (1). If user needs to do some data statistic, account, please refer to some high level
function of Microsoft EXCEL. (2). The report date display fixup at First row, second row,
please do not define data in these grids for users.

58

7 History Data Search Software Package

7.

SD 200

History Data Search Software Package

The history data online search program is the part of SD200 software package for searching
history data. It completes the curve search and data form search, also switch between the curve
interface and the form interface, and display the two interfaces in the same interface. The
program interface is as Figure 7-1 shows.

Figure 7-1

7.1.
7.1.1.

Interface component and basic usage


Interface composing factor

Before introducing the program usage, introduce the interface composing factors for data online
search program:
Menu bar ----- below the title bar, display by the character.
Tool bar ----- below the menu bar, display by the graphic and character, can display or hide.
Float tool bar ----- below the tool bar
Selection area ----- the left window below the float tool bar, can select display or undisplay.
Display area ----- the right window below the float tool bar, locate the right of selection
59

7 History Data Search Software Package

SD 200

area.
Status bar ----- the bottom of the whole program, can display or hide.

7.1.2.

Interface basic operation

The complex tool operating steps in the menu bar, tool bar and float tool bar.

7.1.2.1.

Time search

Step: 1. Click the calendar display on the float tool bar for searching the date, display as Figure
7-2 shows.
2. Select the search date, then calendar automatic close to complete the time setting.

Figure 7-2

7.1.2.2.

Color setting

Method: 1. Click Color on the tool bar, appear the dialog box as Figure 7-3 shows. Otherwise,
Menu ----- Setting ----- Set color also appears the dialog box as Figure 7-3 shows.
2. Click the list bar on the dialog box for data information, select the option of setting color,
then the button under colors will display the selection current color.
3. Click the button under colors, push the color box as Figure 7-4 shows, select the needed
color to confirm, close the color box, back to the dialog box for the curve color setting, the
button under colors display the wanted color, click to confirm to complete the setting.

Figure 7-3
60

7 History Data Search Software Package

SD 200

Figure 7-4

7.1.2.3.

Subsection display time setting

Step: 1. Menu ----- Setting ----- Subsection display, can push the dialog as Figure 7-5
shows.
2. Infill the start time and end time of search, click the confirm button to compete the time
setting.

Figure 7-5

7.1.2.4.

Selection area display or hide

Menu ----- View ----- Selection area, click the selection area with V to hide; click the
selection area without V to display.

61

7 History Data Search Software Package

7.1.2.5.

SD 200

Selection area usage

1. Single curve: click the left mouse button to select the title of needed searching telemeter.
2. Multi curve: click the left mouse button to select the title of needed searching telemeter or the
icon ahead of title telemeter.

7.1.2.6.

Search period selection

Forbid to modify the inputting number for direct searching period by the keyboard, only through
add or reduce mode to modify the number of searching period.

7.1.2.7.

Maximum (Minimum) setting and modifying of curve

It may direct modify the inputting number of maximum (minimum) by the keyboard, then
through add or reduce mode to be available for inputting number.

7.2.

Curve search for daily history data

The curve for daily history can display any daily changeable curve of telemetry until the current
day in a year. It can contrast display any changeable curve of telemetry for any nine days in an
interface, or contrast display any changeable curve of nine telemetries for any day in an
interface. The minimum time definition of curve display is 5 minutes.

7.2.1.

The history curve of telemetry in any day

Select Single curve on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the searching date on the float tool bar, it can draw
the selection telemeter history curve in display area.
As drawing curves it can use different color to draw curve of upper limit and lower limit for
telemeter; above the curve it may display the telemeter title and searching date, below the curve
it may display the maximum, minimum, average and happen time.
It can set the display color for the curve, upper limit, lower limit and background through the
color setting.
The mouse move to the curve area, display the current cursor position in the status bar.

7.2.2.

The history curve of telemetry in any time quantum of one day

Select Single curve on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the searching date on the float tool bar and the
time quantum needed, it can draw the selection telemeter history curve in the time quantum in
display area.
The display sorts of curve, display mode of relating information and color setting are similar to
62

7 History Data Search Software Package

SD 200

7.2.1.

7.2.3.

The history curve of telemetry in any nine days

Select Time-sharing on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the 9 days different searching dates on the float
tool bar, it can draw the 9 days contrast history curves of telemeter in display area.
If want to cancel the curve display of any day, select the time of day again, the original selection
curve will be cancelled.
The sort of curve display is similar to 7.2.1. The curve of different date displays in different
color. The display mode of relating information as below: the top of curve display the title of
telemeter, the bottom display different date in different color. The color setting except unsetting
the color of curve, others is similar to 7.2.1.

7.2.4.

The contrast history curve of telemetry in any nine days

Select Time-sharing on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the 9 days different searching dates on the float
tool bar, then select the time quantum of needed searching, it can draw the 9 days contrast history
curves of telemeter in the time quantum selected in display area.
If want to cancel the curve display of any day, it is similar to 7.2.3.
The display sorts of curve, display mode of relating information and color setting are similar to
7.2.3.

7.2.5.

The contrast history curve of several telemetries in any day

Select Multi-curve on the tool bar, select Day on the float tool bar, select the searching date
on the float tool bar, select the several telemeter titles needed searching in selection area, it can
draw the contrast history curves of several telemeter of one day in display area.
If want to cancel the curve display of telemeter, select telemeter in the selection area again, the
original selection curve will be cancelled.
The sort of curve display is similar to 7.2.1. The curve of different telemeter displays in different
color. The display mode of relating information as below: the top of curve display the searching
date, the bottom display different telemeter in different color. The color setting except unsetting
the color of curve, others are similar to 7.2.1.

7.2.6.

The contrast history curve of several telemetries in any time quantum


of one day

Select Multi-curve on the tool bar, select Day on the float tool bar, select the searching date
on the float tool bar, select the several telemeter titles needed searching in selection area, then
select the time quantum, it can draw the contrast history curves of several telemeter in the time
63

7 History Data Search Software Package

SD 200

quantum selected of one day in display area.


If want to cancel the curve display of one day, it is similar to 7.2.5.
The display sorts of curve, display mode of relating information and color setting are similar to
7.2.5.

7.3.

Curve search for monthly history data

The curve for monthly history can display any monthly changeable curve of telemetry until the
current time in two years. It can contrast display any changeable curve of any nine telemetries of
any one month in an interface

7.3.1.

The history curve of telemetry in any month

Make Day change to Month on the float tool bar in 7.2.1, select Average, Maximum,
Minimum on the float tool bar, others are same.

7.3.2.

The history curve of telemetry in any time quantum of one month

Make Day change to Month on the float tool bar in 7.2.2, select Average, Maximum,
Minimum on the float tool bar, others are same.

7.3.3.

The contrast history curve of several telemetries in any month

Make Day change to Month on the float tool bar in 7.2.5, select Average, Maximum,
Minimum on the float tool bar, others are same.

7.3.4.

The contrast history curve of several telemetries in any time quantum


of one month

Make Day change to Month on the float tool bar in 7.2.6, select Average, Maximum,
Minimum on the float tool bar, others are same.

7.4.

Form search of daily history data

Select Day on the float tool bar, select LCU title on the selection area, select the searching date
on the float tool bar, then select the searching period on the float tool bar, in the display area it
may display the data which LCU stores all telemeter variables of one day in the history database
in the form.

7.5.

Form search of monthly history data

Select Month on the float tool bar, select any option of Average, Maximum, Minimum
on the float tool bar, select the LCU title on the selection area, then select searching date on the
64

7 History Data Search Software Package

SD 200

float tool bar, in the display area it may display the data of Average, Maximum,or
Minimum, which LCU stores all telemeter variables of onemonth in the history database in the
form.