Documente Academic
Documente Profesional
Documente Cultură
com
http://electrical-engineering-portal.com/applications-and-characteristics-of-differential-relays-ansi-87
Applications and Characteristics Of Differential Relays ANSI 87 (on photo: VAMP 265 Generator, transformer and motor diferential
protection relay)
Current-differential relays
Current-differential relays are typically used to protect large transformers, generators, and motors. For these devices
detection of low-level winding-to-ground faults is essential to avoid equipment damage. Current differential relays
typically are equipped with restraint windings to which the CT inputs are to be connected.
For electromechanical 87 current differential relays, the current through the restraint windings for each phase
is summed and the sum is directed through an operating winding. The current through the operating winding must be
above a certain percentage (typically 15%-50%) of the current through the restraint windings for the relay to operate.
For solid-state electronic or microprocessor-based 87 relays the operating windings exist in logic only rather than
as physical windings.
A typical application of current-differential relays for protection of a transformer is shown in figure 1 below. In figure 1,
the restraint windings are labeled as R and the operating windings are labeled as O. Because the delta-wye
transformer connection produces a phase shift, the secondary CTs are connected in delta to counteract this phase
shift for the connections to the relays.
Under normal conditions the operating windings will carry no current.
For a large external fault on the load side of the transformer, differences in CT performance in the primary vs. the
secondary (it is impossible to match the primary and secondary CTs due to different current levels) are taken into
account by the proper percentage differential setting.
Because the CT ratios in the primary vs. secondary will not always be able to match the current magnitudes in the
relay operating windings during normal conditions, the relays are equipped with taps to internally adjust the current
levels for comparison.
The specific connections in this example apply to a delta primary/wye secondary transformer or
transformer bank only. The connections for other winding arrangement will vary, in order to properly
cancel the phase shift.
For many solid-state electronic and microprocessor-based relays, the phase shift is made internally in the relay and
the CTs may be connected the same on the primary and secondary sides of the transformer regardless of the
transformer winding connections.
The manufacturers literature for a given relay make and model must be consulted when planning the CT
connections.
For an electromechanical relay, the percentage characteristic must be specified for each relay; for solid-state
electronic or microprocessor-based relays these characteristics are adjustable. For transformers relays with an
additional harmonic restraint are available. Harmonic restraint restrains the relay when certain harmonics, normally
the 2nd and 5th, are present.
These harmonics are characteristic of transformer inrush and without harmonic restraint the transformer
inrush may cause the relay to operate.
An important concept in the application of differential relays is that the relay typically trips fault interrupting devices on
both sides of the transformer. This is due to the fact that motors and generators on the secondary side of
the protected device will contribute to the fault current produced due to an internal fault in the device.
An example one-line diagram representation of the transformer differential protection from 1 is given in
figure 2 below:
Note that the secondary protective device is shown as a low voltage
power circuit breaker. It is important that the protective devices on both
sides of the transformer be capable of fault-interrupting duty and
suitable for relay tripping.
In figure 2 a lockout relay is used to trip both the primary and
secondary overcurrent devices. The lockout relay is designated 86T
since it is used for transformer tripping, and the differential relay is
denoted 87T since it is protecting the transformer. The wye and delta
CT connections are also noted.
An important concept in protective relaying is the zone of protection.
A zone of protection is the area that a given protective relay and/or
overcurrent device(s) are to protect.
While the zone of protection concept applies to any type of protection
(note the term zone selective interlockingas described earlier in this
section), it is especially important in the application of differential relays
because the zone of protection is strictly defined by the
CT locations.
In figure 2 the zone of protection for the 87T relay is shown by the
dashed-line box around the transformer. For faults within the zone of
protection, the currents in the CTs will not sum to zero at the
relay operating windings and the relays will operate.
Outside the zone of protection the operating winding currents should
sum to zero (or be low enough that the percentage restraint is not
exceeded), and therefore the relays will not operate.
Go back to Index
the voltage across the input during a fault from damaging the input.
The 87 relays are denoted 87B since they are protecting busses. The same applies for the 86B relays. Note also
that the protective zones overlap; this is typical practice to insure that all parts of the bus work are protected.
The high-impedance differential relay is typically set in terms of voltage across the input.
The voltage setting is typically set so that if one CT is fully saturated and the others are not the relay will not operate.
By its nature, the high-impedance differential relay is less sensitive than the current-differential relay, but since it is
typically applied to protect bussing, where fault magnitudes are typically high, the additional sensitivity is not required.
Go back to Index
Reference: System Protection - Bill Brown, P.E., Square D Engineering Services