Sunteți pe pagina 1din 170

GE Consumer & Industrial

Multilin

369 Motor Management Relay


Communications Guide

369 Revision: 3.4x


Manual P/N: 1601-9046-A4
Publication Number: GEK-113493C
Copyright 2010 GE Multilin

GE Multilin
215 Anderson Avenue, Markham, Ontario, Canada L6E 1B3
Tel: (905) 294-6222, 1-800-547-8629 (North America)
Fax: (905) 201-2098
Internet: http://www.GEmultilin.com

*1601-9046-A4*

GE Multilin's Quality Management


System is registered to
ISO9001:2000
QMI # 005094
UL # A3775

2010 GE Multilin Incorporated. All rights reserved.


GE Multilin 369 Motor Management Relay Communications Guide for revision
3.4x.
369 Motor Management Relay, is a registered trademark of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This
documentation is furnished on license and may not be reproduced in whole or
in part without the permission of GE Multilin. The content of this manual is for
informational use only and is subject to change without notice.
Part numbers contained in this manual are subject to change without notice,
and should therefore be verified by GE Multilin before ordering.
Part number: 1601-9046-A4 (July 2010)

TABLE OF CONTENTS

Table of Contents
OVERVIEW .........................................................................................................................................1
ELECTRICAL INTERFACE .....................................................................................................1
PROFIBUS COMMUNICATIONS .........................................................................................2
DEVICENET COMMUNICATIONS .......................................................................................2
MODBUS COMMUNICATIONS ...........................................................................................2
MODBUS/TCP COMMUNICATIONS .................................................................................3
PROFIBUS-DP COMMUNICATIONS .........................................................................................6
PROFIBUS COMMUNICATION OPTIONS ..........................................................................6
369 RELAY PROFIBUS-DP PARAMETERIZATION ...........................................................6
369 RELAY PROFIBUS-DP CONFIGURATION ................................................................6
369 RELAY PROFIBUS-DP DIAGNOSTICS ..................................................................11
PROFIBUS-DP LOSS OF COMMUNICATION TRIP .......................................................18
PROFIBUS-DPV1 COMMUNICATIONS ................................................................................19
369 RELAY PROFIBUS-DPV1 PARAMETERIZATION ..................................................19
369 RELAY PROFIBUS CONFIGURATION .....................................................................19
369 RELAY PROFIBUS INPUT DATA ............................................................................20
369 RELAY PROFIBUS OUTPUT DATA ........................................................................21
369 RELAY PROFIBUS DIAGNOSTICS ..........................................................................22
369 RELAY PROFIBUS-DPV1 ACYCLICAL COMMUNICATION ..................................22
369 RELAY PROFIBUS-DPV1 LOSS OF COMMUNICATION TRIP ............................23
DEVICENET PROTOCOL ............................................................................................................ 24
DEVICENET COMMUNICATIONS ....................................................................................24
POLL DATA ......................................................................................................................25
CHANGE OF STATE (COS) .............................................................................................27
IDENTITY OBJECT (CLASS CODE 01H) ..........................................................................28
MESSAGE ROUTER (CLASS CODE 02H) ........................................................................28
DEVICENET OBJECT (CLASS CODE 03H) .....................................................................28
ASSEMBLY OBJECT (CLASS CODE 04H) .......................................................................29
DEVICENET CONNECTION OBJECT (CLASS CODE 05H) ............................................31
ACKNOWLEDGE HANDLER OBJECT (CLASS CODE 2BH) ...........................................32
I/O DATA INPUT MAPPING OBJECT (CLASS CODE A0H) ..........................................32
I/O DATA OUTPUT MAPPING OBJECT (CLASS CODE A1H) ......................................33
PARAMETER DATA INPUT MAPPING OBJECT (CLASS CODE B0H) ............................33
DEVICENET LOSS OF COMMUNICATION TRIP ............................................................41
DEVICENET DATA FORMATS .........................................................................................42
MODBUS RTU PROTOCOL .......................................................................................................46
DATA FRAME FORMAT AND DATA RATE .....................................................................46
DATA PACKET FORMAT ..................................................................................................46
ERROR CHECKING ..........................................................................................................47
CRC-16 ALGORITHM ....................................................................................................47
TIMING .............................................................................................................................48
SUPPORTED MODBUS FUNCTIONS ..............................................................................48
ERROR RESPONSES ........................................................................................................48
MODBUS COMMANDS ...................................................................................................49
MEMORY MAP ...............................................................................................................................51
MEMORY MAP INFORMATION .......................................................................................51
USER DEFINABLE MEMORY MAP AREA .......................................................................51
EVENT RECORDER ..........................................................................................................52
WAVEFORM CAPTURE ....................................................................................................52

369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL

TOC1

TABLE OF CONTENTS

MOTOR START DATA LOGGER ......................................................................................52


DATA LOGGER .................................................................................................................53
MODBUS MEMORY MAP ................................................................................................54
FORMAT CODES ........................................................................................................... 131
CHANGE NOTES ........................................................................................................................ 163
REVISION HISTORY ...................................................................................................... 163
WARRANTY ................................................................................................................................. 165
WARRANTY INFORMATION ......................................................................................... 165

TOC2

369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL

GE Consumer & Industrial


Multilin

369 Motor Management Relay


Communications Guide

Communications Guide

Overview
1.1

Electrical Interface
The hardware or electrical interface is one of the following:
one of three 2-wire RS485 ports from the rear terminal connector,
the RS232 from the front panel connector
a fibre optic connection.
In a 2-wire RS485 link, data flow is bidirectional. Data flow is half-duplex for both the RS485
and the RS232 ports. That is, data is never transmitted and received at the same time.
RS485 lines should be connected in a daisy chain configuration (avoid star connections)
with a terminating network installed at each end of the link, i.e. at the master end and at
the slave farthest from the master. The terminating network should consist of a 120 ohm
resistor in series with a 1 nF ceramic capacitor when used with Belden 9841 RS485 wire.
The value of the terminating resistors should be equal to the characteristic impedance of
the line. This is approximately 120 ohms for standard #22 AWG twisted pair wire. Shielded
wire should always be used to minimize noise. Polarity is important in RS485
communications. Each '+' terminal of every 369 must be connected together for the
system to operate. See the 369 Instruction Manual, chapter 3 for details on correct serial
port wiring.
When using a fibre optic link the Tx from the 369 should be connected to the Rx of the
Master device and the Rx from the 369 should be connected to the Tx of the Master device.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG1

OVERVIEW

1.2

CGCOMMUNICATIONS GUIDE

Profibus Communications
The 369 Motor Management Relay supports both Profibus-DP (order code P) and ProfibusDPV1 (order code P1) communication interfaces as slave that can be read and written to/
from a Profibus-DP/V1 master. The Profibus-DP/V1 Master must read the GSD (Device
Master Data) file of the 369 for the purposes of configuration and parameterization.
The GSD file for the Profibus-DP option is 369_090C.gse.
The GSD file for the Profibus-DPV1 option is 369_09E6.gse.
The relay supports the following configurations and indications:

Fieldbus type: PROFIBUS-DP (IEC 61158 Type 3, and IEC 61784)

Auto baud rate detection 9.6Kbit - 12Mbit.

Address range: 1-126, setting via EnerVista 369 Setup software or front
keypad.

Input data: 220 bytes - cyclical.

Extended Diagnostic data: 26 bytes - non-cyclical.

Sections 2.2 to 2.4 pertain to the Profibus-DP option.

In addition to the above, the Profibus-DPV1 (P1) option supports:

Fieldbus type: Profibus-DPV1 (IEC 61158 Type 3, and IEC 61784)

Acyclic read/write between a Master (Class1/Class2) and the 369 slave


according to the DPV1 extensions of IEC 61158.

Output Data: 2 bytes - cyclical.

Sections 3.1 to 3.6 of this manual pertain to the Profibus-DPV1 option.

1.3

DeviceNet Communications
The 369 Motor Management Relay supports the optional DeviceNet protocol as slave that
can be read by a DeviceNet master. The device can be added to a DeviceNet list by adding
the 369.eds file in the scanner list. The EDS file can be generated using the EnerVista 369
Setup program.
The relay supports following configuration.
Field bus type: DeviceNet
Functions supported: Explicit, Polled, COS and Cyclic IO messaging
Baud Rate: 125, 250 and 500 kbps, programmable through software or relay front
keypad
Mac ID: 0 to 63, programmable through software or relay front keypad
See section 4: DeviceNet Protocol, for complete details.

1.4

Modbus Communications
The 369 implements a subset of the AEG Modicon Modbus RTU serial communication
standard. Many popular programmable controllers support this protocol directly with a
suitable interface card allowing direct connection of relays. Although the Modbus protocol
is hardware independent, the 369 interfaces include three 2-wire RS485 ports and one

CG2

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

OVERVIEW

RS232 port. Modbus is a single master, multiple slave protocol suitable for a multi-drop
configuration as provided by RS485 hardware. In this configuration up to 32 slaves can be
daisy-chained together on a single communication channel.
The 369 is always a slave. It cannot be programmed as a master. Computers or PLCs are
commonly programmed as masters. The Modbus protocol exists in two versions: Remote
Terminal Unit (RTU, binary) and ASCII. Only the RTU version is supported by the 369.
Monitoring, programming and control functions are possible using read and write register
commands.

1.5

Modbus/TCP Communications
Modbus/TCP Option:
When configured with the E Option, the 369 can connect to Ethernet networks via the
rear RJ45 connection, using the Modbus/TCP protocol as detailed in the document Open
Modbus / TCP Specification by Andy Swales, Release 1.0, 29 March 1999 (a search via the
internet can produce a free copy of this document).
This description contains information to the location of Setting registers for configuring the
369 for a LAN connection, and the physical connection of the 369. Information pertaining
to the application of an IED over Ethernet is beyond the scope of this manual and users
should consult their Network Administrators for configuration details.

Note

The implementation of this option is for the intention of data retrieval and device
configuration. The 369 does not support firmware upgrade via this connection.

Setpoints Configuration:
The user needs to configure the following settings for interface to a LAN: IP ADDRESS,
SUBNET MASK , and GATEWAY ADDRESS. Each setting contains 4 octets. The user
configures the octets as shown in the following example:
IP ADDRESS: 127.0.0.1
SUBNET MASK: 255.255.255.252
GATEWAY ADDRESS: 127.0.0.1
SETPOINT

MEMORY MAP
ADDRESS

DATA VALUE
(DEC)

IP ADDRESS OCTET1

0x101C

127

IP ADDRESS OCTET2

0x101D

IP ADDRESS OCTET3

0x101E

IP ADDRESS OCTET4

0x101F

SUBNET MASK OCTET1

0x1020

255

SUBNET MASK OCTET2

0x1021

255

SUBNET MASK OCTET3

0x1022

255

SUBNET MASK OCTET4

0x1023

252

GATEWAY ADDRESS OCTET1 0x1024

127

GATEWAY ADDRESS OCTET2 0x1025

GATEWAY ADDRESS OCTET3 0x1026

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG3

OVERVIEW

CGCOMMUNICATIONS GUIDE

SETPOINT

MEMORY MAP
ADDRESS

GATEWAY ADDRESS OCTET4 0x1027

DATA VALUE
(DEC)

These settings can also be configured via the keypad under the S1 369 SETUP 369
COMMUNICATIONS path.

Physical Connection:
The 369 can be connected to an Ethernet LAN via the RJ45 connector at the back of the
369.

Ethernet Loss Of Communication Trip


The 369 can detect a failure in communication activity with the MODBUS Master through
Ethernet port. The Ethernet Loss of Communications feature can be used to trip any
combination of output relays.
When equipped with the Ethernet option, the 369 can be configured to check for MODBUS
TCP/IP activity, and raise an alarm and trip an output relay if activity is not detected within
the configured delay. Delays of 0.25 to 10.00 seconds may be configured by the user.
If the Fieldbus Loss of Comms function is enabled , the 369 considers an Ethernet loss of
communication to have occurred in the following conditions:
1.

Link failure (break in physical connection)

2.

If valid MODBUS packets are not received within the configured delay period. Invalid
MODBUS packets, such as ones that contain the wrong slave ID, are not considered
valid. Please note that an ICMP PING message is not a valid MODBUS packet

3.

If packets cannot be received because of buffer overflows or lack of queue space, the
delay timer will continue to decrement, and will not be reset until valid packets are
received. If the queues / buffers cannot be recovered within the configured delay, the
Loss of Communication alarm will be raised, and any configured relays shall trip.

A delay of 0.25 sec to 10.00 sec in steps of 0.25 sec can be programmed to delay the
output relay activation. To avoid false trips, it is advised to set the trip delay greater than
MODBUS timeout delay.
This feature can be programmed for Latched or Unlatched operation.

If programmed as Latched:
The Fieldbus Loss of Comms trip will remain latched until the communication with the
Modbus Master through Ethernet port is (re) established AND the latched trip is manually
reset or remotely reset via Modbus communications.

If programmed as Unlatched:
Any programmed output relays for this feature will be activated until communication with
the Modbus master through Ethernet port is active. Once communication is active, the trip
condition will be cleared and the assigned output relays will automatically de-activate.
The setpoints associated with this feature are:

CG4

1.

Fieldbus Loss of Comms Enable

2.

Fieldbus Loss of Comms Delay

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

OVERVIEW

3.

Assign Loss of Comms Relay

Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more
information on these setpoints.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG5

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Profibus-DP Communications
2.1

Profibus Communication Options


The 369 Motor Management Relay supports either Profibus-DP (order code P) or ProfibusDPV1 (order code P1) communication interfaces as slave that can be read and written to/
from a Profibus-DP/V1 master. The Profibus-DP/V1 Master must read the GSD (Device
Master Data) file of the 369 for the purposes of configuration and parameterization.
The GSD file for the Profibus-DP option is 369_090C.GSE.
The GSD file for the Profibus-DPV1 option is 369_09E6.GSE.
Sections 2.2 to 2.4 pertain to the Profibus-DP option.
Sections 3.1 to 3.6 of this manual pertain to the Profibus-DPV1 option.

2.2

369 Relay Profibus-DP Parameterization


The 369 Motor Management Relay supports mandatory parametrization. The relay keeps
its user parameter data / setpoints in a non-volatile memory and does not need device
related parametrization during startup of the DP master. The EnerVista 369 Setup software
is the best tool for user parametrization of the 369 device.

2.3

369 Relay Profibus-DP Configuration


The Profibus-DP basic configuration has one DP master and one DP slave. In a typical bus
segment up to 32 stations can be connected (a repeater has to be used if more than 32
stations operate on a bus). The end nodes on a Profibus-DP network must be terminated to
avoid reflections on the bus line.
The bus address for the relay as Profibus-DP node can be set using the S1 369 RELAY
SETUP 369 RELAY COMMUNICATIONS PROFIBUS ADDRESS setpoint or via the
EnerVista 369 Setup software, which extends address range from 1 to 126. Address 126 is
used only for commissioning purposes and should not be used to exchange user data.
The media for the fieldbus is a twisted pair copper cable along with 9-pin SUB-D connector,
which connects the bus to the 369 socket on the back of the relay. The 369 Motor
Management Relay has autobaud support. The baud rates and other slave specific
information needed for configuration are contained in 369_090C.gs* which is used by a
network configuration program.
The 369 Motor Management Relay as a DP slave transfers fast process data to the DP
master according to master-slave principle. The 369 Motor Management Relay is a
modular device, supporting up to 8 input modules.
During the configuration session, all modules have to be selected in order to get the entire
area of 110 words of input data. There are no output data for processing. The following
diagram shows the possible DP Master Class 2 configuration menu:

CG6

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DP COMMUNICATIONS

FIGURE CG1: Slave Configuration

Table CG1: Profibus Input Data (Sheet 1 of 5)


OFFSET

CYCLIC DATA
(ACTUAL VALUES)

LENGTH
(BYTES)

MINIMUM
VALUE

HEX

MAXIMUM
VALUE

STEP
VALUE

UNITS

FORMAT
CODE

DEFAULT

HEX

MotorStatus

0000

0004

F133

TC_Used

0000

100

0064

F1

Time_to_Trip

FFFF

65500

FFDC

F20

OverloadLT

0000

50000

C350

F1

StartsHourLT[5]

0000

60

003C

min

F1

10

TimeBetween StartsLT

0000

500

01F4

min

F1

12

RestartBlock LT

0000

50000

C350

F1

14

StartInhibitLT

0000

60

003C

min

F1

16

AccessSwitch Status

0000

0001

F131

18

SpeedSwitch Status

0000

0001

F131

20

SpareSwitch Status

0000

0001

F131

22

DiffSwitch Status

0000

0001

F131

24

EmergencySwitch status

0000

0001

F131

26

ResetSwitch Status

0000

0001

F131

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG7

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Table CG1: Profibus Input Data (Sheet 2 of 5)


OFFSET

CYCLIC DATA
(ACTUAL VALUES)

LENGTH
(BYTES)

MINIMUM
VALUE

HEX

MAXIMUM
VALUE

STEP
VALUE

UNITS

FORMAT
CODE

DEFAULT

HEX

28

TripRelayStatus

0000

0001

N/A

F150

30

AlarmRelayStatus

0000

0001

N/A

F150

32

Aux1RelayStatus

0000

0001

N/A

F150

34

Aux2RelayStatus

0000

0001

N/A

F150

36

Ia

0000

65535

FFFF

F1

38

Ib

0000

65535

FFFF

F1

40

Ic

0000

65535

FFFF

F1

42

AveragePhaseCurrent

0000

65535

FFFF

F1

44

MotorLoad

0000

2000

07D0

xFLA

F3

46

CurrentUnbalance

0000

100

0064

F1

48

U/B Biased Motor Load

0000

2000

07D0

xFLC

F3

50

GroundCurrent

0000

50000

C350

F23

52

Vab

0000

65000

FDE8

F1

54

Vbc

0000

65000

FDE8

F1

56

Vca

0000

65000

FDE8

F1

58

Van

0000

65000

FDE8

F1

60

Vbn

0000

65000

FDE8

F1

62

Vcn

0000

65000

FDE8

F1

64

AvgLineVoltage

0000

65000

FDE8

F1

66

AvgPhaseVoltage

0000

65000

FDE8

F1

68

Frequency

0000

12000

2EE0

Hz

F3

70

BackSpinFrequency

0001

12000

2EE0

Hz

F3

72

PowerFactor

99

FF9D

100

0064

F21

74

RealPowerkW

32000

8300

32000

7D00

kW

F4

76

RealPowerhp

0000

65000

FDE8

hp

F1

78

ReactivePower

32000

8300

32000

7D00

kvar

F4

80

ApparentPower

0000

65000

FDE8

kVA

F1

82

MWh

0000

65535

FFFF

MWh

F1

84

PositiveMvarh

0000

65535

FFFF

Mvarh

F1

86

NegativeMvarh

0000

65535

FFFF

Mvarh

F1

88

HottestStatorRtd

0000

12

000C

F2

CG8

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DP COMMUNICATIONS

Table CG1: Profibus Input Data (Sheet 3 of 5)


OFFSET

CYCLIC DATA
(ACTUAL VALUES)

LENGTH
(BYTES)

MINIMUM
VALUE

HEX

MAXIMUM
VALUE

STEP
VALUE

UNITS

FORMAT
CODE

DEFAULT

HEX

90

HottestStatorRtdTemp

40

FFD8

200

00C8

F4

42

92

LocalRtd1

40

FFD8

200

00C8

F4

42

94

LocalRtd2

40

FFD8

200

00C8

F4

42

96

LocalRtd3

40

FFD8

200

00C8

F4

42

98

LocalRtd4

40

FFD8

200

00C8

F4

42

100

LocalRtd5

40

FFD8

200

00C8

F4

42

102

LocalRtd6

40

FFD8

200

00C8

F4

42

104

LocalRtd7

40

FFD8

200

00C8

F4

42

106

LocalRtd8

40

FFD8

200

00C8

F4

42

108

LocalRtd9

40

FFD8

200

00C8

F4

42

110

LocalRtd10

40

FFD8

200

00C8

F4

42

112

LocalRtd11

40

FFD8

200

00C8

F4

42

114

LocalRtd12

40

FFD8

200

00C8

F4

42

116

CurrentDemand

0000

50000

C350

F1

118

RealPowerDemand

0000

50000

C350

kW

F1

120

ReactivePowerDemand

32000

8300

32000

7D00

kvar

F4

122

ApparentPowerDemand

0000

50000

C350

kVA

F1

124

PeakCurrent

0000

65535

FFFF

F1

126

PeakRealPower

0000

50000

C350

kW

F1

128

PeakReactivePower

32000

8300

32000

7D00

kvar

F4

130

PeakApparentPower

0000

50000

C350

kVA

F1

132

Va angle

0000

359

0167

F1

134

Vb angle

0000

359

0167

F1

136

Vc angle

0000

359

0167

F1

138

Ia angle

0000

359

0167

F1

140

Ib angle

0000

359

0167

F1

142

Ic angle

0000

359

0167

F1

144

Learned
AccelerationTime

0001

2500

09C4

F2

146

Learned StartingCurrent

0000

65535

FFFF

F1

148

Learned
StartingCapacity

0000

100

0064

F1

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG9

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Table CG1: Profibus Input Data (Sheet 4 of 5)


OFFSET

CYCLIC DATA
(ACTUAL VALUES)

LENGTH
(BYTES)

MINIMUM
VALUE

HEX

MAXIMUM
VALUE

STEP
VALUE

UNITS

FORMAT
CODE

DEFAULT

HEX

150

Learned
RunningCoolTime
Constant

0000

500

01F4

min

F1

152

LearnedStoppedCoolTi
me Constant

0000

500

01F4

min

F1

154

Last StartingCapacity

0000

100

0064

F1

156

Learned
UnbalanceKfactor

0000

29

001D

F1

158

BSDState

0000

0006

F27

160

RawPredictionTimer

0000

50000

C350

F2

162

NumberOfStarts

0000

50000

C350

F1

164

NumberOfRestarts

0000

50000

C350

F1

166

DigitalCounter

0000

65535

FFFF

F1

168

MotorRunningHours

0000

65535

FFFF

hr

F1

170

RelayOperatingHours

0000

65535

FFFF

hr

F1

172

Last trip Cause

0000

169

00A9

F134

174

Last trip Date

N/A

N/A

N/A

N/A

N/A

N/A

F18

N/A

178

Last trip Time

N/A

N/A

N/A

N/A

N/A

N/A

F19

N/A

182

Last pre-trip Ia

0000

65535

FFFF

F1

184

Last pre-trip Ib

0000

65535

FFFF

F1

186

Last pre-trip Ic

0000

65535

FFFF

F1

188

Last pre-trip MotorLoad

0000

2000

07D0

FLA

F3

190

Last pre-trip Unbalance

0000

100

0064

F1

192

Last pre-trip Ig

0000

50000

C350

F23

194

Last trip
HottestStatorRtd

0000

12

000C

F1

196

Last trip
HottestStatorTemp

40

FFD8

200

00C8

F4

198

Last pretrip Vab

0000

65000

FDE8

F1

200

Last pretrip Vbc

0000

65000

FDE8

F1

202

Last pretrip Vca

0000

65000

FDE8

F1

204

Last pretrip Van

0000

65000

FDE8

F1

206

Last pretrip Vbn

0000

65000

FDE8

F1

CG10

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DP COMMUNICATIONS

Table CG1: Profibus Input Data (Sheet 5 of 5)


OFFSET

CYCLIC DATA
(ACTUAL VALUES)

LENGTH
(BYTES)

MINIMUM
VALUE

MAXIMUM

HEX

VALUE

HEX

STEP
VALUE

UNITS

FORMAT
CODE

DEFAULT

208

Last pretrip Vcn

0000

65000

FDE8

F1

210

Last pretrip Frequency

0000

12000

2EE0

Hz

F3

212

Last pretrip KiloWatts

32000

8300

32000

7D00

kW

F4

214

Last pretrip KiloVAR

32000

8300

32000

7D00

kvar

F4

216

Last pretrip KiloVA

0000

50000

C350

kVA

F1

218

Last pretrip
PowerFactor

99

FF9D

100

0064

F21

2.4

369 Relay Profibus-DP Diagnostics


The 369 Motor Management Relay supports both slave mandatory (6 bytes system-wide
standardized) and slave specific diagnostic data. If the diagnostics are considered high
priority, the PLC/host program will be informed of the fault (alarm or trip) and can call a
special error routine.
Diagnostic bytes 1 through 6 represent standard diagnostic data and are formatted as
follows.
Table CG2: Diagnostic bytes 1 through 7
BYTE

DESCRIPTION

Station Status 1

Station Status 2

Station Status 3

Diagnostic Master Address

Identification Number (High Byte)

Identification Number (Low Byte)

The extended diagnosis for the relay is composed of 26 bytes (bytes 7 to 32) and contains
diagnostic information according to the following table.
Table CG3: Profibus Diagnostics (Sheet 1 of 8)
BIT

BYTE

FUNCTION

0 to 7

Number of Diagnostic Bytes

SinglePhasingTrip

SpareSwitchTrip

EmergencySwitchTrip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG11

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Table CG3: Profibus Diagnostics (Sheet 2 of 8)


BIT

CG12

BYTE

FUNCTION

DifferentialSwitchTrip

SpeedSwitchTrip

ResetSwitchTrip

Reserved

OverloadTrip

ShortCircuitTrip

ShortCircuitBackupTrip

10

MechanicalJamTrip

11

UndercurrentTrip

12

CurrentUnbalanceTrip

13

GroundFaultTrip

14

GroundFaultBackupTrip

15

Reserved

16

10

AccelerationTimerTrip

17

10

Rtd1Trip

18

10

Rtd2Trip

19

10

Rtd3Trip

20

10

Rtd4Trip

21

10

Rtd5Trip

22

10

Rtd6Trip

23

10

Rtd7Trip

24

11

Rtd8Trip

25

11

Rtd9Trip

26

11

Rtd10Trip

27

11

Rtd11Trip

28

11

Rtd12Trip

29

11

UnderVoltageTrip

30

11

OverVoltageTrip

31

11

VoltagePhaseReversalTrip

32

12

UnderfrequencyTrip

33

12

OverfrequencyTrip

34

12

LeadPowerFactorTrip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DP COMMUNICATIONS

Table CG3: Profibus Diagnostics (Sheet 3 of 8)


BIT

BYTE

FUNCTION

35

12

LagPowerFactorTrip

36

12

PositivekvarTrip

37

12

NegativekvarTrip

38

12

UnderpowerTrip

39

12

ReversePowerTrip

40

13

IncompleteSequenceTrip

41

13

SpareSwitchAlarm

42

13

EmergencySwitchAlarm

43

13

DifferentialSwitchAlarm

44

13

SpeedSwitchAlarm

45

13

ResetSwitchAlarm

46

13

Reserved

47

13

ThermalCapacityAlarm

48

14

OverloadAlarm

49

14

MechanicalJamAlarm

50

14

UndercurrentAlarm

51

14

CurrentUnbalanceAlarm

52

14

GroundFaultAlarm

53

14

UndervoltageAlarm

54

14

OvervoltageAlarm

55

14

OverfrequencyAlarm

56

15

UnderfrequencyAlarm

57

15

LeadPowerFactorAlarm

58

15

LagPowerFactorAlarm

59

15

PositivekvarAlarm

60

15

NegativekvarAlarm

61

15

UnderpowerAlarm

62

15

ReversePowerAlarm

63

15

Rtd1Alarm

64

16

Rtd2Alarm

65

16

Rtd3Alarm

66

16

Rtd4Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG13

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Table CG3: Profibus Diagnostics (Sheet 4 of 8)


BIT

CG14

BYTE

FUNCTION

67

16

Rtd5Alarm

68

16

Rtd6Alarm

69

16

Rtd7Alarm

70

16

Rtd8Alarm

71

16

Rtd9Alarm

72

17

Rtd10Alarm

73

17

Rtd11Alarm

74

17

Rtd12Alarm

75

17

Rtd1HighAlarm

76

17

Rtd2HighAlarm

77

17

Rtd3HighAlarm

78

17

Rtd4HighAlarm

79

17

Rtd5HighAlarm

80

18

Rtd6HighAlarm

81

18

Rtd7HighAlarm

82

18

Rtd8HighAlarm

83

18

Rtd9HighAlarm

84

18

Rtd10HighAlarm

85

18

Rtd11HighAlarm

86

18

Rtd12HighAlarm

87

18

OpenRTDSensorAlarm

88

19

ShortRTDAlarm

89

19

TripCountersAlarm

90

19

StarterFailureAlarm

91

19

CurrentDemandAlarm

92

19

KWDemandAlarm

93

19

KVARDemandAlarm

94

19

KVADemandAlarm

95

19

DigitalCounterAlarm

96

20

OverloadLockoutBlock

97

20

StartInhibitBlock

98

20

StartsHourBlock

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DP COMMUNICATIONS

Table CG3: Profibus Diagnostics (Sheet 5 of 8)


BIT

BYTE

FUNCTION

99

20

TimeBetweenStartsBlock

100

20

RestartBlock

101

20

Reserved

102

20

BackSpinBlock

103

20

LossofRemoteRTDCommunication

104

21

RemoteRTD1Rtd1Trip

105

21

RemoteRTD1Rtd2Trip

106

21

RemoteRTD1Rtd3Trip

107

21

RemoteRTD1Rtd4Trip

108

21

RemoteRTD1Rtd5Trip

109

21

RemoteRTD1Rtd6Trip

110

21

RemoteRTD1Rtd7Trip

111

21

RemoteRTD1Rtd8Trip

112

22

RemoteRTD1Rtd9Trip

113

22

RemoteRTD1Rtd10Trip

114

22

RemoteRTD1Rtd11Trip

115

22

RemoteRTD1Rtd12Trip

116

22

RemoteRTD2Rtd1Trip

117

22

RemoteRTD2Rtd2Trip

118

22

RemoteRTD2Rtd3Trip

119

22

RemoteRTD2Rtd4Trip

120

23

RemoteRTD2Rtd5Trip

121

23

RemoteRTD2Rtd6Trip

122

23

RemoteRTD2Rtd7Trip

123

23

RemoteRTD2Rtd8Trip

124

23

RemoteRTD2Rtd9Trip

125

23

RemoteRTD2Rtd10Trip

126

23

RemoteRTD2Rtd11Trip

127

23

RemoteRTD2Rtd12Trip

128

24

RemoteRTD3Rtd1Trip

129

24

RemoteRTD3Rtd2Trip

130

24

RemoteRTD3Rtd3Trip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG15

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Table CG3: Profibus Diagnostics (Sheet 6 of 8)


BIT

CG16

BYTE

FUNCTION

131

24

RemoteRTD3Rtd4Trip

132

24

RemoteRTD3Rtd5Trip

133

24

RemoteRTD3Rtd6Trip

134

24

RemoteRTD3Rtd7Trip

135

24

RemoteRTD3Rtd8Trip

136

25

RemoteRTD3Rtd9Trip

137

25

RemoteRTD3Rtd10Trip

138

25

RemoteRTD3Rtd11Trip

139

25

RemoteRTD3Rtd12Trip

140

25

RemoteRTD4Rtd1Trip

141

25

RemoteRTD4Rtd2Trip

142

25

RemoteRTD4Rtd3Trip

143

25

RemoteRTD4Rtd4Trip

144

26

RemoteRTD4Rtd5Trip

145

26

RemoteRTD4Rtd6Trip

146

26

RemoteRTD4Rtd7Trip

147

26

RemoteRTD4Rtd8Trip

148

26

RemoteRTD4Rtd9Trip

149

26

RemoteRTD4Rtd10Trip

150

26

RemoteRTD4Rtd11Trip

151

26

RemoteRTD4Rtd12Trip

152

27

RemoteRTD1Rtd1Alarm

153

27

RemoteRTD1Rtd2Alarm

154

27

RemoteRTD1Rtd3Alarm

155

27

RemoteRTD1Rtd4Alarm

156

27

RemoteRTD1Rtd5Alarm

157

27

RemoteRTD1Rtd6Alarm

158

27

RemoteRTD1Rtd7Alarm

159

27

RemoteRTD1Rtd8Alarm

160

28

RemoteRTD1Rtd9Alarm

161

28

RemoteRTD1Rtd10Alarm

162

28

RemoteRTD1Rtd11Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DP COMMUNICATIONS

Table CG3: Profibus Diagnostics (Sheet 7 of 8)


BIT

BYTE

FUNCTION

163

28

RemoteRTD1Rtd12Alarm

164

28

RemoteRTD2Rtd1Alarm

165

28

RemoteRTD2Rtd2Alarm

166

28

RemoteRTD2Rtd3Alarm

167

28

RemoteRTD2Rtd4Alarm

168

29

RemoteRTD2Rtd5Alarm

169

29

RemoteRTD2Rtd6Alarm

170

29

RemoteRTD2Rtd7Alarm

171

29

RemoteRTD2Rtd8Alarm

172

29

RemoteRTD2Rtd9Alarm

173

29

RemoteRTD2Rtd10Alarm

174

29

RemoteRTD2Rtd11Alarm

175

29

RemoteRTD2Rtd12Alarm

176

30

RemoteRTD3Rtd1Alarm

177

30

RemoteRTD3Rtd2Alarm

178

30

RemoteRTD3Rtd3Alarm

179

30

RemoteRTD3Rtd4Alarm

180

30

RemoteRTD3Rtd5Alarm

181

30

RemoteRTD3Rtd6Alarm

182

30

RemoteRTD3Rtd7Alarm

183

30

RemoteRTD3Rtd8Alarm

184

31

RemoteRTD3Rtd9Alarm

185

31

RemoteRTD3Rtd10Alarm

186

31

RemoteRTD3Rtd11Alarm

187

31

RemoteRTD3Rtd12Alarm

188

31

RemoteRTD4Rtd1Alarm

189

31

RemoteRTD4Rtd2Alarm

190

31

RemoteRTD4Rtd3Alarm

191

31

RemoteRTD4Rtd4Alarm

192

32

RemoteRTD4Rtd5Alarm

193

32

RemoteRTD4Rtd6Alarm

194

32

RemoteRTD4Rtd7Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG17

PROFIBUS-DP COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

Table CG3: Profibus Diagnostics (Sheet 8 of 8)


BIT

2.5

BYTE

FUNCTION

195

32

RemoteRTD4Rtd8Alarm

196

32

RemoteRTD4Rtd9Alarm

197

32

RemoteRTD4Rtd10Alarm

198

32

RemoteRTD4Rtd11Alarm

199

32

RemoteRTD4Rtd12Alarm

Profibus-DP Loss Of Communication Trip


If the 369 detects a problem in communicating with the Profibus master, the Profibus Loss
of Communications feature can be used to operate on any combination of output relays.
During parameterization, a Profibus master sets up the communication and monitoring
times for the slave including the watchdog time. A Profibus slave uses a watchdog timer to
enable it to detect bus inactivity with its master. The watchdog timer is reset every time an
error free message is received from the master. If no valid message is received within the
time specified during parameterization, the slave assumes a communication error.
If the 369 Profibus communications is offline and not communicating with a master, then
the Fieldbus Loss of Comms function (if enabled) will activate. This feature can be
programmed for Latched or Unlatched operation.

If programmed as Latched:
The Fieldbus Loss of Comms output relay will remain latched until communication with
the Master is (re) established AND the latched output relay is manually reset or remotely
reset via Modbus communications.

If programmed as Unlatched:
Any output relays programmed for this feature will be de-activated once communication is
restored; the Loss of Communication condition will be cleared and the assigned output
relays will automatically de-activate.
The setpoints associated with this feature are:
1.

Fieldbus Loss of Comms Enable

2.

Fieldbus Loss of Comms Delay

3.

Assigned Fieldbus Loss of Comms Relay

Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more
information on these setpoints.

CG18

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DPV1 COMMUNICATIONS

Profibus-DPV1 Communications
3.1

369 Relay Profibus-DPV1 Parameterization


The 369 Motor Management Relay supports mandatory parametrization as well as three
bytes of user parameter data necessary for DPV1 devices. The relay keeps its user
parameter data/setpoints in a non-volatile memory and does not require device related
parametrization during startup of the DP/V1 master, with the exception of the DPV1 Enable
parameter. To enable the DPV1 acyclical functionality, the DPV1 parameter must be set to
Enable when configuring the device in your master using the GSD file.
The EnerVista 369 Setup software is the best tool for editing user parametrization
(setpoints) of the 369 Relay device.

FIGURE CG2: User Parameter Setup Enable DPV1

3.2

369 Relay Profibus Configuration


The Profibus-DPV1 basic configuration has one DP/V1 master and one DPV1 slave. In a
typical bus segment up to 32 stations can be connected (a repeater has to be used if more
then 32 stations operate on a bus). The end nodes on a Profibus-DPV1 network must be
terminated to avoid reflections on the bus line.
The bus address for the relay as Profibus-DPV1 node can be set using the S1 369 SETUP
369 COMMUNICATIONS PROFIBUS ADDRESS setpoint or via the EnerVista 369
Setup software, which extends address range from 1 to 126. Address 126 is used only for
commissioning purposes and should not be used to exchange user data.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG19

PROFIBUS-DPV1 COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

The Profibus media is a twisted-pair copper cable along with 9-pin Sub-D connector, which
connects the bus to the 369 Relay socket on the back of the relay. The 369 Motor
Management Relay has autobaud support. The baud rates and other slave specific
information needed for configuration are contained in the 369_09E6.gse file, which is used
by a network configuration program.
The 369 Motor Management Relay as a DPV1 slave transfers fast process data to the DP/
V1 master according to master-slave principle. The 369 Relay is a modular device,
supporting up to 111 input modules.
Modules define a block size of input data to be read by the master, starting from offset
zero. Adding modules in your Master configuration increases the size of the total block of
data that the Master will read, making it easy to choose a total block size of data that
matches the user's requirements.

3.3

369 Relay Profibus Input Data


There are two options for configuring what data is made available through Profibus Input
Data, based on the value of the PROFIBUS CYCLIC IN DATA setpoint (see 369 Instruction
Manual, chapter 5 for details). If the PROFIBUS CYCLIC IN DATA setpoint is set to 0
(default map), then the data available to be read matches Table CG1: Profibus Input Data
on page CG7.
The user can also exactly define the data provided and the order of that data. The Modbus
User Definable Memory Map area and the PROFIBUS CYCLIC IN DATA setpoint are used
to define this data. The PROFIBUS CYCLIC IN DATA setpoint determines the number of
16-bit registers available to be read through Profibus Input Data and the Modbus User
Definable Memory Map is used to determine the data provided and the order of the data.
For example, if the user only wishes to read two 16-bit registers of data (4 bytes), the user
selects a number of Input Modules from the GSD file that add up to a total of 4 bytes. When
the Profibus Master is reading the Input data, only 4 bytes of Input data will be sent in the
communication packet. The number of words should match the PROFIBUS CYCLIC IN
DATA setpoint, but it's not necessary. If the number of Input data bytes read from the
master is greater than the user has defined with the PROFIBUS CYCLIC IN DATA
setpoint, the balance of the data will return zero values.

CG20

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DPV1 COMMUNICATIONS

FIGURE CG3: Slave Configuration Example 1 4 Bytes of Input Data

FIGURE CG4: Slave Configuration Example 2 220 Bytes of Input Data

3.4

369 Relay Profibus Output Data


The capability to force the output relays states has been implemented in cyclic output
data. As cyclic data is continuously written, the 369 looks for a change in the value to
execute the force relays command. Refer to the 369 Instruction Manual, chapter 5 for more
information about the force output relays feature.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG21

PROFIBUS-DPV1 COMMUNICATIONS

CGCOMMUNICATIONS GUIDE

A slave configuration example for 4 bytes of input data and 2 bytes of output data is
shown below.

FIGURE CG5: Slave Configuration Example 4 Bytes of Input Data, 2 bytes of Output Data

Table CG4: Profibus Output Data


OFFSE
T

CYCLIC DATA
(ACTUAL VALUES)

LENGTH
(BYTES)

MINIMUM
VALUE

3.5

Force Output Relays

HEX

MAXIMUM
VALUE

15

FORMA
T CODE

HEX

F141

369 Relay Profibus Diagnostics


The diagnostic data available for the Profibus-DPV1 option matches Table CG3: Profibus
Diagnostics on page CG11. When no diagnostic information is available and the master
initiates a diagnostics read, the six slave mandatory bytes are read.

3.6

369 Relay Profibus-DPV1 Acyclical Communication


The following items have been made available through Profibus-DPV1 acyclical
communication. Data is addressed through the use of slot and index addressing. Three
parameters are required to read or write data from the 369 Relay using a Profibus-DPV1
master:

CG22

1.

Slot number

2.

Index number

3.

Data length (number of 16-bit words)

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

PROFIBUS-DPV1 COMMUNICATIONS

The value that is written acyclically to either FORCE OUTPUT RELAYS or BLOCK
PROTECTION FUNCTIONS must be a 16-bit value. The lower byte contains the bitmask

Note

data (as per format codes noted) and the upper byte written must always contain a value
of zero.
Table CG5: Profibus-DPV1 Acyclic Write Data
OBJECT

SLOT

INDEX

LENGTH

DESCRIPTION

FORMAT

2 bytes

Force Output Relays

F141

2 bytes

Block Protection Functions

F180

Refer to the 369 Instruction Manual, chapter 5 for additional information about the force
output relays feature. Refer to the 369 Instruction Manual, chapter 5.3.4 for additional
information about the protection function blocking feature.
Table CG6: Profibus-DPV1 Acyclic Read Data
OBJECT

3.7

SLOT

INDEX

LENGTH

DATA ITEM

FORMAT

2 bytes

Trip Relay Status

F150

2 bytes

Alarm Relay Status

F150

2 bytes

Aux1 Relay Status

F150

2 bytes

Aux2 Relay Status

F150

2 bytes

Functions Currently
Blocked

F141

369 Relay Profibus-DPV1 Loss Of Communication Trip


If the 369 detects a problem in communicating with the Profibus master, the Profibus Loss
of Communications feature can be used to operate on any combination of output relays.
Refer to the following sections for more information regarding this feature:
369 Communications Guide: Section 2.5: Profibus-DP Loss Of Communication Trip
369 Instruction Manual: Chapter 5: 369 Communications (for information regarding the
setpoints for this feature).

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG23

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

DeviceNet Protocol
4.1

DeviceNet Communications
The device profile is an extension of the Generic Device Profile (0x00). It is a group 2 only
server. The MAC ID and baud rate are programmable through relay front panel or the
EnerVista 369 Setup software. The polling function consumes one byte of control data
(described under assembly object class 04, instance 96h) and produces data as per Poll
Data Group 1, Poll Data Group 2, or the User-Defined poll data (described in assembly
object class 04, instance 64h). The COS\CYC operation produces 4 bytes of data as per
Class 4, Instance 66h, Attribute 3.
The EDS file for use with a DeviceNet master can be generated using the EnerVista 369
Setup program. The EDS file differs depending on which Poll Group is selected, and by the
amount of data being returned for the User-Defined Poll Data. Note that only one version
of the EDS file may be used for any one DeviceNet master.
The 369 Motor Management Relay supports following DeviceNet object classes.
Table CG7: DeviceNet Object Classes
CLASS

Object

01h

Identity

02h

Message Router

03h

DeviceNet

04h

Assembly

05h

Connection

2Bh

Acknowledge Handler

A0h

IO data Input Mapping

A1h

IO data Output Mapping

B0h

Parameter Data input Mapping

DeviceNet Loss Of Communication Trip


If the 369 detects a failure in communicating with the DeviceNet master, the Fieldbus Loss
of Communications feature can be used to trip any combination of output relays.
If the 369 DeviceNet communications is offline and not communicating with a master, then
the Fieldbus Loss of Comms function (if enabled) will activate. This feature can be
programmed for Latched or Unlatched operation.
If the Fieldbus Loss of Comms function is enabled , the 369 considers a DeviceNet loss of
communication to have occurred in the following conditions:

CG24

1.

Online; not connected

2.

Critical link failure

3.

Connection timeout.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

Critical link failure is caused by failure of CAN_H or CAN_L bus. To re-establish


communication after recovery of critical link faliure, the 369 Fieldbus comms interface
must be reset. This can be done without recycling the control power to the 369 by using
"RESET FIELDBUS COMMS INTERFACE" command under setting S1 369 SETUP\369
COMMUNICATIONS\ . Refer to section 5.2.3 for more details.

Note

A delay of 0.25 sec to 10.00 sec in steps of 0.25 sec can be programmed to delay the
output relay activation.
This feature can be programmed for Latched or Unlatched operation.

If programmed as Latched:
The DeviceNet Loss of Comms trip will remain latched until the communication with the
Master is (re) established AND the latched trip is manually reset or remotely reset via
Modbus communications.

If programmed as Unlatched:
Any programmed output relays for this feature will be activated until communication is
active. Once communication is active, the trip condition will be cleared and the assigned
output relays will automatically de-activate.
The setpoints associated with this feature are:
1.

Fieldbus Loss of Comms Enable

2.

Fieldbus Loss of Comms Delay

3.

Assign Loss of Comms Relay

Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more
information on these setpoints.

4.2

Poll Data
The polling function consumes one byte of control data and produces data as per Poll Data
Group 1, Poll Data Group 2, or the User-Defined poll data. The control data format is as
follows:

Bit Position

Name

Value

Motor Start

0.1

Motor Stop

0.1

Fault Reset

0.1

Reserved

Reserved

Reserved

Reserved

Reserved

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG25

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

For execution of DeviceNet control commands, one of the switch assignments should be
set to DeviceNet Control and be closed.
The motor start command energizes the output relay set with the START CONTROL RELAY
setpoint. The motor stop command energizes the trip relay. The fault reset command
resets the latched trip and alarm conditions, provided the cause of alarm/trip is removed.
The commands are executed continuously as long as the control bits are high. When two
or more commands are executed simultaneously, only one will be executed. The command
hierarchy for execution is given below.
1.

Motor stop

2.

Fault reset

3.

Motor start

The corresponding command bit should be high for more than 500 ms to execute the
command.

Note

The Polled input bytes can be selected from two predefined groups of parameters or one
group of user-defined parameters with the DeviceNet Input Poll Data Group setpoint. The
list of parameters in each group is given below:

Table CG8: Poll Data Group 1


Byte

Description

Length

Units

Format

Default

Motor Status

F172

Digital Input Status

F173

Digital Output Status

F174

Flag Change State

F175

Thermal Capacity Used

UINT

6 (low), 7 (high)

Time to Trip

seconds

F20

-1

Table CG9: Poll Data Group 2

Byte

CG26

Description

Length

Units

Format

Default

Motor Status - Stopped, Starting, Running,


Tripped

F172

2,3

Cause of Last Trip

F134

4,5

Average Phase Current

F1

6,7

Ground Current

F23

8,9

Average Line Voltage

F1

10,11

Real Power (kW)

kW

F4

12,13

Power Factor

F21

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

Table CG9: Poll Data Group 2

Byte

Description

Length

Units

Format

Default

14

Local Hottest Stator RTD Number

F1

15,16

Local Hottest Stator RTD Temperature

F4

17

Digital Input Status - Access Switch, Speed


Switch, Spare Switch, Differential Switch,
Emergency Switch, Reset Switch

F173

18

Digital Output Status - Trip Relay, Alarm


Relay, Aux Relay 1, Aux Relay 2

F174

User-Defined Poll Data


The user can also define exactly which data will be provided and the order in which that
data is given. The Modbus User Definable Memory Map area (refer to Section 9.6.2: User
Definable Memory Map Area on page 934) and the User-Defined Data Size setpoint are
used to define this data and data size. The User-Defined Data Size setpoint determines
the number of 16-bit registers available to be read through DeviceNet Poll Input Data and
the Modbus User Definable Memory Map is used to determine the data provided and the
order of the data.
For example, if the user only wishes to read two 16-bit registers of data (4 bytes), the user
sets the DeviceNet Input Poll Data Group setpoint to User-Defined and then programs a
value of 2 for the User-Defined Data Size setpoint. When the DeviceNet master reads
the Poll Input data, 4 bytes of Input data will be read as follows.
Byte

Description

Length

1 (Hi), 2 (Lo)

User Defined Memory Map Register 1

1 word

3 (Hi), 4 (lo)

User Defined Memory Map Register 2

1 word

Note that the Explicit message data provided both via Class 04, Instance 64h, Attribute 03
and Class A0h, Instance 01, Attribute 01 will match the the Poll data configuration.

4.3

Change of State (COS)


The COS data is described under class 4, instance 66h, attribute 3. The following data is
provided:

Byte

Description

Length

Units

Format

Default

Motor Status

F172

Digital Input Status

F173

Digital Output Status

F174

Flag Change State

F175

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG27

DEVICENET PROTOCOL

4.4

CGCOMMUNICATIONS GUIDE

Identity Object (class code 01h)


Identity object, Class code 01h, Services.
CODE

SERVICES AVAILABLE TO THIS OBJECT


NAME

DESCRIPTION

0x05

Reset

Reset the device to power up configuration

0x0E

Get_Attribute_Single

Returns the contents of the given attribute

Identity object, Class code 01h, Attributes.


ATTRIBUTE

01h

ACCESS

NAME/DESCRIPTION

Get

DATA TYPE

Revision of Identity object

UINT

VALUE

Identity object, Class code 01h, Instance 01h, Attributes.


ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA TYPE

VALUE

01h

Get

Vendor ID

UINT

928

02h

Get

Device Type

UINT

03h

Get

Product Code

UINT

53

04h

Get

Revision (Major, Minor)

USINT (2)

2.20

05h

Get

Status

F178

---

07h

Get

Product Name

Short-String

369 Motor
Management
Relay

The USINT and UINT data types are defined as follows: USINT = Unsigned integer byte
(range 0 to 255); UINT = Unsigned integer word (range 0 to 65535).

4.5

Message Router (class code 02h)


The message router (class code 2) object provides a messaging connection point through
which a client may address a service to any object or instance residing in the physical
device. There is no external visible interface to the message router object.

4.6

DeviceNet Object (class code 03h)


DeviceNet object, Class code 03h, Services:
CODE

SERVICES AVAILABLE TO THIS OBJECT


NAME

0x0E

Get_Attribute_Single

DESCRIPTION

Returns the contents of the given attribute

DeviceNet object, Class Code 03h, Attributes:


ATTRIBUTE

01h

ACCESS

Get

NAME/DESCRIPTION

Revision of DeviceNet
object

DATA TYPE

USINT

VALUE

DeviceNet object, Class Code 03h, Instance 01h, Attributes:


ATTRIBUTE

01h

CG28

ACCESS

Get

NAME/DESCRIPTION

MAC ID

DATA TYPE

USINT

VALUE

0 to 63

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

ATTRIBUTE

02h

ACCESS

Get

05h

NAME/DESCRIPTION

DATA TYPE

VALUE

USINT

0 = 125 kbps, 1 = 250 kbps,


2 = 500 kbps

Allocation choice

BYTE

Bit 0: explicit messaging


Bit 1: polled I/O
Bit 4: COS I/O
Bit 5: cyclic I/O
Bit 6: acknowledge
suppression

Masters MAC ID

USINT

0 to 63: address;
255 = unallocated

Baud Rate

Get

The USINT and UINT data types are defined as follows: USINT = Unsigned integer byte
(range 0 to 255); UINT = Unsigned integer word (range 0 to 65535).

4.7

Assembly Object (class code 04h)


Assembly object, Class code 04h, Services:
CODE

SERVICES AVAILABLE TO THIS OBJECT


NAME

DESCRIPTION

0x0E

Get_Attribute_Single

Returns the contents of the given attribute

0X10

Set_Attribute_Single

Sets the contents of the given attribute

Assembly object, Class code 04h, Attributes.


ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA TYPE

VALUE

01h

Get

Revision of Assembly object

UINT

02h

Get

Maximum instance number

UINT

150

Assembly object, Class code 04h, Instance 64h, Attributes.


ATTRIBUTE

03h

ACCESS

Get

NAME/DESCRIPTION

DATA TYPE

Motor data1

bytes (7)

VALUE

see below

1. The data available through this Class/Instance/Attribute will depend on which Poll Group is
used (see section 4.2: Poll Data).

Assembly object, Class code 04h, Instance 65h, Attributes.


ATTRIBUTE

03h

ACCESS

Get

NAME/DESCRIPTION

DATA TYPE

Flag change state

byte

VALUE

see below

DATA FORMATS, FLAG CHANGE STATE


BIT POSITION

NAME

VALUES

Trip/alarm flag

0 = no change; 1 = trip or alarm

1 to 7

Reserved

---

Assembly object, Class code 04h, Instance 66h, Attributes.


ATTRIBUTE

03h

ACCESS

Get

NAME/DESCRIPTION

DATA TYPE

Digital data

bytes (4)

VALUE

see below

DATA FORMATS, DIGITAL DATA


BYTE

DESCRIPTION

Motor status

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

LENGTH

1 byte

UNITS

---

FORMAT

F172

DEFAULT

CG29

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

DATA FORMATS, DIGITAL DATA


BYTE

DESCRIPTION

LENGTH

UNITS

FORMAT

DEFAULT

Digital input status

1 byte

---

F173

Digital output status

1 byte

---

F174

Flag change state

1 byte

---

F175

Assembly object, Class code 04h, Instance 67h, Attributes.


ATTRIBUTE

03h

ACCESS

NAME/DESCRIPTION

Get

Thermal capacity used

DATA TYPE

VALUE

USINT

Assembly object, Class code 04h, Instance 68h, Attributes.


ATTRIBUTE

03h

ACCESS

Get

NAME/DESCRIPTION

Time to trip

DATA TYPE

Word

DATA FORMAT

F20

VALUE

1 second

Assembly object, Class code 04h, Instance 96h, Attributes.


ATTRIBUTE

03h

ACCESS

Set

NAME/DESCRIPTION

Control byte

DATA TYPE

1 byte

VALUE

see below

DATA FORMATS, CONTROL BYTE


BIT POSITION

NAME

VALUE

Motor start

0, 1

Motor stop

0, 1

Fault reset

0, 1

Reserved

---

Reserved

---

Reserved

---

Reserved

---

Reserved

---

For execution of DeviceNet control commands, one of the switch assignments should be
set to DeviceNet Control and be closed.
The motor start command energizes the output relay set with the START CONTROL
RELAY setpoint. The motor stop command energizes the trip relay. The fault reset
command resets the latched trip and alarm conditions, provided the cause of alarm/trip is
removed. The commands are executed continuously as long as the control bits are high.
When two or more commands are executed simultaneously, only one will be executed. The
command hierarchy for execution is given below.
1. Motor stop
2. Fault reset
3. Motor start
The corresponding command bit should be high for more than 500 ms to execute the
command.

CG30

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

4.8

DEVICENET PROTOCOL

DeviceNet Connection Object (class code 05h)


The connection objects manage the characteristics of each communication connection.
There are two instances of the connection object in the device: explicit connection (<50 ms
response) and input/output connection poll (<10 ms response).
Connection Object, Class Code 05h, Services:
CODE

0x05

NAME AND DESCRIPTION OF SERVICES AVAILABLE TO THIS OBJECT

Reset the connection - restart timer

0x0E

Get_Attribute_Single: Returns the contents of the given attribute.

0x10

Set_Attribute_Single: Sets the contents of the given attribute

Connection Object, Class Code 05h, Instance 01h (explicit message connection):
ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA
TYPE

VALUE

01h

Get

State

BYTE

0x03

02h

Get

Instance_type

BYTE

0x00, 0x01

03h

Get

Export class trigger

BYTE

0x83

04h

Get

Produced connection ID

UINT

10xxxxxx011, xxxxxx =
MAC ID

05h

Get

Consumed connection ID

UINT

10xxxxxx011, xxxxxx =
MAC ID

06h

Get

Initial comm.
characteristics

UINT

0x21

07h

Get

Produced connection size

UINT

0x12

08h

Get

Consumed connection
size

UINT

0x12

09h

Get/Set

Expected package rate

UINT

0x00

0Ch

Get/Set

Watchdog timeout action

USINT

0 = transition to time-out
1 = auto delete, 2 = auto
reset
3 = deferred delete

0Dh

Get

Produced path length

UINT

0x0000

0Eh

Get

Produced path

BYTE [6]

<null>

0Fh

Get

Consumed path length

UINT

0x0000

10h

Get

Consumed path

BYTE [6]

<null>

11h

Get

Production inhibit timer

UINT

0x0000

Connection Object, Class Code 05h, Instance 02h (polled input/output connection):
ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA TYPE

VALUE

01h

Get

State

BYTE

0x03

02h

Get

Instance_type

BYTE

0x01

03h

Get

Export class trigger

BYTE

0x80, 0x82

04h

Get

Produced connection ID

UINT

MAC ID

05h

Get

Consumed connection ID

UINT

MAC ID

06h

Get

Initial comm. characteristics

UINT

0x01, 0xF1

07h

Get

Produced connection size

UINT

0x01

08h

Get

Consumed connection size

UINT

0x01

09h

Get/Set

Expected package rate

UINT

0x00

0Ch

Get/Set

Watchdog timeout action

UINT

0x00

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG31

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

ATTRIBUTE

4.9

ACCESS

NAME/DESCRIPTION

DATA TYPE

VALUE

0Dh

Get

Produced path length

UINT

0x0006

0Eh

Get

Produced path

BYTE [6]

<null>

0Fh

Get

Consumed path length

UINT

0x0006

10h

Get

Consumed path

BYTE [6]

<null>

11h

Get

Production inhibit timer

UINT

0x0000

Acknowledge Handler Object (class code 2Bh)


Acknowledge Handler Object, Class Code 2Bh, Services:
CODE

NAME

DESCRIPTION

0x0E

Get_Attribute_Single

Returns the contents of the given attribute

0x10

Set_Attribute_Single

Sets the contents of the given attribute

Acknowledge Handler object, Class code 2Bh, Attributes.


ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA TYPE

01h

Get

Revision of Acknowledge Handler


object

02h

Get

Maximum instance number

VALUE

UINT

UINT

Acknowledge Handler object, Class code 2Bh, Instance 01h, Attributes:


ATTRIBUTE

4.10

ACCESS

NAME/DESCRIPTION

DATA TYPE

VALUE

01h

Get

Acknowledge timer

UINT

16 ms

02h

Get

Retry limit

USINT

I/O Data Input Mapping Object (class code A0h)


I/O Data Input Mapping Object, Class code A0h, Services:
CODE

0x0E

NAME

DESCRIPTION

Get_Attribute_Single

Returns the contents of the given attribute

Input/Output Data Input Mapping object, Class code A0h, Attributes.


ATTRIBUTE

01h

ACCESS

Get

NAME/DESCRIPTION

DATA TYPE

Revision of I/O Data Input Mapping


object

UINT

VALUE

I/O Data Input Mapping object, Class code A0h, Instance 01h, Attributes:
ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA TYPE

DATA FORMAT

01h

Get

Motor data1

bytes (7)

see below

02h

Get

Flag change state

byte

F175

03h

Get

Digital data

bytes (4)

see below

04h

Get

Thermal capacity used

USINT

05h

Get

Time to trip

Word

F20

1. The data available through this Class/Instance/Attribute will depend on which Poll Group is used
(see section 4.2: Poll Data)

CG32

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

DATA FORMATS, DIGITAL DATA


BYTE

4.11

DESCRIPTION

LENGTH

1 byte

UNITS

FORMAT

---

DEFAULT

Motor status

F172

Digital input status

1 byte

---

F173

Digital output status

1 byte

---

F174

Flag change state

1 byte

---

F175

I/O Data Output Mapping Object (class code A1h)


I/O Data Output Mapping Object, Class code A1h, Services:
CODE

NAME

DESCRIPTION

0x0E

Get_Attribute_Single

Returns the contents of the given attribute

0x10

Set_Attribute_Single

Sets the contents of the given attribute

I/O Data Input Mapping object, Class code A0h, Instance 01h, Attributes:
ATTRIBUTE

01h

ACCESS

NAME/DESCRIPTION

Set

Control byte

DATA TYPE

1 byte

DATA FORMAT

see below

DATA FORMATS, CONTROL BYTE


BIT POSITION

4.12

NAME

VALUES

Motor start

0, 1

Motor stop

0, 1

Fault reset

0, 1

Reserved

---

Reserved

---

Reserved

---

Reserved

---

Reserved

---

Parameter Data Input Mapping Object (class code B0h)


Parameter Data Input Mapping object, Class code B0h, Services:
CODE

0x0E

NAME

DESCRIPTION

Get_Attribute_Single

Returns the contents of the given attribute

Parameter Data Input Mapping object, Class code B0h, Attributes.


ATTRIBUTE

01h

ACCESS

Get

NAME/DESCRIPTION

Revision of Identity object

DATA TYPE

UINT

VALUE

Parameter Data Input Mapping object, Class code B0h, Instance 01h, Attributes:
ATTRIBUTE

ACCESS

NAME/DESCRIPTION

DATA TYPE

VALUE

01h

Get

Currents

bytes (10)

see below

02h

Get

Current angles

bytes (6)

see below

03h

Get

Motor load

bytes (6)

see below

04h

Get

Line voltages

bytes (8)

see below

05h

Get

Phase voltages

bytes (8)

see below

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG33

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

ATTRIBUTE

ACCESS

06h

Get

07h
08h

NAME/DESCRIPTION

DATA TYPE

VALUE

Phase voltage angles

bytes (6)

see below

Get

Frequency

bytes (2)

see below

Get

BSD state and frequency

bytes (6)

see below

09h

Get

Power

bytes (10)

see below

0Ah

Get

Energy

bytes (6)

see below

0Bh

Get

Local hottest stator RTD and


temperature

bytes (4)

see below

0Ch

Get

Local RTD temperatures

bytes (24)

see below

0Dh

Get

Demand

bytes (8)

see below

0Eh

Get

Peak values

bytes (8)

see below

0Fh

Get

Learned data

bytes (14)

see below

10h

Get

Motor statistics

bytes (8)

see below

11h

Get

Cause of trip

bytes (2)

see below

12h

Get

Last trip date and time

bytes (8)

see below

13h

Get

Last pre-trip currents

bytes (8)

see below

14h

Get

Last pre-trip motor load

bytes (4)

see below

15h

Get

Pre-trip local hottest stator


RTD and temperature

bytes (4)

see below

16h

Get

Last pre-trip line voltages

bytes (6)

see below

17h

Get

Last pre-trip phase voltages

bytes (6)

see below

18h

Get

Last pre-trip frequency

bytes (2)

see below

19h

Get

Last pre-trip power

bytes (8)

see below

1Ah

Get

Trip diagnostic data

bytes (6)

see below

1Bh

Get

Alarm diagnostic data

bytes (8)

see below

1Ch

Get

Start block status data

bytes (18)

see below

1Dh

Get

Actual values

bytes (202)

see below

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 1 of 8)


ATTRIBUTE

01h
CURRENTS

02h
CURRENT
ANGLES

BYTES

CG34

LENGTH

FORMAT

VALUE/UNIT

Phase Current Ia

16 bits

UINT

3,4 (low, high)

Phase Current Ib

16 bits

UINT

5,6 (low, high)

Phase Current Ic

16 bits

UINT

7,8 (low, high)

Average phase
current Iav

16 bits

UINT

9,10 (low, high)

Ground current Ig

16 bits

F23

0.1 A or 0.01 A

1,2 (low, high)

Ia angle

16 bits

UINT

degrees

3,4 (low, high)

Ib angle

16 bits

UINT

degrees

5,6 (low, high)

Ic angle

16 bits

UINT

degrees

1,2 (low, high)

Motor load

16 bits

F3

0.01 FLA

Current unbalance

16 bits

UINT

Unbalanced biased
motor load (Ieq)

16 bits

F3

0.01 FLA

1,2 (low, high)

Voltage Vab

16 bits

UINT

3,4 (low, high)

Voltage Vbc

16 bits

UINT

5,6 (low, high)

Voltage Vca

16 bits

UINT

7,8 (low, high)

Average line voltage

16 bits

UINT

03h
3,4 (low, high)
MOTOR LOAD
5,6 (low, high)
04h
LINE
VOLTAGES

DESCRIPTION

1,2 (low, high)

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 2 of 8)


ATTRIBUTE

05h
PHASE
VOLTAGES

BYTES

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

1,2 (low, high)

Voltage Van

16 bits

UINT

3,4 (low, high)

Voltage Vbn

16 bits

UINT

5,6 (low, high)

Voltage Vcn

16 bits

UINT

7,8 (low, high)

Average phase
voltage

16 bits

UINT

06h
PHASE
VOLTAGE
ANGLES

1,2 (low, high)

Va angle

16 bits

UINT

degrees

3,4 (low, high)

Vb angle

16 bits

UINT

degrees

5,6 (low, high)

Vc angle

16 bits

UINT

degrees

07h
FREQUENCY

1,2 (low, high)

Frequency

16 bits

F3

0.01 Hz

1,2 (low, high)

BSD state

16 bits

F27

--

3,4 (low, high)

Backspin frequency

16 bits

F3

0.01 Hz

5,6 (low, high)

Backspin prediction
timer

16 bits

F1

08h
BSD STATE
AND FREQ.

09h
POWER

0Ah
ENERGY
0Bh
RTD TEMPERATURE

0Ch
LOCAL RTD
TEMPERATURE

1,2 (low, high)

Power factor

16 bits

F21

0.01 PF

3,4 (low, high)

Real power (kW)

16 bits

F4

kW

5,6 (low, high)

Real power (hp)

16 bits

UINT

hp

7,8 (low, high)

Reactive power

16 bits

F4

kvar

9,10 (low, high)

Apparent power

16 bits

UINT

kVA

1,2 (low, high)

MWh

16 bits

UINT

MWh

3,4 (low, high)

Positive Mvarh

16 bits

UINT

Mvarh

5,6 (low, high)

Negative Mvarh

16 bits

UINT

Mvarh

1,2 (low, high)

Local hottest stator


RTD

16 bits

UINT

---

3,4 (low, high)

Local hottest stator


RTD temperature

16 bits

F4

1,2 (low, high)

Local RTD 1
temperature

16 bits

F4

3,4 (low, high)

Local RTD 2
temperature

16 bits

F4

5,6 (low, high)

Local RTD 3
temperature

16 bits

F4

7,8 (low, high)

Local RTD 4
temperature

16 bits

F4

9,10 (low, high)

Local RTD 5
temperature

16 bits

F4

11,12 (low, high)

Local RTD 6
temperature

16 bits

F4

13,14 (low, high)

Local RTD 7
temperature

16 bits

F4

15,16 (low, high)

Local RTD 8
temperature

16 bits

F4

17,18 (low, high)

Local RTD 9
temperature

16 bits

F4

19,20 (low, high)

Local RTD 10
temperature

16 bits

F4

21,22 (low, high)

Local RTD 11
temperature

16 bits

F4

23,24 (low, high)

Local RTD 12
temperature

16 bits

F4

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG35

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 3 of 8)


ATTRIBUTE

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

1,2 (low, high)

Current demand

16 bits

UINT

3,4 (low, high)

Real power demand

16 bits

UINT

kW

5,6 (low, high)

Reactive power
demand

16 bits

UINT

kvar

7,8 (low, high)

Apparent power
demand

16 bits

UINT

kVA

1,2 (low, high)

Peak current
demand

16 bits

UINT

3,4 (low, high)

Peak real power


demand

16 bits

UINT

kW

5,6 (low, high)

Peak reactive power


demand

16 bits

UINT

kvar

7,8 (low, high)

Peak apparent
power demand

16 bits

UINT

kVA

1,2 (low, high)

Learned acceleration
time

16 bits

F2

x 0.1 seconds

3,4 (low, high)

Learned starting
current

16 bits

UINT

5,6 (low, high)

Learned starting
capacity

16 bits

UINT

7,8 (low, high)

Learned running cool


time constant

16 bits

UINT

minutes

9,10 (low, high)

Learned stopped
cool time constant

16 bits

UINT

minutes

11,12 (low, high)

Last starting
capacity

16 bits

UINT

13,14 (low, high)

Learned unbalance
k-factor

16 bits

UINT

--

1,2 (low, high)

Number of starts

16 bits

UINT

--

3,4 (low, high)

Number of restarts

16 bits

UINT

--

5,6 (low, high)

Digital counter

16 bits

UINT

--

7,8 (low, high)

Motor running hours

16 bits

UINT

hours

1,2 (low, high)

Cause of last trip

16 bits

F134

--

1 to 4(low, high)

Last trip date

32 bits

F18

--

5 to 8(low, high)

Last trip time

32 bits

F19

--

1,2 (low, high)

Last pre-trip Ia

16 bits

UINT

3,4 (low, high)

Last pre-trip Ib

16 bits

UINT

5,6 (low, high)

Last pre-trip Ic

16 bits

UINT

7,8 (low, high)

Last pre-trip Ig

16 bits

F2

0.1 A

14h
LAST PRETRIP MOTOR
LOAD

1,2 (low, high)

Last pre-trip motor


load

16 bits

F3

0.01 FLA

3,4 (low, high)

Last pre-trip
unbalance

16 bits

UINT

15h
PRE-TRIP
STATOR RTD
TEMP.

1,2 (low, high)

Local pre-trip hottest


stator RTD

16 bits

UINT

---

3,4 (low, high)

Local pre-trip hottest


stator RTD
temperature

16 bits

F4

0Dh
DEMAND

0Eh
PEAK
DEMAND

0Fh
LEARNED
DATA

10h
MOTOR
STATISTICS
11h
CAUSE OF
LAST TRIP
12h
LAST PRETRIP DATE
AND TIME.
13h
LAST PRETRIP
CURRENTS

CG36

BYTES

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 4 of 8)


ATTRIBUTE

BYTES

16h
LAST PRETRIP LINE
VOLTAGES

1,2 (low, high)

17h
LAST PRETRIP PHASE
VOLTAGES
18h
LAST PRETRIP FREQ.

19h
LAST PRETRIP POWER

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

Last pre-trip Vab

16 bits

UINT

volts

3,4 (low, high)

Last pre-trip Vbc

16 bits

UINT

volts

5,6 (low, high)

Last pre-trip Vca

16 bits

UINT

volts

1,2 (low, high)

Last pre-trip Van

16 bits

UINT

volts

3,4 (low, high)

Last pre-trip Vbn

16 bits

UINT

volts

5,6 (low, high)

Last pre-trip Vcn

16 bits

UINT

volts

1,2 (low, high)

Last pre-trip
frequency

16 bits

F3

0.01 Hz

1,2 (low, high)

Last pre-trip
kilowatts

16 bits

F4

kW

3,4 (low, high)

Last pre-trip kvar

16 bits

F4

kvar

5,6 (low, high)

Last pre-trip KVA

16 bits

UINT

kVA

7,8 (low, high)

Last pre-trip power


factor

16 bits

F21

0.01 PF

1Ah
TRIP DIAG.

6 bytes

Trip diagnostic data

48 bits

F176

1Bh
ALARM DIAG.

8 bytes

Alarm diagnostic
data

64 bits

F177

1,2 (low, high)

Overload lockout
timer

16 bits

UINT

minutes

3,4 (low, high)

Starts timer [1]

16 bits

UINT

minutes

5,6 (low, high)

Starts timer [2]

16 bits

UINT

minutes

7,8 (low, high)

Starts timer [3]

16 bits

UINT

minutes

9,10 (low, high)

Starts timer [4]

16 bits

UINT

minutes

11,12 (low, high)

Starts timer [5]

16 bits

UINT

minutes

13,14 (low, high)

Time between starts


timer

16 bits

UINT

minutes

15,16 (low, high)

Restart block timer

16 bits

UINT

seconds

17,16 (low, high)

Start inhibit timer

16 bits

UINT

minutes

1,2 (low, high)

Phase current Ia

16 bits

UINT

3,4 (low, high)

Phase current Ib

16 bits

UINT

5,6 (low, high)

Phase current Ic

16 bits

UINT

7,8 (low, high)

Average phase
current Iav

16 bits

UINT

1Ch
START BLOCK
STATUS

1Dh
ACTUAL
VALUES

9,10 (low, high)

Ground current Ig

16 bits

F23

0.1 A or 0.01 A

11,12 (low, high)

Ia angle

16 bits

UINT

degrees

13,14 (low, high)

Ib angle

16 bits

UINT

degrees

15,16 (low, high)

Ic angle

16 bits

UINT

degrees

17,18 (low, high)

Motor load

16 bits

F3

0.01 FLA

19,20 (low, high)

Current unbalance

16 bits

UINT

21,22 (low, high)

Unbalanced biased
motor load (Ieq)

16 bits

F3

0.01 FLA

23,24 (low, high)

Voltage Vab

16 bits

UINT

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG37

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 5 of 8)


ATTRIBUTE

1Dh
ACTUAL
VALUES
continued

1Dh
ACTUAL
VALUES
continued

CG38

BYTES

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

25,26 (low, high)

Voltage Vbc

16 bits

UINT

27,28 (low, high)

Voltage Vca

16 bits

UINT

29,30 (low, high)

Average line voltage

16 bits

UINT

31,32 (low, high)

Voltage Van

16 bits

UINT

33,34 (low, high)

Voltage Vbn

16 bits

UINT

35,36 (low, high)

Voltage Vcn

16 bits

UINT

37,38 (low, high)

Average phase
voltage

16 bits

UINT

39,40 (low, high)

Va angle

16 bits

UINT

degrees

41,42 (low, high)

Vb angle

16 bits

UINT

degrees

43,44 (low, high)

Vc angle

16 bits

UINT

degrees

45,46 (low, high)

Frequency

16 bits

F3

0.01 Hz

47,48 (low, high)

BSD state

16 bits

F27

--

49,50 (low, high)

Backspin frequency

16 bits

F3

0.01 Hz

51,52 (low, high)

Backspin prediction
timer

16 bits

F1

seconds

53,54 (low, high)

Power factor

16 bits

F21

0.01 PF

55,56 (low, high)

Real power (kW)

16 bits

F4

kW

57,58 (low, high)

Real power (hp)

16 bits

UINT

hp

59,60 (low, high)

Reactive power

16 bits

F4

kvar

61,62 (low, high)

Apparent power

16 bits

UINT

kVA

63,64 (low, high)

MWh

16 bits

UINT

MWh

65,66 (low, high)

Positive Mvarh

16 bits

UINT

Mvarh

67,68 (low, high)

Negative Mvarh

16 bits

UINT

Mvarh

69,70 (low, high)

Local Hottest stator


RTD

16 bits

UINT

---

71,72 (low, high)

Local Hottest stator


RTD temperature

16 bits

F4

73,74 (low, high)

Local RTD 1
temperature

16 bits

F4

75,76 (low, high)

Local RTD 2
temperature

16 bits

F4

77,78 (low, high)

Local RTD 3
temperature

16 bits

F4

79,80 (low, high)

Local RTD 4
temperature

16 bits

F4

81,82 (low, high)

Local RTD 5
temperature

16 bits

F4

83,84 (low, high)

Local RTD 6
temperature

16 bits

F4

85,86 (low, high)

Local RTD 7
temperature

16 bits

F4

87,88 (low, high)

Local RTD 8
temperature

16 bits

F4

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 6 of 8)


ATTRIBUTE

1Dh
ACTUAL
VALUES
continued

BYTES

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

89,90 (low, high)

Local RTD 9
temperature

16 bits

F4

91,92 (low, high)

Local RTD 10
temperature

16 bits

F4

93,94 (low, high)

Local RTD 11
temperature

16 bits

F4

95,96 (low, high)

Local RTD 12
temperature

16 bits

F4

97,98 (low, high)

Current demand

16 bits

UINT

99,100 (low, high) Real power demand

16 bits

UINT

kW

101,102 (low,
high)

Reactive power
demand

16 bits

F4

kvar

103, 104 (low,


high)

Apparent power
demand

16 bits

UINT

kVA

105, 106 (low,


high)

Peak current
demand

16 bits

UINT

107, 108 (low,


high)

Peak real power


demand

16 bits

UINT

kW

109, 110 (low,


high)

Peak reactive power


demand

16 bits

F4

kvar

111,112 (low,
high)

Peak apparent
power demand

16 bits

UINT

kVA

113,114 (low,
high)

Learned acceleration
time

16 bits

F2

0.1 seconds

115,116 (low,
high)

Learned starting
current

16 bits

UINT

117,118 (low,
high)

Learned starting
capacity

16 bits

UINT

119,120 (low,
high)

Learned running cool


time constant

16 bits

UINT

minutes

121,122 (low,
high)

Learned stopped
cool time constant

16 bits

UINT

minutes

123,124 (low,
high)

Last starting
capacity

16 bits

UINT

125,126 (low,
high)

Learned unbalance
k-factor

16 bits

UINT

--

127,128 (low,
high)

Number of starts

16 bits

UINT

--

129,130 (low,
high)

Number of restarts

16 bits

UINT

--

131,132 (low,
high)

Digital counter

16 bits

UINT

--

133,134 (low,
high)

Motor running Hours

16 bits

UINT

hours

135,136 (low,
high)

Cause of last trip

16 bits

F134

--

137 to 140 (low,


high)

Last trip date

32 bits

F18

--

141 to 144 (low,


high)

Last trip time

32 bits

F19

--

145, 146 (low,


high)

Last pre-trip Ia

16 bits

UINT

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG39

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 7 of 8)


ATTRIBUTE

1Dh
ACTUAL
VALUES
continued

CG40

BYTES

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

147, 148 (low,


high)

Last pre-trip Ib

16 bits

UINT

149, 150 (low,


high)

Last Pre-trip Ic

16 bits

UINT

151, 152 (low,


high)

Last Pre-trip Ig

16 bits

F2

0.1 A

153, 154 (low,


high)

Last pre-trip motor


load

16 bits

F3

0.01 FLA

155, 156 (low,


high)

Last pre-trip
unbalance

16 bits

UINT

157, 158 (low,


high)

Last pre-trip local


hottest stator RTD

16 bits

UINT

---

159, 160 (low,


high)

Last pre-trip local


hottest stator RTD
temperature

16 bits

F4

161, 162 (low,


high)

Last pre-trip Vab

16 bits

UINT

volts

163, 164 (low,


high)

Last pre-trip Vbc

16 bits

UINT

volts

165, 166 (low,


high)

Last pre-trip Vca

16 bits

UINT

volts

167, 168 (low,


high)

Last pre-trip Van

16 bits

UINT

volts

169, 170 (low,


high)

Last pre-trip Vbn

16 bits

UINT

volts

171, 172 (low,


high)

Last pre-trip Vcn

16 bits

UINT

volts

173, 174 (low,


high)

Last pre-trip
frequency

16 bits

F3

0.01 Hz

175, 176 (low,


high)

Last pre-trip
kilowatts

16 bits

F4

kW

177, 178 (low,


high)

Last pre-trip kvar

16 bits

F4

kvar

179, 180 (low,


high)

Last pre-trip KVA

16 bits

UINT

kVA

181, 182 (low,


high)

Last pre-trip power


factor

16 bits

F21

0.01 PF

183 to 188

Trip diagnostic data

48 bits

F176

189 to 196

Alarm diagnostic
data

64 bits

F177

197, 198 (low,


high)

Overload lockout
timer

16 bits

UINT

minutes

199, 200 (low,


high)

Starts timer [1]

16 bits

UINT

minutes

201, 202 (low,


high)

Starts timer [2]

16 bits

UINT

minutes

203, 204 (low,


high)

Starts timer [3]

16 bits

UINT

minutes

205, 206 (low,


high)

Starts timer [4]

16 bits

UINT

minutes

207, 208 (low,


high)

Starts timer [5]

16 bits

UINT

minutes

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 8 of 8)


ATTRIBUTE

4.13

BYTES

DESCRIPTION

LENGTH

FORMAT

VALUE/UNIT

209, 210 (low,


high)

Time between starts


timer

16 bits

UINT

minutes

211, 212 (low,


high)

Restart block timer

16 bits

UINT

seconds

213, 214 (low,


high)

Start inhibit timer

16 bits

UINT

minutes

DeviceNet Loss Of Communication Trip


If the 369 detects a problem in communicating with the DeviceNet master, the DeviceNet
Loss of Communications feature can be used to operate on any combination of output
relays.
If the 369 DeviceNet communications is offline and not communicating with a master, then
the Fieldbus Loss of Comms function (if enabled) will activate. This feature can be
programmed for Latched or Unlatched operation.

If programmed as Latched:
The Fieldbus Loss of Comms output relay will remain latched until communication with
the Master is (re) established AND the latched output relay is manually reset or remotely
reset via Modbus communications.

If programmed as Unlatched:
Any output relays programmed for this feature will be de-activated once communication is
restored; the Loss of Communications condition will be cleared and the assigned output
relays will automatically de-activate.
The setpoints associated with this feature are:
1.

Fieldbus Loss of Comms Enable

2.

Fieldbus Loss of Comms Delay

3.

Assigned Fieldbus Loss of Comms Relay

Refer to the 369 Instruction Manual, Chapter 5: 369 Relay Communications for more
information on these setpoints.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG41

DEVICENET PROTOCOL

4.14

CGCOMMUNICATIONS GUIDE

DeviceNet Data Formats


FORMAT

VALUE

F167

Power off / Not online

Online, Connected

Link failure

Not defined

F168

Connection status: unsigned 16 bit integer

Nonexistent

Configuring

(Not used)

Established

Timed out

5
F170

Deferred delete
DeviceNet baud rate: unsigned 16 bit integer

125 kbps

250 kbps

2
F172

500 kbps
Motor status: Unsigned 8 bit integer

Bit 0

Stopped

Bit 1

Starting

Bit 2

Running

Bit 3

Overloaded

Bit 4

Tripped

Bits 5 to 7

Reserved

F173

Digital input status: unsigned 8 bit integer

Bit 0

Access Switch Status


0 = Open, 1= Closed

Bit 1

Speed Switch Status


0 = Open, 1= Closed

Bit 2

Spare Switch Status


0 = Open, 1= Closed

Bit 3

Differential Switch Status


0 = Open, 1= Closed

Bit 4

Emergency Switch status


0 = Open, 1= Closed

Bit 5

Reset Switch Status


0 = Open, 1= Closed

Bit 6

Reserved

Bit 7
F174

CG42

NAME/DESCRIPTION

Network status: unsigned 16 bit integer

Reserved
Output relay status: unsigned 8 bit integer

Bit 0

Trip Relay Status


0 = De-energized, 1 = Energized

Bit 1

Alarm Relay Status


0 = De-energized, 1 = Energized

Bit 2

Aux1 Relay Status


0 = De-energized, 1 = Energized

Bit 3

Aux2 Relay Status


0 = De-energized, 1 = Energized

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

FORMAT

VALUE

Bits 4 to 7
F175

Flag change state: unsigned 8 bit integer

Bit 0

Trip/Alarm status; 1= operated

Bits 1 to 7

Reserved

F176

Relay trips: bitmask

Byte 1

Byte 2

Byte 3

Byte 4

F176
ctd.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

NAME/DESCRIPTION

Reserved

Byte 5

Bit 0

Single Phasing Trip

Bit 1

Spare Switch Trip

Bit 2

Emergency Switch Trip

Bit 3

Differential Switch Trip

Bit 4

Speed Switch Trip

Bit 5

Reset Switch Trip

Bit 6

Reserved

Bit 7

Overload Trip

Bit 0

Short Circuit Trip

Bit 1

Short Circuit Backup Trip

Bit 2

Mechanical Jam Trip

Bit 3

Undercurrent Trip

Bit 4

Current Unbalance Trip

Bit 5

Ground Fault Trip

Bit 6

Ground Fault Backup Trip

Bit 7

Reserved

Bit 0

Acceleration Timer Trip

Bit 1

RTD 1 Trip

Bit 2

RTD 2 Trip

Bit 3

RTD 3 Trip

Bit 4

RTD 4 Trip

Bit 5

RTD 5 Trip

Bit 6

RTD 6 Trip

Bit 7

RTD 7 Trip

Bit 0

RTD 8 Trip

Bit 1

RTD 9 Trip

Bit 2

RTD 10 Trip

Bit 3

RTD 11 Trip

Bit 4

RTD 12 Trip

Bit 5

Undervoltage Trip

Bit 6

Overvoltage Trip

Bit 7

Voltage Phase Reversal Trip

Bit 0

Underfrequency Trip

Bit 1

Overfrequency Trip

Bit 2

Lead Power Factor Trip

Bit 3

Lag Power Factor Trip

Bit 4

Positive kvar Trip

Bit 5

Negative kvar Trip

Bit 6

Underpower Trip

Bit 7

Reverse Power Trip

CG43

DEVICENET PROTOCOL

CGCOMMUNICATIONS GUIDE

FORMAT

VALUE

Byte 6

NAME/DESCRIPTION

Bit 0

Incomplete Sequence Trip

Bit 1

Reserved

Bit 2

Reserved

Bit 3

Reserved

Bit 4

Reserved

Bit 5

Reserved

Bit 6

Reserved

Bit 7

Reserved

F177

Relay alarms: bitmask

Byte 1

Byte 2

Byte 3

F177
ctd.

Byte 4

Byte 5

CG44

Bit 0

Spare Switch Alarm

Bit 1

Emergency Switch Alarm

Bit 2

Differential Switch Alarm

Bit 3

Speed Switch Alarm

Bit 4

Reset Switch Alarm

Bit 5

Reserved

Bit 6

Thermal Capacity Alarm

Bit 7

Overload Alarm

Bit 0

Mechanical Jam Alarm

Bit 1

Undercurrent Alarm

Bit 2

Current Unbalance Alarm

Bit 3

Ground Fault Alarm

Bit 4

Undervoltage Alarm

Bit 5

Overvoltage Alarm

Bit 6

Overfrequency Alarm

Bit 7

Underfrequency Alarm

Bit 0

Lead Power Factor Alarm

Bit 1

Lag Power Factor Alarm

Bit 2

Positive kvar Alarm

Bit 3

Negative kvar Alarm

Bit 4

Underpower Alarm

Bit 5

Reverse Power Alarm

Bit 6

RTD 1 Alarm

Bit 7

RTD 2 Alarm

Bit 0

RTD 3 Alarm

Bit 1

RTD 4 Alarm

Bit 2

RTD 5 Alarm

Bit 3

RTD 6 Alarm

Bit 4

RTD 7 Alarm

Bit 5

RTD 8 Alarm

Bit 6

RTD 9 Alarm

Bit 7

RTD 10 Alarm

Bit 0

RTD 11 Alarm

Bit 1

RTD 12 Alarm

Bit 2

RTD 1 High Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

DEVICENET PROTOCOL

FORMAT

VALUE

Byte 6

Byte 7

Byte 8

F178

RTD 2 High Alarm

Bit 4

RTD 3 High Alarm

Bit 5

RTD 4 High Alarm

Bit 6

RTD 5 High Alarm

Bit 7

RTD 6 High Alarm

Bit 0

RTD 7 High Alarm

Bit 1

RTD 8 High Alarm

Bit 2

RTD 9 High Alarm

Bit 3

RTD 10 High Alarm

Bit 4

RTD 11 High Alarm

Bit 5

RTD 12 High Alarm

Bit 6

Open RTD Sensor Alarm

Bit 7

Short RTD Alarm

Bit 0

Trip Counters Alarm

Bit 1

Starter Failure Alarm

Bit 2

Current Demand Alarm

Bit 3

kW Demand Alarm

Bit 4

kvar Demand Alarm

Bit 5

kVA Demand Alarm

Bit 6

Digital Counter Alarm

Bit 7

Overload Lockout Block

Bit 0

Start Inhibit Block

Bit 1

Starts Hour Block

Bit 2

Time Between Starts Block

Bit 3

Restart Block

Bit 4

Reserved

Bit 5

Back-Spin Block

Bit 6

Loss of Remote RTD


Communication

Bit 7

Spare Switch Alarm

DeviceNet Communication status: unsigned 16 bit


integer

Bit 0

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

NAME/DESCRIPTION

Bit 3

0 = not owned,
1 = owned by master

Bit 1

Reserved

Bit 2

0 = factory default, 1=
configured

Bits 3 to 7

Reserved

Bit 8

1 = Minor recoverable fault

Bit 9

1 = Minor unrecoverable fault

Bit 10

1 = Major recoverable fault

Bit 11

1 = Major unrecoverable fault

Bits 12 to 15

Reserved

CG45

MODBUS RTU PROTOCOL

CGCOMMUNICATIONS GUIDE

Modbus RTU Protocol


5.1

Data Frame Format and Data Rate


One data frame of an asynchronous transmission to or from an 369 is default to 1 start bit,
8 data bits, and 1 stop bit. This produces a 10 bit data frame. This is important for
transmission through modems at high bit rates (11 bit data frames are not supported by
Hayes modems at bit rates of greater than 300 bps). The parity bit is optional as odd or
even. If it is programmed as odd or even, the data frame consists of 1 start bit, 8 data bits,
1 parity bit, and 1 stop bit.
Modbus protocol can be implemented at any standard communication speed. The 369
RS485, fiber optic and RS232 ports support operation at 1200, 2400, 4800, 9600, and
19200 baud.

5.2

Data Packet Format


A complete request/response sequence consists of the following bytes (transmitted as
separate data frames):
Master Request Transmission:
SLAVE ADDRESS
FUNCTION CODE
DATA
CRC

- 1 byte
- 1 byte
- variable number of bytes depending on FUNCTION CODE
- 2 bytes

Slave Response Transmission:


SLAVE ADDRESS
FUNCTION CODE
DATA
CRC

- 1 byte
- 1 byte
- variable number of bytes depending on FUNCTION CODE
- 2 bytes

SLAVE ADDRESS: This is the first byte of every transmission. It represents the userassigned address of the slave device that is to receive the message sent by the master.
Each slave device must be assigned a unique address and only the addressed slave will
respond to a transmission that starts with its address. In a master request transmission the
SLAVE ADDRESS represents the address of the slave to which the request is being sent. In a
slave response transmission the SLAVE ADDRESS represents the address of the slave that is
sending the response. Note: A master transmission with a SLAVE ADDRESS of 0 indicates a
broadcast command. Broadcast commands can be used for specific functions.
FUNCTION CODE: This is the second byte of every transmission. The modbus protocol
defines function codes of 1 to 127. The 369 implements some of these functions. In a
master request transmission the FUNCTION CODE tells the slave what action to perform. In
a slave response transmission if the FUNCTION CODE sent from the slave is the same as
the FUNCTION CODE sent from the master indicating the slave performed the function as
requested. If the high order bit of the FUNCTION CODE sent from the slave is a 1 (i.e. if the
FUNCTION CODE is > 127) then the slave did not perform the function as requested and is
sending an error or exception response.

CG46

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MODBUS RTU PROTOCOL

DATA: This will be a variable number of bytes depending on the FUNCTION CODE. This may
be actual values, setpoints, or addresses sent by the master to the slave or by the slave to
the master. Data is sent MSByte first followed by the LSByte.
CRC: This is a two byte error checking code. CRC is sent LSByte first followed by the
MSByte.

5.3

Error Checking
The RTU version of Modbus includes a two byte CRC-16 (16 bit cyclic redundancy check)
with every transmission. The CRC-16 algorithm essentially treats the entire data stream
(data bits only; start, stop and parity ignored) as one continuous binary number. This
number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16 bit remainder of the division is appended to the end of the
transmission, LSByte first. The resulting message including CRC, when divided by the same
polynomial at the receiver will give a zero remainder if no transmission errors have
occurred.
If an 369 Modbus slave device receives a transmission in which an error is indicated by the
CRC-16 calculation, the slave device will not respond to the transmission. A CRC-16 error
indicates than one or more bytes of the transmission were received incorrectly and thus
the entire transmission should be ignored in order to avoid the 369 performing any
incorrect operation.
The CRC-16 calculation is an industry standard method used for error detection. An
algorithm is included here to assist programmers in situations where no standard CRC-16
calculation routines are available.

5.4

CRC-16 Algorithm
Once the following algorithm is complete, the working register "A" will contain the CRC
value to be transmitted. Note that this algorithm requires the characteristic polynomial to
be reverse bit ordered. The MSbit of the characteristic polynomial is dropped since it does
not affect the value of the remainder. The following symbols are used in the algorithm:
-->
data transfer
A
16 bit working register
AL
low order byte of A
AH
high order byte of A
CRC
16 bit CRC-16 value
i, j
loop counters
(+)
logical exclusive or operator
Di
i-th data byte (i = 0 to N-1)
G
16 bit characteristic polynomial = 1010000000000001 with MSbit
dropped and bit order
reversed
shr(x)
shift right (the LSbit of the low order byte of x shifts into a carry flag, a '0'
is shifted into the
MSbit of the high order byte of x, all other bits shift right one location
The algorithm is as follows:
1. FFFF hex --> A

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG47

MODBUS RTU PROTOCOL

CGCOMMUNICATIONS GUIDE

2. 0 --> i
3. 0 --> j
4. Di (+) AL --> AL
5. j+1 --> j
6. shr(A)
7. is there a carry?
8. is j = 8?

No: go to 8.
Yes: G (+) A --> A

No: go to 5.
Yes: go to 9.

9. i+1 --> i
10. is i = N?

No: go to 3.
Yes: go to 11.

11. A --> CRC

5.5

Timing
Data packet synchronization is maintained by timing constraints. The receiving device
must measure the time between the reception of characters. If three and one half
character times elapse without a new character or completion of the packet, then the
communication link must be reset (i.e. all slaves start listening for a new transmission from
the master). Thus at 9600 baud a delay of greater than 3.5 1 / 9600 10 = 3.65 ms will
cause the communication link to be reset.

5.6

Supported Modbus Functions


The following Modbus functions are supported by the 369:
03 - Read Setpoints and Actual Values
04 - Read Setpoints and Actual Values
05 - Execute Operation
06 - Store Single Setpoint
07 - Read Device Status
08 - Loopback Test
16 - Store Multiple Setpoints
For detailed Modbus function code descriptions, refer to the Modicon Modbus Protocol
Reference guide.

5.7

Error Responses
When an 369 detects an error other than a CRC error, a response will be sent to the master.
The MSbit of the FUNCTION CODE byte will be set to 1 (i.e. the function code sent from the
slave will be equal to the function code sent from the master plus 128). The following byte
will be an exception code indicating the type of error that occurred.
Transmissions received from the master with CRC errors will be ignored by the 369 Relay.
The slave response to an error (other than CRC error) will be:

CG48

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MODBUS RTU PROTOCOL

SLAVE ADDRESS
FUNCTION CODE
EXCEPTION CODE
CRC

- 1 byte
- 1 byte (with MSbit set to 1)
- 1 byte
- 2 bytes

The 369 implements the following exception response codes.

01 - ILLEGAL FUNCTION:
The function code transmitted is not one of the functions supported by the 369 Relay.

02 - ILLEGAL DATA ADDRESS:


The address referenced in the data field transmitted by the master is not an allowable
address for the 369 Relay.

03 - ILLEGAL DATA VALUE:


The value referenced in the data field transmitted by the master is not within range for
the selected data address.

5.8

Modbus Commands
The following commands can be sent to Modbus address 0x0080 (format code F31).
Commands 1 to 4 can also be sent using Modbus function code 5 (Execute Operation).

Command 1 (Remote Reset 369): Modbus Command 1 will attempt to clear the status
of protection elements and output relay states.

Command 2 (Motor Start): Modbus Command 2 will activate the programmed start
relay, as long as it is not currently active and the stop relay is not currently active.

Command 3 (Motor Stop): Modbus Command 3 will activate the trip relay as long as it
is not currently active and the start relay is not currently active.

Command 4 (Waveform Trigger): Modbus Command 4 will trigger the waveform


capture trace memory.

Command 6 (Clear Trip Counters): Modbus Command 6 will clear all trip counters.

Command 7 (Clear Last Trip Data): Modbus Command 7 will clear the last trip data.

Command 10 (Clear RTD Maximums): Modbus Command 10 will initialize all RTD (and
Remote RTD, if applicable) maximum data to default values.

Command 11 (Reset Motor Info): Modbus Command 11 will clear the number of
motor starts, number of motor restarts, motor running hours, and number of restart
attempts. It will also clear all learned motor statistics and Data Logger data.

Command 12 (Clear/Reset All Data): Modbus Command 12 will clear all event data,
trip counters, last trip data, peak demand data, RTD maximums data, motor statistics
data, Data Logger data, and all energy data.

Command 20 (Protection Function Blocking): This command must be sent using


Modbus function code 10h (Store Multiple Setpoints). This allows the 369 to accept the
two required 16-bit values in one transmission. The first data word is the command
number (20). The 2nd data word contains the bitmask information for which functions
to block/unblock as per format code F180.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG49

MODBUS RTU PROTOCOL

CGCOMMUNICATIONS GUIDE

When this command is sent to the 369, the protection function blocking setpoints
(Modbus addresses 1520 to 1528) are updated accordingly. For example, for Bit 0 in
the 2nd data word, the setpoint value for Block Undercurrent/Underpower at address
1521 will be modified to contain either a 1 or 0, depending on the bit value.
Refer to the 369 Instruction Manual, chapter 5: Block Functions for additional
information about the protection function blocking feature.

Command 21 (Force Output Relays): Modbus Command 20 must be sent using


Modbus function code 10h (Store Multiple Setpoints). This allows the 369 to accept the
two required 16-bit values in one transmission. The first data word is the command
number (21). The 2nd data word contains the bitmask information for which relays to
energize/de-energize as per format code F141.
The purpose of this command is to allow the control of the output relay status,
regardless of the motor status (running, stopped, etc.). Only relays that have been
programmed under the ASSIGN COMMS FORCE RELAYS setpoint can be forced
using this command.
Refer to the 369 Instruction Manual, chapter 5: Force Output Relays for more
information about the force output relays feature.

CG50

Command 24 (Clear Data Logger Data): This command will clear all the existing data
presently available in the Data Logger feature. Please refer to the 369 Instruction
Manual, chapter 6: Data Logger and 6.6: Data Logger for more information on the Data
Logger feature.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Memory Map
6.1

Memory Map Information


The data stored in the 369 is grouped as setpoints and actual values. Setpoints can be read
and written by a master computer. Actual Values are read-only. All setpoints and actual
values are stored as two-byte values. That is, each register address is the address of a twobyte value. Addresses are listed in hexadecimal. Data values (setpoint ranges, increments,
factory values) are in decimal.
Many Modbus communications drivers add 40001d to the actual address of the
register addresses. For example: if address 0h was to be read, 40001d would be the
address required by the Modbus communications driver; if address 320h (800d) was to
be read, 40801d would be the address required by the Modbus communications driver.

Note

6.2

User Definable Memory Map Area


The 369 has a powerful feature, called the User Definable Memory Map, which allows a
computer to read up to 125 non-consecutive data registers (setpoints or actual values) by
using one Modbus packet. It is often necessary for a master computer to continuously poll
various values in each of the connected slave relays. If these values are scattered
throughout the memory map, reading them would require numerous transmissions and
would burden the communication link. The User Definable Memory Map can be
programmed to join any memory map address to one in the block of consecutive User Map
locations, so that they can be accessed by reading these consecutive locations.
The User Definable area has two sections:
1.

A Register Index area (memory map addresses 0180h-01FCh) that contains


125 Actual Values or Setpoints registers.

2.

A Register area (memory map addresses 0100h-017Ch) that contains the data
at the addresses in the Register Index.

Register data that is separated in the rest of the memory map may be remapped to
adjacent register addresses in the User Definable Registers area. This is accomplished by
writing to register addresses in the User Definable Register Index area. This allows for
improved through-put of data and can eliminate the need for multiple read command
sequences. For example, if the values of Average Phase Current (register address 0306h)
and Hottest Stator RTD Temperature (register address 0320h) are required to be read from
an 369, their addresses may be remapped as follows:
1.

Write 0306h to address 0180h (User Definable Register Index 0000) using
function code 06 or 16.

2.

Write 0320h to address 0181h (User Definable Register Index 0001) using
function code 06 or 16.

A read (function code 03 or 04) of registers 0100h (User Definable Register 0000) will return
the Phase A Current and register 0101h (User Definable Register 0001) will return Hottest
Stator RTD Temperature.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG51

MEMORY MAP

6.3

CGCOMMUNICATIONS GUIDE

Event Recorder
The 369 event recorder data starts at address 3000h. Address 3003h is a pointer to the
event of interest (1 representing the oldest event and 512 representing the latest event. To
retrieve event 1, write 1 to the Event Record Selector (3003h) and read the data from
3004h to 3022h. To retrieve event 2, write 2 to the Event Record Selector (3003h) and read
the data from 3004h to 3022h. All 512 events may be retrieved in this manner. The time
and date stamp of each event may be used to ensure that all events have been retrieved in
order without new events corrupting the sequence of events (event 3 should be more
recent than event 2, event 2 should be more recent than event 1, etc.).
The digital counter will be displayed when one of the digital inputs has been set up as a
digital counter. The digital counter can be cleared with the S1 369 SETUP CLEAR/
PRESET DATA PRESET DIGITAL COUNTER setpoint. When the digital counter has
exceeded 65535, it will automatically be reset by the 369 Relay relay to 0.

6.4

Waveform Capture
The 369 stores 16 cycles of A/D samples each time a trip occurs in a trace buffer. The Trace
Memory Trigger is set up in S1 Preferences and determines how many pre-trip and posttrip cycles are stored. The trace buffer is time and date stamped and may be correlated to
a trip in the event record. 7 waveforms are captured this way when a trip occurs. These are
the 3 phase currents, ground current and 3 voltage waveforms. The last three captured
records are retained by the 369. This information is stored in volatile memory and will be
lost if power is cycled to the relay.
To access the captured waveforms, select the captured record by writing to the Trace
Memory Buffer Selector (address 30F5h), then select waveform of interest by writing its
trace memory channel (see following table) to the Trace Memory Channel Selector
(address 30F6h). Then read the trace memory data from address 3100h to 31FFh. The
values read are in actual amperes or volts.
TRACE MEMORY
CHANNEL

WAVEFORM

TRACE MEMORY
CHANNEL

WAVEFORM

Phase A current

Phase A voltage1

Phase B current

Phase B voltage

Phase C current

Phase C voltage1

Ground current

1. For an Open Delta VT connection channel 4 contains Vab data and channel 6 contains Vcb data.

6.5

Motor Start Data Logger


When a motor start status condition is detected by the 369 relay, the MOTOR START
DATA LOGGER is triggered and begins to sample and record the following parameters at
a rate of 1 sample every 200ms:

CG52

True RMS values of the Phase A, B and C Currents (Ia, Ib, and Ic).

True RMS value of the Ground current (Ig).

Current Unbalance (%).

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

True RMS values of the Phase A-N, B-N, and C-N voltages (Van, Vbn, and Vcn) if VT
CONNECTION TYPE is set to Wye.
True RMS values of the Phase A-B, B-C and C-A voltages (Vab, Vbc, and Vca) if VT
CONNECTION TYPE is set to Delta.

Thermal Capacity Used (%).

Frequency.

Breaker/Contactor Contact Input Status

Motor Speed (low/high).

1 second of pre-trigger data and 29 seconds of post-trigger data are recorded. The data
logger ignores all subsequent triggers and continues to record data until the active record
is finished.
A total of 6 logs are stored in the relay. Log #1 is the baseline log, it is written only by the
first start after clearing the MOTOR START DATA LOGGER (see the 369 Instruction
Manual, chapter 5: Clear/Preset Data). Logs #2 to 6 are rolling buffers of the last 5 motor
starts. Each new log automatically shifts the rolling buffer and overwrites the oldest log,
#2.
Log files are formatted using CSV (comma delimited values). The files can be downloaded
and displayed via EnerVista 369 Setup software. All files are stored in non-volatile memory;
information is retained when power to the relay is lost.

6.6

Data Logger
The Data Logger allows up to 16 channels of data parameters (refer to Modbus format
code F189 for the available parameters) to be continually recorded at a defined rate of
between 1 and 3600 seconds. The 369 has allocated 32k bytes of RAM for Data Log
storage. All data will be lost upon loss of the 369 control power.
Internal to the 369, the memory structure is partitioned into 256 blocks containing 64 twobyte registers. Blocks 0 and 1 have been allocated for the Header data, and Blocks 2-255
have been allocated to the logged data. In order to access the Log data and read it via the
"Data Logger Data" Modbus addresses 0x3281 to 0x32C0, a Block index value is stored to
the Data Log Memory Access Block Number at Modbus address 0x1E23. The data obtained
from the Data Logger Data registers will differ depending on the Block index value stored.
Each entry into a Data Log is called a Record. The Record size will vary in size depending
upon the how many channels the user wishes to use. In addition to the actual logged data
itself, the Data Logger contains what is called the Header, which can be read from Modbus
address 0x3200 to 0x3278. The Data Log Header contains the following read-only
information:

Log Time Interval: This is the interval at which the data log will store entries (1~3600s).

Log Record Size: This is the size of each Record entry into the Data Log. It is based
upon how many channels have been selected to use.

Log Total Possible Records: This value indicates the maximum number of potential
records available, which depends on the record size.

Total Logs Since Last Clear: This value indicates the number of Logs that have been
generated since the Data Logger was last cleared. Although it's maximum range is
65535, the 369 will only retain up to the latest 50 records.

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG53

MEMORY MAP

6.7

CGCOMMUNICATIONS GUIDE

Total Logs Presently Used: This value indicates the total number of Logs that have
been captured and are presently available in the 369.

Total Records Presently Used: This is the number of records that have been written
into the Data Log and are presently available in the 369.

Log Status: This reports the current status of the Data Logger (Running or Stopped).

Log Time Remaining Until Next Reading: This is a counter showing how much time
remains until the next record is to be written into the Data Log (1~3600s).

Data Logger Percentage Full: Indicates what percentage of the total available
memory is used.

Pointer To Next Record To Write: This value points to the internal data address of the
location of the next record to be written.

Pointer To Log (1-50) Starting Address : This value points to the internal data address
of the location of each of the potential 50 records.

Log (1-50) Number of Records: This value provides the number of records that each of
the 50 potential Logs contain.

Log (1-50) Start/Stop Method: This value is used to indicate the method by which each
log was started and stopped. If the bit value for the Start is zero, it was started by a
motor start event. Refer to Modbus format code F191 for more information on the
format of this data.

Modbus Memory Map


Table CG10: MEMORY MAP (Sheet 1 of 77)
ADDR
(hex)

0000
0001
0002
0003
0004
0005
0006
0007
0008

000F
0010

0017
--0020
0021
0022

CG54

DESCRIPTION

STEP
VALUE
PRODUCT ID (ADDRESSES 0000 TO 007F)
PRODUCT ID

GE Multilin Product Code


Product Hardware Revision
Firmware Revision
Installed Modifications
Boot Revision
Boot Modification Number
Reserved
Reserved
Order Code

Modify Options
Modify Options Passcode
Characters
1 and 2

Modify Options Passcode


Characters
15 and 16
--Serial Number character 1 and 2
Serial Number character 3 and 4
Serial Number character 5 and 6

MIN.

MAX.

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
N/A
0
0
0
0

26
N/A
65535
999
65535
N/A

1
N/A
1
1
1
-

N/A
N/A
N/A
N/A
N/A

F1
F15
F16
F14
F1
F13
N/A

53
A
N/A
0
0
0
-

32

127

F1

""

32

127

F1

""

N/A
N/A
N/A

N/A
N/A
N/A

N/A
N/A
N/A

ASCII
ASCII
ASCII

F22
F22
F22

N/A
N/A
N/A

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 2 of 77)


ADDR
(hex)

0023

DESCRIPTION

MIN.

0026
0028
...

Serial Number character 7 and 8


Serial Number character 9 and
10
Serial Number character 11 and
12
Main Firmware Build Date
Main Firmware Build Time
Reserved

0040
...

0024
0025

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

N/A

N/A

N/A

ASCII

F22

N/A

N/A

N/A

N/A

ASCII

F22

N/A

N/A

N/A

N/A

ASCII

F22

N/A

N/A
N/A
-

N/A
N/A
-

N/A
N/A
-

F18
F19
-

Manufacturing Date

1995

2094

F18

Reserved

N/A
N/A
Jan.1,199
9
-

SETPOINT ACCESS

0050
0051
0052
0053
0054
0055
0056
0057
0058
0059
...

Keypad Access Level


Comm Access Level
Access Password Character 1
and 2
Access Password Character 3
and 4
Access Password Character 5
and 6
Access Password Character 7
and 8
Encrypted Access Password 1
and 2
Encrypted Access Password 3
and 4
Encrypted Access Password 5
and 6
Encrypted Access Password 7
and 8
Reserved

0
0

1
1

1
1

N/A
N/A

F162
F162

0
0

32

127

F1

""

32

127

F1

""

32

127

F1

""

32

127

F1

32

127

F1

AI

32

127

F1

KF

32

127

F1

BA

32

127

F1

IK

COMMANDS (ADDRESSES 0080 TO 00FB)

0080
0081

...

Command Function Code


Reserved
RRTD 1 Command Function
Code
RRTD 2 Command Function
Code
RRTD 3 Command Function
Code
RRTD 4 Command Function
Code
Reserved

00F0
00F2
...

Time (2 words)
Date (2 words)
Reserved

00FC
00FD

Fieldbus Loss of Comms Enable


Fieldbus Loss of Comms Delay
Assign Fieldbus Loss of Comms
Relay
Profibus Cyclic Input Data
Configuration

0082
0083
0084
0085

21

F31

F31

F31

F31

F31

N/A
N/A

F19
F18

REAL TIME CLOCK

valid
valid

time
date

PROFIBUS COMMUNICATIONS

00FE
00FF

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
25

2
1000

1
250

msec

F115
F2

0 (Off)
25

15

F169

0 (None)

110

F1

CG55

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 3 of 77)


ADDR
(hex)

0100

017C
...
0180

01FC
...

DESCRIPTION

MIN.

STEP
VALUE
USER MAP (ADDRESSES 0100 TO 017F)

User Map Value # 1

User Map Value # 125


Reserved
User Map Address # 1

User Map Address # 125


Reserved

MAX.

UNITS

FORMAT
CODE

FACTORY
DEFAULT

---

---

---

---

---

---

---

---

---

---

---

---

3FFF

hex

F1

3FFF

hex

F1

F133
F1

0
0

F20

-1

ACTUAL VALUES (ADDRESSES 0200 TO 0FFF)


MOTOR STATUS

0200
0201

0
0

4
100

0202

Motor Status
Motor Thermal Capacity Used
Estimated Time to Trip on
Overload

1
1

-1

65500 1

0203
0204
0205

Restart Attempts
Restart Total Delay
Restart In Progress

0
0
0

20000 1
65535 1
1
1

sec.
Y/N

F1
F1
F1

0206

UVR Power Loss Time

40000 1

0.1 s

F2

Read
Only

0207
...

Motor Speed Status


Reserved

N/A

F186

0220
0221
0223
0225
0226
0228
022A
022C
022D
022E
...

Cause of Last Trip


Last Trip Time (2 words)
Last Trip Date (2 words)
Last Trip Motor Speed
Phase A Pre-Trip Current
Phase B Pre-Trip Current
Phase C Pre-Trip Current
Motor Load Pre - Trip
Current Unbalance Pre - Trip
Ground Current Pre - Trip
Reserved
Hottest Stator RTD Owner
During Trip
Hottest Stator RTD During Trip
Pre-Trip Temperature of Hottest
Stator RTD
Pre-Trip Voltage Vab
Pre-Trip Voltage Vbc
Pre-Trip Voltage Vca
Pre-Trip Voltage Van
Pre-Trip Voltage Vbn
Pre-Trip Voltage Vcn
Pre-Trip System Frequency
Pre-Trip Real Power
Pre-Trip Reactive Power
Pre-Trip Apparent Power
Pre-Trip Power Factor

0
N/A
N/A
0
0
0
0
0
0
0
-

276
N/A
N/A
2
65535
65535
65535
2000
100
50000
-

1
N/A
N/A
1
1
1
1
1
1
1
-

N/A
N/A
N/A
A
A
A
FLA
%
A
-

F134
F19
F18
F186
F1
F1
F1
F3
F1
F2
-

0
0
0
0
0
0
0
-

N/A

F165

12

F1

-40

200

F4

0
0
0
0
0
0
0
-32000
-32000
0
-99

65000
65000
65000
65000
65000
65000
12000
32000
32000
50000
100

1
1
1
1
1
1
1
1
1
1
1

V
V
V
V
V
V
Hz
kW
kvar
kVA
-

F1
F1
F1
F1
F1
F1
F3
F4
F4
F1
F21

0
0
0
0
0
0
0
0
0
0
0

AUTORESTART

MOTOR SPEED STATUS

2
LAST TRIP DATA

0233
0234
0235
0236
0237
0238
0239
023A
023B
023C
023D
023E
023F
0240

CG56

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 4 of 77)


ADDR
(hex)

...

DESCRIPTION

Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

ALARM STATUS

0260
0261
0262
0263
0264
...
0267
0268
0269
026A
026B
026C
...
026F
0270
0271
0272
...
0275
0276
0277
0278
0279
027A
...
027D
027E
027F
0280
0281
0282
0283
0284
0285
0286
0287
0288
0289
028A
028B
028C
028D
028E

General Spare Switch Alarm


Status or
Starter Monitor Alarm/Trip
Status
General Emergency Restart
Switch Alarm Status
General Differential Switch
Alarm Status
General Speed Switch Alarm
Status
General Reset Switch Alarm
Status
Reserved
Thermal Capacity Alarm
Overload Alarm Status
Mechanical Jam Alarm Status
Undercurrent Alarm Status
Current Unbalance Alarm Status
Ground Fault Alarm Status
Reserved
Undervoltage Alarm Status
Overvoltage Alarm Status
Overfrequency Alarm Status
Underfrequency Alarm Status
Reserved
Lead Power Factor Alarm Status
Lag Power Factor Alarm Status
Positive kvar Alarm Status
Negative kvar Alarm Status
Underpower Alarm Status
Reverse Power Alarm Status
Reserved
Local RTD #1 Alarm Status
Local RTD #2 Alarm Status
Local RTD #3 Alarm Status
Local RTD #4 Alarm Status
Local RTD #5 Alarm Status
Local RTD #6 Alarm Status
Local RTD #7 Alarm Status
Local RTD #8 Alarm Status
Local RTD #9 Alarm Status
Local RTD #10 Alarm Status
Local RTD #11 Alarm Status
Local RTD #12 Alarm Status
Local RTD #1 High Alarm Status
Local RTD #2 High Alarm Status
Local RTD #3 High Alarm Status
Local RTD #4 High Alarm Status
Local RTD #5 High Alarm Status
Local RTD #6 High Alarm Status

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

F123

F123

F123

F123

F123

0
0
0
0
0
0

4
4
4
4
4
4

1
1
1
1
1
1

F123
F123
F123
F123
F123
F123

0
0
0
0
0
0

0
0
0
0

4
4
4
4

1
1
1
1

F123
F123
F123
F123

0
0
0
0

0
0
0
0
0
0

4
4
4
4
4
4

1
1
1
1
1
1

F123
F123
F123
F123
F123
F123

0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

CG57

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 5 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

028F
0290
0291
0292
0293
0294
0295
0296
0297
0298
0299
029A
029B
029C
029D
029E

Local RTD #7 High Alarm Status


Local RTD #8 High Alarm Status
Local RTD #9 High Alarm Status
Local RTD #10 High Alarm Status
Local RTD #11 High Alarm Status
Local RTD #12 High Alarm Status
Broken / Open RTD Alarm Status
Short / Low Temp Alarm Status
Reserved
Trip Counter Alarm Status
Starter Failure Alarm
Current Demand Alarm Status
kW Demand Alarm Status
kvar Demand Alarm Status
kVA Demand Alarm Status
Self Test Alarm

02C0
02C1
02C2
02C3
02C4
02C5
02C6
02C7
02C8
02C9
02CA
...

Overload Lockout Timer


Start Timer 1
Start Timer 2
Start Timer 3
Start Timer 4
Start Timer 5
Time Between Starts Timer
Restart Block Timer
Reserved
Start Inhibit Timer
Starts Per Hour Lockout Timer
Reserved

02D0
02D1
02D2
02D3
02D4
02D5
...

Access
Speed
Spare
Differential Relay
Emergency Restart
Reset
Reserved

02E0
02E1
02E2
02E3
...

Trip
Alarm
Aux.1
Aux.2
Reserved

02E6

N/A

...

Digital Input and Output Relay


Status
Reserved

02F0
02F4
...

Date (Read Only)


Time (Read Only)
Reserved

N/A
N/A

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
0
0
0
0
0
0
0

4
4
4
4
4
4
4
1

1
1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0

0
0
0
0
0
0
0

4
4
4
4
4
4
4

1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0
0

START BLOCK STATUS

0
0
0
0
0
0
0
0

9999
60
60
60
60
60
500
50000

1
1
1
1
1
1
1
1

min
min
min
min
min
min
min
s

F1
F1
F1
F1
F1
F1
F1
F1

0
0
0
0
0
0
0
0

0
0

500
60

1
1

min
min

F1
F1

0
0

1
1
1
1
1
1

F131
F131
F131
F131
F131
F131

0
0
0
0
0
0

1
1
1
1

N/A
N/A
N/A
N/A

F150
F150
F150
F150

0
0
0
0

N/A

N/A

F192

N/A
N/A

N/A
N/A

F18
F19

N/A
N/A

DIGITAL INPUT STATUS

0
0
0
0
0
0

1
1
1
1
1
1

OUTPUT RELAY STATUS

0
0
0
0

1
1
1
1

369 DIGITAL INPUT AND OUTPUT RELAY STATUS

N/A

REAL TIME CLOCK

CG58

N/A
N/A

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 6 of 77)


ADDR
(hex)

02F8

DESCRIPTION

MIN.

STEP
VALUE
FIELDBUS SPECIFICATION STATUS

02FA
...

Explicit Connection Status


0
Input/Output Polled Connection 0
Status
Network Status
0
Reserved

0300
0302
0304
0306
0308
0309
030A
030B
...

Phase A Current
Phase B Current
Phase C Current
Average Phase Current
Motor Load
Current Unbalance
Unbalaced Biased Motor Load
Ground Current
Reserved

031C

Overall Hottest Stator RTD


Owner
Overall Hottest Stator RTD
Number
Overall Hottest Stator RTD
Temperature

02F9

MAX.

UNITS

FORMAT
CODE

FACTORY
DEFAULT

N/A

F168

N/A

F168

N/A

F167

1
1
1
1
1
1
1
1
-

A
A
A
A
FLA
%
FLA
A
-

F1
F1
F1
F1
F3
F1
F3
F23
-

0
0
0
0
0
0
0
0
-

CURRENT METERING

0
0
0
0
0
0
0
0
-

65535
65535
65535
65535
2000
100
9999
65535
-

OVERALL STATOR RTD

031D
031E

N/A

F165

12

N/A

F1

40

200

F4

TEMPERATURE

0321
0322
0323
0324
0325
0326
0327
0328
0329
032A
032B
032C
...

Local Hottest Stator RTD


Number
Local Hottest Stator RTD
Temperature
Local RTD #1 Temperature
Local RTD #2 Temperature
Local RTD #3 Temperature
Local RTD #4 Temperature
Local RTD #5 Temperature
Local RTD #6 Temperature
Local RTD #7 Temperature
Local RTD #8 Temperature
Local RTD #9 Temperature
Local RTD #10 Temperature
Local RTD #11 Temperature
Local RTD #12 Temperature
Reserved

0360
0361
0362
0363
0364
0365
0366
0367
0368

Vab
Vbc
Vca
Average Line Voltage
Van
Vbn
Vcn
Average Phase Voltage
System Frequency

031F
0320

12

F1

40

200

F4

40

40
40
40
40
40
40
40
40
40
40
40
40

200
200
200
200
200
200
200
200
200
200
200
200

1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
C
C
C
C
C
C
C
C
C

F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4

40
40
40
40
40
40
40
40
40
40
40
40

1
1
1
1
1
1
1
1
1

V
V
V
V
V
V
V
V
Hz

F1
F1
F1
F1
F1
F1
F1
F1
F3

0
0
0
0
0
0
0
0
0

VOLTAGE METERING

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0
0
0
0
0
0
0
0

65535
65535
65535
65535
65535
65535
65535
65535
12000

CG59

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 7 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

BACKSPIN METERING

12000 1

Hz

F3

036A
036B
...

Backspin Frequency (a value of


0 represents low signal)
Backspin Detection State
Backspin Prediction Timer
Reserved

0
0

6
1
50000 1

F27
F1

0
0

0370
0371
0373
0374
0376
0377
0379
037B
037D
037F
0381
...

Power Factor
Real Power
Real Power
Reactive Power
Apparent Power
Positive MegaWatthours
Positive Megavarhours
Negative Megavarhours
Positive KiloWatthours
Positive Kilovarhours
Negative Kilovarhours
Reserved

99
32000
0
32000
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
1
1
1

kW
hp
kvar
kVA
MWh
Mvarh
Mvarh
kWh
kvarh
kvarh

F21
F4
F1
F4
F1
F1
F1
F1
F1
F1
F1

0
0
0
0
0
0
0
0
0
0
0

0390
0392
0394
0396
0397
0399
039B
039D
...

Current Demand
Real Power Demand
Reactive Power Demand
Apparent Power Demand
Peak Current Demand
Peak Real Power Demand
Peak Reactive Power Demand
Peak Apparent Power Demand
Reserved

1
1
1
1
1
1
1
1

A
kW
kvar
kVA
A
kW
kvar
kVA

F1
F1
F1
F1
F1
F1
F1
F1

0
0
0
0
0
0
0
0

03C0
03C1
03C2

03CE

Learned Acceleration Time


Learned Starting Current
Learned Starting Capacity
Learned Running Cool Time
Constant
Learned Stopped Cool Time
Constant
Last Starting Current
Last Starting Capacity
Last Acceleration Time
Average Motor Load Learned
Learned Unbalance k factor
Average Run Time After Start
(Days)
Average Run Time After Start
(Minutes)
Date of Record
Number of Enhanced Learned
Records

03E0
03E1

Local RTD # 1 Max. Temperature -40


Local RTD # 2 Max. Temperature -40

0369

POWER METERING

100
32000
42912
32000
65000
65535
65535
65535
999
999
999

DEMAND METERING

0
0
0
0
0
0
0
0

65535
32000
32000
65000
65535
32000
32000
65000

MOTOR DATA (0 = OFF)

03C3
03C4
03C5
03C6
03C7
03C8
03C9
03CA
03CB
03CC

1
0
0

2500 1
65535 1
100
1

s
A
%

F2
F1
F1

0
0
0

500

min

F1

500

min

F1

0
0
1
0
0

65535
100
2500
2000
29

1
1
1
1
1

A
%
s
x FLA
-

F1
F1
F2
F3
F1

0
0
0
0
0

65535 1

days

F1

1440

minutes F1

F19

65535 1

F1

F4
F4

40
40

LOCAL RTD MAXIMUMS

CG60

200
200

1
1

C
C

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 8 of 77)


ADDR
(hex)

03E2
03E3
03E4
03E5
03E6
03E7
03E8

DESCRIPTION

MIN.

...

Local RTD # 3 Max. Temperature


Local RTD # 4 Max. Temperature
Local RTD # 5 Max. Temperature
Local RTD # 6 Max. Temperature
Local RTD # 7 Max. Temperature
Local RTD # 8 Max. Temperature
Local RTD # 9 Max. Temperature
Local RTD # 10 Max.
Temperature
Local RTD # 11 Max.
Temperature
Local RTD # 12 Max.
Temperature
Reserved

0430
...
0433
...
0436
0437
0438
0439
043A
043B
043C
043D
...
043F
0440
0441
0442
0443
...
0446
0447
0448
0449
044A
044B
...
044E
044F
0450
0451

Total Number of Trips


Reserved
Switch Trips
Reserved
Overload Trips
Short Circuit Trips
Mechanical Jam Trips
Undercurrent Trips
Current Unbalance Trips
Single Phase Trips
Ground Fault Trips
Acceleration Trips
Reserved
Undervoltage Trips
Overvoltage Trips
Phase Reversal Trips
Under Frequency Trips
Over Frequency Trips
Reserved
Lead Power Factor Trips
Lag Power Factor Trips
Positive Reactive Power Trips
Negative Reactive Power Trips
Underpower Trips
Reverse Power Trips
Reserved
Stator RTD Trips
Bearing RTD Trips
Other RTD Trips
Ambient RTD Trips

0452

UVR Undervoltage Trip Counters 0

...
0454
...
0457

Reserved
Incomplete Sequence Trips
Reserved
Trip Counters Last Cleared

03E9
03EA
03EB

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

-40
-40
-40
-40
-40
-40
-40

200
200
200
200
200
200
200

1
1
1
1
1
1
1

C
C
C
C
C
C
C

F4
F4
F4
F4
F4
F4
F4

40
40
40
40
40
40
40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

TRIP COUNTERS

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

50000 1

F1

50000 1

F1

0
0
0
0
0

50000
50000
50000
50000
50000

1
1
1
1
1

F1
F1
F1
F1
F1

0
0
0
0
0

0
0

50000 1
50000 1

F1
F1

0
0

0
0
0
0
0

50000
50000
50000
50000
50000

1
1
1
1
1

F1
F1
F1
F1
F1

0
0
0
0
0

0
0
0
0
0
0

50000
50000
50000
50000
50000
50000

1
1
1
1
1
1

F1
F1
F1
F1
F1
F1

0
0
0
0
0
0

0
0
0
0

50000
50000
50000
50000

1
1
1
1

F1
F1
F1
F1

50000 1

F1

0
0
0
0
Read
Only

50000 1

F1

N/A

N/A

N/A

F18

N/A

N/A

CG61

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 9 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

...

Reserved

0470
0471
0472
0473
...
04A0
...

Number of Motor Starts


0
Number of Emergency Restarts 0
Reserved
Digital Counter
0
Reserved
Motor Running Hours
0
Reserved

0500
0501
0502
0503
0504
0505
...

Va Angle
Vb Angle
Vc Angle
Ia Angle
Ib Angle
Ic Angle
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

MOTOR STATISTICS

50000
50000
65535

1
1
1

65535 1

F1
F1
F1

0
0
0

hr.

F1

degrees
degrees
degrees
degrees
degrees
degrees

F1
F1
F1
F1
F1
F1

0
0
0
0
0
0

PHASORS

0
0
0
0
0
0

359
359
359
359
359
359

1
1
1
1
1
1

REMOTE RTD ACTUAL VALUES (ADDRESSES 0600 TO 1FFF)


RRTD 1 TEMPERATURES

0600
0601
0602
0603
0604
0605
0606
0607
0608
0609
060A
060B
060C
060D
...

RRTD 1 - Hottest Stator Number


RRTD 1 - Hottest Stator
Temperature
RRTD 1 - RTD #1 Temperature
RRTD 1 - RTD #2 Temperature
RRTD 1 - RTD #3 Temperature
RRTD 1 - RTD #4 Temperature
RRTD 1 - RTD #5 Temperature
RRTD 1 - RTD #6 Temperature
RRTD 1 - RTD #7 Temperature
RRTD 1 - RTD #8 Temperature
RRTD 1 - RTD #9 Temperature
RRTD 1 - RTD #10 Temperature
RRTD 1 - RTD #11 Temperature
RRTD 1 - RTD #12 Temperature
Reserved

12

F1

-40

200

F4

40

-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40

200
200
200
200
200
200
200
200
200
200
200
200

1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
C
C
C
C
C
C
C
C
C

F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4

40
40
40
40
40
40
40
40
40
40
40
40

RRTD 2 TEMPERATURES

0610
0611
0612
0613
0614
0615
0616
0617
0618
0619
061A
061B
061C

CG62

RRTD 2 - RTD - Hottest Stator


Number
RRTD 2 - RTD - Hottest Stator
Temperature
RRTD 2 - RTD #1Temperature
RRTD 2 - RTD #2 Temperature
RRTD 2 - RTD #3 Temperature
RRTD 2 - RTD #4 Temperature
RRTD 2 - RTD #5 Temperature
RRTD 2 - RTD #6 Temperature
RRTD 2 - RTD #7 Temperature
RRTD 2 - RTD #8 Temperature
RRTD 2 - RTD #9 Temperature
RRTD 2 - RTD #10 Temperature
RRTD 2 - RTD #11 Temperature

12

F1

-40

200

F4

40

-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40

200
200
200
200
200
200
200
200
200
200
200

1
1
1
1
1
1
1
1
1
1
1

C
C
C
C
C
C
C
C
C
C
C

F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4

40
40
40
40
40
40
40
40
40
40
40

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 10 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

061D
...

RRTD 2 - RTD #12 Temperature


Reserved

0620

RRTD 3 - RTD - Hottest Stator


Number
RRTD 3 - RTD - Hottest Stator
Temperature
RRTD 3 - RTD #1 Temperature
RRTD 3 - RTD #2 Temperature
RRTD 3 - RTD #3 Temperature
RRTD 3 - RTD #4 Temperature
RRTD 3 - RTD #5 Temperature
RRTD 3 - RTD #6 Temperature
RRTD 3 - RTD #7 Temperature
RRTD 3 - RTD #8 Temperature
RRTD 3 - RTD #9 Temperature
RRTD 3 - RTD #10 Temperature
RRTD 3 - RTD #11 Temperature
RRTD 3 - RTD #12 Temperature
Reserved

-40

MAX.

200

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F4

40

RRTD 3 TEMPERATURES

0621
0622
0623
0624
0625
0626
0627
0628
0629
062A
062B
062C
062D
...

12

F1

-40

200

F4

40

-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40

200
200
200
200
200
200
200
200
200
200
200
200

1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
C
C
C
C
C
C
C
C
C

F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4

40
40
40
40
40
40
40
40
40
40
40
40

RRTD 4 TEMPERATURES

0630
0631
0632
0633
0634
0635
0636
0637
0638
0639
063A
063B
063C
063D

RRTD 4 - RTD- Hottest Stator


Number
RRTD 4 - RTD- Hottest Stator
Temperature
RRTD 4 - RTD#1 Temperature
RRTD 4 - RTD#2 Temperature
RRTD 4 - RTD#3 Temperature
RRTD 4 - RTD#4 Temperature
RRTD 4 - RTD#5 Temperature
RRTD 4 - RTD#6 Temperature
RRTD 4 - RTD#7 Temperature
RRTD 4 - RTD#8 Temperature
RRTD 4 - RTD#9 Temperature
RRTD 4 - RTD#10 Temperature
RRTD 4 - RTD#11 Temperature
RRTD 4 - RTD#12 Temperature

12

F1

-40

200

F4

40

-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40
-40

200
200
200
200
200
200
200
200
200
200
200
200

1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
C
C
C
C
C
C
C
C
C

F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4
F4

40
40
40
40
40
40
40
40
40
40
40
40

LOSS OF RRTD COMMUNICATIONS

063E
063F

Lost RRTD Communications


alarm
Actively Communicating RRTDs

F123

15

F183

1
1
1
1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0
0
0
0
0

RRTD 1 ALARM STATUS

0650
0651
0652
0653
0654
0655
0656
0657
0658
0659

RRTD 1 - RTD #1 Alarm Status


RRTD 1 - RTD #2 Alarm Status
RRTD 1 - RTD #3 Alarm Status
RRTD 1 - RTD #4 Alarm Status
RRTD 1 - RTD #5 Alarm Status
RRTD 1 - RTD #6 Alarm Status
RRTD 1 - RTD #7 Alarm Status
RRTD 1 - RTD #8 Alarm Status
RRTD 1 - RTD #9 Alarm Status
RRTD 1 - RTD #10 Alarm Status

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0
0
0
0
0
0
0
0
0

4
4
4
4
4
4
4
4
4
4

CG63

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 11 of 77)


ADDR
(hex)

065A
065B
065C
065D
065E
065F
0660
0661
0662
0663
0664
0665
0666
0667
0668
0669
066A
066B
066C
066D
066E
066F

DESCRIPTION

RRTD 1 - RTD #11 Alarm Status


RRTD 1 - RTD #12 Alarm Status
RRTD 1 - RTD #1 High Alarm
Status
RRTD 1 - RTD #2 High Alarm
Status
RRTD 1 - RTD #3 High Alarm
Status
RRTD 1 - RTD #4 High Alarm
Status
RRTD 1 - RTD #5 High Alarm
Status
RRTD 1 - RTD #6 High Alarm
Status
RRTD 1 - RTD #7 High Alarm
Status
RRTD 1 - RTD #8 High Alarm
Status
RRTD 1 - RTD #9 High Alarm
Status
RRTD 1 - RTD #10 High Alarm
Status
RRTD 1 - RTD #11 High Alarm
Status
RRTD 1 - RTD #12 High Alarm
Status
RRTD 1 - Broken / Open RTD
Alarm Status
RRTD 1 - Short / Low Temp
Alarm Status
RRTD 1 - Digital Input 6 Alarm
Status
RRTD 1 - Digital Input 2 Alarm
Status
RRTD 1 - Digital Input 5 Alarm
Status
RRTD 1 - Digital Input 4 Alarm
Status
RRTD 1 - Digital Input 1 Alarm
Status
RRTD 1 - Digital Input 3 Alarm
Status

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
0

4
4

1
1

F123
F123

0
0

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

1
1
1
1
1
1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0
0
0
0
0
0
0

RRTD 2 ALARM STATUS

0670
0671
0672
0673
0674
0675
0676
0677
0678
0679
067A
067B

CG64

RRTD 2 - RTD #1 Alarm Status


RRTD 2 - RTD #2 Alarm Status
RRTD 2 - RTD #3 Alarm Status
RRTD 2 - RTD #4 Alarm Status
RRTD 2 - RTD #5 Alarm Status
RRTD 2 - RTD #6 Alarm Status
RRTD 2 - RTD #7 Alarm Status
RRTD 2 - RTD #8 Alarm Status
RRTD 2 - RTD #9 Alarm Status
RRTD 2 - RTD #10 Alarm Status
RRTD 2 - RTD #11 Alarm Status
RRTD 2 - RTD #12 Alarm Status

0
0
0
0
0
0
0
0
0
0
0
0

4
4
4
4
4
4
4
4
4
4
4
4

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 12 of 77)


ADDR
(hex)

067C
067D
067E
067F
0680
0681
0682
0683
0684
0685
0686
0687
0688
0689
068A
068B
068C
068D
068E
068F

DESCRIPTION

RRTD 2 - RTD #1 High Alarm


Status
RRTD 2 - RTD #2 High Alarm
Status
RRTD 2 - RTD #3 High Alarm
Status
RRTD 2 - RTD #4 High Alarm
Status
RRTD 2 - RTD #5 High Alarm
Status
RRTD 2 - RTD #6 High Alarm
Status
RRTD 2 - RTD #7 High Alarm
Status
RRTD 2 - RTD #8 High Alarm
Status
RRTD 2 - RTD #9 High Alarm
Status
RRTD 2 - RTD #10 High Alarm
Status
RRTD 2 - RTD #11 High Alarm
Status
RRTD 2 - RTD #12 High Alarm
Status
RRTD 2 - Broken / Open RTD
Alarm Status
RRTD 2 - Short / Low Temp
Alarm Status
RRTD 2 - Digital Input 6 Alarm
Status
RRTD 2 - Digital Input 2 Alarm
Status
RRTD 2 - Digital Input 5 Alarm
Status
RRTD 2 - Digital Input 4 Alarm
Status
RRTD 2 - Digital Input 1 Alarm
Status
RRTD 2 - Digital Input 3 Alarm
Status

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

RRTD 3 ALARM STATUS

0690
0691
0692
0693
0694
0695
0696
0697
0698
0699
069A
069B
069C

RRTD 3 - RTD #1 Alarm Status


RRTD 3 - RTD #2 Alarm Status
RRTD 3 - RTD #3 Alarm Status
RRTD 3 - RTD #4 Alarm Status
RRTD 3 - RTD #5 Alarm Status
RRTD 3 - RTD #6 Alarm Status
RRTD 3 - RTD #7 Alarm Status
RRTD 3 - RTD #8 Alarm Status
RRTD 3 - RTD #9 Alarm Status
RRTD 3 - RTD #10 Alarm Status
RRTD 3 - RTD #11 Alarm Status
RRTD 3 - RTD #12 Alarm Status
RRTD 3 - RTD #1 High Alarm
Status

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0
0
0
0
0
0
0
0
0
0
0

4
4
4
4
4
4
4
4
4
4
4
4

1
1
1
1
1
1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0
0
0
0
0
0
0

F123

CG65

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 13 of 77)


ADDR
(hex)

069D
069E
069F
06A0
06A1
06A2
06A3
06A4
06A5
06A6
06A7
06A8
06A9
06AA
06AB
06AC
06AD
06AE
06AF

DESCRIPTION

RRTD 3 - RTD #2 High Alarm


Status
RRTD 3 - RTD #3 High Alarm
Status
RRTD 3 - RTD #4 High Alarm
Status
RRTD 3 - RTD #5 High Alarm
Status
RRTD 3 - RTD #6 High Alarm
Status
RRTD 3 - RTD #7 High Alarm
Status
RRTD 3 - RTD #8 High Alarm
Status
RRTD 3 - RTD #9 High Alarm
Status
RRTD 3 - RTD #10 High Alarm
Status
RRTD 3 - RTD #11 High Alarm
Status
RRTD 3 - RTD #12 High Alarm
Status
RRTD 3 - Broken / Open RTD
Alarm Status
RRTD 3 - Short / Low Temp
Alarm Status
RRTD 3 - Digital Input 6 Alarm
Status
RRTD 3 - Digital Input 2 Alarm
Status
RRTD 3 - Digital Input 5 Alarm
Status
RRTD 3 - Digital Input 4 Alarm
Status
RRTD 3 - Digital Input 1 Alarm
Status
RRTD 3 - Digital Input 3 Alarm
Status

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

RRTD 4 ALARM STATUS

06B0
06B1
06B2
06B3
06B4
06B5
06B6
06B7
06B8
06B9
06BA
06BB
06BC
06BD

CG66

RRTD 4 - RTD #1 Alarm Status


RRTD 4 - RTD #2 Alarm Status
RRTD 4 - RTD #3 Alarm Status
RRTD 4 - RTD #4 Alarm Status
RRTD 4 - RTD #5 Alarm Status
RRTD 4 - RTD #6 Alarm Status
RRTD 4 - RTD #7 Alarm Status
RRTD 4 - RTD #8 Alarm Status
RRTD 4 - RTD #9 Alarm Status
RRTD 4 - RTD #10 Alarm Status
RRTD 4 - RTD #11 Alarm Status
RRTD 4 - RTD #12 Alarm Status
RRTD 4 - RTD #1 High Alarm
Status
RRTD 4 - RTD #2 High Alarm
Status

0
0
0
0
0
0
0
0
0
0
0
0

4
4
4
4
4
4
4
4
4
4
4
4

1
1
1
1
1
1
1
1
1
1
1
1

F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123
F123

0
0
0
0
0
0
0
0
0
0
0
0

F123

F123

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 14 of 77)


ADDR
(hex)

06BE
06BF
06C0
06C1
06C2
06C3
06C4
06C5
06C6
06C7
06C8
06C9
06CA
06CB
06CC
06CD
06CE
06CF

DESCRIPTION

MIN.

RRTD 4 - RTD #3 High Alarm


Status
RRTD 4 - RTD #4 High Alarm
Status
RRTD 4 - RTD #5 High Alarm
Status
RRTD 4 - RTD #6 High Alarm
Status
RRTD 4 - RTD #7 High Alarm
Status
RRTD 4 - RTD #8 High Alarm
Status
RRTD 4 - RTD #9 High Alarm
Status
RRTD 4 - RTD #10 High Alarm
Status
RRTD 4 - RTD #11 High Alarm
Status
RRTD 4 - RTD #12 High Alarm
Status
RRTD 4 - Broken / Open RTD
Alarm Status
RRTD 4 - Short / Low Temp
Alarm Status
RRTD 4 - Digital Input 6 Alarm
Status
RRTD 4 - Digital Input 2 Alarm
Status
RRTD 4 - Digital Input 5 Alarm
Status
RRTD 4 - Digital Input 4 Alarm
Status
RRTD 4 - Digital Input 1 Alarm
Status
RRTD 4 - Digital Input 3 Alarm
Status

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

F123

RRTD 1 MAXIMUM TEMPERATURES

0700
0701
0702
0703
0704
0705
0706
0707
0708
0709

RRTD 1 - RTD # 1 Max.


Temperature
RRTD 1 - RTD # 2 Max.
Temperature
RRTD 1 - RTD # 3 Max.
Temperature
RRTD 1 - RTD # 4 Max.
Temperature
RRTD 1 - RTD # 5 Max.
Temperature
RRTD 1 - RTD # 6 Max.
Temperature
RRTD 1 - RTD # 7 Max.
Temperature
RRTD 1 - RTD # 8 Max.
Temperature
RRTD 1 - RTD # 9 Max.
Temperature
RRTD 1 - RTD # 10 Max.
Temperature

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

CG67

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 15 of 77)


ADDR
(hex)

070A
070B
...

DESCRIPTION

RRTD 1 - RTD # 11 Max.


Temperature
RRTD 1 - RTD # 12 Max.
Temperature
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

-40

200

F4

40

-40

200

F4

40

RRTD 2 MAXIMUM TEMPERATURES

0710
0711
0712
0713
0714
0715
0716
0717
0718
0719
071A
071B
...

RRTD 2 - RTD # 1 Max.


Temperature
RRTD 2 - RTD # 2 Max.
Temperature
RRTD 2 - RTD # 3 Max.
Temperature
RRTD 2 - RTD # 4 Max.
Temperature
RRTD 2 - RTD # 5 Max.
Temperature
RRTD 2 - RTD # 6 Max.
Temperature
RRTD 2 - RTD # 7 Max.
Temperature
RRTD 2 - RTD # 8 Max.
Temperature
RRTD 2 - RTD # 9 Max.
Temperature
RRTD 2 - RTD # 10 Max.
Temperature
RRTD 2 - RTD # 11 Max.
Temperature
RRTD 2 - RTD # 12 Max.
Temperature
Reserved

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

RRTD 3 MAXIMUM TEMPERATURES

0720
0721
0722
0723
0724
0725
0726
0727
0728
0729
072A
072B
...

CG68

RRTD 3 - RTD # 1 Max.


Temperature
RRTD 3 - RTD # 2 Max.
Temperature
RRTD 3 - RTD # 3 Max.
Temperature
RRTD 3 - RTD # 4 Max.
Temperature
RRTD 3 - RTD # 5 Max.
Temperature
RRTD 3 - RTD # 6 Max.
Temperature
RRTD 3 - RTD # 7 Max.
Temperature
RRTD 3 - RTD # 8 Max.
Temperature
RRTD 3 - RTD # 9 Max.
Temperature
RRTD 3 - RTD # 10 Max.
Temperature
RRTD 3 - RTD # 11 Max.
Temperature
RRTD 3 - RTD # 12 Max.
Temperature
Reserved

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 16 of 77)


ADDR
(hex)

DESCRIPTION

...

RRTD 4 - RTD # 1 Max.


Temperature
RRTD 4 - RTD # 2 Max.
Temperature
RRTD 4 - RTD # 3 Max.
Temperature
RRTD 4 - RTD # 4 Max.
Temperature
RRTD 4 - RTD # 5 Max.
Temperature
RRTD 4 - RTD # 6 Max.
Temperature
RRTD 4 - RTD # 7 Max.
Temperature
RRTD 4 - RTD # 8 Max.
Temperature
RRTD 4 - RTD # 9 Max.
Temperature
RRTD 4 - RTD # 10 Max.
Temperature
RRTD 4 - RTD # 11 Max.
Temperature
RRTD 4 - RTD # 12 Max.
Temperature
Reserved

0800
0801
0802
0803
0804
...

RRTD 1 - Stator RTD Trips


RRTD 1 - Bearing RTD Trips
RRTD 1 - Other RTD Trips
RRTD 1 - Ambient RTD Trips
RRTD 1 - Digital Input Trips
Reserved

0810
0811
0812
0813
0814
...

RRTD 2 - Stator RTD Trips


RRTD 2 - Bearing RTD Trips
RRTD 2 - Other RTD Trips
RRTD 2 - Ambient RTD Trips
RRTD 2 - Digital Input Trips
Reserved

0820
0821
0822
0823
0824
...

RRTD 3 - Stator RTD Trips


RRTD 3 - Bearing RTD Trips
RRTD 3 - Other RTD Trips
RRTD 3 - Ambient RTD Trips
RRTD 3 - Digital Input Trips
Reserved

0830
0831
0832
0833
0834
...

RRTD 4 - Stator RTD Trips


RRTD 4 - Bearing RTD Trips
RRTD 4 - Other RTD Trips
RRTD 4 - Ambient RTD Trips
RRTD 4 - Digital Input Trips
Reserved

0730
0731
0732
0733
0734
0735
0736
0737
0738
0739
073A
073B

MIN.

MAX.

STEP
VALUE
RRTD 4 MAXIMUM TEMPERATURES

UNITS

FORMAT
CODE

FACTORY
DEFAULT

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

-40

200

F4

40

1
1
1
1
1

F1
F1
F1
F1
F1

0
0
0
0
0

1
1
1
1
1

F1
F1
F1
F1
F1

0
0
0
0
0

1
1
1
1
1

F1
F1
F1
F1
F1

0
0
0
0
0

1
1
1
1
1

F1
F1
F1
F1
F1

0
0
0
0
0

RRTD 1 TRIP COUNTER

0
0
0
0
0

50000
50000
50000
50000
50000

RRTD 2 TRIP COUNTER

0
0
0
0
0

50000
50000
50000
50000
50000

RRTD 3 TRIP COUNTER

0
0
0
0
0

50000
50000
50000
50000
50000

RRTD 4 TRIP COUNTER

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0
0
0
0

50000
50000
50000
50000
50000

CG69

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 17 of 77)


ADDR
(hex)

DESCRIPTION

0840
0841
0842
0843
0844
0845
...

Digital Input 3
Digital Input 4
Digital Input 6
Digital Input 5
Digital Input 2
Digital Input 1
Reserved

0850
0851
0852
0853
0854
0855
...

Digital Input 3
Digital Input 4
Digital Input 6
Digital Input 5
Digital Input 2
Digital Input 1
Reserved

0860
0861
0862
0863
0864
0865
...

Digital Input 3
Digital Input 4
Digital Input 6
Digital Input 5
Digital Input 2
Digital Input 1
Reserved

0870
0871
0872
0873
0874
0875
...

Digital Input 3
Digital Input 4
Digital Input 6
Digital Input 5
Digital Input 2
Digital Input 1
Reserved

0880
0881
0882
0883

RRTD 1 - Trip
RRTD 1 - Alarm
RRTD 1 - Aux. 1
RRTD 1 - Aux. 2

0884
...

RRTD1 Digital Input & Output


Relay Status
Reserved

0890
0891
0892
0893

RRTD 2 - Trip
RRTD 2 - Alarm
RRTD 2 - Aux. 1
RRTD 2 - Aux. 2

0894
...

RRTD2 Digital Input & Output


Relay Status
Reserved

08A0

RRTD 3 - Trip

MIN.

STEP
VALUE
RRTD 1 DIGITAL INPUT STATUS

0
0
0
0
0
0

MAX.

1
1
1
1
1
1

1
1
1
1
1
1

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F131
F131
F131
F131
F131
F131

0
0
0
0
0
0

F131
F131
F131
F131
F131
F131

0
0
0
0
0
0

F131
F131
F131
F131
F131
F131

0
0
0
0
0
0

F131
F131
F131
F131
F131
F131

0
0
0
0
0
0

N/A
N/A
N/A
N/A

F150
F150
F150
F150

2
2
2
2

N/A

F193

N/A
N/A
N/A
N/A

F150
F150
F150
F150

2
2
2
2

N/A

F193

N/A

F150

RRTD 2 DIGITAL INPUT STATUS

0
0
0
0
0
0

1
1
1
1
1
1

1
1
1
1
1
1

RRTD 3 DIGITAL INPUT STATUS

0
0
0
0
0
0

1
1
1
1
1
1

1
1
1
1
1
1

RRTD 4 DIGITAL INPUT STATUS

0
0
0
0
0
0

1
1
1
1
1
1

1
1
1
1
1
1

RRTD 1 OUTPUT RELAY STATUS

0
0
0
0

2
2
2
2

1
1
1
1

RRTD 1 DIGITAL INPUT AND OUTPUT RELAY STATUS

N/A

N/A

N/A

RRTD 2 OUTPUT RELAY STATUS

0
0
0
0

2
2
2
2

1
1
1
1

RRTD 2 DIGITAL INPUT AND OUTPUT RELAY STATUS

N/A

N/A

N/A

RRTD 3 OUTPUT RELAY STATUS

CG70

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 18 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

08A1
08A2
08A3

RRTD 3 - Alarm
RRTD 3 - Aux. 1
RRTD 3 - Aux. 2

0
0
0

08A4
...

RRTD3 Digital Input & Output


Relay Status
Reserved

08B0
08B1
08B2
08B3

RRTD 4 - Trip
RRTD 4 - Alarm
RRTD 4 - Aux. 1
RRTD 4 - Aux. 2

08B4

RRTD4 Digital Input & Output


Relay Status
Reserved

MAX.

2
2
2

STEP
VALUE

1
1
1

UNITS

N/A
N/A
N/A

FORMAT
CODE

FACTORY
DEFAULT

F150
F150
F150

2
2
2

N/A

F193

N/A
N/A
N/A
N/A

F150
F150
F150
F150

2
2
2
2

N/A

F193

RRTD 3 DIGITAL INPUT AND OUTPUT RELAY STATUS

N/A

N/A

N/A

RRTD 4 OUTPUT RELAY STATUS

0
0
0
0

2
2
2
2

1
1
1
1

RRTD 4 DIGITAL INPUT AND OUTPUT RELAY STATUS

...

N/A

N/A

N/A

COMMUNICATIONS MODULE

08C0
08C1
...

Ethernet Module Status


Fieldbus Module Software
Revision
Reserved

65535 1

N/A

F164

F16

N/A

F180

PROTECTION FUNCTION BLOCKING

08D0
...

Protection Functions Currently


Blocked
Reserved

256

SETPOINTS (ADDRESSES 1000 TO 1FFF)


DISPLAY PREFERENCES

1000
1001
1002
1003
1004
1005
...

Default Message Cycle Time


Default Message Timeout
Reserved
Flash Message
Temperature Display Units
Energy Unit Display
Reserved

1006
1007

Motor Running Events


Motor Stopped Events

1008
...

Trigger Position
Reserved

100F
1010
1011
1012
1013
1014
1015
1016
1017
1018
1019

Reset Fieldbus Comms Interface


Slave Address
Computer RS232 Baud Rate
Computer RS232 Parity
Channel 1 Parity
Channel 1 Baud Rate
Channel 2 Parity
Channel 2 Baud Rate
Channel 3 Parity
Channel 3 Baud Rate
Channel 3 Connection

5
10

100
900

1
1

s
s

F1
F1

20
300

1
0
0

10
1
1

1
1
1

s
-

F1
F100
F166

2
0
0

1
1

F103
F103

0
0

F1

20

1
1
1
1
1
1
1
1
1
1
1

F103
F1
F101
F102
F102
F101
F102
F101
F102
F101
F151

0
254
4
0
0
4
0
4
0
4
0

EVENT RECORDS

0
0

1
1

WAVEFORM CAPTURE

100

369 COMMUNICATIONS

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
1
0
0
0
0
0
0
0
0
0

1
254
4
2
2
4
2
4
2
4
1

CG71

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 19 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

101A
101B
101C
101D
101E
101F
1020
1021
1022
1023
1024
1025
1026
1027
1028
1029
...

Channel 3 Application
Profibus Slave Address
IP Address Octet 1
IP Address Octet 2
IP Address Octet 3
IP Address Octet 4
Subnet Mask Octet 1
Subnet Mask Octet 2
Subnet Mask Octet 3
Subnet Mask Octet 4
Gateway Address Octet 1
Gateway Address Octet 2
Gateway Address Octet 3
Gateway Address Octet 4
DeviceNet MAC ID
DeviceNet Baud Rate
Reserved

0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1030
1034
...

Date (2 words)
Time (2 words)
Reserved

valid
valid

1041
1042

Default to Current Metering


Default to Motor Load
Default to Delta Voltage
Metering
Default to Power Factor
Default to Positive Watthours
Default to Real Power
Default to Reactive Power
Default to Hottest Stator RTD
Default to Text Message 1
Default to Text Message 2
Default to Text Message 3
Default to Text Message 4
Default to Text Message 5
Default to Hottest Stator RTD
Temperature
Default to Unbalace Biased
Motor Load
Reserved

MAX.

1
126
255
255
255
255
255
255
255
255
255
255
255
255
63
2

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

F149
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F170

0
125
127
0
0
1
255
255
255
0
127
0
0
1
63
0

N/A
N/A

F18
F19

REAL TIME CLOCK

date
time

DEFAULT MESSAGES

1043
1044
1045
1046
1047
1048
1049
104A
104B
104C
104D
104E
104F
...

0
0

1
1

1
1

F103
F103

0
0

F103

0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1

F103
F103
F103
F103
F103
F103
F103
F103
F103
F103

0
0
0
0
0
0
0
0
0
0

F103

F103

MESSAGE SCRATCHPAD

1060

1073
1074

1087

CG72

1st & 2nd Character of 1st


Scratchpad Message

39th & 40th Character of 1st


Scratchpad Message
1st & 2nd Character of 2nd
Scratchpad Message

39th & 40th Character of 2nd


Scratchpad Message

32

127

F1

32

127

F1

""

32

127

F1

32

127

F1

""

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 20 of 77)


ADDR
(hex)

1088

109B
109C

10AF
10B0

10C3
...

DESCRIPTION

1st & 2nd Character of 3rd


Scratchpad Message

39th & 40th Character of 3rd


Scratchpad Message
1st & 2nd Character of 4th
Scratchpad Message

39th & 40th Character of 4th


Scratchpad Message
1st & 2nd Character of 5th
Scratchpad Message

39th & 40th Character of 5th


Scratchpad Message
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

32

127

F1

32

127

F1

""

32

127

F1

32

127

F1

""

32

127

F1

32

127

F1

""

1
1
1
1
1
1
1
1
1
1

MWh
Mvarh
Mvarh
-

F103
F103
F103
F1
F103
F1
F103
F1
F1
F1

0
0
0
0
0
0
0
0
0
0

CLEAR PRESET DATA

1130
1131
1132
1133
1134
1135
1136
1137
1138
1139
113A
113B
113C
...
1140
1141
1142
1143
1144
1145
1146
1147
...

Clear Last Trip Data


Clear Peak Demand Data
Clear RTD Maximums
Preset Positive MWh
Clear Trip Counters
Preset Digital Counter
Clear Event Records
Preset Positive Mvarh
Preset Negative Mvarh
Preset Number Of Motor Starts
Preset Number Of Emergency
Restarts
Preset Motor Running Hours
Preset Autorestart Start
Attempts
Reserved
Clear Motor Data
Reserved
Clear All Data
RRTD 1 - Preset Digital Counter
RRTD 2 - Preset Digital Counter
RRTD 3 - Preset Digital Counter
RRTD 4 - Preset Digital Counter
Clear Energy Data
Reserved

0
0
0
0
0
0
0
0
0
0

1
1
1
65535
1
65535
1
65535
65535
50000

50000 1

F1

65535 1

F1

50000 1

F1

0
0
0
0
0
0
0

1
1
65535
65535
65535
65535
1

1
1
1
1
1
1
1

F103
F103
F1
F1
F1
F1
F103

0
0
0
0
0
0
0

CT/VT SETUP

1180
1181
1182
1183
...
1190
1191
1192

Phase CT Primary
Motor Full Load Amps
Ground CT Type
Ground CT Primary
Reserved
Enable Two Speed Motor
Protection
Speed 2 Phase CT Primary
Speed 2 Motor Full Load Amps

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

1
1
0
1

5000
5000
3
5000

1
1
1
1

A
A
A

F1
F1
F104
F1

500
10
2
100

N/A

F103

1
1

5000
5000

1
1

A
A

F1
F1

5000
10

CG73

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 21 of 77)


ADDR
(hex)

...

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

...

Reserved
Voltage Transformer Connection
Type
Voltage Transformer Ratio
Motor Rated Voltage
Reserved
Nominal Frequency
System Phase Sequence
Speed 2 System Phase
Sequence
Reserved

11C8
11C9
...

Serial Communication Control


Assign Start Control Relays
Reserved

0
0

11CF
11D0
11D1
11D2

10
0
0
0

100
1
7
2

5
1
1
1

s
-

F2
F103
F113
F108

10
0
4
0

F111

11D4
11D5

Start Control Relay Timer


Reduced Voltage Starting
Assign Start Control Relays
Transition On
Incomplete Sequence Trip
Relays
Reduced Voltage Start Level
Reduced Voltage Start Timer

25
1

300
500

1
1

% FLA
s

F1
F1

100
200

11D6
11D7
11D8
11D9
11DA
11DB
11DC
11DD
11DE
11DF
11E0
...

Autorestart
Total Restarts
Restart Delay
Progressive Delay
Hold Delay
Bus Valid
Bus Valid Level
Reserved
Autorestart Attempt Events
Autorestart Success Events
Autorestart Aborted Events
Reserved

0
0
0
0
0
0
15
0
0
0

1
1
1
1
1
1
1
1
1
1

starts
sec.
sec.
sec.
%VT
-

F103
F1
F1
F1
F1
F103
F1
F103
F103
F103

0
1
60
0
0
0
100
0
0
0

11F0
11F1
11F2
11F3
11F4

11F6

Enable UVR
UVR Pickup Level
UVR Assign Trip Relays
UVR Trip Delay
UVR Restoration Level
Immediate Restart Power Loss
Time
Delay1 Restart Power Loss Time

11F7
11F8
11F9
11FA

11A0
11A1
11A2
...
11C0
11C1
11C2

F106

100
100

24000 1
20000 1

F3
F1

35
4160

0
0

2
1

1
1

F107
F124

0
0

F124

1
1

F103
F113

0
2

SERIAL COMM CONTROL

1
7

REDUCED VOLTAGE

11D3

AUTORESTART

1
65000
20000
20000
20000
1
100
1
1
1

UNDERVOLTAGE AUTORESTART

11F5

CG74

0
50
0
0
50

1
100
7
2550
100

1
1
1
1
1

x RATED
x 0.1s
x RATED

F30
F3
F111
F2
F3

0 (Off)
65
0
0
90

500

100

ms

F1

0 (Off)

100

x 0.1s

0 (Off)

Delay2 Restart Power Loss Time 0

3601

Delay1 Restart Time Delay


Delay2 Restart Time Delay
UVR Setup Time

12000 2
12000 2
12000 1

F2
F1 (3601=
Unlimited
)
F2
F2
F2

0
0
0

x 0.1s
x 0.1s
x 0.1s

0 (Off)
20
100
100

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 22 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

DIGITAL COUNTER

12E6
12F2
12F8
12F9
12FA
12FB
12FD
12FE

First Character of Counter Name


First Character of Counter Unit
Name
Counter Type
Digital Counter Alarm
Assign Alarm Relays
Counter Alarm Level
Reserved
Record Alarms as Events

32

127

F1

32

127

F1

0
0
0
0
0

1
2
6
65535
1

1
1
1
1
1

F114
F115
F113
F1
F103

0
0
0
100
0

EMERGENCY

1330
1340
1341
1342
1343
1344
1345
1346
1347
1348
1349
...

1st & 2nd Character of


Emergency Switch Name
General Emergency Switch Type
General Emergency Switch Block
Input From Start
General Emergency Switch
Alarm
General Emergency Switch
Alarm Relays
General Emergency Switch
Alarm Delay
General Emergency Switch
Alarm Events
General Emergency Switch Trip
General Emergency Switch Trip
Relays
General Emergency Switch Trip
Delay
Emergency Switch Assignable
Function
Reserved

32

127

F22

F116

5000

F1

F115

F113

50000 1

100ms

F2

50

F103

F115

F111

50000 1

100ms

F2

50

F110

DIFFERENTIAL

1370
1380
1381
1382
1383
1384
1385
1386
1387
1388
1389
138A
...

1st & 2nd Character of


Differential Switch Name
General Differential Switch Type
General Differential Switch Block
Input From Start
General Differential Switch
Alarm
General Differential Switch
Alarm Relays
General Differential Switch
Alarm Delay
General Differential Switch
Alarm Events
General Differential Switch Trip
General Differential Switch Trip
Relays
General Differential Switch Trip
Delay
Differential Switch Assignable
Function
Assign Differential Switch Trip
Relays
Reserved

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

32

127

F22

F116

5000

F1

F115

F113

50000 1

100ms

F2

50

F103

F115

F111

50000 1

100ms

F2

50

F157

F111

CG75

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 23 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

SPEED

13A0
13B0
13B1
13B2
13B3
13B4
13B5
13B6
13B7
13B8
13B9
13BA
13BB
...

1st & 2nd Character of Speed


Switch Name
General Speed Switch Type
General Speed Switch Block
Input from Start
General Speed Switch Alarm
General Speed Switch Alarm
Relays
General Speed Switch Alarm
Delay
General Speed Switch Alarm
Events
General Speed Switch Trip
General Speed Switch Trip
Relays
General Speed Switch Trip Delay
Speed Switch Assignable
Function
Speed Switch Delay
Assign Speed Switch Trip Relays
Reserved

32

127

F22

F116

5000

F1

F115

F113

50000 1

100ms

F2

50

F103

F115

F111

50000 1

100ms

F2

50

F158

5
0

1000
7

5
1

100ms
-

F2
F111

20
1

RESET

13D0
13E0
13E1
13E2
13E3
13E4
13E5
13E6
13E7
13E8
13E9
...

1st & 2nd Character of Reset


Switch Name
General Reset Switch Type
General Reset Switch Block Input
From Start
General Reset Switch Alarm
General Reset Switch Alarm
Relays
General Reset Switch Alarm
Delay
General Reset Switch Alarm
Events
General Reset Switch Trip
General Reset Switch Trip Relays
General Reset Switch Trip Delay
Reset Switch Assignable
Function
Reserved

32

127

F22

F116

5000

F1

F115

F113

50000 1

100ms

F2

50

F103

0
0
1

2
1
7
1
50000 1

100ms

F115
F111
F2

0
1
50

F160

SPARE

1400
1410
1411
1412
1413
1414
1415
1416

CG76

1st & 2nd Character of Spare


Switch Name
General Spare Switch Type
General Spare Switch Block
Input From Start
General Spare Switch Alarm
General Spare Switch Alarm
Relays
General Spare Switch Alarm
Delay
General Spare Switch Alarm
Events
General Spare Switch Trip

32

127

F22

F116

5000

F1

F115

F113

50000 1

100ms

F2

50

F103

F115

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 24 of 77)


ADDR
(hex)

1417
1418

DESCRIPTION

MIN.

141C
141D
...

General Spare Switch Trip Relays


General Spare Switch Trip Delay
Spare Switch Assignable
Function
Starter Aux Contact Type
Starter Operation Monitor Delay
Time
Starter Operation Monitor Type
Starter Operation Monitor Relays
Reserved

1500
1501
1502
1503
1504
1505
1506
1507
...

Trip Relay Reset Mode


Alarm Relay Reset Mode
Aux 1 Relay Reset Mode
Aux 2 Relay Reset Mode
Trip Relay Operation
Alarm Relay Operation
Aux1 Relay Operation
Aux2 Relay Operation
Reserved

1510

Assign Communications Force


Relays
Trip Communications Force
Relay Output Type
Trip Pulsed Output Dwell Time
Alarm Communications Force
Relay Output Type
Alarm Pulsed Output Dwell Time
Aux1 Communications Force
Relay Output Type
Aux1 Pulsed Output Dwell Time
Aux2 Communications Force
Relay Output Type
Aux2 Pulsed Output Dwell Time
Reserved

1419
141A
141B

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
1

7
1
50000 1

F111
100 ms F2

1
50

F159

F109

60

seconds F1

0 (Off)

0
0

2
15

1
1

F115
F169

0 (Off)
0 (None)

1
1
1
1
1
1
1
1

F117
F117
F117
F117
F161
F161
F161
F161

0
0
0
0
0
1
1
0

OUTPUT RELAY SETUP

0
0
0
0
0
0
0
0

2
2
2
2
1
1
1
1

FORCE OUTPUT RELAYS

1511
1512
1513
1514
1515
1516
1517
1518
...

15

N/A

F169

F181

50000 1

100 ms

F2

F181

50000 1

100 ms

F2

F181

50000 1

100 ms

F2

F181

50000 1

100 ms

F2

PROTECTION FUNCTION BLOCKING

1520
1521
1522
1523
1524
1525
1526
1527
1528
...

Log Blocking Events


Block Undercurrent/Underpower
Block Current Unbalance
Block Incomplete Sequence
Block Thermal Model
Block Short Circuit and Backup
Block Overload Alarm
Block Ground Fault
Block Starts Per Hour and Time
Between Starts
Reserved

0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

F30
F30
F30
F30
F30
F30
F30
F30

0
0
0
0
0
0
0
0

N/A

F30

THERMAL MODEL (0 = Off)

1581

Overload Pickup Level

101

125

0.01xFL F3
A

101

1582

Assign Thermal Capacity Trip


Relay

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

F111

CG77

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 25 of 77)


ADDR
(hex)

1583
1584
1585
1586
1587
1588
1589
158A
158B
158C
158D
158E
158F
1590
1591
...
15AE

DESCRIPTION

Unbalance k Factor (0=Learned)


Running Cool Time Constant
Stopped Cool Time Constant
Hot/Cold Safe Stall Ratio
RTD Biasing
RTD Bias Minimum
RTD Bias Mid Point
RTD Bias Maximum
Thermal Capacity Alarm
Assign Thermal Capacity Alarm
Relays
Thermal Capacity Alarm Level
Thermal Capacity Alarm Events
Enable Learned Cool Time
Enable Unbalance Biasing
Motor Load Averaging Interval
Reserved
Select Curve Style

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
1
1
1
0
0
0
0
0

29
500
500
100
1
198
199
200
2

1
1
1
1
1
1
1
1
1

min
min
C
C
C
-

F1
F1
F1
F3
F103
F1
F1
F1
F115

0
15
30
100
0
40
120
155
0

F113

1
0
0
0
3

100
1
1
1
60

1
1
1
1
3

% used F1
F103
F103
F103
cycles
F1

75
0
0
0
3

F128

O/L CURVE SETUP

15AF
15B0
15B2
15B4
15B6
15B8
15BA
15BC
15BE
15C0
15C2
15C4
15C6
15C8
15CA
15CC
15CE
15D0
15D2
15D4
15D6
15D8
15DA
15DC
15DE
15E0
15E2
15E4
15E6
15E8

CG78

Standard Overload Curve


Number
Time to Trip at 1.01 x FLA
Time to Trip at 1.05 x FLA
Time to Trip at 1.10 x FLA
Time to Trip at 1.20 x FLA
Time to Trip at 1.30 x FLA
Time to Trip at 1.40 x FLA
Time to Trip at 1.50 x FLA
Time to Trip at 1.75 x FLA
Time to Trip at 2.00 x FLA
Time to Trip at 2.25 x FLA
Time to Trip at 2.50 x FLA
Time to Trip at 2.75 x FLA
Time to Trip at 3.00 x FLA
Time to Trip at 3.25 x FLA
Time to Trip at 3.50 x FLA
Time to Trip at 3.75 x FLA
Time to Trip at 4.00 x FLA
Time to Trip at 4.25 x FLA
Time to Trip at 4.50 x FLA
Time to Trip at 4.75 x FLA
Time to Trip at 5.00 x FLA
Time to Trip at 5.50 x FLA
Time to Trip at 6.00 x FLA
Time to Trip at 6.50 x FLA
Time to Trip at 7.00 x FLA
Time to Trip at 7.50 x FLA
Time to Trip at 8.00 x FLA
Time to Trip at 10.0 x FLA
Time to Trip at 15.0 x FLA

15

F1

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534
65534

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s

F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1

17415
3415
1667
795
507
365
280
170
117
86
67
53
44
37
31
27
23
21
18
16
15
12
10
9
7
6
6
6
6

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 26 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

15EA
...

Time to Trip at 20.0 x FLA


Reserved

65534 1

1640
1641
1642
1643
1644
1645

...

Short Circuit Trip


Reserved
Assign Short Circuit Trip Relays
Short Circuit Trip Level
Short Circuit Trip Delay
Short Circuit Trip Backup
Assign Short Circuit Backup
Relays
Add Short Circuit Trip Backup
Delay
Reserved

1650

Overload Alarm

1651

Overload Alarm Level

101

150

1652
1653
1654
...

Assign Overload Alarm Relays


Overload Alarm Delay
Overload Alarm Events
Reserved

0
0
0

7
600
1

1
1
1

1660
1661

Mechanical Jam Alarm


Assign Alarm Relays

0
0

2
7

1
1

1662

Mechanical Jam Alarm Level

101

600

1663
1664
1665
1666

Mechanical Jam Alarm Delay


Mechanical Jam Alarm Events
Mechanical Jam Trip
Assign Trip Relays

5
0
0
0

1250
1
2
7

5
1
1
1

1667

Mechanical Jam Trip Level

101

600

1668
...

Mechanical Jam Trip Delay


Reserved

5
-

1250
-

5
-

1670
1671

0
0

1672

Block Undercurrent from Start


Undercurrent Alarm
Assign Undercurrent Alarm
Relays

1673

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F1

SHORT CIRCUIT TRIP (0 = INSTANTANEOUS TIME DELAY)

F115

0
20
0
0

7
200
255.00
2

1
1
0.01
1

CT
s
-

F111
F2
F3
F115

1
100
0
0

F119

25500 0.01

F3

20

0.01 F
LA
s
-

F115

F3

101

F113
F2
F103

1
10
0

0.01 F
LA
s
0.01 F
LA
s
-

F115
F113

0
1

F3

150

F2
F103
F115
F111

10
0
0
1

F3

150

F2
-

10
-

15000 1
2
1

s
-

F1
F115

0
0

F113

Undercurrent Alarm Level

10

99

F3

70

1674
1675
1676
1677

Undercurrent Alarm Delay


Undercurrent Alarm Events
Undercurrent Trip
Assign Undercurrent Trip Relays

1
0
0
0

255
1
2
7

1
1
1
1

F1
F103
F115
F111

1
0
0
1

1678

Undercurrent Trip Level

10

99

F3

70

1679
...

Undercurrent Trip Delay


Reserved

255

0.01 F
LA
s
0.01 F
LA
s

F1

1680
1681

Block Unbalance From Start


Current Unbalance Alarm

1
1

s
-

F1
F115

0
0

1646
1647

OVERLOAD ALARM

MECHANICAL JAM

UNDERCURRENT

CURRENT UNBALANCE

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0

5000
2

CG79

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 27 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

1682
1683
1684
1685
1686
1687
1688
1689
...

Assign Unbalance Alarm Relays


Unbalance Alarm Level
Unbalance Alarm Delay
Unbalance Alarm Events
Current Unbalance Trip
Assign Unbalance Trip Relays
Unbalance Trip Level
Unbalance Trip Delay
Reserved

0
4
1
0
0
0
4
1

16A1

Ground Fault Alarm


Assign Ground Fault Alarm
Relays
Ground Fault Alarm Pickup
GF Alarm Pickup for GE Multilin
50:0.025 CT
Ground Fault Alarm Delay
Ground Fault Alarm Events
Ground Fault Trip
Assign Ground Fault Trip Relays
Ground Fault Trip Pickup
GF Trip Pickup for GE Multilin
50:0.025 CT
Ground Fault Trip Delay
Ground Fault Trip Backup
Ground Fault Trip Backup Relays
Ground Fault Trip Backup Delay
Reserved

MAX.

7
30
255
1
2
7
30
255

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
1
1
1
1
1
1
1

%
s
%
s

F113
F1
F1
F103
F115
F111
F1
F1

1
15
1
0
0
1
20
1

F115

F113

10

100

0.1 CT F3

10

25

2500

Amps

F3

25

0
0
0
0
10

255.00
1
2
7
100

0.01
1
1
1
1

s
0.1 CT

F3
F103
F 115
F 111
F3

0
0
0
1
20

25

2500

0.1 CT F3

25

0
0
0
0.10

255.00
1
3
255.00

0.01
1
1
0.01

s
s

F3
F115
F119
F3

0
0
33
0.20

GROUND FAULT

16A2
16A3
16A4
16A5
16A6
16A7
16A8
16A9
16AA
16AB
16AC
16AD
16AE
...

ACCELERATION TRIP

16D0
16D1
16D2
...
16E0
16E1

16E3
16E4
16E5
...

Acceleration Trip
Assign Trip Relays
Acceleration Timer From Start
Reserved
Enable Single Shot Restart
Enable Start Inhibit
Maximum Starts/Hour
Permissible
Time Between Starts
Restart Block
Assign Block Relays
Reserved

1780
1781
...
1784
1785
1786
...

Enable Back-Spin Start Inhibit


Minimum Permissible Frequency
Reserved
Enable Prediction Algorithm
Assign Backspin Inhibit Relays
Number of Motor Poles
Reserved

0
0

1
999

1
1

Hz

F103
F3

0
100

0
0
2

1
7
16

1
1
2

F103
F111
F1

1
1
2

1790

Local RTD #1 Application

F121

16E2

0
0
10
0
0

1
7
2500
1
1

1
1
1
1
1

1s
-

F115
F111
F1
F103
F103

0
1
100
0
0

F1

0
0
0

500
1
50000 1
7
1

min
s
-

F1
F1
F111

10
0
3

BACKSPIN DETECTION

LOCAL RTD #1

CG80

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 28 of 77)


ADDR
(hex)

1791
1792
1793
1794
1795
1796
1797
1798
1799
179A
179B
179C

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Local RTD #1 High Alarm


Local RTD #1 High Alarm Relays
Local RTD #1 High Alarm Level
Local RTD #1 Alarm
Local RTD #1 Alarm Relays
Local RTD #1 Alarm Level
Record RTD #1 Alarms as Events
Local RTD #1 Trip
Enable RTD #1 Trip Voting
Local RTD #1 Trip Relays
Local RTD #1 Trip Level
Local RTD #1 RTD Type
First Character of Local RTD #1
Name

8th Character of Local RTD #1


Name
Reserved

0
0
1
0
0
1
0
0
0
0
1
0

2
7
200
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
-

F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1
F120

0
2
130
0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

0
0
0
1
0
0
1
0
0
0
0
1
0

4
2
7
200
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
-

F121
F115
F113
F1
F115
F113
F1
F103
F 115
F122
F111
F1
F120

0
0
2
130
0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

...

Local RTD #2 Application


Local RTD #2 High Alarm
Local RTD #2 High Alarm Relays
Local RTD #2 High Alarm Level
Local RTD #2 Alarm
Local RTD #2 Alarm Relays
Local RTD #2 Alarm Level
Record RTD #2 Alarms as Events
Local RTD #2 Trip
Enable RTD #2 Trip Voting
Local RTD #2 Trip Relays
Local RTD #2 Trip Level
Local RTD #2 RTD Type
First Character of Local RTD #2
Name

8th Character of Local RTD #2


Name
Reserved

17D0
17D1
17D2
17D3
17D4
17D5
17D6
17D7
17D8
17D9
17DA
17DB

Local RTD #3 Application


Local RTD #3 High Alarm
Local RTD #3 High Alarm Relays
Local RTD #3 High Alarm Level
Local RTD #3 Alarm
Local RTD #3 Alarm Relays
Local RTD #3 Alarm Level
Record RTD #3 Alarms as Events
Local RTD #3 Trip
Enable RTD #3 Trip Voting
Local RTD #3 Trip Relays
Local RTD #3 Trip Level

0
0
0
1
0
0
1
0
0
0
0
1

1
1
1
1
1
1
1
1
1
1
1
1

C
C
C

F121
F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1

0
0
2
130
0
1
130
0
0
1
1
130

17A0

17A3
...

LOCAL RTD #2

17B0
17B1
17B2
17B3
17B4
17B5
17B6
17B7
17B8
17B9
17BA
17BB
17BC
17C0

17C3

LOCAL RTD #3

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

4
2
7
200
2
7
200
1
2
13
7
200

CG81

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 29 of 77)


ADDR
(hex)

17DC

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Local RTD #3 RTD Type


First Character of Local RTD #3
Name

8th Character of Local RTD #3


Name
Reserved

F120

32

127

F1

32

127

F1

""

Local RTD #4 Application


Local RTD #4 High Alarm
Local RTD #4 High Alarm Relays
Local RTD #4 High Alarm Level
Local RTD #4 Alarm
Local RTD #4 Alarm Relays
Local RTD #4 Alarm Level
Enable RTD #4 Alarms as Events
Local RTD #4 Trip
Enable RTD #4 Trip Voting
Local RTD #4 Trip Relays
Local RTD #4 Trip Level
Local RTD #4 RTD Type
First Character of Local RTD #4
Name

8th Character of Local RTD #4


Name
Reserved

0
0
0
1
0
0
1
0
0
0
0
1
0

4
2
7
200
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
-

F121
F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1
F120

0
0
2
130
0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

0
0
0
1
0
0
1
0
0
0
0
1
0

4
2
7
250
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1
1

C / F
C
C
-

F121
F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1
F120

0
0
1
130
0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

...

Local RTD #5 Application


Local RTD #5 High Alarm
Local RTD #5 High Alarm Relays
Local RTD #5 High Alarm Level
Local RTD #5 Alarm
Local RTD #5 Alarm Relays
Local RTD #5 Alarm Level
Record RTD #5 Alarms as Events
Local RTD #5 Trip
Enable RTD #5 Trip Voting
Local RTD #5 Trip Relays
Local RTD #5 Trip Level
Local RTD #5 RTD Type
First Character of Local RTD #5
Name

8th Character of Local RTD #5


Name
Reserved

1830
1831
1832
1833

Local RTD #6 Application


Local RTD #6 High Alarm
Local RTD #6 High Alarm Relays
Local RTD #6 High Alarm Level

0
0
0
1

1
1
1
1

F121
F115
F113
F1

0
0
2
130

17E0

17E3
...

LOCAL RTD #4

17F0
17F1
17F2
17F3
17F4
17F5
17F6
17F7
17F8
17F9
17FA
17FB
17FC
1800

1803
...

LOCAL RTD #5

1810
1811
1812
1813
1814
1815
1816
1817
1818
1819
181A
181B
181C
1820

1823

LOCAL RTD #6

CG82

4
2
7
200

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 30 of 77)


ADDR
(hex)

1834
1835
1836
1837
1838
1839
183A
183B
183C
1840

1843
...

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Local RTD #6 Alarm


Local RTD #6 Alarm Relays
Local RTD #6 Alarm Level
Record RTD #6 Alarms as Events
Local RTD #6 Trip
Enable RTD #6 Trip Voting
Local RTD #6 Trip Relays
Local RTD #6 Trip Level
Local RTD #6 RTD Type
First Character of Local RTD #6
Name

8th Character of Local RTD #6


Name
Reserved

0
0
1
0
0
0
0
1
0

2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1

C
C
-

F115
F113
F1
F103
F115
F122
F111
F1
F120

0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

Local RTD #7 Application


Local RTD #7 High Alarm
Local RTD #7 High Alarm Relays
Local RTD #7 High Alarm Level
Local RTD #7 Alarm
Local RTD #7 Alarm Relays
Local RTD #7 Alarm Level
Record RTD #7 Alarms as Events
Local RTD #7 Trip
Enable RTD #7 Trip Voting
Local RTD #7 Trip Relays
Local RTD #7 Trip Level
Local RTD #7 RTD Type
First Character of Local RTD #7
Name

8th Character of Local RTD #7


Name
Reserved

0
0
0
1
0
0
1
0
0
0
0
1
0

4
2
7
200
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
-

F121
F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1
F120

0
0
2
130
0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

Local RTD #8 Application


Local RTD #8 High Alarm
Local RTD #8 High Alarm Relays
Local RTD #8 High Alarm Level
Local RTD #8 Alarm
Local RTD #8 Alarm Relays
Local RTD #8 Alarm Level
Record RTD #8 Alarms as Events
Local RTD #8 Trip
Enable RTD #8 Trip Voting
Local RTD #8 Trip Relays
Local RTD #8 Trip Level
Local RTD #8 RTD Type
First Character of Local RTD #8
Name

0
0
0
1
0
0
1
0
0
0
0
1
0

4
2
7
200
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
-

F121
F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1
F120

0
0
2
130
0
1
130
0
0
1
1
130
0

32

127

F1

LOCAL RTD #7

1850
1851
1852
1853
1854
1855
1856
1857
1858
1859
185A
185B
185C
1860

1863
1864

LOCAL RTD #8

1870
1871
1872
1873
1874
1875
1876
1877
1878
1879
187A
187B
187C
1880

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG83

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 31 of 77)


ADDR
(hex)

1883
1884

DESCRIPTION

8th Character of Local RTD #8


Name
Reserved

MIN.

32

MAX.

127

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F1

""

LOCAL RTD #9

1890
1891
1892
1893
1894
1895
1896
1897
1898
1899
189A
189B
189C
18A0

18A3
18A4

Local RTD #9 Application


Local RTD #9 High Alarm
Local RTD #9 High Alarm Relays
Local RTD #9 High Alarm Level
Local RTD #9 Alarm
Local RTD #9 Alarm Relays
Local RTD #9 Alarm Level
Record RTD #9 Alarms as Events
Local RTD #9 Trip
Enable RTD #9 Trip Voting
Local RTD #9 Trip Relays
Local RTD #9 Trip Level
Local RTD #9 RTD Type
First Character of Local RTD #9
Name

8th Character of Local RTD #9


Name
Reserved

0
0
0
1
0
0
1
0
0
0
0
1
0

4
2
7
200
2
7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1
1
1
1
1
1

C
C
C
-

F121
F115
F113
F1
F115
F113
F1
F103
F115
F122
F111
F1
F120

0
0
2
130
0
1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

Local RTD #10 Application


Local RTD #10 High Alarm
Local RTD #10 High Alarm
Relays
Local RTD #10 High Alarm Level
Local RTD #10 Alarm
Local RTD #10 Alarm Relays
Local RTD #10 Alarm Level
Record RTD #10 Alarms as
Events
Local RTD #10 Trip
Enable RTD #10 Trip Voting
Local RTD #10 Trip Relays
Local RTD #10 Trip Level
Local RTD #10 RTD Type
First Character of Local RTD #10
Name

8th Character of RTD #10 Name


Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

1
0
0
1

200
2
7
200

1
1
1
1

C
C

F1
F115
F113
F1

130
0
1
130

F103

0
0
0
1
0

2
13
7
200
3

1
1
1
1
1

C
-

F115
F122
F111
F1
F120

0
1
1
130
0

32

127

F1

32

127

F1

""

LOCAL RTD #10

18B0
18B1
18B2
18B3
18B4
18B5
18B6
18B7
18B8
18B9
18BA
18BB
18BC
18C0

18C3
...

LOCAL RTD #11

18D0
18D1
18D2
18D3
18D4

CG84

Local RTD #11 Application


Local RTD #11 High Alarm
Local RTD #11 High Alarm
Relays
Local RTD #11 High Alarm Level
Local RTD #11 Alarm

0
0

4
2

1
1

F121
F115

0
0

F113

1
0

200
2

1
1

C
-

F1
F115

130
0

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 32 of 77)


ADDR
(hex)

18D5
18D6
18D7
18D8
18D9
18DA
18DB
18DC

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Local RTD #11 Alarm Relays


Local RTD #11 Alarm Level
Record RTD #11 Alarm Events
Local RTD #11 Trip
Enable RTD #11 Trip Voting
Local RTD #11 Trip Relays
Local RTD #11 Trip Level
Local RTD #11 RTD Type
First Character of Local RTD #11
Name

8th Character of Local RTD #11


Name
Reserved

0
1
0
0
0
0
1
0

7
200
1
2
13
7
200
3

1
1
1
1
1
1
1
1

C
C
-

F113
F1
F103
F115
F122
F111
F1
F120

1
130
0
0
1
1
130
0

32

127

F1

32

127

F1

""

0
0

4
2

1
1

F121
F115

0
0

F113

1
0
0
1

200
2
7
200

1
1
1
1

C
C

F1
F115
F113
F1

130
0
1
130

F103

0
0
0
1
0

2
13
7
200
3

1
1
1
1
1

C
-

F115
F122
F111
F1
F120

0
1
1
130
0

32

127

F1

32

127

F1

""

...

Local RTD #12 Application


Local RTD #12 High Alarm
Local RTD #12 High Alarm
Relays
Local RTD #12 High Alarm Level
Local RTD #12 Alarm
Local RTD #12 Alarm Relays
Local RTD #12 Alarm Level
Record RTD #12 Alarms as
Events
Local RTD #12 Trip
Enable RTD #12 Trip Voting
Local RTD #12 Trip Relays
Local RTD #12 Trip Level
Local RTD #12 RTD Type
First Character of Local RTD #12
Name

8th Character of Local RTD #12


Name
Reserved

1B20
1B21
1B22

Open RTD Alarm


Assign Alarm Relays
Open RTD Alarm Events

1
1
1

F115
F113
F103

0
1
0

1B23
1B24
1B25
...

Short / Low Temp RTD Alarm


Assign Alarm Relays
Short / Low Temp Alarm Events
Reserved

F115
F113
F103
-

0
1
0
-

1B30
1B31
1B32
...

Loss RRTD Comm Alarm


Loss RRTD Comm Alarm Relays
Loss RRTD Comm Alarm Events
Reserved

F115
F113
F103

0
1
0

18E0

18E3
...

LOCAL RTD #12

18F0
18F1
18F2
18F3
18F4
18F5
18F6
18F7
18F8
18F9
18FA
18FB
18FC
1900

1903

OPEN RTD ALARM

0
0
0

2
7
1

SHORT/LOW TEMPERATURE RTD ALARM

0
0
0
-

2
7
1
-

1
1
1
-

LOSS OF REMOTE RTD COMMUNICATIONS

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0
0

2
7
1

1
1
1

CG85

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 33 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

UNDERVOLTAGE

1B6B
...

Undervoltage Active If Motor


Stopped
Undervoltage Alarm
Assign Alarm Relays
Undervoltage Alarm Pickup
Starting Undervoltage Alarm
Pickup
Undervoltage Alarm Delay
Undervoltage Alarm Events
Undervoltage Trip
Undervoltage Trip Relays
Undervoltage Trip Pickup
Starting Undervoltage Trip
Pickup
Undervoltage Trip Delay
Reserved

1B80
1B81
1B82
1B83
1B84
1B85
1B86
1B87
1B88
...

Overvoltage Alarm
Overvoltage Alarm Relays
Overvoltage Alarm Pickup
Overvoltage Alarm Delay
Overvoltage Alarm Events
Overvoltage Trip
Overvoltage Trip Relays
Overvoltage Trip Pickup
Overvoltage Trip Delay
Reserved

0
0
101
0
0
0
0
101
0

1BA0
1BA1
...

Phase Reversal Trip


Assign Trip Relays
Reserved

0
0
-

1BB0
1BB1
1BB2
1BB3
1BB4
1BB5
1BB6
1BB7
1BB8
1BB9
...

Block Overfrequency on Start


Overfrequency Alarm
Assign Alarm Relays
Overfrequency Alarm Level
Overfrequency Alarm Delay
Overfrequency Alarm Events
Overfrequency Trip
Assign Trip Relays
Overfrequency Trip Level
Overfrequency Trip Delay
Reserved

0
0
0
2000
0
0
0
0
2000
0
-

1BC0
1BC1
1BC2
1BC3
1BC4
1BC5

Block Underfrequency on Start


Underfrequency Alarm
Assign Alarm Relays
Underfrequency Alarm Level
Underfrequency Alarm Delay
Underfrequency Alarm Events

0
0
0
2000
0
0

1B60
1B61
1B62
1B63
1B64
1B65
1B66
1B67
1B68
1B69
1B6A

F103

0
0
50

2
7
99

1
1
1

F115
F113
Rated F3

0
1
85

50

99

Rated F3

85

0
0
0
0
50

2550
1
2
7
99

1
1
1
1
1

0.1s
Rated

30
0
0
1
80

50

99

Rated F3

80

2550

0.1s

F2

10

1
1
1
1
1
1
1
1
1

x Rated
s
x Rated
s

F115
F113
F3
F2
F103
F103
F111
F3
F2

0
1
105
10
0
0
1
110
10

1
1
-

F115
F111
-

0
1
-

1
1
1
1
1
1
1
1
1
1
-

s
Hz
s
Hz
s
-

F1
F115
F113
F3
F2
F103
F103
F111
F3
F2
-

1
0
1
6050
10
0
0
1
6050
10
-

1
1
1
1
1
1

s
Hz
s
-

F1
F115
F113
F3
F2
F103

1
0
1
5950
10
0

F2
F103
F115
F111
F3

OVERVOLTAGE

2
7
125
2550
1
1
7
125
2550

PHASE REVERSAL

2
7
-

OVERFREQUENCY

5000
2
7
7000
2550
1
1
7
7000
2550
-

UNDERFREQUENCY

CG86

5000
2
7
7000
2550
1

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 34 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

1BC6
1BC7
1BC8
1BC9
...

Underfrequency Trip
Assign Trip Relays
Underfrequency Trip Level
Underfrequency Trip Delay
Reserved

0
0
2000
0

1BD0

Block Lead Power Factor From


Start
Lead Power Factor Alarm
Assign Lead Power Factor Alarm
Relays
Lead Power Factor Alarm Level
Lead Power Factor Alarm Delay
Lead Power Factor Alarm Events
Lead Power Factor Trip
Lead Power Factor Trip Relays
Lead Power Factor Trip Level
Lead Power Factor Trip Delay
Reserved

MAX.

2
7
7000
2550

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
1
1
1

Hz
s

F115
F111
F3
F2

0
1
5950
10

LEAD POWER FACTOR

1BD1
1BD2
1BD3
1BD4
1BD5
1BD6
1BD7
1BD8
1BD9
...

5000

F1

F115

F113

5
1
0
0
0
5
1

99
2550
1
2
7
99
2550

1
1
1
1
1
1
1

s
s

F3
F2
F103
F115
F111
F3
F2

30
10
0
0
1
10
10

LAG POWER FACTOR

1BE0
1BE1
1BE2
1BE3
1BE4
1BE5
1BE6
1BE7
1BE8
1BE9
...

Block Lag Power Factor From


Start
Lag Power Factor Alarm
Assign Lag Power Factor Alarm
Relays
Lag Power Factor Alarm Level
Lag Power Factor Alarm Delay
Lag Power Factor Alarm Events
Lag Power Factor Trip
Assign Lag Power Factor Trip
Relays
Lag Power Factor Trip Level
Lag Power Factor Trip Delay
Reserved

5000

F1

F115

F113

5
1
0
0

99
2550
1
2

1
1
1
1

s
-

F3
F2
F103
F115

85
10
0
0

F111

5
1

99
2550

1
1

F3
F2

80
10

POSITIVE REACTIVE POWER

1BF0
1BF1
1BF2
1BF3
1BF4
1BF5
1BF6
1BF7
1BF8
1BF9
...

Block Positive kvar Element


From Start
Positive kvar Alarm
Assign Alarm Relays
Positive kvar Alarm Level
Positive kvar Alarm Delay
Positive kvar Alarm Events
Positive kvar Trip
Assign Trip Relays
Positive kvar Trip Level
Positive kvar Trip Delay
Reserved

5000

F1

0
0
1
1
0
0
0
1
1

2
7
25000
2550
1
1
7
25000
2550

1
1
1
1
1
1
1
1
1

kvar
s
kvar
s

F115
F113
F1
F2
F103
F103
F111
F1
F2

0
1
10
10
0
0
1
25
10

NEGATIVE REACTIVE POWER

1C00
1C01
1C02

Block Negative kvar Element


from Start
Negative kvar Alarm
Assign Alarm Relays

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

5000

F1

0
0

2
7

1
1

F115
F113

0
1

CG87

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 35 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

1C03
1C04
1C05
1C06
1C07
1C08
1C09
...

Negative kvar Alarm Level


Negative kvar Alarm Delay
Negative kvar Alarm Events
Negative kvar Trip
Assign Trip Relays
Negative kvar Trip Level
Negative kvar Trip Delay
Reserved

1
1
0
0
0
1
1

1C10
1C11
1C12
1C13
1C14
1C15
1C16
1C17
1C18
1C19
...

Block Underpower From Start


Underpower Alarm
Assign Alarm Relays
Underpower Alarm Level
Underpower Alarm Delay
Underpower Alarm Events
Underpower Trip
Underpower Trip Relays
Underpower Trip Level
Underpower Trip Delay
Reserved

0
0
0
1
5
0
0
0
1
5

1C20
1C21
1C22
1C23
1C24
1C25
1C26
1C27
1C28
1C29
...

Block Reverse Power From Start


Reverse Power Alarm
Assign Alarm Relays
Reverse Power Alarm Level
Reverse Power Alarm Delay
Reverse Power Alarm Events
Reverse Power Trip
Assign Trip Relays
Reverse Power Trip Level
Reverse Power Trip Delay
Reserved

0
0
0
1
5
0
0
0
1
5

1C70
1C71

Number of Starts to Average


Access Learned Data Record
Number

1C80
1C81
1C82
1C83
...

Trip Counter Alarm


Assign Alarm Relays
Alarm Pickup Level
Trip Counter Alarm Events
Reserved

0
0
0
0

1C90
1C91
1C92
1C93
1C94
...

Starter Failure Alarm


Starter Type
Assign Alarm Relays
Starter Failure Delay
Starter Failure Alarm Events
Reserved

0
0
0
10
0

1CD0

Current Demand Period

MAX.

25000
2550
1
1
7
25000
2550

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
1
1
1
1
1
1

kvar
s
kvar
s

F1
F2
F103
F103
F111
F1
F2

10
10
0
0
1
25
10

1
1
1
1
1
1
1
1
1
1

s
kW
s
kW
s

F1
F115
F113
F1
F2
F103
F115
F111
F1
F1

0
0
1
2
1
0
0
1
1
1

1
1
1
1
1
1
1
1
1
1

s
kW
s
kW
s

F1
F115
F113
F1
F2
F103
F115
F111
F1
F2

0
0
1
2
1
0
0
1
1
1

UNDERPOWER

15000
2
7
25000
2550
1
2
7
25000
2550

REVERSE POWER

50000
2
7
25000
300
1
2
7
25000
300

ENHANCED MOTOR LEARNED DATA

F1

65535 1

F1

1
1
1
1

F115
F113
F1
F103

0
1
25
0

1
1
1
10
1

ms
-

F115
F125
F113
F1
F103

0
0
1
100
0

min

F1

15

TRIP COUNTER

2
7
50000
1

STARTER FAILURE

2
1
7
1000
1

CURRENT DEMAND

CG88

90

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 36 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

1CD1
1CD2
1CD3
1CD5
...

Current Demand Alarm


Assign Alarm Relays
Current Demand Alarm Limit
Current Demand Alarm Events
Reserved

0
0
0
0

1CE0
1CE1
1CE2
1CE3
1CE4
...

kW Demand Period
kW Demand Alarm
Assign Alarm Relays
kW Demand Alarm Limit
kW Demand Alarm Events
Reserved

5
0
0
1
0

1CF0
1CF1
1CF2
1CF3
1CF4
...

kvar Demand Period


kvar Demand Alarm
Assign Alarm Relays
kvar Demand Alarm Limit
kvar Demand Alarm Events
Reserved

5
0
0
1
0

1D00
1D01
1D02
1D03
1D04
...

kVA Demand Period


kVA Demand Alarm
Assign Alarm Relays
kVA Demand Alarm Limit
kVA Demand Alarm Events
Reserved

5
0
0
1
0

1D06
...

Assign Service Relay


Reserved

1D40

Enable Analog Output 1


Assign Analog Output 1 Output
Range
Assign Analog Output 1
Parameter
Analog Output 1 Minimum
Analog Output 1 Maximum
Enable Analog Output 2
Assign Analog Output 2 Output
Range
Assign Analog Output 2
Parameter
Analog Output 2 Minimum
Analog Output 2 Maximum
Enable Analog Output 3
Assign Analog Output 3 Output
Range
Assign Analog Output 3
Parameter
Analog Output 3 Minimum
Analog Output 3 Maximum
Enable Analog Output 4

MAX.

2
7
65000
1

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
1
1
1

A
-

F115
F113
F1
F103

0
1
100
0

1
1
1
1
1

min
kW
-

F1
F115
F113
F1
F103

15
0
1
100
0

1
1
1
1
1

min
kvar
-

F1
F115
F113
F1
F103

15
0
1
100
0

1
1
1
1
1

min
kVA
-

F1
F115
F113
F1
F103

15
0
1
100
0

F113

F103

F26

35

F127

TBD
TBD
0

TBD
TBD
1

1
1
1

F1
F1
F103

0
0
0

F26

35

F127

TBD
TBD
0

TBD
TBD
1

1
1
1

F1
F1
F103

0
0
0

F26

35

F127

TBD
TBD
0

TBD
TBD
1

1
1
1

F1
F1
F103

0
0
0

KW DEMAND

90
2
7
50000
1
KVAR DEMAND

90
2
7
50000
1
KVA DEMAND

90
2
7
50000
1

SELF-TEST RELAY

ANALOG OUTPUTS

1D41
1D42
1D43
1D44
1D45
1D46
1D47
1D48
1D49
1D4A
1D4B
1D4C
1D4D
1D4E
1D4F

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG89

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 37 of 77)


ADDR
(hex)

1D50
1D51
1D52
1D53

DESCRIPTION

Assign Analog Output 4 Output


Range
Assign Analog Output 4
Parameter
Analog Output 4 Minimum
Analog Output 4 Maximum

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F26

35

F127

TBD
TBD

TBD
TBD

1
1

F1
F1

0
0

SPEED 2 O/L CURVE SETUP

1DC0
1DC1
1DC2
1DC3
1DC4
1DC5
1DC6
1DC7
1DC8
1DC9
1DCA
1DCB
1DCC
1DCD
1DCE
1DCF
1DD0
1DD1
1DD2
1DD3
1DD4
1DD5
1DD6
1DD7
1DD8

CG90

Speed 2 Standard Overload


Curve Number
Speed 2 Time to Trip at 1.01 x
FLA
Speed 2 Time to Trip at 1.05 x
FLA
Speed 2 Time to Trip at 1.10 x
FLA
Speed 2 Time to Trip at 1.20 x
FLA
Speed 2 Time to Trip at 1.30 x
FLA
Speed 2 Time to Trip at 1.40 x
FLA
Speed 2 Time to Trip at 1.50 x
FLA
Speed 2 Time to Trip at 1.75 x
FLA
Speed 2 Time to Trip at 2.00 x
FLA
Speed 2 Time to Trip at 2.25 x
FLA
Speed 2 Time to Trip at 2.50 x
FLA
Speed 2 Time to Trip at 2.75 x
FLA
Speed 2 Time to Trip at 3.00 x
FLA
Speed 2 Time to Trip at 3.25 x
FLA
Speed 2 Time to Trip at 3.50 x
FLA
Speed 2 Time to Trip at 3.75 x
FLA
Speed 2 Time to Trip at 4.00 x
FLA
Speed 2 Time to Trip at 4.25 x
FLA
Speed 2 Time to Trip at 4.50 x
FLA
Speed 2 Time to Trip at 4.75 x
FLA
Speed 2 Time to Trip at 5.00 x
FLA
Speed 2 Time to Trip at 5.50 x
FLA
Speed 2 Time to Trip at 6.00 x
FLA
Speed 2 Time to Trip at 6.50 x
FLA

15

F1

65534 1

F1

17415

65534 1

F1

3415

65534 1

F1

1667

65534 1

F1

795

65534 1

F1

507

65534 1

F1

365

65534 1

F1

280

65534 1

F1

170

65534 1

F1

117

65534 1

F1

86

65534 1

F1

67

65534 1

F1

53

65534 1

F1

44

65534 1

F1

37

65534 1

F1

31

65534 1

F1

27

65534 1

F1

23

65534 1

F1

21

65534 1

F1

18

65534 1

F1

16

65534 1

F1

15

65534 1

F1

12

65534 1

F1

10

65534 1

F1

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 38 of 77)


ADDR
(hex)

DESCRIPTION

Speed 2 Time to Trip at 7.00 x


FLA
2 Time to Trip at 7.50 x
1DDA Speed
FLA
2 Time to Trip at 8.00 x
1DDB Speed
FLA
2 Time to Trip at 10.0 x
1DDC Speed
FLA
2 Time to Trip at 15.0 x
1DDD Speed
FLA
2 Time to Trip at 20.0 x
1DDE Speed
FLA
...
Reserved
1DD9

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

65534 1

F1

65534 1

F1

65534 1

F1

65534 1

F1

65534 1

F1

65534 1

F1

SPEED 2 UNDERCURRENT

1DF7

Speed 2 Block Undercurrent


from Start
Speed 2 Undercurrent Alarm
Speed 2 Assign Undercurrent
Alarm Relays
Speed 2 Undercurrent Alarm
Level
Speed 2 Undercurrent Alarm
Delay
Speed 2 Undercurrent Alarm
Events
Speed 2 Undercurrent Trip
Speed 2 Assign Undercurrent
Trip Relays

1DF8

Speed 2 Undercurrent Trip Level 10

99

1DF9
...

Speed 2 Undercurrent Trip Delay 1


Reserved

255

1E00

Speed 2 Acceleration Timer from 10


Start
Speed 2 Acceleration Timer from 20
Speed 1 to 2
Speed 2 Speed Switch Time
5
Delay

1DF0
1DF1
1DF2
1DF3
1DF4
1DF5
1DF6

15000 1

F1

F115

F113

10

99

0.01 F F3
LA

70

255

F1

F103

F115

F111

0.01 F F3
LA
s
F1

70
1

SPEED 2 ACCELERATION

1E01
1E02

2500

10

F2

100

2500

F2

200

1000

100 ms

F2

20

DATA LOGGER

1E20

Start/Stop Data Log

F187

1E21

Log Interval

3600

F1

1E22

Recording Type

F188

0 (=Select
Comman
d)
3600
0 (=Run
To Fill)

1E23

Data Log Memory Access Block


Number
Channel 1 Log Assignment
Channel 2 Log Assignment
Channel 3 Log Assignment
Channel 4 Log Assignment
Channel 5 Log Assignment
Channel 6 Log Assignment
Channel 7 Log Assignment
Channel 8 Log Assignment

255

F1

0, 1 (=null)

0
0
0
0
0
0
0
0

102
102
102
102
102
102
102
102

1
1
1
1
1
1
1
1

F189
F189
F189
F189
F189
F189
F189
F189

0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)

1E24
1E25
1E26
1E27
1E28
1E29
1E2A
1E2B

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG91

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 39 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

1E2C
1E2D
1E2E
1E2F
1E30
1E31
1E32
1E33
...

Channel 9 Log Assignment


Channel 10 Log Assignment
Channel 11 Log Assignment
Channel 12 Log Assignment
Channel 13 Log Assignment
Channel 14 Log Assignment
Channel 15 Log Assignment
Channel 16 Log Assignment
Reserved

0
0
0
0
0
0
0
0

1F80
1F81
1F82
1F83
1F84
1F85
1F86
1F87
...

Force Trip Relay


Force Trip Relay Duration
Force AUX1 Relay
Force AUX1 Relay Duration
Force AUX2 Relay
Force AUX2 Relay Duration
Force Alarm Relay
Force Alarm Relay Range
Reserved

1F90
1F91
1F92
1F93
1F94
...

Force Analog Outputs


Analog Output 1 Forced Value
Analog Output 2 Forced Value
Analog Output 3 Forced Value
Analog Output 4 Forced Value
Reserved

1FF0
1FF1
1FF2
1FF3
...

RRTD1 - Slave Address


RRTD2 - Slave Address
RRTD3 - Slave Address
RRTD4 - Slave Address
Reserved

0
0
0
0

2000
2001

RRTD 1 - RTD #1 Application


RRTD 1 - RTD #1 High Alarm
RRTD 1 - RTD #1 High Alarm
Relays
RRTD 1 - RTD #1 High Alarm
Level
RRTD 1 - RTD #1 Alarm
RRTD 1 - RTD #1 Alarm Relays
RRTD 1 - RTD #1 Alarm Level
Record RRTD 1 - RTD #1 Alarms
as Events
RRTD 1 - RTD #1 Trip
Enable RRTD 1 - RTD #1 Trip
Voting
RRTD 1 - RTD #1 Trip Relays
RRTD 1 - RTD #1 Trip Level
RRTD 1 - RTD #1 RTD Type
Reserved

0
0

MAX.

102
102
102
102
102
102
102
102

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
1
1
1
1
1
1
1

F189
F189
F189
F189
F189
F189
F189
F189

0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)
0 (=None)

1
1
1
1
1
1
1
1

s
s
s
s

F150
F1
F150
F1
F150
F1
F150
F1

0
0
0
0
0
0
0
0

% range
% range
% range
% range

F126
F1
F1
F1
F1

0
0
0
0
0

1
1
1
1

F1
F1
F1
F1

0
0
0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

TEST OUTPUT RELAYS

0
1
0
1
0
1
0
1

2
300
2
300
2
300
2
300

TEST ANALOG OUTPUTS

0
0
0
0
0

1
100
100
100
100

1
1
1
1
1

REMOTE RTD SLAVE ADDRESSES

254
254
254
254

RRTD 1 RTD #1

2002
2003
2004
2005
2006
2007
2008
2009
200A
200B
200C
...

CG92

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 40 of 77)


ADDR
(hex)

2010

2013
2014

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

First Character of RRTD 1 - RTD


#1 Name

8th Character of RRTD 1 - RTD


#1 Name
Reserved

32

127

F1

32

127

F1

""

RRTD 1 - RTD #2 Application


RRTD 1 - RTD #2 High Alarm
RRTD 1 - RTD #2 High Alarm
Relays
RRTD 1 - RTD #2 High Alarm
Level
RRTD 1 - RTD #2 Alarm
RRTD 1 - RTD #2 Alarm Relays
RRTD 1 - RTD #2 Alarm Level
Record RRTD 1 - RTD #2 Alarms
as Events
RRTD 1 - RTD #2 Trip
Enable A Remote RTD #2 Trip
Voting
RRTD 1 - RTD #2 Trip Relays
RRTD 1 - RTD #2 Trip Level
RRTD 1 - RTD #2 RTD Type
Reserved
First Character of RRTD 1 - RTD
#2 Name

8th Character of RRTD 1 - RTD


#2 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #3 Application


RRTD 1 - RTD #3 High Alarm
RRTD 1 - RTD #3 High Alarm
Relays
RRTD 1 - RTD #3 High Alarm
Level
RRTD 1 - RTD #3 Alarm
RRTD 1 - RTD #3 Alarm Relays
RRTD 1 - RTD #3 Alarm Level
Record RRTD 1 - RTD #3 Alarms
as Events
RRTD 1 - RTD #3 Trip
Enable RRTD 1 - RTD #3 Trip
Voting
RRTD 1 - RTD #3 Trip Relays
RRTD 1 - RTD #3 Trip Level
RRTD 1 - RTD #3 RTD Type
First Character of RRTD 1 - RTD #
Name

8th Character of RRTD 1 - RTD


#3 Name

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 RTD #2

2020
2021
2022
2023
2024
2025
2026
2027
2028
2029
202A
202B
202C
...
2030

2033
2034

RRTD 1 RTD #3

2040
2041
2042
2043
2044
2045
2046
2047
2048
2049
204A
204B
204C
2050

2053

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG93

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 41 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

...

Reserved

2060
2061

RRTD 1 - RTD #4 Application


RRTD 1 - RTD #4 High Alarm
RRTD 1 - RTD #4 High Alarm
Relays
RRTD 1 - RTD #4 High Alarm
Level
RRTD 1 - RTD #4 Alarm
RRTD 1 - RTD #4 Alarm Relays
RRTD 1 - RTD #4 Alarm Level
Record RRTD 1 - RTD #4 Alarms
as Events
RRTD 1 - RTD #4 Trip
Enable RRTD 1 - RTD #4 Trip
Voting
RRTD 1 - RTD #4 Trip Relays
RRTD 1 - RTD #4 Trip Level
RRTD 1 - RTD #4 RTD Type
First Character of RRTD 1 - RTD
#4 Name

8th Character of RRTD 1 - RTD


#4 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #5 Application


RRTD 1 - RTD #5 High Alarm
RRTD 1 - RTD #5 High Alarm
Relays
RRTD 1 - RTD #5 High Alarm
Level
RRTD 1 - RTD #5 Alarm
RRTD 1 - RTD #5 Alarm Relays
RRTD 1 - RTD #5 Alarm Level
Record RRTD 1 - RTD #5 Alarms
as Events
RRTD 1 - RTD #5 Trip
Enable RRTD 1 - RTD #5 Trip
Voting
RRTD 1 - RTD #5 Trip Relays
RRTD 1 - RTD #5 Trip Level
RRTD 1 - RTD #5 RTD Type
First Character of RRTD 1 - RTD
#5 Name

8th Character of RRTD 1 - RTD


#5 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #6 Application


RRTD 1 - RTD #6 High Alarm
RRTD 1 - RTD #6 High Alarm
Relays

0
0

4
2

1
1

F121
F115

0
0

F113

RRTD 1 RTD #4

2062
2063
2064
2065
2066
2067
2068
2069
206A
206B
206C
2070

2073
2074

RRTD 1 RTD #5

2080
2081
2082
2083
2084
2085
2086
2087
2088
2089
208A
208B
208C
2090

2093
...

RRTD 1 RTD #6

20A0
20A1
20A2

CG94

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 42 of 77)


ADDR
(hex)

20A3
20A4
20A5
20A6
20A7
20A8
20A9
20AA
20AB
20AC
20B0

20B3
...

DESCRIPTION

RRTD 1 - RTD #6 High Alarm


Level
RRTD 1 - RTD #6 Alarm
RRTD 1 - RTD #6 Alarm Relays
RRTD 1 - RTD #6 Alarm Level
Record RRTD 1 - RTD #6 Alarms
as Events
RRTD 1 - RTD #6 Trip
Enable RRTD 1 - RTD #6 Trip
Voting
RRTD 1 - RTD #6 Trip Relays
RRTD 1 - RTD #6 Trip Level
RRTD 1 - RTD #6 RTD Type
First Character of RRTD 1 - RTD
#6 Name

8th Character of RRTD 1 - RTD


#6 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 RTD #7

20C0
20C1
20C2
20C3
20C4
20C5
20C6
20C7
20C8
20C9
20CA
20CB
20CC
20D0

20D3
...

RRTD 1 - RTD #7 Application


RRTD 1 - RTD #7 High Alarm
RRTD 1 - RTD #7 High Alarm
Relays
RRTD 1 - RTD #7 High Alarm
Level
RRTD 1 - RTD #7 Alarm
RRTD 1 - RTD #7 Alarm Relays
RRTD 1 - RTD #7 Alarm Level
Record RRTD 1 - RTD #7 Alarms
as Events
RRTD 1 - RTD #7 Trip
Enable RRTD 1 - RTD #7 Trip
Voting
RRTD 1 - RTD #7 Trip Relays
RRTD 1 - RTD #7 Trip Level
RRTD 1 - RTD #7 RTD Type
First Character of RRTD 1 - RTD
#7 Name

8th Character of RRTD 1 - RTD


#7 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 RTD #8

20E0
20E1
20E2
20E3
20E4
20E5
20E6

RRTD 1 - RTD #8 Application


RRTD 1 - RTD #8 High Alarm
RRTD 1 - RTD #8 High Alarm
Relays
RRTD 1 - RTD #8 High Alarm
Level
RRTD 1 - RTD #8 Alarm
RRTD 1 - RTD #8 Alarm Relays
RRTD 1 - RTD #8 Alarm Level

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

CG95

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 43 of 77)


ADDR
(hex)

20E7
20E8
20E9
20EA
20EB
20EC
20F0

20F3
...

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Record RRTD 1 - RTD #8 Alarms


as Events
RRTD 1 - RTD #8 Trip
Enable RRTD 1 - RTD #8 Trip
Voting
RRTD 1 - RTD #8 Trip Relays
RRTD 1 - RTD #8 Trip Level
RRTD 1 - RTD #8 RTD Type
First Character of RRTD 1 - RTD
#8 Name

8th Character of RRTD 1 - RTD


#8 Name
Reserved

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #9 Application


RRTD 1 - RTD #9 High Alarm
RRTD 1 - RTD #9 High Alarm
Relays
RRTD 1 - RTD #9 High Alarm
Level
RRTD 1 - RTD #9 Alarm
RRTD 1 - RTD #9 Alarm Relays
RRTD 1 - RTD #9 Alarm Level
Record RRTD 1 - RTD #9 Alarms
as Events
RRTD 1 - RTD #9 Trip
Enable RRTD 1 - RTD #9 Trip
Voting
RRTD 1 - RTD #9 Trip Relays
RRTD 1 - RTD #9 Trip Level
RRTD 1 - RTD #9 RTD Type
First Character of RRTD 1 - RTD
#9 Name

8th Character of RRTD 1 - RTD


#9 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #10 Application


RRTD 1 - RTD #10 High Alarm
RRTD 1 - RTD #10 High Alarm
Relays
RRTD 1 - RTD #10 High Alarm
Level
RRTD 1 - RTD #10 Alarm
RRTD 1 - RTD #10 Alarm Relays
RRTD 1 - RTD #10 Alarm Level
Record RRTD 1 - RTD #10 Alarms
as Events
RRTD 1 - RTD #10 Trip
Enable RRTD 1 - RTD#10 Trip
Voting
RRTD 1 - RTD #10 Trip Relays

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

F111

RRTD 1 RTD #9

2100
2101
2102
2103
2104
2105
2106
2107
2108
2109
210A
210B
210C
2110

2113
...

RRTD 1 RTD #10

2120
2121
2122
2123
2124
2125
2126
2127
2128
2129
212A

CG96

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 44 of 77)


ADDR
(hex)

212B
212C
2130

2133
...

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

RRTD 1 - RTD #10 Trip Level


RRTD 1 - RTD #10 RTD Type
First Character of RRTD 1 - RTD
#10 Name

8th Character of RRTD 1 - RTD


#10 Name
Reserved

1
0

200
3

1
1

C
-

F1
F120

130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #11 Application


RRTD 1 - RTD #11 High Alarm
RRTD 1 - RTD #11 High Alarm
Relays
RRTD 1 - RTD #11 High Alarm
Level
RRTD 1 - RTD #11 Alarm
RRTD 1 - RTD #11 Alarm Relays
RRTD 1 - RTD #11 Alarm Level
Record RRTD 1 - RTD #11 Alarms
as Events
RRTD 1 - RTD #11 Trip
Enable RRTD 1 - RTD #11 Trip
Voting
RRTD 1 - RTD #11 Trip Relays
RRTD 1 - RTD #11 Trip Level
RRTD 1 - RTD #11 RTD Type
First Character of RRTD 1 - RTD
#11 Name

8th Character of RRTD 1 - RTD


#11 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 1 - RTD #12 Application


RRTD 1 - RTD #12 High Alarm
RRTD 1 - RTD #12 High Alarm
Relays
RRTD 1 - RTD #12 High Alarm
Level
RRTD 1 - RTD #12 Alarm
RRTD 1 - RTD #12 Alarm Relays
RRTD 1 - RTD #12 Alarm Level
Record RRTD 1 - RTD #12 Alarms
as Events
RRTD 1 - RTD #12 Trip
Enable RRTD 1 - RTD #12 Trip
Voting
RRTD 1 - RTD #12 Trip Relays
RRTD 1 - RTD #12 Trip Level
RRTD 1 - RTD #12 RTD Type
First Character of RRTD 1 - RTD
#12 Name

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

RRTD 1 RTD #11

2140
2141
2142
2143
2144
2145
2146
2147
2148
2149
214A
214B
214C
2150

2153
...

RRTD 1 RTD #12

2160
2161
2162
2163
2164
2165
2166
2167
2168
2169
216A
216B
216C
2170

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG97

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 45 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

...

8th Character of RRTD 1 - RTD


#12 Name
Reserved

2180
2181
2182

RRTD A - Open RTD Alarm


0
RRTD A - Assign Alarm Relays
0
RRTD A - Open RTD Alarm Events 0

2183

RRTD A - Short / Low Temp RTD


Alarm
RRTD A - Assign Alarm Relays
RRTD A - Short / Low Temp
Alarm Events
Reserved

2173

32

MAX.

127

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F1

""

F115
F113
F103

0
1
0

RRTD 1 OPEN RTD ALARM

2
7
1

1
1
1

RRTD 1 SHORT/LOW TEMPERATURE RTD ALARM

2184
2185
...

F115

F113

F103

RRTD 2 RTD #1

2200
2201
2202
2203
2204
2205
2206
2207
2208
2209
220A
220B
220C
2210

2213
...

RRTD 2 - RTD #1 Application


RRTD 2 - RTD #1 High Alarm
RRTD 2 - RTD #1 High Alarm
Relays
RRTD 2 - RTD #1 High Alarm
Level
RRTD 2 - RTD #1 Alarm
RRTD 2 - RTD #1 Alarm Relays
RRTD 2 - RTD #1 Alarm Level
Record RRTD 2 - RTD #1 Alarms
as Events
RRTD 2 - RTD #1 Trip
Enable RRTD 2 - RTD #1 Trip
Voting
RRTD 2 - RTD #1 Trip Relays
RRTD 2 - RTD #1 Trip Level
RRTD 2 - RTD #1 RTD Type
First Character of RRTD 2 - RTD
#1 Name

8th Character of RRTD 2 - RTD


#1 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 2 - RTD #2 Application


RRTD 2 - RTD #2 High Alarm
RRTD 2 - RTD #2 High Alarm
Relays
RRTD 2 - RTD #2 High Alarm
Level
RRTD 2 - RTD #2 Alarm
RRTD 2 - RTD #2 Alarm Relays
RRTD 2 - RTD #2 Alarm Level
Record RRTD 2 - RTD #2 Alarms
as Events
RRTD 2 - RTD #2 Trip
Enable A Remote RTD #2 Trip
Voting
RRTD 2 - RTD #2 Trip Relays

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

F111

RRTD 2 RTD #2

2220
2221
2222
2223
2224
2225
2226
2227
2228
2229
222A

CG98

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 46 of 77)


ADDR
(hex)

222B
222C
2230

2233
...

DESCRIPTION

RRTD 2 - RTD #2 Trip Level


RRTD 2 - RTD #2 RTD Type
First Character of RRTD 2 - RTD
#2 Name

8th Character of RRTD 2 - RTD


#2 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
0

200
3

1
1

C
-

F1
F120

130
0

32

127

F1

32

127

F1

""

RRTD 2 RTD #3

2240
2241
2242
2243
2244
2245
2246
2247
2248
2249
224A
224B
224C
2250

2253
...

RRTD 2 - RTD #3 Application


RRTD 2 - RTD #3 High Alarm
RRTD 2 - RTD #3 High Alarm
Relays
RRTD 2 - RTD #3 High Alarm
Level
RRTD 2 - RTD #3 Alarm
RRTD 2 - RTD #3 Alarm Relays
RRTD 2 - RTD #3 Alarm Level
Record RRTD 2 - RTD #3 Alarms
as Events
RRTD 2 - RTD #3 Trip
Enable RRTD 2 - RTD #3 Trip
Voting
RRTD 2 - RTD #3 Trip Relays
RRTD 2 - RTD #3 Trip Level
RRTD 2 - RTD #3 RTD Type
First Character of RRTD 2 - RTD #
Name

8th Character of RRTD 2 - RTD


#3 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 2 - RTD #4 Application


RRTD 2 - RTD #4 High Alarm
RRTD 2 - RTD #4 High Alarm
Relays
RRTD 2 - RTD #4 High Alarm
Level
RRTD 2 - RTD #4 Alarm
RRTD 2 - RTD #4 Alarm Relays
RRTD 2 - RTD #4 Alarm Level
Record RRTD 2 - RTD #4 Alarms
as Events
RRTD 2 - RTD #4 Trip
Enable RRTD 2 - RTD #4 Trip
Voting
RRTD 2 - RTD #4 Trip Relays
RRTD 2 - RTD #4 Trip Level
RRTD 2 - RTD #4 RTD Type
First Character of RRTD 2 - RTD
#4 Name

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

RRTD 2 RTD #4

2260
2261
2262
2263
2264
2265
2266
2267
2268
2069
226A
226B
226C
2270

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG99

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 47 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

8th Character of RRTD 2 - RTD


#4 Name
Reserved

32

RRTD 2 - RTD #5 Application


RRTD 2 - RTD #5 High Alarm
RRTD 2 - RTD #5 High Alarm
Relays
RRTD 2 - RTD #5 High Alarm
Level
RRTD 2 - RTD #5 Alarm
RRTD 2 - RTD #5 Alarm Relays
RRTD 2 - RTD #5 Alarm Level
Record RRTD 2 - RTD #5 Alarms
as Events
RRTD 2 - RTD #5 Trip
Enable RRTD 2 - RTD #5 Trip
Voting
RRTD 2 - RTD #5 Trip Relays
RRTD 2 - RTD #5 Trip Level
RRTD 2 - RTD #5 RTD Type
First Character of RRTD 2 - RTD
#5 Name

8th Character of RRTD 2 - RTD


#5 Name
Reserved

0
0

0
0

...

RRTD 2 - RTD #6 Application


RRTD 2 - RTD #6 High Alarm
RRTD 2 - RTD #6 High Alarm
Relays
RRTD 2 - RTD #6 High Alarm
Level
RRTD 2 - RTD #6 Alarm
RRTD 2 - RTD #6 Alarm Relays
RRTD 2 - RTD #6 Alarm Level
Record RRTD 2 - RTD #6 Alarms
as Events
RRTD 2 - RTD #6 Trip
Enable RRTD 2 - RTD #6 Trip
Voting
RRTD 2 - RTD #6 Trip Relays
RRTD 2 - RTD #6 Trip Level
RRTD 2 - RTD #6 RTD Type
First Character of RRTD 2 - RTD
#6 Name

8th Character of RRTD 2 - RTD


#6 Name
Reserved

22C0
22C1

RRTD 2 - RTD #7 Application


RRTD 2 - RTD #7 High Alarm

2273
...

MAX.

127

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F1

""

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

1
1

F121
F115

0
0

RRTD 2 RTD #5

2280
2281
2282
2283
2284
2285
2286
2287
2288
2289
228A
228B
228C
2290

2293
...

RRTD 2 RTD #6

22A0
22A1
22A2
22A3
22A4
22A5
22A6
22A7
22A8
22A9
22AA
22AB
22AC
22B0

22B3

RRTD 2 RTD #7

CG100

0
0

4
2

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 48 of 77)


ADDR
(hex)

22C2
22C3
22C4
22C5
22C6
22C7
22C8
22C9
22CA
22CB
22CC
22D0

22D3
...

DESCRIPTION

RRTD 2 - RTD #7 High Alarm


Relays
RRTD 2 - RTD #7 High Alarm
Level
RRTD 2 - RTD #7 Alarm
RRTD 2 - RTD #7 Alarm Relays
RRTD 2 - RTD #7 Alarm Level
Record RRTD 2 - RTD #7 Alarms
as Events
RRTD 2 - RTD #7 Trip
Enable RRTD 2 - RTD #7 Trip
Voting
RRTD 2 - RTD #7 Trip Relays
RRTD 2 - RTD #7 Trip Level
RRTD 2 - RTD #7 RTD Type
First Character of RRTD 2 - RTD
#7 Name

8th Character of RRTD 2 - RTD


#7 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

RRTD 2 RTD #8

22E0
22E1
22E2
22E3
22E4
22E5
22E6
22E7
22E8
22E9
22EA
22EB
22EC
22F0

22F3
...

RRTD 2 - RTD #8 Application


RRTD 2 - RTD #8 High Alarm
RRTD 2 - RTD #8 High Alarm
Relays
RRTD 2 - RTD #8 High Alarm
Level
RRTD 2 - RTD #8 Alarm
RRTD 2 - RTD #8 Alarm Relays
RRTD 2 - RTD #8 Alarm Level
Record RRTD 2 - RTD #8 Alarms
as Events
RRTD 2 - RTD #8 Trip
Enable RRTD 2 - RTD #8 Trip
Voting
RRTD 2 - RTD #8 Trip Relays
RRTD 2 - RTD #8 Trip Level
RRTD 2 - RTD #8 RTD Type
First Character of RRTD 2 - RTD
#8 Name

8th Character of RRTD 2 - RTD


#8 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

RRTD 2 RTD #9

2300
2301
2302
2303
2304
2305

RRTD 2 - RTD #9 Application


RRTD 2 - RTD #9 High Alarm
RRTD 2 - RTD #9 High Alarm
Relays
RRTD 2 - RTD #9 High Alarm
Level
RRTD 2 - RTD #9 Alarm
RRTD 2 - RTD #9 Alarm Relays

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0

2
7

1
1

F115
F113

0
1

CG101

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 49 of 77)


ADDR
(hex)

2306
2307
2308
2309
230A
230B
230C
2310

2313
...

DESCRIPTION

RRTD 2 - RTD #9 Alarm Level


Record RRTD 2 - RTD #9 Alarms
as Events
RRTD 2 - RTD #9 Trip
Enable RRTD 2 - RTD #9 Trip
Voting
RRTD 2 - RTD #9 Trip Relays
RRTD 2 - RTD #9 Trip Level
RRTD 2 - RTD #9 RTD Type
First Character of RRTD 2 - RTD
#9 Name

8th Character of RRTD 2 - RTD


#9 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

200

F1

130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 2 RTD #10

2320
2321
2322
2323
2324
2325
2326
2327
2328
2329
232A
232B
232C
2330

2333
...

RRTD 2 - RTD #10 Application


RRTD 2 - RTD #10 High Alarm
RRTD 2 - RTD #10 High Alarm
Relays
RRTD 2 - RTD #10 High Alarm
Level
RRTD 2 - RTD #10 Alarm
RRTD 2 - RTD #10 Alarm Relays
RRTD 2 - RTD #10 Alarm Level
Record RRTD 2 - RTD #10 Alarms
as Events
RRTD 2 - RTD #10 Trip
Enable RRTD 2 - RTD#10 Trip
Voting
RRTD 2 - RTD #10 Trip Relays
RRTD 2 - RTD #10 Trip Level
RRTD 2 - RTD #10 RTD Type
First Character of RRTD 2 - RTD
#10 Name

8th Character of RRTD 2 - RTD


#10 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 2 - RTD #11 Application


RRTD 2 - RTD #11 High Alarm
RRTD 2 - RTD #11 High Alarm
Relays
RRTD 2 - RTD #11 High Alarm
Level
RRTD 2 - RTD #11 Alarm
RRTD 2 - RTD #11 Alarm Relays
RRTD 2 - RTD #11 Alarm Level
Record RRTD 2 - RTD #11 Alarms
as Events
RRTD 2 - RTD #11 Trip
Enable RRTD 2 - RTD #11 Trip
Voting

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

RRTD 2 RTD #11

2340
2341
2342
2343
2344
2345
2346
2347
2348
2349

CG102

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 50 of 77)


ADDR
(hex)

234A
234B
234C

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

RRTD 2 - RTD #11 Trip Relays


RRTD 2 - RTD #11 Trip Level
RRTD 2 - RTD #11 RTD Type
First Character of RRTD 2 - RTD
#11 Name

8th Character of RRTD 2 - RTD


#11 Name
Reserved

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

...

RRTD 2 - RTD #12 Application


RRTD 2 - RTD #12 High Alarm
RRTD 2 - RTD #12 High Alarm
Relays
RRTD 2 - RTD #12 High Alarm
Level
RRTD 2 - RTD #12 Alarm
RRTD 2 - RTD #12 Alarm Relays
RRTD 2 - RTD #12 Alarm Level
Record RRTD 2 - RTD #12 Alarms
as Events
RRTD 2 - RTD #12 Trip
Enable RRTD 2 - RTD #12 Trip
Voting
RRTD 2 - RTD #12 Trip Relays
RRTD 2 - RTD #12 Trip Level
RRTD 2 - RTD #12 RTD Type
First Character of RRTD 2 - RTD
#12 Name

8th Character of RRTD 2 - RTD


#12 Name
Reserved

2380
2381
2382

RRTD B - Open RTD Alarm


0
RRTD B - Assign Alarm Relays
0
RRTD B - Open RTD Alarm Events 0

F115
F113
F103

0
1
0

2383

RRTD B - Short / Low Temp RTD


Alarm
RRTD B - Assign Alarm Relays
RRTD B - Short / Low Temp
Alarm Events
Reserved

2350

2353
...

RRTD 2 RTD #12

2360
2361
2362
2363
2364
2365
2366
2367
2368
2369
236A
236B
236C
2370

2373

RRTD 2 OPEN RTD ALARM

2
7
1

1
1
1

RRTD 2 SHORT/LOW TEMPERATURE RTD ALARM

2384
2385
...

F115

F113

F103

RRTD 3 RTD #1

2400
2401
2402
2403
2404
2405
2406

RRTD 3 - RTD #1 Application


RRTD 3 - RTD #1 High Alarm
RRTD 3 - RTD #1 High Alarm
Relays
RRTD 3 - RTD #1 High Alarm
Level
RRTD 3 - RTD #1 Alarm
RRTD 3 - RTD #1 Alarm Relays
RRTD 3 - RTD #1 Alarm Level

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

CG103

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 51 of 77)


ADDR
(hex)

2407
2408
2409
240A
240B
240C
2410

2413
2414

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Record RRTD 3 - RTD #1 Alarms


as Events
RRTD 3 - RTD #1 Trip
Enable RRTD 3 - RTD #1 Trip
Voting
RRTD 3 - RTD #1 Trip Relays
RRTD 3 - RTD #1 Trip Level
RRTD 3 - RTD #1 RTD Type
First Character of RRTD 3 - RTD
#1 Name

8th Character of RRTD 3 - RTD


#1 Name
Reserved

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 - RTD #2 Application


RRTD 3 - RTD #2 High Alarm
RRTD 3 - RTD #2 High Alarm
Relays
RRTD 3 - RTD #2 High Alarm
Level
RRTD 3 - RTD #2 Alarm
RRTD 3 - RTD #2 Alarm Relays
RRTD 3 - RTD #2 Alarm Level
Record RRTD 3 - RTD #2 Alarms
as Events
RRTD 3 - RTD #2 Trip
Enable RRTD 3 - RTD #2 Trip
Voting
RRTD 3 - RTD #2 Trip Relays
RRTD 3 - RTD #2 Trip Level
RRTD 3 - RTD #2 RTD Type
First Character of RRTD 3 - RTD
#2 Name

8th Character of RRTD 3 - RTD


#2 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 - RTD #3 Application


RRTD 3 - RTD #3 High Alarm
RRTD 3 - RTD #3 High Alarm
Relays
RRTD 3 - RTD #3 High Alarm
Level
RRTD 3 - RTD #3 Alarm
RRTD 3 - RTD #3 Alarm Relays
RRTD 3 - RTD #3 Alarm Level
Record RRTD 3 - RTD #3 Alarms
as Events
RRTD 3 - RTD #3 Trip
Enable RRTD 3 - RTD #3 Trip
Voting
RRTD 3 - RTD #3 Trip Relays

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

F111

RRTD 3 RTD #2

2420
2421
2422
2423
2424
2425
2426
2427
2428
2429
242A
242B
242C
2430

2433
...

RRTD 3 RTD #3

2440
2441
2442
2443
2444
2445
2446
2447
2448
2449
244A

CG104

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 52 of 77)


ADDR
(hex)

244B
244C
2450

2453
...

DESCRIPTION

RRTD 3 - RTD #3 Trip Level


RRTD 3 - RTD #3 RTD Type
First Character of RRTD 3 - RTD #
Name

8th Character of RRTD 3 - RTD


#3 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
0

200
3

1
1

C
-

F1
F120

130
0

32

127

F1

32

127

F1

""

RRTD 3 RTD #4

2460
2461
2462
2463
2464
2465
2466
2467
2468
2469
246A
246B
246C
2470

2473
...

RRTD 3 - RTD #4 Application


RRTD 3 - RTD #4 High Alarm
RRTD 3 - RTD #4 High Alarm
Relays
RRTD 3 - RTD #4 High Alarm
Level
RRTD 3 - RTD #4 Alarm
RRTD 3 - RTD #4 Alarm Relays
RRTD 3 - RTD #4 Alarm Level
Record RRTD 3 - RTD #4 Alarms
as Events
RRTD 3 - RTD #4 Trip
Enable RRTD 3 - RTD #4 Trip
Voting
RRTD 3 - RTD #4 Trip Relays
RRTD 3 - RTD #4 Trip Level
RRTD 3 - RTD #4 RTD Type
First Character of RRTD 3 - RTD
#4 Name

8th Character of RRTD 3 - RTD


#4 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 - RTD #5 Application


RRTD 3 - RTD #5 High Alarm
RRTD 3 - RTD #5 High Alarm
Relays
RRTD 3 - RTD #5 High Alarm
Level
RRTD 3 - RTD #5 Alarm
RRTD 3 - RTD #5 Alarm Relays
RRTD 3 - RTD #5 Alarm Level
Record RRTD 3 - RTD #5 Alarms
as Events
RRTD 3 - RTD #5 Trip
Enable RRTD 3 - RTD #5 Trip
Voting
RRTD 3 - RTD #5 Trip Relays
RRTD 3 - RTD #5 Trip Level
RRTD 3 - RTD #5 RTD Type
First Character of RRTD 3 - RTD
#5 Name

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

RRTD 3 RTD #5

2480
2481
2482
2483
2484
2485
2486
2487
2488
2489
248A
248B
248C
2490

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG105

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 53 of 77)


ADDR
(hex)

2493
...

DESCRIPTION

MIN.

8th Character of RRTD 3 - RTD


#5 Name
Reserved

32

RRTD 3 - RTD #6 Application


RRTD 3 - RTD #6 High Alarm
RRTD 3 - RTD #6 High Alarm
Relays
RRTD 3 - RTD #6 High Alarm
Level
RRTD 3 - RTD #6 Alarm
RRTD 3 - RTD #6 Alarm Relays
RRTD 3 - RTD #6 Alarm Level
Record RRTD 3 - RTD #6 Alarms
as Events
RRTD 3 - RTD #6 Trip
Enable RRTD 3 - RTD #6 Trip
Voting
RRTD 3 - RTD #6 Trip Relays
RRTD 3 - RTD #6 Trip Level
RRTD 3 - RTD #6 RTD Type
First Character of RRTD 3 - RTD
#6 Name

8th Character of RRTD 3 - RTD


#6 Name
Reserved

0
0

MAX.

127

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F1

""

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 RTD #6

24A0
24A1
24A2
24A3
24A4
24A5
24A6
24A7
24A8
24A9
24AA
24AB
24AC
24B0

24B3
...

RRTD 3 RTD #7

24C0
24C1

...

RRTD 3 - RTD #7 Application


RRTD 3 - RTD #7 High Alarm
RRTD 3 - RTD #7 High Alarm
Relays
RRTD 3 - RTD #7 High Alarm
Level
RRTD 3 - RTD #7 Alarm
RRTD 3 - RTD #7 Alarm Relays
RRTD 3 - RTD #7 Alarm Level
Record RRTD 3 - RTD #7 Alarms
as Events
RRTD 3 - RTD #7 Trip
Enable RRTD 3 - RTD #7 Trip
Voting
RRTD 3 - RTD #7 Trip Relays
RRTD 3 - RTD #7 Trip Level
RRTD 3 - RTD #7 RTD Type
First Character of RRTD 3 - RTD
#7 Name

8th Character of RRTD 3 - RTD


#7 Name
Reserved

24E0
24E1

RRTD 3 - RTD #8 Application


RRTD 3 - RTD #8 High Alarm

24C2
24C3
24C4
24C5
24C6
24C7
24C8
24C9
24CA
24CB
24CC
24D0

24D3

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

1
1

F121
F115

0
0

RRTD 3 RTD #8

CG106

0
0

4
2

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 54 of 77)


ADDR
(hex)

24E2
24E3
24E4
24E5
24E6
24E7
24E8
24E9
24EA
24EB
24EC
24F0

24F3
...

DESCRIPTION

RRTD 3 - RTD #8 High Alarm


Relays
RRTD 3 - RTD #8 High Alarm
Level
RRTD 3 - RTD #8 Alarm
RRTD 3 - RTD #8 Alarm Relays
RRTD 3 - RTD #8 Alarm Level
Record RRTD 3 - RTD #8 Alarms
as Events
RRTD 3 - RTD #8 Trip
Enable RRTD 3 - RTD #8 Trip
Voting
RRTD 3 - RTD #8 Trip Relays
RRTD 3 - RTD #8 Trip Level
RRTD 3 - RTD #8 RTD Type
First Character of RRTD 3 - RTD
#8 Name

8th Character of RRTD 3 - RTD


#8 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 RTD #9

2500
2501
2502
2503
2504
2505
2506
2507
2508
2509
250A
250B
250C
2510

2513
...

RRTD 3 - RTD #9 Application


RRTD 3 - RTD #9 High Alarm
RRTD 3 - RTD #9 High Alarm
Relays
RRTD 3 - RTD #9 High Alarm
Level
RRTD 3 - RTD #9 Alarm
RRTD 3 - RTD #9 Alarm Relays
RRTD 3 - RTD #9 Alarm Level
Record RRTD 3 - RTD #9 Alarms
as Events
RRTD 3 - RTD #9 Trip
Enable RRTD 3 - RTD #9 Trip
Voting
RRTD 3 - RTD #9 Trip Relays
RRTD 3 - RTD #9 Trip Level
RRTD 3 - RTD #9 RTD Type
First Character of RRTD 3 - RTD
#9 Name

8th Character of RRTD 3 - RTD


#9 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 - RTD #10 Application


RRTD 3 - RTD #10 High Alarm
RRTD 3 - RTD #10 High Alarm
Relays
RRTD 3 - RTD #10 High Alarm
Level
RRTD 3 - RTD #10 Alarm
RRTD 3 - RTD #10 Alarm Relays

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0

2
7

1
1

F115
F113

0
1

RRTD 3 RTD #10

2520
2521
2522
2523
2524
2525

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG107

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 55 of 77)


ADDR
(hex)

2526
2527
2528
2529
252A
252B
252C
2530

2533
...

DESCRIPTION

RRTD 3 - RTD #10 Alarm Level


Record RRTD 3 - RTD #10 Alarms
as Events
RRTD 3 - RTD #10 Trip
Enable RRTD 3 - RTD#10 Trip
Voting
RRTD 3 - RTD #10 Trip Relays
RRTD 3 - RTD #10 Trip Level
RRTD 3 - RTD #10 RTD Type
First Character of RRTD 3 - RTD
#10 Name

8th Character of RRTD 3 - RTD


#10 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

200

F1

130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 RTD #11

2540
2541
2542
2543
2544
2545
2546
2547
2548
2549
254A
254B
254C
2550

2553
...

RRTD 3 - RTD #11 Application


RRTD 3 - RTD #11 High Alarm
RRTD 3 - RTD #11 High Alarm
Relays
RRTD 3 - RTD #11 High Alarm
Level
RRTD 3 - RTD #11 Alarm
RRTD 3 - RTD #11 Alarm Relays
RRTD 3 - RTD #11 Alarm Level
Record RRTD 3 - RTD #11 Alarms
as Events
RRTD 3 - RTD #11 Trip
Enable RRTD 3 - RTD #11 Trip
Voting
RRTD 3 - RTD #11 Trip Relays
RRTD 3 - RTD #11 Trip Level
RRTD 3 - RTD #11 RTD Type
First Character of RRTD 3 - RTD
#11 Name

8th Character of RRTD 3 - RTD


#11 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 3 - RTD #12 Application


RRTD 3 - RTD #12 High Alarm
RRTD 3 - RTD #12 High Alarm
Relays
RRTD 3 - RTD #12 High Alarm
Level
RRTD 3 - RTD #12 Alarm
RRTD 3 - RTD #12 Alarm Relays
RRTD 3 - RTD #12 Alarm Level
Record RRTD 3 - RTD #12 Alarms
as Events
RRTD 3 - RTD #12 Trip
Enable RRTD 3 - RTD #12 Trip
Voting

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

RRTD 3 RTD #12

2560
2561
2562
2563
2564
2565
2566
2567
2568
2569

CG108

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 56 of 77)


ADDR
(hex)

256A
256B
256C

DESCRIPTION

MIN.

...

RRTD 3 - RTD #12 Trip Relays


RRTD 3 - RTD #12 Trip Level
RRTD 3 - RTD #12 RTD Type
First Character of RRTD 3 - RTD
#12 Name

8th Character of RRTD 3 - RTD


#12 Name
Reserved

2580
2581
2582

RRTD 3 - Open RTD Alarm


0
RRTD 3 - Assign Alarm Relays
0
RRTD 3 - Open RTD Alarm Events 0

2583

RRTD 3 - Short / Low Temp RTD


Alarm
RRTD 3 - Assign Alarm Relays
RRTD 3 - Short / Low Temp
Alarm Events
Reserved

2570

2573

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

F115
F113
F103

0
1
0

RRTD 3 OPEN RTD ALARM

2
7
1

1
1
1

RRTD 3 SHORT/LOW TEMPERATURE RTD ALARM

2584
2585
...

F115

F113

F103

RRTD 4 RTD #1

2600
2601
2602
2603
2604
2605
2606
2607
2608
2609
260A
260B
260C
2610

2613
....

RRTD 4 - RTD #1 Application


RRTD 4 - RTD #1 High Alarm
RRTD 4 - RTD #1 High Alarm
Relays
RRTD 4 - RTD #1 High Alarm
Level
RRTD 4 - RTD #1 Alarm
RRTD 4 - RTD #1 Alarm Relays
RRTD 4 - RTD #1 Alarm Level
Record RRTD 4 - RTD #1 Alarms
as Events
RRTD 4 - RTD #1 Trip
Enable RRTD 4 - RTD #1 Trip
Voting
RRTD 4 - RTD #1 Trip Relays
RRTD 4 - RTD #1 Trip Level
RRTD 4 - RTD #1 RTD Type
First Character of RRTD 4 - RTD
#1 Name

8th Character of RRTD 4 - RTD


#1 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 - RTD #2 Application


RRTD 4 - RTD #2 High Alarm
RRTD 4 - RTD #2 High Alarm
Relays
RRTD 4 - RTD #2 High Alarm
Level
RRTD 4 - RTD #2 Alarm
RRTD 4 - RTD #2 Alarm Relays
RRTD 4 - RTD #2 Alarm Level

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

RRTD 4 RTD #2

2620
2621
2622
2623
2624
2625
2626

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG109

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 57 of 77)


ADDR
(hex)

2627
2628
2629
262A
262B
262C
2630

2633
...

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

Record RRTD 4 - RTD #2 Alarms


as Events
RRTD 4 - RTD #2 Trip
Enable A Remote RTD #2 Trip
Voting
RRTD 4 - RTD #2 Trip Relays
RRTD 4 - RTD #2 Trip Level
RRTD 4 - RTD #2 RTD Type
First Character of RRTD 4 - RTD
#2 Name

8th Character of RRTD 4 - RTD


#2 Name
Reserved

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 - RTD #3 Application


RRTD 4 - RTD #3 High Alarm
RRTD 4 - RTD #3 High Alarm
Relays
RRTD 4 - RTD #3 High Alarm
Level
RRTD 4 - RTD #3 Alarm
RRTD 4 - RTD #3 Alarm Relays
RRTD 4 - RTD #3 Alarm Level
Record RRTD 4 - RTD #3 Alarms
as Events
RRTD 4 - RTD #3 Trip
Enable RRTD 4 - RTD #3 Trip
Voting
RRTD 4 - RTD #3 Trip Relays
RRTD 4 - RTD #3 Trip Level
RRTD 4 - RTD #3 RTD Type
First Character of RRTD 4 - RTD #
Name

8th Character of RRTD 4 - RTD


#3 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 - RTD #4 Application


RRTD 4 - RTD #4 High Alarm
RRTD 4 - RTD #4 High Alarm
Relays
RRTD 4 - RTD #4 High Alarm
Level
RRTD 4 - RTD #4 Alarm
RRTD 4 - RTD #4 Alarm Relays
RRTD 4 - RTD #4 Alarm Level
Record RRTD 4 - RTD #4 Alarms
as Events
RRTD 4 - RTD #4 Trip
Enable RRTD 4 - RTD #4 Trip
Voting
RRTD 4 - RTD #4 Trip Relays

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

F111

RRTD 4 RTD #3

2640
2641
2642
2643
2644
2645
2646
2647
2648
2649
264A
264B
264C
2650

2653
...

RRTD 4 RTD #4

2660
2661
2662
2663
2664
2665
2666
2667
2668
2669
266A

CG110

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 58 of 77)


ADDR
(hex)

266B
266C
2670

2673
...

DESCRIPTION

RRTD 4 - RTD #4 Trip Level


RRTD 4 - RTD #4 RTD Type
First Character of RRTD 4 - RTD
#4 Name

8th Character of RRTD 4 - RTD


#4 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
0

200
3

1
1

C
-

F1
F120

130
0

32

127

F1

32

127

F1

""

RRTD 4 RTD #5

2680
2681
2682
2683
2684
2685
2686
2687
2688
2689
268A
268B
268C
2690

2693
...

RRTD 4 - RTD #5 Application


RRTD 4 - RTD #5 High Alarm
RRTD 4 - RTD #5 High Alarm
Relays
RRTD 4 - RTD #5 High Alarm
Level
RRTD 4 - RTD #5 Alarm
RRTD 4 - RTD #5 Alarm Relays
RRTD 4 - RTD #5 Alarm Level
Record RRTD 4 - RTD #5 Alarms
as Events
RRTD 4 - RTD #5 Trip
Enable RRTD 4 - RTD #5 Trip
Voting
RRTD 4 - RTD #5 Trip Relays
RRTD 4 - RTD #5 Trip Level
RRTD 4 - RTD #5 RTD Type
First Character of RRTD 4 - RTD
#5 Name

8th Character of RRTD 4 - RTD


#5 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 - RTD #6 Application


RRTD 4 - RTD #6 High Alarm
RRTD 4 - RTD #6 High Alarm
Relays
RRTD 4 - RTD #6 High Alarm
Level
RRTD 4 - RTD #6 Alarm
RRTD 4 - RTD #6 Alarm Relays
RRTD 4 - RTD #6 Alarm Level
Record RRTD 4 - RTD #6 Alarms
as Events
RRTD 4 - RTD #6 Trip
Enable RRTD 4 - RTD #6 Trip
Voting
RRTD 4 - RTD #6 Trip Relays
RRTD 4 - RTD #6 Trip Level
RRTD 4 - RTD #6 RTD Type
First Character of RRTD 4 - RTD
#6 Name

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

RRTD 4 RTD #6

26A0
26A1
26A2
26A3
26A4
26A5
26A6
26A7
26A8
26A9
26AA
26AB
26AC
26B0

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG111

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 59 of 77)


ADDR
(hex)

26B3
...

DESCRIPTION

MIN.

8th Character of RRTD 4 - RTD


#6 Name
Reserved

32

RRTD 4 - RTD #7 Application


RRTD 4 - RTD #7 High Alarm
RRTD 4 - RTD #7 High Alarm
Relays
RRTD 4 - RTD #7 High Alarm
Level
RRTD 4 - RTD #7 Alarm
RRTD 4 - RTD #7 Alarm Relays
RRTD 4 - RTD #7 Alarm Level
Record RRTD 4 - RTD #7 Alarms
as Events
RRTD 4 - RTD #7 Trip
Enable RRTD 4 - RTD #7 Trip
Voting
RRTD 4 - RTD #7 Trip Relays
RRTD 4 - RTD #7 Trip Level
RRTD 4 - RTD #7 RTD Type
First Character of RRTD 4 - RTD
#7 Name

8th Character of RRTD 4 - RTD


#7 Name
Reserved

0
0

MAX.

127

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F1

""

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 RTD #7

26C0
26C1
26C2
26C3
26C4
26C5
26C6
26C7
26C8
26C9
26CA
26CB
26CC
26D0

26D3
...

RRTD 4 RTD #8

26E0
26E1

...

RRTD 4 - RTD #8 Application


RRTD 4 - RTD #8 High Alarm
RRTD 4 - RTD #8 High Alarm
Relays
RRTD 4 - RTD #8 High Alarm
Level
RRTD 4 - RTD #8 Alarm
RRTD 4 - RTD #8 Alarm Relays
RRTD 4 - RTD #8 Alarm Level
Record RRTD 4 - RTD #8 Alarms
as Events
RRTD 4 - RTD #8 Trip
Enable RRTD 4 - RTD #8 Trip
Voting
RRTD 4 - RTD #8 Trip Relays
RRTD 4 - RTD #8 Trip Level
RRTD 4 - RTD #8 RTD Type
First Character of RRTD 4 - RTD
#8 Name

8th Character of RRTD 4 - RTD


#8 Name
Reserved

2700
2701

RRTD 4 - RTD #9 Application


RRTD 4 - RTD #9 High Alarm

26E2
26E3
26E4
26E5
26E6
26E7
26E8
26E9
26EA
26EB
26EC
26F0

26F3

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

1
1

F121
F115

0
0

RRTD 4 RTD #9

CG112

0
0

4
2

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 60 of 77)


ADDR
(hex)

2702
2703
2704
2705
2706
2707
2708
2709
270A
270B
270C
2710

2713
...

DESCRIPTION

RRTD 4 - RTD #9 High Alarm


Relays
RRTD 4 - RTD #9 High Alarm
Level
RRTD 4 - RTD #9 Alarm
RRTD 4 - RTD #9 Alarm Relays
RRTD 4 - RTD #9 Alarm Level
Record RRTD 4 - RTD #9 Alarms
as Events
RRTD 4 - RTD #9 Trip
Enable RRTD 4 - RTD #9 Trip
Voting
RRTD 4 - RTD #9 Trip Relays
RRTD 4 - RTD #9 Trip Level
RRTD 4 - RTD #9 RTD Type
First Character of RRTD 4 - RTD
#9 Name

8th Character of RRTD 4 - RTD


#9 Name
Reserved

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 RTD #10

2720
2721
2722
2723
2724
2725
2726
2727
2728
2729
272A
272B
272C
2730

2733
...

RRTD 4 - RTD #10 Application


RRTD 4 - RTD #10 High Alarm
RRTD 4 - RTD #10 High Alarm
Relays
RRTD 4 - RTD #10 High Alarm
Level
RRTD 4 - RTD #10 Alarm
RRTD 4 - RTD #10 Alarm Relays
RRTD 4 - RTD #10 Alarm Level
Record RRTD 4 - RTD #10 Alarms
as Events
RRTD 4 - RTD #10 Trip
Enable RRTD 4 - RTD#10 Trip
Voting
RRTD 4 - RTD #10 Trip Relays
RRTD 4 - RTD #10 Trip Level
RRTD 4 - RTD #10 RTD Type
First Character of RRTD 4 - RTD
#10 Name

8th Character of RRTD 4 - RTD


#10 Name
Reserved

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 - RTD #11 Application


RRTD 4 - RTD #11 High Alarm
RRTD 4 - RTD #11 High Alarm
Relays
RRTD 4 - RTD #11 High Alarm
Level
RRTD 4 - RTD #11 Alarm
RRTD 4 - RTD #11 Alarm Relays

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0

2
7

1
1

F115
F113

0
1

RRTD 4 RTD #11

2740
2741
2742
2743
2744
2745

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG113

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 61 of 77)


ADDR
(hex)

2746
2747
2748
2749
274A
274B
274C
2750

2753
...

DESCRIPTION

MIN.

RRTD 4 - RTD #11 Alarm Level


Record RRTD 4 - RTD #11 Alarms
as Events
RRTD 4 - RTD #11 Trip
Enable RRTD 4 - RTD #11 Trip
Voting
RRTD 4 - RTD #11 Trip Relays
RRTD 4 - RTD #11 Trip Level
RRTD 4 - RTD #11 RTD Type
First Character of RRTD 4 - RTD
#11 Name

8th Character of RRTD 4 - RTD


#11 Name
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

200

F1

130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

RRTD 4 RTD #12

2760
2761

...

RRTD 4 - RTD #12 Application


RRTD 4 - RTD #12 High Alarm
RRTD 4 - RTD #12 High Alarm
Relays
RRTD 4 - RTD #12 High Alarm
Level
RRTD 4 - RTD #12 Alarm
RRTD 4 - RTD #12 Alarm Relays
RRTD 4 - RTD #12 Alarm Level
Record RRTD 4 - RTD #12 Alarms
as Events
RRTD 4 - RTD #12 Trip
Enable RRTD 4 - RTD #12 Trip
Voting
RRTD 4 - RTD #12 Trip Relays
RRTD 4 - RTD #12 Trip Level
RRTD 4 - RTD #12 RTD Type
First Character of RRTD 4 - RTD
#12 Name

8th Character of RRTD 4 - RTD


#12 Name
Reserved

2780
2781
2782

RRTD 4- Open RTD Alarm


0
RRTD 4 - Assign Alarm Relays
0
RRTD 4 - Open RTD Alarm Events 0

2783

RRTD 4 - Short / Low Temp RTD


Alarm
RRTD 4 - Assign Alarm Relays
RRTD 4 - Short / Low Temp
Alarm Events
Reserved

2762
2763
2764
2765
2766
2767
2768
2769
276A
276B
276C
2770

2773

0
0

4
2

1
1

F121
F115

0
0

F113

200

F1

130

0
0
1

2
7
200

1
1
1

F115
F113
F1

0
1
130

F103

F115

13

F122

0
1
0

7
200
3

1
1
1

C
-

F111
F1
F120

1
130
0

32

127

F1

32

127

F1

""

F115
F113
F103

0
1
0

RRTD 4 OPEN RTD ALARM

2
7
1

1
1
1

RRTD 4 SHORT/LOW TEMPERATURE RTD ALARM

2784
2785
...

F115

F113

F103

F117
F117
F117

0
0
0

RRTD 1 OUTPUT RELAY SETUP

27A0
27A1
27A2

CG114

Trip Relay Reset Mode


Alarm Relay Reset Mode
Aux 1 Relay Reset Mode

0
0
0

2
2
2

1
1
1

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 62 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

27A3
27A4
27A5
27A6
27A7
...

Aux 2 Relay Reset Mode


Trip Relay Operation
Alarm Relay Operation
Aux1 Relay Operation
Aux2 Relay Operation
Reserved

0
0
0
0
0

27B0
27B1
27B2
27B3
27B4
27B5
27B6
27B7
...

Trip Relay Reset Mode


Alarm Relay Reset Mode
Aux 1 Relay Reset Mode
Aux 2 Relay Reset Mode
Trip Relay Operation
Alarm Relay Operation
Aux1 Relay Operation
Aux2 Relay Operation
Reserved

27C0
27C1
27C2
27C3
27C4
27C5
27C6
27C7
...

Trip Relay Reset Mode


Alarm Relay Reset Mode
Aux 1 Relay Reset Mode
Aux 2 Relay Reset Mode
Trip Relay Operation
Alarm Relay Operation
Aux1 Relay Operation
Aux2 Relay Operation
Reserved

27D0
27D1
27D2
27D3
27D4
27D5
27D6
27D7
...

Trip Relay Reset Mode


Alarm Relay Reset Mode
Aux 1 Relay Reset Mode
Aux 2 Relay Reset Mode
Trip Relay Operation
Alarm Relay Operation
Aux1 Relay Operation
Aux2 Relay Operation
Reserved

27E0

Enable Analog Output 1


Assign Analog Output 1 Output
Range
Assign Analog Output 1
Parameter
Analog Output 1 Minimum
Analog Output 1 Maximum
Enable Analog Output 2
Assign Analog Output 2 Output
Range
Assign Analog Output 2
Parameter
Analog Output 2 Minimum
Analog Output 2 Maximum

MAX.

2
1
1
1
1

STEP
VALUE

1
1
1
1
1

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F117
F161
F161
F161
F161

0
0
1
1
0

F117
F117
F117
F117
F161
F161
F161
F161

0
0
0
0
0
1
1
0

F117
F117
F117
F117
F161
F161
F161
F161

0
0
0
0
0
1
1
0

F117
F117
F117
F117
F161
F161
F161
F161

0
0
0
0
0
1
1
0

RRTD 2 OUTPUT RELAY SETUP

0
0
0
0
0
0
0
0

2
2
2
2
1
1
1
1

1
1
1
1
1
1
1
1

RRTD 3 OUTPUT RELAY SETUP

0
0
0
0
0
0
0
0

2
2
2
2
1
1
1
1

1
1
1
1
1
1
1
1

RRTD 4 OUTPUT RELAY SETUP

0
0
0
0
0
0
0
0

2
2
2
2
1
1
1
1

1
1
1
1
1
1
1
1

RRTD 1 ANALOG OUTPUTS

27E1
27E2
27E3
27E4
27E5
27E6
27E7
27E8
27E9

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

F103

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40

200
200

1
1

F4
F4

-40
200

CG115

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 63 of 77)


ADDR
(hex)

27EA
27EB
27EC
27ED
27EE
27EF
27F0
27F1
27F2
27F3
...

DESCRIPTION

MIN.

Enable Analog Output 3


Assign Analog Output 3 Output
Range
Assign Analog Output 3
Parameter
Analog Output 3 Minimum
Analog Output 3 Maximum
Enable Analog Output 4
Assign Analog Output 4 Output
Range
Assign Analog Output 4
Parameter
Analog Output 4 Minimum
Analog Output 4 Maximum
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F103

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40

200
200

1
1

F4
F4

-40
200

RRTD 2 ANALOG OUTPUTS

2800
2801
2802
2803
2804
2805
2806
2807
2808
2809
280A
280B
280C
280D
280E
280F
2810
2811
2812
2813
...

Enable Analog Output 1


Assign Analog Output 1 Output
Range
Assign Analog Output 1
Parameter
Analog Output 1 Minimum
Analog Output 1 Maximum
Enable Analog Output 2
Assign Analog Output 2 Output
Range
Assign Analog Output 2
Parameter
Analog Output 2 Minimum
Analog Output 2 Maximum
Enable Analog Output 3
Assign Analog Output 3 Output
Range
Assign Analog Output 3
Parameter
Analog Output 3 Minimum
Analog Output 3 Maximum
Enable Analog Output 4
Assign Analog Output 4 Output
Range
Assign Analog Output 4
Parameter
Analog Output 4 Minimum
Analog Output 4 Maximum
Reserved

F103

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40

200
200

1
1

F4
F4

-40
200

RRTD 3 ANALOG OUTPUTS

2820
2821
2822
2823
2824
2825

CG116

Enable Analog Output 1


Assign Analog Output 1 Output
Range
Assign Analog Output 1
Parameter
Analog Output 1 Minimum
Analog Output 1 Maximum
Enable Analog Output 2

F103

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 64 of 77)


ADDR
(hex)

2826
2827
2828
2829
282A
282B
282C
282D
282E
282F
2830
2831
2832
2833
...

DESCRIPTION

MIN.

Assign Analog Output 2 Output


Range
Assign Analog Output 2
Parameter
Analog Output 2 Minimum
Analog Output 2 Maximum
Enable Analog Output 3
Assign Analog Output 3 Output
Range
Assign Analog Output 3
Parameter
Analog Output 3 Minimum
Analog Output 3 Maximum
Enable Analog Output 4
Assign Analog Output 4 Output
Range
Assign Analog Output 4
Parameter
Analog Output 4 Minimum
Analog Output 4 Maximum
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40

200
200

1
1

F4
F4

-40
200

RRTD 4 ANALOG OUTPUTS

2840

2852
2853
2854

Enable Analog Output 1


Assign Analog Output 1 Output
Range
Assign Analog Output 1
Parameter
Analog Output 1 Minimum
Analog Output 1 Maximum
Enable Analog Output 2
Assign Analog Output 2 Output
Range
Assign Analog Output 2
Parameter
Analog Output 2 Minimum
Analog Output 2 Maximum
Enable Analog Output 3
Assign Analog Output 3 Output
Range
Assign Analog Output 3
Parameter
Analog Output 3 Minimum
Analog Output 3 Maximum
Enable Analog Output 4
Assign Analog Output 4 Output
Range
Assign Analog Output 4
Parameter
Analog Output 4 Minimum
Analog Output 4 Maximum
Reserved

2860

1st & 2nd Character of Digital


Input 2 Name

2841
2842
2843
2844
2845
2846
2847
2848
2849
284A
284B
284C
284D
284E
284F
2850
2851

F103

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40
0

200
200
1

1
1
1

F4
F4
F103

-40
200
0

F26

12

24

F127

13

-40
-40

200
200

1
1

F4
F4

-40
200

F22

GE

RRTD 1 DIGITAL INPUT 2

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

32

127

CG117

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 65 of 77)


ADDR
(hex)

2865
2870
2871
2872
2873
2874
2875
2876
2877
2878
2879
---

DESCRIPTION

MIN.

11th & 12th Character of Digital


Input 2 Name
Digital Input 2 Type
Reserved
Digital Input 2 Alarm
Digital Input 2 Alarm Relays
Digital Input 2 Alarm Delay
Digital Input 2 Alarm Events
Digital Input 2 Trip
Digital Input 2 Trip Relays
Digital Input 2 Trip Delay
Digital Input 2 Assignable
Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 1 DIGITAL INPUT 5

2880

2885
2890
2891
2892
2893
2894
2895
2896
2897
2898
2899
...

1st & 2nd Character of Digital


Input 5 Name

11th & 12th Character of Digital


Input 5 Name
Digital Input 5 Type
Reserved
Digital Input 5 Alarm
Digital Input 5 Alarm Relays
Digital Input 5 Alarm Delay
Digital Input 5 Alarm Events
Digital Input 5 Trip
Digital Input 5 Trip Relays
Digital Input 5 Trip Delay
Digital Input 5 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 1 DIGITAL INPUT 4

28A0

28A5
28B0
28B1
28B2
28B3
28B4
28B5
28B6
28B7
28B8
28B9
...

CG118

1st & 2nd Character of Digital


Input 4 Name

11th & 12th Character of Digital


Input 4 Name
Digital Input 4 Type
Reserved
Digital Input 4 Alarm
Digital Input 4 Alarm Relays
Digital Input 4 Alarm Delay
Digital Input 4 Alarm Events
Digital Input 4 Trip
Digital Input 4 Trip Relays
Digital Input 4 Trip Delay
Digital Input 4 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 66 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

RRTD 1 DIGITAL INPUT 1

28C0

28C5
28D0
28D1
28D2
28D3
28D4
28D5
28D6
28D7
28D8
28D9
...

1st & 2nd Character of Digital


Input 1 Name

11th & 12th Character of Digital


Input 1 Name
Digital Input 1 Type
Reserved
Digital Input 1 Alarm
Digital Input 1 Alarm Relays
Digital Input 1 Alarm Delay
Digital Input 1 Alarm Events
Digital Input 1 Trip
Digital Input 1 Trip Relays
Digital Input 1 Trip Delay
Digital Input 1 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 1 DIGITAL INPUT 6

28E0

28E5
28F0
28F1
28F2
28F3
28F4
28F5
28F6
28F7
28F8
28F9
...

1st & 2nd Character of Digital


Input 6 Name

11th & 12th Character of Digital


Input 6 Name
Digital Input 6 Type
Reserved
Digital Input 6 Alarm
Digital Input 6 Alarm Relays
Digital Input 6 Alarm Delay
Digital Input 6 Alarm Events
Digital Input 6 Trip
Digital Input 6 Trip Relays
Digital Input 6 Trip Delay
Digital Input 6 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 1 DIGITAL INPUT 3

2900

2905
2910
2911
2912
2913
2914
2915
2916
2917
2918
2919

1st & 2nd Character of Digital


Input 3 Name

11th & 12th Character of Digital


Input 3 Name
Digital Input 3 Type
Reserved
Digital Input 3 Alarm
Digital Input 3 Alarm Relays
Digital Input 3 Alarm Delay
Digital Input 3 Alarm Events
Digital Input 3 Trip
Digital Input 3 Trip Relays
Digital Input 3 Trip Delay
Digital Input 3 Assignable
Function

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

CG119

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 67 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

...

Reserved

2920

1st & 2nd Character of Digital


Input 2 Name

11th & 12th Character of Digital


Input 2 Name
Digital Input 2 Type
Reserved
Digital Input 2 Alarm
Digital Input 2 Alarm Relays
Digital Input 2 Alarm Delay
Digital Input 2 Alarm Events
Digital Input 2 Trip
Digital Input 2 Trip Relays
Digital Input 2 Trip Delay
Digital Input 2 Assignable
Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

RRTD 2 DIGITAL INPUT 2

2925
2930
2931
2932
2933
2934
2935
2936
2937
2938
2939
...

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 2 DIGITAL INPUT 5

2940

2945
2950
2951
2952
2953
2954
2955
2956
2957
2958
2959
...

1st & 2nd Character of Digital


Input 5 Name

11th & 12th Character of Digital


Input 5 Name
Digital Input 5 Type
Reserved
Digital Input 5 Alarm
Digital Input 5 Alarm Relays
Digital Input 5 Alarm Delay
Digital Input 5 Alarm Events
Digital Input 5 Trip
Digital Input 5 Trip Relays
Digital Input 5 Trip Delay
Digital Input 5 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 2 DIGITAL INPUT 4

2960

2965
2970
2971
2972
2973
2974
2975
2976
2977
2978

CG120

1st & 2nd Character of Digital


Input 4 Name

11th & 12th Character of Digital


Input 4 Name
Digital Input 4 Type
Reserved
Digital Input 4 Alarm
Digital Input 4 Alarm Relays
Digital Input 4 Alarm Delay
Digital Input 4 Alarm Events
Digital Input 4 Trip
Digital Input 4 Trip Relays
Digital Input 4 Trip Delay

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 68 of 77)


ADDR
(hex)

2979
...

DESCRIPTION

MIN.

Digital Input 4 Assignable


Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F163

RRTD 2 DIGITAL INPUT 1

2980

2985
2990
2991
2992
2993
2994
2995
2996
2997
2998
2999
...

1st & 2nd Character of Digital


Input 1 Name

11th & 12th Character of Digital


Input 1 Name
Digital Input 1 Type
Reserved
Digital Input 1 Alarm
Digital Input 1 Alarm Relays
Digital Input 1 Alarm Delay
Digital Input 1 Alarm Events
Digital Input 1 Trip
Digital Input 1 Trip Relays
Digital Input 1 Trip Delay
Digital Input 1 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 2 DIGITAL INPUT 6

29A0

29A5
29B0
29B1
29B2
29B3
29B4
29B5
29B6
29B7
29B8
29B9
...

1st & 2nd Character of Digital


Input 6 Name

11th & 12th Character of Digital


Input 6 Name
Digital Input 6 Type
Reserved
Digital Input 6 Alarm
Digital Input 6 Alarm Relays
Digital Input 6 Alarm Delay
Digital Input 6 Alarm Events
Digital Input 6 Trip
Digital Input 6 Trip Relays
Digital Input 6 Trip Delay
Digital Input 6 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 2 DIGITAL INPUT 3

29C0

29C5
29D0
29D1
29D2
29D3
29D4
29D5
29D6
29D7

1st & 2nd Character of Digital


Input 3 Name

11th & 12th Character of Digital


Input 3 Name
Digital Input 3 Type
Reserved
Digital Input 3 Alarm
Digital Input 3 Alarm Relays
Digital Input 3 Alarm Delay
Digital Input 3 Alarm Events
Digital Input 3 Trip
Digital Input 3 Trip Relays

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0

2
6
50000
1
2
6

1
1
1
1
1
1

100ms
-

F115
F113
F2
F103
F115
F111

0
0
50
0
0
0

CG121

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 69 of 77)


ADDR
(hex)

29D8
29D9
...

DESCRIPTION

MIN.

Digital Input 3 Trip Delay


Digital Input 3 Assignable
Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

50000 1

100ms

F2

50

F163

RRTD 3 DIGITAL INPUT 2

29E0

29E5
29F0
29F1
29F2
29F3
29F4
29F5
29F6
29F7
29F8
29F9
...

1st & 2nd Character of Digital


Input 2 Name

11th & 12th Character of Digital


Input 2 Name
Digital Input 2 Type
Reserved
Digital Input 2 Alarm
Digital Input 2 Alarm Relays
Digital Input 2 Alarm Delay
Digital Input 2 Alarm Events
Digital Input 2 Trip
Digital Input 2 Trip Relays
Digital Input 2 Trip Delay
Digital Input 2 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 3 DIGITAL INPUT 5

2A00

2A05
2A10
2A11
2A12
2A13
2A14
2A15
2A16
2A17
2A18
2A19
...

1st & 2nd Character of Digital


Input 5 Name

11th & 12th Character of Digital


Input 5 Name
Digital Input 5 Type
Reserved
Digital Input 5 Alarm
Digital Input 5 Alarm Relays
Digital Input 5 Alarm Delay
Digital Input 5 Alarm Events
Digital Input 5 Trip
Digital Input 5 Trip Relays
Digital Input 5 Trip Delay
Digital Input 5 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 3 DIGITAL INPUT 4

2A20

2A25
2A30
2A31
2A32
2A33
2A34
2A35
2A36

CG122

1st & 2nd Character of Digital


Input 4 Name

11th & 12th Character of Digital


Input 4 Name
Digital Input 4 Type
Reserved
Digital Input 4 Alarm
Digital Input 4 Alarm Relays
Digital Input 4 Alarm Delay
Digital Input 4 Alarm Events
Digital Input 4 Trip

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0

2
6
50000
1
2

1
1
1
1
1

100ms
-

F115
F113
F2
F103
F115

0
0
50
0
0

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 70 of 77)


ADDR
(hex)

2A37
2A38
2A39
...

DESCRIPTION

MIN.

Digital Input 4 Trip Relays


Digital Input 4 Trip Delay
Digital Input 4 Assignable
Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
1

6
1
50000 1

100ms

F111
F2

0
50

F163

RRTD 3 DIGITAL INPUT 1

2A40

2A45
2A50
2A51
2A52
2A53
2A54
2A55
2A56
2A57
2A58
2A59
...

1st & 2nd Character of Digital


Input 1 Name

11th & 12th Character of Digital


Input 1 Name
Digital Input 1 Type
Reserved
Digital Input 1 Alarm
Digital Input 1 Alarm Relays
Digital Input 1 Alarm Delay
Digital Input 1 Alarm Events
Digital Input 1 Trip
Digital Input 1 Trip Relays
Digital Input 1 Trip Delay
Digital Input 1 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 3 DIGITAL INPUT 6

2A60

2A65
2A70
2A71
2A72
2A73
2A74
2A75
2A76
2A77
2A78
2A79
...

1st & 2nd Character of Digital


Input 6 Name

11th & 12th Character of Digital


Input 6 Name
Digital Input 6 Type
Reserved
Digital Input 6 Alarm
Digital Input 6 Alarm Relays
Digital Input 6 Alarm Delay
Digital Input 6 Alarm Events
Digital Input 6 Trip
Digital Input 6 Trip Relays
Digital Input 6 Trip Delay
Digital Input 6 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 3 DIGITAL INPUT 3

2A80

2A85
2A90
2A91
2A92
2A93
2A94
2A95

1st & 2nd Character of Digital


Input 3 Name

11th & 12th Character of Digital


Input 3 Name
Digital Input 3 Type
Reserved
Digital Input 3 Alarm
Digital Input 3 Alarm Relays
Digital Input 3 Alarm Delay
Digital Input 3 Alarm Events

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0

2
6
50000
1

1
1
1
1

100ms
-

F115
F113
F2
F103

0
0
50
0

CG123

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 71 of 77)


ADDR
(hex)

2A96
2A97
2A98
2A99
...

DESCRIPTION

MIN.

Digital Input 3 Trip


Digital Input 3 Trip Relays
Digital Input 3 Trip Delay
Digital Input 3 Assignable
Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
0
1

2
1
6
1
50000 1

100ms

F115
F111
F2

0
0
50

F163

RRTD 4 DIGITAL INPUT 2

2AA0

2AA5
2AB0
2AB1
2AB2
2AB3
2AB4
2AB5
2AB6
2AB7
2AB8
2AB9
...

1st & 2nd Character of Digital


Input 2 Name

11th & 12th Character of Digital


Input 2 Name
Digital Input 2 Type
Reserved
Digital Input 2 Alarm
Digital Input 2 Alarm Relays
Digital Input 2 Alarm Delay
Digital Input 2 Alarm Events
Digital Input 2 Trip
Digital Input 2 Trip Relays
Digital Input 2 Trip Delay
Digital Input 2 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 4 DIGITAL INPUT 5

2AC0

2AC5
2AD0
2AD1
2AD2
2AD3
2AD4
2AD5
2AD6
2AD7
2AD8
2AD9
...

1st & 2nd Character of Digital


Input 5 Name

11th & 12th Character of Digital


Input 5 Name
Digital Input 5 Type
Reserved
Digital Input 5 Alarm
Digital Input 5 Alarm Relays
Digital Input 5 Alarm Delay
Digital Input 5 Alarm Events
Digital Input 5 Trip
Digital Input 5 Trip Relays
Digital Input 5 Trip Delay
Digital Input 5 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 4 DIGITAL INPUT 4

2AE0

2AE5
2AF0
2AF1
2AF2
2AF3
2AF4

CG124

1st & 2nd Character of Digital


Input 4 Name

11th & 12th Character of Digital


Input 4 Name
Digital Input 4 Type
Reserved
Digital Input 4 Alarm
Digital Input 4 Alarm Relays
Digital Input 4 Alarm Delay

32

127

F22

GE

32

127

F22

GE

F116

0
0
1

2
1
6
1
50000 1

100ms

F115
F113
F2

0
0
50

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 72 of 77)


ADDR
(hex)

2AF5
2AF6
2AF7
2AF8
2AF9
...

DESCRIPTION

MIN.

Digital Input 4 Alarm Events


Digital Input 4 Trip
Digital Input 4 Trip Relays
Digital Input 4 Trip Delay
Digital Input 4 Assignable
Function
Reserved

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

0
0
0
1

1
2
6
50000

1
1
1
1

100ms

F103
F115
F111
F2

0
0
0
50

F163

RRTD 4 DIGITAL INPUT 1

2B00

2B05
2B10
2B11
2B12
2B13
2B14
2B15
2B16
2B17
2B18
2B19
...

1st & 2nd Character of Digital


Input 1 Name

11th & 12th Character of Digital


Input 1 Name
Digital Input 1 Type
Reserved
Digital Input 1 Alarm
Digital Input 1 Alarm Relays
Digital Input 1 Alarm Delay
Digital Input 1 Alarm Events
Digital Input 1 Trip
Digital Input 1 Trip Relays
Digital Input 1 Trip Delay
Digital Input 1 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 4 DIGITAL INPUT 6

2B20

2B25
2B30
2B31
2B32
2B33
2B34
2B35
2B36
2B37
2B38
2B39
...

1st & 2nd Character of Digital


Input 6 Name

11th & 12th Character of Digital


Input 6 Name
Digital Input 6 Type
Reserved
Digital Input 6 Alarm
Digital Input 6 Alarm Relays
Digital Input 6 Alarm Delay
Digital Input 6 Alarm Events
Digital Input 6 Trip
Digital Input 6 Trip Relays
Digital Input 6 Trip Delay
Digital Input 6 Assignable
Function
Reserved

32

127

F22

GE

32

127

F22

GE

F116

0
0
1
0
0
0
1

2
6
50000
1
2
6
50000

1
1
1
1
1
1
1

100ms
100ms

F115
F113
F2
F103
F115
F111
F2

0
0
50
0
0
0
50

F163

RRTD 4 DIGITAL INPUT 3

2B40

2B45
2B50
2B51
2B52
2B53

1st & 2nd Character of Digital


Input 3 Name

11th & 12th Character of Digital


Input 3 Name
Digital Input 3 Type
Reserved
Digital Input 3 Alarm
Digital Input 3 Alarm Relays

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

32

127

F22

GE

32

127

F22

GE

F116

0
0

2
6

1
1

F115
F113

0
0

CG125

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 73 of 77)


ADDR
(hex)

2B54
2B55
2B56
2B57
2B58

DESCRIPTION

MIN.

...

Digital Input 3 Alarm Delay


Digital Input 3 Alarm Events
Digital Input 3 Trip
Digital Input 3 Trip Relays
Digital Input 3 Trip Delay
Digital Input 3 Assignable
Function
Reserved

2B60
2B61
2B62
2B63
2B64
2B65
2B66
2B67
...

Force Trip Relay


Force Trip Relay Duration
Force AUX1 Relay
Force AUX1 Relay Duration
Force AUX2 Relay
Force AUX2 Relay Duration
Force Alarm Relay
Force Alarm Relay Range
Reserved

2B70
2B71
2B72
2B73
2B74
2B75
2B76
2B77
...

Force Trip Relay


Force Trip Relay Duration
Force AUX1 Relay
Force AUX1 Relay Duration
Force AUX2 Relay
Force AUX2 Relay Duration
Force Alarm Relay
Force Alarm Relay Range
Reserved

2B80
2B81
2B82
2B83
2B84
2B85
2B86
2B87
...

Force Trip Relay


Force Trip Relay Duration
Force AUX1 Relay
Force AUX1 Relay Duration
Force AUX2 Relay
Force AUX2 Relay Duration
Force Alarm Relay
Force Alarm Relay Range
Reserved

2B90
2B91
2B92
2B93
2B94
2B95
2B96
2B97
...

Force Trip Relay


Force Trip Relay Duration
Force AUX1 Relay
Force AUX1 Relay Duration
Force AUX2 Relay
Force AUX2 Relay Duration
Force Alarm Relay
Force Alarm Relay Range
Reserved

2BA0
2BA1

Force Analog Outputs


Analog Output 1 Forced Value

2B59

MAX.

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

1
0
0
0
1

50000
1
2
6
50000

1
1
1
1
1

100ms
100ms

F2
F103
F115
F111
F2

50
0
0
0
50

F163

s
s
s
s

F150
F1
F150
F1
F150
F1
F150
F1

0
0
0
0
0
0
0
0

s
s
s
s

F150
F1
F150
F1
F150
F1
F150
F1

0
0
0
0
0
0
0
0

s
s
s
s

F150
F1
F150
F1
F150
F1
F150
F1

0
0
0
0
0
0
0
0

s
s
s
s

F150
F1
F150
F1
F150
F1
F150
F1

0
0
0
0
0
0
0
0

F126
% range F1

0
0

RRTD 1 TEST OUPUT RELAYS

0
0
0
0
0
0
0
01

2
300
2
300
2
300
2
300

1
1
1
1
1
1
1
1

RRTD 2 TEST OUPUT RELAYS

0
0
0
0
0
0
0
0

2
300
2
300
2
300
2
300

1
1
1
1
1
1
1
1

RRTD 3 TEST OUPUT RELAYS

0
0
0
0
0
0
0
0

2
300
2
300
2
300
2
300

1
1
1
1
1
1
1
1

RRTD 4 TEST OUPUT RELAYS

0
0
0
0
0
0
0
0

2
300
2
300
2
300
2
300

1
1
1
1
1
1
1
1

RRTD 1 TEST ANALOG OUTPUTS

CG126

0
0

1
100

1
1

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 74 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

2BA2
2BA3
2BA4
...

Analog Output 2 Forced Value


Analog Output 3 Forced Value
Analog Output 4 Forced Value
Reserved

0
0
0

2BB0
2BB1
2BB2
2BB3
2BB4
...

Force Analog Outputs


Analog Output 1 Forced Value
Analog Output 2 Forced Value
Analog Output 3 Forced Value
Analog Output 4 Forced Value
Reserved

2BC0
2BC1
2BC2
2BC3
2BC4
...

Force Analog Outputs


Analog Output 1 Forced Value
Analog Output 2 Forced Value
Analog Output 3 Forced Value
Analog Output 4 Forced Value
Reserved

2BD0
2BD1
2BD2
2BD3
2BD4
...

Force Analog Outputs


Analog Output 1 Forced Value
Analog Output 2 Forced Value
Analog Output 3 Forced Value
Analog Output 4 Forced Value
Reserved

2BE0

First Character of Counter Name


First Character of Counter Unit
Name
Counter Type
Digital Counter Alarm
Assign Alarm Relays
Counter Alarm Level
Reserved
Record Alarms as Events
Reserved

MAX.

100
100
100

STEP
VALUE

1
1
1

UNITS

FORMAT
CODE

FACTORY
DEFAULT

% range F1
% range F1
% range F1

0
0
0

% range
% range
% range
% range

F126
F1
F1
F1
F1

0
0
0
0
0

% range
% range
% range
% range

F126
F1
F1
F1
F1

0
0
0
0
0

% range
% range
% range
% range

F126
F1
F1
F1
F1

0
0
0
0
0

RRTD 2 TEST ANALOG OUTPUTS

0
0
0
0
0

1
100
100
100
100

1
1
1
1
1

RRTD 3 TEST ANALOG OUTPUTS

0
0
0
0
0

1
100
100
100
100

1
1
1
1
1

RRTD 4 TEST ANALOG OUTPUTS

0
0
0
0
0

1
100
100
100
100

1
1
1
1
1

RRTD 1 DIGITAL COUNTER

2BEC
2BF2
2BF3
2BF4
2BF5
2BF7
2BF8
...

32

127

F1

32

127

F1

0
0
0
0
0

1
2
6
65535
1

1
1
1
1
1

F114
F115
F113
F1
F103

0
0
0
100
0

RRTD 2 DIGITAL COUNTER

2C00
2C0C
2C12
2C13
2C14
2C15
2C17
2C18
...

First Character of Counter Name


First Character of Counter Unit
Name
Counter Type
Digital Counter Alarm
Assign Alarm Relays
Counter Alarm Level
Reserved
Record Alarms as Events
Reserved

32

127

F1

32

127

F1

0
0
0
0
0

1
2
6
65535
1

1
1
1
1
1

F114
F115
F113
F1
F103

0
0
0
100
0

RRTD 3 DIGITAL COUNTER

2C20
2C2C

First Character of Counter Name 32


First Character of Counter Unit 32
Name

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

127

F1

127

F1

CG127

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 75 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

2C32
2C33
2C34
2C35
2C37
2C38
...

Counter Type
Digital Counter Alarm
Assign Alarm Relays
Counter Alarm Level
Reserved
Record Alarms as Events
Reserved

0
0
0
0
0

2C40

First Character of Counter Name


First Character of Counter Unit
Name
Counter Type
Digital Counter Alarm
Assign Alarm Relays
Counter Alarm Level
Reserved
Record Alarms as Events
Reserved

MAX.

1
2
6
65535
1

STEP
VALUE

1
1
1
1
1

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F114
F115
F113
F1
F103

0
0
0
100
0

RRTD 4 DIGITAL COUNTER

2C4C
2C52
2C53
2C54
2C55
2C57
2C58
...

32

127

F1

32

127

F1

0
0
0
0
0

1
2
6
65535
1

1
1
1
1
1

F114
F115
F113
F1
F103

0
0
0
100
0

EVENT RECORDER / TRACE MEMORY / MOTOR START DATA LOGGER (ADDRESSES 3000 TO 3FFF)
EVENT RECORDER

3000
3002
3003
3004
3005
3007
3009
...
300B
300C
300D
300E
300F
3010
3011
3012
3013
...
301A
301B
301C
301D
301E
301F
3020
3021
3022
3023

CG128

Event Recorder Last Reset (2


words)
Total Number of Events Since
Last Clear
Event Record Selector (1=oldest,
512=newest)
Cause of Event
Time of Event (2 words)
Date of Event (2 words)
Motor Speed During Event
Reserved
Event Phase A Current
Event Phase B Current
Event Phase C Current
Event Motor Load
Event Current Unbalance
Event Ground Current
Event Hottest Stator RTD Owner
Event Hottest Stator RTD
Event Temperature of Hottest
Stator RTD
Reserved
Event Voltage Vab
Event Voltage Vbc
Event Voltage Vca
Event Voltage Van
Event Voltage Vbn
Event Voltage Vcn
Event System Frequency
Event Real Power
Event Reactive Power
Event Apparent Power

N/A

N/A

N/A

N/A

F18

N/A

65535 1

N/A

F1

512

N/A

F1

0
N/A
N/A
0

281
N/A
N/A
2

1
N/A
N/A
1

N/A
N/A
N/A

F134
F19
F18
F186

0
N/A
N/A
N/A

0
0
0
0
0
0
0
0

65535
65535
65535
2000
100
50000
5
12

1
1
1
1
1
1
1
1

A
A
A
FLA
%
A
N/A
-

F1
F1
F1
F3
F1
F23
F165
F1

0
0
0
0
0
0
0
0

-40

200

oC

F4

0
0
0
0
0
0
0
-32000
-32000
0

20000
20000
20000
20000
20000
20000
12000
32000
32000
50000

1
1
1
1
1
1
1
1
1
1

V
V
V
V
V
V
Hz
kW
kvar
kVA

F1
F1
F1
F1
F1
F1
F3
F4
F4
F1

0
0
0
0
0
0
0
0
0
0

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG10: MEMORY MAP (Sheet 76 of 77)


ADDR
(hex)

3024
...

DESCRIPTION

MIN.

Event Power Factor


Reserved

-99

MAX.

100

STEP
VALUE

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F21

WAVEFORM CAPTURE / MOTOR START DATA LOGGER

30EF

Buffer Memory Access Type

F184

30F0
30F2

Trace Memory Clear Date


Trace Memory Clear Time
Trace Memory Triggers Since
Last Clear
Trace Memory Buffer Selector

N/A
N/A

N/A
N/A

N/A
N/A

N/A
N/A

F18
F19

0 (Trace
Memory)
N/A
N/A

65535 1

F1

F1

F1

F1

11

F1

N/A
N/A
N/A
N/A
0

N/A
N/A
N/A
N/A
2

N/A
N/A
N/A
N/A
1

N/A
N/A
N/A
N/A
-

F18
F18
F19
F19
F85

0
0 (None
Selected)
0
0 (None
Selected)
N/A
N/A
N/A
N/A
N/A

F1

100

F1

N/A

F185

N/A

-32767 32767 1
-32767 32767 1

F4
F4

N/A
N/A

-32767 32767 1
-32767 32767 1

F4
F4

N/A
N/A

30F4
30F5

Motor Start Log Buffer Selector

Trace Memory Channel Selector


Motor Start Log Channel
Selector
Trace Memory Trigger Date
30F7
Motor Start Log Trigger Date
Trace Memory Trigger Time
30F9
Motor Start Log Trigger Time
Trace Memory Trigger Cause
30FB1 Number of Recorded Motor Start
Logs
Trace Memory Trigger Index
30FC1 Motor Start Log Phase Voltage
Type
...
Reserved
First Trace Memory Sample
3100
First Memory Sample

Last Trace Memory Sample


31FF
Last Memory Sample
30F6

DATA LOGGER LOG HEADER

3200
3201
3202
3203
3204
3205

Log Time Interval


Log Record Size
Log Total Possible Records
Total Logs Since Last Clear
Total Logs Presently Used
Total Records Presently Used

1
0
0
0
0
0

3600
16
16256
65535
50
16256

1
1
1
1
1

s
Words
-

F1
F1
F1
F1
F1
F1

3206

Log Status

F190

3207
3208
3209
320B

Log Time Until next Reading


Data Logger Percentage Full
Date of Latest Record
Time of Latest record
Address Pointer To Next Record
To Write
Pointer to 1st Log Start Address
1st Log Number of Records
...
Pointer to 50th Log Start
Address
50th Log Number of Records

1
0
-

3600
100
-

1
1
-

s
%
-

F1
F1
F18
F19

3600
N/A
N/A
0
0
0
0=
Stopped
3600
0
-

16255 1

F1

0
0
...

16255 1
16256 1
...
...

...

F1
F1
...

N/A
N/A
...

16255 1

F1

N/A

16256 1

F1

N/A

320D
320E
320F
...
3270
3271

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG129

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG10: MEMORY MAP (Sheet 77 of 77)


ADDR
(hex)

DESCRIPTION

MIN.

3272
3273
3274
3275
3276
3277
3278

Log 1-8 Start/Stop Method


Log 9-16 Start/Stop Method
Log 17-24 Start/Stop Method
Log 25-32 Start/Stop Method
Log 33-40 Start/Stop Method
Log 41-48 Start/Stop Method
Log 49-50 Start/Stop Method

0
0
0
0
0
0
0

3280

Data Log Memory Access Block 0


Number
Data Log Register 1
Data Log Register 2
Data Log Register 3
Data Log Register 4
...
...
Data Log Register 63
Data Log Register 64
Reserved
...
...
Reserved

MAX.

FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF

STEP
VALUE

N/A
N/A
N/A
N/A
N/A
N/A
N/A

UNITS

FORMAT
CODE

FACTORY
DEFAULT

F191
F191
F191
F191
F191
F191
F191

N/A
N/A
N/A
N/A
N/A
N/A
N/A

F1

DATA LOGGER DATA

3281
3282
3283
3284
...
32BF
32C0
32C1
...
3FFF

255

...
-

...
-

...
-

F1
F1
F1
F1
...
F1
F1

...
-

...

...

...

...

...

1. Addresses 0x030FB and 0x30FC have different functionality, depending on which functionality is selected in address 0x30EF, Waveform Capture, Motor Start Data Logger

CG130

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

6.8

MEMORY MAP

Format Codes

Table CG11: Memory Map Data Formats (Sheet 1 of 27)


CODE

TYPE

DEFINITION

F1

16 bits

UNSIGNED VALUE
Example: 1234 stored as 1234

F2

16 bits

UNSIGNED VALUE, 1 DECIMAL PLACE


Example: 123.4 stored as 1234

F3

16 bits

UNSIGNED VALUE, 2 DECIMAL PLACES


Example: 12.34 stored as 1234

F4

16 bits

2s COMPLEMENT SIGNED VALUE


Example: -1234 stored as -1234 (i.e. 64302)

F5

16 bits

2s COMPLEMENT SIGNED VALUE, 1 DECIMAL PLACES


Example: -123.4 stored as -1234 (i.e. 64302)

F6

16 bits

2s COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACES


Example: -12.34 stored as -1234 (i.e. 64302)

F7

16 bits

2s COMPLEMENT SIGNED VALUE, 3 DECIMAL PLACES


Example: -1.234 stored as -1234 (i.e. 64302)

F8

16 bits

2s COMPLEMENT SIGNED VALUE, 4 DECIMAL PLACES


Example: -0.1234 stored as -1234 (i.e. 64302)

F13

16 bits

INSTALLED OPTIONS

xxxx xxxx xxxx xxx1

Profibus-DP (0 = Not Installed, 1 = Installed)

xxxx xxxx xxxx xx1x

Fiber Optic (0 = Not Installed, 1 = Installed)

xxxx xxxx xxxx x1xx

Metering (0 = Not Installed, 1 = Installed)

xxxx xxxx xxxx 1xxx

Backspin (0 = Not Installed, 1 = Installed)

xxxx xxxx xxx1 xxxx

Local RTD (0 = Not Installed, 1 = Installed)

xxxx xxxx xx1x xxxx

Power Supply Type (0 = LO, 1 = HI)

xxxx xxxx 1xxx xxxx

Modbus/TCP (0 = Not Installed, 1 = Installed)

xxxx xxx1 xxxx xxxx

DeviceNet (0 = Not Installed, 1 = Installed)

xxxx xx1x xxxx xxxx

Harsh Environment (0 = Not Installed, 1 = Installed)

xxxx x1xx xxxx xxxx

Profibus-DPV1 (0 = Not Installed, 1 = Installed)

xxxx 1xxx xxxx xxxx

Enhanced Diagnostics (0 = Not Installed, 1 = Installed)

16 bits

HARDWARE REVISION

0000 0000 0000 0001

1=A

0000 0000 0000 0010

2=B

0000 0000 0000 0011

3=C

0000 0000 0001 1010

26 = Z

F15

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG131

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 2 of 27)


CODE

F16

DEFINITION

16 bits

SOFTWARE REVISION

1111 1111 xxxx xxxx

Major Revision Number, 0 to 9 in steps of 1

xxxx xxxx 1111 1111

Minor Revision Number (two BCD digits), 00 to 99 in steps of


1
Example: Revision 2.30 stored as 0230 hex

32 bits

DATE (MM/DD/YYYY)
Example: Feb. 20, 1995 stored as 34867142 (i.e. 1st word:
0214, 2nd word 07C6)

1st byte

Month (1 to 12)

2nd byte

Day (1 to 31)

3rd and 4th byte

Year (1998 to 2097)

32 bits

TIME (HH:MM:SS:hh)
Example: 2:05pm stored as 235208704 (i.e. 1st word: 0E05,
2nd word 0000)

1st byte

Hours (0 to 23)

2nd byte

Minutes (0 to 59)

3rd byte

Seconds (0 to 59)

4th byte

Hundreds of seconds (0 to 99) - Not used by 369

F20

16 bits

2s COMPLEMENT SIGNED LONG VALUE


Example: 1234 stored as 1234. Note: -1 means Never

F21

16 bits

2s COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACES


(Power Factor)
Example: Power Factor of 0.87 lag is used as 87 (i.e. 0057)

<0

Leading Power Factor - Negative

>0

Lagging Power Factor - Positive

16 bits

TWO 8-BIT CHARACTERS PACKED INTO 16-BIT UNSIGNED


Example: String "AB" stored as 4142 hex.

MSB

First Character

LSB

Second Character

F23

16 Bits

UNSIGNED VALUE (For 1A/5 A CT, 1Decimal Place) (For 50:


0.025 A CT, 2 Decimal Places)
Example: For 1A/5A CT, G/F current = 1000.0 A
Example: For 50: 0.025 A CT, G/F current = 25.00

F26

16 Bits

ANALOG OUTPUT SELECTION

0 - 1mA

0 - 20 mA

4 - 20 mA

16 Bits

BACKSPIN DETECTION STATE

Motor Running

F18

F19

F22

F27

CG132

TYPE

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 3 of 27)


CODE

F30

F31

F85

F100

TYPE

DEFINITION

No Backspin

Slowdown

Acceleration

---

Backspinning

Prediction

Soon to Restart

16 Bits

DISABLE/ENABLE SELECTION

Disabled

Enabled

16 Bits

COMMAND FUNCTION CODES

Not in use

Reset 369

Motor Start

Motor Stop

Waveform Trigger

Reserved

Clear Trip Counters

Clear Last Trip Data

Reserved

Reserved

10

Clear RTD Maximums

11

Reset Motor Info

12

Clear/Reset all Data

20

Block/Unblock Protection Functions

21

Force Output Relays

Unsigned 16 bit integer

WAVEFORM CAPTURE TRIGGER CAUSE

None

Manual

Automatic

Unsigned 16 bit integer

TEMPERATURE DISPLAY UNITS

Celsius

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG133

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 4 of 27)


CODE

F101

F102

F103

F104

F105

F106

F107

F108

CG134

TYPE

DEFINITION

Fahrenheit

Unsigned 16 bit integer

BAUD RATE

1200 baud

2400 baud

4800 baud

9600 baud

19200 baud

Unsigned 16 bit integer

PARITY

None

Odd

Even

Unsigned 16 bit integer

OFF/ON OR NO/YES SELECTION

Off / No

On / Yes

Unsigned 16 bit integer

GROUND CT TYPE

None

1 A Secondary

5 A Secondary

Multilin CT 50/0.025

Unsigned 16 bit integer

CT TYPE

None

1 A Secondary

5 A Secondary

Unsigned 16 bit integer

VOLTAGE TRANSFORMER CONNECTION TYPE

None

Open Delta

Wye

Unsigned 16 bit integer

NOMINAL FREQUENCY

60 Hz

50 Hz

Variable

Unsigned 16 bit integer

REDUCED VOLTAGE STARTING TRANSITION ON

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 5 of 27)


CODE

F109

F110

F111

F112

TYPE

DEFINITION

Current Only

Current or Timer

Current and Timer

Unsigned 16 bit integer

STARTER STATUS SWITCH

Starter Aux a (52a)

Starter Aux b (52b)

Unsigned 16 bit integer

EMERGENCY RESTART SWITCH INPUT FUNCTION

Off

Emergency Switch

General Switch

Digital Counter

Waveform Capture

DeviceNet Control

Speed Switch1

Reserved

Unsigned 16 bit integer

TRIP RELAYS

none

Trip

Aux1

Aux2

Trip & Aux1

Trip & Aux2

Aux1 & Aux2

Trip & Aux1 & Aux2

Unsigned 16 bit integer

NOT DEFINED

0
1
F113

Unsigned 16 bit integer

ALARM RELAYS

None

Alarm

Aux1

Aux2

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG135

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 6 of 27)


CODE

F114

F115

F116

F117

F119

F120

F121

CG136

TYPE

DEFINITION

Alarm & Aux1

Alarm & Aux2

Aux1 & Aux2

Alarm & Aux1 & Aux2

Unsigned 16 bit integer

COUNTER TYPE

Increment

Decrement

Unsigned 16 bit integer

ALARM/TRIP TYPE SELECTION

Off

Latched

Unlatched

Unsigned 16 bit integer

SWITCH TYPE

Normally Open

Normally Closed

Unsigned 16 bit integer

RESET MODE

All Resets

Remote Reset Only

Local Reset Only

Unsigned 16 bit integer

BACKUP RELAYS

None

Aux 1

Aux1 & Aux2

Aux2

Unsigned 16 bit integer

RTD TYPE

100 Ohm Platinum

120 Ohm Nickel

100 Ohm Nickel

10 Ohm Copper

Unsigned 16 bit integer

RTD APPLICATION

None

Stator

Bearing

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 7 of 27)


CODE

F122

F123

F124

F125

F127

TYPE

DEFINITION

Ambient

Other

Unsigned 16 bit integer

LOCAL/REMOTE RTD VOTING SELECTION

Off

RTD #1

RTD #2

RTD #3

RTD #4

RTD #5

RTD #6

RTD #7

RTD #8

RTD #9

10

RTD #10

11

RTD #11

12

RTD #12

13

All Stator

Unsigned 16 bit integer

ALARM STATUS

Off

Not Active

Timing Out

Active

Latched

Unsigned 16 bit integer

PHASE ROTATION AT MOTOR TERMINALS

ABC

ACB

Unsigned 16 bit integer

STARTER TYPE

Breaker

Contactor

Unsigned 16 bit integer

ANALOG OUTPUT PARAMETER SELECTION

Phase A Current

Phase B Current

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG137

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 8 of 27)


CODE

CG138

TYPE

DEFINITION

Phase C Current

Average Phase Current

AB Line Voltage

BC Line Voltage

CA Line Voltage

Average Line Voltage

Phase AN Voltage

Phase BN Voltage

10

Phase CN Voltage

11

Average Phase Voltage

12

Hottest Stator RTD

13

Local RTD #1

14

Local RTD #2

15

Local RTD #3

16

Local RTD #4

17

Local RTD #5

18

Local RTD #6

19

Local RTD #7

20

Local RTD #8

21

Local RTD #9

22

Local RTD #10

23

Local RTD #11

24

Local RTD #12

25

Power Factor

26

Reactive Power (kvar)

27

Real Power (kW)

28

Apparent Power (KVA)

29

Thermal Capacity Used

30

Relay Lockout Time

31

Reserved

32

Reserved

33

Reserved

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 9 of 27)


CODE

F128

F130

F131

F133

F134

TYPE

DEFINITION

34

Reserved

35

Motor Load

36

MWhrs

Unsigned 16 bit integer

CURVE STYLE

Standard

Custom

Unsigned 16 bit integer

DIGITAL INPUT PICKUP TYPE

Over

Under

Unsigned 16 bit integer

INPUT SWITCH STATUS

Open

Closed

Unsigned 16 bit integer

MOTOR STATUS

Stopped

Starting

Running

Overloaded

Tripped

Unsigned 16 bit integer

CAUSE OF EVENT

No Event

Forced Setpoints Dump

Speed Switch Trip

Differential Switch Trip

Reserved

Spare Switch Trip

Emergency Switch Trip

Unexpected Reset

EEPROM Memory

Reset Switch Trip

10

Upgrade Default Dump

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG139

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 10 of 27)


CODE

CG140

TYPE

DEFINITION

11

Overload Trip

12

Short Circuit Trip

13

Short Circuit Backup Trip

14

Mechanical Jam Trip

15

Undercurrent Trip

16

Current Unbalance Trip

17

Single Phasing Trip

18

Ground Fault Trip

19

Ground Fault Backup Trip

20

Overload Block

21

Acceleration Timer Trip

22

Start Inhibit Block

23

Starts Hour Block

24

Time Between Starts Block

25

Restart Block

26

Backspin Block

27

Single Shot Restart

28

Undervoltage Trip

29

Overvoltage Trip

30

Voltage Phase Reversal Trip

31

Underfrequency Trip

32

Overfrequency Trip

33

Lead Power Factor Trip

34

Lag Power Factor Trip

35

Positive Kvar Trip

36

Negative Kvar Trip

37

Underpower Trip

38

Reverse Power Trip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 11 of 27)


CODE

TYPE

DEFINITION

39

RTD1 Trip

40

RTD2 Trip

41

RTD3 Trip

42

RTD4 Trip

43

RTD5 Trip

44

RTD6 Trip

45

RTD7 Trip

46

RTD8 Trip

47

RTD9 Trip

48

RTD10 Trip

49

RTD11 Trip

50

RTD12 Trip

51

Reserved

52

Reserved

53

Spare Switch Alarm

54

Emergency Switch Alarm

55

Diff Switch Alarm

56

Speed Switch Alarm

57

Reset Switch Alarm

58

Reserved

59

Thermal Capacity Alarm

60

Overload Alarm

61

Mechanical Jam Alarm

62

Undercurrent Alarm

63

Current Unbalance Alarm

64

Ground Fault Alarm

65

Undervoltage Alarm

66

Overvoltage Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG141

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 12 of 27)


CODE

CG142

TYPE

DEFINITION

67

Overfrequency Alarm

68

Underfrequency Alarm

69

Lead Power Factor Alarm

70

Lag Power Factor Alarm

71

Positive Kvar Alarm

72

Negative Kvar Alarm

73

Underpower Alarm

74

Reverse Power Alarm

75

RTD1 Alarm

76

RTD2 Alarm

77

RTD3 Alarm

78

RTD4 Alarm

79

RTD5 Alarm

80

RTD6 Alarm

81

RTD7 Alarm

82

RTD8 Alarm

83

RTD9 Alarm

84

RTD10 Alarm

85

RTD11 Alarm

86

RTD12 Alarm

87

RTD1 Hi Alarm

88

RTD2 Hi Alarm

89

RTD3 Hi Alarm

90

RTD4 Hi Alarm

91

RTD5 Hi Alarm

92

RTD6 Hi Alarm

93

RTD7 Hi Alarm

94

RTD8 Hi Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 13 of 27)


CODE

TYPE

DEFINITION

95

RTD9 Hi Alarm

96

RTD10 Hi Alarm

97

RTD11 Hi Alarm

98

RTD12 Hi Alarm

99

Reserved

100

Lost RTD Comm Alarm

101

Low RTD Alarm

102

Trip Counter Alarm

103

Current Demand Alarm

104

Kw Demand Alarm

105

Kvar Demand Alarm

106

Kva Demand Alarm

107

Digital Counter Alarm

108

Service Alarm

109

Control Power Lost

110

Control Power App

111

Emergency Restart Closed

112

Emergency Restart Open

113

Start While Blocked

114

Reserved

115

Breaker Failure

116

Welded Contactor

117

Incomplete Sequence Trip

118

Reserved

119

Reserved

120

Reserved

121

RRTD1 RTD1 Trip

122

RRTD1 RTD2 Trip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG143

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 14 of 27)


CODE

CG144

TYPE

DEFINITION

123

RRTD1 RTD3 Trip

124

RRTD1 RTD4 Trip

125

RRTD1 RTD5 Trip

126

RRTD1 RTD6 Trip

127

RRTD1 RTD7 Trip

128

RRTD1 RTD8 Trip

129

RRTD1 RTD9 Trip

130

RRTD1 RTD10 Trip

131

RRTD1 RTD11 Trip

132

RRTD1 RTD12 Trip

133

RRTD2 RTD1 Trip

134

RRTD2 RTD2 Trip

135

RRTD2 RTD3 Trip

136

RRTD2 RTD4 Trip

137

RRTD2 RTD5 Trip

138

RRTD2 RTD6 Trip

139

RRTD2 RTD7 Trip

140

RRTD2 RTD8 Trip

141

RRTD2 RTD9 Trip

142

RRTD2 RTD10 Trip

143

RRTD2 RTD11 Trip

144

RRTD2 RTD12 Trip

145

RRTD3 RTD1 Trip

146

RRTD3 RTD2 Trip

147

RRTD3 RTD3 Trip

148

RRTD3 RTD4 Trip

149

RRTD3 RTD5 Trip

150

RRTD3 RTD6 Trip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 15 of 27)


CODE

TYPE

DEFINITION

151

RRTD3 RTD7 Trip

152

RRTD3 RTD8 Trip

153

RRTD3 RTD9 Trip

154

RRTD3 RTD10 Trip

155

RRTD3 RTD11 Trip

156

RRTD3 RTD12 Trip

157

RRTD4 RTD1 Trip

158

RRTD4 RTD2 Trip

159

RRTD4 RTD3 Trip

160

RRTD4 RTD4 Trip

161

RRTD4 RTD5 Trip

162

RRTD4 RTD6 Trip

163

RRTD4 RTD7 Trip

164

RRTD4 RTD8 Trip

165

RRTD4 RTD9 Trip

166

RRTD4 RTD10 Trip

167

RRTD4 RTD11 Trip

168

RRTD4 RTD12 Trip

169

RRTD1 RTD1 Alarm

170

RRTD1 RTD2 Alarm

171

RRTD1 RTD3 Alarm

172

RRTD1 RTD4 Alarm

173

RRTD1 RTD5 Alarm

174

RRTD1 RTD6 Alarm

175

RRTD1 RTD7 Alarm

176

RRTD1 RTD8 Alarm

177

RRTD1 RTD9 Alarm

178

RRTD1 RTD10 Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG145

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 16 of 27)


CODE

CG146

TYPE

DEFINITION

179

RRTD1 RTD11 Alarm

180

RRTD1 RTD12 Alarm

181

RRTD1 RTD1 Hi Alarm

182

RRTD1 RTD2 Hi Alarm

183

RRTD1 RTD3 Hi Alarm

184

RRTD1 RTD4 Hi Alarm

185

RRTD1 RTD5 Hi Alarm

186

RRTD1 RTD6 Hi Alarm

187

RRTD1 RTD7 Hi Alarm

188

RRTD1 RTD8 Hi Alarm

189

RRTD1 RTD9 Hi Alarm

190

RRTD1 RTD10 Hi Alarm

191

RRTD1 RTD11 Hi Alarm

192

RRTD1 RTD12 Hi Alarm

193

RRTD1 Open RTD Alarm

194

RRTD1 Low RTD Alarm

195

RRTD2 RTD1 Alarm

196

RRTD2 RTD2 Alarm

197

RRTD2 RTD3 Alarm

198

RRTD2 RTD4 Alarm

199

RRTD2 RTD5 Alarm

200

RRTD2 RTD6 Alarm

201

RRTD2 RTD7 Alarm

202

RRTD2 RTD8 Alarm

203

RRTD2 RTD9 Alarm

204

RRTD2 RTD10 Alarm

205

RRTD2 RTD11 Alarm

206

RRTD2 RTD12 Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 17 of 27)


CODE

TYPE

DEFINITION

207

RRTD2 RTD1 Hi Alarm

208

RRTD2 RTD2 Hi Alarm

209

RRTD2 RTD3 Hi Alarm

210

RRTD2 RTD4 Hi Alarm

211

RRTD2 RTD5 Hi Alarm

212

RRTD2 RTD6 Hi Alarm

213

RRTD2 RTD7 Hi Alarm

214

RRTD2 RTD8 Hi Alarm

215

RRTD2 RTD9 Hi Alarm

216

RRTD2 RTD10 Hi Alarm

217

RRTD2 RTD11 Hi Alarm

218

RRTD2 RTD12 Hi Alarm

219

RRTD2 Open RTD Alarm

220

RRTD2 Low RTD Alarm

221

RRTD3 RTD1 Alarm

222

RRTD3 RTD2 Alarm

223

RRTD3 RTD3 Alarm

224

RRTD3 RTD4 Alarm

225

RRTD3 RTD5 Alarm

226

RRTD3 RTD6 Alarm

227

RRTD3 RTD7 Alarm

228

RRTD3 RTD8 Alarm

229

RRTD3 RTD9 Alarm

230

RRTD3 RTD10 Alarm

231

RRTD3 RTD11 Alarm

232

RRTD3 RTD12 Alarm

233

RRTD3 RTD1 Hi Alarm

234

RRTD3 RTD2 Hi Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG147

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 18 of 27)


CODE

CG148

TYPE

DEFINITION

235

RRTD3 RTD3 Hi Alarm

236

RRTD3 RTD4 Hi Alarm

237

RRTD3 RTD5 Hi Alarm

238

RRTD3 RTD6 Hi Alarm

239

RRTD3 RTD7 Hi Alarm

240

RRTD3 RTD8 Hi Alarm

241

RRTD3 RTD9 Hi Alarm

242

RRTD3 RTD10 Hi Alarm

243

RRTD3 RTD11 Hi Alarm

244

RRTD3 RTD12 Hi Alarm

245

RRTD3 Open RTD Alarm

246

RRTD3 Low RTD Alarm

247

RRTD4 RTD1 Alarm

248

RRTD4 RTD2 Alarm

249

RRTD4 RTD3 Alarm

250

RRTD4 RTD4 Alarm

251

RRTD4 RTD5 Alarm

252

RRTD4 RTD6 Alarm

253

RRTD4 RTD7 Alarm

254

RRTD4 RTD8 Alarm

255

RRTD4 RTD9 Alarm

256

RRTD4 RTD10 Alarm

257

RRTD4 RTD11 Alarm

258

RRTD4 RTD12 Alarm

259

RRTD4 RTD1 Hi Alarm

260

RRTD4 RTD2 Hi Alarm

261

RRTD4 RTD3 Hi Alarm

262

RRTD4 RTD4 Hi Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 19 of 27)


CODE

TYPE

DEFINITION

263

RRTD4 RTD5 Hi Alarm

264

RRTD4 RTD6 Hi Alarm

265

RRTD4 RTD7 Hi Alarm

266

RRTD4 RTD8 Hi Alarm

267

RRTD4 RTD9 Hi Alarm

268

RRTD4 RTD10 Hi Alarm

269

RRTD4 RTD11 Hi Alarm

270

RRTD4 RTD12 Hi Alarm

271

RRTD4 Open RTD Alarm

272

RRTD4 Low RTD Alarm

273

Power Failure

274

Software Reset

275

Clock Failure

276

A/D Failure

277

Autorestart Attempt

278

Autorestart Success

279

Autorestart Aborted 1

280

Autorestart Aborted 2

281

Autorestart Aborted 3

282

Autorestart Aborted 4

283

Autorestart Aborted 5

284

Motor Running

285

Motor Stopped

286

Fieldbus Comms Reset

287

RTD 1 Open Alarm

288

RTD 2 Open Alarm

289

RTD 3 Open Alarm

290

RTD 4 Open Alarm

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG149

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 20 of 27)


CODE

CG150

TYPE

DEFINITION

291

RTD 5 Open Alarm

292

RTD 6 Open Alarm

293

RTD 7 Open Alarm

294

RTD 8 Open Alarm

295

RTD 9 Open Alarm

296

RTD 10 Open Alarm

297

RTD 11 Open Alarm

298

RTD 12 Open Alarm

299

Starter Operation Monitor Alarm

300

Starter Operation Monitor Trip

301

Block Undercurrent/Underpower (37)

302

Unblock Undercurrent/Underpower (37)

303

Block Current Unbalance (46)

304

Unblock Current Unbalance (46)

305

Block Incomplete Sequence (48)

306

Unblock Incomplete Sequence (48)

307

Block Thermal Model (49)

308

Unblock Thermal Model (49)

309

Block Short Circuit and Backup (50)

310

Unblock Short Circuit and Backup (50)

311

Block Overload Alarm (51)

312

Unblock Overload Alarm (51)

313

Block Ground Fault (51G)

314

Unblock Ground Fault (51G)

315

Block Starts Per Hour and Time Between Starts (66)

316

Unblock Starts Per Hour and Time Between Starts (66)

317

Fieldbus Loss of Communications

318

UVR Trip

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 21 of 27)


CODE

TYPE

DEFINITION

319

UVR Undervoltage On

320

UVR Undervoltage Off

321

UVR In Progress On

322

UVR In Progress Off

323

UVR Close On

324

UVR Close Off

325

UVR Imm. Restart On

326

UVR Imm. Restart Off

327

UVR Stop On

328

UVR Stop Off

329

Motor Starting

F138

Reserved

Reserved

F139

Reserved

Reserved

F141

Unsigned 16 bit integer

OUTPUT RELAY STATUS

bit 0

Trip

bit 1

Alarm

bit 2

Auxiliary 1

bit 3

Auxiliary 2

Unsigned 16 Bit
Integer

CHANNEL 3 APPLICATION

MODBUS

Remote RTD

Unsigned 16 Bit
Integer

OUTPUT RELAY STATUS

De - Energized

Energized

Unsigned 16 Bit
Integer

CHANNEL TYPE

RS 485

Fiber Optic

Unsigned 16 Bit
Integer

NUMBER OF RECORDS

1 64 cycles

2 32 cycles

F149

F150

F151

F152

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG151

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 22 of 27)


CODE

F156

F157

F158

F159

CG152

TYPE

DEFINITION

4 16 cycles

8 8 cycles

Unsigned 16 Bit
Integer

REMOTE RTD COMMUNICATION STATUS

Remote RTD Module Communication Lost

Remote RTD Communication on Line

Unsigned 16 Bit
Integer

DIFFERENTIAL SWITCH INPUT FUNCTION

OFF

Differential Switch

General Switch

Digital Counter

Waveform Capture

DeviceNet Control

Reserved

Reserved

Unsigned 16 Bit
Integer

SPEED SWITCH INPUT FUNCTION

OFF

Speed Switch

General Switch

Digital Counter

Waveform Capture

DeviceNet Control

Two-speed Monitor1

Reserved

Unsigned 16 Bit
Integer

SPARE SWITCH INPUT FUNCTION

OFF

Starter Status Switch

General Switch

Digital Counter

Waveform Capture

DeviceNet Control

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 23 of 27)


CODE

F160

F161

F162

F163

F164

TYPE

DEFINITION

Reserved

Reserved

Unsigned 16 Bit
Integer

RESET SWITCH INPUT FUNCTION

OFF

Reset Switch

General Switch

Digital Counter

Waveform Capture

DeviceNet Control

Speed Switch1

Reserved

Unsigned 16 Bit
Integer

OUTPUT RELAY FAILSAFE CODE

Failsafe

Non Failsafe

Unsigned 16 Bit
Integer

ACCESS LEVEL

Read Only

Read / Write

Factory Service

Unsigned 16 Bit
Integer

RRTD DIGITAL INPUT FUNCTION

Off

undefined

General Switch

Digital Counter

Unsigned 16 Bit
Integer

COMMUNICATIONS MODULE STATUS

0x0001

Ethernet Connection OK

0x0002

IP Configuration OK

0x0004

IP Address Error

0x0008

Communications Module Error

0x0010

Network Activity Present

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG153

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 24 of 27)


CODE

F165

F166

F169

F180

CG154

TYPE

DEFINITION

Unsigned 16 Bit
Integer

OVERALL HOTTEST STATOR RTD OWNER

No RTDs programmed or available

Remote RTD #1

Remote RTD #2

Remote RTD #3

Remote RTD #4

Local 369

Unsigned 16 Bit
Integer

ENERGY UNIT DISPLAY

Mega

Kilo

Unsigned 16 Bit
Integer

TRIP AND ALARM RELAYS

None

Trip

Alarm

Aux1

Aux2

Trip and Alarm

Trip and Aux1

Trip and Aux2

Alarm and Aux1

Alarm and Aux2

10

Aux1 and Aux2

11

Trip and Alarm and Aux1

12

Trip and Alarm and Aux2

13

Trip and Aux1 and Aux2

14

Alarm and Aux1 and Aux2

15

All Relays

Unsigned 16 Bit
Integer

ANSI/IEEE DEVICE

37 - Undercurrent/Underpower

46 - Current Unbalance

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 25 of 27)


CODE

F181

F182

F183

F184

F185

F186

F187

TYPE

DEFINITION

48 - Incomplete Sequence

49 - Thermal Model

50 - Short Circuit and Backup

51 - Overload Alarm

51G - Ground Fault

66 - Starts Per Hour / Time Between Starts

Unsigned 16 Bit
Integer

OUTPUT RELAY TYPE

Latched

Pulsed

Unsigned 16 Bit
Integer

PROTECTION FUNCTION BLOCKING STATUS

Not Blocked

Blocked

16 bits

ACTIVELY COMMUNICATING RRTDs

xxxx xxxx xxxx 0000

No RRTDs Actively Communicating

xxxx xxxx xxxx xxx1

RRTD1 Communicating

xxxx xxxx xxxx xx1x

RRTD2 Communicating

xxxx xxxx xxxx x1xx

RRTD3 Communicating

xxxx xxxx xxxx 1xxx

RRTD4 Communicating

Unsigned 16 bit
Integer

DATA RECORD ACCESS TYPE

Access Trace Memory data

Access Motor Start Data Logger data

Unsigned 16 bit
Integer

VT CONNECTION TYPE

Phase-Neutral Voltage

Phase-Phase Voltage

Unsigned 16 bit
Integer

MOTOR SPEED

Not Programmed

Speed 1 (Low Speed)

Speed 2 (High Speed)

16 bitS

START/STOP DATA LOG COMMAND

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG155

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG11: Memory Map Data Formats (Sheet 26 of 27)


CODE

F188

TYPE

DEFINITION

None (Select Command)

Start Log

Stop Log

16 bitS

DATA LOG RECORDING TYPE

Run To Fill

Circulate

F189

SEE TABLE 9-12 BELOW

F190

16 bitS

DATA LOG STATUS

Stopped

Running

16 bits

DATA LOG START/STOP METHOD

xxxx xxxx xxxx xxx1

Log 1/9/17/25/33/41/49 Start Method

xxxx xxxx xxxx xx1x

Log 1/9/17/25/33/41/49 Stop Method

xxxx xxxx xxxx x1xx

Log 2/10/18/25/34/42/50 Start Method

xxxx xxxx xxxx 1xxx

Log 2/10/18/25/34/42/50 Stop Method

xxxx xxxx xxx1 xxxx

Log 3/11/19/25/35/43/ Start Method

xxxx xxxx xx1x xxxx

Log 3/11/19/25/35/43/ Stop Method

xxxx xxxx x1xx xxxx

Log 4/12/20/25/36/44/ Start Method

xxxx xxxx 1xxx xxxx

Log 4/12/20/25/36/44/ Stop Method

xxxx xxx1 xxxx xxxx

Log 5/13/21/25/37/45/ Start Method

xxxx xx1x xxxx xxxx

Log 5/13/21/25/37/45/ Stop Method

xxxx x1xx xxxx xxxx

Log 6/14/22/25/38/46/ Start Method

xxxx 1xxx xxxx xxxx

Log 6/14/22/25/38/46/ Stop Method

xxx1 xxxx xxxx xxxx

Log 7/15/23/25/39/47/ Start Method

xx1x xxxx xxxx xxxx

Log 7/15/23/25/39/47/ Stop Method

x1xx xxxx xxxx xxxx

Log 8/16/24/25/40/48/ Start Method

1xxx xxxx xxxx xxxx

Log 8/16/24/25/40/48/ Stop Method

F191

BIT VALUE

F192

CG156

Log Started/Stopped From Motor Start/Stop or Run To Fill

Log Started/Stopped Manually

Bitmask

369 DIGITAL INPUT AND OUTPUT RELAY STATUS

xxxx xxxx xxxx xxx1

Access Switch

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG11: Memory Map Data Formats (Sheet 27 of 27)


CODE

F193

TYPE

DEFINITION

xxxx xxxx xxxx xx1x

Speed Switch

xxxx xxxx xxxx x1xx

Spare Switch

xxxx xxxx xxxx 1xxx

Differential Switch

xxxx xxxx xxx1 xxxx

Emergency Switch

xxxx xxxx xx1x xxxx

Remote Reset Switch

xxxx xxx1 xxxx xxxx

Trip Relay Status

xxxx xx1x xxxx xxxx

Alarm Relay Status

xxxx x1xx xxxx xxxx

Aux1 Relay Status

xxxx 1xxx xxxx xxxx

Aux2 Relay Status

Bitmask

RRTD DIGITAL INPUT AND OUTPUT RELAY STATUS

xxxx xxxx xxxx xxx1

Digital Input 3

xxxx xxxx xxxx xx1x

Digital Input 4

xxxx xxxx xxxx x1xx

Digital Input 6

xxxx xxxx xxxx 1xxx

Digital Input 5

xxxx xxxx xxx1 xxxx

Digital Input 2

xxxx xxxx xx1x xxxx

Digital Input 1

xxxx xxx1 xxxx xxxx

Trip Relay Status

xxxx xx1x xxxx xxxx

Alarm Relay Status

xxxx x1xx xxxx xxxx

Aux1 Relay Status

xxxx 1xxx xxxx xxxx

Aux2 Relay Status

1. Only shown when ENABLE 2-SPEED MOTOR PROTECTION is set to Yes

Table CG12: Format Code F189


CODE

F189

PARAMETER LIST
VALUE

DATA ITEM

FORMAT CODE

None

N/A

Motor Thermal Capacity Used

F1

Digital Input and Output Relays Status

F192

Phase A Current

F1

Phase B Current

F1

Phase C Current

F1

Average Phase Current

F1

Motor Load

F3

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG157

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG12: Format Code F189


CODE

CG158

PARAMETER LIST
VALUE

DATA ITEM

FORMAT CODE

Current Unbalance

F1

Unbalanced Biased Motor Load

F3

10

Ground Current

F23

11

Vab*

F1

12

Vbc*

F1

13

Vca*

F1

14

Average Line Voltage*

F1

15

Van*

F1

16

Vbn*

F1

17

Vcn*

F1

18

Average Phase Voltage*

F1

19

System Frequency

F3

20

Power Factor

F21

21

Real Power (kW)

F4

22

Real Power (hp)

F1

23

Reactive Power

F4

24

Apparent Power

F1

25

Positive MegaWatthours

F1

26

Positive Megavarhours

F1

27

Negative Megavarhours

F1

28

Positive KiloWatthours

F1

29

Positive Kilovarhours

F1

30

Negative Kilovarhours

F1

31

Local RTD #1 Temperature

F4

32

Local RTD #2 Temperature

F4

33

Local RTD #3 Temperature

F4

34

Local RTD #4 Temperature

F4

35

Local RTD #5 Temperature

F4

36

Local RTD #6 Temperature

F4

37

Local RTD #7 Temperature

F4

38

Local RTD #8 Temperature

F4

39

Local RTD #9 Temperature

F4

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG12: Format Code F189


CODE

PARAMETER LIST
VALUE

DATA ITEM

FORMAT CODE

40

Local RTD #10 Temperature

F4

41

Local RTD #11 Temperature

F4

42

Local RTD #12 Temperature

F4

43

Current Demand

F1

44

Real Power Demand

F1

45

Reactive Power Demand

F1

46

Apparent Power Demand

F1

47

Peak Current Demand

F1

48

Peak Real Power Demand

F1

49

Peak Reactive Power Demand

F1

50

Peak Apparent Power Demand

F1

51

RRTD 1 - RTD #1 Temperature

F4

52

RRTD 1 - RTD #2 Temperature

F4

53

RRTD 1 - RTD #3 Temperature

F4

54

RRTD 1 - RTD #4 Temperature

F4

55

RRTD 1 - RTD #5 Temperature

F4

56

RRTD 1 - RTD #6 Temperature

F4

57

RRTD 1 - RTD #7 Temperature

F4

58

RRTD 1 - RTD #8 Temperature

F4

59

RRTD 1 - RTD #9 Temperature

F4

60

RRTD 1 - RTD #10 Temperature

F4

61

RRTD 1 - RTD #11 Temperature

F4

62

RRTD 1 - RTD #12 Temperature

F4

63

RRTD 2 - RTD #1 Temperature

F4

64

RRTD 2 - RTD #2 Temperature

F4

65

RRTD 2 - RTD #3 Temperature

F4

66

RRTD 2 - RTD #4 Temperature

F4

67

RRTD 2 - RTD #5 Temperature

F4

68

RRTD 2 - RTD #6 Temperature

F4

69

RRTD 2 - RTD #7 Temperature

F4

70

RRTD 2 - RTD #8 Temperature

F4

71

RRTD 2 - RTD #9 Temperature

F4

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG159

MEMORY MAP

CGCOMMUNICATIONS GUIDE

Table CG12: Format Code F189


CODE

CG160

PARAMETER LIST
VALUE

DATA ITEM

FORMAT CODE

72

RRTD 2 - RTD #10 Temperature

F4

73

RRTD 2 - RTD #11 Temperature

F4

74

RRTD 2 - RTD #12 Temperature

F4

75

RRTD 3 - RTD #1 Temperature

F4

76

RRTD 3 - RTD #2 Temperature

F4

77

RRTD 3 - RTD #3 Temperature

F4

78

RRTD 3 - RTD #4 Temperature

F4

79

RRTD 3 - RTD #5 Temperature

F4

80

RRTD 3 - RTD #6 Temperature

F4

81

RRTD 3 - RTD #7 Temperature

F4

82

RRTD 3 - RTD #8 Temperature

F4

83

RRTD 3 - RTD #9 Temperature

F4

84

RRTD 3 - RTD #10 Temperature

F4

85

RRTD 3 - RTD #11 Temperature

F4

86

RRTD 3 - RTD #12 Temperature

F4

87

RRTD 4 - RTD #1 Temperature

F4

88

RRTD 4 - RTD #2 Temperature

F4

89

RRTD 4 - RTD #3 Temperature

F4

90

RRTD 4 - RTD #4 Temperature

F4

91

RRTD 4 - RTD #5 Temperature

F4

92

RRTD 4 - RTD #6 Temperature

F4

93

RRTD 4 - RTD #7 Temperature

F4

94

RRTD 4 - RTD #8 Temperature

F4

95

RRTD 4 - RTD #9 Temperature

F4

96

RRTD 4 - RTD #10 Temperature

F4

97

RRTD 4 - RTD #11 Temperature

F4

98

RRTD 4 - RTD #12 Temperature

F4

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CGCOMMUNICATIONS GUIDE

MEMORY MAP

Table CG12: Format Code F189


CODE

PARAMETER LIST
VALUE

DATA ITEM

FORMAT CODE

99

RRTD 1 Digital Input and Output Relays


Status

F193

100

RRTD 2 Digital Input and Output Relays


Status

F193

101

RRTD 3 Digital Input and Output Relays


Status

F193

102

RRTD 4 Digital Input and Output Relays


Status

F193

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

CG161

MEMORY MAP

CG162

CGCOMMUNICATIONS GUIDE

369 MOTOR MANAGEMENT RELAY COMMUNICATIONS GUIDE

GE Consumer & Industrial


Multilin

369 Motor Management Relay


Appendix: Revisions

Revisions

A.1

Change Notes
A.1.1

Revision History
Table A1: Revision History
MANUAL P/N

RELEASE DATE

1601-9046-A1 (New Manual)

31 March 2008

1601-9046-A2

17 October 2008

1601-9046-A3

13 March 2009

1601-9046-A4

3 June 2010

ECO

Table A2: Major Updates for 369CG-A4


SECTION A3

SECTION A4

CHANGES

New manual revision number: A4


4.1

4.1

New section added in DeviceNet section: DeviceNet


Loss of Communication Trip

6.7

6.7

Minor Modbus Map (Fieldbus) changes.

Table A3: Major Updates for 369CG-A3


SECTION A2

SECTION A3

CHANGES

New manual revision number: A3


N/A

1.6

369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL

New section: Ethernet Loss of Communication Trip

A163

CHANGE NOTES

CHAPTER A: REVISIONS

Table A3: Major Updates for 369CG-A3


SECTION A2

6.7

SECTION A3

CHANGES

Modbus Map changes (from Profibus to Fieldbus) three addresses only.

6.7

Table A4: Major Updates for 369CG-A2


SECTION

SECTION

CHANGES

New manual revision number: A2


4.2

A164

4.2

Tables CG 8 and CG 9 Format Code corrections

369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL

CHAPTER A: REVISIONS

A.2

WARRANTY

Warranty
A.2.1

Warranty Information

GE MULTILIN RELAY WARRANTY


General Electric Multilin (GE Multilin) warrants each relay it manufactures to
be free from defects in material and workmanship under normal use and
service for a period of 24 months from date of shipment from factory.
In the event of a failure covered by warranty, GE Multilin will undertake to
repair or replace the relay providing the warrantor determined that it is
defective and it is returned with all transportation charges prepaid to an
authorized service centre or the factory. Repairs or replacement under
warranty will be made without charge.
Warranty shall not apply to any relay which has been subject to misuse,
negligence, accident, incorrect installation or use not in accordance with
instructions nor any unit that has been altered outside a GE Multilin
authorized factory outlet.
GE Multilin is not liable for special, indirect or consequential damages or for
loss of profit or for expenses sustained as a result of a relay malfunction,
incorrect application or adjustment.
For complete text of Warranty (including limitations and disclaimers), refer to
GE Multilin Standard Conditions of Sale.

369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL

A165

WARRANTY

A166

CHAPTER A: REVISIONS

369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL