Documente Academic
Documente Profesional
Documente Cultură
To
acquire
experience
on
three
basic
heat
exchangers
geometry.
To experimentally determine contributions of individual convective heat transfer
coefficients.
To isolate contribution of one of the coefficients, vary temperature of only one of
the fluids.
To calculate the efficiency and dirt factor the shell and tube sides.
ABTRACT
When conduct this experiment, the objectives to determine heat load and heat balance,
LMTD and overall heat transfer are successfully achieved. We also determined the
Reynolds number, heat transfer coefficient and the pressure drop of the system. All the
results have been presented in the table in the results section. All about the data have
been discussed in the discussion section. Heat exchange is an important unit operation
that contributes to efficiency and safety of many processes. In this project we will
evaluate performance of three different types of heat exchangers (tubular, plate, and
shell & tube). All these heat exchangers can be operated in both parallel- and counterflow configurations. The heat exchange is performed between hot and cold water. Heat
exchangers with only one phase (liquid or gas) on each side can be called one-phase or
single-phase heat exchangers. Two-phase heat exchangers can be used to heat a liquid
to boil it into a gas (vapor), sometimes called boilers, or cool a vapor to condense it into
a liquid (called condensers), with the phase change usually occurring on the shell side.
Boilers in steam engine locomotives are typically large, usually cylindrically-shaped
shell-and-tube heat exchangers. In large power plants with steam-driven turbines, shelland-tube surface condensers are used to condense the exhaust steam exiting the
turbine into condensate water which is recycled back to be turned into steam in the
steam generator.
APPARATUS
RECOMMENDATION
During the experiment, first the recommended are the measurement must be taken
when the pressure drop was stabilized, same as to the other such as flow rates and
temperature. When the measurement made when these properties are not in stabilized
condition, error might be occur and it will affect the calculation. The flow rate of the
water must be ensuring to be accurate. For the improving the system of shell and tube
heat exchanger, it is recommended that the shell and tube heat exchanger have their
own alert sign system that can give a sign to the engineer who handles the equipment
to take the readings at the correct and accurate time in order to get accurate readings.
So, this can help in reducing the inaccuracy of the measurements.There are many
recommendations when operating the heat exchanger experiment are as follows:
1. Safety glasses with side shields shall be worn at all times during the experiment. Hot
and cold water is used in this experiment under building main pressure reduced to
approximately 30 psi. There is a chance of a tube bursting or a valve leaking water and
start to spray the area around the area of the heat exchanger.
2. Prior to operation of the system, familiarize yourself with the equipment. Trace all
process lines, test all valves, and ensure that all valves are closed.
3. Cold water should be admitted first and then the hot water in order to avoid damage
due to thermal expansion.
4. While admitting hot water to the system, open the valves cautiously and check all
connections for possible leaks.
5. At the end of the experiment, the hot water supply should be shut off first. Allow the
cold water to circulate for a couple of minutes before shutting off the cold water supply.
6. We must aware of unlagged hot water lines, they heat up rapidly.
7. If a valve appears tight or doesn't yield to hand force, do not attempt to turn it with a
wrench. Turn off the steam or hot water, permit the system to drain and cool down, then
loosen the packing bonnet slightly and try again.
8. Keep the laboratory working space clean and uncluttered. Be aware of potential
hazards such as wet spots or debris on floors that could cause slips or falls.
9. There is no waste associated with this experiment. Only hot and cold water are used
in this experiment and they can be sent to the drain.
REFERENCES
Fundamentals
Marcel Dekker, Inc., New York, N.Y., 1999, Chaper 7.7, pp 768-828
Holman, J.P., "Heat Transfer", McGraw Hill, Fifth Edition, New York, N.Y., 1981,
RESULTS
EXPERIMENT 1.A:COUNTER-CURRENT SHELL & TUBE HEAT EXCHANGER
FT1
(LPM)
FT1
(LPM)
TT1
(C)
TT2
(C)
TT3
(C)
TT4
(C)
DPT2
(mmH2O
)
DPT2
(mmH2O
)
10
10
10
10
10
2
4
6
8
10
43.5
39.2
36.8
35.0
34.7
30.4
30.1
29.5
29.9
30.5
47.5
47.0
46.3
45.6
44.8
49.2
49.7
49.7
48.9
48.9
97
103
100
91
92
18
23
65
130
190
FT1
(LPM)
10
10
10
10
10
PROCEDURES
TT1
(C)
31.9
32.9
33.4
34.3
35.0
TT2
(C)
30.4
30.5
30.5
30.6
30.8
TT3
(C)
37.8
42.9
44.1
44.5
45.4
TT4
(C)
48.7
48.8
49.1
49.7
49.8
DPT1
(mmH2O)
5
5
5
60
82
DPT2
(mmH2O)
195
194
193
192
191
1. A quick inspection a perform to make sure that the equipment is in a proper working
condition.
2. All the valves are make sure initially closed,except V1 and V2.
3. Hot water tank is filled up via a water supply hose connected to valve V27.Once the
tank is full,valve is closed.
4. The cold water tank is filled up by V28 and the valve opened is leaved for continues
water supply.
5. A drain hose is connected to the cold water drain point.
6. Main power is switched on.The heater for the hot watr tank is switched on and point
the temperature controller is set to 50 C.
7. The water temperature is allowed in the hot water tank to reach the set-point.
8. The valve is switched to counter current Shell & Tube Heat Exchanger arrangement.
9 The pumps P1 and P2 is switched on.
10. Valves V3 and V4 is opened and adjusted to obtain the desired flowrates for hot
water and cold water streams for 10 minutes.
11. FT1,FT2,TT1,TT2,TT3,TT4 is recorded.
12. Presure drop measurement for shell-side and tube-side for pressure drop studies is
recorded.
13. Step 4 to 7 is repeated for different combinations of flowrates FT1 And FT2 as in
result sheet.
14. Pumps P1 and P2 is switched off after the completion of experiment.
15. The equipment is shut-downed.
CONCLUSION
In this experiment we can achieve all the objectives but the result obtained quite
difference with the theory. The basic theory in this experiment is Qh = Qc, which the
amount of heat transfer is equal to the amount of heat absorb. By carrying this
experiment, we cannot achieve that theory 100% because the theory only can used if it
is no heat is dissipated to the surrounding .In conclusion it is impossible to achieve
since in reality, there must be some heat leaves the system to the surrounding. At the
end of the experiment student able to investigate effects of the control parameters and
the heat exchanger configuration on the rate of the heat transfer, Qc. and to calculate
the heat transfer coefficient for inside and outside fluids also to measure and determine
the shell and tube sides heat loss rate. Next able to check validity of the theoretical
models and able to investigate dependence of convective heat transfer coefficients on
the flow geometry. Student also able to experimentally determine contributions of
individual convective heat transfer coefficient and able to isolate contribution of one of
the coefficients, vary temperature of only one of the fluids also to calculate the efficiency
and dirt factor the shell and tube sides.
THEORY
How do we account for the effect of heat loss to the surroundings on the analysis for the
overall heat transfer coefficient? The answer is found by setting up and solving the
differential energy balance equations for the hot and cold streams to determine the
relative heat transfer rate between the hot and cold streams and the heat transfer rate
from the cold stream to the surroundings. The laboratory shell and tube heat exchanger
may be operated in either of the two flow patterns illustrated in Figure 1. In all cases, the
hot stream is passed through the tubes. The differential energy balances around the hot
and cold streams assume steady-state operation and plug flow. The analysis also
assumes constant, average, properties. The fluid properties are evaluated at the
average temperature between the feed and effluent. It is assumed that the
thermocouples measure the mixed-cup temperature of each stream.
Figure 1. Heat exchanger flow patterns
In a heat exchanger, the temperature difference between the hot fluid and cold fluid may
vary along the length of the heat exchanger. This is due to the fact that the hot fluid
temperature decreases as it transfers heat to the cold fluid, while the cold fluid
temperature increases.Therefore, the overall heat transfer rate in a heat exchanger
cannot be simply calculated via equation of Newtons of Cooling,
Q = h A T
The overall heat transfer rate is expressed in terms of an overall heat transfer coefficient and a mean temperature, as follows:
Q = Uov Aov Tm
The mean temperature difference is not taken simply as the difference between the
average bulk temperature of the hot fluid and the cold fluid but calculated according to
the formula of Log Mean Temperature Difference.
where,
dQ/dt = Rate of heat transfer between two fluids
U
This part of the calculation is to use the data in Table to check the heat load and and
to select the set of values where is closest to .
HW
Hot water flow rate (
QH
FH Cp H (t1 t 2 )
CW
Hot water flow rate (
FC Cp C (T2 T1 )
QC
=
where:
QH
QC
= Heat load for cold water flow rate
FH
FC
Cold water mass flow rate
t1
t2
T1
T2
LMTD
(t1 T 2 ) (t 2 T1 )
(t T2 )
ln 1
(t 2 T1 )
Where, all variables are same with equation (1.1) and (1.2).
R
(t1 T2 )
(t2 t1 )
(t2 t1 )
(T1 t1 )
UD
equation
Q
A LMTD
Where:
Q
QH
QC
or
Q 0.5(QC QH )
U ave
value based on equation of
CW
Re(s )
Shell-side
Re( s )
for
De.Gs
Where:
De
de
12
2
do
4(1 / 2 PT 0.86PT 1 / 2 .
)
4
de
1 / 2 .do
At which:
PT
do
Pitch = 0.81inch
Viscosity, taken at average fluid temperature in the shell, lbmft -1hr-1
Gs
Ws
As
(lbmft-2hr-1)
Ws
HW
Re(t )
Tube-side
for
D.Gt
Re(t )
Where:
hi
jH .k
k 1.3 W 0.14
.(
) .( )
De Cp.
hi
jH .k
k 1.3 W 0.14
.(
) .( )
D Cp.
And
Where:
k
W
Fluid viscosity for different value of hot and cold water stream
jH
Rd
Rd
UC U D
U C .U D
Where:
UC
Clean overall heat transfer coefficient from both individual inside and
outside fluids
UD
UC
Based on equation showed before,
coefficients, the Reynolds number (i.e flow rates), the flowing fluids properties and the
Heat Exchanger diameters.
UD
value however is determined from actual heat transfer experiments at the Heat
Exchanger diameters.
It is the dirty or design heat transfer coefficient. Fouling phenomenon would reduce
UD
value. Fouling may get worse with operation, resulting in reduced heat transfer and
increasing pressure drop (and loss of flow).
Pressure drop
HW
:
The measured tube-inside pressure drop DP (tube) which will be corrected and is
CW
:
The measured shell-inside pressure drop DP (shell) which will be corrected and
Both calculated pressure and also measured pressure are considered in unit mmH 2O. In
this case, since calculated pressure drop in both of shell and tube side have been
obtained during the experiment, so its only required conversion factor to change the
value into unit of mmH2O.
x.bar
1 10 5 Pa 1mmH 2O
1bar
(9.81) Pa
Conversion factor:
where
The shell and tube-side pressure drop (DP) are measured using the differential
pressure transmitter (DPT) and then indicated digitally at the panel DP (DPI*). A selector
switch with a set of 5 solenoid valves allows both the shell and tube-sides pressure drop
i.e. DP (shell), DP (tube), to be measured one at a time.
INTRODUCTION
In many heat transfer processes, heat is transferred from one fluid to another through a
solid wall. The exchanger geometry, fluid properties, and flow rates are the parameters
that influence the rate of heat transfer. A study of these parameters forms the basis for
design of heat exchangers. The shell-and-tube exchanger consists of a bundle of tubes
with their axes parallel - much in the manner of soda straws in a carton - but supported
at various points by baffles at right angles to the tube axes, which serve to keep the
tubes fixed in space in a particular configuration, for example, with the axes spaced on
equilateral triangles, or squares, etc. Flow flows through groups of the tubes in parallel.
The tube bundle is encased in a shell, which confines the fluid which flows over the
outside of the tubes in the tube bundle. The fluid which flows within the tubes (the tubeside fluid) may make a single pass through the exchanger or multiple passes, where the
tubes are divided into groups via baffling at the ends of the exchangers and flow is
reversed at the end of the exchanger and sent back and forth through different groups
of tubes. Similarly, the fluid flowing external to the tubes (the shell-side fluid) may also
make one or more passes across the tube bundle, depending upon the configuration of
the baffles.
Two important problems in heat exchanger analysis are :
1. rating existing heat exchangers
2. sizing heat exchangers for a particular application.
Rating involves determination of the rate of heat transfer, the change in temperature of
the two fluids and the pressure drop across the heat exchanger.
Sizing involves selection of a specific heat exchanger from those currently available or
determining the dimensions for the design of a new heat exchanger, given the required
rate of heat transfer and allowable pressure drop.
The LMTD method can be readily used when the inlet and outlet temperatures of both
the hot and cold fluids are known. When the outlet temperatures are not known, the
LMTD can only be used in an iterative scheme. The most commonly used type of heat
exchanger is the shell-and-tube heat exchanger.
Shell and Tube heat exchangers are applied where high temperature and pressure
demands are significant and can be employed for a process requiring large quantities of
fluid to be heated or cooled. Due to their design, these exchangers offer a large heat
transfer area and provide high heat transfer efficiency in comparison with others.
Shell and tube heat exchangers consist of a series of tubes. One set of these tubes
contains the fluid that must be either heated or cooled. The second fluid runs over the
tubes that are being heated or cooled so that it can either provide the heat or absorb the
heat required. Shell and Tube heat exchangers are typically used for high pressure
applications (with pressures greater than 30 bar and temperatures greater than
260C. This is because the shell and tube heat exchangers are robust due to their
shape.
There are several thermal design features that are to be taken into account when
designing the tubes in the shell and tube heat exchangers. These include:
Tube diameter: Using a small tube diameter makes the heat exchanger both
economical and compact. However, it is more likely for the heat exchanger to foul
up faster and the small size makes mechanical cleaning of the fouling difficult. To
prevail over the fouling and cleaning problems, larger tube diameters can be
used. Thus to determine the tube diameter, the available space, cost and the
fouling nature of the fluids must be considered.
Tube thickness: The thickness of the wall of the tubes is usually determined to
ensure:
There is enough room for corrosion
That flow-induced vibration has resistance
Axial strength
Availability of spare parts
Hoop strength (to withstand internal tube pressure)
Buckling strength (to withstand overpressure in the shell)
Tube length: heat exchangers are usually cheaper when they have a smaller
shell diameter and a long tube length. Also, it has to be remembered that long,
thin tubes are difficult to take out and replace.
Tube pitch: when designing the tubes, it is practical to ensure that the tube pitch
(i.e., the centre-centre distance of adjoining tubes) is not less than 1.25 times the
tubes' outside diameter. A larger tube pitch leads to a larger overall shell diameter
which leads to a more expensive heat exchanger.
Tube corrugation: this type of tubes, mainly used for the inner tubes, increases
the turbulence of the fluids and the effect is very important in the heat transfer
giving a better performance.
Tube Layout: refers to how tubes are positioned within the shell. There are four
main types of tube layout, which are, triangular (30), rotated triangular (60),
square (90) and rotated square (45). The triangular patterns are employed to
give greater heat transfer as they force the fluid to flow in a more turbulent
fashion around the piping. Square patterns are employed where high fouling is
experienced and cleaning is more regular.
Baffle Design: baffles are used in shell and tube heat exchangers to direct fluid
across the tube bundle. They run perpendicularly to the shell and hold the
bundle, preventing the tubes from sagging over a long length. They can also
prevent the tubes from vibrating. The most common type of baffle is the
segmental baffle. The semicircular segmental baffles are oriented at 180 degrees
to the adjacent baffles forcing the fluid to flow upward and downwards between
the tube bundle. Baffle spacing is of large thermodynamic concern when
designing shell and tube heat exchangers. Baffles must be spaced with
consideration for the conversion of pressure drop and heat transfer. It is also
important to ensure the baffles are spaced close enough that the tubes do not
sag. The other main type of baffle is the disc and donut baffle which consists of
two concentric baffles, the outer wider baffle looks like a donut, whilst the inner
baffle is shaped as a disk. This type of baffle forces the fluid to pass around each
side of the disk then through the donut baffle generating a different type of fluid
flow.
heat exchanger. Single passes heat exchanger can prevent back mixing even more
effectively by using straight tube sections.
CALCULATION
= Qc/Qh x 100%
= ((43.5-49.2)-(30.4-47.5))/(In ((43.5-49.2))/((30.4-47.5)))
= -10.38C
Dirt Factor, Q = 0.5 (QH+QC)
= 0.5 (9007.67+236.01)
=4621.84
2.
Calculation On Heat Transfer and heat load (constant FT1) and Calculation of
= Qc/Qh x 100%
= 11.98 %
3.
Calculation On Heat Transfer and heat lost (constant FT1) and Calculation of Log
Efficiency
= Qc/Qh x 100%
= 28.21 %
= -14.76C
Calculation On Heat Transfer and heat lost (constant FT1) and Calculation of Log
= Qc/Qh x 100%
= 52.28 %
= -14.78C
5.
Calculation On Heat Transfer and heat lost (constant FT1) and Calculation of Log
= Qc/Qh x 100%
= 2846.01/2887.96 x 100%
= 98.75 %
= -14.25C
Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
= Qc/Qh x 100%
2.
Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Efficiency
= Qc/Qh x 100%
= 620.43 %
LMTD, Tlm = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,outTc,in)]
= ((32.9-48.8)-(30.5-42.9))/(In ((32.9-48.8))/((30.5-42.9)))
= -14.08C
Dirt Factor, Q = 0.5 (QH+QC)
=0.5 (660.10+4095.47)
=2377.79
3.
Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
= -2274.30 W
Efficiency
= Qc/Qh x 100%
= 290.09 %
LMTD, Tlm = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,outTc,in)]
= ((33.4-49.1)-(30.5-44.1))/(In ((33.4-49.1))/((30.5-44.1)))
= -14.62C
Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Efficiency
= Qc/Qh x 100%
= 177.35 %
LMTD, Tlm = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,outTc,in)]
= ((34.3-49.7)-(30.6-44.5))/(In ((34.3-49.7))/((30.6-44.5)))
= -14.63C
5.
Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
= Qc/Qh x 100%
= 3054.25/2887.95 x 100%
= 105.76 %
LMTD, Tlm = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,outTc,in)]
= ((35.0-49.8)-(30.8-45.4))/(In ((35.0-49.8))/((30.8-45.4)))
= -14.70C
DISCUSSION
Based on the calculation LMTD, all the values of LMTD we get negative values .Besides
that, the objective of this experiment is to evaluate and to study regarding the heat
transfer coefficient for cold and hot water, Qh and Qc. The value of heat transfer
coefficient for both shell and tube sides is calculated from the formula given in the
theory.
Then, many precaution step that we have to take, firstly to make sure the machine in
good condition we must do inspections at regular intervals will be performed on the
apparatus to ensure that the apparatus is kept in a safe and well maintained condition.
Regularly check for bare & cut electrical wires in the apparatus. Second, the hot water
connectors should not be changed during the experiment to avoid effect the reading of
temperature during experiment is conducted. Third A fuse may occasionally blow in the
apparatus when attempting to start the pump. It will be evident that this occurred
because the pump will not turn on, because there is no flow in the hot water circuit. If
this occurs then contact the lab technician for assistance. This is more apt to happen
when the apparatus is being started up after not being used for a long period of time.
The cold water flow rate will vary due to building use and cannot be prevented.
Lastly,make sure the flow of cold water can range from 0~4.7 L/min and the hot water
flow ranges from 0~1.5 L/min. It is best to operate in the middle ranges of these values.