Documente Academic
Documente Profesional
Documente Cultură
grilles
Contents
< Introduction
Contents
INTRODUCTION
Contents
RENSON Corporate Identity
General
Definitions
Louvre selector guide
Watertightness tests (HEVAC-test)
Service
Options
BUILT-IN WALL LOUVRES aluminium
411
Wall louvre, standard series, pitch 33
412
Wall louvre with chevron section blades, pitch 20
421
Wall louvre, heavy-duty series, pitch 50
422
Wall louvre with chevron section blades,
heavy-duty series, pitch 33
425
Wall louvre, extra-heavy-duty series, pitch 95
427
Wall louvre, extra-heavy-duty series,
with adjustable blades, pitch 100
451
Wall louvre, heavy-duty series, pitch 66
452
Wall louvre, heavy-duty series with
chevron section blades, pitch 66
452V
Wall louvre, heavy-duty series with
vertical chevron section blades, pitch 66
453
Wall louvre, heavy-duty series,
with aluminium coil blades, pitch 65
480
High-airflow wall louvres, pitch 60
481
Wall louvre, heavy-duty series, pitch 50
491
Storm wall louvre, pitch 33
511
Wall louvre, galvanised steel, pitch 34
521
Wall louvre, heavy-duty series,
galvanised steel, pitch 50
621
Wall louvre, stainless steel, pitch 50
surface-mounted louvres aluminium
431
Surface-mounted wall louvre, pitch 33
432
Surface-mounted, glazed-in louvre with frame
433
Pressure-relief damper
glazed-in louvres aluminium
414
Glazed-in louvre, pitch 33
414VA
Controllable louvre, pitch 33
414THF Thermally insulated window grille, pitch 33
415
Glazed-in louvre with chevron
section blades, pitch 20
415VA
Controllable louvre with chevron
section blade, pitch 20
424
Glazed-in louvre, heavy-duty series, pitch 50
428
Glazed-in louvre with chevron section blades,
heavy-duty series, pitch 95
483
High-airflow glazed-in louvre, pitch 60
484
Glazed-in louvre, heavy-duty series, pitch 50
494
Glazed-in louvre, heavy-duty series, pitch 50
425GL
Glazed-in louvre, extra-heavy-duty series, pitch 95
427GL
Glazed-in louvre with adjustable blades,
extra-heavy-duty series, pitch 100
acoustic louvres aluminium
445/86
Acoustic wall louvre, pitch 60
2
3
4
5
6
8
10
11
12
14
15
16
17
18
20
21
21
22
23
24
25
26
27
28
29
31
32
33
35
36
37
38
39
446/150
446/225
446/300
447/150
447/225
468AK/1
48
48
48
50
50
52
53
54
55
56
aluminium
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Fire-Resistant
Incendo 464
465
466
72
73
74
louvres
Fire-resistant louvre with angled blades
Fire-resistant louvre with angled blades
Fire-resistant louvre with horizontal blades
45
76
77
78
79
80
81
46
References
82
40
41
42
43
44
General
< Introduction
Material
All louvres in this brochure have been manufactured from aluminiumprofiles AlMgSi 0,5 (according EN 12020-2).
Light, strong & durable
Aluminium is a very light metal, about one third of the weight of steel.
This evolves in a lighter product, more efficient use of transport, high
loading capacity, lower material usage
Anti-corrosion
The finished aluminium louvre is corrosion persistent. In order to
improve this persistency, the louvre can be anodized or powder-
coated. On top of that, aluminium is UV-resistant and can easily handle
fluctuation in temperature.
100% recyclable
Aluminium is 100% recyclable without loss of quality.
The energy used to fuse the product takes only about 5%
of the energy used to produce the original product.
Did you know that 75% of the produced aluminium is
still circulating the world?
Finishing
Anodized in satin/bronze colour (20 micron) or powder-coated in
any RAL or Syntha Pulvin colour (40 micron).
For UK: Marine grade and special colour paint finishes available upon
request. Alternative anodising finsihes and thicknesses available upon
request.
Maintenance
The only maintenance required is cleaning the louvre.
Warranty
RENSON NV provides the installers with a warranty valid on the goods
delivered to them for 2 years from the date of production covering
all defects that may occur during normal use and maintenance of the
delivered goods. The guarantee for colourfast of the aluminium powdercoated parts is 10 years. A warranty of 5 years applies to the gloss of
the coated profiles.
Packing
Louvres will be packed in a transparent plastic foil. In case the louvre is
larger than 500 mm on one side, expanded polystyrene will be added on
the framework as protection. For very large louvres, an additional carton
packaging ensures the right protection.
Introduction >
Service
Website
On the website you can find an overview of all louvres including tech
nical drawings, leaflets and product summaries (NBS specs).
Test reports
Louvres with specific requirements have
been tested according to EN norms.
Test reports for IP-classification, burglarproof, acoustic damping and weatherability
are available on demand.
< Introduction
Family
WAT
E
E SIS
-R
T
0,5 m/s
A class
Blade
pitch
Physical
free area
K-factor
(supply)
Page
K-factor
Coeffi- Coeffi(discharge) cient Ce cient Cd
412
20
39
33,8
33,8
0,172
0,172
14
412R
20
39
33,8
33,8
0,172
0,172
77
415
20
39
33,8
33,8
0,172
0,172
37
V20-blade
415/VA
20
n.a.
n.a.
n.a.
n.a.
n.a.
38
V20-blade
415R
20
39
33,8
33,8
0,172
0,172
81
L.033.01
411
33,3
45
23,56
25,51
0,206
0,198
12
L.033.07
411R
33,3
40,5
23,56
25,51
0,206
0,198
76
L.033.01
Glazed-in louvres
414
33,3
45
23,56
25,51
0,206
0,198
33
L.033.07
414R
33,3
40,5
23,56
25,51
0,206
0,198
80
L.033.01
Glazed-in louvres
414/D
33,3
n.a.
n.a.
n.a.
n.a.
n.a.
35
L.033.01
414/VA
33,3
n.a.
n.a.
n.a.
n.a.
n.a.
35
L.033.01
Glazed-in louvres
414THF
33,3
45
33,56
25,51
0,206
0,198
36
L.033.01
Surface-mounted louvres
431
33,3
45
23,56
25,51
0,206
0,198
29
L.033.01
Surface-mounted louvres
431R
33,3
40,5
23,56
25,51
0,206
0,198
79
L.033.01
Surface-mounted louvres
432
33,3
45
23,56
25,51
0,206
0,198
31
L.033.01
Louvre box
440/11
33,3
45
23,56
25,51
0,206
0,198
56
491
33,3
26
123,5
118,1
0,09
0,092
25
494
33,3
26
123,5
118,1
0,09
0,092
43
WAT
E
WAT
E
E SIS
-R
T
WAT
E
0,5 m/s
A class
E SIS
-R
T
E
NC
WAT
E
A class
E
NC
L.050.00
E SIS
-R
T
0,5 m/s
A class
E
NC
L.033V
L.033V
0,5 m/s
Glazed-in louvres
E SIS
-R
T
E
NC
L.033.08
L.033.08
0,5 m/s
A class
422
33,3
43
61,04
61,04
0,128
0,128
16
428
33,3
43
61,04
61,04
0,128
0,128
40
421
50
49
12,57
8,91
0,282
0,335
15
L.050.00
421R
50
47
12,57
8,91
0,282
0,335
78
L.050.00
Louvre box
440/21
50
49
12,57
8,91
0,282
0,335
56
L.050.00
Glazed-in louvres
424
50
49
12,57
8,91
0,282
0,335
39
L.050HF
481
50
60
8,75
8,45
0,338
0,344
24
L.050HF
Glazed-in louvres
484
50
60
8,75
8,45
0,338
0,344
42
RE S IS
T
WAT
E
E
NC
L.050W
L.060HF
3,0 m/s
A2 class
450
50
57
10,47
16,50
0,310
0,246
480
60
76
4,81
4,52
0,456
0,470
23
41
L.060HF
Glazed-in louvres
483
60
76
4,81
4,52
0,456
0,470
L.066.01
451
66
49
12,71
11,77
0,280
0,291
20
L.066V
452
66
41
66,1
79,7
0,123
0,112
21
L.066V
L.065AL
E SIS
-R
T
E
NC
WAT
E
1 m/s
A class
E SIS
-R
T
1,5 m/s
A class
E
NC
WAT
E
A class
E
NC
Glazed-in louvres
A class
E SIS
-R
T
0,5 m/s
V20-blade
E SIS
-R
T
E
NC
V20-blade
0,5 m/s
WAT
E
WAT
E
V20-blade
Product type
E
NC
Louvre type
Blade type
Linius
Airflow
452v
66
41
60,1
79,9
0,129
0,114
21
453
65
55
13,32
17,08
0,274
0,242
22
Introduction >
Family
Blade type
Linius
Louvre type
L.095.01
L.095.01
Glazed-in louvres
mouvable blade
mouvable blade
L.060AC
L.150ACS.01
Acoustic louvres
Airflow
Page
Blade
pitch
Physical
free area
K-factor
(supply)
425
95
55
11,41
11,65
0,296
0,293
17
425/GL
95
55
11,41
11,65
0,296
0,293
44
427
100
53
11,41
11,65
0,296
0,293
18
Glazed-in louvres
427/GL
100
53
11,41
11,65
0,296
0,293
45
Acoustic louvres
445/86
60
34
9,22
13,29
0,329
0,274
46
446/150
150
34,3
38,46
34,48
0,161
0,169
48
446/225
150
34,3
37,3
41,9
0,164
0,15
48
446/300
150
34,3
45,93
45,93
0,148
0,148
48
Product type
E SIS
-R
T
E
NC
WAT
E
0,5 m/s
A class
E SIS
-R
T
K-factor
Coeffi- Coeffi(discharge) cient Ce cient Cd
Acoustic louvres
L.150ACS.01
Acoustic louvres
L.150ACS.01
Acoustic louvres
447/150
170
37
25,46
25,15
0,198
0,200
50
L.150ACL.01
Acoustic louvres
447/225
170
37
28,58
30,88
0,187
0,180
50
acoustic
Acoustic louvres
468AK
85
29
86,85
89,35
0,107
0,106
52
floor grille
Floor grilles
311
16,5
76
n.a.
n.a.
n.a.
n.a.
64
floor grille
Floor grilles
371
20,5
61
n.a.
n.a.
n.a.
n.a.
65
punched
Ventilation grilles
381
n.a.
80
n.a.
n.a.
n.a.
n.a.
63
bar blade
392
13
76
n.a.
n.a.
n.a.
n.a.
66
bar blade
394
16,5
59
n.a.
n.a.
n.a.
n.a.
67
E
NC
WAT
E
L.150ACL.01
0,5 m/s
A class
E SIS
-R
T
A class
E
NC
WAT
E
0,5 m/s
punched
Punched grilles
435R
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
61
slide blade
4032
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
59
slide blade
441
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
58
slide blade
442
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
57
door blade
Door grilles
461
20
39
33,8
33,8
0,172
0,172
68
433
3 6,5
or 99
n.a.
n.a.
n.a.
n.a.
n.a.
32
extractor
Surface-mounted louvres
door blade
Door grilles
469 Invisido
n.a.
n.a.
17,03
17,03
0,24
0,24
70
door blade
Door grilles
461AK Silendo
n.a.
27
6,13
6,13
0,40
0,40
69
burglarproof blade
Burglarproof louvres
421WK2
50
43
13,82
12,85
0,269
0,279
53
burglarproof blade
Burglarproof louvres
423WK4
50
22
27,06
27,28
0,193
0,192
55
L.033.07
Burglarproof louvres
431WK2
33,3
40,5
23,56
25,51
0,206
0,198
54
fire blade
Fire blade
464 Incendo
20
51
10,27
10,27
0,312
0,312
72
fire blade
Fire blade
465
17,5
57
8,16
8,16
0,350
0,350
73
fire blade
Fire blade
466
20
70
6,80
6,80
0,383
0,383
74
galvanised blade
511
33,3
43
92,13
84,73
0,104
0,109
26
galvanised blade
521
33,3
47
24,21
21,26
0,203
0,217
27
stainless blade
621
50
47
26,27
22,59
0,195
0,210
28
controllable
XD
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
60
Watertightness tests
< Introduction
1 m/s
E
NC
WAT
E
Without waterchannel
E SIS
-R
T
A
W ind 13 m/s
Precipit ation
75 mm/h (= 75 l/h)
A class
Suction side
air velocit y
0..0,5..1,0..1,5 m/s
D
C
Cla ss
With waterchannel
Precipit ation
75 mm/h (= 75 l/h)
Transferred
water
Suction side
air velocit y
0..0,5..1,0..1,5 m/s
D
C
B
A
Waterchannel
Transferred
water
Introduction >
Class
A
B
C
D
% water infiltration
0 - 1%
1,1 - 5%
5,1 - 20%
> 20%
Standard design
Watertightness tests
Suction air
resistance class
(Ce-coefficint)
Class
Class
96,7
95,0
93,3
< 80
B
B
C
D
98,7
98,0
96,4
88,5
B
B
B
C
4
4
4
4
98,1
96,9
89,96
90,6
87,7
< 80
< 80
B
B
C
C
C
D
D
99,5
99,0
98,0
96,9
95,6
93,7
89,0
A
A
B
B
B
C
C
4
4
4
3
3
3
3
82,0
74,8
< 80
< 80
< 80
91,0
89,3
87,1
81,6
70,7
96,7
95,0
93,3
< 80
C
D
D
D
D
C
C
C
C
D
B
B
C
D
96,6
93,9
90,0
83,5
76,3
98,0
96,1
94,2
89,5
B
C
C
C
D
B
B
C
C
3
3
3
3
3
3
3
3
3
A
A
A
B
D
D
A
A
A
A
C
D
D
A
A
B
D
D
D
A
A
A
A
A
A
A
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
100,0
99,9
99,6
94,0
56,9
28,3
100,0
100,0
100,0
99,7
80,2
11,3
7,9
100,0
99,7
91,6
50,1
16,3
14,7
100
100
100
100
99,9
99,9
99,2
84,2
81,0
< 80
C
C
D
94,2
91,8
89,5
85,7
C
C
C
C
3
3
3
3
99,3
98,11
93,39
87,46
59,97
25,03
17,94
< 80
A
B
C
C
D
D
D
D
99,93
99,46
96,91
87,92
62,24
21,99
18,08
91,3
88,3
85,1
79,4
A
A
B
C
D
D
D
C
C
C
D
4
4
4
4
4
4
4
3
3
3
3
85,4
83,6
< 80
C
C
D
92,0
90,1
88,2
83,5
B
B
C
C
3
3
3
3
2
2
2
2
2
2
2
Definitions
< Introduction
Geometric terms for louvres
Visual free area = determined by the ratio between the visual distance
between two blades (A) and the blade pitch (C).
Physical free area = determined by the ratio between the smallest gap
between two blades (B) and the blade pitch (C). Owing to peripheral
effects and assembly, a maximum deviation of 5% must be considered.
Remark: The top and bottom blades are not taken into account in
the two free area definitions.
All louvre characteristics can be calculated making use of free software
on the website www.rensonlouvres.eu
Airflow
K-factor = a value describing aerodynamic resistance to airflow.
Contrary to the free area, this value describes the link between the
airflow through the louvre and the pressure drop over it.
Ce = entry loss coefficient = a value describing the aerodynamic channelling of the airflow on entry. This value represents the ratio between the
actual airflow compared to the theoretical airflow.
Acoustic terms
A
dB(a) = the decibel (dB) in this brochure is used to characterize the noise
reduction of a louvre. The A-weight (dB(a)) shows that the acoustic tests
have been taken out according to the sensitivity of the human sound
spectrum.
Dn,e,w = weighted, element-normalized sound level difference, used to
characterise a single element like louvres.
Rw (C;Ctr) = weighted sound reduction index, used to characterise
glazing, brick walls, wall louvres, etc.
C = spectrum correction term for pink noise, always added to Rw or Dn,e,w
when the source of the noise is, for example, fast-moving traffic.
Ctr = spectrum correction term for traffic noise, always added to Rw or
Dn,e,w when the source of the noise is, for example, urban traffic.
Frequency = pitch expressed in Hertz (Hz), or the number of vibrations
per second.
Remark: in order to select the correct louvre for your application please
refer to local building regulations.
Technical terms
IP-class = international protection rating, protection rate to classify
intruding objects and water penetration. Distance to the electrical installation is measured from the outside surface of the louvre.
10
Introduction >
Drainage profiel
Options
This profile is designed for all types of aluminium rectangular wall louvres
Coupled louvres
Dust filter
This profile is designed for all louvre types
Equipped with dust filter class G4
33,5
Water channel
This profile is designed for many louvre types
It collects any water infiltration and channels it
outside
41
Dimensions
Minimum dimensions:
190x190 mm
Maximum dimensions :
1500x1200 mm
Advantages
Integrated water channel
Aesthetical mesh
No technical details visible
Applicable to louvres with water
channel
Remark: not applicable to surfacemounted louvres
18
11
411
Stock models
411 with thermal insulation panel
12
Dimensions
Satin anodised
RAL 9010
200 x 200
300 x 200
300 x 300
400 x 200
400 x 300
400 x 400
500 x 300
500 x 400
500 x 500
600 x 300
600 x 400
600 x 600
700 x 700
1000 x 500
1000 x 1000
142 x 142
34
411ZF
412ZF
50
Aarding
20
35
33
20
50
33
13
20
411
421ZF
34
34
26
11
Cross-sections
Without flange
ref. 411ZF
21
Muuranker nr.418
29
Options
Controllable
Special shape
Technical specifications
411
Airflow
K-factor (supply)
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
Physical free area
IP class (louvre with mesh; electrical installation at
least 100mm from louvre)
59 %
45 %
IP2XD
412
50
13
E SIS
-R
T
0,5 m/s
Ear
Aardingthing lug
20
E
NC
WAT
E
Without flange
ref. 412ZF
A class
Muuranker nr.418
21
Aarding
Ear
thing lug
29
Technical specifications
412
Airflow
K-factor (supply)
(EN 13030)
33,80
K-factor (discharge)
33,80
Ce coefficient
0,172
Cd coefficient
0,172
Technical data
Visual free area
14
600 x 400
35
500 x 300
50
34
34
400 x 300
412ZF
3
421ZF
20
300 x 300
34
411ZF
6
33
200 x 200
Cross-sections
26
Satin
anodised
13
Dimensions
20
Stock models
11
Typical applications
High-voltage stations
IT rooms
93 %
39 %
IP class
IP2XD
421
412ZF
50
34
50
3
451ZF
3
452ZF
65
89
20
27
35
47
50
35
66
20
50
20
Aarding
66
33
13
33
20
51
34
3
422ZF
3
421ZF
411ZF
11
50
11
Cross-sections
40
Without flange
ref. 421ZF
46
Technical specifications
421
Airflow
K-factor (supply)
K-factor (discharge)
(EN 13030)
12,57
8,91
Ce coefficient
0,282
Cd coefficient
0,335
Technical data
Visual free area
Physical free area
IP class (louvre with mesh; electrical installation at
least 100mm from louvre)
70 %
49 %
IP2XD
15
422
50
50
50
20
47
35
66
20
Aarding
33
20
50
33
20
51
13
33
422ZF
421ZF
34
34
3
451
7
412ZF
411ZFCross-sections
A class
11
WAT
E
E
NC
0,5 m/s
11
E SIS
-R
T
A
40
Without flange
ref. 422ZF
46
Technical specifications
422
Airflow
K-factor (supply)
(EN 13030)
61,04
K-factor (discharge)
61,04
Ce coefficient
0,128
Cd coefficient
0,128
Technical data
16
59 %
43 %
IP class
IP2XD
65
425
3
Cross-sections
453ZF
65
3
425ZF
89
89
87
82
427ZF
89
40
40
H
50
57
Without flange
ref. 425ZF
12
88
82
95
100
95
60
45
13
65
64
16
16
3
480ZF
16
3
2ZF
66
4
Technical specifications
425
Airflow
(EN 13030)
K-factor (supply)
11,41
K-factor (discharge)
11,65
Ce coefficient
0,296
Cd coefficient
0,293
Technical data
Visual free area
86 %
55 %
17
427
Type 427/1
Typical applications
Powers stations
High buildings
Controlled ventilation
Production halls
Type 427/2
Type 427/3
Type 427/4
Type 427/5
Technical specifications
427
Airflow (in open position)
(EN 13030)
K-factor (supply)
11,41
K-factor (discharge)
11,65
Ce coefficient
0,296
Cd coefficient
0,293
Technical data
18
88 %
53 %
H+100
12
88
100
H (#x100 + 90)
40
64
50
87
82
66
50
Type 427/1
Manual control
Minimum louvre
height: 290 mm
Type 427/2
Cable control up to 5000 mm
Minimum louvre
height: 390 mm
50
300
12,5
87,5
H
H + 100
100
40
64
50
86,5
3
453ZF
480ZF
3
425ZF
89
89
Type 427/4
220 V/24 V motor
control
Minimum louvre
height: 390 mm
Type 427/5
Air pressure control
Minimum louvre
height: 390 mm
427ZF
89
65
40
57
40
16
16
65
71
16
Type 427/3
Ultraflex control up
to max. 7 m
Minimum louvre
3
height: 690 mm
81,5
100
95
88
82
12
60
45
Without flange
ref. 427ZF
66
4
427
451
19
47
47
20
66
X = variabel
66
32
32
7.2
65
25
25
Without flange
ref. 451ZF
5
60
60
Technical specifications
451
Airflow
(EN 13030)
K-factor (supply)
13,62
K-factor (discharge)
14,91
Ce coefficient
0,271
Cd coefficient
0,259
Technical data
20
70 %
49 %
452
3
453ZF
65
89
65
WAT
E
3
452ZF
3
480ZF
3
425ZF
89
89
16
16
7
50
57
6
H
65
H
66
66
47
95
60
27
40
H
40
16
46
17
82
20
35
45
66
27
20
50
20
33
40
11
1 m/s
A class
11
87 50
50
3
451ZF
E SIS
-R
T
E
NC
3
422ZF
Cross-sections
3
421ZF
Typical applications
Application where strength, stick-proof and excellent weatherability
are important selection criteria
High-voltage cabins
HVAC
No see-through
Without flange
ref. 452ZF
46
64
70
82
Bracket
ref. 429
Technical specifications
(EN 13030)
66,1
60,1
79,7
79,9
Ce coefficient
0,123
0,129
Cd coefficient
0,112
0,114
E SIS
-R
T
1,5 m/s
E
NC
(EN 13030)
K-factor (discharge)
452V
WAT
E
Airflow
K-factor (supply)
452V
452
A class
Technical data
Visual free area
70 %
70 %
41 %
41 %
IP2XD
IP2XD
A (1m/s)
A (1,5m/s)
21
453
3
422ZF
3
421ZF
50
50
65
3
453ZF
89
65
3
480
11
65
20
32
11
34
451ZF
Cross-sections
3
452ZF
16
412ZF
Typical applications
Aesthetical
3
13
33
57
47
40
65
60
45
35
66
65
27
H
66
Aarding
20
50
20
57
40
16
46
17
Without flange
ref. 453ZF
25
46
60
Technical specifications
453
Airflow
K-factor (supply)
(EN 13030)
13,32
K-factor (discharge)
17,08
Ce coefficient
0,274
Cd coefficient
0,242
Technical data
22
69 %
55 %
480
Options
Water channel
Drainage profile
Removable mesh
Filter
Without flange
C
AL
FRE
PHY
65
89
427ZF
16
89
16
50
7
64
40
57
20
AIRFLOW
89
16
89
3
425ZF
40
87
76%
3
480ZF
RE
452ZF
Cross-sections
3
453ZF
E
A
Typical applications
Underground parkings
Industrial
applications
3
66
65
27
100
Supply
Bracket ref. 429
12
82
88
82
60
16
95
60
45
45
Without flange
ref. 480ZF
17
Technical specifications
66
4
480
Airflow
(EN 13030)
K-factor (supply)
4,81
K-factor (discharge)
4,59
Ce coefficient
0,456
Cd coefficient
0,470
Technical data
Visual free area
Physical free area
IP class (louvre with mesh; electrical installation at
least 180mm from louvre
90 %
76 %
IP2XD
Discharge
23
481
51
50
50
30
11
50
30
40
Without flange
ref. 481ZF
46
Technical specifications
481
Airflow
(EN 13030)
K-factor (supply)
8,75
K-factor (discharge)
8,45
Ce coefficient
0,338
Cd coefficient
0,344
Technical data
Visual free area
Physical free area
IP class (louvre with mesh; electrical installation at
least 105mm from louvre)
24
70 %
60 %
IP2XD
491
Cross-sections
5.6
34
26
33.5
33
33.3
.6
11
14
Supply
21
Without flange
ref. 491ZF
Muuranker nr.418
29
Technical specifications
Discharge
491
(EN 13030)
K-factor (discharge)
118,1
Ce coefficient
0,090
Cd coefficient
0,092
E SIS
-R
T
0,5 m/s
E
NC
123,5
K-factor (supply)
WAT
E
Airflow
A class
Technical data
Visual free area
57 %
26 %
25
511
26
33
Dimensions
Galvanised steel
200 x 200
300 x 300
400 x 200
34
Stock models
25
21
28
Technical specifications
511
Airflow
K-factor (supply)
(EN 13030)
92,91
K-factor (discharge)
84,73
Ce coefficient
0,104
Cd coefficient
0,109
Technical data
26
61 %
43 %
521
42
Stock models
Dimensions
Galvanised steel
400 x 400
500 x 500
600 x 600
1000 x 1000
40
34
50
43
Technical specifications
521
Airflow
K-factor (supply)
(EN 13030)
24,21
K-factor (discharge)
21,26
Ce coefficient
0,203
Cd coefficient
0,217
Technical data
Visual free area
68 %
47 %
27
621
40
34
50
42
50
43
Technical specifications
621
Airflow
K-factor (supply)
(EN 13030)
26,27
K-factor (discharge)
22,59
Ce coefficient
0,195
Cd coefficient
0,210
Technical data
28
68 %
47 %
431
Stock models
Dimensions
Satin
anodised
RAL
9010
165 x 165 mm
225 x 225 mm
325 x 325 mm
425 x 425 mm
525 x 525 mm
Nightcooling
29
33
29
20
431
Technical specifications
431
Airflow
K-factor (supply)
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
59 %
45 %
IP2XD
432
24
33
14
Cross-section
32
40
Technical specifications
432
Airflow
K-factor (supply)
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
59 %
45 %
31
433
RAL
8019
246 x 246 mm
Pressure-relief louvres
428 x 428 mm
528 x 528 mm
29
29
7,5
328 x 328 mm
7,5
29
29
32
99
7,5
173 x 173 mm
210 x 210 mm
36,5
RAL
9010
99
Satin
anodised
7,5
Length x Height
(L) x (H)
36,5
Stock models
Pressure-relief louvre
414
21
20
33
27
Technical specifications
414
Airflow
(EN 13030)
K-factor (supply)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
59 %
45 %
IP2XD
33
414
414VA
Controllable louvre
Material
Made from aluminium sections: AlMgSi 0.5 (according to EN 12020-2)
Stainless steel 304 mesh (2.3 x 2.3 mm) or insect screen (6 x 6 mm)
on request
Finishing: anodized in satin/bronze colour (20 micron) or powdercoated in any RAL or Syntha Pulvin colour (40 micron)
Dimensions
Blade pitch: 33,3 mm
Frame thickness: 24, 28 or 32 mm
Minimumdimensions: 130x130 mm
Specify on ordering: width x height in mm (overall dimensions)
Controllable in combination with 100, 130 and 150 mm hit-andmiss ventilators or with insulated aluminium door (414/D) (max size
800x800 mm H)
Fixing
Suitable for 24, 28, 32 mm glazing sections. Other thicknesses on
request.
414VA
414/D
34
24
Glazed-in louvre - 42 mm
414/D
21
20
33
27
10 13
Technical specifications
414VA
Airflow
(EN 13030)
K-factor (supply)
28,13
Ce coefficient
0,189
35
414THF
O
33
14
20
10
24 24/28/32
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
U-value
36
59 %
1,1 W/m2K
415
0,5 m/s
34
A class
24
21
13
20
27
E
NC
WAT
E
Cross-section
Technical specifications
415
Airflow
K-factor (supply)
(EN 13030)
33,80
K-factor (discharge)
33,80
Ce coefficient
0,172
Cd coefficient
0,172
Technical data
Visual free area
93 %
39 %
IP class
IP2XD
37
415VA
0,5 m/s
A class
E
NC
WAT
E
E SIS
-R
T
R
Cross-section
34
24
10 13
20
27
21
13
Technical specifications
415VA
Airflow
K-factor (supply)
34,24
Ce coefficient
0,171
38
(EN 13030)
424
Cross-section
51
24
31
35
50
42
11
Technical specifications
424
Airflow
K-factor (supply)
K-factor (discharge)
(EN 13030)
12,57
8,91
Ce coefficient
0,282
Cd coefficient
0,335
Technical data
Visual free area
Physical free area
IP class (louvre with mesh; electrical installation at
least 105mm from louvre)
70 %
49 %
IP2XD
39
428
E SIS
-R
T
0,5 m/s
E
NC
WAT
E
Cross-section
A class
51
24
31
20
33
42
11
Technical specifications
428
Airflow
(EN 13030)
K-factor (supply)
61,04
K-factor (discharge)
61,04
Ce coefficient
0,128
Cd coefficient
0,128
Technical data
Visual free area
59 %
43 %
IP class
40
IP2XD
483
PHY
38
76%
40
24
FRE
25
AL
RE
Cross-section
Typical applications
Applications with request for high air-flow
58
60
45
64
Technical specifications
483
Airflow
(EN 13030)
K-factor (supply)
4,81
K-factor (discharge)
4,52
Ce coefficient
0,456
Cd coefficient
0,470
Technical data
Visual free area
90 %
76 %
41
484
50
42
11
31
30
Technical specifications
484
Airflow
(EN 13030)
K-factor (supply)
8,75
K-factor (discharge)
8,45
Ce coefficient
0,338
Cd coefficient
0,344
Technical data
Visual free area
42
70 %
60 %
IP2XD
494
AIRFLOW
14
33
12
21
Supply
24
Technical specifications
494
(EN 13030)
K-factor (discharge)
118,1
Ce coefficient
0,090
Cd coefficient
0,092
Technical data
Visual free area
57 %
26 %
Discharge
E SIS
-R
T
0,5 m/s
E
NC
123,5
A
K-factor (supply)
WAT
E
Airflow
A class
43
425GL
38
58
82
95
40
25
64
Technical specifications
425GL
Airflow
(EN 13030)
K-factor (supply)
11,41
K-factor (discharge)
11,65
Ce coefficient
0,296
Cd coefficient
0,293
Technical data
44
86 %
55 %
427GL
40
24
66
40
12,5
87,5
100
H (#x100 + 177)
40
57,5
25
Technical specifications
427GL
Airflow
(EN 13030)
K-factor (supply)
11,41
K-factor (discharge)
11,65
Ce coefficient
0,296
Cd coefficient
0,293
Technical data
Visual free area
86 %
53 %
45
445/86
The acoustic properties of the RENSONblades have been tested by the internatio
nally recogn ized laboratory, IFT Lab
R osenheim (Germany)
46
Technical specifications
445/86
Airflow
K-factor (supply)
(EN 13030)
9,22
K-factor (discharge)
13,29
Ce coefficient
0,329
Cd coefficient
Comfort
Sound reduction in open position Rw (C;Ctr)
0,274
(EN ISO 140-10, EN ISO 717-1)
6 (-1;-2) dB
Technical data
Visual free area
Physical free area
Depth to fit
77 %
34 %
86 mm
R in dB
10,4
125
5,8
250
1,5
500
1,6
1000
4,5
2000
9,9
4000
10,8
445/86
446/150
446/225
446/300
E SIS
-R
T
0,5 m/s
E
NC
WAT
E
A class
Dimensions
Blade pitch: 150 mm
Depth to fit: 446/150: 143 mm
446/225: 218 mm
446/300: 293 mm
Frame thickness: 55mm
Height in steps of 150 mm (space between blades)
Minimum dimensions: 446/150: 300 W x 410 H
446/225: 300 W x 500 H
446/300: 311 W x 421 H
Fixing
Fixing bracket: installation with bracket no. 1428 possible
- position 1: up to 100 mm wall thickness
- position 2: for wall thickness up to 200 mm
Screws: Fix the screws from the outside through the flange
(screw holes upon request)
Pull bracket: fixation with a long pull bracket and expander bolts for
wall mounting or a short pull bracket for connection to a ventilation
channel (pull bracket rod optional)
Fixation on the backside: by screwing a hammerhead bolt to a
structural backframe
For louvres 446/300 larger than 3m, a backframe structure is
required
Fixing
Fixing
Screw from
Long pull
Short pull
bracket
bracket
the outside
bracket
bracket
pos. 1
pos.2
Sealing possibilities
Sealing gasket: suitable for reduction of contact sounds (option
sealing gasket)
PU sealing tape: against water infiltration (option PU sealing tape)
Silicone seal: seal the flange on the outside with silicone
(option silicone)
Options
Drainage profile
446/150
48
Fastening
backside with
hammerhead
bolts
446/225
446/300
446/150
446/225
446/300
Technical specifications
446/150
Airflow
446/225
446/300
(EN 13030)
K-factor (supply)
38,46
37,30
K-factor (discharge)
34,48
41,90
45,93
Ce coefficient
0,161
0,164
0,148
Cd coefficient
0,169
0,150
0,148
Comfort
Sound reduction in open
position Rw (C;Ctr)
45,93
15 (-1;-4) dB
17 (-1;-4) dB
Technical data
Visual free area
54 %
54 %
54 %
34,3 %
34,3 %
34,3 %
Watertightness
A (1 m/s)
A (1 m/s)
A (1 m/s)
Depth to fit
150 mm
225 mm
300 mm
446/150
446/225
446/300
R in dB
R in dB
R in dB
13,8
15,0
15,7
125
6,9
8,7
7,3
250
3,6
4,5
5,5
500
6,4
9,1
11,8
1000
13,4
18,2
24,0
2000
13,8
23,7
25,9
4000
12,1
15,8
22,6
f in Hz
63
The acoustic properties of the RENSONblades have been tested by the internatio
nally recogn ized laboratory, IFT Lab
R osenheim (Germany)
Water resistance tested by BSRIA laboratories.
447/150, 447/225
447/150
Fixing
Fixing
Screw from
Long pull
Short pull
bracket
bracket
the outside
bracket
bracket
pos. 1
pos.2
Fastening
backside with
hammerhead
bolts
Sealing possibilities
Sealing gasket: suitable for reduction of contact sounds (option
sealing gasket)
PU sealing tape: against water infiltration (option PU sealing tape)
Silicone seal: seal the flange on the outside with silicone (option
silicone)
Options
Drainage profile
447/225
The acoustic properties of the RENSONblades have been tested by the internatio
nally recogn ized laboratory, IFT Lab
R osenheim (Germany)
50
447/150
Detaildoorsnede
447/225
Technical specifications
447/150
447/225
Airflow
(EN 13030)
K-factor (supply)
25,46
K-factor (discharge)
25,15
30,88
Ce coefficient
0,198
0,187
Cd coefficient
0,200
Comfort
28,58
0,180
(EN ISO 140-10, EN ISO 717-1)
9 (0;-1) dB
13 (-1;-3) dB
59 %
59 %
37 %
37 %
150 mm
225 mm
447/150
447/225
R in dB
R in dB
63
5,9
13,6
125
4,2
10,1
250
2,9
4,6
Depth to fit
f in Hz
500
447/150, 447/225
5,4
7,8
1000
11,5
15,4
2000
11,2
17,8
4000
9,6
13,7
468AK/1
Dimensions
Minimum dimensions: 200 x 180 mm H
Maximum dimensions: 800 x 775 mm H
Height in 85 mm steps (blade pitch)
Depth to fit: 48 mm
Flange size: 30 mm
Typical applications
Schools
Hospitals
Elderly homes
Pitch = 85
Cross-section
Technical specifications
447/150
Airflow
(EN 13030)
K-factor (supply)
86,85
K-factor (discharge)
89,35
Ce coefficient
0,107
Cd coefficient
0,106
25 m/h
30 (-1;-2) dB
50 m/h
28 (-1;-2) dB
75 m/h
26 (-1;-2) dB
100 m/h
25 (-1;-2) dB
Comfort
Sound reduction Rw (C;Ctr)
Technical data
Visual free area
52
29 %
29 %
IP2XD
421WK2
AIRFLOW
Typical applications
Schools
Shops
Apartments
Cross-sections
50
46
Supply
10
21.5
50
VVD =
70%
50-15
50
= 43%
=
15
35
50
21.5
FVD =
40
Discharge
Special bracket
Technical specifications
421WK2
Airflow
K-factor (supply)
(EN 13030)
13,82
K-factor (discharge)
12,85
Ce coefficient
0,269
Cd coefficient
0,279
Technical data
Visual free area
70 %
43 %
53
431WK2
Technical specifications
431WK2
Airflow
K-factor (supply)
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
Physical free area
Aesthetically identical to the standard louvre 431
54
59 %
40,5 %
423
20
11
Features
Aesthetical and functional high-quality louvre:
50 with prEN 1627 till
- Burglarproof class WK4 (RC4), in accordance
47
1630 (May 2009)
- Official test report No. DE78A982
Typical applications
Banks, IT rooms, museums and jewellers.
20 (S
teel)
35
50
Cross-sections
100
20
100
Technical specifications
423
Airflow
K-factor (supply)
(EN 13030)
27,06
K-factor (discharge)
27,28
Ce coefficient
0,193
Cd coefficient
0,192
Technical data
Visual free area
70 %
22 %
IP class
IP2XD
55
440
30
Cross-sections
30
53
53
92.5
92.5
B - 84
41
B - 84
B
B + 106
56
12
L + 106
41
L - 84
12
442
121
90
130
26
20
Cross-section
Stock models
Dimensions
length x height (L) x (H)
Satin
anodised
RAL
9010
Airway opening in
cm2
Airflow at
2 Pa in m/h
Airflow at 20Pa
in m/h
265 x 90 mm
38
15
49,4
57
441
33.5
28.5
254
H=212
63
Dimensions
Depth to fit: 28.5 mm
Flange size: 21 mm
20 25
Rotating knob for louvre lengths of 500 mm and above
(possibility of pull-cord or rod operation)
21
26
Fixing
Spring clips available on request
259
Stock models
RAL
9010
Airway opening
in cm2
Airflow at
33.5
2 Pa
in m/h
28.5
113
34
140
38
260
87
217 x 212 mm
33.5
28.5
248 x 212 mm
20 25
Cross-sections
26
21
254
H=212
63
307 x 312 mm
H=212
Satin
anodised
254
Dimensions
length x height (L) x (H)
21
26
290
259
33.5
28.5
20 25
33.5
33.5
28.5
28.5
110
354
349
290
33.5
28.5
33.5
20 25
H=312
354
26
21
254
H=212
110
28.5
349
33.5
28.5
349
26
21
354
H=312
110
20 25
26
21
290
26
21
26
H=212
21
21
26
254
H=212
63
254
259
58
H=312
20 25
4032
Register to fix
Material
Made from aluminium sections: AlMgSi 0.5 (according to EN 12020-2)
Stainless steel 304 insect screen (2.3 x 2.3 mm)
Finishing: anodized in satin/bronze colour (20 micron) or powdercoated in any RAL or Syntha Pulvin colour (40 micron)
150
Dimensions
Slide knob control
Rotating knob for louvre lengths of 500 mm and above
(possibility of pull-cord operation)
Special heights on request
The louvre height must fit within 100, 130 or 150 mm modules
Fixing
Screws and plugs are included
175
200
Stock models
Satin
anodised
RAL
9010
150
Dimensions
length x height (L) x (H)
Airflow at
2 Pa in 4 m/h
49
17,6
113
40,7
260
93,6
68
24,5
113
40,7
240
200
300
175
Airway opening
in cm2
Cross-sections
4032/1
240
150
325
4032/3
4032/4
100
175
300
4032/2
300
100
200
4032/5
325
240
100
450
300
300
4
100
450
325
100
59
300
XD
Cross-sections
80, 100, 140 of 170
Technical specifications
XD1
XD2
System C
all wet areas
System A
Toilet
Closed area
14 m2
XD3
Use
Airflow
System A
Openspace kitchen
Close area
14 m2
(EN 13141-1)
Position I:
not possible
Position II:
22 m/h at 2 Pa
Position I:
39,2 m/h at 2 Pa
Position II:
50,4 m/h at 2 Pa
Position I:
63,0 m/h at 2 Pa
Position II:
87,1 m/h at 2 Pa
80 mm
(max 140 mm)
Duct diameter
Colors
RAL 9006
RAL 9010
60
435R
Cross-sections
Stock models
Diameter
RAL
9010
RAL
8019
RAL
9006
RAL
7016
Airway opening
in cm2
Airflow at
2 Pa in m/h
80 mm
27
8,3
100 mm
51
15,2
115 mm
75
23,6
145 mm
119
35,2
190 mm
204
53,1
245 mm
339
74,0
61
436
Cross-section
Stock models
62
Dimensions
(L x H)
F1
RAL
9010
RAL
8019
Airflow at
2 Pa m3/h
150 x 150
16 m3/h
150 x 200
21,9 m3/h
200 x 100
12 m3/h
200 x 200
22,1 m3/h
200 x 250
36,7 m3/h
250 x 100
18,5 m3/h
250 x 250
46,6 m3/h
300 x 100
20,2 m3/h
300 x 300
73,5 m3/h
400 x 100
28,8 m3/h
400 x 400
86,4 m3/h
500 x 500
125,9 m3/h
381
Typical applications
Kitchens, refrigerators, counters
14
17
66
80
6,5
12
Cross-sections
32
15
15
30
14
150
130
80
60
17
46
66
80
66
86
116
6,5
14
136
14
12
100
14
32
381/60
381/80
381/130
381/100
381/150
15
15
14
150
116
100
86
Satin
anodised
Gold
anodised
Ral
9010
RAL
8022
RAL
9005
Net free
area cm2
400 x 60 mm
500 x 60 mm
59
2000 x 60 mm
244
80
66
60
46
130
Dimensions
length x height (L) x (H)
136
Stock 14models
14
44
300 x 80 mm
400 x 80 mm
56
500 x 80 mm
74
600 x 80 mm
87
1000 x 80 mm
149
2000 x 80 mm
305
300 x 100 mm
61
400 x 100 mm
78
500 x 100 mm
104
43
600 x 100 mm
122
1000 x 100 mm
209
2000 x 100 mm
427
500 x 130 mm
149
1000 x 130 mm
298
2000 x 130 mm
610
500 x 150 mm
179
2000 x 150 mm
732
Other finishes and dimensions are available upon request, only for large quantities.
63
12.5
25
25
20
20
25
20
12.5
23
20
12.5
7
4
311
25
Technical specifications
311
Technical data
Visual free area
76 %
76 %
371
12.5
12.5
12.5
L
L
L
8
8
8
4 44
7
7 18
18
7 18
2525
25
Cross-sections
20
2020
Typical applications
Grilles for swimming pool drains, cellars, garages, car parks,
abattoirs, etc
To cover underfloor wiring ducts in computer rooms
14
14
14
12.5
12.5
12.5
L
L
L
8
8
8
2020
20
2323
23
2 22
18
18 6
6 14
14
18 6 14
2020
20
12.5
12.5
12.5
Technical specifications
371
Technical data
Visual free area
61 %
61 %
65
392
16
21
19
10
BL
392/1: Linear bar grille without flanged Z frame
16
21
19
10
15
15
BL
10
21
19
10
16
10
10
16
L
10
392/2: Linear bar grille
10
3with flanged Z frame
3
16
10
BL
392/3: Frameless linear bar grille
Technical specifications
392
Technical data
Visual free area
76 %
76 %
66
394
Ref. 394/08
Bars:
3000 mm or 6000 mm lengths
Ref. 394/06
Clip section:
L = 209 mm
Ref. 394/02
Frame section:
3000 mm or 6000 mm lengths
Elements
Simple clip assembly
Ref. 394/04
Typical applications
Counters, radiator frame
Ref. 394/05
Cross-sections
15
16
12
15
1216
19
210Bmm
max.
=
210
max.
210
mmmm
max.
9,5 9,5
7 7
19
U-section
Extending slide
(for widths over 200 mm)
Length: 3000 mm
Stiffening channel
13
10
13
10
209 (13)
209 (13)
193 (12)
193 (12)
58 (3)58 (3)
75 (4)75 (4)
91 (5)91 (5)
107 (6)
107 (6)
123 (7)
123 (7)
139 (8)
139 (8)
155 (9)
155 (9)
171 (10)
171 (10)
187 (11)
187 (11)
Technical specifications
394
Technical data
Visual free area
59 %
59 %
461
LxH
20
(L + 30) x (H + 30)
20
15
Min.30
Max.54
Stock models
68
Dimensions
length x height (L) x (H)
Satin
anodised
RAL
9010
200 x 100 mm
400 x 200 mm
400 x 300 mm
500 x 300 mm
147,0
464,9
600 x 400 mm
244,2
772,2
425 x 76 mm
19,2
60,7
RAL
8019
Airflow at
2 Pa in m/h
Airflow at
20 Pa in m/h
13,6
43,0
72,4
228,9
117,6
371,9
Visual
free area
Physical
free area
93%
39%
58
14 13
48
13
31
Min. 37
Max. 43
425
31
48
58
14
13
16
48
58
13
420
Min. 37
Max. 43
447
Technical specifications
Silendo
Airflow
(EN 13141-1)
Q at 1 Pa
17,7 m3/h
Q at 2 Pa
25,1 m3/h
Q at 10 Pa
56,1 m3/h
Q at 20 Pa
Comfort
Sound reduction Dn,e,w (C;Ctr)
79,4 m3/h
(EN ISO 140-10, EN ISO 717-1)
32 (0;-2) dB
Technical data
Visual free area
27%
27%
Colours
Natural
RAL 9010
RAL 8019
461AK Silendo
Invisido 469
Cross-sections
Technical specifications
Invisido type 469
Airflow
(EN 13141-1)
Q at 1 Pa
Q at 2 Pa
25,3 m/h
Q at 10 Pa
58,8 m/h
Q at 20 Pa
84,7 m/h
Comfort
70
28 (-1;0) dB
Natural
RAL 9010
RAL 9005
RAL 1015
725 mm
825 mm
925 mm
468AK/2
193
85
25
30
35
30
12
Technical specifications
468 AK/2
Airflow
K-factor (supply)
(EN 13030)
K-factor (discharge)
89,35
Ce coefficient
0,107
Cd coefficient
Q at 2 Pa - grille 292 x 193 mm
(EN 13030)
86,85
0,106
25 m/h
30 (-1;-2) dB
50 m/h
28 (-1;-2) dB
75 m/h
26 (-1;-2) dB
100 m/h
Comfort
Sound reduction in open
position Rw (C;Ctr)
25 (-1;-2) dB
(EN ISO 140-10, EN ISO 717-1)
8 (-1;-2) dB
Technical data
Visual free area
29 %
29 %
IP2XD
71
Incendo 464
20
23
Cross-section
Min. 40
Technical specifications
Incendo 464
Airflow
(EN 13030)
K-factor (supply)
10,27
K-factor (discharge)
10,27
Ce coefficient
0,312
Cd coefficient
0,312
Technical specifications
Visual free area
51 %
Ip class
IP2XD
Fire resistance
72
61 %
(EN 13501-2)
EI 60 (ho i<->o)
EI 60 (ve i<->o)
EI 60 / EW 60 (ve i<->o)
EI 30 / EW 30 (ve i<->o)
465
Technical specifications
Fire resistance: Rf 1 hour
Testreport on request (Belgian BBRI test)
Visual free area: 67%
Physical free area: 57%
Fixing
Secure the louvre in the opening
Fill the gap between the louvre and the door/wall with fire-resistant
mortar
Dimensions
length x high
(L) x (H)
465/1
(with frame)
200 x 200 mm
300 x 300 mm
400 x 200 mm
500 x 200 mm
465/2
(with frame
and backframe)
Typical applications
Fire door apartments
40
15
34,6
,5
11
,5
11
Cross-sections
15
40
34,6
40
40
73
466
Cross-sections
6
14
14
6
40
74
40
Round louvres
411R
27
19
back view
33
14
23
+ (2 x 23mm)
front view
28
30
Technical specifications
411R
Airflow
K-factor (supply)
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
76
59 %
40,5 %
IP2XD
412R
E SIS
-R
T
27
2323
0,5 m/s
A class
27
19
13
33
back view
14
20
E
NC
WAT
E
+ (2 x 23mm)
front view
34
3628
30
Technical specifications
412R
Airflow
K-factor (supply)
(EN 13030)
33,80
K-factor (discharge)
33,80
Ce coefficient
0,172
Cd coefficient
0,172
Technical data
Visual free area
93 %
39 %
IP class
IP2XD
77
421R
25
35
50
60
57
Technical specifications
421R
Airflow
K-factor (supply)
K-factor (discharge)
(EN 13030)
12,57
8,91
Ce coefficient
0,282
Cd coefficient
0,335
Technical data
Visual free area
78
70 %
47 %
IP2XD
431R
18
14
33
40
Technical specifications
431R
Airflow
K-factor (supply)
(EN 13030)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
59 %
40,5 %
IP2XD
79
414R
23
42
19
14
33
27
Technical specifications
414R
Airflow
(EN 13030)
K-factor (supply)
23,56
K-factor (discharge)
25,51
Ce coefficient
0,206
Cd coefficient
0,198
Technical data
Visual free area
80
59 %
40,5 %
IP2XD
415R
20
27
Cross-section
42
13
24
42
Technical specifications
415R
Airflow
K-factor (supply)
(EN 13030)
33,80
K-factor (discharge)
33,80
Ce coefficient
0,172
Cd coefficient
0,172
Technical data
Visual free area
Physical free area
IP class
93 %
39 %
IP2XD
81
References
82
References
83
C r e a t i n g
h e a l t h y
s p a c e s
RENSON Ventilation NV
IZ 2 Vijverdam Maalbeekstraat 10 8790 Waregem Belgium
Tel. +32 (0)56 62 71 11 Fax +32 (0)56 60 28 51
info@renson.be www.renson.eu
V E N T I L AT I O N
S U N P ROT E C T I O N
OUTDOOR
06/14
L2006201
RENSON reserves the right to make technical changes to the products shown.
The latest brochures may be downloaded from www.renson.eu
UK/Export - English
Dealer