Documente Academic
Documente Profesional
Documente Cultură
The Fig 1 shows a 3 phase rectifier feeding a linear load made up of a resistor. The circuit is
mainly designed for a 220V AC input. The 3phase AC input is rectified using a bridge rectifier
having 3 legs. The AC input is first given to a 3 phase VI measurement block to get the
instantaneous voltages and currents. These instantaneous active and reactive powers (P and Q)
are obtained by using the P-Q transformation block. The linear load is made up of a resistive
load of 10k. The output is also connected to a 1k resistive load.
Generally, the THD of a balanced load is comparatively improved as the neutral current is
always zero. Hence the use of neutral conductors should be reduced in order to obtain a
improved power factor by reducing the load imbalances. Thus, this reduces the THD in the
circuit.
The simulation was carried out and the below results were observed.
For an AC input voltage of 220V-50Hz, the observed voltage is 300V. This is due to the internal
inductance of 16.58mH and resistance of 0.8929.
The Fig 2b.1, Fig 2b.2 and Fig 2b.3 shows the input current from the 3 phases A, B and C is
found to be 0.02A. The THD is calculated with respect to the input currents.
Fig 7: Total Harmonic Distortion analysis of currents across Phase A, Phase B and Phase C
The Fig 7 shows the Total Harmonic Distortion (THD) spectrum of the currents flowing through
the 3 phases. For a fundamental frequency of 50Hz and with the number of cycles considered is
2, the THD is found to be around 4.60%.
The Fig 8 shows a 3 phase rectifier feeding a non-linear load made up of a resistor. The circuit is
mainly designed for a 220V AC input. The 3phase AC input is rectified using a bridge rectifier
having 3 legs. The AC input is first given to a 3 phase VI measurement block to get the
instantaneous voltages and currents. These instantaneous active and reactive powers (P and Q)
are obtained by using the P-Q transformation block. The non-linear load is made up of an
asynchronous machine.
The THD of a non-linear load is high compared to that of a linear load. This can be proved
seeing the waveforms obtained from the simulation.
The Fig 2b.1, Fig 2b.2 and Fig 2b.3 shows the input current from the 3 phases A, B and C is
found to be 22A. The THD is calculated with respect to the input currents.
Fig 11 shows the output voltage from the 3 phase rectifier circuit. The output from the rectifier is
seen to be distorted and has a large number of ripples. The output from the rectifier has a
magnitude almost equal to 10V.
Fig 11 shows the active and reactive powers from the circuit. the active power is found to be
around 500W and the reactive power is found to be nearly equal to 10W.
The Fig 12.shows the current Iabc from the VI measurement block. it can be seen that all the 3
phase currents do not have the same magnitude. This is due to the non-linear load.
Fig 13: Total Harmonic Distortion analysis of currents across Phase A, Phase B and Phase C
The Fig 13 shows the Total Harmonic Distortion (THD) spectrum of the currents flowing
through the 3 phases. For a fundamental frequency of 60Hz and with the number of cycles
considered is 2, the THD is found to be around 28.75%.
INFERENCES
Seeing the above obtained graphs and THD spectrum it can thereby be verified that, the THD of
a linear load is comparatively less than the THD obtained from a linear load.
Thus balanced loads are preferred in order to reduce the THD. If the THD is reduces the power
factor is also improved. Improved power factor implies the power factor being close to unity.
This thereby will improve the overall efficiency of the system.