Product

Data

38EYX 50 Hz
Heat Pump
Sizes 024, 036, 048, and 060

The 38EYX 50 Hertz Outdoor


Sections of Split-System Heat Pumps
are designed for quiet, reliable heating
during the winter and cooling during
the summer with Puron refrigerant.
These heat pump systems provide
economy of operation through energy
conservation when used with
components designated by the
manufacturer. The 38EYX recovers
heat for indoor comfort from outdoor
air during the heating season and, by
automatically reversing the
refrigerant system, remove indoor
heat and excess humidity during the
cooling season.

AVAILABLE OPTIONS
Electrical Range The 024 size unit
is available in 230V, single phase. The
036, 048, and 060 sizes are 400V,
three phase.
Size Range The 38EYX is
available in nominal sizes 024, 036,
048, and 060 to meet the needs of
residential and light commercial
applications.
Puron, the environmentally sound
refrigerantThe 38EYX uses Puron,
the environmentally sound refrigerant
that provides homeowners with
additional peace of mind because
Puron has zero ozone-depletion
potential.
In addition, thanks to the performance
advantage of Puron, the 38EYX is
extremely efficient. Maximum
performance and efficiency are made
possible through the use of the FX4C
fan coils, which are custom made for
Puron applications.

Copyright 2005 Carrier Corporation

Form 38EYX-C3PD

Puron refrigerant also protects


homeowners against the future cost of
service from the potentially increased
cost of servicing units using R-22 as it
is phased out.
Compressor The 38EYX features a
scroll compressor. These compressors
are specially designed for Puron
applications, with its thicker shell and
an anti-reverse rotation device in scroll
compressors for superior reliability and
quiet operation. In addition, each
compressor is mounted on rubber
isolators for additional sound reduction.
For improved serviceability, all models
are equipped with a compressor
terminal plug. Continuous operation is
approved down to 34C in the heating
mode and down to 13C in the cooling
mode.
Built-in-Reliability Components
Includes a suction-tube accumulator
that reduces the amount of liquid
refrigerant that reaches the
compressor; high pressure switch to
prevent excessive pressure build-up;
low-pressure switch to stop the
compressor if refrigerant charge is
lost; crankcase heater on 036-060 units
to keep compressor oil warm and free
of refrigerant for maximum lubricity;
internal compressor relief valve for
high-pressure protection.
3-Phase Monitor Board Control
board that monitors the electrical

phase and prevents compressor


operation if wired incorrectly.
Discharge Silencer Minimizes low
frequency sound and pressure
pulsation generated by compressor
discharge gas.
Defrost Control Board
Incorporates a defrost relay, defrost
timer, and low-voltage terminations.
The defrost control is a time and
temperature initiation/termination
control which includes 4 fieldselectable (DIP switch) time periods of
30, 60, 90, and 120 minutes. The
control includes built-in 5-minute
compressor delay for short cycle
protection. This control also includes a
field-selectable (DIP switch) Quiet
Shift mode, which if selected, maintains
quiet operation during defrost.
Weather-Protective Cabinet The
cabinet is constructed with galvanized,
prepainted steel, providing each unit
with a finish that will last for many
years.
All screws on cabinet exterior are
coated for a long-lasting rust-resistant,
quality appearance.

and is designed for optimum heat


transfer and corrosion protection. The
vertical air discharge carries the sound
and air up and away from adjacent
patio areas and foliage. Coils can be
cleaned with a common garden hose.
External Service Valves Both
service valves are brass, front seating
type. Valves are externally located
so refrigerant tube connections can
be made quickly and easily. Each
valve has a service port for ease of
checking operating refrigerant
pressures. The 38EYX has sweat field
connections.
Sound Hood All sizes have a
compressor sound hood for noise
attenuation.
Safety The design and construction
are in compliance with European
standards to bear the CE Mark.
Operating Range Minimum
outdoor operating ambient in cooling
mode is 13C, maximum is 52C.
Minimum outdoor operating range for
heating mode is -34C, maximum is
19C.

Unit Design All units are equipped


with totally enclosed fan motors for
greater reliability under adverse
weather conditions. The large,
wraparound coil uses copper tube and
epoxy coated, enhanced aluminum fin

Quality Assurance
ISO 9001:2000

REGISTERED

IP24

REGISTERED QUALITY
SYSTEM

Model number nomenclature


38EYX

024

Electric Heat Pump

Packaging
Series

Nominal Capacity
024 24,000 Btuh (7.0 kW)
048 48,000 Btuh (14.1 kW)
036 36,000 Btuh (10.6 kW) 060 60,000 Btuh (17.6 kW)

Electrical
7 230-1-50
9 400-3-50

Physical data
UNIT SIZE/SERIES
OPERATING WT (Kg)

024-7A

036-9A

048-9A

060-9A

65.8

83.9

99.3

111.6

4.82

6.35

COMPRESSOR

Scroll

REFRIGERANT
Control
Charge (Kg) @ 7.6m
CONDENSER FAN
Air Discharge
Air Qty (L/S)
Nominal Motor RPM (50 Hz)
CONDENSER COIL
Face Area (m 2)

Puron (R410A)
Piston
2.61

3.69

Propeller Type, Direct Drive


Vertical
708

1274

1416

1180

900

900

900

900

1.00

1.49

2.06

1.72

Sweat

CONNECTION (In./mm ID)


Vapor
Liquid

5/8/15.88

REFRIGERANT TUBES*
(In./mm OD)
Vapor
Liquid

5/8/15.88

3/4/19.05

7/8/22.23
3/8

3/4/19.05

7/8/22.23

1-1/8/28.58

3/8

* Tube sizes are for lengths up to 15.2m and/or 6.1m vertical differential.
NOTE: See unit Installation Instructions for proper installation.

METERING DEVICE
UNIT
SIZE

OUTDOOR
PISTON

INDOOR
PISTON

024-7A

40

52

036-9A

49

65

048-9A

65

76

060-9A

73

88

Accessories
ORDERING NUMBER
KAACH1201AAA

DESCRIPTION
Crankcase Heater Size 024

KAAFT0101AAA

Evaporator Freeze Thermostat All Sizes

KHAIR0101AAA

Isolation Relay All Sizes

Standard

Cycle Protector All Sizes

KSAHS1501AAA

Compressor Start Assist (Capacitor/Relay) Size 024

KAACS0101PTC

Start Assist (PTC) Size 024

KSATX0201PUR

TXV Size 024

KSATX0301PUR

TXV Size 036

KSATX0401PUR

TXV Size 048

KSATX0501PUR

TXV Size 060

KHALS0401LLS

Liquid Solenoid Valve (LSV) All Sizes

Standard

Filter Drier Bi-flow All Sizes

KSALA0401AAA*

MotorMaster Control Size 024

KSALA0501AAA*

MotorMaster Control Sizes 036, 048, 060

* Isolation relay required.


Consult low-ambient controller Installation Instructions for application.
N/A Not applicable in this application.

THERMOSTAT

DESCRIPTION

TSTATCCNHP01-C

Thermostat, Auto Changeover, Non-Programmable, F/C, 2-Stage Heat, 1-Stage Cool

TSTATCCPHP01-B

Thermostat, Auto Changeover, 7-Day Programmable, F/C, 2-Stage Heat, 1-Stage Cool

TSTATXXSEN01-B

Outdoor Air Temperature Sensor

Accessory description and usage (Listed alphabetically)


1. Compressor Start Assist-Capacitor/Relay Type
Start capacitor and start relay gives hard boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds15.2m.
Installations where outdoor design temperature exceeds 40.6C.
Replacement installations with hard shutoff expansion valve or liquid line solenoid on indoor coil.
Units installed with low-ambient controller.
2. Compressor Start AssistPC Type
Solid state electrical device which gives a soft boost to the compressor at each start-up.
SUGGESTED USE: Suggested in installations with marginal power supply.
Use only on single phase units.
3. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on
restart and minimizes the chance of liquid slugging.
NOTE: Some heat pumps are factory supplied with a crankcase heater. See accessory list for units that come standard with a crankcase heater. For units that do
not use the guideline below.
SUGGESTED USE: Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
4. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where low-ambient controller has been added.
5. Filter DrierBi-flow
A device for removing contaminants from refrigerant circulating in an air conditioner or heat pump system; bi-flow for heat pumps.
SUGGESTED USE: All field-connected split-system units.
6. Isolation Relay
An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.
SUGGESTED USE: All heat pumps where low-ambient controller has been added.
7. Liquid-Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit
to control refrigerant off cycle migration in the heating mode.
SUGGESTED USE: An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode.
Consult Equipment Distributor.
8. MotorMaster Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to 28C, it maintains condensing temperature at 37.8 5.5C.
SUGGESTED USE: Cooling operation at outdoor temperatures below 13C.
All commercial installations.
9. Outdoor Air Temperature Sensor
A thermistor type sensor that responds to changes in outdoor temperature and provides a signal to the room thermostat for display of outdoor temperature.
USAGE GUIDELINE: Required if outdoor temperature display is desired on the room thermostat. See Accessory list for compatible thermostats.
10. Room Thermostat
A 24 volt temperature control that cycles the heating and cooling equipment based on room demand. Both programmable and non-programmable versions are
available.
USAGE GUIDELINE: Required for equipment control.
11. Thermostatic Expansion Valve (TXV) Bi-Flow
A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator.
USAGE GUIDELINE: All installations where low ambient cooling is needed.
Installations with interconnecting tubing that exceeds 15m.
All commercial installations.

Electrical data
OPER VOLTS*

OUTDOOR
UNIT

V/PH

Max

Min

024-7A

230-1

253

187

COMPRESSOR

048-9A

400-3

440

360

060-9A

MAX
LENGTH MAX FUSE
(m)
OR CKT
60C/ 75C BKR AMPS

RLA

FAN
FLA

MRC

61.0

12.5

0.60

16.2

14/14

14.9/14.3

48.0

6.4

0.70

8.7

14/14

26.8/25.3

15

64.0

9.0

0.70

12.0

14/14

20.1/18.9

20

74.0

10.6

0.70

14.0

14/14

17.1/16.5

20

LRA

036-9A

MIN WIRE
SIZE**
60C/ 75C

25

**

Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
Time-delay fuse.
Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
If wire is applied at ambient greater than 30C (86F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathedcable (NM), trade name ROMEX, shall be that of 60C (140F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.
If other than uncoated (non-plated), 60 or 75C (140 or 167F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
FLA Full Load Amps
LRA Locked Rotor Amps
MRC Maximum Running Current
RLA Rated Load Amps
NOTE: Control circuit is 24v on all units and requires external power source. Copper wire must be used from disconnect to unit. All motors/compressors contain internal overload protection.

A-weighted sound power


UNIT
SIZE

SOUND
LEVEL
(dBA)

125

250

500

1000

2000

4000

8000

024-7A
036-9A
048-9A
060-9A

72
72
72
74

76.0
71.5
67.5
70.0

69.0
68.0
66.0
68.5

66.0
68.5
69.5
68.5

65.5
67.5
67.5
69.0

61.5
65.5
63.0
65.5

58.0
61.5
60.5
61.5

56.0
53.5
57.0
55.5

TYPICAL OCTAVE BAND (without tone adjustment)

Note: Tested in accordance with ARI Standard 270-95.

Detailed cooling capacities* (S.I.)


CONDENSER ENTERING AIR TEMPERATURES C

COIL
AIR

L/S

28

32

36

40

44

48

52

Capacity
kW

Capacity
kW

Capacity
kW

Capacity
kW

Capacity
kW

Capacity
kW

Capacity
kW

Sys.

Sys.

Sys.

Sys.

Sys.

Sys.

Sys.

(C)
Power
Power
Power
Power
Power
Power
Power
EWB Total Sens kW** Total Sens kW** Total Sens kW** Total Sens kW** Total Sens kW** Total Sens kW** Total Sens kW**

38EYX0247A Outdoor Section With FX4CSX024 Indoor Section


330

380

425

22
20
18
16
14
22
20
18
16
14
22
20
18
16
14

7.35
7.17
6.93
6.71
6.63
7.39
7.20
6.99
6.79
6.77
7.40
7.23
7.02
6.85
6.84

3.86
4.64
5.49
6.45
6.63
3.93
4.77
5.70
6.79
6.77
4.00
4.88
5.88
6.85
6.84

1.78
1.77
1.76
1.74
1.74
1.80
1.80
1.78
1.77
1.77
1.83
1.82
1.81
1.79
1.79

22
20
18
16
14
22
20
18
16
14
22
20
18
16
14

11.22
10.76
10.21
9.58
9.55
11.29
10.86
10.36
9.92
9.93
11.33
10.52
10.47
10.18
10.18

5.99
7.22
8.52
9.58
9.55
6.16
7.54
9.04
9.92
9.93
6.31
7.13
9.49
10.18
10.18

2.69
2.66
2.63
2.62
2.62
2.74
2.71
2.68
2.67
2.67
2.78
2.77
2.73
2.72
2.72

22
20
18
16
14
22
20
18
16
14
22
20
18
16
14

14.88
14.47
14.05
13.42
13.19
14.94
14.54
14.13
13.59
13.48
14.99
14.61
14.17
13.80
13.79

7.76
9.30
11.07
12.72
13.19
7.87
9.51
11.41
13.23
13.48
8.04
9.82
11.84
13.80
13.79

3.61
3.59
3.56
3.55
3.55
3.66
3.64
3.62
3.60
3.59
3.74
3.72
3.70
3.67
3.68

22
20
18
16
14
22
20
18
16
14
22
20
18
16
14

19.59
18.56
17.25
16.14
16.05
19.64
18.61
17.32
16.22
16.17
19.67
18.67
17.38
16.32
16.30

10.37
12.34
14.22
15.94
16.05
10.44
12.48
14.40
16.19
16.17
10.51
12.60
14.59
16.32
16.30

5.21
5.15
5.11
5.08
5.08
5.24
5.18
5.13
5.10
5.10
5.26
5.20
5.15
5.12
5.12

7.18
7.00
6.79
6.49
6.45
7.20
7.01
6.85
6.61
6.61
7.22
7.04
6.87
6.71
6.71

3.81
4.62
5.53
6.36
6.45
3.88
4.73
5.78
6.61
6.61
3.95
4.85
5.98
6.71
6.71

1.99
1.98
1.96
1.94
1.94
2.01
2.00
1.98
1.97
1.97
2.03
2.02
2.01
2.00
2.00

6.99
6.84
6.57
6.26
6.25
7.01
6.89
6.64
6.42
6.42
7.03
6.90
6.68
6.53
6.53

3.74
4.60
5.48
6.26
6.25
3.82
4.77
5.75
6.42
6.42
3.89
4.88
5.98
6.53
6.53

2.18
2.16
2.15
2.13
2.13
2.21
2.19
2.17
2.16
2.16
2.23
2.21
2.19
2.19
2.19

6.85
6.62
6.32
6.03
6.03
6.87
6.66
6.39
6.21
6.21
6.84
6.69
6.44
6.32
6.32

3.72
4.53
5.39
6.03
6.03
3.81
4.70
5.68
6.21
6.21
3.83
4.86
5.93
6.32
6.32

2.38
2.36
2.34
2.33
2.33
2.41
2.39
2.37
2.36
2.36
2.43
2.41
2.39
2.39
2.39

6.58
6.34
6.04
5.80
5.80
6.61
6.39
6.11
5.97
5.97
6.63
6.42
6.16
6.08
6.08

3.62
4.44
5.29
5.80
5.80
3.73
4.62
5.58
5.97
5.97
3.81
4.79
5.81
6.08
6.08

2.59
2.57
2.55
2.54
2.54
2.61
2.59
2.58
2.57
2.57
2.64
2.62
2.60
2.60
2.60

6.28
6.04
5.73
5.54
5.54
6.31
6.08
5.80
5.70
5.71
6.32
6.10
5.85
5.81
5.81

3.51
4.33
5.16
5.54
5.54
3.62
4.52
5.46
5.70
5.71
3.71
4.69
5.69
5.81
5.81

2.81
2.79
2.77
2.77
2.76
2.84
2.82
2.80
2.79
2.79
2.86
2.84
2.82
2.82
2.82

5.94
5.70
5.39
5.26
5.27
5.96
5.74
5.46
5.42
5.42
5.97
5.76
5.52
5.51
5.51

3.39
4.20
5.02
5.26
5.27
3.49
4.40
5.30
5.42
5.42
3.58
4.57
5.52
5.51
5.51

3.04
3.02
3.00
2.99
2.99
3.07
3.05
3.03
3.02
3.02
3.09
3.07
3.05
3.05
3.05

5.43
6.55
7.56
7.80
7.80
5.69
6.99
8.10
8.14
8.14
5.92
7.38
8.38
8.39
8.39

4.04
4.01
3.99
3.98
3.98
4.09
4.06
4.03
4.03
4.03
4.14
4.11
4.09
4.08
4.08

8.87
8.17
7.44
7.39
7.39
8.97
8.29
7.70
7.70
7.71
9.02
8.38
7.95
7.95
7.95

5.24
6.34
7.30
7.39
7.39
5.50
6.77
7.70
7.70
7.71
5.74
7.18
7.95
7.95
7.95

4.35
4.32
4.30
4.29
4.29
4.40
4.37
4.35
4.35
4.35
4.45
4.42
4.40
4.40
4.40

6.82
8.39
10.03
10.96
10.96
6.95
8.65
10.45
11.21
11.21
7.15
9.04
11.03
11.47
11.47

5.86
5.82
5.79
5.78
5.78
5.91
5.88
5.84
5.83
5.83
5.99
5.96
5.92
5.92
5.92

11.69
11.28
10.72
10.40
10.40
11.71
11.32
10.81
10.62
10.62
11.74
11.36
10.91
10.85
10.85

6.53
8.10
9.72
10.40
10.40
6.67
8.36
10.13
10.62
10.62
6.87
8.75
10.67
10.85
10.85

6.34
6.31
6.27
6.25
6.25
6.39
6.36
6.32
6.31
6.31
6.48
6.44
6.40
6.40
6.40

8.68
10.70
12.56
13.18
13.18
8.74
10.82
12.73
13.28
13.28
8.79
10.94
12.89
13.38
13.38

7.34
7.27
7.21
7.19
7.19
7.36
7.29
7.23
7.22
7.22
7.38
7.31
7.25
7.24
7.24

14.27
13.64
12.73
12.48
12.49
14.28
13.66
12.76
12.58
12.58
14.28
13.68
12.81
12.67
12.67

8.17
10.25
12.13
12.48
12.49
8.22
10.35
12.29
12.58
12.58
8.27
10.46
12.44
12.67
12.67

7.78
7.71
7.64
7.64
7.64
7.80
7.74
7.67
7.66
7.66
7.83
7.76
7.69
7.69
7.69

38EYX0369A Outdoor Section With FX4CSX036 Indoor Section


500

560

640

10.93
10.46
9.77
9.23
9.22
11.01
10.59
9.94
9.58
9.58
11.06
10.66
10.08
9.85
9.85

5.91
7.19
8.37
9.23
9.22
6.10
7.56
8.91
9.58
9.58
6.28
7.88
9.40
9.85
9.85

2.95
2.92
2.90
2.89
2.89
3.00
2.97
2.95
2.94
2.94
3.05
3.02
2.99
2.99
2.99

10.70
10.08
9.37
8.90
8.90
10.73
10.22
9.54
9.25
9.25
10.77
10.31
9.67
9.52
9.53

5.87
7.07
8.20
8.90
8.90
6.03
7.46
8.76
9.25
9.25
6.21
7.83
9.24
9.52
9.53

3.20 10.31 5.76


3.17 9.66 6.91
3.15 8.93 8.02
3.14 8.56 8.56
3.14 8.56 8.56
3.25 10.42 5.99
3.22 9.79 7.32
3.20 9.10 8.56
3.19 8.90 8.90
3.19 8.90 8.90
3.30 10.49 6.21
3.27 9.89 7.71
3.24 9.25 9.03
3.24 9.17 9.17
3.24 9.17 9.17

3.46 9.88 5.60


3.43 9.20 6.74
3.41 8.46 7.80
3.40 8.19 8.19
3.40 8.20 8.20
3.51 9.98 5.85
3.48 9.33 7.16
3.46 8.63 8.34
3.45 8.53 8.53
3.45 8.53 8.53
3.56 10.04 6.07
3.53 9.43 7.56
3.51 8.79 8.79
3.50 8.80 8.80
3.50 8.80 8.80

3.74
3.71
3.69
3.68
3.68
3.79
3.76
3.74
3.74
3.74
3.84
3.81
3.79
3.79
3.79

9.40
8.70
7.95
7.80
7.80
9.49
8.84
8.17
8.14
8.14
9.55
8.92
8.38
8.39
8.39

38EYX0489A Outdoor Section With FX4CSX048 Indoor Section


650

730

800

14.46
14.16
13.59
12.93
12.78
14.50
14.21
13.71
13.11
13.06
14.54
14.23
13.83
13.38
13.38

7.59
9.26
10.94
12.50
12.78
7.71
9.48
11.36
13.01
13.06
7.89
9.78
11.99
13.38
13.38

4.07
4.03
4.01
4.00
4.00
4.12
4.09
4.06
4.05
4.04
4.20
4.17
4.15
4.13
4.13

14.19
13.69
13.11
12.46
12.38
14.21
13.77
13.22
12.66
12.66
14.17
13.86
13.33
12.97
12.97

7.53
9.09
10.73
12.24
12.38
7.64
9.34
11.14
12.66
12.66
7.76
9.73
11.76
12.97
12.97

4.48
4.45
4.43
4.42
4.42
4.53
4.50
4.48
4.46
4.46
4.61
4.58
4.56
4.55
4.55

13.63
13.17
12.59
11.96
11.95
13.67
13.23
12.69
12.22
12.22
13.72
13.30
12.80
12.51
12.51

7.30
8.87
10.52
11.96
11.95
7.45
9.12
10.93
12.22
12.22
7.66
9.50
11.55
12.51
12.51

4.92
4.89
4.87
4.85
4.85
4.97
4.94
4.92
4.90
4.90
5.05
5.02
5.00
4.98
4.98

13.06
12.61
12.03
11.48
11.48
13.09
12.67
12.13
11.74
11.74
13.11
12.72
12.24
12.02
12.02

7.08
8.65
10.29
11.48
11.48
7.22
8.90
10.71
11.74
11.74
7.41
9.29
11.32
12.02
12.02

5.38
5.35
5.32
5.31
5.31
5.43
5.40
5.37
5.36
5.36
5.51
5.49
5.45
5.44
5.44

12.41
11.98
11.41
10.96
10.96
12.44
12.03
11.51
11.21
11.21
12.46
12.08
11.61
11.47
11.47

38EYX0609A Outdoor Section With FX4CSX060 Indoor Section


850

875

900

18.78
17.75
16.58
15.51
15.51
18.82
17.81
16.64
15.64
15.64
18.85
17.86
16.70
15.76
15.76

10.03
12.03
13.92
15.51
15.51
10.10
12.16
14.11
15.64
15.64
10.17
12.29
14.29
15.76
15.76

5.65
5.59
5.53
5.51
5.50
5.67
5.61
5.55
5.52
5.52
5.69
5.63
5.58
5.55
5.55

18.04
17.06
15.89
14.98
14.98
18.08
17.10
15.95
15.10
15.10
18.10
17.15
16.00
15.22
15.22

9.76
11.73
13.61
14.98
14.98
9.83
11.86
13.79
15.10
15.10
9.90
11.99
13.97
15.22
15.22

6.05
5.98
5.93
5.91
5.91
6.07
6.01
5.96
5.93
5.93
6.09
6.03
5.98
5.95
5.95

17.22
16.31
15.19
14.43
14.43
17.25
16.35
15.24
14.55
14.55
17.27
16.39
15.29
14.66
14.66

9.43
11.42
13.29
14.43
14.43
9.50
11.55
13.48
14.55
14.55
9.57
11.67
13.65
14.66
14.66

6.46
6.40
6.34
6.32
6.32
6.49
6.42
6.37
6.34
6.34
6.51
6.44
6.39
6.36
6.36

16.37
15.49
14.40
13.82
13.82
16.39
15.53
14.45
13.93
13.93
16.41
15.57
14.51
14.04
14.04

9.08
11.07
12.94
13.82
13.82
9.14
11.20
13.12
13.93
13.93
9.20
11.32
13.29
14.04
14.04

6.90
6.83
6.77
6.75
6.75
6.92
6.85
6.80
6.78
6.78
6.94
6.88
6.82
6.80
6.80

15.41
14.62
13.58
13.18
13.18
15.40
14.66
13.63
13.28
13.28
15.41
14.69
13.68
13.38
13.38

* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length
and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
Sensible capacities shown are based on 27C entering air at the indoor coil. For sensible capacities at other than 27C, deduct 245 kW per 480
L/S of indoor coil air for each degree below 27C, or add 245 kW per 480 L/S of indoor coil air per degree above 27C.
** System kW is total of indoor and outdoor unit kilowatts.
EWB Entering Wet Bulb
L/S Liters per second

Heat pump heating performance (S.I.)


OUTDOOR COIL ENTERING AIR TEMPERATURES C
16
INDOOR
AIR
(C)
EDB

L/ S

Capacity
kW

8
Total
Power

Total Integ kW*

Capacity
kW

0
Total
Power

Total Integ kW*

Capacity
kW

4
Total
Power

Total Integ kW*

Capacity
kW

8
Total
Power

Total Integ kW*

Capacity
kW

12
Total
Power

Total Integ kW*

Capacity
kW

16
Total
Power

Total Integ kW*

Capacity
kW

20
Total
Power

Total Integ kW*

Capacity
kW

Total
Power

Total Integ kW*

38EYX0247A Outdoor Section With FX4CSX024 Indoor Section


12
15
18
21
24

330
380
425
330
380
425
330
380
425
330
380
425
330
380
425

3.61
3.65
3.69
3.54
3.58
3.62
3.47
3.52
3.55
3.41
3.45
3.48
3.35
3.38
3.41

3.32
3.36
3.39
3.26
3.30
3.33
3.20
3.23
3.27
3.14
3.17
3.20
3.08
3.11
3.14

1.28
1.27
1.27
1.37
1.36
1.36
1.47
1.45
1.45
1.56
1.55
1.55
1.66
1.66
1.65

4.71
4.76
4.80
4.64
4.69
4.73
4.58
4.62
4.66
4.51
4.56
4.59
4.44
4.49
4.53

500
560
640
500
560
640
500
560
640
500
560
640
500
560
640

5.29
5.35
5.42
5.19
5.27
5.33
5.10
5.17
5.24
5.02
5.08
5.15
4.93
5.00
5.06

4.87
4.92
4.98
4.77
4.85
4.90
4.69
4.75
4.81
4.61
4.67
4.73
4.54
4.59
4.65

1.96
1.98
2.00
2.08
2.08
2.11
2.21
2.21
2.22
2.33
2.34
2.35
2.47
2.47
2.49

6.91
6.99
7.06
6.81
6.89
6.96
6.71
6.79
6.86
6.61
6.69
6.76
6.50
6.57
6.65

650
730
800
650
730
800
650
730
800
650
730
800
650
730
800

7.82
7.88
7.96
7.74
7.80
7.90
7.64
7.71
7.81
7.51
7.58
7.70
7.34
7.42
7.55

7.19
7.24
7.33
7.12
7.18
7.26
7.03
7.09
7.18
6.91
6.98
7.08
6.75
6.83
6.94

2.66
2.64
2.64
2.88
2.87
2.86
3.10
3.09
3.09
3.32
3.31
3.31
3.52
3.52
3.52

9.81
9.88
9.98
9.72
9.79
9.90
9.65
9.72
9.82
9.56
9.64
9.74
9.47
9.54
9.65

850
875
900
850
875
900
850
875
900
850
875
900
850
875
900

9.37
9.39
9.42
9.21
9.24
9.27
9.04
9.07
9.09
8.83
8.86
8.90
8.61
8.64
8.68

8.61
8.64
8.66
8.47
8.50
8.53
8.31
8.34
8.37
8.12
8.15
8.18
7.91
7.95
7.98

3.70
3.70
3.71
3.91
3.91
3.92
4.12
4.12
4.13
4.33
4.33
4.34
4.53
4.54
4.55

11.80
11.83
11.85
11.66
11.70
11.73
11.52
11.55
11.58
11.35
11.38
11.42
11.16
11.19
11.23

4.29
4.33
4.37
4.23
4.27
4.31
4.17
4.21
4.25
4.11
4.15
4.18
4.05
4.09
4.13

1.37
1.36
1.35
1.46
1.45
1.44
1.57
1.55
1.54
1.67
1.65
1.64
1.78
1.76
1.75

5.90
5.79
5.69
5.92
5.85
5.77
5.87
5.88
5.83
5.80
5.84
5.85
5.72
5.77
5.80

5.12
5.02
4.93
5.13
5.07
5.00
5.09
5.10
5.05
5.03
5.06
5.07
4.95
5.00
5.03

1.48
1.44
1.43
1.59
1.55
1.53
1.70
1.66
1.64
1.83
1.78
1.76
1.94
1.91
1.88

6.31
6.13
5.89
6.38
6.23
6.10
6.42
6.31
6.19
6.43
6.35
6.26
6.40
6.38
6.31

6.16
5.98
5.75
6.22
6.08
5.95
6.26
6.15
6.04
6.28
6.20
6.11
6.25
6.22
6.16

1.52
1.48
1.45
1.64
1.60
1.57
1.76
1.71
1.69
1.88
1.84
1.81
2.01
1.96
1.93

6.66
6.23
5.89
6.77
6.52
6.19
6.85
6.67
6.45
6.90
6.76
6.62
6.92
6.82
6.70

6.66
6.23
5.89
6.77
6.52
6.19
6.85
6.67
6.45
6.90
6.76
6.62
6.92
6.82
6.70

1.57
1.49
1.45
1.69
1.63
1.58
1.82
1.76
1.72
1.95
1.89
1.85
2.08
2.02
1.98

6.78
6.27
5.90
7.08
6.60
6.23
7.27
6.88
6.53
7.36
7.13
6.79
7.42
7.24
7.02

6.78
6.27
5.90
7.08
6.60
6.23
7.27
6.88
6.53
7.36
7.13
6.79
7.42
7.24
7.02

1.58
1.49
1.45
1.73
1.64
1.58
1.87
1.78
1.72
2.01
1.94
1.87
2.15
2.08
2.02

6.85
6.30
5.89
7.19
6.65
6.26
7.49
6.97
6.58
7.74
7.25
6.87
7.86
7.49
7.13

6.85
6.30
5.89
7.19
6.65
6.26
7.49
6.97
6.58
7.74
7.25
6.87
7.86
7.49
7.13

1.58
1.49
1.45
1.73
1.64
1.58
1.90
1.79
1.73
2.06
1.95
1.88
2.22
2.11
2.03

6.91
6.30
5.56
7.29
6.70
6.25
7.62
7.06
6.62
7.90
7.42
6.94
8.11
7.63
7.24

6.91
6.30
5.56
7.29
6.70
6.25
7.62
7.06
6.62
7.90
7.42
6.94
8.11
7.63
7.24

1.58
1.49
1.43
1.74
1.64
1.58
1.91
1.80
1.73
2.08
1.97
1.88
2.25
2.12
2.04

12.43
12.05
11.73
12.54
12.21
11.92
12.62
12.34
12.08
12.66
12.43
12.21
12.66
12.48
12.30

2.89
2.80
2.75
3.08
2.98
2.93
3.26
3.17
3.11
3.46
3.36
3.30
3.65
3.55
3.49

13.25
12.77
12.24
13.41
12.97
12.61
13.52
13.13
12.81
13.61
13.28
12.98
13.64
13.37
13.11

13.25
12.77
12.24
13.41
12.97
12.61
13.52
13.13
12.81
13.61
13.28
12.98
13.64
13.37
13.11

3.01
2.91
2.82
3.21
3.09
3.03
3.41
3.28
3.21
3.61
3.49
3.41
3.82
3.69
3.61

18.56
18.49
18.28
18.45
18.45
18.31
18.30
18.35
18.30
18.12
18.21
18.24
17.88
18.04
18.14

3.57
3.43
3.28
3.85
3.71
3.55
4.15
4.00
3.83
4.46
4.29
4.12
4.77
4.61
4.42

20.13
19.96
19.62
20.05
19.95
19.70
19.94
19.90
19.72
19.79
19.81
19.71
19.62
19.67
19.64

20.13
19.96
19.62
20.05
19.95
19.70
19.94
19.90
19.72
19.79
19.81
19.71
19.62
19.67
19.64

3.76
3.59
3.42
4.05
3.88
3.69
4.35
4.18
3.98
4.66
4.48
4.28
4.97
4.79
4.59

22.41
22.48
22.55
22.09
22.16
22.23
21.78
21.85
21.91
21.47
21.54
21.60
21.16
21.23
21.30

4.87
4.85
4.84
5.13
5.11
5.09
5.40
5.38
5.36
5.69
5.66
5.64
5.99
5.96
5.93

24.96
25.05
25.12
24.61
24.69
24.76
24.24
24.32
24.40
23.88
23.96
24.04
23.53
23.61
23.69

24.96
25.05
25.12
24.61
24.69
24.76
24.24
24.32
24.40
23.88
23.96
24.04
23.53
23.61
23.69

5.19
5.17
5.14
5.46
5.43
5.40
5.74
5.71
5.68
6.03
5.99
5.96
6.33
6.29
6.26

38EYX0369A Outdoor Section With FX4CSX036 Indoor Section


12
15
18
21
24

6.30
6.37
6.43
6.20
6.27
6.34
6.11
6.18
6.24
6.02
6.09
6.15
5.92
5.99
6.05

2.15
2.15
2.16
2.27
2.27
2.28
2.40
2.40
2.40
2.54
2.53
2.53
2.68
2.67
2.67

8.83
8.90
8.90
8.71
8.79
8.85
8.58
8.67
8.74
8.45
8.54
8.62
8.33
8.42
8.50

7.65
7.71
7.71
7.54
7.62
7.67
7.43
7.51
7.58
7.33
7.40
7.47
7.22
7.30
7.37

2.40
2.38
2.37
2.53
2.52
2.51
2.66
2.65
2.66
2.80
2.79
2.79
2.96
2.93
2.93

9.84
9.76
9.65
9.77
9.77
9.70
9.65
9.71
9.70
9.51
9.60
9.65
9.37
9.47
9.55

9.60
9.53
9.42
9.53
9.53
9.47
9.41
9.48
9.47
9.28
9.37
9.42
9.15
9.24
9.31

2.51
2.48
2.47
2.67
2.63
2.61
2.83
2.78
2.76
2.98
2.96
2.92
3.13
3.11
3.10

10.71
10.53
10.35
10.73
10.59
10.44
10.70
10.62
10.51
10.63
10.62
10.54
10.50
10.57
10.55

10.71
10.53
10.35
10.73
10.59
10.44
10.70
10.62
10.51
10.63
10.62
10.54
10.50
10.57
10.55

2.63
2.58
2.56
2.79
2.74
2.71
2.96
2.90
2.87
3.13
3.07
3.04
3.32
3.25
3.21

11.58
11.30
11.06
11.64
11.41
11.20
11.68
11.49
11.31
11.68
11.55
11.39
11.64
11.56
11.44

11.58
11.30
11.06
11.64
11.41
11.20
11.68
11.49
11.31
11.68
11.55
11.39
11.64
11.56
11.44

2.76
2.70
2.66
2.93
2.86
2.82
3.11
3.04
3.00
3.29
3.22
3.17
3.48
3.40
3.35

12.43
12.05
11.73
12.54
12.21
11.92
12.62
12.34
12.08
12.66
12.43
12.21
12.66
12.48
12.30

38EYX0489A Outdoor Section With FX4CSX048 Indoor Section


12
15
18
21
24

8.93
9.00
9.09
8.86
8.92
9.02
8.79
8.85
8.95
8.71
8.78
8.87
8.63
8.69
8.79

2.77
2.74
2.71
3.01
2.97
2.94
3.26
3.22
3.18
3.48
3.47
3.43
3.76
3.70
3.66

12.30
12.39
12.53
12.19
12.27
12.41
12.07
12.16
12.29
11.91
12.00
12.17
11.77
11.87
12.01

10.66
10.74
10.86
10.56
10.64
10.75
10.46
10.54
10.65
10.32
10.40
10.55
10.20
10.28
10.41

2.96
2.90
2.85
3.21
3.15
3.09
3.47
3.41
3.34
3.72
3.66
3.61
3.99
3.93
3.86

13.69
13.80
13.96
13.55
13.65
13.81
13.40
13.51
13.66
13.26
13.36
13.52
13.11
13.22
13.37

13.36
13.47
13.62
13.22
13.33
13.48
13.08
13.19
13.33
12.94
13.04
13.19
12.80
12.90
13.05

3.09
3.02
2.96
3.34
3.27
3.20
3.61
3.53
3.45
3.88
3.80
3.72
4.16
4.08
3.99

15.22
15.35
15.48
15.04
15.17
15.34
14.86
14.99
15.17
14.69
14.82
14.99
14.52
14.64
14.82

15.22
15.35
15.48
15.04
15.17
15.34
14.86
14.99
15.17
14.69
14.82
14.99
14.52
14.64
14.82

3.25
3.17
3.06
3.51
3.42
3.34
3.77
3.68
3.59
4.05
3.95
3.86
4.33
4.24
4.13

16.94
16.99
16.94
16.76
16.86
16.89
16.55
16.69
16.80
16.34
16.49
16.66
16.12
16.28
16.49

16.94
16.99
16.94
16.76
16.86
16.89
16.55
16.69
16.80
16.34
16.49
16.66
16.12
16.28
16.49

3.41
3.28
3.16
3.71
3.56
3.42
3.99
3.86
3.70
4.27
4.16
3.99
4.56
4.44
4.29

18.56
18.49
18.28
18.45
18.45
18.31
18.30
18.35
18.30
18.12
18.21
18.24
17.88
18.04
18.14

38EYX0609A Outdoor Section With FX4CSX060 Indoor Section


12
15
18
21
24

10.74
10.77
10.80
10.63
10.65
10.68
10.49
10.52
10.55
10.34
10.37
10.40
10.16
10.20
10.23

3.87
3.87
3.87
4.09
4.09
4.10
4.33
4.33
4.33
4.57
4.57
4.57
4.81
4.81
4.81

14.69
14.73
14.77
14.51
14.55
14.59
14.34
14.37
14.41
14.18
14.21
14.25
14.00
14.03
14.07

12.73
12.77
12.80
12.58
12.61
12.64
12.43
12.46
12.49
12.29
12.32
12.35
12.13
12.17
12.20

4.09
4.08
4.08
4.33
4.32
4.31
4.58
4.57
4.56
4.84
4.83
4.82
5.11
5.10
5.09

16.34
16.38
16.43
16.14
16.18
16.22
15.92
15.99
16.03
15.69
15.73
15.78
15.49
15.53
15.57

15.95
15.99
16.03
15.75
15.80
15.83
15.53
15.61
15.64
15.31
15.36
15.40
15.12
15.16
15.20

4.23
4.23
4.22
4.48
4.47
4.46
4.73
4.73
4.72
4.99
4.98
4.97
5.27
5.26
5.25

18.07
18.12
18.17
17.83
17.88
17.93
17.61
17.66
17.71
17.39
17.44
17.48
17.17
17.22
17.26

18.07
18.12
18.17
17.83
17.88
17.93
17.61
17.66
17.71
17.39
17.44
17.48
17.17
17.22
17.26

4.40
4.39
4.38
4.65
4.64
4.62
4.91
4.90
4.88
5.19
5.17
5.16
5.47
5.45
5.44

20.11
20.17
20.23
19.84
19.90
19.96
19.57
19.63
19.69
19.31
19.36
19.42
19.05
19.10
19.16

20.11
20.17
20.23
19.84
19.90
19.96
19.57
19.63
19.69
19.31
19.36
19.42
19.05
19.10
19.16

4.61
4.60
4.58
4.87
4.85
4.83
5.13
5.11
5.10
5.41
5.39
5.37
5.70
5.68
5.66

22.41
22.48
22.55
22.09
22.16
22.23
21.78
21.85
21.91
21.47
21.54
21.60
21.16
21.23
21.30

* The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these
values to obtain total system kilowatts.
The kW heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The kW heating from supplement heaters should be added to those values to obtain total system capacity.
EDB Entering Dry Bulb.

Combination ratings
HEATING CAPACITY
OUTDOOR
UNIT SIZESERIES
024-7A
036-9A
048-9A
060-9A

COOLING CAP @ 35C


NOMINAL AIRFLOW
INDOOR UNIT
FX4CSX024
FX4CSX036
FX4CSX048
FX4CSX060

CFM
800
1200
1550
1850

Rated Capacity

L/ S

BTUH

kW

380
560
730
875

23,300
34,070
46,620
57,100

6.83
9.98
13.66
16.73

Hi Temp 7C
Rated Capacity

Rated
EER (W/W)

BTUH

kW

3.22
3.18
3.13
2.85

22,660
35,450
49,430
58,270

6.64
10.39
14.48
17.07

COP
(W/W)
3.63
3.49
3.79
3.39

* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 27C db 19C wb indoor entering air temperature and 35C db air entering outdoor unit.
High-Temperature Heating Standard: 20 db indoor entering air temperature and 7C db 6C wb air entering outdoor unit.

System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than
0.01-in. wg.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 13C.
3. Maximum outdoor operating air temperature for cooling mode is 52C.
4. Minimum outdoor operating air temperature for heating mode is 34C.
5. Maximum outdoor operating air temperature for heating mode is 19C.
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 15m, indoor coil below = 45m.
(See items 8 and 9 following.)
8. For interconnecting refrigerant tube lengths greater than 15.2m, consult Long-Line Application Guideline available from equipment distributor.
9. Not more than 91cm of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a
minimum 15cm) vertical rise to the valve connections at the unit.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.

10

SERIES

7A
9A
9A
9A

UNIT

024
036
048
060

A
571.5
762.0
762.0
762.0

B
760.4
760.4
1014.4
862.0

AIR DISCHARGE

DIA TIEDOWN
KNOCKOUTS
(2) PLACES

3/8 -IN. ( 9.5 mm)

AIR IN

C
81.0
81.0
82.6
82.6

F
G

D
5/8 in.
3/4 in.
7/8 in.
7/8 in.

AIR IN

AIR IN

E
93.7
165.1
165.1
165.1

AIR IN

A SQ
AIR DISCHARGE

2 7/8" C
(73.0 mm)

UNIT DIMENSIONS
G
H
501.7
549.3
692.2
739.8
692.2
739.8
692.2
739.8

J
365.1
508.0
508.0
508.0

DIMENSIONS (MM)
K
479.4
669.9
669.9
669.9

L
560.4
750.9
750.9
750.9

M
279.4
406.4
381.0
349.3

2. Minimum outdoor operating ambient in cooling mode is 13 C


(unless low ambient control is used) max 52 C.
3. Maximum outdoor operating ambient in heating mode is 19 C.
4. Series designation is the 13th position of the unit model number.
5. Center of gravity .

N
127.0
355.6
400.1
396.9

DIA LIQUID
LINE CONN

3/8 -IN. (9.5 mm)

P
355.6
317.5
355.6
381.0

FIELD CONTROL SUPPLY


CONN 7/8 -IN. (22.2 mm)
DIA HOLE

FIELD POWER SUPPLY CONN


7/8 -IN. (22.2 mm) DIA HOLE WITH
1 1/8 -IN. (28.6 mm) DIA KNOCKOUT
AND 1 3/8 -IN. (34.9 mm) DIA
KNOCKOUT

D DIA VAPOR LINE CONN


1 1/4"
(31.8 mm)
NOTES:
1. Allow 76 cm clearance to service side of unit, 122 cm above unit,
15 cm on one side, 30 cm on remaining side, and 61 cm between
units for proper airflow.

F
460.4
596.9
596.9
596.9

AIR DISCHARGE

MINIMUM MOUNTING
PAD DIMENSIONS
571.5 x 571.5
762.0 x 762.0
762.0 x 762.0
762.0 x 762.0

A04178

Dimensions

A04176

11

Guide specifications

GENERAL
System Description
Outdoor-mounted, air-cooled, split-system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air-cooled coil, propeller-type
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
Unit shall be manufactured in a facility registered to ISO9001/
BS5750 Part II, International Standard for Quality Systems. Unit
design shall comply with European standard and bear the
CE Mark.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC (U.S.A. Standard).
Unit will be constructed in accordance with European
standards.
Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500-hr salt spray test
(U.S.A. Standard).
Air-cooled condenser coils will be leak tested at
1724 KPa and pressure tested at 3103 KPa.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturers recommendations.

PRODUCTS
Equipment
Factory-assembled, single piece, air-cooled heat pump unit.
Contained within the unit enclosure will be all factory wiring,
piping, controls, compressor, refrigerant charge (R-410A), and
special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized, prepainted,
steel.
Fans
Condenser fan will be direct-drive propeller type, discharging
air upward.

Air-Cooled, Split-System
Heat Pump
38EYX
2 To 5 Tons Nominal
(7 To 17.5 kW)
Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with
PVC-coated steel wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of epoxy coated, aluminum fins
mechanically bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
Refrigeration circuit components will include liquid line
shutoff valve with sweat connections, suction shutoff valves with
sweat connections, system charge of refrigerant R-410A,
compressor oil, accumulator, and reversing valve.
Operating Characteristics
The capacity of the unit will meet or exceed ____ Btuh
(____ kW) at a suction temperature of ____ F (____ C). The
power consumption at full load will not exceed ____ kW.
Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of ____ Btuh (____ kW) or
greater at conditions of ____ CFM (____ L/S) entering air
temperature at the evaporator at ____ F (____ C) wet bulb
and ____ F (____ C) dry bulb, and air entering the unit
at ____ F (____ C).
Electrical Requirements
Nominal unit electrical characteristics will be ____ v,
____ phase, 50 hz. The unit will be capable of satisfactory
operation within voltage limits of ____ v to ____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.

Carrier Corporation Indianapolis, IN 46231

9-05

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book

Tab

5a 5a

Page 12

Printed in U.S.A.

PC 101

Form 38EYX-C3PD
Replaces: 38EYX-C2PD

Product
Data

FX4C (50 Hz)


Direct Expansion
Fan Coil
Sizes 024 thru 060

Quality Assurance
ISO 9001:2000

REGISTERED

IP20
FX4C Fan Coil Air
Handling Technology at its
Finest

A02332

Copyright 2004 Carrier Corporation

The FX4C fan coil is the latest in air


handling technology. Its the one to
choose for high efficiency operation,
application versatility, ease of
installation, and high-tech performance.
FX4C fan coils are encased, 1-piece
units, designed for vertical (upflow or
downflow) and horizontal installations.
Downflow installations require an
accessory adapter package. The FX4C
is compact, designed for upflow,
downflow, and horizontal installations,
and ready to fit right where you need it.
The solid construction of the prepainted
metal cabinet ensures years of rugged
service, and its packed with the most
advanced components so you know its
going to perform like a deluxe fan coil
should.
Inside, youll find grooved copper
tube/lanced sine wave aluminum fin
coil. Solid-state cooling controls are
included with every unit.
Efficient and dependable metering of
the refrigerant is provided by our
AccuRater, a device which improves
overall system reliability and is easily
accessible for piston changeout and
routine maintenance. Carrier also
engineered the FX4C with dedicated
refrigerant circuitry, and high-density
insulation. For leak-free connections,
the FX4C is equipped with sweat
connections.
The FX4C offers superior versatility
with its 3-speed PSC motor. Electric
heaters are not offered as accessories for
CE mark units.
Form FX4C-C1PD

Compact and attractive with a


low-maintenance, easy-to-clean,
permanent filter, the FX4C is a favorite
for contractors and homeowners. Just

consider the first-cost affordability and


Carrier performance and its easy to
see why its the fan coil of choice.

Features FX4C
4 models available
All units multipoise install upflow, horizontal, or downflow
Unique cabinet design that meets new stringent regulations for air leakage. Meets requirements of a 2% cabinet leakage rate
when tested at 25 mm of static pressure
Grooved copper tubes
Lanced sine wave aluminum fins
Fully wettable coil
Cooling controls on every unit
40va control power transformer
Replaceable 5-amp blade-type automotive fuse protects against transformer secondary short
Solid-state interlock control board
3-speed motor
Easy access filter for cleaning no tools required
Newly improved filter rack area filter door insulation added for an improved air seal
Inspection plate for cleaning coil face (048-060 sizes)
Prepainted galvanized steel sheetmetal
High-density insulation
Sweat connections
AccuRater piston
Multiple electric entry
Reinforced plastic condensate pan with brass drain connection inserts
Secondary drain connection

Model number nomenclature


F

024

000

Nominal Capacity (Btu)


024 24,000
048 48,000
036 36,000
060 60,000
X Export with CE Mark
S 230-1-50
C Series
4 Multipoise
X R-410A
F Fan Coil

5"

FRONT VIEW

INLET AIR

OPENING
D

FITTING
PANEL

TOP VIEW

1 15/16"

7/8", 1 3/32"
2" DIA. K.O.'s
FOR HIGH VOLTAGE
POWER WIRING

SERIES
A
A
A
A

UNIT
SIZE

FX4CSX024

FX4CSX036

FX4CSX048

FX4CSX060

Slope

Slope

COIL
TYPE

FILTER ACCESS
PANEL

6 3/16"

SUCTION LINE CONNECTION

LIQUID LINE CONNECTION

COIL ACCESS
PANEL

BLOWER, CONTROL,
& ELECTRIC HEATER
ACCESS PANEL

DISCONNECT OR
CIRCUIT BREAKER
LOCATION

1"
1 3/8"

7/8" DIA. K.O.


FOR LOW VOLTAGE
CONTROL WIRING

SHOWN WITH "A" COIL DETAIL CONNECTION


LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS

1"

10 7/16"

2 5/8"

15/16"

1 7/8"

Dimensions

In.

9 1/2"

53-7/16

49-5/8

53-7/16

47-11/16

10 3/4"

3 1/16"

4 11/16"

1357.3

1260.5

1357.3

1211.5

mm

In.

21-1/8

21-1/8

21-1/8

17-5/8

CONNECTION LOCATIONS SHOWN


FOR UPFLOW OR HORIZ.
LEFT APPLICATIONS

SLOPE COIL DETAILS

SUCTION LINE
CONNECTION

LIQUID LINE
CONNECTION

SUCTION: 024 - 5/8" I.D. SWEAT


036 - 3/4" I.D. SWEAT
048 & 060 - 7/8" I.D. SWEAT
LIQUID: 3/8" I.D. SWEAT
CONDENSATE: 3/4" FIT

UNIT CONNECTION SIZES

1. SERIES DESIGNATION IS THE 14TH POSITION


OF UNIT PRODUCT NUMBER.

NOTE:

536.5

536.5

536.5

447.5

mm

In.

19-1/4

19-1/4

19-1/4

15-3/4

DOWNFLOW APPLICATIONS

"A" COILS

DOWNFLOW OR HORIZ.
RIGHT APPLICATIONS
AND

SLOPE COILS

ACCESS PANEL CONFIG. FOR

LIQUID LINE
CONNECTION

INLET AIR

ALTERNATE
7/8" DIA. K.O.
FOR LOW VOLTAGE
CONTROL WIRING

NOTE: ALLOW 21" FROM FRONT


FOR SERVICE.

1 1/4"

1 3/4"

1 3/16"

2 1/8"

489.0

489.0

489.0

400.1

mm

11"

19-1/8

19-1/8

19-1/8

15-5/8

In.

INLET AIR

RIGHT SIDE VIEW

OPENING
19 13/16"

19"

mm

485.8

485.8

485.8

396.9

OUTLET AIR

ALTERNATE
7/8", 1 3/32", 2" DIA. K.O.'S
FOR HIGH VOLTAGE
POWER WIRING
OPPOSITE SIDE

22 1/16"

OPTIONAL FIELD CONVERTED


RIGHT SIDE RETURN OPENING
(SLOPE COIL UNITS ONLY)

1"

10 3/16"

2 1/2"

MAX

1 1/2"

3/4"

7/8"

19

17

In.

J
mm

462.6

431.8

A04165

4
SERIES
A
A
A
A

UNIT
SIZE
FX4CSX024
FX4CSX036
FX4CSX048
FX4CSX060

Dimensions continued

Slope

Slope

COIL
TYPE

27-1/4

23-7/16

26-15/16

23-1/8

In.

692.2

593.3

684.2

587.4

mm

26-15/16

23-1/8

27-1/2

23-5/8

In.

G
mm

684.2

587.4

698.5

600.0

A02293

Physical data
SI
024

036

048

060

NOMINAL CAPAC
KILOWATTS

UNIT SIZE
TR
*

2.0
8.2

3.0
12.3

4.0
17.3

5.0
17.6

OPERATING WEIGHT

KG

55

67

72

80

DIMENSIONS (VERT)
HEIGHT
WIDTH
DEPTH

MM
MM
MM

1212
448
560

1357
536
560

1261
537
560

1357
537
560

REFRIGERANT
REFRIG CONTROL

R-22
Bypass AccuRater

UNIT ARRANGEMENT
FAN
AIRFLOW/NOM.
MOTOR TYPE
NOMINAL
SPEEDS
INDOOR COIL
FACE AREA
ARRANGEMENT
ROWS
FIN DENSITY

Upflow/Downflow/Horizontal (LH)
L/S
KW
R/S
SQ M

475
0.24

/M

0.28
Slope
3
551

IN.
IN.

16
9.5

FILTER
COIL CONNECTIONS
VAPOR (OD)
LIQUID (OD)

600
0.24

750
PSC

0.56
16.7/15.0/13.3
Copper Tube/Aluminum Fin with Lanced Sine Wave
0.32
0.41
Slope
A
3
3
551
551
Permanent Type/25 mm (1 in.) Thick

825
0.56

0.55
A
3
551

Sweat-Type
19
9.5

22.2
9.5

22.2
9.5

* Based on nominal airflow rates, 19.4C entering wet bulb and 7.2C sat suction temp.

Performance data
SI

COOLING CAPACITIES (Kw)


COIL REFRIGERANT TEMPERATURE* (C)
2

036

048

060

10

12

Evaporator Air Entering Wet-Bulb Temp (C)

UNIT L/S
SIZE BPF

024

22

350

TC

0.04

SC

475

TC

0.07

SC

525

TC

0.08

SC

475

TC

0.05

SC

20

18

16

13.8 12.1 10.6


6.8

7.2

7.5

18

16

18

16

20

18

16

22

20

18

16

22

20

18

9.1 12.9 11.1

22

9.5

8.0 11.9 10.0

8.4

7.0 10.8

8.9

7.4

5.9

9.5

7.6

6.2

4.9

8.1

6.3

5.3

4.4

7.7

7.1

7.3

6.5

6.7

5.7

5.9

5.9

4.8

5.2

5.4

4.9

4.4

4.6

4.7

4.4

6.4

20
6.8

15.9 14.0 12.1 10.3 14.8 12.8 11.0


7.7

8.3

8.9

9.4

7.3

7.8

8.3

16.7 14.6 12.7 10.8 15.6 13.4 11.5


8.3

8.8

9.3

9.9

7.9

8.3

8.8

22
5.9

20
6.2

8.8

9.2

5.4

16

9.3 13.6 11.6

9.8

8.1 12.3 10.3

8.6

7.0 10.9

8.9

7.4

6.1

9.2

7.2

6.1

5.5

8.8

7.7

8.1

7.1

7.0

6.1

6.4

6.1

5.2

5.5

5.7

5.5

6.9

7.3

6.4

6.8

5.7

9.8 14.4 12.1 10.3

8.6 13.0 10.7

9.0

7.4 11.5

9.3

7.7

6.5

9.8

7.6

6.5

5.8

9.2

8.6

7.5

7.4

6.5

6.8

6.5

5.6

5.9

6.0

5.8

7.4

7.8

8.2

19.8 17.2 14.7 12.2 18.3 15.6 13.1 10.8 16.6 13.9 11.5
9.4 10.0 10.5 10.9

22

9.7 10.1

8.1

8.6

8.9

6.9

7.2

6.3

9.3 14.9 12.1

9.9

7.9 13.0 10.2

8.2

6.6 10.9

8.3

6.9

6.0

9.2

8.1

7.9

7.1

7.1

6.2

6.3

6.0

7.4

7.8

6.6

7.0

5.9

600

TC

22.6 19.7 17.0 14.4 21.0 18.0 15.3 12.7 19.1 16.1 13.5 11.0 17.2 14.1 11.7

9.4 15.1 12.0

9.9

8.2 12.6

9.7

8.3

7.3

0.07

SC

11.0 11.7 12.3 13.0 10.3 10.9 11.5 12.1

9.4

8.7

8.2

7.4

7.6

7.3

700

TC

24.5 21.4 18.6 15.8 22.8 19.7 16.8 13.9 21.0 17.6 14.8 12.1 18.9 15.4 12.8 10.5 16.6 13.2 11.0

9.3 14.0 10.8

9.2

8.3

0.09

SC

11.9 12.9 13.7 14.5 11.3 12.1 12.8 13.4 10.4 11.2 11.8 12.1

9.3

8.5

8.3

575

TC

23.5 20.5 17.8 15.2 21.8 18.8 16.0 13.3 19.9 16.9 14.2 11.6 18.0 15.0 12.4 10.0 16.1 12.9 10.6

8.7 13.5 10.5

8.8

7.7

0.05

SC

11.3 12.0 12.7 13.3 10.5 11.3 11.9 12.4

8.7

8.0

7.7

750

TC

26.7 23.3 20.3 17.6 25.0 21.6 18.5 15.6 22.9 19.6 16.6 13.8 20.7 17.3 14.6 12.1 18.4 14.8 12.6 10.9 15.7 12.2 10.6

9.7

0.07

SC

13.0 14.0 15.0 16.0 12.3 13.4 14.2 14.9 11.5 12.5 13.3 13.8 10.7 11.5 12.3 12.1

9.7

27.6 24.4 21.2 18.1 25.9 22.5 19.5 16.5 23.8 20.4 17.3 14.5 21.6 18.0 15.2 12.8 19.3 15.5 13.2 11.5 16.4 12.7 11.1 10.4

9.5 10.1 10.6 11.0

9.8 10.5 11.1 11.5

8.7

9.3

9.7

9.6 10.3 10.8 10.5


9.1

9.7 10.1 10.0

7.8
8.7
8.2

8.4
9.4
8.7

9.7
9.1

9.8 10.7 11.2 10.9

7.0
7.9
7.4
8.7

8.4
7.8
9.4

9.8

825

TC

0.08

SC

13.6 14.8 16.0 17.0 12.7 14.0 15.1 16.2 12.0 13.2 14.1 14.5 11.3 12.3 13.0 12.8 10.4 11.3 11.8 11.5

600

TC

25.7 22.1 19.0 16.1 23.6 20.2 17.2 14.2 21.6 18.2 15.1 12.2 19.5 16.0 13.0 10.1 17.0 13.7 10.8

8.1 14.3 11.0

9.0

7.5

0.03

SC

12.4 13.0 13.4 13.8 11.5 12.0 12.4 12.8 10.7 11.1 11.4 11.7

8.1

8.1

7.5

9.8 10.2 10.4 10.1

8.7

9.1

9.1

9.4 10.1 10.5 10.4


7.7

8.1

750

TC

29.6 25.8 22.3 18.9 27.5 23.7 20.2 16.8 25.2 21.3 17.7 14.2 22.8 18.8 15.2 11.8 20.2 16.2 13.0 10.0 17.1 13.1 10.8

9.2

0.05

SC

14.4 15.3 16.0 16.6 13.4 14.2 14.9 15.6 12.5 13.2 13.7 14.1 11.6 12.2 12.4 11.8 10.5 11.1 11.2 10.0

9.2

900

TC

32.6 28.5 24.7 21.0 30.3 26.2 22.3 18.6 27.8 23.7 19.8 16.0 25.2 21.0 17.2 13.7 22.4 18.0 14.6 11.8 19.0 14.7 12.3 10.7

0.06

SC

15.9 17.1 18.1 19.1 14.9 16.1 16.9 17.7 13.9 14.9 15.7 16.0 12.8 13.7 14.3 13.7 11.8 12.5 12.6 11.8 10.5 11.3 11.3 10.7

9.2

9.9

9.9

LEGEND
L/S Liters per second
BF Bypass factor
Sensible heat capacity (kw)
1. Gross capacities shown do not include a deduction for evaporator fan motor heat.
2. Contact Carrier for cooling capacities at conditions other than shown in table.
3. Direct interpolation is permissible. Do not extrapolate.
4. SHC is based on 26.7C temperature of air entering the indoor unit. At any other temperature, correct the SHC read from the table of cooling
capacities as follows:
Corrected SHCKW = SHC + [1.23 x 103 x (1-BF) x (Cdb-26.7) x L/s]
Observe the rule of signs. Above 26.7C, SHC correction will be positive; add it to SHC. Below 26.7C, SHC correction will be negative; subtract it
from SHC.
5. Formula:
Cldb = Cedb

SHCkW
1.23 x 10 3 x (L/s)

Leaving wet bulb = wet bulb temperature corresponding to enthalpy of air leaving coil (hlwb).
hlwb = hewb

TCkW
1.20 x 10 3 x (L/s)

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

Performance data continued


AIRFLOW PERFORMANCE*
AIRFLOW RATE L/S

SI
UNIT
SIZE

EXTERNAL STATIC PRESSURE (PA)

BLOWER MOTOR
SPEED

25

50

75

100

125

HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW

519
462
415
692
612
511
812
770
713
885
803
671

482
429
386
658
581
494
765
724
671
844
767
647

431
385
340
619
544
472
716
678
630
800
731
624

369
321

571
496
439
661
628
579
755
690

299

478

595

706

024
036
048
060

NOTES:
Fan performance based on wet coil with factory-supplied filter; no internal heaters.
Not recommended for use above 150 Pa external static pressure.

Physical data
ENGLISH
024

036

048

060

NOMINAL CAPAC
1000 BTU/HR

UNIT SIZE
TR
**

2.0
26

3.0
42

4.0
59

5.0
60

OPERATING WEIGHT

LB

126

147

158

168

DIMENSIONS (VERT)
HEIGHT
WIDTH
DEPTH

IN.
IN.
IN.

47-11/16
17-5/8
22-1/16

53-7/16
21-1/8
22-1/16

53-7/16
21-1/8
22-1/16

53-7/16
21-1/8
22-1/16

REFRIGERANT
REFRIG CONTROL

R-22
Bypass AccuRater

UNIT ARRANGEMENT
FAN
AIRFLOW/NOM.
MOTOR TYPE
NOMINAL
SPEEDS
INDOOR COIL
FACE AREA
ARRANGEMENT
ROWS
FIN DENSITY

Upflow/Downflow/Horizontal (LH)
CFM

1000

1250

HP
RPM

1/3

1/3

SQ FT
/IN.

1600

1750

3/4

3/4

1000/900/800
Copper Tube/Aluminum Fin with Lanced Sine Wave
2.97
Slope
3
14-1/2

FILTER
COIL CONNECTIONS
VAPOR (ODS)
LIQUID (ODS)

PSC

4.45
A
3
14-1/2

3.46
Slope
3
14-1/2

5.93
A
3
14-1/2

Permanent Type/25 mm (1 in.) Thick


Sweat-Type
IN.
IN.

5/8
3/8

3/4
3/8

7/8
3/8

7/8
3/8

** Based on nominal airflow rates, 67F entering wet bulb and 45F sat suction temp.

Performance data continued


AIRFLOW PERFORMANCE*
AIRFLOW RATECFM

ENGLISH
UNIT
SIZE

EXTERNAL STATIC PRESSUREIn. wc

BLOWER MOTOR
SPEED

0.10

0.20

0.30

0.40

0.50

HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW

1100
980
880
1466
1296
1082
1720
1632
1510
1876
1702
1422

1022
910
818
1394
1232
1046
1622
1535
1422
1788
1625
1372

914
815
720
1312
1152
1000
1518
1436
1334
1696
1548
1322

782
680

1210
1050
930
1400
1330
1226
1600
1462

634

1012

1260
1212

1496

024
036
048
060

NOTES:
Fan performance based on wet coil with factory-supplied filter; no internal heaters.
Not recommended for use above 0.60-in. wg external static pressure.

Carrier accessories
ITEM

ACCESSORY PART NO.*

FAN COIL SIZE USED WITH

Disconnect Kit

KFADK0201DSC

All

Downflow Base Kit

KFACB0201CFB

024

Downflow Conversion Kit


Filter Kit (12 Pack)

KFACB0301CFB

036, 048, 060

KFADC0201SLP

Slope Coil Units024, 036

KFADC0401ACL

A-Coil Units048, 060

KFAFK0212MED

024

KFAFK0312LRG

036, 048, 060

PVC Condensate Trap Kit (50 Pack)

KFAET0150ETK

All Sizes

Downflow/Horizontal Conversion Gasket Kit

KFAHD0101SLP

All

* Factory authorized and listed, field installed.

Accessory Kits Description Suggested and Required Use


1. Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: All (Consult local code).
2. Downflow Base Kit
This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap free
seal with the floor.
REQUIRED USE: This kit can be used whenever fan coils are used in downflow applications and local code requires a metal base for the unit.
3. Downflow Conversion Kit
Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and
support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
4. Fan Coil Filter
The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents them from
collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efficiency of the system.
SUGGESTED USE: To replace filters in FX4C fan coils.
5. Condensate Drain Trap Kit
This kit consists of 50 PVC condensate traps. Each trap is pre-formed and ready for field installation. This deep trap helps the system make and hold
proper condensate flow even during blower initiation.
SUGGESTED USE: All FX4C fan coils.
6. Downflow/Horizontal Conversion Gasket Kit
This kit provides the proper gasketing of units when applied in either a Downflow or Horizontal application.

Accessory electric heaters


FAN COIL ELECTRICAL DATA
(UNITS WITHOUT ELECTRICAL HEAT)
BRANCH CIRCUIT

UNIT SIZE

VOLTS
(1-PHASE)

FLA

024

230

036

230

048
060

Max Wire
Length (Ft/M)

MCA

Min Wire
Size* AWG

208V

230V

Fuse
Amps

1.5

1.9

14

210/64

225/69

15

1.8

2.3

14

125/38

150/46

15

230

2.7

3.4

14

90/27

100/30

15

230

3.6

4.5

14

90/27

100/30

15

* Use copper wire only to connect unit. If other than uncoated (nonplated), 75C ambient, copper wire (solid wire for 10 AWG and smaller, stranded
wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code (ANSI/NFPA 70, U.S.A.).
Length shown is as measured 1 way along wire path between unit and service panel for a maximum 2% voltage drop.
FLA Full Load Amps; Rated in accordance with UL/U.S.A. Standard 1995.
MCA Minimum Circuit Amps; Calculated in accordance with NEC/U.S.A. Article 430.

ESTIMATED SOUND POWER LEVEL FOR FX4C FAN COILS*


Lw (dB)
UNIT
SIZE

English
ESP

L/S

Octave Band Center Frequency (HZ)


250

500

1000

2000

4000

FX4CSX-024 50 Hz

1000

0.23

472

57

66.2

62.2

58.2

55.2

53.2

51.2

47.2

FX4CSX-036 50 Hz

1250

0.37

590

92

71.3

67.3

63.3

60.3

58.3

56.3

52.3

FX4CSX-048 50 Hz

1600

0.22

755

55

67.9

63.9

59.9

56.9

54.9

52.9

48.9

FX4CSX-060 50 Hz

1800

0.36

755

90

72.7

68.7

64.7

61.7

59.7

57.7

53.7

METHOD:

CFM

SI
ESP

63

125

Estimated Fan Sound Power (in decibels 10E-12 watts) is calculated in accordance with procedure described in ASHRAE 1987
HVAC Systems and Applications Handbook, Chapter 52, Sound and Vibration Control, using the Specific Sound Power
Level approach.
ACCURACY:
This is a prediction method, based on an accepted method which has demonstrated satisfactory results in field applications.
However, field test results may generate sound pressure values which differ from these predicted values, as the current state
of the art in determining sound power varies in accuracy from 0.2 db in mid-range (250 to 4000 Hz bands) to 3 to 4 db in 125
and 8000 Hz bands and up to 6 to 8 db in 63 Hz band.
MINOR CHANGES: Use for estimating sound power at other conditions of airflow and external static pressure.

10

Conversion factors
METRIC
TECH
Area
cm
cm
m
m
Length
m
m
mm
mm
mm
m
m
m
Mass
g
g
kg
kg
tonne. Mg
tonne. Mg
Power
kcal/h
kcal/h
HP metric
HP metric
Mcal/h
Mcal/h
Pressure
mm w.g 4C
mm w.g 4C
mm Hg 0C
mm Hg 0C
kgf/cm2
kgf/cm2
mH2O

ENGLISH
UNIT

X=

X=

SI UNIT

METRIC
TECH

X=

ENGLISH
UNIT

X=

SI UNIT

Temperature
0.1550

in.

10.76

ft

39.37

micro-in.

0.03937
0.003281

in.
ft

3.281
1.094

ft
yd

0.03527

oz

2.205

lb

1.102

U.S. ton
(2000 lb)

100
645.2
1.0
0.09290

mm
mm
m
m

1.0
0.0254
1.0
25.4
304.8
1.0
0.3048
0.9144

m
m
mm
mm
mm
m
m
m

1.0

3.968
0.9863

28.35
1.0
0.4536
1.0
0.9072

Btu/h
HP (550

ft lb
s

0.3307

Ton ref.

0.03937

in H2O 39.2F

0.03937

in Hg 32F

14.22
3.281

psi
ft H2O

g
g
kg
kg
tonne. Mg
tonne. Mg

1.163
0.2931
0.7355

W
W
kW

0.7457
1.163
3.517

kW
kW
kW

9.806
249.1
0.1333
3.386
98.07
6.895
2.989

Pa
Pa
kPa
kPa
kPa
kPa
kPa

Interval
C
C

1.8

1.0
0.5556

k
C

Velocity
m/s
m/s
m/s

3.281
196.9

ft/s
ft/min

1.0
0.3048
0.00508

m/s
m/s
m/s

1.0 x 106
0.01639
1.0
28.32
1.0
0.7646
3.785
0.4732
1.0
29.57

L
L
L
L
m
m
L
L
mL
mL

Volume
mm
mm
L
L
m
m
L
L
mL . cm
mL . cm
Volume/Time
m3/h
m3/h
m3/h
L/h
L/h
(m3/h)/
(1000 kcal/h)

6.102x103

in.

0.03531

ft

1.308
0.2642
2.113

yd
U.S. gal
U.S. pint

0.03381

U.S. oz

0.5886
4.403

ft3/min
U.S. gal/min

4.303x103

U.S. gal/min

1.780

cfm/ton

METRIC
TECH

CONVERSION
FACTOR

ENGLISH
UNIT

Temperature
C
C

(Cx1.8) + 32

0.2778
0.4719
0.06309
2.778x104
0.06309
0.1342

L/s
L/s
L/s
L/s
L/s
L/s kW

CONVERSION
FACTOR
SI UNIT
C + 273.15 K
(F32) 1.8C

Applications
Install these units in the
conditioned space or in an
unconditioned space. They are tested
and approved for installation in
unconditioned space per ARI
Standards (27C; 80F db, 24C;
75F wb indoor temperature; 27C;
80F db outdoor temperature).

Insulate supply and return air


ductwork in unconditioned space. It
is recommended that insulation with
vapor barrier be used.
SoundFor acoustical
treatment of ductwork, see FX4C
Installation, Start-Up, and Service
Instructions.

11

Matched system

OUTDOOR UNIT

HUMIDIFIER

FAN COIL
AIR FLOW
ELECTRONIC
AIR CLEANER
A02306

Copyright 2004 Carrier Corporation Syracuse, New York 13221

9-04

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book

Tab

3d 2e

Page 20

Catalog No. 02FX-4C0

Printed in U.S.A.

PC 101

Form FX4C-C1PD
Replaces: NEW