Sunteți pe pagina 1din 32

MEDIUM VOLTAGE SWITCHING DEVICE

HVX
Vacuum circuit-breaker
≤ 17,5 kV (> 2500 A / ≤ 50 kA)

Installation
Operation
0
Maintenance
No. AGS 531 461-01
Edition 06/07
X
HV

Technical instruction

AREVA T&D
AREVA T&D
T&D Worldwide Contact Centre
http://www.areva-td.com/contactcentre/
 +44 (0) 1785 250 070

Manufacturer:
AREVA Energietechnik GmbH
Sachsenwerk Medium Voltage
Rathenaustraße 2
D-93055 Regensburg
 +49 (0)9 41/46 20-0
 +49 (0)9 41/46 20-418
Service:

Should you have any queries as to our


service, please contact:
AREVA Energietechnik GmbH
Sachsenwerk Medium Voltage
Service-Center
D-93055 Regensburg
 +49 (0)9 41/4620-777
 +49 (0)9 41/4620-778

© AREVA Energietechnik GmbH, Sachsenwerk Medium Voltage -2007-


All rights reserved to this technical instruction.
Reproduction and making available of this technical instruction, or extracts, to third parties are prohibited.
Only integral reproduction of this technical instruction is permitted with the written permission from AREVA Energietechnik GmbH,
Sachsenwerk Medium Voltage.
Electronic copies in e.g. PDF-format or scanned version have the status “for information only” .
The only valid version of technical Instructions are always enclosed directly to the product in question by the factory.
Content

1 Regulations and Provisions 4


1.1 Remarks on this Technical Instruction 4
1.2 Terms and symbols used 4
1.3 Use in line with the intended purpose 4
1.4 Applied standards 5
1.5 Safety provisions 5
1.6 Disposal after the end of service life 5

2 Variants 6

3 Technical data 8
3.1 Type designation 8
3.2 Technical data 8
3.3 Control and operating devices 9

4 Shipping instructions 11
4.1 Packaging 11
4.2 Delivery 11
4.3 Storage 11
4.4 Transport 11

5 Assembly 12
5.1 Instructions for assembly 12
5.2 HVX-F – Mechanical assembly 12
5.3 HVX-E – Mechanical assembly 14
5.4 Connecting the control lines 15

6 Commissioning 16
6.1 HVX-E (withdrawable unit) 17
6.2 HVX-F (fixed type) 17

7 Operation 18
7.1 Control elements and operator interface 18
7.2 Interlocks 19
7.3 Charging the energy storing device 19
7.4 Switching the circuit breaker 20
7.5 Actuate withdrawable part 21

8 Servicing 22
8.1 Safety 22
8.2 Servicing schedule 22
8.3 Cleaning insulating components 23
8.4 Corrosion protection 23
8.5 Avoid condensation 23
8.6 Lubrication instructions 24
8.7 Maximum admissible number of breaking
operations of the vacuum chambers 27

9 Annex 28
9.1 Accessories 28
9.2 Auxiliary products 28
9.3 Screw fastenings 29
9.4 How to treat the contact surfaces 29

3
1 Regulations and Provisions

1.1 Remarks on 1.2 Terms and 1.3 Use in line with the
this Technical symbols used intended purpose
Instruction
This Technical Instruction uses cer- The HVX vacuum circuit-breaker is
This Technical Instruction describes tain terms and symbols. They warn intended exclusively as a switching
transport, assembly, operation, hand- about dangers or provide important unit in air-insulated medium-voltage
ling and maintenance of the series information which must be complied switchgear. It may only be used in
HVX vacuum circuit breakers. with at all costs so as to avoid dan- the scope of the specified standards
ger and damage: and the switchgear-specific techni-
It must be stored so that it is at any
cal data. Any other use constitutes
time readily accessible and can be „Warning“ improper use and may result in dan-
used by persons who work on the This warning symbol in- gers and damage.
circuit-breaker or the switchgear dicates dangerous
with this circuit-breaker. electrical voltage. Con- Important:
tact with voltage may result in Operating reliability and
When re-selling the circuit-breaker
fatal injury! service life depend on cor-
or the switchgear with circuit-brea-
rect operation.
ker, make sure that this Technical In- „Warning“
struction is transmitted as well. This warning symbol in-
dicates danger of inju- Disclaimer of liability
The following additional documents
ry. Observe alle instruc-
must be observed for this circuit- The manufacturer shall not be held
tions that are labeled with this
breaker: responsible for damage which oc-
sign to avoid death or serious
injury. curs if
• Purchase agreement containing
the stipulations on the specific
„Important“ • instructions in this Technical In-
equipment of the circuit-breaker struction are not complied with,
This notice symbol is used
and the legal details.
for information which is im- • the circuit-breaker is not opera-
• The contract specific circuit brea- portant to avoid damage. ted according to its intended use
ker wiring diagram / documentati- (see above),
on
• the circuit-breaker is assembled,
• Project notes regarding the HVX connected or operated improper-
circuit breaker ly,
• For assembly and operation of • accessories or spare parts are
the circuit-breaker, the operating used which have not been appro-
manual of the switchgear in ved by the manufacturer,
which it is operated must be
• the circuit-breaker is converted
complied with.
without the manufacturer's appro-
As our products are subject to conti- val, or if inadmissible parts are at-
nuous further development, we re- tached.
serve the right to changes regarding
standards, illustrations and technical
data.

All dimensions not specified in detail


are in millimeters.

4
1.4 Applied 1.5 Safety provisions 1.6 Disposal after the
standards end of service life
The work described in this Technical
The three-pole HVX vacuum circuit- Instruction may only be performed by A manual on disposal after the end
breaker specialist electricians who have pro- of the service life is available for dis-
ved their experience with the HVX posal of the HVX vacuum circuit
• corresponds to the requirements breaker.
circuit-breaker and all relevant Safety
for AC switchgear for voltages
provisions.
above 1 kV acc. to IEC 62271- Disposal at the end of the service life
100; Applicable standards and regulati- is performed as a service by the Ser-
ons: vice Center at the manufacturer's
• complies, regarding its switching
which is subject to a fee. Please
capacity and insulating level, • The locally applicable accident contact the Service Center (see
ANSI C37.... (please enquire at prevention, operating and work page 2).
the manufacturer's) instructions must be complied
• corresponds, as a withdrawable with.
unit, to IEC 62271-102. • Installation 2):
IEC 61936-1 / HD 637 S1
Type approval of vacuum interrup- • Operation of electrical equip-
ter chambers acc. to. RöV ment 2): EN 50110-1
The vacuum interrupter chambers 2) The national standards applicable in
have been approved by the X-Ray the country where the equipment is
Ordinance (RöV) of the Federal Re- to be installed must be complied
public of Germany up to a maximum with.
voltage amounting to the rated short- Read these instructions carefully be-
time power-frequency voltage (rated fore you work on the circuit-breaker,
power frequency withstand voltage) and perform the work detailed in it
defined by DIN VDE/IEC. Thus, they according to the descriptions. Do
satisfy the conditions for operation not perform any work on the circuit-
exempt of approval up to the voltage breaker which is not described in
in question according to the X-Ray this Technical Instruction.
Ordinance (RöV).
Warning!
Before starting work on
Environmental and the circuit-breaker, de-
operating conditions energize the system,
HVX circuit-breakers may only be verify it for zero voltage
operated under normal operating and earth the system according
conditions acc. to IEC 60694. Ope- to the applicable safety rules
ration under conditions deviating pursuant to EN50110-1.
from these is only admissible upon Warning!
consultation and with the written ap- Before performing work
proval of the manufacturer. on the circuit-breaker,
switch off the supply
Ambient conditions voltage and prevent it
Temperature class from reclosing.
"minus 5 indoors" 1)
Warning!
Ambient temperature There is a risk of injury
-5 / 40oC 1)
min./max. when working on the
Average value over 24 drive mechanism.
35oC 1) Before commencing work, re-
hours (max.)
lease the energy-storing device
Max. installation altitu- by performing the operating se-
1000 m 1)
de above sea level quence OFF-ON-OFF and re-
1) higher values on request mount the drive´s transport se-
curing device (see Chapter 6).

5
2 Variants

16
1
15
2

4
14 5
6

7
13

8
9

10
11

12

Fig. 2.1
Vacuum circuit breaker HVX-F – fixed type

1 64-pole low-voltage terminal 10 Insertion opening for manual char-


2 Information plate for commissioning ging of the closing spring
3 User interface 11 Operation counter
4 Switch circuit-breaker ON 12 Press rod (transfer of ON/OFF swit-
ching movement)
5 Switch circuit-breaker OFF
13 Drive casing
6 Handles (optional)
14 Vacuum interrupter chamber
7 Nameplate
15 Conductor bar terminal
8 Position indicator of closing spring
16 Pole partitions
9 Position indicator of circuit breaker

6
14
1
2
13

12 3

11
7
10
9

Fig. 2.2
Vacuum circuit breaker HVX-E with withdrawable part for PIX switchgear panels

14
1
2 1 Low-voltage terminal
13 2 Information plate for commissioning
3 User interface
4 Position indicator - withdrawable
part in service position
12 3
5 Position indicator - withdrawable
part in disconnected position
6 Lever for locking/unlocking the with-
drawable part in the panel
7 Insertion opening for manual racking
4 in/out the withdrawable part
5 8 Slide for opening the insertion ope-
ning (7) for manual racking the with-
11 6 drawable part in and out manually
9 Withdrawable part´s rollers
7 10 Withdrawable part
10 8 11 Press rod (transfer of ON/OFF swit-
ching movement)
9 12 Vacuum interrupter chamber
13 Moving contacts
14 Pole partitions

Fig. 2.3
Vacuum circuit breaker HVX-E with withdrawable part for PIX high current switchgear
panels

7
3 Technical data

3.1 Type designation Example HVX 12 - 50 - 12 - E


The type designation on the name- Series HVX
plate (Fig. 2.1) specifies essential
technical data. The type designation Rated voltage 12 kV
(1) is broken down in this example.
Rated short-circuit breaking current 50 kA

Rated normal current 1250 A

F: fixed type
E: Withdrawable unit

The following data on the nameplate


are relevant for replacement or in
case of any queries: 2

• Type designation (1) 1 3


• Serial number (2)
• Year of construction (3) 4

Fig. 2.1
Nameplate
1 Type designation
2 Serial number
3 Year of construction
4 Technical data

3.2 Technical data

Rated voltage Ur [kV] 12 17,5


Rated lightning impulse withstand voltage Up [kV] 75 95
Rated power frequency withstand voltage Ud [kV] 28 38
Rated operating current Ir max. [A] 3150 1)
Rated cable-charging breaking current Ic [A] 25 31,5
Rated short-circuit breaking current Isc max. [kA] 50
Rated short-time current Ik max. [kA] 50 (3 s)
Rated frequency fr [Hz] 50/60
1) Higher rated currents possible on request (with fan)

8
3.3 Control and operating devices
The circuit breaker has been desi- Overview of rated supply voltages
gned on principle so as to permit
manual operation. Direct voltage DC [V] 24 48 60 110 125 220
Alternating voltage AC [V] (110) / 120 (220) / 230
The drive mechanisms of the indivi-
dual switching devices can be
equipped, depending on the specific Power consumption, solenoids and motor
customer's model, with additional
electrical control and operating devi- Solenoids/motor Power consumption [W]
ces. These are defined in the circuit Closing release < 250
breaker-specific wiring diagram ( see
Opening release < 250
separate documentation).
Undervoltage release 15
Component fitting options:
Secondary release 12
Motor for energy-storage device 150
Motor for withdrawable part < 200

• for charging the energy-storing Information about the power consumption of solenoids and the motor is available from
the manufacturer. The supply voltage data is required to this effect.
device (spiral spring)
• HVX-E: electric actuation of the
withdrawable part Operating times for solenoids and motor
Minimum command time "OFF" el. tripping [ms] 20
Closing release Minimum command time "ON" el. tripping [ms] 20
• 1 ea. Motor charging time [s] 4 – 12

Opening release Anti-pumping relay


• 3 ea. max. If an ON and OFF command is si-
multaneously and permanently pre-
sent at the circuit-breaker, the latter
Secondary release returns to its initial position after clo-
(Transformer-operated release)
sing. It remains in this initial position
• 1 ea. max. until the ON command is issued
anew. This prevents continuous clo-
Maximum equipment opening release
sing and opening ("pumping").
and secondary release: 3 units in to-
tal

Undervoltage release (optional)


• 1 ea.

Blocking coil
• Blocking coils prevent the circuit
breaker from being closed and
opened via the push-buttons
"ON" or "OFF", as well as manual
actuation of the withdrawable
part.
If the rated supply voltage has
fallen or is shut off, all blocking
coils are in "blocked" position.

9
Auxiliary switch Technical data of auxiliary switches for circuit-breaker (3 x 8-pole)
Auxiliary switches are always actua-
Rated DC AC
ted directly by the switch shaft via an
intermediate linkage. Their position supply voltage [V] <48 125 220 120 230
always corresponds to that of the
Switching capacity [A] 10 3,8 2 10
main contacts.
Time factor T=L/R [ms] 10 20 –
The switching functions have been
set in the factory according to the Rated short-time
250 A / 3 s
circuit diagram. current
Rated continuous
[A] 15
current

Auxiliary switch on the withdrawable part for PIX high current panels
Other switching functions of the au-
xiliary switch can be set by adjusta-
ble cams (Fig. 2.2).

Important: Cam
Nocken
The auxiliary switches may
only be set by specialists
who dispose of experience
regarding the auxiliary switches in-
stalled. Auxiliary switches must not
be disassembled.
Viewing direction for
Blickrichtung
adjustment
für die Einstellung

Fig. 2.2
Setting the cams of the auxiliary switch

Technical data of auxiliary switches on the withdrawable part for PIX high current panels

DC AC
Rated supply voltage
[V] 24 48 60 110 220 120 230

Switching capacity [A] 8 4 3 2 1 10

Time factor T=L/R [ms] < 20 –

Rated short-time current 100 A for a duration of 30 ms

Rated continuous current [A] 10

10
4 Shipping instructions

4.1 Packaging 4.4 Transport


• As standard, the switching devi- Transport using a forklift truck:
Type HVX Weight [kg]
ces are packed in cardboard bo-
xes and fastened on a pallet by Only transport the circuit-breaker on fixed type 230
means of two plastic straps. a pallet.
withdrawable unit 330
• For sea transport, several card- Transport without pallet:
(Guide values without packaging)
board boxes are additionally pak-
Lift circuit-breaker acc. to Fig. 4.2.
ked in a closed crate (also in
3 ropes (not metallic steel cables) Important:
container transport). The crate is
Ø 12 to 15 mm or straps are requi- HVX-E circuit-breakers with
hot-sealed in aluminium foil with
red to this effect. guide rollers on the withdra-
desiccant.
Warning! wable part (see also Fig. 5.4)
Make sure the rope or must be placed on wooden bars or
4.2 Delivery rails as shown in Fig. 4.1 in order
strap is strong enough
• Handle shipping units carefully to bear the weight of not to damage the guide rollers.
when unloading and unpacking the circuit-breaker.
them.
• Shipping units must be unpacked
immediately after receipt. Any da-
mage occurred in transit must be
recorded and reported immedia-
tely to the manufacturer.
• On delivery, the consignment
must be checked for complete-
ness.
• The supplier must be notified in
writing about any discrepancies.

4.3 Storage
If the switching devices are not in-
stalled immediately upon delivery,
they can be stored for max. 2 years if
packed in hot-sealed aluminium foil
with desiccant. The ambient conditi- 1
ons for storage must comply with the
admissible operating conditions.
Protect circuit breakers and acces-
sories against condensation.
2
Warning!
≥ 20
Sufficient stability and
evenness of the sup-
porting area (floor) Fig. 4.1
must be ensured. Lifting and depositing the HVX circuit-breaker
1 Guide rollers (only on the withdrawable part for PIX panels and for pole center
spacing of 254)
2 Wooden bars or rails as base

11
5 Assembly

5.1 Instructions for assembly


Warning!
Observe the safety pro-
• Dimension drawings are made The vacuum circuit-breakers HVX-F
visions of chapter 1.5.
available on request. and HVX-E are delivered in comple-
Warning! tely assembled and ready-to-operate
• Check technical data on name-
Risk of injuries. condition. They are supplied in posi-
plate.
The energy storing de- tion "OFF" and with the energy sto-
vice must not be char- • Check supply voltage for the ring device "released".
ged until assembly is finished. control and operating devices in-
stalled.

5.2 HVX-F – Mechanical assembly

Screws and attachments are not in-


cluded in the scope of supply.

Fastening the circuit-breaker


Warning!
The frame being used
must be suitable to
bear the weight of the
circuit-breaker (see Chapter 4).

Dimensions and arrangement of fas-


teners: see dimension drawing.

Important:
Comply with the specified
tightening torques (refer to
Annex).

Make sure not to distort the circuit-


breaker when screw-fastening it.

Earth terminal

• Design and dimensioning of the


Fig. 5.1
circuit-breaker's earth terminal
HVX-F
acc. to IEC 62271-100.
• Select the cross section of and
Important:
the material used for the earth
Coat contact surfaces and
conductor according to HD 637
comply with the specified
S1 or the appropriate national
tightening torques (refer to
work instruction.
Annex).

Connect earth line to the circuit-


breaker housing (see dimension
drawing).

12
Connecting conductor bars
Important:
Aluminium conductor bars
must not be connected to M 12
M12
silver-plated connection Thread reach
Einschraub-
areas of the circuit-breaker. Inadmis- 15 – 22 mm
tiefe 15-22 mm
sible matching of materials. 60
Important:
Coat contact surfaces and

50
90
comply with the specified
tightening torques (refer to
Annex).

340
30
• Take account of DIN 43 670 and
DIN 43 671 regarding the di-
mensioning for continuous cur-
rent.
• Maximum distance of the next
support point from the circuit-
breaker’s terminals in the directi-
on of the switch pole axis. 3 x
the pole center spacing of the
circuit-breaker (unless the next Fig. 5.2
High-voltage terminal for the HVX-F
supporting point is located in the
direction of the switch pole axis,
make sure that the circuit-brea- Connection areas
ker pole is not exposed to higher
electrodynamic forces). on the circuit-breaker on the conductor bar

• Screw-fasten conductor bar Silver-plated copper Copper or silver-plated copper


(take account of DIN 43 679). In case of aluminium:
use an intermediate layer of copper (thickness
• The circuit-breaker must not be 0.1 mm) corresponding to the full size of the
deformed by screw-fastening the connection area (reduction of rated normal
conductor bars. current by 13 %)

13
5.3 HVX-E – Mechanical assembly
A transport truck (optional) is used
to rack the circuit-breaker into the
switchgear panel (Fig. 5.6). For the
design and method of operation of
the transport truck used, please refer
to the instructions for the panel in
question.

Placing the circuit-breaker on


transport truck and racking
it into the switchgear

Important:
When performing the follo-
wing assembly steps, ob-
serve and comply with the
instructions given for the panel used.

Important:
Optionally, HVX withdrawa-
ble units and panels may
be coded to match (Fig.
5.4). This is to prevent a withdrawa-
ble unit from being racked comple-
tely into the panel if the rated data
do not match.
Fig. 5.3
1. Check the ratings indicated on Transport truck with HVX-E circuit-breaker in front of the panel
the nameplate between the
HVX-E and the appropriate pa-
3
nel.
2. Place the circuit-breaker on the 4
transport trolley rails.
3. Lock the circuit-breaker on the
transport trolley.
4. Couple the transport trolley to
the panel. 2

5. Unlock the circuit-breaker from


the transport trolley and rack the 1
circuit-breaker into the panel.
Fig. 5.4
– HVX withdrawable units for Bottom of a HVX-E circuit breaker for PIX switchgear panels
PIX panels must latch into 1 Spindle of the withdrawable part
the lock rocker of the panels 2 Spindle nut of withdrawable part
(Fig. 5.4). (must be latched in the cell)
3 Circuit-breaker coding
– HVX withdrawable units for 4 Guide rollers
PIX High Current Panels are
anchored in the panel by ac-
tuation of the withdrawable
part interlock (Fig. 5.5).
6. Release the transport trolley Fig. 5.5
from the panel. Withdrawable part locking device in pa-
nel

14
Earth terminal 5.4 Connecting the control lines
The switching device potential is lin- The control lines are connected, de-
ked to the panel via the four wheels pending on design, via control con- 1 2
of the withdrawable part (Fig. 5.6). nectors (Fig. 5.9 and 5.10) or con-
trol lines to the terminal strips in the
drive casing. The control lines are
wired in the circuit-breaker up to the
control connector or up to the termi-
nal strip.

Single-wire conductors or strands


can be connected

• to terminal strip up to 2.5 mm2


• in control connector up to 1.5
Fig. 5.6 Fig. 5.9
mm2 Control connector, 64-pin
Equipotential bonding within the cell
1 Insert control connector
2 Lock
Terminal with control connector
Optionally, the HVX-E circuit-breaker
is available with short-circuit proof Push the control connector onto the
earthing (Fig. 5.7 und 5.8). 64-(36-) pin right-angle plug-and
socket connector of the circuit-brea-
ker, and lock it (Fig. 5.9 und 5.10).

Important:
Connector interlock in case
1 of HVX-E: The control con-
nector on the panel can
only be inserted or removed while Fig. 5.10
the circuit-breaker is in disconnec- Insertion of the control connector, 36-pin
ted position.

Fig. 5.7
1 Earth bar at the HVX-E for PIX
Connection to terminal strip
switchgear panels
1. Remove the cover plate. 1

2. Connect external control lines via


the terminal strip (Fig. 5.11). The
valid wiring diagram has been en-
closed with each circuit-breaker.
If additional control lines are pla-
ced in the drive casing, leave a
sufficient distance from the mo-
Fig. 5.11
vable parts of the drive.
1 1 Control connection on terminal strip
3. After connecting the external
control line, mount the cover pla-
te.
Fig. 5.8
1 Earth bar at the HVX-E for PIX high Important:
current switchgear panels Comply with the tightening
torques specified for
screw-fastening (refer to
Annex).

15
6 Commissioning

• Check circuit-breaker for external Remove transport protection


damage.
Important: 1. Remove front cover.
• Make sure that there are no ex- Observe the warning and
2. Remove transport securing devi-
ternal parts in the circuit-breaker notification plates on the
ce (red) by releasing the thread-
compartment. front cover and in the drive
cutting screw M5 using a wrench
• Check surface of insulating com- (Fig. 6.1).
of TORX-Nr. T25 (Fig. 5.2). Store
ponents for impurities. If neces- The circuit-breaker is equipped with the device for maintenance work.
sary, clean (see Chapter 8). a transport securing device in the 3. Secure front cover again using
Important: drive (Fig. 6.1). Remove transport the screws. Tightening torque:
Observe the operating and securing device before commissio- 4.7 Nm + 15 %.
locking conditions (Chap- ning:
ter 7).

Important:
The energy storing device
of motorized circuit-brea-
kers is charged automati-
cally once the supply voltage is ap-
plied.

Important:
Undervoltage releases (op-
tional) enable switching
tests only to be performed
with the supply voltage applied.
2

1
3

Fig. 6.1
Remove transport securing device in the drive
1 Front cover
2 Transport protection
3 Label with instructions for commissioning

16
6.1 HVX-E 6.2 HVX-F
(withdrawable unit) (fixed type)
Perform functional tests: Check assembly work:
1. Charge energy-storing device – Check securing bolts.
using the crank. Check the spring
– Check the conductor bars'
position indicator.
screw couplings using a tor-
2. Switch circuit-breaker on and off que wrench.
several times by hand. Check po-
– Check the screw coupling of
sition indicator.
the earth terminal.
3. Move the withdrawable part to its
Perform functional tests:
service and disconnected positi-
on via the crank handle. 1. Charge energy-storing device
Check mechanical interlocks bet- using the crank. Check the spring
ween the HVX-E and the cell. position indicator.
Check position indication. 2. Switch circuit-breaker on and off
4. Check electrical functions of con- several times by hand. Check po-
trol and operating devices. sition indicator.
Apply supply voltage. 3. Check electrical functions of con-
5. Actuate the releases to perform trol and operating devices.
switching operations and check Apply supply voltage.
functions/interlocks. Watch posi- 4. Actuate the releases to perform
tion indicators. switching operations and check
6. Rack the circuit-breaker in and functions / interlocks.
out via the motor-drive (optional). Watch position indicators.
At the same time, check the posi- 5. Check interlocks between circuit-
tion indicators and the interlocks breaker and other devices.
in the circuit-breaker and with re-
gard to other devices.

17
7 Operation

7.1 Control elements and operator interface

button (rocker “O”) or pushbutton “O”


to switch circuit breaker OFF (open)

button (rocker “I”) or pushbutton “I” to


0 l switch circuit breaker ON (close)

Nameplate

Sachsenwerk Type HVX 24 -16 -00 -21


NO SW1 3340121001
U 24 kV
1999
Im 800 A / 50/60 Hz Operation counter
Um 125 kV Isc 16 kA /th 3 s
0 - 3min - 00-3min-00

Made in Germany

Position indicator of circuit breaker

00215 Position indicator of closing spring

Insertion opening for charging the


HVX energy storing device

Fig. 7.1
Operator interface of HVX circuit-breaker

1
1
1
2 2

2
3
3 3

4
4

Fig. 7.2 Fig. 7.3 Fig. 7.4


Control elements for the circuit-breaker Control elements for the circuit-breaker Control elements for the circuit-breaker
HVX-F HVX-E in PIX switchgear panels HVX-E in PIX high current switchgear
panels
1 closed door of switchgear panel 3 Spring charging crank for energy
2 ON/OFF operating rod storing device
4 Moving crank handle for withdrawa-
ble part
18
7.2 Interlocks
Warning! Mechanical interlocks Electrical interlocks
You must be familiar
The HVX switch features basic inter- have been designed according to
with these interlocks
locks to prevent operating errors. the circuit diagram.
before operating the
circuit-breaker.

Interlock Function of interlock Method of operation of interlock


Switch cannot be moved into service position un-
The opening for the moving crank
less the low-voltage connector is inserted and lok-
Between the circuit-breaker ked handle is locked
withdrawable part and the
low-voltage connector The low-voltage connector can only be inserted or The interlock between low voltage
removed while the withdrawable part is in its dis- connector and the withdrawable
connected position part is activated
The withdrawable part cannot be moved to service
The moving crank handle is uncou-
position in while the earthing switch of the switch-
Between the circuit-breaker gear panel is in "ON" position pled automatically
withdrawable part and the
earthing switch The earthing switch cannot be switched on once
The earthing switch cannot be
the withdrawable part has left its disconnected po-
switched on. Do not apply force!
sition
Circuit-breaker cannot be moved to service/discon- The opening for the moving crank
nected position while it is switched on handle is locked

Between the circuit-breaker The circuit-breaker cannot be switched on unless


and the withdrawable part – it is completely set to its service/ disconnected
The circuit-breaker cannot be swit-
position and
ched on or off
– the actuating crank for the withdrawable part
mechanism has been removed

7.3 Charging the energy storing device


Manually Via motor
Move circuit-breaker in "ready-for- The energy storing device of motori-
closing" position: zed circuit-breakers is charged auto-
matically as soon as the supply vol-
1. Insert crank into opening for ten- tage is applied.
sioning the energy storing device
(Fig. 7.5).
2. Charge the spiral spring using
the spring charging crank. As
soon as the spiral spring is char-
ged, the spring charging mecha-
nism is decoupled and the positi-
on indicator signals "charged"
(Fig. 7.5). If the motor starts du-
Fig. 7.5
ring this process, this does not
Turn spring charging crank until the po-
constitute a risk. sition indicator of the energy storage de-
vice indicates "charged".
3. Remove crank. The circuit-brea-
ker is ready for closing (table in
chapter 7.4, Pos. 2).

19
7.4 Switching the circuit breaker
Closing (ON) Opening (OFF)

l 0
• Push button "ON" (I) or • Push button "OFF" (O) or

• actuate closing release electrical- • actuate via opening release or


ly
• by undervoltage release or se-
The position indicator shows the condary release
switch position "ON" (table item 3).
The position indicator shows the
The position of the auxiliary switch switch position "OFF" (table item 1
has changed. or 2).

The energy storing device can be The position of the auxiliary switch
charged immediately after switching has changed.
ON (by hand or by motor). If supply
voltage is applied to the motor, char-
ging is performed automatically.
The position indicator shows the
energy storing device position "char-
ged" (table item 4).

Position indicators on circuit-breaker and possible operating sequences

Item Position indicator Position indicator possible operating


sequence
Energy-storing device ON/OFF
(closing spring) Switch position

1 released OFF none

2 charged OFF C- O

3 released ON O

4 charged ON O- C- O

C = Switching ON O = Switching OFF

20
7.5 Actuate withdrawable part
Important:
Observe interlock conditi-
ons (see chapter 7.2).

7.5.1 Withdrawable part for PIX 7.5.2 Withdrawable part for PIX high current switchgear panels
switchgear panels
Move circuit-breaker from Move circuit-breaker from
Move circuit-breaker from disconnected into service service into disconnected
disconnected into service position by hand: position by hand:
position by hand:
Initial situation: Initial situation:
Initial situation: Circuit-breaker OFF Circuit-breaker OFF
Circuit-breaker OFF Earthing switch OFF
Earthing switch OFF 1. Push interlocking slide (Fig. 7.7,
1. Push interlocking slide (Fig. 7.7, item 1) to the left to free the in-
1. Insert crank handle with integra- item 1) to the left to free the in- sertion opening.
ted slip coupling (Fig. 7.6) and sertion opening.
2. Insert crank (2) and turn it coun-
move it clockwise to its stop or
2. Insert crank (2) and turn it clock- ter-clockwise to its stop. The cir-
until the slip coupling reacts; the
wise to its stop. The circuit-brea- cuit-breaker moves into discon-
circuit-breaker is racked into its
ker moves into service position. nected position. The position in-
service position. Observe the po-
The position indicator must indi- dicator must indicate "O" (4).
sition indicator on the switchgear
cate "I" (3).
panel. 3. Remove crank.
3. Remove crank.

3
Fig. 7.6
Crank handle to rack the circuit-breaker 4
in and out

2. Remove crank handle.

Move circuit-breaker from


service into disconnected
position by hand: 2

Initial situation:
Circuit-breaker OFF
Fig. 7.7
1. Insert crank handle with integra- Moving the withdrawable part in PIX High Current Panels
ted slip coupling (Fig. 7.6) and 1 Interlocking slide to free the insertion opening
2 Crank
move it counter-clockwise to its 3 Position indicator “I”: Withdrawable part in service position
stop or until the slip coupling re- 4 Position indicator "O": Withdrawable part in disconnected position
acts; the circuit-breaker is racked
into its disconnected position.
Observe the position indicator on 7.5.3 Motor drive in the withdrawable part
the switchgear panel. Enter command to the local or remo-
2. Remove crank handle. te control. Observe position indica-
tor.

21
8 Servicing

8.1 Safety 8.2 Servicing schedule


Only specialist electricians certified 1. On principle, the 5 safety rules Series HVX vacuum circuit-breakers
by the manufacturer for maintenance applicable for electrical enginee- require regular inspections. The in-
work regarding series HVX vacuum ring must be complied with befo- tervals depend on the strain to which
circuit-breakers and who have the re maintenance work on the cir- the switches are subject during ope-
required knowledge regarding ope- cuit-breaker is started: ration, and on the operating conditi-
ration of medium-voltage switchgear ons.
• Isolate switchgear from power
are permitted to perform maintenan-
supply In case of frequent condensation or
ce and cleaning work.
• Prevent it from reclosing air pollution (dust, smoke or corrosi-
Warning! ve gases), the maintenance intervals
Observe the safety pro- • Verify it for zero voltage must be adapted to the actual condi-
visions of Chapter 1.5. • Earth and short-circuit it tions.

• Cover or bar off adjacent live IMPORTANT:


Warning! components. The circuit-breaker opera-
Risk of injury: ting company is responsible
2. Switch off the supply voltage for
The circuit-breaker for complying with the spe-
the circuit-breaker drive and se-
must not be disassem- cified maintenance intervals and for
cure it against reclosing.
bled for maintenance performing maintenance according
work. 3. Release the energy-storing devi- to the actual operating and ambient
ce by performing the correspon- conditions.
ding operating sequence on the
circuit-breaker OFF – ON – OFF In case of queries or ambiguities,
(see Chapter 7) and re-mount please contact the manufacturer.
the drive´s transport securing de-
vice (see Chapter 6).

Servicing schedule

Maintenance intervals (ambient conditions Qualification/position


Maintenance work
according to IEC 60 694) performing the work

• Check for contamination/condensation


and damage
at least every 4 years • If necessary, clean circuit-breaker/with-
drawable part (see section 8.3) and
perform several switching tests Staff qualified accordingly
• Clean, grease circuit-breaker/withdra- for the work to be done
wable part (see Chapter 8.3 and 8.6)
after 20 years and perform several switching tests
• Check releases and blocking coils for
proper working order
after 10,000 operating cycles of the circuit
Revision of the circuit breaker
breaker
after 1,000 operating cycles of the withdrawa-
Revision of the withdrawable part Manufacturer's Service
ble part
Center
once the max. admissible number of breaking
operations for the vacuum chambers has been Replace vacuum chambers
reached (see section 8.7)

22
8.3 Cleaning insulating 8.4 Corrosion 8.5 Avoid
components protection condensation
To ensure the specified insulating le- Drive mechanisms and covers have a To ensure the specified insulating le-
vel, the insulating components must long-term protection against corrosi- vel, the circuit-breaker - especially its
be clean. on. Any damage to the paint, scrat- insulating components - must not be
ches and other damage must be re- exposed to condensation.
On principle, general cleanliness of paired immediately to avoid corrosi-
the circuit-breaker or of its external on. Contact the manufacturer's Ser-
parts should be ensured. vice Center. Measures to take in case
of condensation:

Use a dry cleaning cloth for slight 1. If condensation of the circuit-


soiling: breaker is detected, the swit-
ching device must be cleaned
Clean by means of a dry, lint-free according to section 8.3.
cloth. Depending on dirt collected,
replace cloth as often as necessary. 2. Inspect or install heating. It must
provide a sufficient heating per-
formance to prevent condensati-
Use cleaning agents for severe on on the circuit-breaker.
soiling:
Cleaning agent, 1 l can (see Chapter
9.2).

The use of other cleaning agents is


not admissible.

• Wear protective gloves


• Use cleaning agent according to
manufacturer's instructions
• Soak the cloth thoroughly and
wipe the insulating components.
Keep duration of exposure as
short as possible.
• Expose the cleaned surface to
the air for at least two hours.
When performing cleaning, make
sure that the lubrication in the drive
mechanisms is not removed. If the
drive mechanisms are no longer suf-
ficiently lubricated, new lubrication
must be applied.

23
8.6 Lubrication instructions

Warning! Important: Important:


Comply with safety pro- The following elements Only approved lubricants
visions (Chapter 1.5). must not be lubricated: may be used (section 9.2).

- Motor Preparation
Warning! - Electric releases
Risk of injury: Remove the withdrawable part from
- Push switches
Circuit-breakers and the switchgear cubicle for inspection
- Blocking coils
drives must not be dis- (see instructions for the panel con-
- Auxiliary switches
assembled for service and cerned). Remove the cover plate of
- Ball bearings
maintenance work. the circuit-breaker drive and re-
mount the drive´s transport securing
device.

Lubricant Symbol Lubrication points Lubrication procedure


Drive: lever on plastic housing of spring charging Clean lubricating points using a lint-
Silicon grease
mechanism free cloth or a soft paint-brush, if ne-
Cryogenic grease Drive: roller levers cessary using cleaning agent (use
High-pressure Drive: cam discs, cogwheels and other friction sparingly, just moisten points of lubri-
grease points cation).
Contact lubricant Apply a thin coat of lubricant (using
Moving contacts, earth bar e.g. a paintbrush).
Kontasynth

Lubrication points inside the circuit breaker´s drive

Fig. 8.1 High-pressure grease Silicon grease


Circuit-breaker drive mechanism
Cryogenic grease

24
Withdrawable part in PIX switchgear panels
• Spindle of withdrawable part me-
2
chanism (Fig. 8.2, item 1). The
spindle is accessible from below
• Geared wheels of withdrawable
part mechanism (only in case of
motor-drive (Fig. 8.2, item 2)).
The geared wheels are accessi-
ble once the lower front cover
has been removed.

Fig. 8.2  High-pressure grease


Rack-in mechanism in PIX switchgear 1 Spindle
panels 2 Geared wheels

Withdrawable part in PIX high current switchgear panels

To obtain access to the lubrication


points, the withdrawable part must
KL
be in service position (see chapter
7.5.2).

FL

Fig. 8.3
Rack-in mechanism in PIX high current switchgear panels

Lubricant Points of lubrication Lubrication procedure


Clean lubricating points using a lint-free cloth or a soft paint-
All accessible friction and sliding brush, if necessary using cleaning agent (use sparingly, just
Lubricant KL
points in the rack-in mechanism moisten points of lubrication). Apply a thin coat of lubricant
(using e.g. a paint-brush).

Pour drops of liquid lubricant (oil can, drip feed lubricator)


Liquid lubricant Bearing, joints and guide mecha- into the bearing gap. Liquid lubricant gets between the be-
FL nisms in the rack-in mechanism aring surfaces due to the capillary effect. In case of inacces-
sible lubrication points, use an extension tube or spray.

25
Moving contacts
The lubrication procedure is descri-
bed in the table on page 24.

Fig. 8.4
Moving contacts
 Contact lubricant Kontasynth

Final steps
Remove transport securing device in
the drive. Re-mount the cover plate
and insert the circuit-breaker in the
panel (see section 5). Check circuit-
breaker according to section 6
"Commissioning".

26
8.7 Maximum admissible number of breaking operations of the vacuum chambers
The diagram defines exclusively the
Rated (normal) current Ir 1250
Bemessungs-Betriebsstrom Ir A, 2500
1250 A, 3150
A, 2500 A
A, 3150 A
maximum admissible numbers of
30 000
breaking operations of the circuit-
breaker as a function of the rated 10 000
normal current Ir and of the short-cir-

operations n n
5000
cuit breaking current Isc. It indicates

Ausschaltzahl
when the vacuum interrupter cham-
bers need to be replaced. 1000
500

Number of breaking
100
50

10
Ir I SC

Breaking current log


Ausschaltstrom log IIa

Ir = Rated (normal) current [A]


Isc = Short-circuit breaking current [kA]

The possible combinations depend


ISC [kA]
on the rated normal voltage: Ir [A]
31,5 40 50

1250 – – 
2500 – – 
3150   

For the data regarding the rated nor-


mal current Ir and the short-circuit
breaking current Isc, please refer to
the nameplate (Fig. 8.5). 1

Fig. 8.5
Data for rated normal current Ir (1) and short-circuit breaking current Isc (2) on the na-
meplate

27
9 Annex

9.1 Accessories

1 2 3 4

Fig. 9.1
Accessories for HVX circuit-breaker

Position Designation Order no.

1 ON/OFF operating rod AGS H35 446-01

2 Spring charging crank for spring operating mechanism AGS H30 498-01

AGS H31 642-01 1)


Moving crank handle with integrated slip coupling for withdrawable parts in PIX
3 AGS H32 532-01 2)
switchgear panels
AGS H31 674-01 3)

4 Moving crank handle for withdrawable parts in PIX high current switchgear panels AGS C66 911-01
1) Withdrawable part, manually actuated, shape of insertion opening: hexagonal
2) Withdrawable part, manually actuated, shape of insertion opening: square
3) Emergency crank handle for withdrawable part, motor-actuated

9.2 Auxiliary products


Only the following auxiliary products
Designation Symbol Order no.
may be used, which are available
from the manufacturer. The use of Cleaning agent, 1 l can S 008152
other auxiliary products is not admis-
Contact lubricant Kontasynth, 0.5 kg can S 008167
sible.
High-pressure grease ST 312-101-001
Warning!
Danger of injury when Cryogenic grease ST 312-105-001
wrong handling the au-
xiliary products. Comply Silicon grease ST 312-504-001
with the safety data sheets sup- Lubricant KL, 0,5 kg can ST 312-111-835
plied by the manufacturers of
the auxiliary products. Liquid lubricant FL, 0,5 kg can S 008153

28
9.3 Screw fastenings
The following elements must be
Thread Tightening torque Thread Tightening torque
used for all metal screw couplings:
size [Nm] size [Nm]
• Screws and bolts: min. max. min. max.
Grade ≥ 8.8
M5 3,8 4,7 M6 5,5 7,5
• Nuts:
M6 7 9 M8 15 19
Grade 8.
M8 16 24 M10 30 40
M10 36 44 M12 60 76
M12 63 77 Table 2:
Table 1: Screw coupling between switching
Hex. bolts and socket-head caps- device and conductor bar with cop-
crews (except slotted screws) and per as conductor material
nuts

9.4 How to treat the contact surfaces


Important: Important:
Caution when handling Contact areas coated with
bars insulated by heat- lubricant Kontasynth should
shrinkable sleeves: The not be touched, if possible.
heat-shrinkable sleeve must not get
into contact with lubricant (swelling).

1. Contact surfaces must be subjected to preliminary treatment before screw-fastening:

Material of contact surfaces Pre-treatment


Silver-plated contact surfaces Clean 1)
Copper or copper alloy Clean 1), expose metallic surface 2)

Aluminium Clean 1), expose metallic surface 2)

Zinc-plated steel Remove passivation, not, however, the zinc layer 3)

Hot-galvanized sheet-metal Clean 1), passivation need not be removed

1) Clean by means of lint-free cloth; use cleaning agent in case of serious contamination (see above)
2) Expose metallic surface
– by treating the entire surface with emery cloth or a rotating grinding tool (grain size 100 or 80) or
– using a wire brush which is clearly marked for use exclusively for aluminium or exclusively for copper
3) using a brass brush, steel brush

2. Immediately after the pre-treat-


ment, coat the contact surfaces
with lubricant Kontasynth so
that the space between the
contact surfaces is completely
filled once the screws have
been fastened.

29
Notes:
 +44 (0) 1785 250 070
AREVA T&D Worldwide Contact Centre
http://www.areva-td.com/contactcentre/
AREVA Energeitechnik GmbH - Sachsenwerk Medium Voltage - AGS 531 461-01 - © - AREVA - 2007. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA
The other names mentioned, registered or not, are the property of their respective companies - 389191982 RCS PARIS - Creation: WAB Ingenieurdienstleistungs GmbH Bayreuth - Printed in Germany

S-ar putea să vă placă și