ANDIVI TRC-A

TECHNICAL MANUAL
08/14, fw. ver. V1.2, V1.3

www.andivi.com

Andivi TRC-A Technical Manual

ATTENTION!
In the event of an incorrect connection of the room controller or a short circuit in
the installation and actuators, irreparable damage to the room controller can occur.
Therefore, pay special attention during the installation and follow the instructions
carefully!

CAREFUL!
Regular maintenance of convectors can avoid excessive burdens of the room
thermostat, which can lead to the destruction of it. When a building is under
construction, the bearings in the convectors can often get too dusty, which can lead
to excessively high starting current that can damage or destroy the room thermostat.

Carefully read these instructions before starting the installation.


Room controller Andivi must be installed according to applicable standards.
Before any intervention, make sure the power is turned off.

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

index

FRONT VIEW (LEGEND OF SYMBOLS)

INSTALLATION
MOUNTING ON ELECTRIC BOX
MOUNTING THE FRONT COVER
WIRING EXAMPLE

5
5
5
5

OPERATION
ROOM CONTROLLER TYPES
USER MODE OPERATION
WORKING MODE
Cooling MODE
heating MODE
ON FUNCTION
ANTI-FREEZING PROTECTION
ECONOMY MODE
PROTECT MODE
FIRMWARE VERSION
ENGINEER MODE OPERATION
Table: Engineer mode menu items description

NETWORK SPECIFICATIONS

Table: Read/Write Coils (function code 01/05/15)

Table: Read discrete input (function code 02)
Table: Read/write holding register (function code 03/06/16/23)

Table: Read input register (function code 04)

6
6
6
7
7
8
8
8
9
9
9
10
11
13
14
15
16
18

WARRANTY, CONDITIONS

19

08/14, fw. ver. V1.2, V1.3

Intelligent room controller

TRC-A Technical Manual


15

14

13

12

11

10
9

6
7

Fig 1-1: Front view

Item

Description

FIRE icon or Flake icon

Fire icon for Heating action; Flake icon for Cooling action

ON/Active icon

Indicate room controller ON status

Sleep icon

[not used]

Clock icon

Indicate Protect mode

DOWN button

Decrease setting / Previous item

UP button

Increase setting / Next item

FAN SPEED button

Toggle to change fan speed over Auto / Off / Stage I / Stage II / Stage III

Power On/Off button

Turn room controller on/off

MODE button

Cooling/Heating changeover / Setting confirmation

10

House with thermometer icon

Indicate Anti-Freezing active

11

AUTO icon

Automatic fan mode

12

Fan icon

Indicate fan state

13

LCD

Display temperature and operation data

14

Moon icon

Indicate Economy mode

15

Thermometer icon

Temperature set-point mode

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

Installation
MOUNTING ON ELECTRIC BOX
1. Separate the back plate from the controller by loosening the cover screw.
2. Align the mounting holes on the screw holes of the electric box. Suitable is a 3-module electric box 3M, for example Gewiss
GW24203, GW24207; TEM Catez DM30, HM30. Electric box is mounted vertically.
3. Fix the back plate on the electric box by tightening the back plate screws. Suggested for use is Philips wider truss head
or washer head #6-32x 3/4(20mm).
4. DO NOT let the bolt head rise above the wall of the mounting holes of the back plate. It might cause a short circuit of the
room controller.

MOUNTING THE FRONT COVER


1. Lock front cover on the back plate by tightening the cover screw underneath with screwdriver of Philips electronic instrument
type or similar.

WIRING EXAMPLE
All wires that come from electric box must be inserted above the retainers of respective terminal block before tightening the
captive screws.
~

24VAC

ESI2

4
5
6
7
8

TR

Economy mode input (econ)


I.
II.
III.

FAN

EXT.L

RS 9

Remote sensor (RS)

10

Protect mode input (PROT)

ESI 11
A01 + 12

Cooling/Heating valve

0(2)-10Vdc

13
A02 + 14

Fig. 2-1:
2 Pipe Control, 24VAC

C+ 15

Modbus

C - 16

24VAC

ESI2

4
5
6
7
8

RS

Economy mode input (ECON)


I.
II.
III.

ESI

Remote sensor (RS)

Fig. 2-2:
4 Pipe Control, 24VAC

08/14, fw. ver. V1.2, V1.3

Protect mode input (PROT)

11

13
A02 + 14

C+ 15
C - 16

FAN

EXT.L

10

A01 + 12

TR

0(2)-10Vdc

Cooling valve

0(2)-10Vdc

Heating valve
Modbus

Andivi TRC-A Technical Manual

operation
ROOM CONTROLLER TYPES
The type of room controller is selectable in Engineer mode and over the Modbus communication.
Item

Description

B - Type

4-Pipe Heating or Cooling (Manually Selectable)

C - Type

4-Pipe Heating and Cooling (Auto changeover)

E - Type

2-Pipe Heating or Cooling (Manually Selectable)

USER MODE OPERATION


The first tier of operation includes settings as Figure 3-1 shows. To operate:
1. Press Power button ON or OFF to turn ON/OFF the room controller. In ON state, symbol ON is activated.
2. At state ON, press any other button to start the User Mode operation. Press FAN SPEED button to toggle over different fan
speeds. Press MODE button to toggle working modes over Cooling/Heating. Press Up/Down button to increase/decrease
temperature set-point;
3. If no button is pressed for 10 seconds, it will return to current temperature display with the latest setting.
Item

Description

Current Temperature

Display current temperature

Temperature Setting

Set the required temperature

Cooling/Heating Select

Toggle to change the working


mode over Cooling/Heating

Fan Auto/Continuous

Remarks

Only applied to models with Cooling/


Heating mode selectable types.

Toggle to change fan speed over


Auto / Off / Stage I / Stage II / Stage III

Current
Temperature
FAN
AUTO
Continuous

4
2

Temperature
Setting

0.5C
Cooling/
Heating
Select **

* Back to 1 when no
button was pressed for 10s
Fig. 3-1:
User Mode operation
sequence

08/14, fw. ver. V1.2, V1.3

** For Cool or Heat


selectable Models only

Andivi TRC-A Technical Manual

WORKING MODE
1. For Cooling or Heating mode manually
selectable type (B, E), working mode
depends on the users setting.
2. For Cooling and Heating mode
automatical changeover type (C),
working mode depends on the Room
temperature as following:

Cooling mode

Room
Temperature
Heating mode

Set-point
(SP)
Dead band
(BD)
DB

Cooling MODE

Valve control for cooling mode


Valve control for cooling mode

Valve control for Cooling mode

AO1 10V
AO1 10V

AO1 min.
output
AO1
min.
output

Room
Temperature
Room

Proportional
Band
(PB-R)
Proportional

Set-point
Set-point

Temperature

Band (PB-R)

Cooling
Cooling

FAN control for cooling mode


FAN control for cooling mode

1/3 PB
1/3 PB

FAN control for Cooling mode


Stage
Differential
Stage
Differential

Fan stage III


Fan stage III

1/3
Proportional
1/3
Band
(PB)
Proportional

Fan stage II
Fan stage II

Band (PB)

Fan stage I
Fan stage I

Fan Off
Set-point

Room
Temperature
Room

Set-point

Temperature

Fan Off

Cooling
Cooling

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

heating MODE

Valve
mode
Valvecontrol
control for
for heating
heating mode

Valve control for Heating mode


AO210V
10V
AO2

AO2min.
min.
AO2
output
output

Proportional
Proportional
Band (PB-R)
(PB-R)
Band

Set-point
Set-point

Room
Room
Temperature
Temperature

Heating
Heating

FAN control for heating mode


FAN control for heating mode

FAN control for Heating mode

1/3 PB
1/3 PB

Fan stage III

Stage
Differential
Stage
Differential

Fan stage III


1/3
Proportional
1/3
Band (PB)
Proportional
Band (PB)

Fan stage II

Fan stage II
Fan stage I

Fan stage I
Fan Off
Set -Point

Fan Off

Set -Point

Room
Temperature
Room
Temperature

Heating

Heating

ON FUNCTION
If Power On/Off button is locked, it is not possible to switch the room controller ON or OFF locally with the button. But the ON/
OFF state can be changed by the Modbus communication.

ANTI-FREEZING PROTECTION
1. If the present temperature falls under 10C (adjustable in Engineer mode and Modbus), a Heating valve opens to 100%. This
is active always, even when the room controller is off. In the 4-Pipe system (B or C), a Heating valve on terminal 14 activates.
In the 2-Pipes system (E), a valve output on terminal 12 activates. Anti-Freezing protection is ON by default, but it also is
switchable to OFF in the Engineer mode and Modbus.
2. If the present temperature falls under PtCF (default 10C), a fire icon and a house with thermometer will be active on
LCD.

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

Type

Room controller OFF

Room controller ON

2-Pipe system (E)

Valve is always ON

Valve is always ON

4-Pipe system (B or C)

Heating valveValve
is always
Heating valve is always ON
controlON
for Anti-Freezing Protection

Valve control for Anti-Freezing


Protection

0.5
Differential (C)

Valve 10V

Valve
not active
PtCF
(Temp. for Anti-Freezing)

Room
Temperature

Anti-Freezing

ECONOMY MODE
Economy mode can be activated with the digital input on terminal 4 or with the Modbus coil, address 3. Active Economy
mode is indicated with the Moon symbol on LCD. If the present temperature in this mode is between Economy Cooling setpoint and Economy Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits,
corresponding cooling or heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have
priority.

PROTECT MODE
Protect mode can be activated with the digital input on terminal 11 or with the Modbus coil, address 2. Active Protect mode
is indicated with the Clock symbol on LCD. If the present temperature in this mode is between Protect Cooling set-point and
Protect Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits, corresponding
cooling or heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have priority.

FIRMWARE VERSION
The firmware version can be read with the Power On/Off button pressed for over 5 seconds.

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

ENGINEER MODE OPERATION


It is highly recommended for this mode to be operated by trained engineers because it is related to system parameters that will
affect the control results. To operate:
1. Press Up and Down buttons for over 5 seconds to enter into Engineer mode.
2. Press UP or DOWN button to rotate the menu item and press MODE button to enter into the item.
3. Press UP or DOWN button to change the setting and press MODE button to confirm the setting and return to menu item
selection. If no button is pressed for 10 seconds, it will go back to menu item selection. The setting wont be changed then.
4. To leave Engineer mode, rotate till End and press MODE button or leave the button intact for 10 seconds.
5. Engineer mode can be locked for the user. In this case, it is not possible to enter in this mode with the above procedure. For
the safety reason, enter the Engineer mode is possible with the Up and Down buttons pressed for over 60 seconds.
6. Engineer mode operation flow chart:

E01

E01
Setting

E02

E02
Setting

No button pressed
for 10s under menu
item selection

Previous

End

Fig. 4-1:
Engineer mode operation
sequence

10

08/14, fw. ver. V1.2, V1.3

User
Mode

Andivi TRC-A Technical Manual

Engineer mode menu items description

Item Mnemonic

1
2

ESIC
ESIH

LOC

C Type
Default
Range

Description

Protect (PROT) Cooling set-point


Protect (PROT) Heating set-point
Locking buttons and functions
Examples:
Bit Value:
0: Unlock / enable all
0: Unlock / enable
1: Lock / disable
1: Disable Local
PROTECT
Bit Definition:
Bit 0: Local PROTECT 2: Lock MODE button
detection
3: Both 1 and 2
4: Lock Up/Down
Bit 1: MODE button
Bit 2: Up/Down
button
5: Both 1 and 4
button
Bit 3: FAN SPEED
7: 1, 2, and 4
button
8: Lock Fan button
Bit 4: On/Off button 16: Lock Power
Bit 5: Local Economy button
detection
127: Lock/disable all
Bit 6: Engineer mode
Bit 7: Not used

30.0
15.0

18
(Lock
MODE
and
Power
buttons)

Step

20.0~40.0
00.0~25.0

86.0
59.0

68.0~104.0 0.1 /
32.0~77.0 0.1 /

0~127

18
(Lock
MODE
and
Power
buttons)

0~127

247
C
E-type
7.2

2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
1
C/F
B, C, E
0~18.0
0.1C/F

0~10.0

7.2

0~18.0

0.1C/F

0.5
10.0
30.0
1
0.0

0.1~1.0
0~50.0
0~50.0
0~1
-9.0~9.0

0.9
50.0
86.0
1
0.0

0.1~1.8
32.0~122.0
32.0~122.0
0~1
-17.0~17.0

Source of temperature sensor

0~2

0~2

Proportional band for fan control


Deadband for I-value for temperature PI
regulator

4.0

0~10

7.2

0~18

0.1C/F
0.1C/F
0.1C/F
0: N.O. / 1: N.C.
0.1C/F
0: Built-in /
1: Remote
2: Built-in +
remote
(average)
0.1C/F

0.2

0~10

0.3

0~18

0.1C/F

Lowest fan speed used for fan auto mode

0~1

0~1

0~1

0~1

10
On
60
20
1
0.0
27.0
18.0

0~15
On/Off
0~500
0~120
0~1
-9.0~9.0
20.0~40.0
00.0~25.0

50
On
60
20
1
0.0
80.6
64.4

32~59
On/Off
0~500
0~120
0~1
-17.0~17.0
68.0~104.0
32.0~77.0

baud

Baud rate

19200

Prty

Parity / Data/ Stop bits

8N2

6
7
8
9

nodE
Unit
type
db

247
C
E-type
4.0

10

Pb

4.0

11
12
13
14
15

diFF
SP-L
SP-H
ESI
OFSt

Modbus Node ID
Unit
Type of room controller
Deadband for Cooling/Heating valve control
Proportional band for cooling/Heating
valve control (PB-R)
Stage differential
Low limit for temperature set-point
High limit for temperature set-point
PROTECT contact definition
Offset for built-in temperature sensor

2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
C/F
B, C, E
0~10.0

16

rS

17

F-Pb

18

i-db

19

LFAn

20

PvLC

21
22
23
24
25
26
27
28

PtCF
AntF
I-t
Pit
ESI2
EoSt
ES2C
ES2H

11

F Type
Default
Range

Display present value of temperature or setpoint for normal displaying


Present temperature to anti-freezing
Anti-Freezing Protection
Integral time (I-part) PI regulator
Period of sensor suffocating time
Economy contact definition
Offset for external temperature sensor
Economy (ECON) Cooling set-point
Economy (ECON) Heating set-point

08/14, fw. ver. V1.2, V1.3

19200

8N2

0: Stop /
1: Low speed
0: Display PV /
1: Display SP
0.1C/F

1 sec.
0: N.O. / 1: N.C.
0.1C/F
0.1C/F
0.1C/F

Andivi TRC-A Technical Manual

29

Fand

0~600

0~600

10 sec.

6 (0V)

0~125

6 (0V)

0~125

LSB (0.04V)

SPAn

Fan off delay


Minimum voltage on analog output AO1,
AO2
Analog output voltage Offset for AO1, AO2

30

OP-L

31

-5 (10V)

-55~0

-5 (10V)

-55~0

32

rE-C

Output AO1 - Cooling

0~1

0~1

33

rE-H

Output AO2 - Heating

0~1

0~1

34

HFAn

0~3

0~3

35

OutC

0~31

0~31

36

Outr

Maximum fan speed


3
Output control
Bit Value:
0: output controlled with internal r. regulator
1: output directly controlled via Modbus
communication
Bit definition:
0
Bit 0: AO1 - output Cooling valve
Bit 1: AO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 - bit 7: Not used
Not used

LSB (0.04V)
0: normal /
1: inverse
0: normal /
1: inverse
1

0: In fan Manual
mode fan is
active also in
case of inactive
Cooling/Heating
valve /
1: Fan can be
active only in
case of active
Cooling/Heating
valve
0: Disabled /
1: Enabled
0: Disabled /
1: Enabled

37

FAnr

Fan control

0~1

0~1

38

FCOL

Fan enable in Cooling mode

0~1

0~1

39

FHEt

Fan enable in Heating mode

0~1

0~1

40

Ao1d

0~100

0~100

1%

41

AO2d

0~100

0~100

1%

42

tFAn

300

0~9990

300

0~9990

10 sec.

43

IFAn

1000

0~9990

1000

0~9990

10 sec.

44

ESIt

0~600

0~600

10 sec.

45
46
47
48

FOnt
Ret1
tESt
End

10

0~9990

10

0~9990

10 sec.

12

Analog output AO1 value in case of direct


control (look at the setting OutC pos. 35)
Analog output AO2 value in case of direct
control (look at the setting OutC pos. 35)
Minimum time previous fan stage upward
Integral time (I-part) PI regulator for fan
control
Protect mode ON delay time via digital
input
Fan ON delay time in AUTO mode
Return to factory defaults
Self-diagnostic
Exit Engineer mode

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

NETWORK SPECIFICATIONS
Transmission
Physical layer: RS485 (2 wires)
Baud rate: 19200 bps
Data format (RTU mode): 1 start bit, 8 data bits, no parity check, 2 stop bit
Modbus
Address range: 1~247.
Suppose function code: 1, 2, 3, 4, 5, 6, 15, 16, 23.
Data format: address | function code | data 1 | | data n | CRC-16 low byte | CRC-16 high byte
Data bytes: 252 bytes (max.)
Temperature representation: the original temperature degree value has be multiplied by 10 to be saved in the register
Examples: 25.5C is represented by: 00 FF (in hex) i.e. 255 (in dec.)

5.0C is represented by: 00 32 (in hex) i.e. 50 (in dec.)

13

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

Read/Write Coils (function code 01/05/15)

Function Register
code
address

01

01

01

01
01

4
5

01

01

01

Function Register
code
address

05/15

05/15

05/15

05/15
05/15

4
5

05/15

05/15

05/15

14

Description

Definition

Status of room controller


Status of Protect mode
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Status of Economy mode
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Not used
Not used
Status of direct control for DO3 Fan Stage I
(Active only in case of active bit 2 of output direct control register refer to
Modbus holding register address 38 and Engineer table parameter 35 OutC.)
Status of direct control for DO4 Fan Stage II
(Active only in case of active bit 3 of output direct control register refer to
Modbus holding register address 38 and Engineer table parameter 35 OutC.)
Status of direct control for DO5 Fan Stage III
(Active only in case of active bit 4 of output direct control register refer to
Modbus holding register address 38 and Engineer table parameter 35 OutC.)

0: Off / 1: On

Description

Definition

Remote room controller On/Off control


Remote control for Protect mode
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Remote control for Economy mode
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 LOC.)
Not used
Not used
Direct control for DO3 Fan Stage I
(Active only in case of active bit 2 of output direct control register refer to
Modbus holding register address 38 and Engineer table parameter 35 OutC.)
Direct control for DO4 Fan Stage II
(Active only in case of active bit 3 of output direct control register refer to
Modbus holding register address 38 and Engineer table parameter 35 OutC.)
Direct control for DO5 Fan Stage III
(Active only in case of active bit 4 of output direct control register refer to
Modbus holding register address 38 and Engineer table parameter 35 OutC.)

0: Off / 1: On

08/14, fw. ver. V1.2, V1.3

0: Protect mode not active /


1: Protect mode active
0: Economy mode not active /
1: Economy mode active

0: Not active / 1: Active

0: Not active / 1: Active

0: Not active / 1: Active

0: Protect mode not active /


1: Protect mode active
0: Economy mode not active /
1: Economy mode active

0: Not active / 1: Active

0: Not active / 1: Active

0: Not active / 1: Active

Andivi TRC-A Technical Manual

Read discrete input (function code 02)

Function Register
code
address

15

02

02
02
02
02
02
02

2
3
4
5
6
7

02

02

Description

Status of Protect mode


(Effective only when the local PROTECT detection is enabled. Please
refer to Modbus holding register address 6, and Engineer table
parameter 03 - LOC.)
Status of Heating/Cooling action
Not used
Not used
Relay 3 (Fan Stage I)
Relay 4 (Fan Stage II)
Relay 5 (Fan Stage III)
Status of Economy mode
(Effective only when the local ECONOMY detection is enabled.
Please refer to Modbus holding register address 6, and Engineer
table parameter 03 - LOC.)
Status of Anti-Freezing Protection

08/14, fw. ver. V1.2, V1.3

Definition

0: Protect mode not active /


1: Protect mode active
0: Not active / 1: Active

0: Not active / 1: Active


0: Not active / 1: Active
0: Not active / 1: Active
0: Economy mode not active /
1: Economy mode active
0: Not active / 1: Active

Andivi TRC-A Technical Manual

Read/write holding register (function code 03/06/16/23)

Function
code

Register
address

03/06/16/23

03/06*/16*/23*

03/06/16/23

03/06/16/23
03/06/16/23

4
5

03/06/16/23

03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23

7
8
9
10
11
12

03/06/16/23

13

03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23

14
15
16
17
18

03/06/16/23

19

03/06/16/23
03/06/16/23
03/06/16/23

20
21
22

03/06/16/23

23

03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23

24
25
26
27
28
29
30
31
32
33
34
35

16

08/14, fw. ver. V1.2, V1.3

Description

Definition

SP
0~500 (0~50.0C)
Heating/Cooling mode (*Command write only for
0: Cool / 1: Heat
Cooling or Heating mode selectable type)
0: Off / 1: Manual Stage I / 2: Manual Stage II /
Fan mode
3: Manual Stage III / 4: Auto
Protect (PROT) Cooling set-point
C: 200~400 (20.0~40.0C) / F: 680~1040 (68.0~104.0F)
Protect (PROT) Heating set-point
C: 0~250 (00.0~25.0C) / F: 320~770 (32.0~77.0F)
Examples:
Bit Value:
0: Unlock / enable all
0: Unlock / enable
1: Disable Local
1: Lock / disable
Bit Definition (Low Byte): PROTECT
2: Lock MODE
0: Local PROTECT
Button
detection
3: Both 1 and 2
1: MODE button
4: Lock Up/Down
2: Up/Down buttons
LOCK
button
3: FAN SPEED button
Locking buttons and functions
4: Power On/Off button 5: Both 1 and 4
7: 1, 2, and 4
5: Local ECONOMY
8: Lock Fan speed
detection
button
6: Engineer mode
16: Lock Power
7: Not used
button
127: Lock/disable all
Baud rate
0: 2400 / 1: 4800 / 2: 9600 / 3: 19200
Data/Parity/Stop bits
0: 8O1 / 1: 8E1 / 2: 8N1 / 3: 8N2
Modbus node ID
1~255
C / F
0: C / 1: F
Type of room controller
0: E type / 1: B type /2: C type
Deadband for Cooling/Heating valve control
C: 0~100 (0~10.0C) / F: 0~180 (0~18.0F)
Proportional band for Cooling/Heating valve
C :0~100 (0~10.0 C) / F : 0~180 (0~18.0 F)
control (PB-R)
Stage differential
C: 1~10 (0.1~1.0C) / F: 1~18 (0.1~1.8F)
Low limit for temperature set-point
C: 0~500 (0~50.0C) / F: 320~1220 (32.0~122.0F)
High limit for temperature set-point
C: 0~500 (0~50.0C) / F: 320~1220 (32.0~122.0F)
PROTECT contact definition
0: N.O. / 1: N.C
Offset for built-in temperature sensor
C: -90~90 (-9.0~9.0C) / F:- 170~170 (-17.0~17.0F)
0: Built-in / 1: Remote / 2: Built-in + Remote
Sensor
(average)
Proportional band for fan control
C: 0~100 (0~10.0C) / F: 0~180 (0~18.0F)
Deadband for I-value for temperature PI regulator C :0~100 (0~10.0 C) / F : 0~180 (0~18.0 F)
Lowest fan speed used for fan auto mode
0: Stop / 1: Low speed
Display present value of temperature or set-point
0: Display PV / 1: Display SP
for normal displaying
Present temperature to anti-freezing
C: 0~150 (0~15.0C) / F: 320~1220 (32.0~122.0F)
Anti-Freezing Protection
0: Off / 1: On
Integral time (I-part) PI regulator
0~500 s
Sensor suffocating time
0~20 seconds
ECONOMY contact definition
0: N.O. / 1: N.C
Offset for external temperature sensor
C: - 90~90 (-9.0~9.0C) / F:-170~170 (-17.0~17.0F)
Economy (ECON) Cooling set-point
C: 200~400 (20.0~40.0C) / F: 680~1040 (68.0~104.0F)
Economy (ECON) Heating set-point
C: 0~250 (00.0~25.0C) / F: 320~770 (32.0~77.0F)
Fan off delay
0~600 s
Minimum voltage on analog output AO1, AO2
0~250 (step 0.04)
Analog output voltage Offset for AO1, AO2
-55~0 (step 0.04)
Output AO1 - Cooling
0: Normal output / 1: Inverted output

Andivi TRC-A Technical Manual

03/06/16/23
03/06/16/23

36
37

Output AO2 - Heating


Maximum fan speed

03/06/16/23

38

Output control

03/06/16/23

39

Not used

03/06/16/23

40

Fan control

03/06/16/23
03/06/16/23

41
42

03/06/16/23

43

03/06/16/23

44

03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06

45
46
47
48
49

Fan enable in Cooling mode


Fan enable in Heating mode
Analog output AO1 value in case of direct control
(look at the setting OutC pos. 35)
Analog output AO2 value in case of direct
control (look at the setting OutC pos. 35)
Minimum time previous fan stage upward
Integral time (I-part) PI regulator for fan control
Protect mode ON delay time via digital input
Fan ON delay time in AUTO mode
Return to factory defaults

17

08/14, fw. ver. V1.2, V1.3

0: Normal output / 1: Inverted output


0: Off / 1: Stage I / 2: Stage II / 3: Stage III
Bit value:
0: Output controlled with internal r. controller
1: Output directly controlled via Modbus
communication
Bit definition:
Bit 0: AO1 - output Cooling valve
Bit 1: AO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 - bit7: Not used
0: In fan Manual mode fan is active also in case
of inactive Cooling/Heating valve / 1: Fan can be
active only in case of active Cooling/Heating valve
0: Disabled / 1: Enabled
0: Disabled / 1: Enabled
0~100 %
0~100 %
0~9990 sec.
0~9990 sec.
0~600 sec.
0~9990 sec.
1: Reset to factory defaults

Andivi TRC-A Technical Manual

Read input register (function code 04)

Function
code

Register
address

04

Current temperature

04

Fan speed

04
04
04
04
04
04
04

3
4
5
6
7
8
9

Cooling controller
Heating controller
Cooling valve output AO1
Heating valve output AO2
Temperature of built-in sensor
Temperature of external sensor
Software version

Description

Definition

200~1000 (-20.0~100.0C)
0: Off / 1: Stage I /
2: Stage II / 3: Stage III
0~100 (0% - 100%)
0~100 (0% - 100%)
0~100 (0% - 100%)
0~100 (0% - 100%)
-200~1000 (-20.0~100.0C)
-200~1000 (-20.0~100.0C)
10H~FFH (V1.0~VF.F)

NOTICE:
If a value of a register is changed on the room controller (with buttons), a next write command to this value will be ignored,
and the room controller will not reply back anything. Those registers are:
1. Modbus Function 05,15 register address 01.
2. Modbus Function 06,16,23 register address 01~48.
For example, if users re-set the Set-Point valve with buttons, a next Modbus command Fun.06/16/23 reg. address 01 from DDC/
BMS will be ignored and the room controller will not reply back any to DDC/BMS sent. (Note: While a value of a register is changing on the room controller (with buttons), any write command to this value will be ignored, but the room controller will reply
back the same data which DDC/BMS sent.)
This special strategy is integrated, because registers must be changeable on both sites (master and slave).

18

08/14, fw. ver. V1.2, V1.3

Andivi TRC-A Technical Manual

Attention!
In the event of an incorrect connection of the room controller or a short
circuit in the installation and actuators, irreparable damage to the room
controller can occur. Therefore, pay special attention during the installation
and follow the instructions carefully!

EU DECLARATION OF CONFORMITY
We, Andivi, declare that this device is in compliance with the essential
requirements and other relevant provisions of Directive 2004/108/EC.

SAFETY WARNINGS
This device must be installed according to the applicable norms.
This device is for indoor use only.
Do not attempt to repair the device yourself; an after-sales service is
available. Any changes or modifications to this unit not expressly approved
by the party responsible for compliance could void the users authority to
operate the equipment.

IMPORTANT INFORMATION ABOUT YOUR RIGHTS AND OBLIGATIONS, AS


WELL AS LIMITATIONS AND EXCLUSIONS THAT MAY APPLY TO YOU,
YOUR RIGHTS AND THIS LIMITED WARRANTY
This Limited Warranty gives you specific legal rights. You may also have
other legal rights that vary by state, province or jurisdiction. The disclaimers,
exclusions, and limitations of liability under this Limited Warranty will not
apply to the extent prohibited by applicable law. For a full description of
your legal rights you should refer to the laws applicable in your jurisdiction
and you may wish to contact a relevant consumer advisory service.

WHAT THIS LIMITED WARRANTY COVERS; PERIOD OF COVERAGE


Andivi d.o.o., Zagrebska cesta 102, 2000 Maribor, Slovenia (Andivi)
warrants to the owner of the enclosed product that the product contained in
this box (Product) will be free from defects in materials and workmanship
for a period of two (2) years [one (1) year for Factory Refurbished Products]
from the date of delivery following the original retail purchase (the
Warranty Period). If the Product fails to conform to this Limited Warranty
during the Warranty Period, Andivi will, at its sole discretion, either (a)
repair or replace any defective Product or component; or (b) accept the
return of the Product and refund the money actually paid by the original
purchaser for the Product. Repair or replacement may be made with a new
or refurbished Product or components, at Andivis sole discretion.
If the Product or a component incorporated within it is no longer available,
Andivi may replace the Product with a similar product of similar function, at
Andivis sole discretion. This is your sole and exclusive remedy for breach of
this Limited Warranty. Any Product that has either been repaired or replaced
under this Limited Warranty will be covered by the terms of this Limited
Warranty for the longer of ninety (90) days from the date of delivery or the
remaining Warranty Period. This Limited Warranty is transferable from the
original purchaser to subsequent owners, but the Warranty Period will not
be extended in duration or expanded in coverage for any such transfer.

TOTAL SATISFACTION RETURN POLICY


If you are the original purchaser of the Product and you are not satisfied
with this Product for any reason, you may return it in its original condition
within thirty (30) days of the original purchase and receive a full refund.

WARRANTY CONDITIONS; HOW TO GET SERVICE IF YOU WANT TO CLAIM


UNDER THIS LIMITED WARRANTY
Before being able to claim under this Limited Warranty, the owner of the
Product must (a) notify Andivi of the intention to claim by sending and e-mail
to info@andivi.com<mailto:info@andivi.com> during the Warranty Period
and providing a description of the alleged failure, and (b) comply with Andivis
return shipping instructions, and (c) ship the Product at owners cost (except
where prohibited by applicable law) to Andivi for repair or replacement.
Andivi will have no warranty obligations with respect to a returned Product if
it determines, in its reasonable discretion after examination of the returned
Product, that the Product is an Ineligible Product (defined below). Andivi
will bear all costs of return shipping to owner, except with respect to any
Ineligible Product, for which owner will bear all shipping costs.

19

08/14, fw. ver. V1.2, V1.3

WHAT THIS LIMITED WARRANTY DOES NOT COVER


This warranty does not cover the following (collectively Ineligible
Products): Products marked as sample or sold as is; or Products that
have been subject to: (a) modifications, alterations, tampering, or improper
maintenance or repairs; (b) handling, storage, installation, testing, or use
not in accordance with the Installation Guide or other instructions provided
by Andivi; (c) abuse or misuse of the Product; (d) breakdowns, fluctuations,
or interruptions in electric power or the telecommunications network;
or (e) Acts of God, including lightning, fire, flood, tornado, earthquake,
or hurricane. This warranty does not cover consumable parts, unless
damage is due to defects in materials or workmanship of the Product, or
software (even if packaged or sold with the Product). Andivi recommends
that you use only authorised service providers for maintenance or repair.
Unauthorised use of the Product or software can impair the Products
performance and may invalidate this Limited Warranty.
Andivi does not warrant that operation of the Product will be error-free
or uninterrupted or that the Product will in every case process all data
correctly.

DISCLAIMER OF WARRANTIES
Except as stated above in this limited warranty, and to the maximum extent
permitted by applicable law, Andivi disclaims all express, implied, and
statutory warranties and conditions with respect to the Product, including
the implied warranties of merchantability, fitness for a particular purpose.
To the maximum extent permitted by applicable law, Andivi also limits the
duration of any implied warranties or conditions to the duration of this
limited warranty.

LIMITATION OF DAMAGES
In addition to the above warranty disclaimers, in no event will Andivi be
liable for any consequential, incidental, exemplary, or special damages,
including any damages for lost data or lost profits, arising from or relating
to this limited warranty or the Product, and Andivis total cumulative
liability arising from or related to this limited warranty or the Product
will not exceed the amount actually paid for the Product by the original
purchaser.

LIMITATION OF LIABILITY
Andivi disclaims all liability of any kind of Andivis distributors. The type of
Product peripherals that may be connected to your Product may change
from time to time. The services may be used to control your heating,
ventilation, and AC system or Product peripherals via the Product. Without
limiting the generality of the disclaimers above, all Product information is
provided for your convenience, as is, and as available. Andivi does not
represent, warrant, or guarantee that Product information will be available,
accurate, or reliable or that Product information or use of the services or
Product will decrease the energy consumption of your building. You are
solely responsible for all energy bills incurred by your home. You use all
Product information, the services, and the Product at your own discretion
and risk. You will be solely responsible for (and Andivi disclaims) any and
all loss, liability, or damages, including to your HVAC system, plumbing,
building, Product, Product peripherals, and all other items in your building,
resulting from your use of the Product information, services, or Product.
Product information provided by the services is not intended as a substitute
for direct means of obtaining the information. For example, a temperature
reading in the Product information provided by the services is not intended
as a substitute for reading the temperature as directly displayed by the
Product.
VARIATIONS THAT MIGHT APPLY TO THIS LIMITED WARRANTY
Some jurisdictions do not allow limitations on how long an implied
warranty lasts or exclusions/limitations on incidental or consequential
damages, so some of the limitations set out above may not apply to you.