TECHNICAL MANUAL
08/14, fw. ver. V1.2, V1.3
www.andivi.com
ATTENTION!
In the event of an incorrect connection of the room controller or a short circuit in
the installation and actuators, irreparable damage to the room controller can occur.
Therefore, pay special attention during the installation and follow the instructions
carefully!
CAREFUL!
Regular maintenance of convectors can avoid excessive burdens of the room
thermostat, which can lead to the destruction of it. When a building is under
construction, the bearings in the convectors can often get too dusty, which can lead
to excessively high starting current that can damage or destroy the room thermostat.
index
INSTALLATION
MOUNTING ON ELECTRIC BOX
MOUNTING THE FRONT COVER
WIRING EXAMPLE
5
5
5
5
OPERATION
ROOM CONTROLLER TYPES
USER MODE OPERATION
WORKING MODE
Cooling MODE
heating MODE
ON FUNCTION
ANTI-FREEZING PROTECTION
ECONOMY MODE
PROTECT MODE
FIRMWARE VERSION
ENGINEER MODE OPERATION
Table: Engineer mode menu items description
NETWORK SPECIFICATIONS
Table: Read/Write Coils (function code 01/05/15)
Table: Read discrete input (function code 02)
Table: Read/write holding register (function code 03/06/16/23)
Table: Read input register (function code 04)
6
6
6
7
7
8
8
8
9
9
9
10
11
13
14
15
16
18
WARRANTY, CONDITIONS
19
14
13
12
11
10
9
6
7
Item
Description
Fire icon for Heating action; Flake icon for Cooling action
ON/Active icon
Sleep icon
[not used]
Clock icon
DOWN button
UP button
Toggle to change fan speed over Auto / Off / Stage I / Stage II / Stage III
MODE button
10
11
AUTO icon
12
Fan icon
13
LCD
14
Moon icon
15
Thermometer icon
Installation
MOUNTING ON ELECTRIC BOX
1. Separate the back plate from the controller by loosening the cover screw.
2. Align the mounting holes on the screw holes of the electric box. Suitable is a 3-module electric box 3M, for example Gewiss
GW24203, GW24207; TEM Catez DM30, HM30. Electric box is mounted vertically.
3. Fix the back plate on the electric box by tightening the back plate screws. Suggested for use is Philips wider truss head
or washer head #6-32x 3/4(20mm).
4. DO NOT let the bolt head rise above the wall of the mounting holes of the back plate. It might cause a short circuit of the
room controller.
WIRING EXAMPLE
All wires that come from electric box must be inserted above the retainers of respective terminal block before tightening the
captive screws.
~
24VAC
ESI2
4
5
6
7
8
TR
FAN
EXT.L
RS 9
10
ESI 11
A01 + 12
Cooling/Heating valve
0(2)-10Vdc
13
A02 + 14
Fig. 2-1:
2 Pipe Control, 24VAC
C+ 15
Modbus
C - 16
24VAC
ESI2
4
5
6
7
8
RS
ESI
Fig. 2-2:
4 Pipe Control, 24VAC
11
13
A02 + 14
C+ 15
C - 16
FAN
EXT.L
10
A01 + 12
TR
0(2)-10Vdc
Cooling valve
0(2)-10Vdc
Heating valve
Modbus
operation
ROOM CONTROLLER TYPES
The type of room controller is selectable in Engineer mode and over the Modbus communication.
Item
Description
B - Type
C - Type
E - Type
Description
Current Temperature
Temperature Setting
Cooling/Heating Select
Fan Auto/Continuous
Remarks
Current
Temperature
FAN
AUTO
Continuous
4
2
Temperature
Setting
0.5C
Cooling/
Heating
Select **
* Back to 1 when no
button was pressed for 10s
Fig. 3-1:
User Mode operation
sequence
WORKING MODE
1. For Cooling or Heating mode manually
selectable type (B, E), working mode
depends on the users setting.
2. For Cooling and Heating mode
automatical changeover type (C),
working mode depends on the Room
temperature as following:
Cooling mode
Room
Temperature
Heating mode
Set-point
(SP)
Dead band
(BD)
DB
Cooling MODE
AO1 10V
AO1 10V
AO1 min.
output
AO1
min.
output
Room
Temperature
Room
Proportional
Band
(PB-R)
Proportional
Set-point
Set-point
Temperature
Band (PB-R)
Cooling
Cooling
1/3 PB
1/3 PB
1/3
Proportional
1/3
Band
(PB)
Proportional
Fan stage II
Fan stage II
Band (PB)
Fan stage I
Fan stage I
Fan Off
Set-point
Room
Temperature
Room
Set-point
Temperature
Fan Off
Cooling
Cooling
heating MODE
Valve
mode
Valvecontrol
control for
for heating
heating mode
AO2min.
min.
AO2
output
output
Proportional
Proportional
Band (PB-R)
(PB-R)
Band
Set-point
Set-point
Room
Room
Temperature
Temperature
Heating
Heating
1/3 PB
1/3 PB
Stage
Differential
Stage
Differential
Fan stage II
Fan stage II
Fan stage I
Fan stage I
Fan Off
Set -Point
Fan Off
Set -Point
Room
Temperature
Room
Temperature
Heating
Heating
ON FUNCTION
If Power On/Off button is locked, it is not possible to switch the room controller ON or OFF locally with the button. But the ON/
OFF state can be changed by the Modbus communication.
ANTI-FREEZING PROTECTION
1. If the present temperature falls under 10C (adjustable in Engineer mode and Modbus), a Heating valve opens to 100%. This
is active always, even when the room controller is off. In the 4-Pipe system (B or C), a Heating valve on terminal 14 activates.
In the 2-Pipes system (E), a valve output on terminal 12 activates. Anti-Freezing protection is ON by default, but it also is
switchable to OFF in the Engineer mode and Modbus.
2. If the present temperature falls under PtCF (default 10C), a fire icon and a house with thermometer will be active on
LCD.
Type
Room controller ON
Valve is always ON
Valve is always ON
4-Pipe system (B or C)
Heating valveValve
is always
Heating valve is always ON
controlON
for Anti-Freezing Protection
0.5
Differential (C)
Valve 10V
Valve
not active
PtCF
(Temp. for Anti-Freezing)
Room
Temperature
Anti-Freezing
ECONOMY MODE
Economy mode can be activated with the digital input on terminal 4 or with the Modbus coil, address 3. Active Economy
mode is indicated with the Moon symbol on LCD. If the present temperature in this mode is between Economy Cooling setpoint and Economy Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits,
corresponding cooling or heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have
priority.
PROTECT MODE
Protect mode can be activated with the digital input on terminal 11 or with the Modbus coil, address 2. Active Protect mode
is indicated with the Clock symbol on LCD. If the present temperature in this mode is between Protect Cooling set-point and
Protect Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits, corresponding
cooling or heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have priority.
FIRMWARE VERSION
The firmware version can be read with the Power On/Off button pressed for over 5 seconds.
E01
E01
Setting
E02
E02
Setting
No button pressed
for 10s under menu
item selection
Previous
End
Fig. 4-1:
Engineer mode operation
sequence
10
User
Mode
Item Mnemonic
1
2
ESIC
ESIH
LOC
C Type
Default
Range
Description
30.0
15.0
18
(Lock
MODE
and
Power
buttons)
Step
20.0~40.0
00.0~25.0
86.0
59.0
68.0~104.0 0.1 /
32.0~77.0 0.1 /
0~127
18
(Lock
MODE
and
Power
buttons)
0~127
247
C
E-type
7.2
2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
1
C/F
B, C, E
0~18.0
0.1C/F
0~10.0
7.2
0~18.0
0.1C/F
0.5
10.0
30.0
1
0.0
0.1~1.0
0~50.0
0~50.0
0~1
-9.0~9.0
0.9
50.0
86.0
1
0.0
0.1~1.8
32.0~122.0
32.0~122.0
0~1
-17.0~17.0
0~2
0~2
4.0
0~10
7.2
0~18
0.1C/F
0.1C/F
0.1C/F
0: N.O. / 1: N.C.
0.1C/F
0: Built-in /
1: Remote
2: Built-in +
remote
(average)
0.1C/F
0.2
0~10
0.3
0~18
0.1C/F
0~1
0~1
0~1
0~1
10
On
60
20
1
0.0
27.0
18.0
0~15
On/Off
0~500
0~120
0~1
-9.0~9.0
20.0~40.0
00.0~25.0
50
On
60
20
1
0.0
80.6
64.4
32~59
On/Off
0~500
0~120
0~1
-17.0~17.0
68.0~104.0
32.0~77.0
baud
Baud rate
19200
Prty
8N2
6
7
8
9
nodE
Unit
type
db
247
C
E-type
4.0
10
Pb
4.0
11
12
13
14
15
diFF
SP-L
SP-H
ESI
OFSt
Modbus Node ID
Unit
Type of room controller
Deadband for Cooling/Heating valve control
Proportional band for cooling/Heating
valve control (PB-R)
Stage differential
Low limit for temperature set-point
High limit for temperature set-point
PROTECT contact definition
Offset for built-in temperature sensor
2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
C/F
B, C, E
0~10.0
16
rS
17
F-Pb
18
i-db
19
LFAn
20
PvLC
21
22
23
24
25
26
27
28
PtCF
AntF
I-t
Pit
ESI2
EoSt
ES2C
ES2H
11
F Type
Default
Range
19200
8N2
0: Stop /
1: Low speed
0: Display PV /
1: Display SP
0.1C/F
1 sec.
0: N.O. / 1: N.C.
0.1C/F
0.1C/F
0.1C/F
29
Fand
0~600
0~600
10 sec.
6 (0V)
0~125
6 (0V)
0~125
LSB (0.04V)
SPAn
30
OP-L
31
-5 (10V)
-55~0
-5 (10V)
-55~0
32
rE-C
0~1
0~1
33
rE-H
0~1
0~1
34
HFAn
0~3
0~3
35
OutC
0~31
0~31
36
Outr
LSB (0.04V)
0: normal /
1: inverse
0: normal /
1: inverse
1
0: In fan Manual
mode fan is
active also in
case of inactive
Cooling/Heating
valve /
1: Fan can be
active only in
case of active
Cooling/Heating
valve
0: Disabled /
1: Enabled
0: Disabled /
1: Enabled
37
FAnr
Fan control
0~1
0~1
38
FCOL
0~1
0~1
39
FHEt
0~1
0~1
40
Ao1d
0~100
0~100
1%
41
AO2d
0~100
0~100
1%
42
tFAn
300
0~9990
300
0~9990
10 sec.
43
IFAn
1000
0~9990
1000
0~9990
10 sec.
44
ESIt
0~600
0~600
10 sec.
45
46
47
48
FOnt
Ret1
tESt
End
10
0~9990
10
0~9990
10 sec.
12
NETWORK SPECIFICATIONS
Transmission
Physical layer: RS485 (2 wires)
Baud rate: 19200 bps
Data format (RTU mode): 1 start bit, 8 data bits, no parity check, 2 stop bit
Modbus
Address range: 1~247.
Suppose function code: 1, 2, 3, 4, 5, 6, 15, 16, 23.
Data format: address | function code | data 1 | | data n | CRC-16 low byte | CRC-16 high byte
Data bytes: 252 bytes (max.)
Temperature representation: the original temperature degree value has be multiplied by 10 to be saved in the register
Examples: 25.5C is represented by: 00 FF (in hex) i.e. 255 (in dec.)
5.0C is represented by: 00 32 (in hex) i.e. 50 (in dec.)
13
Function Register
code
address
01
01
01
01
01
4
5
01
01
01
Function Register
code
address
05/15
05/15
05/15
05/15
05/15
4
5
05/15
05/15
05/15
14
Description
Definition
0: Off / 1: On
Description
Definition
0: Off / 1: On
Function Register
code
address
15
02
02
02
02
02
02
02
2
3
4
5
6
7
02
02
Description
Definition
Function
code
Register
address
03/06/16/23
03/06*/16*/23*
03/06/16/23
03/06/16/23
03/06/16/23
4
5
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
7
8
9
10
11
12
03/06/16/23
13
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
14
15
16
17
18
03/06/16/23
19
03/06/16/23
03/06/16/23
03/06/16/23
20
21
22
03/06/16/23
23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
24
25
26
27
28
29
30
31
32
33
34
35
16
Description
Definition
SP
0~500 (0~50.0C)
Heating/Cooling mode (*Command write only for
0: Cool / 1: Heat
Cooling or Heating mode selectable type)
0: Off / 1: Manual Stage I / 2: Manual Stage II /
Fan mode
3: Manual Stage III / 4: Auto
Protect (PROT) Cooling set-point
C: 200~400 (20.0~40.0C) / F: 680~1040 (68.0~104.0F)
Protect (PROT) Heating set-point
C: 0~250 (00.0~25.0C) / F: 320~770 (32.0~77.0F)
Examples:
Bit Value:
0: Unlock / enable all
0: Unlock / enable
1: Disable Local
1: Lock / disable
Bit Definition (Low Byte): PROTECT
2: Lock MODE
0: Local PROTECT
Button
detection
3: Both 1 and 2
1: MODE button
4: Lock Up/Down
2: Up/Down buttons
LOCK
button
3: FAN SPEED button
Locking buttons and functions
4: Power On/Off button 5: Both 1 and 4
7: 1, 2, and 4
5: Local ECONOMY
8: Lock Fan speed
detection
button
6: Engineer mode
16: Lock Power
7: Not used
button
127: Lock/disable all
Baud rate
0: 2400 / 1: 4800 / 2: 9600 / 3: 19200
Data/Parity/Stop bits
0: 8O1 / 1: 8E1 / 2: 8N1 / 3: 8N2
Modbus node ID
1~255
C / F
0: C / 1: F
Type of room controller
0: E type / 1: B type /2: C type
Deadband for Cooling/Heating valve control
C: 0~100 (0~10.0C) / F: 0~180 (0~18.0F)
Proportional band for Cooling/Heating valve
C :0~100 (0~10.0 C) / F : 0~180 (0~18.0 F)
control (PB-R)
Stage differential
C: 1~10 (0.1~1.0C) / F: 1~18 (0.1~1.8F)
Low limit for temperature set-point
C: 0~500 (0~50.0C) / F: 320~1220 (32.0~122.0F)
High limit for temperature set-point
C: 0~500 (0~50.0C) / F: 320~1220 (32.0~122.0F)
PROTECT contact definition
0: N.O. / 1: N.C
Offset for built-in temperature sensor
C: -90~90 (-9.0~9.0C) / F:- 170~170 (-17.0~17.0F)
0: Built-in / 1: Remote / 2: Built-in + Remote
Sensor
(average)
Proportional band for fan control
C: 0~100 (0~10.0C) / F: 0~180 (0~18.0F)
Deadband for I-value for temperature PI regulator C :0~100 (0~10.0 C) / F : 0~180 (0~18.0 F)
Lowest fan speed used for fan auto mode
0: Stop / 1: Low speed
Display present value of temperature or set-point
0: Display PV / 1: Display SP
for normal displaying
Present temperature to anti-freezing
C: 0~150 (0~15.0C) / F: 320~1220 (32.0~122.0F)
Anti-Freezing Protection
0: Off / 1: On
Integral time (I-part) PI regulator
0~500 s
Sensor suffocating time
0~20 seconds
ECONOMY contact definition
0: N.O. / 1: N.C
Offset for external temperature sensor
C: - 90~90 (-9.0~9.0C) / F:-170~170 (-17.0~17.0F)
Economy (ECON) Cooling set-point
C: 200~400 (20.0~40.0C) / F: 680~1040 (68.0~104.0F)
Economy (ECON) Heating set-point
C: 0~250 (00.0~25.0C) / F: 320~770 (32.0~77.0F)
Fan off delay
0~600 s
Minimum voltage on analog output AO1, AO2
0~250 (step 0.04)
Analog output voltage Offset for AO1, AO2
-55~0 (step 0.04)
Output AO1 - Cooling
0: Normal output / 1: Inverted output
03/06/16/23
03/06/16/23
36
37
03/06/16/23
38
Output control
03/06/16/23
39
Not used
03/06/16/23
40
Fan control
03/06/16/23
03/06/16/23
41
42
03/06/16/23
43
03/06/16/23
44
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06
45
46
47
48
49
17
Function
code
Register
address
04
Current temperature
04
Fan speed
04
04
04
04
04
04
04
3
4
5
6
7
8
9
Cooling controller
Heating controller
Cooling valve output AO1
Heating valve output AO2
Temperature of built-in sensor
Temperature of external sensor
Software version
Description
Definition
200~1000 (-20.0~100.0C)
0: Off / 1: Stage I /
2: Stage II / 3: Stage III
0~100 (0% - 100%)
0~100 (0% - 100%)
0~100 (0% - 100%)
0~100 (0% - 100%)
-200~1000 (-20.0~100.0C)
-200~1000 (-20.0~100.0C)
10H~FFH (V1.0~VF.F)
NOTICE:
If a value of a register is changed on the room controller (with buttons), a next write command to this value will be ignored,
and the room controller will not reply back anything. Those registers are:
1. Modbus Function 05,15 register address 01.
2. Modbus Function 06,16,23 register address 01~48.
For example, if users re-set the Set-Point valve with buttons, a next Modbus command Fun.06/16/23 reg. address 01 from DDC/
BMS will be ignored and the room controller will not reply back any to DDC/BMS sent. (Note: While a value of a register is changing on the room controller (with buttons), any write command to this value will be ignored, but the room controller will reply
back the same data which DDC/BMS sent.)
This special strategy is integrated, because registers must be changeable on both sites (master and slave).
18
Attention!
In the event of an incorrect connection of the room controller or a short
circuit in the installation and actuators, irreparable damage to the room
controller can occur. Therefore, pay special attention during the installation
and follow the instructions carefully!
EU DECLARATION OF CONFORMITY
We, Andivi, declare that this device is in compliance with the essential
requirements and other relevant provisions of Directive 2004/108/EC.
SAFETY WARNINGS
This device must be installed according to the applicable norms.
This device is for indoor use only.
Do not attempt to repair the device yourself; an after-sales service is
available. Any changes or modifications to this unit not expressly approved
by the party responsible for compliance could void the users authority to
operate the equipment.
19
DISCLAIMER OF WARRANTIES
Except as stated above in this limited warranty, and to the maximum extent
permitted by applicable law, Andivi disclaims all express, implied, and
statutory warranties and conditions with respect to the Product, including
the implied warranties of merchantability, fitness for a particular purpose.
To the maximum extent permitted by applicable law, Andivi also limits the
duration of any implied warranties or conditions to the duration of this
limited warranty.
LIMITATION OF DAMAGES
In addition to the above warranty disclaimers, in no event will Andivi be
liable for any consequential, incidental, exemplary, or special damages,
including any damages for lost data or lost profits, arising from or relating
to this limited warranty or the Product, and Andivis total cumulative
liability arising from or related to this limited warranty or the Product
will not exceed the amount actually paid for the Product by the original
purchaser.
LIMITATION OF LIABILITY
Andivi disclaims all liability of any kind of Andivis distributors. The type of
Product peripherals that may be connected to your Product may change
from time to time. The services may be used to control your heating,
ventilation, and AC system or Product peripherals via the Product. Without
limiting the generality of the disclaimers above, all Product information is
provided for your convenience, as is, and as available. Andivi does not
represent, warrant, or guarantee that Product information will be available,
accurate, or reliable or that Product information or use of the services or
Product will decrease the energy consumption of your building. You are
solely responsible for all energy bills incurred by your home. You use all
Product information, the services, and the Product at your own discretion
and risk. You will be solely responsible for (and Andivi disclaims) any and
all loss, liability, or damages, including to your HVAC system, plumbing,
building, Product, Product peripherals, and all other items in your building,
resulting from your use of the Product information, services, or Product.
Product information provided by the services is not intended as a substitute
for direct means of obtaining the information. For example, a temperature
reading in the Product information provided by the services is not intended
as a substitute for reading the temperature as directly displayed by the
Product.
VARIATIONS THAT MIGHT APPLY TO THIS LIMITED WARRANTY
Some jurisdictions do not allow limitations on how long an implied
warranty lasts or exclusions/limitations on incidental or consequential
damages, so some of the limitations set out above may not apply to you.
Copyright Andivi 2014 All rights reserved. Reproduction and distribution
prohibited without written authorization from Andivi.