NFPA EQUIPMENT SIZING GUIDE - VACUUM SYSTEM

Name of Facility:
Project Number:
ENTER REQUIRED DATA IN THE BLUE SHADED AREAS BELOW

VACUUM - NFPA Method


LOCATION OF OUTLETS

Units Required

Units

Outlet CFM

Simutanious Use
%

Outlet CFM

Anesthetizing Location
1
2
3

Operating Room
Cystoscopy
Delivery

0
0
0

Room(s)
Room(s)
Room(s)

3.5
2
1

100
100
100

4
5
6
7

Special Proced. (Open heart, Transplant, etc.)


Emergency/ Major Trauma Room
Other Anesthetizing Location
Evacuation Vacuum

0
0
0
0

Room(s)
Room(s)
Room(s)
Room(s)

4
3
1
2

100
100
50
100

1
2
3
4

(Non-Anesthetizing)
Recovery Room
I.C.U (Except Cardiac)
Cardiac I.C.U
Emergency Room

0
0
0
0

Bed(s)
Bed(s)
Bed(s)
Bed(s)

1.5
2
1
1

50
75
50
100

5
6
7
8

Special Procedures (X-Ray, dialysis, etc.)


Catherterization Lab
Surgical Excision Room
Neonatal I.C.U,

0
0
0
0

Room(s)
Room(s)
Room(s)
Bed(s)

1.5
1
1
1

30
10
10
50

1
2
3
4
5

(Non-Anesthetizing)
Patient Room - Surgical
Patient Room - Medical
Exam & Treatment Room
Nursery
Nursery Premature

0
0
0
0
0

Bed(s)
Bed(s)
Room(s)
Bassinet(s)
Bassinet(s)

1.5
1
1
1
1

15
10
10
10
25

1
2
3
4
5
6
7

Respiratory Care Dep't


Teaching
Autopsy
Location1: Vac*
Location2:
Location3:
Location4:

0
0
0
0
0
0
0

Room(s)
Room(s)
Table(s)
Outlet(s)
Outlet(s)
Outlet(s)
Outlet(s)

1.5
1.5
1.5
3

10
10
10
100

Acute Care Location

Sub-Acute Patient Care

Other Patient Rooms

0.00

Future Expansion
PEAK CALCULATED DEMAND IN SCFM @ 19"hg:
Altitude above sea level, ft:
PEAK CALCULATED DEMAND IN SCFM @ 19"hg, ALTITUDE ADJUSTED:

0.00
#N/A

NOTE: The system model below are provided as a reference and variation of the systems are available. Please contact your
local sales rep for details.
* Maybe used alone if you wish to only count outlets needed. You may change that field as you see fit.

Amico Source Contact Information


Project Management - USA
Project Management - Canada
Project Management - International
Parts
Tech Support

Telephone
1-877-462-6426
1-877-462-6426
1-877-462-6426
1-877-462-6426
1-888-770-6035

E-MAIL
as-usa@amico.com
as-canada@amico.com
as-intl@amico.com
as-parts@amico.com
as-techsupport@amico.com

Lubricated Rotary Vane System


System Model #

Drawing Link

Tank Mount Horizontal

#N/A

#N/A

Tank Mount Space Saver

#N/A

#N/A

Duplex Skid Mount

#N/A

#N/A

Triplex Skid Mount

#N/A

#N/A

Quadraplex Skid Mount

#N/A

#N/A

Dry Rotary Vane System


System Model #

Drawing Link

Tank Mount Horizontal

#N/A

#N/A

Tank Mount Space Saver

#N/A

#N/A

Duplex Skid Mount

#N/A

#N/A

Triplex Skid Mount

#N/A

#N/A

Quadraplex Skid Mount

#N/A

#N/A

Dry Contactless Claw System


System Model #

Drawing Link

Tank Mount Horizontal

#N/A

#N/A

Tank Mount Space Saver

#N/A

#N/A

Duplex Skid Mount

#N/A

#N/A

Triplex Skid Mount

#N/A

#N/A

Quadraplex Skid Mount

#N/A

#N/A

NFPA EQUIPMENT SIZING GUIDE - AIR COMPRESSOR SYSTEM


Name of Facility:
Project Number:
ENTER REQUIRED DATA IN THE BLUE SHADED AREAS BELOW

LOCATION OF OUTLETS

MEDICAL AIR - US Typical Method


Simutanious Use
Outlet CFM
%

Units Required

Units

Outlet CFM

Surgical Procedures
1
2
3
4
5
6
7

PreOp Holding
Major Invasive
Minor Invasive
Trauma and Emergency
Catherization & Lab work
Endoscopy
Recovery

1
2
3
4
5
6
7

X-ray, CAT, NMR, PET scans


Dialysis
Exam and Minor Treatment
EEG/EKG
Pulmonary Function
Respiratory Care
Observation

1
2
3
4

Birthing or LDRP
Delivery Room
Nursery
NICU

1
2
3

Adult ICU, CCU, etc.


Pediatric ICU (Except NICU)
Emergency (not surgical)

Workrooms

Medical Lab Uses

1
2
3
4
5
6

Patient rooms
Ventilator
Location1: Critical*
Location2: Non Critical*
Location3: Support Gas*
Location4:

0
0
0
0
0
0
0

Bed(s)
Room(s)
Room(s)
Room(s)
Room(s)
Room(s)
Bed(s)

1
3.5
2
3
1
2
1.5

10
100
100
100
10
100
50

0
0
0
0
0
0
0

Room(s)
Bed(s)
Room(s)
Room(s)
Bed or outlet
Bed or outlet
Bed or outlet

1.5
1.5
1
1
1.5
1.5
1

30
30
10
10
30
30
10

0
0
0
0

Room(s)
Room(s)
Bed(s)
Bed(s)

1
0.5
0.5
1.5

100
100
10
50

0
0
0

Bed(s)
Bed(s)
Bed(s)

2
2
2

50
50
10

Outlet(s)

1.5

10

Outlet(s)

1.5

25

0
0
0
0
0
0

Room(s)
Unit(s)
Outlet(s)
Outlet(s)
Outlet(s)
Outlet(s)

0.5
3
6
3.5
5

10
50
100
100
100

Tests and Outpatient Procedures

Perinatal and Pediatric

Intensive Care

Equipment Maintenance

Laboratory

Other

0.00

Future Expansion
PEAK CALCULATED DEMAND IN SCFM:
NOTES:
1. The SCFM above is based on a peak OUTLET demand of 50 psi. Air compressors operate at 100 psi. When sizing a compressor, you MUST
figure the compressor capacity for operation at 100 psi.

0.00

2. Air outlets in labs used for analysis, research or teaching should be supplied by a seperated compressed air system, not medical air system.
3. * Maybe used alone if you wish to only count outlets needed. You may change that field as you see fit.
Altitude above sea level, ft:
Intake air temperature, F:
Relative Humidity, %:

0%

PEAK CALCULATED DEMAND IN SCFM, ADJUSTED:


NOTE: The system model below are provided as a reference and variation of the systems are available. Please contact your
local sales rep for details.

Amico Source Contact Information


Project Management - USA
Project Management - Canada
Project Management - International
Parts
Tech Support

Telephone
1-877-462-6426
1-877-462-6426
1-877-462-6426
1-877-462-6426
1-888-770-6035

E-MAIL
as-usa@amico.com
as-canada@amico.com
as-intl@amico.com
as-parts@amico.com
as-techsupport@amico.com

Oil-less Scroll System


System Model #

Drawing Link

Tank Mount Horizontal

#N/A

#N/A

Duplex Skid Mount

#N/A

#N/A

Triplex Skid Mount

#N/A

#N/A

Quadraplex Skid Mount

#N/A

#N/A

Oil-less Reciproating System


System Model #

Drawing Link

Tank Mount Horizontal

#N/A

#N/A

Duplex Skid Mount

#N/A

#N/A

Triplex Skid Mount

#N/A

#N/A

Quadraplex Skid Mount

#N/A

#N/A

#N/A

S-ar putea să vă placă și