APPLICATION
The H7625B, H7635B, H7655B Duct-Mount and H7635C
Outdoor-Mount Humidity/Temperature Sensors are
universal Relative Humidity transmitters that can be
powered with either a +18 to 36 Vdc or 24 Vac supply.
The sensors use a half-wave bridge rectifier to convert
AC power to a usable DC voltage. The device also
includes a 20K ohm temperature sensor for optional use.
The humidity sensors are designed with a fieldselectable 4 to 20 mA, 0 to 5 Vdc, or 0 to 10 Vdc output
signal equivalent to 0 to 100% RH. All units are shipped
from the factory with a default setting to accept AC power
with three-wire, 0 to 10 Vdc loop-powered output.
INSTALLATION
Mounting
The method of mounting depends on the particular
sensor application. The following procedures include
outdoor and duct applications. Also refer to the
instructions for the electronic control.
Duct Mounting
The H7625B, H7635B and H7655B can be mounted in a
duct to sense humidity and temperature.
IMPORTANT
Select a location to expose sensor to average
duct humidity and temperature. Avoid locations
where stratification can cause sensing errors.
NOTES:
1.
2.
3.
4.
5.
6.
CAUTION
7.
CAUTION
63-25793
Outdoor Mounting
The H7635C senses outdoor air humidity and
temperature. Mount this control where it can sense
average outdoor air humidity and temperature. Normally,
the north side of a building provides a suitable location.
NOTES:
1.
7.
W7750B,C
0-10 Vdc On On Vout
W7760C,
(default)
W7753, W7760
H7621/31
T7350, XL50,
XL100,
XL500 XF
Modules, XFL
n/a
Controller
On On Vout
n/a
OFF
ON
0-10 VDC
NORMAL OPERATION
OFF
OFF
ON
ON
4-20 MA
OFF
ON
0-5 VDC
M22705
63-25793
WIRING
For voltage output, shielded cable (16-22 AWG) should
be used.
mA OUTPUT
TRANSDUCER
ONLY
18 TO 36 Vdc
POWER SUPPLY
Vin
Io
CONTROLLER, METER
OR RECORDER
+ INPUT SIGNAL
COMMON
GROUND
M22528
Fig. 2. Typical wiring diagram for transducer with twowire mA output and external DC power supply.
OUTDOOR
AIR
SENSOR
T7350
SUBBASE
T5
T6
T7
DISCHARGE
AIR
SENSOR
T4
HEAT
RELAY 2
T3
OS
OS
AS
AS
HP
RH
COMPRESSOR
CONTACTOR 4
W3/Y4 Y3
COMPRESSOR
CONTACTOR 2
W2
Y2
Y1
5
HS
HC
RC
AUX
W1
COMPRESSOR
CONTACTOR 3
Vo Gnd Vin
(0-10 Vdc)
(Vac)
MOTION
SENSOR
HEAT
RELAY 1
HUMIDITY SENSOR
4
1
FAN
RELAY
COMPRESSOR
CONTACTOR 1
ECONOMIZER
L2
L1
(HOT)
M22529
63-25793
P7640
COM
O OUT
COM
19
20
21
22
23
Vin (Vac)
Gnd
O Vo (0-10 Vdc)
O OUT
10
11
12
13
E
GND
AI
1
AI
2
AI
GND
AI
3
AI
4
AI
GND
AI
5
AI
6
AI
GND
AI
7
AI
8
AI
GND
DI
1
DI
2
DI
3
DI
4
25
26
27
28
18
PWR
W7760A
17
H76XX
P7640
PWR
24
GND GND
15
16
ANALOG
OUT
AO
AO
1
2
14
AO
GND
24
24
24
24
24
24
24 OUT 21 GND
VAC VAC VAC VAC VAC VAC VAC COM VDC
COM COM
OUT
29
31
32
33
34
35
36
37
38
39
40
E-BUS
41
42
E-BUS
43
L1
(HOT)
L2
M18302B
Fig. 4. Typical wiring diagram for 5-wire temperature/humidity sensor with Vdc output
(used with the XL15A controller).
63-25793
44
CHECKOUT
Converting Output Signal to Percent RH
CAUTION
4 to 20mA Signal
signal [in mA] 4
------------------------------------------------- = percent RH
0.16
Example: 12 mA output signal
(12 - 4)/ 0.16 = 50% RH
0 to 10 Vdc Signal
Example: 8 VDC transmitter signal output
8 Vdc/0.10 = 80% RH
Table 2. Troubleshooting.
Problem
Items to Check
No reading
Erratic readings
63-25793
APPENDIX
RH Test and Configuration DIP Switch Settings (Table 3)
IMPORTANT
Only adjust these switches for troubleshooting or
recalibrating the sensor. (Adjustment is not
normally necessary.)
For normal operation, always keep DIP switch 3
in the ON position. When DIP switch 3 is off, the
RH transmitter cannot read the sensor. This
inability-to-read forces the output to never
change.
Table 3. Test/Calibration Settings (Six-Switch Block).
Setting
Normal Operation (Default)
On
0% RH Output
On
50% RH Output
On
100% RH Output
On
Increment RH Output
On
Decrement RH Output
On
On On
63-25793
100% RH Output
Transmitter always outputs a signal of 20 mA, 5 VDC, or
10 VDC. The sensor does not affect the transmitter
output. Sensor doesnt affect the transmitter output.
CALIBRATION
All transducers are factory calibrated to meet/exceed published
specifications. Field adjustment should not be necessary.
IMPORTANT
Do not verify comparative RH with a sling
psychrometer. Too many variables exist which
induce errors into this process.
Recalibration must be done in a controlled
environment. Relative humidity must be held
stable while making any adjustment.
Verify the device output directly with calibrated
instrumentation and verify RH with calibrated
instrumentation. Never use a controller output.
With correct power applied, and only a meter
connected to the transducer output, ensure that
the output is proportional to the true RH.
Decrement RH Output
This DIP switch allows calibration in the same way as the
Increment RH. The difference is that each toggle results
in a decrease of 0.5% RH.
63-25793
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to,
the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages,
including attorneys fees, arising out of, or resulting from, any modification to the literature by you.
35 Dynamic Drive
customer.honeywell.com
U.S. Registered Trademark
2005 Honeywell International Inc.
63-25793 B.B. Rev. 01-05