Documente Academic
Documente Profesional
Documente Cultură
ASSIGNMENT 2
JOHN O’CONNOR
04/12/09
CONTENTS
SUMMARY……………………………………………………2
INTRODUCTION……………………………………………..3
CONCLUSION……………………………………………….11
DISCUSSION…………………………………………………12
REFERENCES………………………………………………..17
SUMMARY
This report entails information about fault limiting reactors, and my findings
are:
For the circuit shown below, generator voltage is 25kV, resistance is 0.7
Ohms and reactance is 8.5 Ohms.
The type of protection used is based on time delay overcurrent relays and
time-based discrimination.
INTRODUCTION
• Figure 2.1 below shows a series R-L circuit that represents the
impedance of a synchronous generator.
• Figure 3.1 below shows a radial 33kV distribution system fed from a Dy
transformer.
• What protection scheme would typically be, and is in place for this
system?
• Identify the protection strategy
• How does the protection of this system work in terms of function
principles
REPORT AND ANALYSIS
Resistance – 0.7Ω
Reactance – 8.5Ω
V
Iac =
Z
25000
Iac =
€ (0.7) 2 + (8.5) 2
Iac = 2.931kA
€
X 8.5
= = 12.14
R 0.7
K(0.5) = 1.48
€
€
Asymmetrical fault current, T= 3 cycles:
K(3) = 1.04
€
4
Vx in absolute terms = × 25kV = 1kV
100
1×1000
XL per phase €
= = 0.19Ω / phase
3 × 2931.25
Power €reactors are used for a number of different functions, from limiting fault
current to controlling and regulating the reactive power in a system. They are
essentially a winding with either an iron core or an air core.
A reactor has only one winding per phase and different types vary from air-
cooled to oil-immersed. The latter becoming more popular due to its
maintenance advantages and safety factor.
Reactors have different magnetic characteristics according to the intended
use. In the case of current limiting, a linear reactor is used. Reactors that have
linear magnetic characteristics are the air cored type (a.k.a. coreless type).
The lack of an iron core results in a large leakage flux (iron cores are used to
mitigate this loss in transformers). It is therefore necessary to provide some
type of shielding to prevent heat problems and the flux affecting the reactance
of the coil.
When reactors are used for current limiting they are connected in series with a
load, as shown below:
They limit currents by increasing the impedance of the circuit, as in the case
of the switching of high voltage capacitor banks. The inrush current when
carrying out this procedure is controlled by having a near constant reactance
provided by the air cored reactor adding impedance.
Identify and describe the protection scheme used in the system below
(Figure 1)
The figure above shows a radial 33kV distribution system fed from a Dy
transformer. The protection scheme used in this example is one that uses
circuit breakers and overcurrent relays that have time delays incorporated into
them. The system is designed so that there is minimal disruption in the event
of a fault.
The time delays on the relays are set up so that the circuit breaker closest to
the fault opens and the other upstream breakers remain closed. The strategy
relies on large current to be generated by a fault. The shortest delay times are
set on the furthest breakers from the source. This is because the fault current
will not be as large as a fault current nearer the transformer.
From the diagram shown above, a fault occurring at point P2 should cause
breaker B2 to open, whilst breaker B1 remains closed. Breaker B1 would
have a longer time delay than breaker B2. The next breaker upstream of the
breaker that should open on a fault also provides a back up, if for whatever
reason the first breaker fails to open.
With the radial distribution shown, the largest fault current will be closest to
the source, which is the transformer. Faults occurring further downstream will
have the impedance of the line to limit the fault current.
The grading of a system refers to the delay times decreasing as the distance
from the source increases. The delay settings have to take in to account the
type of breakers used in the system. Older breakers will take longer to trip,
150ms for older oil breakers, whereas modern breakers can operate in 50ms.
(Figure 2)
The diagram above shows the typical time delays (grading) on overcurrent
relays on a radial feeder.
(Figure 3)
The time delay from when the overcurrent occurs to when the breaker
operates is inversely proportional to the magnitude or size of the fault current.
Relay characteristics can vary from extremely inverse to definite, which
means the more a relay has an inverse characteristic, the faster it will operate
on higher fault currents.
Each phase has its own CTs and relays and if an imbalance is detected in
one phase the breaker will open all phases and the generator neutral.
(Figure 4)
Generator protection.
(Figure 5)
Transformer protection.
The asymmetrical fault current is found in a similar way, using the formula for
the asymmetry factor and using 3 as the value for t. Again multiplying the rms
fault current by the K value gives the asymmetrical fault current.
To find the reactance per phase in the case of the current limiting reactor with
a voltage drop of the reactor phase to phase of 4%, firstly involved finding the
actual value of the 4% of the voltage, which was 25kV.
Next the voltage is divided by the fault current multiplied by the square root of
three to give the reactance per phase in ohms.
DISCUSSION
The task in the report and analysis section dealing with relay protection
schemes was concerned with a radial system. Grading or the use of time
delay relays is also used with ring feeders as shown in the diagram below.
(Figure 6)
When a system is fed from two sources directional relays can be used. This is
because fault currents can flow in both directions. A directional relay operates
when fault currents are flowing in only one direction. They are often used in
conjunction with over-current relays.
The switching of high voltage capacitor banks can produce transients in the
power system. Transients are changes in voltage and/or current that can have
very short time periods. Capacitor switching transients are the result of a
capacitor becoming energised when discharged. In effect a short circuit is
created which results in high inrush currents and thus voltage dips on the
supply.
The high inrush currents can, over time, be detrimental to the switching
equipment and the capacitors themselves. It is important to limit these high
inrush currents as much as possible. There are several methods that can be
employed to do this, using reactors or inductors, pre-insertion inductors, zero-
crossing breakers and pre-insertion resistors.
A technical paper written by Michael Beanland, Thomas Speas and Joe
Rostron was prepared for a conference on relay protection in 2004.
Using a full-time inductor (reactor) to limit the inrush current to levels below
which any damage could occur to the switching device and the capacitor units
works although there is a trade off as the reactor is continuously energised
and produces heat losses from its resistance.