Documente Academic
Documente Profesional
Documente Cultură
CHAPTER 5
Fig. 1-1
In two-way design, as close as slab strips to the column support, it will carry a much higher
moment than that of the mid-span. This two-way design helps you attain an exact amount of force
distribution among the slab strip. After obtaining the moment in slab strips, the design of reinforcement
will follow.
CHAPTER 5
The slab thickness is the most important part of the dead load structure such that the weight of
the slab can be determined already. The minimum slab thickness must be thick enough to provide the
sufficient shear strength.
The following are the direct design method limitations according to NSCP 2010 code sec. 413.7:
1) There shall be a minimum of three continuous spans in each direction.
2) Panels shall be rectangular, with a ratio of shorter to longer span center-to-center supports
within a panel not greater than 2.
3) Successive span lengths center-to-center supports in each direction shall not differ by more
than one-third the longer span.
4) Offset of columns by a maximum of 10% of the span in direction of offset from either axis
between center lines of successive columns shall be permitted.
5) All loads shall be due to gravity only and uniformly distributed over an entire panel. Live load
shall not exceed two times dead load.
6) For a panel with beams between supports on all sides, the relative stiffness of beams in two
perpendicular directions
1 2 2
Eq. 1-1
2 1 2
Shall not be less than 0.2 nor greater than 5.0, where 1 and 2 are calculated in accordance
with equation (1-3).
Eq. 1-2
7) Moment redistribution as permitted by section 408.5 shall not be applied for slab systems
designed by the direct design method.
8) Variations from the limitations of section 413.7.1 shall be permitted if demonstrated by
analysis as long as requirements of section 413.6.1 are satisfied.
Fig.1-2
CHAPTER 5
409.6.3.3
For slabs with beams spanning between the supports on all sides, the minimum thickness shall be
as follows:
1. For fm equal to or less than 0.2, the provisions of section 409.6.3.2 shall apply.
2. For fm greater than 0.2 but not greater than 2.0, the thickness shall not be less than:
36+5( 0.2)
(0.8 +
1400
Eq.1-3
(0.8+
)
1400
Eq.1-4
36+9
CHAPTER 5
4. At discontinuous edges, an edge beam shall be provided with a stiffness ratio fm not less than
0.8; or the minimum thickness required by Eq. 1-3 or 1-4 shall be increased by at least 10% in the
panel with a discontinuous edge.
413.3.5
When used to reduce the amount of negative moment reinforcement over a column or minimum
required slab thickness, a drop panel shall:
1. Project below the slab at least one quarter of the adjacent slab thickness; and
2. Extend in each direction from the centerline of support a distance not less than one-sixth the span
length measured from center-to-center of supports in that direction.
413.7.3.3
In an end span, total factored static moment Mo shall be distributed as follows:
CHAPTER 5
413.7.4.2
Column strips shall be proportioned to resist the following percentage of exterior negative
factored moments:
Linear interpolation shall be made between values shown, where t is calculated in Eq. 413-5 and C is
calculated in Eq. 413-6
Eq. 1-5
2
3
= (1 0.63 )
Eq. 1-6
The constant C or T or L-sections shall be permitted to be evaluated be dividing the section into separate
rectangular parts, as defined in sec. 413.3.4, and summing the values of C for each part.
413.7.4.3
Where supports consists of columns or walls extending for a distance equal to or greater than
three-fourths the span length l2 used to compute Mo, negative moments shall be considered to be
uniformly distributed across l2.
413.7.4.4
Column strips shall be proportioned to resist the following percentage of positive factored
moment:
CHAPTER 5