GESTRA

GESTRA Steam Systems

Intermittent blowdown valve MPA / PA up to PN250


z Intermittent Blowdown Valve
z Special Design
-Radial Multi-stages Nozzle
-Large Opening Area
-Spring Closing Force
z Fail Safe Function
z Boiler Pressure closes Valve
z Pneumatic Actuator Possible
z Function max
max. 3 Sec.
Sec
z PN 40-250
z DN 20-50

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Boiler water discharge of different valves

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 31 of 74

GESTRA

GESTRA Steam Systems

Automated intermittend blowdown system conventional

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Bottom Blowdown Range up to PN250

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 32 of 74

GESTRA

GESTRA Steam Systems

The Benefits of the New GESTRA Intermittent Blowdown Valves


Improved blowdown effectiveness through integrated pressure chamber in the outlet
section of the body
Greater
G t titightness
ht
th
throughh additional
dditi l wiper
i rings
i
between
b t
the
th packing
ki seals
l
Longer service life and availability through radial stage nozzle downstream of the valve
seat
Insensitive to waterhammer through absence of large body cover
Reduced wear through new arrangement of the seals on the low pressure side
Consistent
C i t t implementation
i l
t ti off th
the workk safety
f t regulations
l ti
th
throughh novell di
distance
t
ttube
b
Quick and easy installation thanks to multifunction parts
g additional cupp springs
p g actingg on the
Reduced maintenance and service effort through
compression spring and through the possibility of tensioning the seals from outside
Better checking functionally through relief vent for leak detection from outside
Greater convenience through innovative clip fastening of the hand lever PA 46/47

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

Blowdown receiver

GESTRA Steam Systems

Flash steam discharge/vent

Cooling Water

Hot waste water


Cooling Water
Mixed cooled water

Drain

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 33 of 74

GESTRA

GESTRA Steam Systems

Boiler blow down with sample cooler

For Safety
For Accurate Measurement
[Result of Lab test from sampling
without sample cooler leads to too
high TDS, resulting in the excessive
blowdown due to loss of flash steam
to atmosphere]

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Excessive Blowdown from sampling without sample cooler


Ex :

Boiler Pressure 10 barg with boiler TDS = 3500 ppm (mg/l)


or
TDS / water = 3,500 / 1,000,000 = 0.0035
Sample water from 10 barg to ATM will flash by 16%
so water
t ffrom 1,000,000
1 000 000 kg
k will
ill bbe 160,000
160 000 kg
k off flflashh steam
t
TDS / water new = 3,500 / 840,000 = 0.0042
D i ti = [0
Deviation
[0.0042-0.0035]x100
0042 0 0035] 100 / 0.0035
0 0035 ~ 20% hi
higher
h th
than the
th fact
f t
So if we calibrate TDS from this lab value then the exact value in the
boiler is by 2,916 ppm excessive blowdown Energy Loss

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 34 of 74

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Flash vessel

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 35 of 74

GESTRA

GESTRA Steam Systems

Flash vessel

GESTRA

GESTRA Steam Systems

GESTRA Flash Vessel Design

Large diameter

Velocity of evaporation rate is


0 6 0 8 m/s
0.6-0.8
/ tto avoid
id carry over.
Condensate inlet over a
tangential pipe helps reduce
the impact to the vessel.

condensate inlet over


a tangential pipe

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 36 of 74

GESTRA

GESTRA Steam Systems

Heat Recovery Skid

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 37 of 74

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

Or conductivity (uS/cm)

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 38 of 74

GESTRA

GESTRA Steam Systems

BA(E) 46 PN40 Surface blow down valve discharge capacity

GESTRA

GESTRA Steam Systems

(M)PA46 PN40 Bottom blow down valve discharge capacity

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 39 of 74

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

261.82 x (781.66-450.51)/2236.86
= 38.76
38 76 kg/h
= 38.76x 24 x 300 kg/year
y
= 279.07 ton/year
279,072 x4.18 x (107.434 - 30) kJ/year
= 90,328,384 kJ/year
= 90,328,384
90 328 384 /2236.86
/2236 86 = 40.38
40 38 ton/year
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

223.06 x 4.18 x (107.434 - 40) kJ/h


= 62,874.41 kJ/h
62,874.41/2236.86 kg/h
= 28.11 kg/h
= 28.11
28 11 x 24 x 300 kg/year
k /
= 202,382.7 kg/year
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 40 of 74

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 41 of 74

GESTRA

GESTRA Steam Systems

Heat Recovery from Surface Blowdown


Sensible heat of blowdown water = 261.82 x 781.66 = 204,654.22 kJ/h
at 10 barg (781.66 kJ/kg)
Sensible heat of drain point of = 261.82 x 4.18 x 40 = 43,776.3 kJ/h
blowdown water at 40
40C
C
(specific heat of water (C) ~ 4.18 kJ/kg)

Energy Recovery
Equivalent to 0.3 barg steam

= 204,654.22
204 654 22-43
43,776.3
776 3 = 160,877.92
160 877 92 kJ/h
= 160,877.92 /2,236.86 = 71.92 kg/h

(latent heat of steam (r) at 0.3


0 3 barg = 2,236.86
2 236 86 kJ/kg)

Equivalent steam saving per year= 71.92 x 300 x 24 = 517,824 kg/year


(steam cost = 985.12 B/t)
= 517.824
517 824 x 985.12
985 12
~ 510, 118 Baht + Water treatment cost
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Level
Control
Monitor

Page 42 of 74

GESTRA

GESTRA Steam Systems

Water Level Controls


The regulations concerning the control of Boilers vary from
Country to Country.
Country In general however we can say that most
regulations require the Boiler to be fitted with :-

Two independent low water alarms


A device to control the boilerwater level
within specified limits
Mostt regulations
M
l ti
also
l require
i th
the B
Boiler
il Al
Alarms tto bbe
tested daily.
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Extracted from Transaction Volume


4
Page 43 of 74

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float


body
magnet switch
magnet
g

rod
1 1

measuring chamber

float

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float


Routine test by pressure or magnetic force

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 44 of 74

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float


Problem
P
bl nott only
l ffrom th
the moving
i partt bbutt
also the boiler water quality
Float get struck from scale and dirt
Pitting (not cause boiler explosion)

Pitures extracted from other Safety Technology Bureau/ DIW

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float

Former German Regulation

body
magnet switch
magnet
g

rod
1 1

measuring chamber

float

Owing to the physical measurement principle


and the experience obtained in practice, which
i also
is
l reflected
fl t d in
i the
th TV ddamage ddata
t fil
files,
additional requirements for the operation were
p
of the technical
issued in the later development
rules; these included a reduction of the
maximum permissible boiler-water conductivity
f
from
8 000 to
8,000
t 300 S/cm,
S/
regular
l replacement
l
t
of the magnetic switches etc. measures
which were intended to pprevent boiler damage
g
but at the same time in-creased the operating
costs
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 45 of 74

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float

extracted from National Board BULLETIN Issue : winter 1999

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 46 of 74

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float

extracted from National Board BULLETIN Issue : winter 1999

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Water limiter Mechanical Float


Test Requirement EN 1295-9 for Mechanical Float in EU

Float Movement : min 250,000 test cycles


Electromechanical switches : min 100,000 cycle
Outside float and inside chamber : min 10 mm
No float switches for LW in EU
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 47 of 74

GESTRA

GESTRA Steam Systems

Developement of GESTRA boiler control equipment

1969
ER 14

1977
1972
ER 77
MR 16
First self monitoring

1978
ER 55

1981
1980
ER 96
ER 83-3
First Capacitance

1999
NRG 26

2010
NRG 16
SIL3

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Measuring Principals
z Conductive:

For level detection/Control

z Low level limiters


z Multiple tip electrodes
z Conductivity Control

z Capacitance:
C
it

F modulating
For
d l ti LLevell C
Control
t l

z Level control
z Integrated
I t
t d Hi
Highh llevell Al
Alarm

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 48 of 74

GESTRA

GESTRA Steam Systems

Pressure temperature range of Conductive Electrode


The conductive probes are available for:
z PN 6

Tmax: 156C / 313F

Pmax: 6 bar

z
z
z
z
z

Tmax: 180C / 356F


Tmax: 238C / 460F
Tmax: 275
275C
C / 527
527F
F
Tmax: 311C / 592F
Tmax:: 400C /752F

Pmax: 10 bar
Pmax: 32 bar
Pmax: 60 bar
Pmax: 100 bar
P max 183 bar

PN 10
PN 40
PN 63
PN 160
PN 320

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Conductive - Simple low level alarm

insulator
Isolator

Probe tip
Mespitze

Megef
egef
Measuring chamberM

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 49 of 74

GESTRA

GESTRA Steam Systems

Concept Design of Conductivity Electrode

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Possible danger of limiter with conventional design


2

insulator
1 1

Probe tip

M
Measuring
i chamber
h b
1

Short curcuit by means of deposits

condensation
after steam penetration

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 50 of 74

GESTRA

GESTRA Steam Systems

Simple low level alarm

insulator
Isolator

Probe tip
Mespitze

Electrode rod is covered by


PTFE to protect the short circuit

Measuring chamberMegef

**spacer to lock for multiple


Electrode tip

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Selection of Controller

extracted from National Board BULLETIN Issue : winter 1999

Spacer to lock electrode tips

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 51 of 74

GESTRA

GESTRA Steam Systems

Water level limiter special design self monitoring

monitoring electrode
fi t iinsulator
first
l t
second insulator

insulator

Monitoring electrode

probe tip

Probe tip

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

State of the Art Technology - Self Monitoring Level Limiter


Measured
Value
Device
Status
(Alarm,
Configuration,
Configuration
Watch Dog)

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 52 of 74

GESTRA

GESTRA Steam Systems

Basic of Self Monitoring : Wheatstone bridge

RST = R of insulation across monitoring electrode


and boiler shell => insulation check
RK = R across monitoring electrode and boiler shell
=> scale check
RP1, RP2 = Fixed R of the design circuit

R1/R2 = R3/Rx
IG => 0

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Failure Dianogsis of Periodic Self-Checking Controller

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 53 of 74

GESTRA

GESTRA Steam Systems

Boiler Equipment acc. TRD


For boiler operation acc.to TRD 604 (max. 72 hrs without supervision)
t self-monitoring
two
lf
it i low
l level
l l lilimiters
it are required
i d andd ffor bboiler
il operation
ti tto
TRD602(max. 2 hrs) only one self-monitoring low-level limiter is necessary

Boiler Equipment acc.to PED, EN 12952 and EN12953


Self-monitoring
S
lf
it i equipment
i
t with
ith periodic-self
i di
lf checking
h ki iis required
i d ffor bboilers
il
with temperature/pressure rating > 1 bar and > 120C and a volume > 50 l
Two self-monitoring
self monitoring low
low-level
level for 24 hrs without supervision

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Function Safety acc.to PED, EN 12952 and EN12953


Since the international standards IEC 61508 and IEC 61511 for functional
safety
sa
e y came
ca e intoo eeffect
ec there
e e has
as been
bee an
a ever-increasing
e e c eas g demand
de a d for
o
analysing equipment and process instruments that meet the requirements
accordingg to SIL ((Safetyy Integrity
g y Level)) classification. The European
p
directives
EN12952 and 12953 demand that a hazard analysis shall be carried out for
each limitingg device function and appropriate levels of functional safetyy be
Implemented.
Note 1 states : Typical Safety Integrity Level (SIL) requirements for boiler
protective systems are not less than 2

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 54 of 74

GESTRA

GESTRA Steam Systems

Safety Integrity Level (SIL) Overview

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Safety Integrity Level (SIL) Overview

Page 55 of 74

GESTRA

GESTRA Steam Systems

Safety Integrity Level (SIL) Overview

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Safety Integrity Level (SIL) of GESTRA low water limiter

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 56 of 74

GESTRA

GESTRA Steam Systems

ON-OFF LEVEL CONTROL APPLICATION

Pump on/off

Pump off
Pump on
Low Alarm 2
Multiple tip electrode
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Inside the Spector Compact NRGS 16-2

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 57 of 74

GESTRA

GESTRA Steam Systems

On- Off level control with self monitoring low level alarm

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

On/Off Level Control


Advantages
p , suitable for low capacity
p y boiler(<3-5
(
t/h),
), condensate and feed tank
Simple,
Inexpensive for investment
Good for stand by boilers
boilers.
Disadvantages
Intense thermal shock stress in the boiler
Leads to strongly
g y modulating
g operation
p
of burner
Integration into a heat recovery concept or exhaust gas cooling using the
principle
p is not p
possible
economizer p
More wear and tear on the feed pump and control gear and burner
Variable steam pressure and flow rate
rate.
More boiler water carry over.

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 58 of 74

GESTRA

GESTRA Steam Systems

Comparison: Intermittend / Continous


Intermittend with fixed switch points

Continuous with variable switch points

High level -Alarm

High level-Alarm

Pump Off

9
Set point

Pump On

Low level - alarm

Low level -Alarm

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Capacitance level probe

Measuring pipe

insulator

20 mA
4-20 mA adjustable
for the whole probe
length

Measuring chamber

4 mA
plug

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 59 of 74

GESTRA

GESTRA Steam Systems

Principle capacitance measurement

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Principle capacitance level measurement

Page 60 of 74

GESTRA

GESTRA Steam Systems

Principle capacitance level measurement

Capacitive Reactance XC

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Measurement with Capacitance Probes


Low Voltage
AC Supply
Current
Flows

Insulated
Probe
Rod

Less Current
Flows

Liquid
in a
Metal
Vessel

Probe Deeply Immersed


Current flows due to Capacitance
between Probe rod and Water

Lower Water Level


Less Current Flows
Page 61 of 74

GESTRA

GESTRA Steam Systems

Level Calibration of Capacitance Probe


HD

H=HDielectric
HD = Steam
HT

HW

W = Water

T = Teflon
L = Air

HD

Probe tipp cannot be cut

Durch den Einflu des Druckes wird der


Luftspalt zwischen Teflonisolation und
g
Merohr verdrngt

Durch den Einflu der Temperatur lngt


sich der Teflonschlauch und wird somit
dnner

GESTRA

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA Steam Systems

Modulating level control-conventional

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 62 of 74

GESTRA

GESTRA Steam Systems

Pump speed control with compact probe NRGT 26-1


Frequency driven feedwater control

4...20 mA
Steam

SpeiseFeed water
wasser

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Modulating Level Control


Advantages
Economic Operation (economizer)
Higher steam quality (reduce carry over)
Steady steam pressure and flow rate.
No strongly modulating operation of burner and more efficient
burner operation.
Less thermal stress on the boiler shell.
Less wear and tear on the feed pump and burner.
Capability of adapting to difficult situations regarding the
controlled system e.g. sudden change of steam consuption
Disadvantages
Less suitable for stand
stand by
by operation.
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 63 of 74

GESTRA

GESTRA Steam Systems

Influence of the boiler capacity on the low level switchpoint

Main steam valve

Low level limiter

Main steam valve

Steam area

Low level limiter

Steam area

Combustion tube

Fire tube

Shell boiler without steam p


production

Shell boiler with steam p


production

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Sudden increasing steam consumption in the boiler leads to :


z Pressure drop in the boiler
z Extension of steam bubbles
z Increasing water level
z Closure of the control valve
z Pressure drop leads to increasing burner output
z Steam bubbles are compressed
z Water level decreases partial below low level
z Boiler is shut down due to low level alarm !
z Remedy ????

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 64 of 74

GESTRA

GESTRA Steam Systems

Mode of Boiler Operation


Sudden increase in steam consumption
Boiler performance during feedwater filling without
economizer
design
Operation at higher level or lower pressure of boiler design.
Three elements control for sudden change of steam
consuption

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Three element control


TIC
D

N
LIC

Boiler

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 65 of 74

GESTRA

GESTRA Steam Systems

Boiler equipment with SPECTORbus

GESTRA

GESTRA Steam Systems

Recommendation for installation 40 mm

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 66 of 74

GESTRA

GESTRA Steam Systems

Recommendation for installation 40 mm

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Self monitoring External Low Level Limiter


Risks with external
measuring pots :
Stop
Stop-valve
valve blocking
Mud inside level pot
F
Failure
il
in
i changing
h
i
level
l
l
detection

Page 67 of 74

GESTRA

GESTRA Steam Systems

Level probe installed in an external measuring pot with SRL

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Level probe installed in an external measuring pot with SRL

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 68 of 74

GESTRA

GESTRA Steam Systems

Compact Design and compatible to conventional systems


Easily accessible connection terminals
Compact Design and compatible to conventional systems
Supply voltage 24 VDC, improved EMC control (other voltages with separate power unit)
Switchable sensitivity : 0.5 or 10 S/cm
Supply via reliable networks possible without additional component (inverters)
Intuitive operating using rotary pushbutton or color touch display
SPECTORmodule Touch with separate control unit and greatly extended
functionality
Now also as modulating controller and three-element control
All limiter systems with SIL3 certification

GESTRA

GESTRA Steam Systems

SPECTORmodul TOUCH
Continous level controller

NRR 2-52
2 52

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 69 of 74

GESTRA

GESTRA Steam Systems

Screen shots of NRR 2-52 operating unit URB 50

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Screen shots of NRR 2-52 operating unit URB 50

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 70 of 74

GESTRA

GESTRA Steam Systems

Condensate Monitoring

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Diffuse or stray light in water


90 Streulicht

Scattering light
Lichtem pfnger
15 Streulicht
Lichtem pfnger
Durchlic ht

Opto
p transmitter

Opto
p reciver
Opto reciver

Lichtsender

Scattering of solids 90

Streuung von Feststoffen, daher


H auptanw endungsgebiet in der
Trinkw asser-A ufbereitung / -Versorgung

Scatteringg of oil 15

Streuung von ltropfen, daher A nw endung des


15 S tteulichtverfahrens
li ht
f h
zur lerkennung
l k

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 71 of 74

GESTRA

GESTRA Steam Systems

Functional principle of the OR


Automatische Kompensation von Strgren wie:
) Verfrbung
) Lampenalterung
p
g
) Verschmutzung der Glser

Automaticly compansation of
Variable disturbance

TV

Alarm
Ventil
Umschaltung

Alarm
Valve switch over

3 12 V

Istwert
X

Sollwert
W

Lampenspannung
12 V

Actual value
Setpoint

Voltage 12 V

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Saving from Condensate Return


Condition : Condensate 1 t/h, P1 = 5 barg, P2 = 0.3 barg
Sensible heat of blowdown water = 1,000 x 671
= 671,000 kJ/h
at 5 barg (671 kJ/kg)
Feed water temp 30
30C
C
= 1,000 x 4.18 x 30 = 125,400 kJ/h
(specific heat of water (C) ~ 4.18 kJ/kg)

Energy Recovery
Equivalent to 0.3 barg steam

= 671,000
671 000-125
125,400
400 = 545,600
545 600 kJ/h
= 545,600 /2,236.86 ~ 244 kg/h

(latent heat of steam (r) at 0.3


0 3 barg = 2,236.86
2 236 86 kJ/kg)

Equivalent steam saving per year= 244 x 300 x 24 = 1,756,800 kg/year


(if steam cost = 1,000 B/t)
= 1,756.8
1 756 8 x 1,000
1 000
~ 1,756, 800 Baht + Water treatment cost
ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 72 of 74

GESTRA

GESTRA Steam Systems

Example of saving from condensate return

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

GESTRA

GESTRA Steam Systems

Example of saving from condensate return

ENERGY TECHNOLOGY CO., LTD. 0-2721-3860

Page 73 of 74

GESTRA

GESTRA Steam Systems

Page 74 of 74