External Static Pressure Calculation Sheet

Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

2.9

5.1

136.88

2.9

5.1

136.88

0.492

0.32

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)

DISCHARGE SIDE
SUPPLY AIR
GRILLE

250*200

Straight Duct

350*150.

VCD

350*150.

2.9

5.1

0.52

136.88

0.492

2.65

ELBOW

350*150.

2.9

5.1

0.16

136.88

0.492

0.82

Straight Duct

350*150.

2.9

5.1

136.88

0.492

2.09

Reducer

350*150/350*275

2.9

5.1

0.05

136.88

0.492

0.26

TEE

350*275X 300*225

9.7982

0.11

363.44

0.61

1.08

9.7982

363.44

0.61

4.91

9.7982

363.44

0.61

0.49

0.65

42.40

1-2.

Straight Duct
Reducer

2-3.

350*275
500*350/350*275

4.25

8.05

0.05

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02

Description

NODE

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

14.82

0.02

809.48

0.625

0.30

14.82

809.48

0.625

2.13

5.4

17.4

877.92

0.729

0.35

5.4

17.4

877.92

0.729

2.48

500*375/500*350

5.4

17.4

0.05

877.92

0.729

0.87

500*375 X
150*150

5.3

16.94

0.02

929.84

0.679

0.34

5.3

16.94

929.84

0.679

2.31

Size(mm)

TEE

500*350X 400*300

Straight Duct

500*350
3-4.

TEE

500*349 X
250*150

Straight Duct

500*350

Reducer

4-5.

TEE
Straight Duct

4-5.

500*375

Length(m)

3.4

3.4

3.4

0.02

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)

Reducer

500*400/500*375

5.3

16.94

0.05

929.84

0.679

0.85

TEE

500*400 X
150*150

5.25

16.54

0.02

981.76

0.637

0.33

5.25

16.54

981.76

0.637

2.17

5-6.
Straight Duct

500*400

3.4

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02
Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

5.53

18.34

0.02

5.53

18.34

500*425/500*400

5.53

18.34

0.05

500*425 X
150*150

5.45

17.86

0.02

5.45

17.86

Description

NODE

Size(mm)

TEE

6-7.

500*400 X
150*150

Straight Duct

6-7.

500*400

Reducer

6-7.

TEE
Straight Duct

7-8.

500*425

Length(m)

3.4

3.4

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)
1033.68

0.702

0.37

1033.68

0.702

2.39

1033.68

0.702

0.92

1085.6

0.66

0.36

1085.6

0.66

2.24

Reducer

500*450/500*425

5.45

17.86

0.05

1085.6

0.66

0.89

TEE

500*450.X
150X150

5.4

17.46

0.02

1137.52

0.623

0.35

5.4

17.46

1137.52

0.623

2.12

5.64

19.1

1189.44

0.678

0.38

5.64

19.1

1189.44

0.678

2.31

8-9.
Straight Duct

500*450.

TEE

500*450.X
150*150

Straight Duct

9-10.

500*450.

3.4

3.4

0.02

##

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02

Description

NODE
9-10.

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)

Reducer

500*475/500*450

5.64

19.1

0.05

1189.44

0.678

0.96

TEE

500*475.X
150*150

5.6

18.64

0.02

1241.36

0.641

0.37

5.6

18.64

1241.36

0.641

2.18

5.8

20.22

1293.28

0.693

0.40

5.8

20.22

1293.28

0.693

2.36

10-11.
Straight Duct

500*475.

TEE

500*475.X
150*150

Straight Duct

11-12.

500*475.

3.4

3.4

0.02

REDUCER

500*500 /500*475.

5.8

20.22

0.05

1293.28

0.693

1.01

TEE

500*500.X
150*150

5.734

19.76

0.02

1345.2

0.656

0.40

5.734

19.76

1345.2

0.656

2.23

5.955

21.31

1397.12

0.705

0.43

5.955

21.31

1397.12

0.705

2.40

12-13.
Straight Duct

500*500.

TEE

500*500.X
150*150

Straight Duct

13-14.

500*500.

3.4

3.4

0.02

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02

Description

NODE
13-14.

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)

Reducer

525*500/500*500.

5.955

21.31

0.05

1397.12

0.705

1.07

TEE

525*500.X
150*150

5.88

20.8

0.02

1449.04

0.669

0.42

5.88

20.8

1449.04

0.669

2.27

Straight Duct

14-15.

525*500.

3.4

Reducer

550*500/525*500.

5.88

20.8

0.05

1449.04

0.669

1.04

TEE

550*500.X
150*150

5.82

20.34

0.02

1500.96

0.637

0.41

5.82

20.34

1500.96

0.637

2.17

21.77

1552.88

0.679

0.44

21.77

1552.88

0.679

2.31

15-16.
Straight Duct

550*500.

TEE

550*500.X
150*150

Straight Duct

16-17.

550*500.

3.4

3.4

0.02

Reducer

575*500/550*500.

5.88

20.8

0.05

1449.04

0.669

1.04

TEE

575*500.X
150*150

5.955

21.31

0.02

1604.8

0.648

0.43

17-18.

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02
Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

575*500.

3.4

5.955

21.31

TEE

575*500.X
150*150

6.15

22.7

6.15

22.7

Description

NODE

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)

17-18.

Straight Duct

18-19.

575*500.

3.4

0.02

1604.8

0.648

2.20

1656.72

0.688

0.45

1656.72

0.688

2.34

Reducer

600*500/575*500.

6.15

22.7

0.05

1656.72

0.688

1.14

TEE

600*500 X
150*150

6.1

22.21

0.02

1708.64

0.657

0.44

6.1

22.21

1708.64

0.657

2.23

6.27

23.59

1760.56

0.696

0.47

6.27

23.59

1760.56

0.696

2.37

19-20.
Straight Duct

600*500

TEE

600*500 X
150*150

Straight Duct

20-21.

600*500.

3.4

3.4

0.02

Reducer

625*500/600*500.

6.27

23.59

0.05

1760.56

0.696

1.18

TEE

625*500./ 150*150

6.2

23.1

0.02

1812.48

0.665

0.46

21-22.

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02
Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

625*500.

3.4

6.2

23.1

TEE

625*500.X
150*150

6.4

24.43

6.4

24.43

Description

NODE

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)

21-22.

Straight Duct

22-23.

625*500.

3.4

0.02

1812.48

0.665

2.26

1864.4

0.702

0.49

1864.4

0.702

2.39

Reducer

650*500/625*500

6.4

24.43

0.05

1864.4

0.702

1.22

TEE

650*500./150*150

6.3

23.92

0.02

1916.32

0.673

0.48

6.3

23.92

1916.32

0.673

2.29

6.48

25.24

1968.24

0.708

0.50

6.48

25.24

1968.24

0.708

2.41

23-24.
Straight Duct

650*500.

TEE

650*500.X
150*150

Straight Duct

24-25.

650*500.

3.4

3.4

0.02

Reducer

675*500/650*500.

6.48

25.24

0.05

1968.24

0.708

1.26

TEE

675*500.X
150*150

6.413

24.71

0.02

2020.16

0.679

0.49

25-26.

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

25-26.

675*500.

3.4

6.413

24.71

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)
2020.16

0.679

2.31

Reducer

700*500/675*500.

6.413

24.71

0.05

2020.16

0.679

1.24

TEE

700*500.X
150*150

6.35

24.24

0.02

2072.08

0.652

0.48

6.35

24.24

2072.08

0.652

2.31

6.511

25.47

2124

0.684

0.51

6.511

25.47

2124

0.684

2.33

6.511

25.47

2124

0.684

10.19

6.511

25.47

2124

0.684

4.10

26-27.
Straight Duct

700*500.

TEE

700*500./ 150*150

Straight Duct

700*500.

ELBOW

27-28.

3.55

3.4

700*500.

Straight Duct

700*500

Mouth Connection

700*500

0.02

0.4

3.50

SUCTION SIDE
Mouth Connection

700*500

28-29.

6.511

25.47

2124

0.684

3.50

External Static Pressure Calculation Sheet


Project

: WSTOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-02

Description

Straight tDuct
SAND TRAP
LOUVRE

NODE

28-29.

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

700*500

6.511

25.47

3.26

6.38

1000*700

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional Total Pressure drop


(lps) loss (Pa/m)
(pa)
0

0.684

2124

CALCULATED PRESSURE DROP IN Pa


SAFETY FACTOR 30%
TOTAL PRESSURE DROP IN Pa

1.37

16.90

179.567
53.870
233.437

TOTAL PRESSURE DROP IN inches of Water

0.919

DESIGN PRESSURE DROP IN inches of Water

1.500

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

DISCHARGE SIDE
SUPPLY AIR GRILL

400*250

Straight Duct

325*250.

VCD

5.36
0.65

299.657

3.953

9.387

325*250.

3.953

9.387

0.52

ELBOW

325*250.

3.953

9.387

0.42

Straight Duct

325*250.

3.953

9.387

Reducer

550*250/325*250

14.50

299.657

0.651

0.42

299.657

0.651

4.88

299.657

0.651

3.94

299.657

0.651

2.77

299.657

0.614

0.00

1-2.

4.25

3.953

0.05

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

TEE
Straight Duct

Size(mm)

Length(m)

550*250X 325*250
2-3.

550*250

8.05

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

4.82

13.95

0.02

599.313

0.697

0.28

4.82

13.95

599.313

0.697

5.61

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

Reducer

550*350/550*250

4.82

13.95

0.05

599.313

0.697

0.70

TEE

550*350X 325*250

5.04

15.26

0.01

898.97

0.608

0.15

5.04

15.26

898.97

0.608

2.07

Straight Duct

3-4.

550*350

3.4

Reducer

550*425/550*350

5.04

15.26

0.05

898.97

0.608

0.76

TEE

550*425X 325*250

5.49

18.08

0.01

1198.63

0.63

0.18

5.49

18.08

1198.63

0.63

2.14

Straight Duct

4-5.

550*425

3.4

Reducer

550*500/550*425

5.49

18.08

0.05

1198.63

0.63

0.90

TEE

550*500X 325*250

5.81

20.26

0.01

1498.28

0.635

0.20

5-6.

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

5-6.

550*500

3.4

5.81

20.26

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

1498.28

0.635

2.16

Reducer

550*550/550*500

5.81

20.26

0.05

1498.28

0.635

1.01

TEE

550*550X325*250

6.33

24.1

0.01

1797.94

0.706

0.24

6.33

24.1

1797.94

0.706

2.40

Straight Duct

6-7.

550*550

3.4

Reducer

625*550/550*550

6.33

24.1

0.05

1797.94

0.706

1.21

TEE

625*550X325*250

6.51

25.45

0.01

2097.6

0.688

0.25

6.51

25.45

2097.6

0.688

2.34

Straight Duct

7-8.

625*550

3.4

Reducer

700*550/625*550

6.51

25.45

0.05

2097.6

0.688

1.27

TEE

700*550X325*250

6.66

26.644

0.01

2397.25

0.672

0.27

6.66

26.644

2397.25

0.672

2.28

Straight Duct

8-9.

700*550

3.4

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE
8-9.

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

Reducer

775*550/700*550

6.66

26.644

0.05

2397.25

0.672

1.33

TEE

775*550X325*250

6.79

27.71

0.01

2696.91

0.66

0.28

6.79

27.71

2696.91

0.66

2.24

Straight Duct

9-10.

775*550

3.4

Reducer

825*550/775*550

6.79

27.71

0.05

2696.91

0.66

1.39

TEE

825*550X 325*250

7.11

30.37

0.01

2996.57

0.692

0.30

7.11

30.37

2996.57

0.692

2.35

Straight Duct

10-11.

825*550

3.4

Reducer

900*550/825*550

7.11

30.37

0.05

2996.57

0.692

1.52

TEE

900*550X325*250

7.2

31.16

0.01

3296.22

0.675

0.31

7.2

31.16

3296.22

0.675

2.30

7.2

31.16

3296.22

0.675

1.56

Straight Duct
Reducer

11-12.

900*550
950*550/900*550

3.4

0.05

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

TEE
Straight Duct

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

7.47

33.53

0.01

7.47

33.53

1025*550/
950*550

7.47

33.53

0.05

1025*550X
325*250

7.54

34.17

0.01

7.54

34.17

Length(m)

950*550X325*250
12-13.

TEE
Straight Duct

Velocity
(m/s)

Size(mm)

13-14.

950*550

1025*550

3.4

3.4

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

3595.88

0.702

0.34

3595.88

0.702

2.39

3595.88

0.702

1.68

3895.53

0.684

0.34

3895.53

0.684

2.33

REDUCER

1075*550/
1025*550

7.54

34.17

0.05

3895.53

0.684

1.71

TEE

1075*550X
325*250

7.77

36.29

0.01

4195.19

0.706

0.36

7.77

36.29

4195.19

0.706

2.40

Straight Duct

14-15.

1075*550

3.4

Reducer

1150*550/
1075*550

7.77

36.29

0.05

4195.19

0.706

1.81

TEE

1150*550X
325*250

7.828

36.818

0.01

4494.85

0.69

0.37

15-16.

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

15-16.

1150*550

3.4

7.828

36.818

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

4494.85

0.69

2.35

Reducer

1250*550/
1150*550

7.828

36.818

0.05

4494.85

0.69

1.84

TEE

1250*550
X325*250

7.742

36

0.01

4794.5

0.645

0.36

7.742

36

4794.5

0.645

2.19

Straight Duct

16-17.

1250*550

3.4

Reducer

1250*575/
1250*550

7.742

36

0.05

4794.5

0.645

1.80

TEE

1250*575X
325*250

7.834

36.88

0.01

5094.16

0.641

0.37

7.834

36.88

5094.16

0.641

2.18

Straight Duct

17-18.

1250*575

3.4

Reducer

1250*600/
1250*575

7.834

36.88

0.05

5094.16

0.641

1.84

TEE

1250*600 X
325*250

7.92

37.68

0.01

5393.82

0.636

0.38

7.92

37.68

5393.82

0.636

2.16

18-19.
Straight Duct

1250*600

3.4

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Length(m)

1250*600
X325*250

TEE
Straight Duct

Size(mm)

19-20.

1250*600

3.4

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

8.36

41.99

0.01

8.36

41.99

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

5693.47

0.706

0.42

5693.47

0.706

2.40

Reducer

1250*625/
1250*600

8.36

41.99

0.05

5693.47

0.706

2.10

TEE

1250*625 X
325*250

8.42

42.57

0.01

5993.13

0.696

0.43

8.42

42.57

5993.13

0.696

2.37

Straight Duct

20-21.

1250*625

3.4

Reducer

1250*650/
1250*625

8.42

42.57

0.05

5993.13

0.696

2.13

TEE

1250*650X
325*250

8.472

43.12

0.01

6292.79

0.687

0.43

8.472

43.12

6292.79

0.687

2.34

Straight Duct

21-22.

1250*650

3.4

Reducer

1250*675/
1250*650

8.472

43.12

0.05

6292.79

0.687

2.16

TEE

1250*675X
325*250

8.522

43.63

0.01

6592.44

0.678

0.44

22-23.

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

22-23.

1250*675

3.4

8.522

43.63

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

6592.44

0.678

2.31

Reducer

1250*700/
1250*675

8.522

43.63

0.05

6592.44

0.678

2.18

TEE

1250*700X
325*250

8.57

44.11

0.01

6892.1

0.669

0.44

8.57

44.11

6892.1

0.669

2.27

Straight Duct

23-24.

1250*700

3.4

Reducer

1250*725/
1250*700

8.57

44.11

0.05

6892.1

0.669

2.21

TEE

1250*725 *
325*250

8.6

44.56

0.01

7191.76

0.661

0.45

8.6

44.56

7191.76

0.661

2.25

Straight Duct

24-25.

1250*725

3.4

Reducer

1250*750/
1250*725

8.6

44.56

0.05

7191.76

0.661

TEE

1250*750 X
325*250

8.653

44.98

0.01

7491.41

0.652

0.45

8.653

44.98

7491.41

0.652

2.22

25-26.
Straight Duct

1250*750

3.4

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Length(m)

1250*750 X
325*250

TEE
Straight Duct

Size(mm)

26-27.

1250*750

3.4

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

48.65

0.01

48.65

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

7791.07

0.703

0.49

7791.07

0.703

2.39

Reducer

1250*775/
1250*750

48.65

0.05

7791.07

0.703

2.43

TEE

1250*775/
325*250

48.937

0.01

8090.73

0.693

0.49

48.937

8090.73

0.693

2.46

Straight Duct

27-28.

1250*775

3.55

Reducer

1250*800 /
1250*775

48.937

0.05

8390.38

0.693

2.45

TEE

1250*800 X
325*250

9.05

49.22

0.01

8390.38

0.683

0.49

9.05

49.22

8390.38

0.683

2.32

Straight Duct

28-29.

1250*800

3.4

Reducer

1250*825/
1250*800

9.05

49.22

0.05

8390.38

0.683

2.46

TEE

1250*825 X
325*250

9.075

49.48

0.01

8690

0.673

0.49

29-30.

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

29-30.

1250*825

3.4

9.075

49.48

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

8690

0.673

2.29

Reducer

1250*850/
1250*825

9.075

49.48

0.05

8690

0.673

2.47

TEE

1250*850/
325*250

8.89

47.5

0.01

8784.42

0.635

0.48

Straight Duct

1250*850

8.89

47.5

8784.42

0.635

3.81

8.89

47.5

0.75

8784.42

0.635

35.63

8.89

47.5

8784.42

0.635

3.20

8.89

47.5

8878.8

0.635

1.27

8.89

47.5

0.52

8784.42

0.635

24.70

8.89

47.5

8784.42

0.635

3.20

ELBOW

30-31.

1250*850

MOUTH
CONNECTION

SUCTION SIDE
Straight Duct

1250*850

VCD

1250*850

31-32.
MOUTH
CONNECTION

External Static Pressure Calculation Sheet


Project

Consultant

Main contractor :
Unit Ref.

:STPRF-01 Basement-02 to Machine floor

Description
SAND TRAP
LOUVRE

31-32.
NODE

Size(mm)

1800X1600

Length(m)

Velocity
(m/s)
3.25

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings
1

Airflow Frictional
(lps) loss (Pa/m)
8784.42

0.635

Total Pressure
drop (pa)
15.80

CALCULATED PRESSURE DROP IN Pa

235.00

SAFETY FACTOR(30%)

70.50

TOTAL PRESSURE DROP IN Pa

305.51

TOTAL PRESSURE DROP IN INCHES OF WATER

1.20

PRESSURE DROP AS PER DESIGN(INCHES OF WATER)

2.50

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

SL#

: CPRF-1
Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

DISCHARGE SIDE
1

SUPPLY AIR
GRILLE

STRAIGHT DUCT

VCD

500X350
350X200

2
0.3

236
236

6.2

3.665

8.1

0.626

0.1878

350X200

3.665

8.1

0.52

236

3.665

8.1

0.185

236

0.626

1.50

3.665

8.1

236

0.626

2.1284

4.21

1-2.
4

ELBOW

350X200

STRAIGHT DUCT

350X200

REDUCER

350*325/350*200

4.424

8.1

0.29

236

2.35

TEE

350X325 * 350X200

4.424

11.76

0.02

472

0.24

STRAIGHT DUCT

REDUCER

450X350/350X325

10

TEE

450X350 * 350X200

11

STRAIGHT DUCT

12

Reducer

13

TEE

14

STRAIGHT DUCT

15

REDUCER

16

TEE

2-3.

3-4.

350X325

450*350

3.4

3.4

4.8

450*425
450*425/450*350

5-6.

472

0.652

2.22

11.76

0.05

472

0.652

0.59

13.9

0.01

708

0.626

0.14

708

0.626

2.13

0.626

0.70

3.4

450X425/450X350

4-5.

11.76

4.8

13.9

0.05

708

5.26

16.61

0.01

944

3.4

944
5.26

16.61

0.05

944

5.592

18.79

0.01

1180

0.17
0.656

2.23
0.83

0.668

0.19

##

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: CPRF-1
Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

500*450

3.4

5.592

18.79

5.592

18.79

0.05

5.854

20.59

0.01

5.854

20.59

REDUCER

5.854

20.59

0.05

22

TEE

6.07

22.13

0.01

23

STRAIGHT DUCT

6.07

22.13

24

REDUCER

6.07

22.13

0.05

1652

1.11

25

TEE

6.254

23.5

0.01

1888

0.24

26

STRAIGHT DUCT

27

REDUCER

6.254

23.5

0.05

1888

1.18

28

TEE

6.42

24.73

0.01

2124

0.25

29

STRAIGHT DUCT

30

REDUCER

6.42

24.73

0.05

2124

1.24

31

TEE

6.729

27.21

0.01

2360

0.27

32

STRAIGHT DUCT

33

REDUCER

SL#

Description

17

STRAIGHT DUCT

18

REDUCER

19

TEE

20

STRAIGHT DUCT

21

NODE

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

5-6.

5-6.

6-7.

7-8.

8-9.

9-10.

10-11.

575*450

650*450

725*450

800*450

800*475

3.4

3.4

3.4

1180

0.668

2.27

1180

0.668

0.94

1415

0.67

0.21

1416

0.67

2.28

1416

0.67

1.03

1652
1652

6.254

1888

3.4

2124

3.4

2360
6.729

27.21

0.05

2360

0.22
0.668

0.664

0.659

0.697

2.27

2.26

2.24

2.37
1.36

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: CPRF-1

SL#

Description

34

TEE

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

6.658

26.636

0.01

Airflow Frictional
(lps) loss (Pa/m)
2596

Total Pressure
drop (pa)
0.27

11-12.
35

STRAIGHT DUCT

800*525

3.4

36

REDUCER

37

TEE

38

STRAIGHT DUCT

39

REDUCER

6.9

28.75

0.05

2832

1.44

40

TEE

7.22

31.33

0.01

3068

0.31

41

STRAIGHT DUCT

42

REDUCER

7.22

31.33

0.05

3068

1.57

43

TEE

7.1

30

0.01

3304

0.30

44

STRAIGHT DUCT

45

REDUCER

7.1

30

46

TEE

7.273

31.787

47

STRAIGHT DUCT

48

REDUCER

7.273

31.787

0.05

3540

1.59

49

TEE

7.464

33.47

0.01

3776

0.33

50

STRAIGHT DUCT

11-12.

12-13.

13-14.

14-15

15-16.

16-17

800*550

800*570

800*625

800*650

800*675

2596

2.18

6.658

26.636

0.05

2596

1.33

6.9

28.75

0.01

2832

0.29

3.4

2832

3.4

3068

3.4

3304
0.05
0.01

3.4

3.4

0.64

0.668

0.71

0.642

2.27

2.41

2.18

3304

0.00

3540

0.32

3540

3776

0.662

0.68

2.25

2.31

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: CPRF-1

SL#

Description

51

REDUCER

52

TEE

NODE
16-17

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

7.464

33.47

0.05

3776

1.67

7.642

35.1

0.01

4012

0.35

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

17-18
53

STRAIGHT DUCT

800*700

3.4

54

REDUCER

55

TEE

56

STRAIGHT DUCT

57

REDUCER

7.625

34.94

0.05

4248

1.75

58

TEE

7.824

36.78

0.01

4484

0.37

59

STRAIGHT DUCT

60

REDUCER

7.824

36.78

0.05

4484

1.84

61

TEE

38.59

0.01

4720

0.39

62

STRAIGHT DUCT

63

REDUCER

38.59

0.05

4720

1.93

64

TEE

7.99

38.33

0.01

4956

0.38

65

STRAIGHT DUCT

66

REDUCER

7.99

38.33

0.05

4956

1.92

67

TEE

38.12

0.01

5192

0.38

17-18

18-19

19-20

20-21

21-22

22-23

850*700

875*700

900*700

950*700

4012

0.695

2.36

7.642

35.1

0.05

4012

1.76

7.625

34.94

0.01

4248

0.35

3.4

4248

3.4

4484

3.4

4720

3.4

4956

0.668

0.69

0.71

0.684

2.27

2.35

2.41

2.33

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: CPRF-1
Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

SL#

Description

NODE

Size(mm)

Length(m)

68

STRAIGHT DUCT

22-23

1000*700

3.4

69

REDUCER

38.12

0.05

5192

1.91

70

TEE

38.7

0.01

5428

0.39

71

STRAIGHT DUCT

72

REDUCER

38.7

0.05

5428

1.94

73

TEE

39.3

0.01

5664

0.39

74

STRAIGHT DUCT

39.3

5664

75

TEE

39.3

76

STRAIGHT DUCT

39.3

77

ELBOW

39.3

78

MOUTH
CONNECTION

23-24

1000*725

1000*750

24-25.

1000*750

5192

3.4

13.695

4.8

1000X750

5428

0.01

5664
5664

1.1

0.661

0.656

2.25

2.23

0.65

8.90

0.65

0.39

0.65

3.12

0.65

86.46

5664

5664

3.50

5664

3.50

SUCTION SIDE
79

MOUUTH
CONNECTION

80

STRAIGHT DUCT

1000X750

25-26.

1000*750

5.4

39.3
39.3

81

VCD

1000X750

82

SAND TRAP
LOUVER

1500*1200

3.363

0.52

5664

0.65

3.51

5664

0.65

20.44
16.00

CALCULATED PRESSURE DROP IN Pa

242.58

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

SL#

: CPRF-1
Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

SAFETY FACTOR(30%)
TOTAL PRESSURE DROP IN Pa
TOTAL PRESSURE DROP IN INCHES OF WATER

DESIGN PRESSURE DROP

Total Pressure
drop (pa)

72.77
315.35
1.242
2.5

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

DISCHARGE SIDE
SUPPLY AIR GRILL

350*125

Straight Duct

300*200

VCD

169.92
0.65

3.05

5.59

300*200

3.05

5.59

0.52

ELBOW

300*200

3.05

5.59

0.16

Straight Duct

300*200

3.05

5.59

Reducer

350*300/300*200

3.05

5.59

24.60

169.92

0.487

0.32

169.92

0.487

2.91

169.92

0.487

0.89

169.92

0.487

2.07

169.92

0.487

0.28

1-2.

4.25

0.05

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE

Length(m)

350*300X
300*225

TEE
Straight Duct

Size(mm)

2-3.

350*300

8.05

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

4.17

10.46

0.04

410.64

0.614

0.42

4.17

10.46

410.64

0.614

4.94

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

Reducer

400*350/350*300

4.17

10.46

0.05

410.64

0.614

0.52

TEE

400*350 X
350*200

4.78

13.73

0.01

627.76

0.664

0.14

4.78

13.73

627.76

0.664

2.26

Straight Duct

3-4.

400*350

3.4

Reducer

450*400/400*350

4.78

13.73

0.05

627.76

0.664

0.69

TEE

450*400X300*225

5.2

16.25

0.01

877.92

0.667

0.16

5.2

16.25

877.92

0.667

2.27

5.2

16.25

877.92

0.667

0.81

4-5.
Straight Duct

450*400

Reducer

450*400/500*400

3.4

0.05

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE

TEE
Straight Duct

Size(mm)

Length(m)

500*400X250*150
5-6.

500*400

3.4

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

5.2

16.227

0.01

972.32

0.626

0.16

5.2

16.227

972.32

0.626

2.13

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

Reducer

500*425/500*400

5.2

16.227

0.05

972.32

0.626

0.81

TEE

500*425X250*150

5.36

17.25

0.01

1066.72

0.64

0.17

5.36

17.25

1066.72

0.64

2.18

Straight Duct

6-7.

500*425

3.4

Reducer

500*450/500*425

5.36

17.25

0.05

1066.72

0.64

0.86

TEE

500*450X 250*150

5.502

18.19

0.01

1161.12

0.648

0.18

5.502

18.19

1161.12

0.648

2.20

Straight Duct

7-8.

500*450

3.4

Reducer

525*450/ 500*450

5.502

18.19

0.05

1161.12

0.648

0.91

TEE

525*450 X
250*150

5.67

19.32

0.01

1255.52

0.67

0.19

8-9.

##

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Straight Duct

8-9.

525*450

3.4

5.67

19.32

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

1255.52

0.67

2.28

Reducer

550*450/ 525*450

5.67

19.32

0.05

1255.52

0.67

0.97

TEE

550*450X 250*150

5.8

20.37

0.01

1349.92

0.68

0.20

5.8

20.37

1349.92

0.68

2.31

Straight Duct

9-10.

550*450

3.4

Reducer

575*450/550*450

5.8

20.37

0.05

1349.92

0.68

1.02

TEE

575*450X 250*150

5.97

21.38

0.01

1444.32

0.694

0.21

5.97

21.38

1444.32

0.694

2.36

Straight Duct

10-11.

575*450

3.4

Reducer

600*450/575*450

5.97

21.38

0.05

1444.32

0.694

1.07

TEE

600*450 X
250*150

6.1

22.38

0.01

1538.72

0.707

0.22

6.1

22.38

1538.72

0.707

2.40

Straight Duct

11-12.

600*450

3.4

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE
11-12.

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

Reducer

650*450/600*450

6.1

22.38

0.05

1633.12

0.707

1.12

TEE

650*450 X
250*150

21.62

0.01

1633.12

0.653

0.22

21.62

1633.12

0.653

2.22

Straight Duct

12-13.

650*450

3.4

REDUCER

675*450/650*450

21.62

0.05

1633.12

0.653

1.08

TEE

675*450 X
250*150

6.12

22.5

0.01

1727.52

0.664

0.23

6.12

22.5

1727.52

0.664

2.26

Straight Duct

13-14.

675*450

3.4

Reducer

700*450/675*450

6.12

22.5

0.05

1727.52

0.664

1.13

TEE

700*450 X
250*150

6.2

23.38

0.01

1821.92

0.673

0.23

6.2

23.38

1821.92

0.673

2.29

6.2

23.38

1821.92

0.673

1.17

Straight Duct
Reducer

14-15.

700*450
725*450/700*450

3.4

0.05

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE

Length(m)

725*450 X
250*150

TEE
Straight Duct

Size(mm)

15-16.

725*450

3.4

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

6.35

24.2

0.01

6.35

24.2

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

1916.32

0.683

0.24

1916.32

0.683

2.32

Reducer

750*450/725*450

6.35

24.2

0.05

1916.32

0.683

1.21

TEE

750*450 X
250*150

6.45

25

0.01

2010.72

0.69

0.25

6.45

25

2010.72

0.69

2.35

Straight Duct

16-17.

750*450

3.4

Reducer

800*450/750*450

6.45

25

0.05

2010.72

0.69

1.25

TEE

800*450 X
250*150

6.36

24.29

0.01

2105.12

0.647

0.24

6.36

24.29

2105.12

0.647

2.20

6.641

26.5

0.01

2199.52

0.704

0.27

6.641

26.5

0.77

2199.52

0.704

2.39

17-18.
Straight Duct

800*450

TEE

800*450 X
250*150

Straight Duct

18-19.

800*450

3.4

3.4

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE
18-19.

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

Reducer

800*475/800*450

6.541

26.5

0.77

2199.52

0.704

20.41

TEE

800*475 X
250*150

6.541

25.7

0.01

2293.92

0.66

0.26

6.541

25.7

2293.92

0.66

2.24

Straight Duct

19-20.

800*475

3.4

Reducer

800*500/800*475

6.541

25.7

0.05

2293.92

0.66

1.29

TEE

800*500 X
250*150

6.45

24.994

0.01

2388.32

0.622

0.25

2388.32

0.622

2.11

2482.72

0.669

0.27

2482.72

0.669

2.27

20-21.
Straight Duct

800*500

TEE

800*500 X
250*150

Straight Duct

21-22.

800*500

3.4

3.4

6.45
6.705

27.01

0.01

6.705

27.01

0.8

Reducer

800*525/800*500

6.609

27.01

0.8

2482.72

0.669

21.61

TEE

800*525 X
250*150

6.609

26.24

0.01

2577.12

0.631

0.26

22-23.

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor

Description

NODE

Size(mm)

Length(m)

Straight Duct

800*525

3.4

TEE

800*525 X
250*150

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

22-23.

Straight Duct

23-24.

800*525

3.4

6.852

28.21

6.852

28.21

0.01

2577.12

0.631

2.15

2671.52

0.676

0.28

2671.52

0.676

2.30

Reducer

800*550/800*525

6.852

28.21

0.05

2671.52

0.676

1.41

TEE

800*550 X
250*150

6.76

27.42

0.01

2765.92

0.639

0.27

2765.92

0.639

2.17

2860.3

0.681

0.29

2860.32

0.681

2.32

24-25.
Straight Duct

800*550

TEE

800*550 X
250*150

Straight Duct

25-26.

800*550

3.4

3.4

6.76
6.99

29.33

6.99

29.33

0.01

Reducer

800*575/800*550

6.99

29.33

0.05

2860.32

0.681

1.47

TEE

800*575 X
250*150

6.891

28.53

0.01

2954.72

0.645

0.29

26-27.

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

: LPRF-03 Basement-02 to Machine floor


Size(mm)

Length(m)

Velocity
(m/s)

Straight Duct

800*575

3.4

6.891

TEE

800*575 X
250*150

Description

NODE

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

26-27.

Straight Duct

23-24

800*575

3.55

7.11

30.38

7.11

30.38

0.01

2954.72

0.645

2.19

3049.12

0.685

0.30

3049.12

0.685

2.43

0.685

1.52

Reducer

800*600/800*575

7.11

30.38

0.05

3049.12

TEE

800*600 X
250*150

7.01

29.56

0.01

3143.52

7.01

29.56

3143.52

0.65

2.21

7.224

31.36

3237.92

0.687

0.31

7.224

31.36

3237.92

0.687

2.34

24-25
Straight Duct

800*600

TEE

800*600 X
250*150

Straight Duct

800*600

REDUCER

825*600/800*600

TEE

3.4

3.4

25-26

Straight Duct

825*600

ELBOW

825*600

0.01

0.30

31.36

0.05

3237.92

0.687

1.57

7.2

31.3

0.01

3332.32

0.674

0.31

7.2

31.3

3332.32

0.674

4.04

31.3

1.1

3332.32

34.43

External Static Pressure Calculation Sheet


Project

: WS TOWER

Consultant

Main contractor :
Unit Ref.

25-26
: LPRF-03 Basement-02 to Machine floor

Description

NODE

Mouth Connection

Size(mm)

Length(m)

Velocity
(m/s)

Velocity
pressureVp(Pa)

Loss
coefficient
-C

Qty of
fittings

825*600

Airflow Frictional
(lps) loss (Pa/m)

Total Pressure
drop (pa)

3332.32

3.20

3332.32

3.20

SUCTION SIDE
Mouth Connection
Straight Duct
LOUVRE

825*600
26-27

825*600
1800*1200

2
2

7.2
3.52

31.3

3332.32
1

0.674

3332.32

TOTAL PRESSURE DROP CALCULATED(Pa)


SAFETY FACTOR (30%)
TOTAL PRESSURE DROP (Pa)

PREESSURE DROP IN INCHES OF WATER


PRESSURE DROP AS PER DESIGN(INCHES OF WATER)

1.35
15.95

230.35
69.11
299.46
1.18
1.5